GOODMAN Package Units(both Units Combined) Manual L0806747
CHIEF Power Screwdriver PACHFK1 L0806747
User Manual: GOODMAN GOODMAN Package Units(both units combined) Manual GOODMAN Package Units(both units combined) Owner's Manual, GOODMAN Package Units(both units combined) installation guides
Open the PDF directly: View PDF
.
Page Count: 37
| Download | |
| Open PDF In Browser | View PDF |
INSTALLATION
& OPERATING
INSTRUCTIONS
for
GPG13
SINGLE PACKAGE GAS-ELECTRIC
HEATING & COOLING UNIT
Affix this manual and Users Information Manual adjacent to the unit.
This Forced Air Central Unit Design Complies With
Requirements
Embodied in The American National
Standard / National Standard of Canada Shown Below.
ANSI Z21.47,CSA-2.3 Central Furnaces
_
RECOGNIZE
THIS SYMBOL
AS A SAFETY
PRECAUTION.
ATTENTION INSTALLING PERSONNEL
Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During
installation or repair, caution is to be observed.
It is your responsibility to install the product safely and to educate the customer on its safe use.
These
installation
instructions
cover
the outdoor
installation of single package gas electric heating and
cooling units. See the Product Data Book applicable to
your model* for information regarding accessories.
IO-288A
02/07
*NOTE: Please contact your distributor or our
website for the applicable product data
book referred to in this manual.
Goodman Manufacturing
Company, L.P.
2550 North Loop West, Suite 400, Houston, TX 77092
www.qoodmanmfq.com
© 2005 - 2007 Goodman
Manufacturing
Company,
L.P.
INDEX
Replacement Parts .............................................................................................................................................................
ORDERING
PARTS
..............................................................................................................................................
Safety Instructions .............................................................................................................................................................
Unit location ........................................................................................................................................................................
ALL INSTALLATIONS:
GROUND
LEVEL
ROOFTOP
ROOF
...........................................................................................................................................
INSTALLATIONS
INSTALLATIONS
ONLY:
CURB INSTALLATIONS
ONLY:
..................................................................................................................
...........................................................................................................................
ONLY:
.......................................................................................................................
General Information ...........................................................................................................................................................
3
3
3
4
4
4
4
5
DAMAGE ...................................................................................................................................
5
6
Rigging Details ...................................................................................................................................................................
Gas piping ...........................................................................................................................................................................
6
6
TRANSPORTATION
HIGH ALTITUDE DERATE (U.S.
INSTALLATIONS ONLY) ...............................................................................................
PIPING .............................................................................................................................................................
GAS
PIPING
CHECKS ..........................................................................................................................................
Propane Gas Installations ..................................................................................................................................................
TANKS AND PIPING .............................................................................................................................................
Electrical Wiring .................................................................................................................................................................
THERMOSTAT LOCATION
UNIT VOLTAGE
.......................................................................................................................................
...................................................................................................................................................
HEAT ANTICIPATOR SETrlNG
..................................................................................................................................
Circulating Air and Filters ................................................................................................................................................
AIRFLOW
CONVERSION
......................................................................................................................................
6
6
7
7
8
8
8
9
9
10
10
Duc_nNORK...............................................................................................
10
FILTERS ..........................................................................................................................................................
Venting ..............................................................................................................................................................................
FLUE HOOD INSTALLATION ...................................................................................................................................
Drain ..............................................................................................................................................................
CONDENSATE
DRAINCONNECTION ........................................................................................................................
normal sequences of operation .......................................................................................................................................
HEA_NG ..........................................................................................................................................................
COOLING.........................................................................................................................................................
FAN ONLY ......................................................................................................................................................
Condensate
Startup, Adjustments, and Checks ..................................................................................................................................
HEA_HGSTARTEP............................................................................................................................................
COOLING STARTUP
...........................................................................................................................................
Troubleshooting ................................................................................................................................................................
IGNITION CONTROL
ERROR CODES
ABNORMAL
OPERATION
ABNORMAL
OPERATION-
Maintenance
CLEAN
- HEATING ....................................................................................................................
COOLING
...................................................................................................................
.....................................................................................................................................................................
FILTER REPLACEMENT
CABINET
......................................................................................................................
OR CLEANING
FINISH MAINTENANCE
OUTSIDE
CONDENSER,
FLAME SENSOR
FLUE PASSAGES
CLEANING
COIL
(QUALIFIED
EVAPORATOR,
(QUALIFIED
(QUALIFIED
FLUE PASSAGES
....................................................................................................................
...........................................................................................................................
SERVICER
ONLY)
AND INDUCED DRAFT
SERVICER
SERVICER
(QUALIFIED
ONLY)
ONLY)
.............................................................................................
MOTORS
.....................................................................................
......................................................................................................
.....................................................................................................
SERVICER
ONLY)
......................................................................................
MAIN BURNER FLAME (QUALIFIED SERVICER ONLY) ..............................................................................................
CLEANING BURNERS .........................................................................................................................................
Accessories and Functional Parts ...................................................................................................................................
SHEET METAL ACCESSORIES
FUNCTIONAL
GENERAL
PARTS
..............................................................................................................................
..........................................................................................................................................
INFORMATION
.....................................................................................................................................
Ignition Control Diagnostic Indicator Chart ....................................................................................................................
Heating Timing Chart .......................................................................................................................................................
Cooling Timing Chart .......................................................................................................................................................
APPENDIX .........................................................................................................................................................................
Wiring Diagrams ..........................................................................................................................................................
Minimum Clearances .......................................................................................................................................................
Recommended Filter Sizes .............................................................................................................................................
2
10
10
11
11
tl
11
tt
tt
12
12
12
15
15
t5
15
16
t6
16
16
t7
t7
17
17
t7
t7
18
18
18
18
18
19
19
19
20
2t-36
37
37
REPLACEMENT
PARTS
AWARNING
ORDERING
PARTS
THIS PRODUCT
When reporting shortages or damages, or ordering repair parts,
give the complete unit model and serial numbers as stamped
on the unit's nameplate.
MAY CAUSE
STATE
OF
CONTAINS
OR PRODUCES
SERIOUS
ILLNESS
CALIFORNIA
TO
REPRODUCTIVE
CAUSE
CANCER,
OR CHEMICALS
WHICH
BIRTH
ARE
KNOWN
DEFECTS
WHICH
TO THE
OR OTHER
AWARNING
HEATING
SERVICE PARTS DEPARTMENT
GOODMAN MANUFACTURING COMPANY, L.E
2550 NORTH LOOP WEST, SUITE 400
HOUSTON, TEXAS 77092
(713) 861 2500
UNIT
INSPECTION,
DEVICE
SUCH
DEVICE
EVENT
THAT
AND
INSTRUCTIONS
SHOULD
WILL
IN THE
BE DRAINED
SHOULD
to familiarize
adhered to,
to unit, air
motor speed
BE VACANT,
INSPECTED,
BUILDING
BE VACANT,
MAYBE
ALL
AND
THAT
WILL
AS WELL
TO
BUILDING
BE VACANT,
AND,
IN SUCH
AND
THE
CASE,
HYDRONIC
BE DRAINED,
WATER
THE
SOURCE
TO
COIL
ALTERNATIVE
IN THE
TEMPERATURES
MAY BE EXPOSED
ANY
AN_
THAT
MONITORED.
SHOULD
AND
IN WHICH
BE TAKEN
FREEZING
PIPES
ROUTINE,
BUlLIDNG
SHOULD
MAINTAINED
EXPOSED
WINTERIZED,
THE
REASONABLE,
IF THE
CARE
WATER-BEARING
BE PROPERLY
EVENT
WITHOUT
SUPERVISION.
WILL
IS ROUTINELY
THE
TEMPERATURES
TO THE INSTALLER
BE UTILIZED
AND
IS LOCATED
SHOULD
CLOSED.
NOT
MAINTENANCE
SUCH
BUILDING
Before installing this unit, please read this manual
yourself on the specific items which must be
including maximum external static pressure
temperature rise, minimum or maximum CFM and
connections.
AND
HARM.
Replacement parts for this appliance are available through your
contractor or local distributor. For the location of your nearest
distributor, consult the white business pages, the yellow page
section of the local telephone book or contact:
SAFETY
A CHEMICAL
OR DEATH
FREEZING
UNITS
HEAT
SHOULD
SOURCES
BE UTILIZED.
AWARNING
TO THE OWNER
TO
AVOID
THIS
A warranty certificate is provided with the unit. Read the
warranty carefully and note what is covered. Keep the warranty
certificate in a safe place so you can find it when necessary.
UNIT
PROPERTY
IF ANY
QUALIFIED
SERVICE
ANY
OF THE
PART
UNDER
DAMAGE,
PART
HAS
PERSONAL
BEEN
TECHNICIAN
CONTROL
UNDER
INJURY
TO INSPECT
SYSTEM
OR DEATH,
WATER.
THE
AND ANY
DO NOT
IMMEDIATELY
FURNACE
GAS
CALL
AND
CONTROL
USE
A
TO REPLACE
HAVING
BEEN
WATER.
Keep this literature in a safe place for future reference.
AWARNING
IF
THE INFORMATION
FIRE
IN THESE
OR EXPLOSION
INJURY
Do
OR LOSS
NOT
AWARNING
INSTRUCTIONS
MAY RESULT
IS NOT FOLLOWED
CAUSING
PROPERTY
EXACTLY,
DAMAGE,
A
THIS
PERSONAL
OF LIFE.
STORE
USE MAY
OR USE GASOLINE
OR OTHER
FLAMMABLE
VAPORS
LOW
AND
DIRTY
LIQUIDS
IN THE VICINITY
OF
THIS
OR ANY
OTHER
• DO
NOT
TRY
• DO
NOT
TOUCH
TO LIGHT
IN YOUR
• IMMEDIATELY
PHONE
ANY
FOLLOW
• IF YOU
CANNOT
SWITCH;
DO
NOT USE ANY
FROM
A NEIGHBOR'S
BUILDING
CALL
YOUR
THE GAS
REACH
GAS
SUPPLIER
SUPPLIER'S
YOUR
GAS
NOT
RESULT
RETURN
BE USED
AS A "CONSTRUCTION
OF CONSTRUCTION
IN PREMATURE
ON A NEW
FAILURE
AIR TERMPERATURES
AND
HEATER"
STRUCTURE.
OF THE
UNIT
EXPOSURE
DUE TO
DURING
THIS
THE
TYPE
TO CORROSIVE
OR VERY
ATMOSPHERES.
DISCONNECT ALL POWER BEFORE SERVICING OR
INSTALLING THIS UNIT• MULTIPLE POW]ER SOURCES MA_P
INSTRUCTIONS
SUPPLIER,
CALL
BE PRESENT. FAILURE TO DO $O MAY CAUSE PROPERTY _f
THE
FIRE
I
DAMAGE,
PERSONAL
INJURY
OR
DEATH.
DEPARTMENT
INSTALLATION
SERVICE
AN D SERVICE
AGENCY
OR THE
I
MUST BE PERFORMED
BY A QUALIFIED
INSTALLER,
GAS SUPPLIER
AWARNING
SHOULD
OVERHEATING
OCCUR
OR THE GAS
SUPPLY
FAIL TO
SHUT
OFF,
TURN
:cSTc\OLV,;L,;
E ERNAL
TO
THE
FURNACE
OEFORE
INSTALLATION
A
Do
NOT CONNECT
BY GOODMAN
PERSONAL
CONDITIONS
TO
FOR USE WITH
INJURY,
REDUCED
MAY RESULT
DEVICE
THAT
THIS
UNIT. SERIOUS
UNIT
PERFORMANCE
FROM
IS NOT
THE USE OF SUCH
I_WARNING
AND
PERFORMEDONLY
WARNING
OR USE ANY
OF
EXTREMELY
&w.....o lll1111
.o.vo,,,oo
ANY APPLIANCE
ELECTRICAL
MUST
PHASES
APPLIANCE
WHAT TO DO IF YOU SMELL GAS:
PHONE
UNIT
FINISHING
DESIGN
PROPERTY
AND/OR
OF THIS UNIT
BY INDIVIDUALS
SHOULD
MEETING
BE
THE
REQUIREMENTS
OF AN "ENTRY LEVEL TECHNICIAN"
AS SPECIFIED
BY THE AIR CONDITIONING
AND
CERTIFIED
REFRIGERA'I1ON
INSTITUTE (ARI).
ATTEMPTING
INSTALL OR REPAIR THIS UNIT WITHOUT
SUCH
DAMAGE,
HAZARDOUS
NON-APPROVED
REPAIR
RESULT
DEVICES.
3
IN PRODUCT
DAMAGE,
PERSONAL
TO
BACKGROUND
INJURY
OR DEATH.
MAY
To avoid possible illness or death of the building occupants,
do NOT locate outside air intake device (economizer,
manual fresh air intake, motorized fresh air intake) too close
to an exhaust outlet, gas vent termination, or plumbing vent
outlet. For specific distances required, consult local codes.
Allow minimum clearances from the enclosure for fire
protection, proper operation, and service access (see
appendix). These clearances must be permanently
maintained.
The combustion air inlet and flue outlet hoods on the unit
CARBON
MONOXIDE
POISONING
must never be obstructed. If used, do not allow the
economizer/manual fresh air damper/motorized fresh air
damper to become blocked by snow or debris. In some
climates or locations, it may be necessary to elevate the
unit to avoid these problems.
HAZARD
Special
WarningfurInstaila_on
ofFurnaces
or AirHandling
Unitsin
Enclosed
AreassuchasGarages,UflityRoomsor Parking ,&.teas
Carbonmono_depmdudng
devices(suchasan automobile,
space
heater,gaswaterheater,etc.)should
notbeoperated
in enclosed
areas
suchasunventilated
garages,ubltiy
roomsorparkingareasbecauseof
thedangerofcarbonmonoxide
(CO)poisoning
resulting
fmrntheexhaust
emissic_s.
If a furnaceorairhandlerisinstalledinanenclosedareasuch
asa garage,utilityroomor parking
areaanda carbonmonoxide
produdng
deviceisoperated
therein,theremustbeadequate,
directoutside
ven_lation.
When the unit is heating, the temperature of the return air
entering the unit must be between 50 ° F and 100° F.
GROUND
LEVEL
INSTALLATIONS
ONLY:
When the unit is installed on the ground adjacent to the
building, a level concrete (or equal) base is recommended.
Prepare a base that is 3" larger than the package unit
footprint and a minimum of 3" thick.
The base should also be located where no runoff of water
Thisventilation
isnecassawtoavoidthedangerofCOpoisoning
which
canoccurifa carbonmonoxide
producing
devicecontinues
tooperatein
theenclosed
area.Carbonmonoxideemissions
can be (re)circulated
throughout
thestructure
if 6_efurnaceorairhandlerisoperating
in any
mode.
COcancausesedous
illness
including
permanent
braindamage
ordeath.
from higher ground can collect in the unit.
B1025_216
UNIT
LOCATION
I_WARNING
TO
PREVENT
INJURY
WHEN
POSSIBLE
OR DEATH,
INSTALLtNG
EQUIPMENT
DAMAGE,
THE
FOLLOWING
BULLET
THE
UNIT.
PROPERTY
POINTS
MUST
DAMAGE,
PERSONAL
BE OBSERVED
IMPORTANT NOTE: Remove wood shipping rails prior to installation of the unit.
ALL INSTALLATIONS:
For proper flame pattern within the heat exchanger and
proper condensate drainage, the unit must be mounted
level.
The flue outlet hood must be at least 12 inches from any
opening through which flue gases could enter a building,
and at least three feet above any forced air inlet located
within ten feet. The eoonomizer/manual fresh air intake/
motorized fresh air intake and combustion
air inlet
mounted on the unit are not affected by this restriction.
Outside Slab Installation
ROOFTOP
INSTALLATIONS
ONLY:
To avoid possible property damage or personal injury, the
roof must have sufficient structural strength to carry the
weight of the unit(s) and snow or water loads as required
by local codes. Consult a structural engineer to determine
the weight capabilities of the roof.
To avoid possible corrosion of the heat exchanger, do not
locate the unit in an area where the outdoor air (i.e.
combustion air for the unit) will be frequently contaminated
by compounds containing chlorine or fluorine. Common
sources of such compounds include swimming pool
chemicals
and chlorine
bleaches,
paint stripper,
adhesives, paints, varnishes, sealers, waxes (which are
not yet dried) and solvents used during construction and
remodeling. Various commercial and industrial processes
may also be sources of chlorine/fluorine compounds.
4
RooRoplns_ll_ion
The unit may be installed directly on wood floors or on
Class A, Class B, or Class C roof covering material.
To avoid possible personal injury, a safe, fiat surface for
service personnel should be provided.
ROOF CURB
INSTALLATIONS
Roof Curb Installation
ONLY:
Sufficient structural support must be determined prior to
locating and mounting the curb and package unit.
GENERAL
Ductwork must be constructed using industry guidelines.
The duct work must be placed into the roof curb before
mounting the package unit.
INFORMATION
_WARNING
Curb insulation, cant strips, flashing and general roofing
material are furnished by the contractor.
To PREVENT
PROPERTY
EXPLOSIONS,
SMOKE,
MONOXIDE,
AND
THIS
UNIT
DAMAGE,
SOOT,
MUST
PERSONAL
CONDENSATION,
BE PROPERLY
INJURY
OR DEATH,
DUE TO
ELECTRIC
SHOCK
OR CARBON
INSTALLED,
REPAIRED,
FIRE
OPERATED,
MAINTAINED.
This unit is approved for outdoor installation ONLY. To assure
that your unit operates safely and efficiently, it must be installed,
operated, and maintained in accordance with these installation and
operating instructions, all local building codes and ordinances, or in
their absence, with the latest edition of the National Fuel Gas Code
NFPA54/ANSI 7323.1 and National Standard of Canada CAN/CSA
B14g Installation Codes.
The heating and cooling capacities of the unit should be greater
than or equal to the design heating and cooling loads of the area to
be conditioned. The loads should be calculated by an approved
method or in accordance with A.S.H.R.A.E. Guide or Manual J Load Calculations published by the Air Conditioning Contractors of
America.
Obtain from:
American National Standards Institute
1430 Broadway
New York, NY 10018
5
TRANSPORTATION
DAMAGE
GAS
Check the carton upon arrival for external damage. If damage is
found, a request for inspection by carrier agent should be made in
writing immediately.
IMPORTANT NOTE: This unit is factory set to operate on natural
as at the altitudes shown on the rating plate.
Carefully inspect the unit for damage including damage to the
cabinetry. Any bolts or screws which may have loosened in transit
must be re-tightened. In the event of damage, the receiver should:
1. Make notation on delivery receipt of any visible damage to
shipment or container.
2. Notify carrier promptly and request an inspection.
3. In case of concealed damage, carder should be notified
as soon as possible-preferably within 5 days.
4. File the claim with the following supporting documents:
a. Original Bill of Lading, certified copy, or indemnity bond.
b. Original paid freight bill or indemnity in lieu thereof.
c. Original invoice or certified copy thereof, showing trade
and other discounts or reductions.
_,WARNING
To AVOID
USING
THE
KITS
]'O
PREVENT
POSITION
LIFTING
PROPERTY
DURING
AND
B.DEQUATE
ALL
MOVING
CABLE
DAMAGE,
RIGGING
WHEN
A CRANE
MOVING
SHOULD
PLACE
FOR
REMAIN
TO
INJURY
HIGHER
FAILURE
AND/OR
INSTALLATIONS
OR
AND
DAMAGE.
ARE
WHEN
OBTAIN
TO DO SO CAN
EQUIPMENT
ONLY
DEATH
ALTITUDES,
EITHER
AND
RESULT
HIGH
INSTALL
IN
ALTITUDE
NOT APPROVED
FOR
USE
Min. Gas
5.0" W.C.,
Max. 10.0" W.C.
Inlet
Pressure
[
Propane
Min. 11.0" W.C._ Max. 13.0" W.C.
InletGas PressureMust Not Exceedthe MaximumValueShownin Table
Above.
The minimum supply pressure should not vary from that shown in
the table above because this could prevent the unit from having
dependable ignition. In addition, gas input to the burners must not
exceed the rated input shown on the rating plate. Overfiring of the
unit could result in premature heat exchanger failure.
DERATE
(U.S.
INSTALLATIONS
ONLY)
IMPORTANT NOTE: The gas/electric units naturally derate with altitude. Do not attempt to increase the tiring rate by changing orifices or increasing the manifold pressure. This can cause poor combustion and equipment failure. At all altitudes, the manifold pressure must be within 0.3 inches W.C. of that listed on the nameplate
for the fuel used. At all altitudes and with either fuel, the air temperature rise must be within the range listed on the unit nameplate.
Refer to the Installation Manual provided with the LP kit for conversion from natural gas to propane gas and for altitude adjustments.
IN AN UPRIGHT
FACILITATE
THE UNITIN
KIT(S).
OPERATION
U.S.
HIGH ALTITUDE
OPERATIONS.
IS USED,
CONVERSION
PERSONAL
OR AT
I Natural
WARNING
THE UNIT
ARE
DAMAGE,
ALONE
The rating plate is stamped with the model number, type of gas and
gas input rating. Make sure the unit is equipped to operate on the
type of gas available. Conversion to LP gas is permitted with the
use of the factory authorized conversion kit LPT-00A.
DETAILS
AND
PROPER
GAS
IN CANADA.
NOTE: When inspecting the unit for transportation damage, remove
all packaging materials. Recycle or dispose of the packaging material according to local codes.
_lk
PROPER_rY
PROPANE
UNSATISFACTORY
d. Copy of the inspection
report issued by carrier
representative
at the time damage is reported to the
carrier. The carrier is responsible for making prompt
inspection of damage and for a thorough investigation of
each claim. The distributor or manufacturer will not accept
claims from dealers for transportation damage.
RIGGING
PIPING
AN
SLING.
Important: If using bottom discharge with roof curb, ductwork should
be attached to the curb prior to installing the unit. Ductwork dimensions are shown in roof curb installation instructions.
PIPING
IMPORTANT NOTE: To avoid possible unsatisfactory operation or
equipment damage due to under firing of equipment, do not undersize the natural/propane gas piping from the meter/tank to the unit.
When sizing a trunk line, include all appliances on that line that
could be operated simultaneously.
The rating plate is stamped with the model number, type of gas
and gas input rating. Make sure the unit is equipped to operate on
the type of gas available. The gas line installation must comply
with local codes, or in the absence of local codes, with the latest
edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.
Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National
Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit,
center of gravity will cause condenser end to be lower than supply
air end.
Natural Gas Connection
Natural
in Cubic
Gas Capacity
Nominal
Black
Pipe Size (inches)
Length of
"ipe in Feet
10
1/2
132
3/4
278
1
520
20
30
92
73
190
152
350
285
730
590
1100
980
40
63
130
245
500
760
50
60
56
50
115
105
215
195
440
400
670
610
70
46
96
180
370
560
80
43
90
170
350
530
90
40
84
160
320
490
100
38
79
150
305
460
Pressure
CFH =
Rigging
of Pipe
Feet of Gas Per Hour (CFH)
1
1/4
1050
1
1/2
1600
50 PSIG or le_ssand Pressure Drop of 0 3" W C (Based
on 0 60 Specific Gravity Gas)
BTUH Furnace
Input
Heating Value of Gas (BTU/Cubic_Foot)
6
Referto the
GAS PIPING
Proper Piping Practice drawing for the general layout
at the unit. The following rules apply:
1. Use black iron pipe and fittings for the supply piping. The
use of a flex connector and/or copper piping is permitted
as long as it is in agreement with local codes.
2. Use pipe joint compound on male threads only. Pipe joint
compound must be resistant to the action of the fuel used.
3. Use ground joint unions.
4. Install a drip leg to trap dirt and moisture before it can enter
the gas valve. The drip leg must be a minimum of three
inches long.
5. Use two pipe wrenches when making connection to the gas
valve to keep it from turning.
6. Install a manual shut-off valve in a convenient location
(within six feet of unit) between the meter and the unit.
7. Tighten all joints securely.
8.
CHECKS
A
To
PREVENT
FOLLOWING
PROPERTY
• THE
AND
UNIT
AND
PLACING
FIRE,
EXCEED
GAS
UNIT
THE GAS
HEAT
AND
EXCHANGE
DURING
UNIT
BE ISOLATED
CLOSING
TESTING
EQUAL
MUST
ITS MANUAL
OF THE
MUST
PRESSURE
OF 1/2
SUPPLY
THAN
FLAME
TESTED
THE
BEFORE
OF EXPLOSION
TO TEST
FOR
HIGHER
OVERFIRING
VALVE
WHICH
OR
NEVER
LEAKS.
PRESSURE
MAY
MAY RESULT
IN
1/2
BE DISCONNECTED
TESTING
OF THAT
FROM
SYSTEM
AT
PSIG (s.4sKPA).
FROM
SHUT-OFF
GAS
TO OR LESS
FIRE,
GAS
FAILURE.
ANY
IN EXCESS
BE LEAK
DANGER
FOR TESTING.
CAUSE
ITS SHUT-OFF
SUPPLY
MUST
OF THE
OR OPEN
PRESSURES
• THIS
Rigid metallic pipe and fittings
Semirigid metallic tubing and metallic fittings (Aluminum
alloy tubing must not be used in exterior locations)
Listed gas appliance connectors used in accordance with
the terms of their listing that are completely in the same
room as the equipment
In the prior two methods above the connector or tubing
must be protected from physical and thermal damage.
Aluminum alloy tubing and connectors must be coated to
protect against external corrosion when in contact with
masonry, plaster or insulation or are subject to repeated
wettings by liquids (water - not rain water, detergents or
sewage)
BECAUSE
AND
DUE TO
REGARDING
TESTING:
PRESSURES
VALVE
INJURY
BE PERFORMED
CONNECTIONS
USE A MATCH
PREMATURE
The unit must be connected to the building piping by one
of the following methods:
GAS
SPECIFIED
DAMAGE
TEST
PRESSURE
ITS
OR PERSONAL
MUST
IN OPERATION.
NEVER
• THIS
DAMAGE
INSTRUCTIONS
CONNECTIONS
CAUTION
THE
VALVE
PIPING
GAS
SUPPLY
DURING
SYSTEM
ANY
SYSTEM
BY
PRESSURE
AT TEST
PRESSURES
PSIG (3_e KPA).
AWARNING
To AVOID
PROPERTY DAMAGE OR PERSONAL INJURY_ BE SURE THERE
NO OPEN FLAME
IN THE VICINITY
DURING
IS
AIR BLEEDING.
There will be air in the gas supply line after testing for leaks
on a new installation. Therefore, the air must be bled from the
line by loosening the ground joint union until pure gas is
expelled. Tighten union and wait for five minutes until all gas
has been dissipated in the air. Be certain there is no open
flame in the vicinity during air bleeding procedure. The unit is
placed in operation by closing the main electrical disconnect
switch for the unit.
PROPANE
GAS
INSTALLATIONS
Iio
MANUAL
AWARNING
VAL_
/
HUT,OFF
"0 AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEA'II"I DUE TO FIRE
_DRIP
IR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS
DETECTING WARNING DEVICE• SINCE RUST CAN REDUCE THE LEVEL
LEG
//rl_
OF ODORANT
IN PROPANE
IS THE ONLY RELIABLE
_
GROUND
(INSTALl
CONTACT
JOINT UNION
_
_AS
AHEAD OF GAS VALVE)
A LOCAL
DETECTING
GAS, A GAS DETECTING
WAY TO DETECT
PROPANE
WARNING
WARNING
A PROPANE
GAS SUPPLIER
ABOUT
DEVICE
GAS LEAK.
INSTALLING
A
DEVICE•
IMPORTANT NOTE: Propane gas conversion kits must be
installed to convert units to propane gas.
All propane gas equipment must conform to the safety
standards of the National Board of Fire Underwriters (See NBFU
Manual 58).
For satisfactory operation, propane gas supply pressure must
be within 9.7 - 10.3 inches W.C. at the manifold with all gas
appliances in operation. Maintaining proper gas pressure
depends on three main factors:
1. Vaporization rate, which depends on (a) temperature of the
liquid, and (b) wetted surface area of the container or
containers.
Proper Piping Practice
NOTE: The unit gas supply entrance is factory sealed with plugs.
Keep plugs in place until gas supply is ready to be installed. Once
ready, replace the plugs with the supplied grommets and install gas
supply line.
2. Proper pressure regulation.
3. Pressure drop in lines between regulators, and between
second stage regulator and the appliance. Pipe size
required will depend on length of pipe run and total load of
all appliances.
7
TANKS AND PIPING
_WARNING
Complete information regarding tank sizing for vaporization,
recommended regulator settings and pipe sizing is available
from most regulator manufacturers and propane gas suppliers.
Since propane gas will quickly dissolve white lead or most
standard commercial compounds, special pipe dope must be
used. Shellac base compounds resistant to the actions of
liquefied petroleum gases such as Gasolac ®, Stalactic ®,
Clyde's ® or John Crane® are satisfactory.
To
PREVENT
FIRE OR
DETECTING
IF THE
• PROPANE
SETTLE
GAS
IN ANY
• PROPANE
5to15
FirstStage
EXCEPT
IS INSTALLED
IS HEAVIER
THAN
AREAS
A WARNING
DEVICE
LEAK,
INJURY
INSTALL
IN AN EXCAVATED
IS REQUIRED
AIR AND
OR CONFINED
MAY FADE,
DUE TO
A GAS
ANY
DUE
AREA
OR A
TO:
LEAKING
GAS
CAN
SPACES.
MAKING
THE GAS
UNDETECTABLE
DEVICE.
ELECTRICAL
THERMOSTAT
Second
Stage
NOMINAL PIPE SIZE
SCHEDULE 40
TUBING SIZE, O.D., TYPE L
LOCATION
Movement of air must not be obstructed by furniture, door,
draperies, etc. The thermostat must not be mounted where it
will be affected by drafts, hot or cold water pipes or air ducts in
walls, radiant heat from fireplace, lamps, the sun, television,
etc. Consult the Instruction Sheet packaged with thermostat
for mounting instructions.
All units have one stage of heating and one stage of
mechanical cooling. Units which will have economizers may
use thermostats with one or two stages of cooling.
*PG1360***1A ONLY: These models have two stages of
mechanical
cooling. A 1-stage heat, 2-stage cooling
thermostat is recommended for these models.
Sizing Between Nrst and Se(_nd Slage Regulator
MaXimum propane Capacri_s listed are based on 1 PSIG pressure Drop at 10
PSIG Set_ng Capacfaes in 1,000 BTU/HR
PiPE OR
WIRING
Mount the thermostat approximately five feet above the floor,
in an area that has an inside, vibration-free wall and has good
air circulation.
Typical Propane Gas Piping
3/8"
1/2"
5/8"
3/4"
7/8"
1/2"
3/4"
30
309
700
1,303
2,205
3,394
1,843
3,854
40
265
59_
1,115
1,887
2,904
1,5(7
3,298
50
235
531
988
1,672
2.574
1,398
2,9"23
60
213
481
896
1,515
2.332
1,267
2,649
70
196
446
824
1,394
2,146
1,165
2,437
80
182
412
767
1,297
1,996
1,084
2,267
90
171
386
719
1,217
1.873
1,017
2,127
100
161
365
679
1,149
1,769
961
2,009
150
130
293
546
923
1,421
/72
1,613
200
111
251
467
790
1,216
660
1,381
250
90
222
414
700
1,078
585
1,224
300
89
201
378
634
976
530
1,109
350
82
185
345
584
898
488
1,020
400
76
172
321
543
836
454
949
_LWARNING
The units are designed for operation on 60 hertz current and
at voltages as shown on the rating plate. All internal wiring in
the unit is complete. It is necessary to bring in the power supply
to the contactor as shown on the unit wiring diagram which is
supplied with each unit. 24 volt wiring must be connected
between the unit control panel and the room thermostat.
Multiply by 1 130
Mul_ply by 0 879
st_ng BetweenSingle or SeOmldStage Regulator and Appliance*
Ma>3mumpropane Capaci_esLISI_I al_ Based on 1/'2,,W C pr_SSUroDropat
11"WC SetUng Capacdl(_inl.0OOBPJ/HR
PiPE OR
TUBING
PERSONAL
GAS
PSIG
200 PSIG
Maximum
To o_nved to Capacit_s at 15 PSIG Se_ngs
To conver t to Capacri_s at 5 PSIG SellJngs
UNIT
A WARNING
LOW
OR SERIOUS
BY A PROPANE
DEVICE.
GAS ODORANT
WITH
Conbnuous
11" W.C.
TUBING
LENGTH,
FEET
GAS
SPACE,
DAMAGE
CAUSED
WARNING
PROPANE
CONFINED
See below for typical propane gas piping.
PROPERTY
EXPLOSION
NOMINAL
PIPE SIZE,
SCHEDULE
40
TUBING SIZE, O.D., WPE L
LENGTH,
FEET
3/8"
112"
518"
3/4"
718"
112"
3/4"
1"
1-114"
1-112"
10
49
110
205
348
539
291
6G_
1,146
2.353
3,525
20
34
76
141
239
368
200
418
,'88
1,61,'
2,423
30
27
61
114
192
296
161
336
632
1,299
1,946
40
23
52
97
164
253
137
284
541
1,111
1,665
50
20
46
86
146
224
122
255
480
985
4,476
60
19
42
78
132
20_
110
231
436
892
4,33•
80
16
35
67
113
174
94
19_
372
764
1,144
1_
14
32
59
100
154
84
175
330
677
1,014
125
12
28
52
89
137
74
155
29_
600
899
150
11
26
48
80
124
6•
141
265
544
815
200
10
22
41
69
1_
58
120
227
465
697
250
9
19
36
61
94
51
10•
201
412
618
30(]
8
18
33
55
85
46
97
48_
374
560
350
7
15
30
51
78
43
89
167
344
515
4_
•
15
28
47
73
4o
83
155
3_0
479
Ez_g
Ez_
*DATA
IN ACCORDANCE
WiTH
NFPA
PAMPHLET
NO
z,
=
©
CRYWG
LOW VOLTAGE
CONNECTOR
54
Low Voltage Wiring
Table 3 - Propane Gas Pipe Sizing
8
"Note:Junction box location
shown is optional and is
for illustration purposes only.
JUNCTION
Y_2C
BOX
R YIWG
LOW VOLTAGE
CONNECTOR
Electrical Power Directly To Junction Box
Low Voltage Wiring-*PG1360"*'1A
Only
Refer to the unit wiring diagram for electrical connections.
When installed, the unit must be electrically grounded in
accordance with local codes or in the absence of local codes,
with the National Electrical Code, ANSI/NFPA No. 70, and/or
the CSA C22.1 Electrical
Code. Ensure low voltage
connections are waterproof.
,_
TO
AVOID
THE
POLARIZED
RISK
AND
OF
WARNING
ELECTRICAL
SHOCK,
WIRING
TO THE UNIT
MUST
BE
GROUNDED.
Electrical Power Routed Through Bottom of Unit
i_
To AVOID
ONLY
PROPERTY
COPPER
DAMAGE
CAUTION
OR PERSONAL
_,BEL ALL
_/ERIFY
IMPROPER
WIRES
PROPER
INJURY
DUE TO
FIRE,
UNITVOLTAGE
USE
CONDUCTORS.
i_
O PREVENT
Typical Electrical Wiring Unit Voltage
PRIOR
AND
TO
OPERATION
CAUTION
DANGEROUS
OPERATION
DISCONNECTION
AFTER
The unit transformer is factory connected for 230V operation.
If the unit is to operate on 208V, reconnect the transformer
primary lead as shown on the unit wiring diagram. The induced
draft blower on some models is equipped with a 230V lead
(red) and a 208V lead (black). If equipped, connect the induced
draft blower 208V lead (black) in place of the 230V lead (red).
Tape the unused 230V lead.
WHEN
DUE
TOWIRING
SERVICING
ERRORS
CONTROLS.
SERVICING.
For unit protection, use a fuse or HACR circuit breaker that is
in excess of the circuit ampacity, but less than or equal to the
maximum overcurrent protection device. DO NOT EXCEED
THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON
UNIT DATA PLATE.
HEAT ANTICIPATOR
SETTING
The heat anticipator
is to be set by measuring the load
(amperage) atthe "R" circuit. Followthe instructions provided
by the thermostat for more details.
All line voltage
connections
must be made through
weatherproof fittings. All exterior power supply and ground
wiring must be in approved weatherproof conduit. Low voltage
wiring from the unit control panel to the thermostat requires
coded cable. See below for ground level and rooftop wiring.
Typical Thermostat and Unit 24 V Wiring Hookup
9
Down Discharae AoDlications
)
Dol
y/y2
Cut insulation around bottom openings and remove panels
from the bottom of the unit, saving the screws holding the
panels in place.
DUCTWORK
Duct systems and register sizes must be properly designed
for the C.EM. and external static pressure rating of the unit.
Ductwork should be designed
in accordance
with the
recommended methods of Air Conditioning Contractors of
America Manual D (Residential) or Manual Q (Commercial).
All ductwork
exposed to the outdoors
must include a
weatherproof barrier and adequate insulation.
....._
Aduct system should be installed in accordance with Standards
of the National Board of Fire Underwriters for the Installation
of Air Conditioning, Warm Air Heating and Ventilating Systems.
Pamphlets No. 90A and 90B.
The supply duct from the unit through a wall may be installed
without clearance. However, minimum unit clearances as
shown in the appendix must be maintained. The supply duct
should be provided with an access panel large enough to
inspect the air chamber downstream of the heat exchanger. A
cover should be tightly attached to prevent air leaks.
Typical 2-Stage Cool Thermostat and
Unit 24 V Wiring Hookup
*PG136O***1A Only
CIRCULATING
AIR
AND
FILTERS
AIRFLOW CONVERSION
Units can easily be converted from horizontal to downdischarge airflow delivery. In down_lischarge or high static
installations, the installer should measure the total external
static and review the blower performance charts before
performing the installation. In some installations it will be
necessary to change the blower speed to provide proper air
flow.
For duct flange dimensions on the unit refer to the Unit
Dimension illustration in the appendix.
For down-discharge
applications, the ductwork should be
attached to the roof curb prior to installing the unit. Ductwork
dimensions are shown in the roof curb installation manual.
If desired, supply and return duct connections to the unit may
be made with flexible connections to reduce possible unit
operating sound transmission.
Horizontal Air Flow
Remove supply and return duct covers which are attached to
the unit as shown below.
FILTERS
A
To
PREVENT
EQUIPMENT
PROPERTY
EFFICIENCY
BUILD UP ON INTERNAL
FILTER
_emove
_e_e
for horizontal
INSTALLED
CAUTION
DAMAGE
DUE TO FIRE AND LOSS OF
OR EQUIPMENT
PARTS,
NEVER
IN THE RETURN
DAMAGE DUETODUSTANDLINT
OPERATE
UNIT WITHOUT
AN AIR
AIR SYSTEM.
Even though a return air filter is not supplied with this unit,
there must be a means of filtering
all return air. The
*PG1336(3A,4A), *PG1342, *PG1348, and *PG1360 models
are provided with internal filter racks for down-discharge
applications. All units may be externally filtered.
Refer to the unit filter size chart in the appendix for filter size
information.
Filters installed external to the unit should be sized in
accordance with their manufacturer
recommendations.
A
covers
duct
applica_or_
throwaway filter must be sized for a maximum face velocity of
300 feet per minute.
Filter Installation
Important: When installing a filter, the air flow arrows on the
filter must point toward the circulator blower.
VENTING
NOTE: Venting is self-contained.
Remove these panels
for downflowduct
applications
Duct Cover Installation
10
Do not modify or block.
FLUE HOOD INSTALLATION
Install the flue hood and bug screen prior to operation of the
unit.
4.
To install the flue hood cover and bug screen:
1. Remove the flue hood and bug screen from inside the
heat exchanger compartment.
2. Slide the bug screen over the flanges of the flue hood and
attach the flue hood and screen to the unit with the sheet
second on delay period. ECM motor will energize at heating
speed after the 45 second delay regardless of the status
of the main burner flame.
The unit delivers heat to the conditioned space until the
thermostat is satisfied.
5. The gas valve deenergizes.
The induced draft blower
continues operation for a 29-second post-purge.
6. Ignition control begins timing the HEAT FAN OFF delay.
There is an adjustable
HEAT FAN OFF delay of
approximately 120/135/150 seconds (factory set at 150).
After the H EAT FAN OFF delay time has elapsed, the blower
will deenergize. This allows any additional heat in the
heat exchanger to be transferred to the conditioned space.
*PGI 3(48,60)**'1A ONLY: HEAT FAN OFF delay is fixed at
180 seconds. Airflow level is 50% of nominal heating
airflow.
metal screws provided.
COOLING
1. Thermostat calls for cooling. The compressor and outdoor
fan are energized.
2. Approximately seven seconds later, the indoor fan starts.
3. The unit will deliver cooling to the conditioned space until
the thermostat is satisfied.
4. The compressor and outdoor fan will be deenergized when
the thermostat opens.
5. The indoor fan continues to run for approximately
60
seconds after the thermostat is satisfied.
This allows
additional cooling from the indoor coil to be transferred to
the conditioned space. Then, the indoor fan stops.
*PG1348***1A ONLY:
1. Thermostat calls for cooling. Outdoor fan and compressor
are energized. ECM motor is energized almost immediately
for 30 seconds at 50%ofthe nominal airflow. Airflow then
increases to nominal airflow.
2. The unit will deliver cooling to the conditioned space until
thermostat is statisfiod.
Flue Hood and Bug Screen Installation
CONDENSATE
CONDENSATE
DRAIN
DRAIN CONNECTION
A 314" NPT drain connection is supplied for condensate piping. An
external trap must be installed for proper condensate drainage.
DRAIN
CONNECTION
3. The outdoor fan and compreesor will be de-energized when
thermostat opens.
4. ECM motor continues to operate for approximately
60
seconds at 50% of nominal airflow after thermostat opens.
2.1.1.u.1 1/
]_J BING-HONE
_
*PG1360***1A ONLY:
1. Thermostat calls for low stage cooling. Outdoor fan and
low stage compressor are energized. ECM motor is
energized almost immediately for 30 seconds at 50% of
the nominal low stage airflow. Airflow then increases to
nominal low stage airflow.
If thermostat calls for high stage cooling, outdoor fan and
low and high stage compressor is energized. ECM motor is
energized almost immediately for 30 seconds at 50% of
the nominal high stage airflow. Airflow then increases to
nominal high stage airflow.
2. The unit will deliver cooling to the conditioned space until
thermostat is satisfied.
3. The outdoor fan and low stage compressor (or low and high
stage compressor) will be de-energized when thermostat
opens.
4. ECM motor continues to operate for approximately 60
seconds at 50% of nominal low stage airflow (or high stage
airflow if thermostat call was for high stage cooling) after
thermostat opens.
3" MINIMUM
o
,
_PA
POSITIVE
SEAL
LIQUID
iS REQUIRED
Drain Connection
NORMAL
SEQUENCES
OF
OPERATION
HEATING
This unit is equipped with an ignition control that automatically
lights the main burner. DO NOT attempt to light the main
burners by any other method.
1. Thermostat calls for heat. The induced draft blower
energizes for a 15-second pre-purge.
2. The spark igniter and gas valve energizes for 7 seconds.
NOTE: The igniter produces a very intense electrical spark
that ignites the gas.
3. The 30-second HEAT FAN ON delay time begins.
*PGI3(48,6O)***IA
ONLY: Heat on delay begins when
thermostat calls for heat. ECM motor is energized
approximately 45 seconds later. NOTE: ECM motor may
operate at approximately 100 CFM or less during the 45
NOTE: A 180-second anti-short cycle is integral to the control and
prevents recycling of the compressor.
11
FAN
Secondan/Limit
ONLY
The secondary limit control is located on the top of the blower
scroll assembly.
This control opens when elevated
temperatures are sensed. Elevated temperatures at the
control are normally caused by blower failure. The reason for
the opening should be determined and repaired prior to
resetting.
If the power to the unit is interrupted during the heating cycle,
it may cause the secondary limit to trip. Once the blower
compartment temperature
drops below the limit reset
temperature, the limit will automatically reset.
1. Thermostat calls for FAN ONLY by energizing "G".
2. Approximately seven seconds later, the indoor fan starts.
3. The indoor fan continues to run for approximately
60
seconds after "G" is de-energized.
*PG13(48,6O)***1A ONLY:
1. Thermostat calls for FAN ONLY by energizing "G".
2. ECM motor is energized
almost immediately
at
approximately 30% of the nominal high stage cooling
airflow, depending on setting (see "Blower Speed
Adjustment" section).
3. EfiM is de-energized almost immediately after =G" is deenergized.
STARTUP,
ADJUSTMENTS,
AND
Control
CHECKS
HEATING STARTUP
This unit is equipped with an electronic ignition device to
automatically light the main burners. It also has a power vent
blower to exhaust combustion products.
On new installations, or if a major component has been
replaced, the operation of the unit must be checked.
Check unit operation as outlined in the following instructions.
If any sparking, odors, or unusual sounds are encountered,
shut off electrical power and recheck for wiring errors, or
obstructions in or near the blower motors. Duct covers must
be removed before operating unit.
Backof Und
Secondary Limit Control
Heat AnUcioator Settine
Pre-ODeration Checks
Set the heat anticipator on the room thermostat to 0.4 amps to
obtain the proper number of heating cycles per hour and to
prevent the room temperature from overshooting the room
thermostat setting.
1.
2.
3.
4.
Close the manual gas valve external to the unit.
Turn off the electrical power supply to the unit.
Set the room thermostat to its lowest possible setting.
Remove the heat exchanger door on the side of the unit by
removing screws.
5. This unit is equipped
with an ignition device which
automatically lights the main burner. DO NOT try to light
burner by any other method.
6. Move the gas control valve switch to the OFF position. Do
not force.
Rollout Protection Control
The rollout protection device opens, cutting power to the gas
valve, if the flames from the burners are not properly drawn
into the heat exchanger. The rollout protection device is located
on the burner bracket. The reason for elevated temperatures
at the control should be determined and repaired prior to
resetting this manual reset control.
7. Wait five minutes to clear out any gas.
8. Smell for gas, including near the ground. This is important
because some types of gas are heavier than air. If you
have waited five minutes
and you do smell gas,
immediately follow the warnings on page 3 of this manual.
If having waited for five minutes and no gas smell is noted,
move the gas control valve switch to the ON position.
9. Replace the heat exchanger door on the side of the unit.
10. Open the manual gas valve external to the unit.
11. Turn on the electrical power supply to the unit.
12. Set the thermostat to desired setting.
_bWARNING
To AVOID
PROPERTY
OR EXPLOSION,
DAMAGE,
A QUALIFIED
PERSONAL
SERVICER
THE
ROLLOUT
PROTECTION
DEVICE
THE
ROLLOUT
PROTECTION
DEVICE.
./<
INJURY
MUST
TO OPEN
OR
DEATH
INVESTIGATE
BEFORE
DUE TO
THE
MANUALLY
FIRE
REASON
FOR
RESETTING
/
_
FRoIIout Protection
IN
@
White-Rodgers
Rollout Protection on Burner Bracket
12
Model 36F22
OUTLET
Only small variations in gas flow should be made by means
of the pressure regulator adjustment. In no case should the
final manifold pressure vary more than plus or minus 0.3
inches water column from the specified nominal pressure.
Any major changes in flow should be made by changing the
size of the burner orifices. The measured input rate to the
furnace must not exceed the rating specified on the unit rating
plate.
/ GasValve
Or_Off
Selector
Switch
White-Rodgers
For natural gas, the manifold pressure must be between 3.2
and 3.8 inches water column (3.5 nominal).
36G22
For propane gas, the manifold pressure must be between 9.7
and 10.3 inches water column (10.0 nominal).
Gas SUDDIVAnd Manifold Check
Gas supply pressure and manifold pressure with the burners
operating must be as specified on the rating plate.
Gas Inout tNatural Gas Onlv_ Check
To measure the gas input use a gas meter and proceed as
follows:
Gas Inlet Pressure Check
Gas inlet pressure must be checked and adjusted
accordance to the type of fuel being consumed.
in
With Power And Gas Off:
1. Connect a water manometer or adequate gauge to the inlet
pressure tap of the gas valve.
Inlet gas pressure can also be measured by removing the
cap from the dripleg and installing a predrilled cap with a
hose fitting.
With Power And Gas On:
2. Put unit into heating cycle and turn on all other gas
consuming appliances.
Natural
Inlet
Gas W.C.,
Pressure
Min. 5.0"
Max. 10.0" W.C.
I
Propane
Min. 1!.0" W.C., Max. 13.0" W.C.
I
1. Turn off gas supply to all other appliances except the unit.
2. With the unit operating, time the smallest dial on the meter
for one complete revolution. If this is a 2 cubic foot dial,
divide the seconds by 2; if it is a 1 cubic foot dial, use the
seconds as is. This gives the seconds per cubic foot of gas
being delivered to the unit.
3. INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT
Example: Natural gas with a heating value of 1000 BTU per cubic
foot and 34 seconds per cubic foot as determined by Step 2, then:
Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. NOTE:
BTU content of the gas should be obtained from the gas
supplier. This measured input must not be greater than
shown on the unit rating plate.
4. Relight all other appliances turned off in step 1. Be sure all
pilot burners are operating.
Main Burner Flame Check
Flames should be stable, soff and blue (dust may cause orange
tips but they must not be yellow) and extending directly outward
from the burner without curling, floating or lifting off.
NOTE: Inlet Gas Pressure Must Not Exceed the Maximum Value
Shown.
If operating pressures differ from above, make necessary
pressure regulator adjustments, check piping size, etc., and/
or consult with local utility.
v_
_bne
To F_
Man_r
Measuring Inlet Gas Pressure
Alternate Method
Manifold Pressure Check
The gas valve has a tapped opening to facilitate measurement
of the manifold pressure. A"U" Tube manometer having a scale
range from 0 to 12 inches of water should be used for this
measurement. The manifold pressure must be measured with
the burners operating.
To adjust the pressure regulator, remove the adjustment screw
or cover on the gas valve. Turn out (counterclockwise) to
decrease pressure, turn in (clockwise) to increase pressure.
Temoerature
Rise Check
Check the temperature rise through the unit by placing
thermometers in supply and return air registers as close to the
unit as possible. Thermometers must not be able to sample
temperature directly from the unit heat exchangers, or false
readings could be obtained.
1. All registers must be open; all duct dampers must be in their
final (fully or partially open) position and the unit operated
for 15 minutes before taking readings.
2. The temperature rise must be within the range specified on
the rating plate.
NOTE: Air temperature rise is the temperature difference between
supply and return air.
With a properly designed system, the proper amount of
temperature rise will normally be obtained when the unit is
operated at rated input with the recommended blower speed.
If the correct amount of temperature rise is not obtained, it
may be necessary to change the blower speed. A higher blower
speed will lower the temperature rise. A slower blower speed
will increase the temperature rise.
NOTE: Blower speed MUST be set to give the corTect air temperature rise through the unit as marked on the rating plate.
13
External Static Pressure Check
Dipswitch Settings and Corresponding
The total external static pressure must be checked on this
unit to determine if the airflow is proper.
Model
GPG13480701*
GPG13480901*
GPG13481151*
GPG13600901*
GPG13601151*
GPG13601401*
Blower SPeed Adjustments
I
,_WARNING
TO
AVOID
PERSONAL
INJURY
E_ECNTER/CMALTPoORWERFROM
OR DEATH
THE UNIT
DUE TO
BEFORE
ELECTRIC
CHANGING
SHOCK,
SPEED
TAPS
Model
ON THE
GPG13480701*
GPG13480901*
GPG13481151*
GPG13600901*
GPG13601151*
GPG13601401*
Cooling-Yellow Lead
T4 - Low Speed
T5 - High Speed
COOL
CFM
HEAT
COOL
1020
1540
1140
1540
1420
1540
1140
1810
1420
1810
1700
1810
The adjustment factors for theADJUST function areA= 1, B =
1.10 (+10%) and C = 0.85 (-15%). The D tap for the ADJUST
function has no effect on airflow. Example: Airflow tables
indicate 1425 CFM. With the ADJUST set to B tap, the CFM
becomes 1.10"1425 CFM = 1568 CFM.
Dehumidification
The GE ECM motor has the capability to provide increased
dehumidification
during cooling operation.
This is
accomplished by lowering the airflow to approximately 85%
of the nominal cooling airflow. Example: Unit is operating at
1400 CFM and humidistat calls for dehumidification. Resulting
airflow is 0.85* 1400 CFM = 1190 CFM
ADJUST
COOL
8
OFF
OFF
OFF
OFF
OFF
OFF
*PGI360***1A ONLY: Low stage airflow is approximately 75%
of high stage cooling airflow. Example: High stage cooling
airflow is 1800 CFM. Low stage cooling airflow is 6.75"1806
CFM = 1350 CFM.
To make use of this feature, a 24VAC humidistat which
opens on humidity rise is required. Connect humidistat to
the HUMIDISTAT/HUM terminal on the low voltage terminal
board (see wiring diagram in the appendix). Clip the HUM/
PJ6jumper on the low voltage terminal board. The system
is now ready to provide dehumidification.
To adjust the HEAT, COOL or ADJUST functions, simply change
the ON/OFF position of the appropriate dipswitchos. The table
below shows the ON/OFF combinations for the various switches
and the corresponding A, B, C, or D taps. Refer to the Product
Data Book applicable to your model for airflow tables and
temperature rise. The =Dipswitch Position" table below shows
the factory dipswitch settings for each model. The =CFM" table
below shows the nominal heating and cooling CFM for each
model.
HEAT
7
OFF
OFF
OFF
OFF
OFF
OFF
NOTE: Heating airflow must be adjusted to provide the temperature rise shown on rating plate.
lo,,,,,,,,
DELAY
DIP SWITCH POSITION
3
4
5
6
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF OFF
OFF
OFF
OFF OFF
OFF
OFF
OFF OFF
OFF
Unit dipswitches are factory set for each model, see label on
blower housing for CFM adjustment next to low voltage terminal
connections.
*PG13(48, 60)**'1A models are equipped with GE ECM
motors. These motors offer greater airflow flexibility as well
as dehumidification. The airflow delivery for these models
can be adjusted by changing the position of dip switches on
a low voltage terminal board. The figure below shows the
dipswitch layout on the low voltage terminal board as well as
the function of each set of switches. The "HEAT" function
(switches 1 and 2) provides airflow adjustment for heating
airflow. The "COOL" adjustment function (switches 5 and 6)
provides airflow adjustments for cooling airflow. The
=ADJUST" function (switches 7 and 8) will adjust the heating
AND cooling airflow +10% or - 15%. The "DELAY" function
(switches 3 and 4) is not field adjustable.
HEAT
2
ON
ON
OFF
ON
ON
OFF
REMOVE
Refer to the wiring diagram in the appendix to verity speed tap
settings.
Blower speeds are to be changed at the ignition control board.
Both heat speed and cool speed terminals are supplied on
the board along with two unused motor lead terminals.
*PG13(48, 60)**'1B, 3A, 4A models are equipped with X-13
motors. X-13 motors are constant torque motors with very low
power consumption. This motor is energized by 24V. Adjust
the CFM for the unit by changing the 24V low voltage leads to
the speed terminal block on the motor.
Heating-White Lead
T1 - Low Speed
T2 - Medium Speed
T3 - High Speed
1
ON
OFF
ON
ON
OFF
ON
Tap
Limit Check
Check limit control operation after 15 minutes of operation
by blocking the return air grille(s).
1. After several minutes the main burners must go OFF.
Blower will continue to run.
2. Remove air restrictions and main burners will relight
after a cool down period of a few minutes.
Adjust the thermostat setting below room temperature.
1. Main burners must go OFF.
2. Circulating Air Blower will continue to run for 120, 135 or
150 seconds, depending on the setting.
*PGI3(48,6O)***1A ONLY: Circulating Air Blower will
continue to run for 180 seconds.
ADJUST
$ Factory Set, not rmld adJustable
• Tap D haS no effect on airflow
14
to ensure the proper refrigerant superheat at the compressor
is adjusted for each application. For example, 10 degree
refrigerant superheat level is adequate for a 95 degree outdoor
ambient temperature and a 78 - 80 degree for indoor return air
temperature. As the outdoor ambient temperature rises the
superheat decreases and as the outdoor ambient temperature
lowers the superheat increases. Proper superheat adjustment
optimizes cooling performance.
For models equipped with thermostatic expansion valve, charge
system to 12-14 degrees of subceoling, adjust expansion valve
stem for superheat setting when necessary.
NOTE: The expansion valve will not need adjustment for most
applications. Ensure system superheat is set between 10-12 degrees
after final adjustment.
Control Board (Top)
NOTE: If necessary, adjust fan OFF delay settings to obtain satisfactory comfort level.
_I=
THIS
UNIT
FINISHING
USE
LOW
MAY
MUST
BE
OF
RESULT
RETURN
D_RTY
NOT
pHASES
IN
AIR
USED
AS
PREMATURE
NOTE: Mechanical cooling cannot be reliably provided at ambient
temperatures below 50 ° F.
WARNING
A "CONSTRUCTION
CONSTRUCTION
ON
A
FAILURE
TERMPERATURES
AND
HEATER"
NEW
OF
Coolinn ODeration
DURING
STRUCTURE.
THE
UNIT
EXPOSURE
DUE
TO
THIS
TO
THE
TYPE
1. Turn on the electrical power supply to the unit.
2. Place the room thermostat selector switch in the COOL
position (or AUTO if available, and if automatic changeover
from cooling to heating is desired).
3. Set the room thermostat to the desired temperature.
OF
EXTREMELY
CORROSIVE
OR
VERY
ATMOSPHERES.
Untt Shutdown
TROUBLESHOOTING
1. Set the thermostat to lowest setting.
2. Turn off the electrical power supply to the unit.
3. Remove the heat exchanger door on the side of the unit by
removing screws.
4. Move the gas control valve switch to the OFF position. Do
not force.
5. Close manual gas shutoff valve external to the unit.
6. Replace the heat exchanger door on the unit.
7. If cooling and/or air circulation will be desired, turn ON the
electrical power.
COOLING
IGNITION CONTROL
The following presents probable causes of questionable unit
operation.
Refer to Diagnostic
Indicator Chart for an
interpretation of the signal and to this section for an explanation.
Remove the control box access panel and note the number of
diagnostic LED flashes. Refer to Diagnostic Indicator Chart
for an interpretation of the signal and to this section for an
explanation.
STARTUP
NOTE: Check all manual reset limit controls in heating circuit if
cooling mode does not operate.
Comeressor Protection Devices
ABNORMAL
_bWARNIN
To PREVENT
PERSONAL
BEFORE
INJURY
INSPEC'RNG
PROToEuCT1
_)Nc_D FEVAICESRESET
OR DEATH,
OR SERVICING
If the integrated ignition control in this unit encounters an
internal fault, it will go into a "hard" lockout and turn off the
diagnostic LED. If diagnostic LED indicates an internal fault,
check power supply to unit for proper voltage, check all fuses,
circuit breakers and wiring. Disconnect electric power for five
seconds. If LED remains off after restoring power, replace
control.
AUTOMATICALLY.
G
ALWAYS
DISCONNECT
THE UNIT. ALL
ENERGIZING
OPERA TION - HEATING
Internal Control Failure
The compressor includes components which are designed
to protect the compressor against abnormal operating
conditions.
POWER
ERROR CODES
ELECTRICAl
Extemal
Lockout
COMPRESSOR
An external lockout occurs if the integrated ignition control
determines that a measurable
combustion cannot be
established within three (3) consecutive ignition attempts. If
flame is not established within the seven (7) second trial for
ignition, the gas valve is deenergized, 15 second inter-purge
cycle is completed, and ignition is reattempted. The control
will repeat this routine three times if a measurable combustion
is net established. The control will then shut off the induced
draft blower and go into a lockout state.
If flame is established but lost, the control will energize the
circulatorblower at the heat speed and then begin a new ignition
sequence. If flame is established then lost on subsequent
attempts, the control will recycle for four (4) consecutive
ignition attempts (five attempts total) before locking out.
THE CONTACTOR
Coolino Refriaerant Charoino
Check unit charge before putting the cooling section into full
operation. The unit is factory charged with R-22 for nominal air
flow and static pressure conditions. The unit has a piston
flowrater expansion device.
NOTE: *PG1360 is equipped with a thermostatic valve expansion
device.
To ensure the unit is properly charged for the intended
application, check the unit refrigerant superheat at the
compressor. The refrigerant superheat is a function of outdoor
ambient temperature and return air temperature of the
conditioned space. It is the installing contractors responsibility
15
The diagnostic fault code is 1 flash for a lockout due to failed
ignition attempts or flame dropouts. The integrated control
will automatically reset after one hour, or it can be reset by
removing the thermostat signal or disconnecting the electrical
power supply for over five seconds. If the diagnostic LED
indicates an external lockout, perform the following checks:
Check the supp/y and manifold pressures
Check the gas orifices for debris
Check gas valve for proper operation
Check secondary limit
A dirty filter, excessive duct static, insufficient air flow, a
faulty limit, or a failed circulator blower can cause this
limit to open. Check filters, total external duct static,
circulator blower motor, blower motor speed tap (see
wiring diagram), and limit. An interruption in electrical
power during a heating cycle may also cause the
auxiliary limit to open. The automatic reset secondary
limit is located on top of the circulator blower assembly.
Check rollout limit
If the burner flames are not properly drawn into the heat
exchanger, the flame rollout protection device will open.
Possible causes are restrictedor blocked flue passages,
blocked or cracked heat exchanger, a failed induced
draft blower, or insufficient combustion air. The rollout
protection device is a manual reset limit located on the
burner bracket. The cause of the flame rollout must be
determined and corrected before resetting the limit.
Check flame sensor
A drop in flame signal can be caused by neady invisible
coating on the sensor. Remove the sensor and carefully
clean with steel wool.
Check wiring
Check wiring for opens/shorts and miswiring.
Important: If you have to frequently reset your gas/electric
package unit, it means that a problem exists that should be
corrected.
Contact a qualified
servicer
for further
information.
Flame Detected with Gas Valve Closed
If flame is detected with the gas valve deenergized, the
combustion and air circulator blowers are energized. The
diagnostic fault code is five (5) flashes for this condition. The
control can be reset by removing the power supply to the unit
or it will automatically reset after one hour. Miswiring is the
probable cause for this fault.
ABNORMAL
OPERA TION - COOLING
Short Cycle Compressor Delay
The automatic ignition control has a built-in feature that
prevents damage to the compressor in short cycling
situations. In the event of intermittent power losses or
intermittent thermostat operation, the ignition control will delay
output to the compressor contactor for three minutes from the
time power is restored. (Compressor is off a total of three
minutes). The diagnostic LED will flash six (6) times to indicate
the compressor contactor output is being delayed.
NOTE:
Some
electronic
thermostats
also have a built-in
compressor short cycle timer that may be longer than the three
minute delay given above. If you are using an electronic thermostat
and the compressor has not started after three minutes, wait an
additional five minutes to allow the thermostat to complete its short
cycle delay time.
MAINTENANCE
.1o.
VO,T,O,
=1111
&w.....o
_lll 1
o°
.%AOSE
P.OP/
DISCONNECTALL POWERBEFORESERVICINGOR
INSTALLINGTHISUNIT. MULTIPLE POWEREOURCESMA_
Pressure Switch Stuck Open
Have the gas heating section of the unit checked at least
once a year before the heating season begins, to be sure that
the combustion air inlet and flue outlet hoods are not blocked
by debris, which would prevent adequate combustion air and
a prepedy operating vent system.
A pressure switch stuck open can be caused by a faulty
pressure switch, faultywidng, a disconnected or damaged hose,
a blocked or restricted flue, or a faulty induced draft blower.
If the control senses an open pressure switch during the prepurge cycle, the induced draft blower only will be energized. If
the pressure switch opens after ignition has begun the gas
valve is deenergized, the circulator blower heat off cycle begins,
and the induced draft blower remains on. The diagnostic fault
codeistwoflashes.
FILTER REPLACEMENT
A return air filter is not supplied with this unit; however, there
must be a means of filtering all of the return air. The filter(s)
may be located in the return air duct(s), or return air filter
grille(s). Consult with your installing dealer for the actual
location of the return air filter(s) for your unit.
Dirty filters are the most common cause of inadequate heating
or cooling performance. Filter inspection should be made at
least every two months; more often if necessary because of
local conditions and usage.
Dirty throwaway filters should be discarded and replaced with
a new, clean filter. Dirty permanent filters should be washed
with water, thoroughly dried and sprayed with a filter adhesive
before being reinstalled. (Filter adhesives may be found at
many hardware stores.) Permanent filters should last several
years. However, should one become tom or uncleanable, it
should be replaced.
Pressure Switch Stuck Closed
A stuck
pressure
pressure
off. The
OR CLEANING
closed pressure switch can be caused by a faulty
switch or faulty wiring. If the control encounters a
switch stuck closed, the induced draft blower remains
diagnostic LED code for this fault is three (3) flashes.
Ooen Thermal Protection Device
If the primary limit switch opens, the gas valve is immediately
deenergized, the induced draft and air circulating blowers are
energized. The induced draft and air circulator blowers remain
energized until the limit switch recloses. The diagnostic fault
code for an open limit is four (4) flashes.
A primary limit will open due to excessive supply air
temperatures. This can be caused by a dirty filter, excessive
duct static, insufficient air flow, or a faulty limit. Check filters,
total external duct static, blower motor, blower motor speed
tap (see widng diagram), and limit. This limit will automatically
reset once the temperature falls below a preset level.
CABINET FINISH MAINTENANCE
Use a fine grade automotive wax on the cabinet finish to
maintain the finish's original high luster. This is especially
important in installations with extended periods of direct
sunlight.
16
CLEAN
OUTSIDE
COIL
(QUALIFIED
SERVICER
ONLY)
CLEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY)
The ceil with the outside air flowing over it should be inspected
annually and cleaned as frequently as necessary to keep the
finned areas free of lint, hair and debris.
1. Shut off electric power and gas supply to the unit.
2. Remove burner assembly by disconnecting the gas line
and removing the manifold bracket from the partition panel.
3. Remove the flue from the induced draft blower and the
collector box cover from the partition panel.
4. The primary heat exchanger tubes can be cleaned using a
round wire brush attached to a length of high grade stainless
steel cable, such as drain cleanout cable. Attach a variable
speed reversible drill to the other end of the spring cable.
Slowly rotate the cable with the drill and insert it into one of
the primary heat exchanger tubes. While reversing the drill,
work the cable in and out several times to obtain sufficient
cleaning. Use a large cable for the large tube, and then
repeat the operation with a small cable for the smaller tube.
Repeat for each tube.
5. Whenallheatexchangertubeshavebeencleaned,
replace
the parts in the reverse order in which they were removed.
6. To reduce the chances of repeated fouling of the heat
exchanger, perform the steps listed in =Startup, Adjustments,
and Checks".
CONDENSER_ EVAPORATOR_AND INDUCED DRAFT MOTORS
Bearings on the air circulating blower motor, condenser motor
and the combustion fan motor are permanently lubricated. No
additional oiling is required.
FLAME SENSOR (QUALIFIED SERVICER ONLY)
A drop in the flame curTentcan be caused by a nearly invisible
coating on the flame sensor. This coating, created by the fuel
or combustion air supply, can be removed by carefully cleaning
the flame sensor with steel wool.
NOTE: After cleaning, the microamp signal should be stable and in
the range of 4 - 6 microamps DC.
/
Flame
_
_Sensor
MAIN BURNER FLAME (QUALIFIED SERVICER ONLY)
Flames should be stable, soft and blue (dust may cause
orange tips but must not be yellow). The flames must extend
directly outward from the burner without curling, floating or
lifting off.
Flame Sensor
_heck the burner flames for:
1. Good adjustment
2. Stable, son and blue
3. Not curling, floating, or lifting off.
FLUE PASSAGES (QUALIFIED SERVICER ONLY)
At the start of each heating season, inspect and, if necessary,
clean the unit flue passage.
Burner Flame
_WARNING
To AVOID
DO NOT
PERSONAL
REMOVE
ADJUSTMENT.
FLAME
SHOULD
ANY
INJURY
OR
INTERNAL
CONTACT
DEATH
DUE TO
COMPARTMENT
A QUALIFIED
SERVICER
ELECTRIC
COVERS
AT ONCE
SHOCK,
OR ATTEMPT
ANY
IF AN AeNORMAL
DEVELOP.
At least once a year, prior to or during the heating season,
make a visual check of the burner flames.
NOTE: This will involve removing and reinstalling the heat exchanger
door on the unit, which is held by two screws. If you are uncertain
about your ability to do this, contact a qualified servicer.
If a strong wind is blowing, it may alter the airflow pattern within the
unit enough that an inspection of the burner flames is not possible.
17
CLEANING
ACCESSORIES
BURNERS
1. Shut oft electric power and gas supply to the unit.
2. Remove the screws securing the manifold to the burner
retention bracket. Remove the manifold and rotate each
burner counterclockwise to remove.
AND
FUNCTIONAL
PARTS
SHEET METAL ACCESSORIES
Additional accessories can be purchased to fit specific application
needs. Parts and instructions are available from your distributor.
FUNCTIONAL PARTS
Burner
Bracket
;Ill _[q/Is] _r,jll
_uxliary Limit Switch
Blower Housing
Circulator Blower Motor
Blower Wheel
Burner
Manifold_
Capacitor
Compressor
3ondenser Coil
Condenser Fan Blade
Condenser Fan Motor
Contactor
Gas Manifold
Manifold Assembly
3. Remove the burners.
4. Use a bottle brush to clean burner insert and inside of the
burners.
LABEL
ALL WIRES
WIRING
ERRORS
PRIOR
IMPROPER
1_
ALWAYS
VERIFY
PROPER
Functional Parts List
GENERAL INFORMATION
1. Refer to the description in Functional Parts List when
ordering any of the listed functional parts. Be sure to provide
the unit model and serial numbers with the order.
CAUTION
TO DISCONNECTION
CAN CAUSE
WHEN
SERVICING
AND DANGEROUS
CONTROLS.
2. Although only functional parts are shown, all sheet metal
parts, doors, etc. may be ordered by description.
3. Parts are available from your distributor.
OPERATION.
CAUTION
OPERATION
Heat Exchanger
High Limit Switch
Igniter
Ignition Control
Induced Draft Blower
Pressure Switch
Pressure Switch Hose
Transformer
Evaporator Coil
5. Replace burners and manifold, inspect the burner assembly
for proper seating of burners in retention slots.
6. Reconnect electrical power and gas supply.
_k
__,_:_i.
Flame Roll-out Switch
Flame Sensor
Gas Orifice
Gas Valve
AFTER
SERVICING.
For further information on the yearly inspection, consult the
User Manual. it is recommended that a qualified servicer inspect
and service the unit at least once each year.
Turn the unit on at the thermostat. Wait a few minutes, since
any dislodged dust will alter the normal flame appearance.
Flames should be predominantly blue and directed into the
tubes. They should not be yellow. They should extend directly
outward from the burner ports without curling downward,
floating or lifting off the ports.
18
IGNITION
CONTROL
Light Signal
Off
1 Flash
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
DIAGNOSTIC
Pressure Switch Stuck Open
Pressure Switch Stuck Closed
Thermal Protection Device Open
Flame Detected with Gas Valve Closed
Short Cycle Compressor Delay (Cooling Only)
TIMING
i
On
off
Gas Valve
On
CHART
Refer to Abnormal Heating or Cooling Operation Sections of this Manual
Internal Control Failure
External Lockout
HEATING
Circulator
Blower
INDICATOR
CHART
i
100 %
50 %
i
i
Off
Igniter
On
off
Induced
Draft
Blower
On
off
Thermostat
On
i
i
i
i
I
i
i
i
i
Off
Seconds
i
0
i
i
15
i
i
22
45
i
i
i
52
0
20
i
i
i
120, 135,150
180"PG1348,60
Legend: --*PG10,12,24-60,
*PG1324-42
........ *PG1348,60
COOLING
Circulator
Blower
ON
i
OFF _
i
OutdoorFan
and
Compressor
ON
OFF
ON
J
I
I
i
Legend: --
i
I
I
i
i
i
1
i
7
30
1
0
100%
_%
,'"i
ii
OFF
CHART
.....
ii
' '
Thermostat
Seconds
TIMING
i
i
0
*PGI O,12,24-60, *PG1324-42
........ *PG1348,60
19
60
ONLY
APPENDIX
UNIT
DIMENSIONS
47
23/4
BEHIND COMPI:_SSOR
ACCESS PANEL
RE]URN
SUPPLY
POWER WIRE ENTRANCE
COMBUSTION/_R
INLETS
SUPPLY
RE3URN
2O
DIMB_ISION
INCHES
MEDIUM
LARGE
A
32
40
B
16
18
C
9 1/2
14
GPG13(24,30,36,42)1A
WARNING
WIRING
DIAGRAM
DISCONNECT
ALL
POWER
BEFORE
SERVICING
ORINSTALLING
UNIT.
MULTIPLE
POWER
SOURCES
MAY BE PRESENT.
FAILURE THIS
TO
HIGH VOLTAGE!
DO SO MAY CAUSE PROPERTY
DAMAGE, PERSONAL
R
INJURY OR DEATH.
R
°L?
BL
Y
CH OPTIONAL
CONNECTED AT L1, L2
CH OPTIONAL
NOTE 4
PU
POWER
SUPPLY
20_23011!60
T .s
BR _B
NOTE 5
CAP2
BL
NOTE
R
7
PU(L2)
R
LOW
[_k
B
BR
BR
MED]UM
HIGH
PU BR
ALT 3 SPEED
MOTOR
I
LB
PU
4 SPEED
MOTOR
BL
I
I
k
)
ECON
F
NOTEp6L
G
GAS VALVE
YBL
1
GAS VALVE
_
FS
,=_o
IIC
PU
BL
I
I
I I I
TO THC
I
_EETHCFIELDWIRINGBELOW)
O
NOTE 5
PU
R
J
CAP1
PU
PU
BR
Y
B4312003 REV. B
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to.late
21
wiring.
GPG13(24,30,36,42)1A
WARNING
L1
WIRING
DIAGRAM
DISCONNECT
ALLPOWER
BEFORE
SERVICING
ORINSTALLING
THIS
UNIT. VOLTAGE!
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
I HIGH
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
SUPPLY VOLTAGE
1.2
COMPONENT LEGEND
208-230/1/60
CH
ccT__r_<_
NOTE
_
_c
ALS AU_LLARY LIMIT SWITCH
CAP CAPACITOR
COMP COMPRESSOR
CM CONDENSER MOTOR
4
i_
@
CC CONTACTOR
DH CRANKCASE HEATER
cApz
_
°WIRE SPLICE
GVJ_RKED TERMINAL
cUNMARKED TERMINAL
WIRING
LINE VOLTAGE
LOW VOLTAGE
FIELD INSTALLED POWER
FIELD INSTALLED CONTROL
EM EVAPORATOR MOTOR
FS FLAME SENSOR
GV GAS VALVE
lID INTEGRATED IGNITION CONTROL
IGN IGNITOR
LS LIMITSWITCH
PL PLUG
PS PRESSURESWITCH
RS ROLLOUTSWlTCH
THC ]I-IERMOSTATHEAT&COOL
TRANS TRANSFORMER
VM VENTMOTOR
(HIGH)
®
WIRE CODE
B BLACK
BL BLUE
BR BROWN
G GREEN
O ORANGE
PK PINK
PU PURPLE
R RED
W WHITE
Y YELLOW
NOTES
1. REPLACEMENT
INSULATIOR
WIRE MUST BE THE
AS ORIGINAL(USE
2. FOR 206 VOLT TRANSFORMER
FROM _RMINAL
3. SOME MODELS
®TO
SAME SIZE .&NO TYPE OF
COPPER
CONDUCTOR
OPERATION
TERMINAL
_ON
HAVE VENT MOTORS
MOVE
ONLY).
SLACK WIRE
]WANSFORMENo
EQUIPPED
WITH A 23OV LEAD (RED)
AND A 208V (SLACK), IF EQUIPPED, CONNECT VENT MOTOR BLACK LEAD
IN PLACE OF RED LEAD AT IIC (DI) FOR 2DSV OPERATION.
4. CRANKCASE HEATER (OPTIONAL).
5. FOR DIFFERENT THAN FACTORY SPEED TAP CHANGE COOLING
@
SPEED AT COOL TERMINAL (IIC). CHANGE HEATING SPEED AT HEAT
TERMINAL (IIC)
4 SPEED MOTOR
B - HIGH SPEED
BL - MEDIUM HIGH SPEED
Y - MEDIUM LOW SPEED
R - LOW SPEED
3 SPEED=MOTOR
B - HIGH SPEED
BL - MEDIUM SPEED
R - LOW SPEED
6, ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS)ADJACENT
TO BLOWER HOUSING IN RETURN AIR COMPARMEN][
208-230/1160
TOTHC
INSTALLER/SERVICEMAN
THC-FIELD
TH E STATUS LIGHT ON THE FLIRNACE CONTROL 1_L_YBE L_ED AS A GUIDE TO
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:
STATUS LIGHT
EQUIR STATUS
THC-NO
CHECK
ECONOMIZER
WIRING
2_NG
w
®
w
®
y
®
®
©
R
Pu
¥
®
@
@
ON
NOI_MAL OPERATION
OFF
NO POWER OR
INTERNAL CONTROL
FAULT
GHECKINPIJTFOWER
_ECKFU_ el0_l]_.
REPLACE CONTROL
-
1 BLINK
IGNITION FAILURE
OR
OPEN ROLLOUT
SWITCH
OR
OPEN AUX. LIMIT
SWITCH
GAS FLOW
GAS PRESSURE
GAS VALVE
FLAME SENSOR
FLAME ROLLOUT
BAD SWITCH
AUX. LIMIT OPEN
2 BLINKS
PRESSURE SWITCH
OPEN
CHECK
PRESSURE SWITCH
S SLINKS
FRESSLRE SWITCHGLOSEJ
WITHOUT INDUCER ON
CHECK
PRESSURE SWITCH
4 SLINKS
OPEN LIMIT SWITCH
MAIN LIMIT OPEN
BAD SWITCH
R
®
5 BLINKS
FALSE FLAME SENSED
STICKINGGAS VN-VE
PU
®
S BLINKS
COMPRESSOR
OUTPUT DELAY
3 MIN, COMP
ANS].C'fCLE ]]MER
BL
®
BL
TI-IC-W ITH ECONOMIZER OPTION
w
B4312003 REV. B
Wiringis subjectto change. Alwaysrefer to the wiringdiagramon the unitfor the mostup-to.late wiring.
22
GPG13(48)1A
WARNING
WIRING
DIAGRAM
DISCONNECT
ALLPOWER
BEFORE
SERVICING
ORINSTALLING
THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
HIGH VOLTAGE!
ATH._I
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE
CH OP I]ONAL
CONNEC1ED AT L1, L2
NOTE4
POWER SUpI_y
208_301116D
i
I ............................
Q
2O8
TRANS
24V
TO THC
8L
I ALS
Pu
R
G
Y
R
G
Y
R
G
W
Y
Y1
Y2
W
y
Y
NOTE 5
PL
PU
IIC
W R
(ALT) HONEYWELL
GAS VALVE
[
GAS VALVE
BL
NOTE
3
CAP1
Pu
R
Pu
BR
Y
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to.late
23
B431211114
wiring.
Rev.
A
GPG13(48)1A
WARNING
L1
WIRING
DIAGRAM
DISCONNECT
ALLPOWER
BEFORE
SERVICING
ORINSTALLING
THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
HIGH
V
OLTAGE
ATH.% II I
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE
SUPPLy VC_TAGE
208_30tl/60
COMPONENT LEGEND
AIS AL_(ILLARy LIMIT S_VlTCH
o WtRESPLICE
CAP CAPACITOR
O
COMp COMPRESSOR
CM
CONDENSER MOTOR
CC
CH
CONTACTOR
CRANKCASE HEATER
WIRING
FS FLAME SENSOR
GV G_S VALVE
m
LINEVOLTAGE
.......
LOW VC_TAGE
FIELO INSTALLED pOWER
FIELD INST_
IIC INTEGRATED IGNITIO N CONTROL
IGN
MARKED TERMINAL
O UNMARKED TERMINAL
IGNITOR
CONTROL
WIRE CCDE
LS LIMITSWITCH
B
PL PLUG
BL BLUE
PS PRESSURESWITCH
BR
RS ROLLOUTSWITCH
G
GREFN
I_
0
ORANGE
TERMINAL BLOCK
BLACK
BROWN
MC ITIEt_4OSTATHEAT&COOL
TRANS TRANSFORMER
PK PINK
PU pURPLE
VM
R
VENTMOTOR
VSM VAR SPEEDMOTOR
RED
W WHrlE
y YELLOW
VSTB VARIABLE SPEED TERM BLOCK
NOTES
1 REPLACEMENT WIRE MUST BE THE SAME SIZF AND TYpE OF
INSULAtiON AS ORIGINAL (USE COppER CONDUCTOR ONLY)
IIC
2 FOR 208 VOLT I_ANSFORMER
FROM TERMINAL@TO
OpE3_ATION MOVE BLACK WIRE
TERMINAL@ ON TRANSFORMER
3 SOME MODES HAVE VENT MOTORS EQUIPPED WrlH A 230V LEAD (RED)
AND A 208V (BLACk') IF EQUIPPED, CONNECT VENT MOTOR BLACK LEAD IN
pLACE OF rED LEAD AT UII {DI) FOR _
OPERATION
4 CRANKCASE HF_. {_R (OPTIONAl)
5 AOBESSORY ECONOMIZER PLUG {ON S[_E_q MODI LS) ADJACENT
TO BLOWER HOUSING IN R_rURN AIR _O Mp.%RMENT
6 TWO STAGE MERMOSTAT
OPTION INSTNJ£O
S]B
CONNECTIONS IF USED WITH ECOI_OMIZER
NOTE6
TO THC
208_3_1_0
INSTALLER/SERVICEMAN
I_E
STATUS UGHT (_N THE FURNACE CONTROL
]ROLIBI
FSHOOTING
STATUS
LIGHT
ON
]H_S APPLIANCE
STATUS
EQUIP
NORMAL
THC-FIELD
WIRING
MAy BE USED AS A GUIDE TO
UGHT CODES AR_/_
STA PJS
TH_NO
FOLLOWS:
CHECK
ECONOMIZER
2 STAGE
COOLING
W .........
OPERATION
G ..........
OFF
NO pOWER
OR
FAULT
1 BLINK
IGNITION
FAILURE
OR
OPEN ROLLOIJT
SWITCH
or
OPEN AUX LIMIT
SWITCH
Cp_< INFUI I_0_
G"_<
FL_E _ (30NT_qCL
RE_LA_E CONIRCL
2 BLINKS
pRESSURE
SWrlCH
OPEN
CHECK
pIqESSU RE SWITCH
3 BLINKS
PRESSURE SWtTO_ C_(3S_
I_ON
CHECK
pIqESSU RE SWITCH
4 BLINKS
OPEN
LIMIT SWITCH
5 BLINKS
FALSE FLAME SENSED
6 BLINKS
COMPRESSOR
OU]pLrl
DELAy
o
GAS FLOW
GAS PRESSURE
GAS VALVE
FLAME SENSOR
FLAME ROLLOUT
BAD SWITCH
AUX LIMrl OPEN
PU
y
BL
TH_WITH
.........
..........
.........
(_
@
(_
ECONOMIZER OPTION
MAIN UMIT OPEN
BA D SWITCH
SlICinG
PU
........
W .........
G_S VALME
3 MIN COMP
ANTI_;yCLE
TIMER
BL .........
B4312004 Rev A
Wiring is subjectto change. Always refer to the wiringdiagram on the unitfor the most up-to.late wiring.
24
GPG13(60)1A
WIRING
DIAGRAM
HIGH VOLTAGE!
WARNING
DISCONNECT
ALLPOWER
BEFORE
SERVICING
ORINSTALLING
THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY
DAMAGE, PERSONAL
INJURY OR DEATH.
Y
R
.'P:
GRD
BL
BL
BL
B
Y
1
CH OPTIONAL
CONNEC
--
B--
I
I_D AT LI. L_
NOI_ 4
I
__
CH (_'_TIONAL
i
petER
SUPPLY
BR
@
C
2_
240
nn_d_ls
TOTI_
tSE_RaD_'q_
BL
R
G
Y
W
PU
PU
Y
Y
Y
NOI_
5
PU
/
WWR
(ALT)
IIC
HO N Lc_P_'ELL
GAS VALVE
ii i
BL
PU
o
CAP1
BR
Y
B4312005 R_. A
Wiring is subjectto change. Always refer to the wiringdiagramon the unitfor the most up-to.late wiring.
25
GPG13(60)1A
WARNING
I
WIRING
DISCONNECTALLPOWERBEFORESERVICINGORINSTALLINGTHIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
_
HIGH VOLTAGE!
DO SO MAY CAUSE PROPERTY
L1
DIAGRAM
DAMAGE, PERSONAL
SUPPLy VOLTAGE
208_3011/60
INJURY OR DE
COMPONENT LEGEND
A[S AUXILLA}_ UMIT SWITCH
CH
NOTE
4
o
O
MARleD TERMINAL
COMp COMPRESSOR
©
UNMAPJ_ED I_RMINAL
CM
CONDENSER MOTOR
CC
CH
CONTACTOR
CRANKCASE HEA I_R
GV GAS VALVE
IIC INI_GRATED
NOTE0
NOTE
IGN
2
I
I
FS
WIRE SPLICE
CAP CAPACITOR
WIRING
FS FLAME SE]dSOR
FS @
ATH._I
IGNmO
m
LINE VOLTAGE
.......
LOW VOLTAGE
FIELD INSTALLE_ POWER
FIELD INSTALL_
N CONIROL
IGNITOR
CONTROL
WIRE CCOE
LS LIMITSWITCH
B
PL PLUG
BL BLUE
PS PRESSURESWITCH
BR
RS ROLLOUTSWlTCH
G
GREFN
SOL SOLENOID (2 STAG[d}
O
OPJ_NGE
T8
PK PINK
TERMINAL BLOCK
BLACK
BROWN
?tic I]4EI_MIOSTATHEAT&COOL
PRANS q_ANSFORMER
PU pURPLE
R RED
VM VENT MOTOR
W
WHITE
VSM VAR
y
Y_LLOW
SPEEDMOTOR
VSTB VARIAB[E SPEED TB_M BLOCK
I
NOTES
1 REPLACEMENT
WIRE
INSULATION
AS ORIGINAL
2 FOR
2Og VOLT
FROM
3
MUST
BE ?tiE
(USE
I_ANS_ORMER
TERMINAl@TO
SAME
COppER
OPERATION
TERMINAl@ON
SIZE AND
TYpE
O_NDUCTOR
MOVE
OF
ONLy)
8LACK
WIRE
]RANSFO_MER
NOME MODELS
HAVE VENT MOTORS
EQUIppED
_
A 230V LEAD (RED)
AND A _08V LEAD {BLACK)
IF EQIJIpF_D,
OONNE_T
V[_q
MOTOR BLACK
LEAD IN PLACE OF RED LEAD AT Ull (D1) FOR 208V OPERATION
4 CRANKCASE HEATER (OPTIONAL)
5 ACCESSORY ECONOMIZBR PLUG (ON S[_ECI _DI
I_) ADJACENT
TO BLOWER HOUSING IN NEf UI_I AIR _O Mp._NMENT
1B
6 TWO STAGE
ITIERMOSTAT
OPTION
INST_D
CONNECTIONS
IF USED WITH
EC_ZBR
208_3_1_0
INSTALLER/SERVICEMAN
I]4E STAI_S UGHT ON *q_E _
I]_D_JD[FSHCOTING
ITIIS API_IANCE
STA]US
LIGHT
ON
OFF
_
STATt._
E(_JIp
NORMAL
MAY BE _
AS AGUI[3E
LIGHT CO[3FS ARE AS Rll
THC-FIELDWIRING
TO
OIA_:
SI A]US
TH_NO
CHECK
ECONOMIZER
3 BU_KS
W ..........
W ..........
NO pOWEROR
O4BCKINPUT
R)t_
R
2 BU_KS
ECONOMIZFR
OPERATICN
FAULT
1 BLINK
THC-W_TH
IGN113ON FAILURE
OR
OPEN ROLl OrS1
SWITCH
OR
OPEN AUX LIMIT
SWITCH
GAS PLOW
PRESSURE
G/_ VALVE
FLAME SENSOR
FLAME ROLLOUT
BAD SWITCH
AL_ LIMIT Op_
pRESSURE
SWITCH
OPEN
CHECK
pRES_RE
SWITCH
PRESSURE SIhl_:H (3L(3_13)
_M]_3UI
INBUCD_ON
4 BU_KS
OPEN LIMIT SWITCH
5 BLI N_S
FALSE FRAME SENSE[}
5 BUi'_KS
COMPRESSOR
OU]PUT DELAy
..........
IN
R
I
_.
•......
I:IB_L_:ECQNIR(1
_
CHECK
pRES_RE
SWITCH
FROM
TERMINAL
BLOCK
FROM
BE
..........
_N
J
........
D
ECON
PLUG
MAIN UMIT OPEN
BAD SWITCH
S1]CI_NG G_
VhL'_
3 MINt COMp
ANTH3y(:&E
TIMER
B4312005 Rev. A
Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to4ate wiring.
26
GPG13(36)3A
WIRING
DIAGRAM
HIGH VOLTAGE!
WARNING
DISCONNECT
ALLPOWER
BEFORE
SERVICING
ORINSTALLING
THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
)
)
8L
BL
_
8L
BL _°_
5k
Yk
cH OPTIONAL
CN OPTIONAL
CONNECTED AT L1, L2
NOTE 3
'
I
t
BK
SEE NOTE 3
POWER SUPPLY
208 230/3t60
SEE NOTE 6
BR
208
TR
//_
_
NOTE 2
24V
BL
NOTE 4
2411
RD
SPEED
2TOR
RD
PU
BL
BK
[D
B
E
BR
ECON
I
PU
C=9
W R
GAS VALVE
(ALT) HONEYWELL
GAS VALVE
FS
lie
PU
BL
Y2YICRYWG
I
I
°t=_RD
)
II I I
TO _ERMOSTAT
_=_BK
F
_BL
tt
NOTE 94t
RD
FC
Pu
PU
RD
PU
BR
Wiring is subjectto change. Always refer to the wiringdiagramon the unitfor the most up-to.late wiring.
27
GPG13(36)3A
WARNING
WIRING
UNIT.
MULTIPLE POWER
Ii
DISCONNECT
HIGH VOLTAGE{ALL POWER
DO SO MAY CAUSE
SUPPLy VOLTAGE
L2
SOURCES
MAY
BE PRESENT.
FAILURE THIS
TO
BEFORE
SERVICING
OR INSTALLING
ATH
._I
PROPERTY
DAMAGE,
PERSONAL
INJURY OR DE
L3
CH
_/_v
_
COMp
COMPRESSOR
I
CM
CONDENSER
C
CONTACTOR
CH
CRANKCASE
EM
EVAPORATOR
FC
IGN
FS _
_
C
NOTE2
F
AU)0LLARY LIMIT SWITCH
°
_
_)
FACTORY WIRING
ALS
T3
T2
c_
LEGEND
COMPONENT
208 230/'3/60
NOTE3
DIAGRAM
MOTOR
VOLTAGE
VOLTAGE
_)F_llON AL HIGH VOLTAGE
HEATER
FIELD WIRING
MOTOR
HIGH VOLTAGE
F
FUSE
FC
FAN CAPACITOR
LOW
VOLTAGE
FS
FLAME SENSOR
WIRE CODE
GND
EQUIPMENT GROUND
BK BLACK
GV
GAS VALVE
BL BLUE
IIC
IGN
INTEGRATE D IGNI]ION CONIROL
IGNrl OR
BR BROWN
GR GREEN
LS
LIMIT SWITCH
or
ORANGE
PLF
FEMALE PLUG/CONNECTOR
PK
PINK
PS
pRFSSURE SWITCH
PU
PURPLE
RS
ROLLOUT SWITCH
RO
RED
TR
TRANSFORMER
WH
WHILE
VM
VENT MOTOR
YL yELlOW
FS
NOTES
1 REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYpE OF
INSULAllON
ALS
AS ORIGINAL {USE COPPER CONDUCTOR ONLY)
2 FOR 208 VOLT TRANSFORME3R OPERATION MOVE BLACK WIRE
RS
FROM TERMINAL
3 TO T_INAL
2 ON TRANSF(]_IER
3 CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS
4 FOR DIFFERENTTHAN
FACTORY SPEED TAP CHANGE COOLING
SPEED AT COOL TERMINAL (IIC)_ CHANGE HEATING SPEED AT HEAT
TERMINAL (IIC)
3 SPEED MOTOR
BK
HIGH SPEED
BL
MEDIUM SPEED
RD
LOW SPEED
5 ACCESSORY ECONOMIZER
PLUG (ON SELECT MOD_S)
ADJACENT
TO BLOWER HOUSING IN RETURN AIR COMPARMENT
6 USECOOPERCONDUCTORS
_
ONLY
USE NECCLASS2WIRE
208 23013/60
THERMOSTAT FIELD WIRING
INSTALLER/SERVICEMAN
THE STA I_S UGHT ON THE FURJ_CE CGNIROL MAy BE US_ P_ A GU_E TO
1ROIJt_ E_DOTING ITIIS APPLIhNCE STAIUS UGWI CODES ARE _ FOU OWS:
STATUS
LIGHT
EQUIP
STATUS
NOI_IAL
OFF
NO POWER OR
INTERNAL CON 13_OL
OP_ATION
FAULT
FAILURE
OR
GPEN ROLLOUT
LIMIT
At_
pRESSURE
SWITCH
OPEN
pRES_IJRE S_ITOt
WI MOUT
INDUCER
6 BLINKS
FALSE FLAME
GR
RD
RD
YL
PU
BL
YL
DEtAy
BL
®
WITHECONC_ZEROPTION
LIMIT OpEN
CHECK
pRESSURE
SW]TCH
CLOSED
ON
SENSED
COMPRESSOR
OUTPUT
GR
FLAME SENSOR
FLAME ROLl OUT
BAD SWITCH
4 BLINKS
5 BLINKS
FOYER
GAS FLOW
GAS pRESSURE
GAS VALVE
SW1TCH
3 BLINKS
CIEOKINI_fl
REFq_CE
IGNITION
SW]TCH
OR
OPEN AUX
2 BLINKS
2 STAGEC00L_G
CHECK
ON
1 BUNK
N0 ECONOWER
_
CHECK
pRESSURE
SW]TCH
GR
MAIN LIMIT OP_
BAD SWITCH
RD
S I]O(ING
3 MIN
GAS VALVE
PU
COMp
ANTFCYCLE
BL
I]M_
0140G00085P
Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to.late wiring.
28
GPG13(48,60)3A
I1,_
WARNIN G
WIRING DIAGRAM
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
HIGH VOLTAGE!
ATH._
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE
YL
RD
BK
Pu
RD
BK
BL
BL
'_KBK
CHOPTIONAL
CONNECIED
ATL1.L2
BL
BL
YL YL RD
L G
8L
N
8L
RD
BL
EM
NOIE
4
YL
r=
I
I ll_
NOTE 5
YL
i
SEE
NO1E7
IIC
pu
8L
Y2Y1CRYWG
BL
TO _ ERMC_TAT
RD
WH
BR
Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to.late wiring.
29
GPG13(48,60)3A
I1,
L1
WARNIN G
SUpPLy
VOLTAGE
WIRING
DIAGRAM
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
HIGH VOLTAGE!
ATH._
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE
L2
L3
COMPONENT LEGE]_D
FACTORY WIRING
208 230/3/60
CH
)
_
NOTE
3
T2
c T1 -f--_
C
%
I1_
FC
VMR
)
SEF NOIE2
i
z
FNOTE
7
TR
O
IGN FS
©
@
ALS
AL_ILLARy UMrr SWITCH
_
COMP
CM
COMPRESSOR
CONDENSER MOTOR
_
C
CONTACTOR
CH
CRANKCASE HEATER
EM
EVAPOP,ATOR MOTOR
F
PC
FUSE
FAN CA pACITOR
FS
FLAME SENSOR
VOLTAGE
_0P:rlONAL HIGH VOLTAGE
RELD WIRING
HIGH VOLTA(t
_<_N VOLTAGE
GND
EQUII_/_NT GROUND
WIRE CODE
GV
GAS VALVE
BK BLACK
IIC
IN1EGRATED IGNINON CONTROL
BL BLUE
IGN
IGFITOR
BR BROWN
LS
LNIT SWITCH
GR GREEN
PLF
FEMAI E PLUG/CONNECTOR
OR ORANGE
PS
PRESSURES'WITCH
PK
RNK
rs
ROLLOUT SWITCH
PU
PURPLE
I_
TRANS_ORM_
RD RED
VM
VMR
VENT MOTOR
VENT MOTOR RELAy
WH WHrlE
YL yELlOW
N°TE
IIC
VOLTAGE
NOTFS
1 REPLACEMENT WIRE MUST lIE THE SAME SIZ_/_ND WpE OF
INSU[ATIGN AS ORIGINAL(USE
2 F_
VMR
208 VOLT IN_ISFOR_R
FROMIERMIN,_k
COPpB_ O3NDUCT_
Op[2_TION
3 TO I_I_L
ONLY)
MOVE BlinK
'_RE
2 ON PNr_ISF_I_
3 CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS
4 FGR DIFP B_BqT THAN FACI CRy SPEB) TAP CHANGE CCOUNG
SPEED AT MOT(3R T4 AND T5 TEPJ_INALS CHANGE HEATING
SPEED AT MOT(3R T1, T2 AND 13 I_RM I_A LS
COOLING SPED
T4 LOWSPEED
T5
NOTE
5
(YELLOW WIRE)
HIGH SPEE])
12
MED SPED
13
HIGH SPEFD
5 ACCESSORY ECONOMIZER PLUG (ON SELFCI MODELS) ADJACENT
TO BLOWER HOUSING iN RETURN AI_ COMPARMENT
PLF
6 USE COOPER CONDUCTORS ONLy
_ _
USE NEC CL_
2 WIRE
7 L1 AND L2 ON ICC eONTR_
TOTHE_TAT
HEATING SPEE]) (WHITE WIRE)
T1 LOWSPEE_
IS 24V INPIXI
_
2_6 230/3/60
THERMOSTAT
INSTALLER/SERVICEMAN
THE S TATOSLIGHT _N ]HE FURNACE CO@]R(3_MAYBE L_
AS A GUIDE TO
TROUB[FSHOO 13NG]H IS _PPLIANCE STATtJS LIGffl COOES _F _S FOLLOWS:
STATUS
LIGHT
_N
OFF
EC_JIP
NORMAL
STATUS
FIELD
WIRING
_
2 STA_EC0(]LIk_
CHECK
OPERATION
NO pOWER
OR
O4E(_INPUI
GR
I_M[_
ar
_._
RD
FAULT
1 BLINK
IGNrl
ION FAILU R_
C_
OPEN ROLLO UT
SWITCH
(3PEN
OR
AUX LIMIT
SWITCH
2 BLINKS
3 BLINKS
4 BLINKS
5 BLINKS
6 BLINKS
pRFSSURE
LIMIT SWITCH
F*_LSE FLAME
SENS_
COMpREsSOR
C_JTPUT
DELAY
CONtrOL
YL
GAS FLOW
GAS pRESSURE
GAS VALVE
FLAME SENSOR
FI_,M E ROLLO_JT
WffHECO_IZER _PTION
AUX
SWITCH
OPEN
pRFS_ JRE _*_*ITCH CLO_EO
WITHOUT
INDUCER ON
OPEN
R_ RAC_
LIMIT OPEN
CP_CK
pRESSURE
SWITCH
CF_CK
pRESSURE
SWITCH
GR
RB
MAIN LIMIT OPEN
BAD SWrl C_
SlICiNG
PU
GAS VALVE
3MIN
ANTI_,yCLE
COMp
BL
TIM_
0140G00087
Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to.late wiring.
3O
GPG13(36)4A
I1,
WARNIN G
WIRING
DIAGRAM
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
HIGH VOLTAGE!
ATH._
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE
,°
)
PB_
)
GND
BL
CN OPTIONAL
C_NECl_D AT LI, L2
NOTE 2
BR
MMR
BE
C
TR
IBR
BL
BL
BK
1
IL
PU
NOTE 4
PLF
YL
PU
GASVALVE
PU
GASVALVE
PU
BL
YI C R YW
G
BL
I
I
I
I
I
I
I
TD 1}IE
F_OS%AT
±±
FC
RD
BK
BR
Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to.late wiring.
31
GPG13(36)4A
I1,
L1
WARNIN G
WIRING
DIAGRAM
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
HIGH VOLTAGE!
ATH._
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE
k2
SUPPLYVOLTAGE
L3
COMFONENI
IF
NOTE 5
LEGE]_D
FACTORY WIRING
ALS
AL_(ILLARy LIMIT SWITC H
_
COMp
COMPRESSOR
_
CM
CONDENSER
C
CH
CONTACTOR
CRANKCASE HEATEr
EM
EVAPORATOR MOTOR
MOTOR
VOLTAGE
VOLTAGE
_:_P-TIONAL HIGH VOLTAGE
FIELD WIRING
HIGH VOLTAGE
tOW VOLTAGE
F
FUSE
FC
FAN CAPACITOR
FS
FLAME SE_ISOR
WIRE CODE
GND
EQUIPMENT GROUND
8K BLACK
GV
GAS VALVE
BL BLUE
IBR
INDOOR BLOWER RELAY
8R
BROWN
IIC
INTEGRATED IGNI nON CONTROL
GR
GREEN
IGN
IGNITOR
OR
ORANGE
LS
LIMIT SWITCIt
PK PINK
PLF
FEMALE PLUG/CONNECTOR
PU
PS
RS
prESSURE SWITCH
ROLLOUT SWITCH
RD RED
WH WHITE
TR
TRANSFORMER
VM
VENT MOTOr
VMR
VENT MOTOr
PURPLE
YL YELLOW
REI Ay
NOTES
1 REPLACEMENT WIRE MUST BE THE SAME SIZE AND ]YPE OF
INSULATION AS ORIGINAL (USE COPPER CONDUCTOR ONLY)
2 CRANKCASE HEALER NOT SUPPLIED ON ALL UNITS
3 460V UNITS ARE SINGLE SPEED, TO CHANGE FROM HIGH TO LOW
SPEED REPLACE TH[ BLACK MOTOR LE._
AT IBR#3 WITH RED
LEAD FROM MOTOR
2 SPEED MOTOR
BL
P_/YL
HIGH SpEFD
LOW SPEED
4 ACCESSORy ECONOMI_R
PLUG (ON S E'LECT MODELS) ADJACENT
TO BLOWER HOUSING IN RETURN AIR COMpARMENT
5 L1 AND L2 ON IIC CONTROL IS 24V INPUT
6 USE COOPER CONDUCTORS
_
ONLY
USE NECCL,_SS2WIRE
±±
460/3/60
THERMOSTAT
INSTALLER/SERVICEMAN
]HE STATUS LIGHTON ]HE FURNAC_ CON I_OL MAy BE IJ_ED AS A GUIDETO
]ROIJ BLFSHOOTING THIS APPLIANCE STAI_S LIGHT CODESARE AS FOLLOWS:
STA]IJS
LIGHT
EQUIP
STA]HS
CN
NORMAL
OFF
NO pOWER OR
INT_NAL
CON I_OL
FAULT
1 BLINK
OPERA
FAILURE
OR
(3PEN I_O LLOUT
SWITCH
OR
OPEN AUX LIMIT
SWITCH
2 BUNKS
3 BUNKS
4 BLINKS
5 BUNKS
6 BLINKS
PRES_URE
SWITCH
OPEN
R_3SSURE SWlT(:H (:LOS_)
WITHOUT
li'JOUCEr ON
OPEN
FAL_
LIMITSWITCH
FLAME
SENSED
COMPRESSOR
OUTPUT
DELAY
_
NOECON(]MI_
ff
2 ST_,GECOOUNG
6R
Gr
RD
RD
YL
Pu
Yu
CHECK
13ON
IGNITION
FIELD WIRING
(3HEO_INFUI
pOM3_
QB}G_J_
REPLACE CC_N]ROL
GAS FLOW
GAS pRESSUrE
GAS VALVE
FLAME SENSOR
BL
_L
FLAME RCLLO UT
BADSWITCH
AUX LIMIT OPEN
_;
_c)
WflH ECON{_IIZER (]PTION
CHECK
PRESSURE
SWITCH
CHECK
PRESSURE
SW113CH
GR
MAIN LIMIT OPEN
BAD SWITCH
RD
S I]C_ NG G_6 VALVE
FU
3 MIN
COMp
BL
AI_I I CYCLE TIM_
0140G00088
Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to.late wiring.
32
GPG13(48,60)4A
Ij,
WARNIN G
WIRING DIAGRAM
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
HIGH VOLTAGE!
ATH._
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE
YL
RD
BK
BK
GND
BL
YL
CH OPTIONAL
CONNECTED
AT L1, L2
NOTE 2
CH OPTIONAL
--
BR
POWER
SUPPLY
460/3/60
SEE NOTE
T_R
J
c
48O
_IE NOTE 7
5
TR
I E3
BL
RD
RD
RD
BL
=
i
YL
PU
YL
Pu
IIC
PU
PU
BL
Y2YICRYWG
IIIIII
BL
TO THERMOSTAT
RD
RD
OR
RD
FC
PO
BL
YL
WH
BR
BR
Wiring is subjectto change. Always refer to the wiringdiagram on the unitfor the most up-to.late wiring.
33
YL YL
RD
GPG13(48,60)4A
I WARNIN
L1
WIRING
P_
_'_ II UNIT.
MULTIPLE POWER
MAY BE PRESENT.
FAILURE TO "_
;IIsGH°vN°NELTcAGELL
P°wERSOURCES
BEF°RESERVICING
°RINSTALLINGTHIS
I
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
SUpPLy VOLTAGE
460/3/60
L2
L3
COMPONENT LEGE_iD
CH
_
c
NOTE
2
T2
T1 A_
C
_
I_
FC
_
VM r
SEE NOTE
z
FNOTE
6
l
•
TR
(_
IGN FS
@
Q
DIAGRAM
IIC
FACTORY WIRING
ALS
AUXILLARY LIMIT SWITCH
_
COMp
COMPRESSOr
_
CM
CONI]E NSE3RMOTOR
C
CH
CONTACTOR
CRANKCASE HE_IER
E_I
EVAPORATOR MOTOR
F
FUSE
FC
FS
FAN CAPACITOR
FLAME SENSOR
GND
EQUII_VENT GROUN D
GV
GAS VALVE
VOLTAGE
VOLTAGE
_OPTIONAL HIGH VOLTAGE
FIELD WIRING
HIGH VOLTAGE
_(_/VOLTAGE
WIRF CODE
BK BLACK
IIC
IN I_GRA I_D IGNITION CONTROL
BL BLUE
IGN
IGNITOR
Br
LS
PLF
LNIT SWITCH
FEMALE pLUG/CONNECTOR
GR GREEN
OR ORANCE
PS
PRFSSUrE SWITCH
PR
PINK
RS
ROLLOUT SWITCH
PU
PURPLE
TR
TRANSFORMER
RD RED
VM
VENT MOTOR
WH WHITE
VMR
VENT MOTOR RELAy
BROWN
YL YELLOW
NOTFS
FS©
_
0@_NOTE
°,O I
1 REPL&CE3_ENT WIRE MUST BE ME SAME SIZ_ AND _tPE OF
@
INSULATION AS ORIGINAL (USE COppER CONDUCTOR ONLy)
2 CRANKCASE HEALER NOT SUPPLIED GN ALL UNITS
O_
VMR
3 FOR DIFP ERE]qT THAN FACTORY SPEED TAP CHANGE COOLING
SPED
AT MOTOr T4 AND T5 _RMINALS
CHANGE HEATNNG
SPE DAT MOTOr T1, T2 AN D T3 1ERMffqALS
CO(lING
T4
15
®1
SPEED (YELLOW WtRE)
LOWSpEE])
HIGHSpEFD
HEATING SPEFD (wHrl E WIRE)
T1
12
LOWSpEE])
MEDSPED
T3
HIGH SPEFD
4 ACCESSORy ECONOMIZER PLUG (ON SELECT MODELS) ADJACD_iT
TO BLOWER HOUSING IN RETURN AIR COMpAPJ_3qT
5 USE COOPER CONDUCTORS ONLy
NOTE
4
6 L1 AND L2 ON ICC CON IROL IS 24V INPU,
PLF
7 STEPDOWN TRANSFORMEr
460V PRIMARY INPUT &240V SECONDARy OUTPUT
TO THERMOSTAT
_ _
_
_)
USE NEC CLASS 2 WIRE
4(WN_60
THERMOSTAT FIELD WIRING
INSTALLER/SERVICEMAN
_
ITIE STATUS UGHT ONTHE FURNACE C(3N]ROL MAy BE USEDAS A GUIDE TO
NOEC(_O_IZER
TROUBLESHCO]]NG THIS APPLIANCE _IATL_ UGFrl CODES AREAS FC_-LOWS:
STATUS
LIGHT
ON
OFF
EQ_JIp
NORMAL
STATUS
NO pOWER
cr
3 BLINKS
FAILURE
OR
OPEN ROLLOUT
SWITCH
Cf_
4 BLINKS
5 BLINKS
6 BLINKS
pRESSURE
L_IIT
SW1TCH
OPEN
PI_t3SSL_E S_ITCH CL_
WITHOUT
INDUCER ON
OPEN
FALSE
LIMIT SWITCH
FLAME
SENSED
COMp RESSC_
C_ITPUT
CHECKINPUI
GR
FOWI_
O_]XFL_OqG_IRI
RFpLAC_ _
IGNITION
(3PEN AUX
SWITCH
2 BLINKS
W
CHECK
OPERATION
FAULT
1 BUNK
2 STAGE
C00L_'_
D ELAy
RD
YL
GAS FLOW
GAS pRESSURE
GAS VALVE
FLP_E SENSOR
FLAME ROLL_JT
BL
BAD SW1TCH
AUX LIMIT OpEN
YL
_
BL
_C)
_,_HECONOI_,_R
OP lION
CHECK
pRESSURE
SW1TCH
CHECK
pRESSURE
SW1TCH
GR
MAIN LIMIT OPEN
BAD SW1TCH
S]]Q(ING
RD
PU
GA_ V_LVE
3 MIN COMp
AN11 CYCLE
BL
0140G00089
TIME R
Wiring is subjectto change. Always refer to the wiringdiagramon the unitfor the most up-to.late wiring.
34
GPG13(48,60)1B
WIRING
DIAGRAM
DISCONNECT
ALL POWER
BEFORE
SERVICING
OR INSTALLING
THIS
UNIT.
MULTIPLE
POWER
SOURCES
MAY BE PRESENT.
FAILURE
TO
HIGH VOLTAGE!
I_
DO SO MAY CAUSE
PROPERTY
DAMAGE,
PERSONAL
INJURY OR DEATH.
YL
RD
RD
BK
PU
BK
GND
BL
YL
BK
_'
B_ 8KSK
BK
CH OPTIONAL
POWER
BK
SUPPLY
208 23(Y_/60
SEE NOTE 6
PU
PJ
YL YL RD YL
BL BL BL
RD
YL
I llli!
_PU
YL
YL
NOTE 5
PLF
PU
GR Y
YL
W
R
GAS VALVE
_e_]
e _ ] SEE
NOTE 7
(ALT) HONEYWELL
GAS
VALVE
IIC
PJ
L
BL
YIC
RYW
BL
TOTHERMOSTAT
RD
RD
OR
RCCF
PU
BL
YL
BR
BR
LI
SUPPLYVOLTAGE
L2
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to.late
35
wiring.
GPG13(48,60)1B
WARNING
SUPPLY
DIAGRAM
uD_ISTC.CNuNETCTLAELL;_/E_RERoBEFOFRs
E SERVBICINGE{_R/N.ST_LL/NR_TT_S
I HIGH VOLTAGE!
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
['_
L1
WIRING
VOLTAGE
COMPONENT
LEGEND
FACTORY
WIRING
20_230/I/60
CH
NOTE
3
T2
C
ALS
AUXILIARY
LIMIT SWrl CH
CC_p
COMPRESSOR
CM
CONDENSER
C
CONTACTOR
CH
CRANKCASE
EM
EVAPORATOR
F
FUSE
FS
FLAME
GND
EQUIPMENT
GV
GAS VALVE
IIC
INTEGI_I_D
IGN
_MOLT_E
_
VOLTAGE
MOTOR
_'_10
NAL HIGH
VCtTAG
E
HEATER
MOTOR
FIELD WIRING
HIgH
SE_OR
_k_
VOLTAGE
VOLTAGE
C4tOUND
WIRE CODE
IGNITIONC(_ITRI_
BK
BLACK
IGNITOR
BL
BLUE
LS
LIMIT SWITCH
BR
13ROWN
pkF
FEMALE
GR
GREEN
pS
PRESSURE
SWIII2H
OR
ORANGE
R_F
RUN
TO R FO R COM PRESSOR/'P,%N
pK
pINK
RS
RC_kOUT
PU
pURPLE
TR
TRANSFORMER
RB
RED
VM
VENT
MOTOR
WH
WHITE
VMR
VENT
MOTOR
VMR
NOTE
2
[R
©
I
,G.
.o
PLUG/CONNECTOR
CAPACI
SWI I_H
_1_¥
_FL
yEUC_
NOI_S
1 REPlaCEMENT
INSUlaTION
2
WIRE MUST
I_RMINAL
3
CRANKCASE
4
FOR DIFFERENT
3
SPEED
AT MOTOR
SPEED
AT MOTOR
COOLING
SPEED
2
FACTORY
MOVE
TI,
T2 AND
I_pE
OF
ONLY)
BLACK
WIRE
ON ALL UNITS
SPEED
TAP
T4 AND T5 TERMINALS
(yELLOW
_,ND
ON TttANSF_ER
NOT SUPPLIEO
THAN
SI_
CONDUCTOR
OPENATION
TO T_,tlNAL
HEATER
SAME
COppER
FOR 20B VOLT _I,ISFORMER
FROM
CHANGE
CO_ING
CHANGE
HEATING
13 •EI_IINAkS
W1RE)
HEATING
SPEED
T4
LOWSPEED
TI
LOWSPEED
T5
HIGHSPEED
T2
MEO
13
HIGH
5 ACCESSORY
ECONOMIZER
TO BLOWER
N(_E
BE THE
AS ORIGINAk(USE
6 USE COOPER
HOUSING
PLUG (ON SELECT
MODE/S)
IN RE I]JRN AIR COMPARM
CONDUCTORS
0NHIrE
WIRE)
SPEED
SPEED
AD JACI3_IT
ENT
ONLy
• _ USE.ECCLASS2WIRE
•
L1 AND
k2 ON ICC CONI
LIGHT
ON
OFF
EQUIP
NOP_AL
STATUS
OR
IGNII3ON
F_,JLU RE
OR
OPEN ROLLOLrl
SWITCH
OPEN
OR
AUX UMIT
SWITCH
NOECON(]I/I_
ER
_ECI(INI_TI_O_3_
RI3°_C_
AL_
_qt _L_q_
S_IT(:t_I CLOS _
WI MOUT
INDUCI3_ ON
CHECK
pRESSURE
SW1TCH
6 BUNKS
FALSE
FLAME
SENSED
COMPRESSOR
OUTPUT
DELAy
IN
YL
_J
BL
YL
BL
tilTH
ECONO_EROPTIOI_
LIMIT OPEN
3 BUNKS
LIMIT SVClTCH
GR
_R;
FLAME RC_I OUT
BAD SWITCH
CHECK
pRESSURE
SW1TCH
5 BUNKS
2 STAGE COOUNG
CONIRG[
GAS FLOW
GAS pRESSURE
CAS VALVE
FLAME SENSOR
PRESSURE
SWITCH
OPEN
OPEN
FIELD WIRING
CHECK
2 BUNKS
4 BUNKS
INpIJI
O pERATICN
NO pOWER
FAULT
BLINK
IS 24V
THERMOSTAT
INSTALLER/SERVICEMAN
I_IE STATUS LIC-F_ONME FURNACECON_I_DLMAy BE U_D ASA GUIDE TO
]I_OUBLESP:OOTING]HIS APPLIANCE STA]US LIGHT CODES/_RE AS FOLI OWS:
STATUS
I_L
GR
MAIN LIMIT OPEN
BAD SWITCH
PU
S]]CKING C._ VhLVE
3 MIN
COMp
ANTFCYC[E
BL
TIMI3_
0140G00267
Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to.late wiring.
36
MINIMUM
CLEARANCES
48" MIN
12" MIN
12" MIN
36" MIN
(FOR SERVICE)
NOTE: Roof overhang should be no more than 36".
UNIT
Min. Filter Size
2 Ton
(1)20x20x1
2 1/2 Ton
3 Ton
(1)20x25x11(1)25x25x1
3 1/2-
(2)20x20x1
I
RECOMMENDED
FILTER
© 2005 - 2007 Goodman Manufacturing
37
4 Ton
SIZES
Company, L.E
5 Ton
(2)20x25x1
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 37 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Sun Jul 20 21:06:41 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools