GOODMAN Package Units(both Units Combined) Manual L0806747
CHIEF Power Screwdriver PACHFK1 L0806747
User Manual: GOODMAN GOODMAN Package Units(both units combined) Manual GOODMAN Package Units(both units combined) Owner's Manual, GOODMAN Package Units(both units combined) installation guides
Open the PDF directly: View PDF .
Page Count: 37
Download | |
Open PDF In Browser | View PDF |
INSTALLATION & OPERATING INSTRUCTIONS for GPG13 SINGLE PACKAGE GAS-ELECTRIC HEATING & COOLING UNIT Affix this manual and Users Information Manual adjacent to the unit. This Forced Air Central Unit Design Complies With Requirements Embodied in The American National Standard / National Standard of Canada Shown Below. ANSI Z21.47,CSA-2.3 Central Furnaces _ RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION. ATTENTION INSTALLING PERSONNEL Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During installation or repair, caution is to be observed. It is your responsibility to install the product safely and to educate the customer on its safe use. These installation instructions cover the outdoor installation of single package gas electric heating and cooling units. See the Product Data Book applicable to your model* for information regarding accessories. IO-288A 02/07 *NOTE: Please contact your distributor or our website for the applicable product data book referred to in this manual. Goodman Manufacturing Company, L.P. 2550 North Loop West, Suite 400, Houston, TX 77092 www.qoodmanmfq.com © 2005 - 2007 Goodman Manufacturing Company, L.P. INDEX Replacement Parts ............................................................................................................................................................. ORDERING PARTS .............................................................................................................................................. Safety Instructions ............................................................................................................................................................. Unit location ........................................................................................................................................................................ ALL INSTALLATIONS: GROUND LEVEL ROOFTOP ROOF ........................................................................................................................................... INSTALLATIONS INSTALLATIONS ONLY: CURB INSTALLATIONS ONLY: .................................................................................................................. ........................................................................................................................... ONLY: ....................................................................................................................... General Information ........................................................................................................................................................... 3 3 3 4 4 4 4 5 DAMAGE ................................................................................................................................... 5 6 Rigging Details ................................................................................................................................................................... Gas piping ........................................................................................................................................................................... 6 6 TRANSPORTATION HIGH ALTITUDE DERATE (U.S. INSTALLATIONS ONLY) ............................................................................................... PIPING ............................................................................................................................................................. GAS PIPING CHECKS .......................................................................................................................................... Propane Gas Installations .................................................................................................................................................. TANKS AND PIPING ............................................................................................................................................. Electrical Wiring ................................................................................................................................................................. THERMOSTAT LOCATION UNIT VOLTAGE ....................................................................................................................................... ................................................................................................................................................... HEAT ANTICIPATOR SETrlNG .................................................................................................................................. Circulating Air and Filters ................................................................................................................................................ AIRFLOW CONVERSION ...................................................................................................................................... 6 6 7 7 8 8 8 9 9 10 10 Duc_nNORK............................................................................................... 10 FILTERS .......................................................................................................................................................... Venting .............................................................................................................................................................................. FLUE HOOD INSTALLATION ................................................................................................................................... Drain .............................................................................................................................................................. CONDENSATE DRAINCONNECTION ........................................................................................................................ normal sequences of operation ....................................................................................................................................... HEA_NG .......................................................................................................................................................... COOLING......................................................................................................................................................... FAN ONLY ...................................................................................................................................................... Condensate Startup, Adjustments, and Checks .................................................................................................................................. HEA_HGSTARTEP............................................................................................................................................ COOLING STARTUP ........................................................................................................................................... Troubleshooting ................................................................................................................................................................ IGNITION CONTROL ERROR CODES ABNORMAL OPERATION ABNORMAL OPERATION- Maintenance CLEAN - HEATING .................................................................................................................... COOLING ................................................................................................................... ..................................................................................................................................................................... FILTER REPLACEMENT CABINET ...................................................................................................................... OR CLEANING FINISH MAINTENANCE OUTSIDE CONDENSER, FLAME SENSOR FLUE PASSAGES CLEANING COIL (QUALIFIED EVAPORATOR, (QUALIFIED (QUALIFIED FLUE PASSAGES .................................................................................................................... ........................................................................................................................... SERVICER ONLY) AND INDUCED DRAFT SERVICER SERVICER (QUALIFIED ONLY) ONLY) ............................................................................................. MOTORS ..................................................................................... ...................................................................................................... ..................................................................................................... SERVICER ONLY) ...................................................................................... MAIN BURNER FLAME (QUALIFIED SERVICER ONLY) .............................................................................................. CLEANING BURNERS ......................................................................................................................................... Accessories and Functional Parts ................................................................................................................................... SHEET METAL ACCESSORIES FUNCTIONAL GENERAL PARTS .............................................................................................................................. .......................................................................................................................................... INFORMATION ..................................................................................................................................... Ignition Control Diagnostic Indicator Chart .................................................................................................................... Heating Timing Chart ....................................................................................................................................................... Cooling Timing Chart ....................................................................................................................................................... APPENDIX ......................................................................................................................................................................... Wiring Diagrams .......................................................................................................................................................... Minimum Clearances ....................................................................................................................................................... Recommended Filter Sizes ............................................................................................................................................. 2 10 10 11 11 tl 11 tt tt 12 12 12 15 15 t5 15 16 t6 16 16 t7 t7 17 17 t7 t7 18 18 18 18 18 19 19 19 20 2t-36 37 37 REPLACEMENT PARTS AWARNING ORDERING PARTS THIS PRODUCT When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit's nameplate. MAY CAUSE STATE OF CONTAINS OR PRODUCES SERIOUS ILLNESS CALIFORNIA TO REPRODUCTIVE CAUSE CANCER, OR CHEMICALS WHICH BIRTH ARE KNOWN DEFECTS WHICH TO THE OR OTHER AWARNING HEATING SERVICE PARTS DEPARTMENT GOODMAN MANUFACTURING COMPANY, L.E 2550 NORTH LOOP WEST, SUITE 400 HOUSTON, TEXAS 77092 (713) 861 2500 UNIT INSPECTION, DEVICE SUCH DEVICE EVENT THAT AND INSTRUCTIONS SHOULD WILL IN THE BE DRAINED SHOULD to familiarize adhered to, to unit, air motor speed BE VACANT, INSPECTED, BUILDING BE VACANT, MAYBE ALL AND THAT WILL AS WELL TO BUILDING BE VACANT, AND, IN SUCH AND THE CASE, HYDRONIC BE DRAINED, WATER THE SOURCE TO COIL ALTERNATIVE IN THE TEMPERATURES MAY BE EXPOSED ANY AN_ THAT MONITORED. SHOULD AND IN WHICH BE TAKEN FREEZING PIPES ROUTINE, BUlLIDNG SHOULD MAINTAINED EXPOSED WINTERIZED, THE REASONABLE, IF THE CARE WATER-BEARING BE PROPERLY EVENT WITHOUT SUPERVISION. WILL IS ROUTINELY THE TEMPERATURES TO THE INSTALLER BE UTILIZED AND IS LOCATED SHOULD CLOSED. NOT MAINTENANCE SUCH BUILDING Before installing this unit, please read this manual yourself on the specific items which must be including maximum external static pressure temperature rise, minimum or maximum CFM and connections. AND HARM. Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact: SAFETY A CHEMICAL OR DEATH FREEZING UNITS HEAT SHOULD SOURCES BE UTILIZED. AWARNING TO THE OWNER TO AVOID THIS A warranty certificate is provided with the unit. Read the warranty carefully and note what is covered. Keep the warranty certificate in a safe place so you can find it when necessary. UNIT PROPERTY IF ANY QUALIFIED SERVICE ANY OF THE PART UNDER DAMAGE, PART HAS PERSONAL BEEN TECHNICIAN CONTROL UNDER INJURY TO INSPECT SYSTEM OR DEATH, WATER. THE AND ANY DO NOT IMMEDIATELY FURNACE GAS CALL AND CONTROL USE A TO REPLACE HAVING BEEN WATER. Keep this literature in a safe place for future reference. AWARNING IF THE INFORMATION FIRE IN THESE OR EXPLOSION INJURY Do OR LOSS NOT AWARNING INSTRUCTIONS MAY RESULT IS NOT FOLLOWED CAUSING PROPERTY EXACTLY, DAMAGE, A THIS PERSONAL OF LIFE. STORE USE MAY OR USE GASOLINE OR OTHER FLAMMABLE VAPORS LOW AND DIRTY LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER • DO NOT TRY • DO NOT TOUCH TO LIGHT IN YOUR • IMMEDIATELY PHONE ANY FOLLOW • IF YOU CANNOT SWITCH; DO NOT USE ANY FROM A NEIGHBOR'S BUILDING CALL YOUR THE GAS REACH GAS SUPPLIER SUPPLIER'S YOUR GAS NOT RESULT RETURN BE USED AS A "CONSTRUCTION OF CONSTRUCTION IN PREMATURE ON A NEW FAILURE AIR TERMPERATURES AND HEATER" STRUCTURE. OF THE UNIT EXPOSURE DUE TO DURING THIS THE TYPE TO CORROSIVE OR VERY ATMOSPHERES. DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT• MULTIPLE POW]ER SOURCES MA_P INSTRUCTIONS SUPPLIER, CALL BE PRESENT. FAILURE TO DO $O MAY CAUSE PROPERTY _f THE FIRE I DAMAGE, PERSONAL INJURY OR DEATH. DEPARTMENT INSTALLATION SERVICE AN D SERVICE AGENCY OR THE I MUST BE PERFORMED BY A QUALIFIED INSTALLER, GAS SUPPLIER AWARNING SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN :cSTc\OLV,;L,; E ERNAL TO THE FURNACE OEFORE INSTALLATION A Do NOT CONNECT BY GOODMAN PERSONAL CONDITIONS TO FOR USE WITH INJURY, REDUCED MAY RESULT DEVICE THAT THIS UNIT. SERIOUS UNIT PERFORMANCE FROM IS NOT THE USE OF SUCH I_WARNING AND PERFORMEDONLY WARNING OR USE ANY OF EXTREMELY &w.....o lll1111 .o.vo,,,oo ANY APPLIANCE ELECTRICAL MUST PHASES APPLIANCE WHAT TO DO IF YOU SMELL GAS: PHONE UNIT FINISHING DESIGN PROPERTY AND/OR OF THIS UNIT BY INDIVIDUALS SHOULD MEETING BE THE REQUIREMENTS OF AN "ENTRY LEVEL TECHNICIAN" AS SPECIFIED BY THE AIR CONDITIONING AND CERTIFIED REFRIGERA'I1ON INSTITUTE (ARI). ATTEMPTING INSTALL OR REPAIR THIS UNIT WITHOUT SUCH DAMAGE, HAZARDOUS NON-APPROVED REPAIR RESULT DEVICES. 3 IN PRODUCT DAMAGE, PERSONAL TO BACKGROUND INJURY OR DEATH. MAY To avoid possible illness or death of the building occupants, do NOT locate outside air intake device (economizer, manual fresh air intake, motorized fresh air intake) too close to an exhaust outlet, gas vent termination, or plumbing vent outlet. For specific distances required, consult local codes. Allow minimum clearances from the enclosure for fire protection, proper operation, and service access (see appendix). These clearances must be permanently maintained. The combustion air inlet and flue outlet hoods on the unit CARBON MONOXIDE POISONING must never be obstructed. If used, do not allow the economizer/manual fresh air damper/motorized fresh air damper to become blocked by snow or debris. In some climates or locations, it may be necessary to elevate the unit to avoid these problems. HAZARD Special WarningfurInstaila_on ofFurnaces or AirHandling Unitsin Enclosed AreassuchasGarages,UflityRoomsor Parking ,&.teas Carbonmono_depmdudng devices(suchasan automobile, space heater,gaswaterheater,etc.)should notbeoperated in enclosed areas suchasunventilated garages,ubltiy roomsorparkingareasbecauseof thedangerofcarbonmonoxide (CO)poisoning resulting fmrntheexhaust emissic_s. If a furnaceorairhandlerisinstalledinanenclosedareasuch asa garage,utilityroomor parking areaanda carbonmonoxide produdng deviceisoperated therein,theremustbeadequate, directoutside ven_lation. When the unit is heating, the temperature of the return air entering the unit must be between 50 ° F and 100° F. GROUND LEVEL INSTALLATIONS ONLY: When the unit is installed on the ground adjacent to the building, a level concrete (or equal) base is recommended. Prepare a base that is 3" larger than the package unit footprint and a minimum of 3" thick. The base should also be located where no runoff of water Thisventilation isnecassawtoavoidthedangerofCOpoisoning which canoccurifa carbonmonoxide producing devicecontinues tooperatein theenclosed area.Carbonmonoxideemissions can be (re)circulated throughout thestructure if 6_efurnaceorairhandlerisoperating in any mode. COcancausesedous illness including permanent braindamage ordeath. from higher ground can collect in the unit. B1025_216 UNIT LOCATION I_WARNING TO PREVENT INJURY WHEN POSSIBLE OR DEATH, INSTALLtNG EQUIPMENT DAMAGE, THE FOLLOWING BULLET THE UNIT. PROPERTY POINTS MUST DAMAGE, PERSONAL BE OBSERVED IMPORTANT NOTE: Remove wood shipping rails prior to installation of the unit. ALL INSTALLATIONS: For proper flame pattern within the heat exchanger and proper condensate drainage, the unit must be mounted level. The flue outlet hood must be at least 12 inches from any opening through which flue gases could enter a building, and at least three feet above any forced air inlet located within ten feet. The eoonomizer/manual fresh air intake/ motorized fresh air intake and combustion air inlet mounted on the unit are not affected by this restriction. Outside Slab Installation ROOFTOP INSTALLATIONS ONLY: To avoid possible property damage or personal injury, the roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structural engineer to determine the weight capabilities of the roof. To avoid possible corrosion of the heat exchanger, do not locate the unit in an area where the outdoor air (i.e. combustion air for the unit) will be frequently contaminated by compounds containing chlorine or fluorine. Common sources of such compounds include swimming pool chemicals and chlorine bleaches, paint stripper, adhesives, paints, varnishes, sealers, waxes (which are not yet dried) and solvents used during construction and remodeling. Various commercial and industrial processes may also be sources of chlorine/fluorine compounds. 4 RooRoplns_ll_ion The unit may be installed directly on wood floors or on Class A, Class B, or Class C roof covering material. To avoid possible personal injury, a safe, fiat surface for service personnel should be provided. ROOF CURB INSTALLATIONS Roof Curb Installation ONLY: Sufficient structural support must be determined prior to locating and mounting the curb and package unit. GENERAL Ductwork must be constructed using industry guidelines. The duct work must be placed into the roof curb before mounting the package unit. INFORMATION _WARNING Curb insulation, cant strips, flashing and general roofing material are furnished by the contractor. To PREVENT PROPERTY EXPLOSIONS, SMOKE, MONOXIDE, AND THIS UNIT DAMAGE, SOOT, MUST PERSONAL CONDENSATION, BE PROPERLY INJURY OR DEATH, DUE TO ELECTRIC SHOCK OR CARBON INSTALLED, REPAIRED, FIRE OPERATED, MAINTAINED. This unit is approved for outdoor installation ONLY. To assure that your unit operates safely and efficiently, it must be installed, operated, and maintained in accordance with these installation and operating instructions, all local building codes and ordinances, or in their absence, with the latest edition of the National Fuel Gas Code NFPA54/ANSI 7323.1 and National Standard of Canada CAN/CSA B14g Installation Codes. The heating and cooling capacities of the unit should be greater than or equal to the design heating and cooling loads of the area to be conditioned. The loads should be calculated by an approved method or in accordance with A.S.H.R.A.E. Guide or Manual J Load Calculations published by the Air Conditioning Contractors of America. Obtain from: American National Standards Institute 1430 Broadway New York, NY 10018 5 TRANSPORTATION DAMAGE GAS Check the carton upon arrival for external damage. If damage is found, a request for inspection by carrier agent should be made in writing immediately. IMPORTANT NOTE: This unit is factory set to operate on natural as at the altitudes shown on the rating plate. Carefully inspect the unit for damage including damage to the cabinetry. Any bolts or screws which may have loosened in transit must be re-tightened. In the event of damage, the receiver should: 1. Make notation on delivery receipt of any visible damage to shipment or container. 2. Notify carrier promptly and request an inspection. 3. In case of concealed damage, carder should be notified as soon as possible-preferably within 5 days. 4. File the claim with the following supporting documents: a. Original Bill of Lading, certified copy, or indemnity bond. b. Original paid freight bill or indemnity in lieu thereof. c. Original invoice or certified copy thereof, showing trade and other discounts or reductions. _,WARNING To AVOID USING THE KITS ]'O PREVENT POSITION LIFTING PROPERTY DURING AND B.DEQUATE ALL MOVING CABLE DAMAGE, RIGGING WHEN A CRANE MOVING SHOULD PLACE FOR REMAIN TO INJURY HIGHER FAILURE AND/OR INSTALLATIONS OR AND DAMAGE. ARE WHEN OBTAIN TO DO SO CAN EQUIPMENT ONLY DEATH ALTITUDES, EITHER AND RESULT HIGH INSTALL IN ALTITUDE NOT APPROVED FOR USE Min. Gas 5.0" W.C., Max. 10.0" W.C. Inlet Pressure [ Propane Min. 11.0" W.C._ Max. 13.0" W.C. InletGas PressureMust Not Exceedthe MaximumValueShownin Table Above. The minimum supply pressure should not vary from that shown in the table above because this could prevent the unit from having dependable ignition. In addition, gas input to the burners must not exceed the rated input shown on the rating plate. Overfiring of the unit could result in premature heat exchanger failure. DERATE (U.S. INSTALLATIONS ONLY) IMPORTANT NOTE: The gas/electric units naturally derate with altitude. Do not attempt to increase the tiring rate by changing orifices or increasing the manifold pressure. This can cause poor combustion and equipment failure. At all altitudes, the manifold pressure must be within 0.3 inches W.C. of that listed on the nameplate for the fuel used. At all altitudes and with either fuel, the air temperature rise must be within the range listed on the unit nameplate. Refer to the Installation Manual provided with the LP kit for conversion from natural gas to propane gas and for altitude adjustments. IN AN UPRIGHT FACILITATE THE UNITIN KIT(S). OPERATION U.S. HIGH ALTITUDE OPERATIONS. IS USED, CONVERSION PERSONAL OR AT I Natural WARNING THE UNIT ARE DAMAGE, ALONE The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. Conversion to LP gas is permitted with the use of the factory authorized conversion kit LPT-00A. DETAILS AND PROPER GAS IN CANADA. NOTE: When inspecting the unit for transportation damage, remove all packaging materials. Recycle or dispose of the packaging material according to local codes. _lk PROPER_rY PROPANE UNSATISFACTORY d. Copy of the inspection report issued by carrier representative at the time damage is reported to the carrier. The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage. RIGGING PIPING AN SLING. Important: If using bottom discharge with roof curb, ductwork should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in roof curb installation instructions. PIPING IMPORTANT NOTE: To avoid possible unsatisfactory operation or equipment damage due to under firing of equipment, do not undersize the natural/propane gas piping from the meter/tank to the unit. When sizing a trunk line, include all appliances on that line that could be operated simultaneously. The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. The gas line installation must comply with local codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1. Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual. Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end. Natural Gas Connection Natural in Cubic Gas Capacity Nominal Black Pipe Size (inches) Length of "ipe in Feet 10 1/2 132 3/4 278 1 520 20 30 92 73 190 152 350 285 730 590 1100 980 40 63 130 245 500 760 50 60 56 50 115 105 215 195 440 400 670 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure CFH = Rigging of Pipe Feet of Gas Per Hour (CFH) 1 1/4 1050 1 1/2 1600 50 PSIG or le_ssand Pressure Drop of 0 3" W C (Based on 0 60 Specific Gravity Gas) BTUH Furnace Input Heating Value of Gas (BTU/Cubic_Foot) 6 Referto the GAS PIPING Proper Piping Practice drawing for the general layout at the unit. The following rules apply: 1. Use black iron pipe and fittings for the supply piping. The use of a flex connector and/or copper piping is permitted as long as it is in agreement with local codes. 2. Use pipe joint compound on male threads only. Pipe joint compound must be resistant to the action of the fuel used. 3. Use ground joint unions. 4. Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long. 5. Use two pipe wrenches when making connection to the gas valve to keep it from turning. 6. Install a manual shut-off valve in a convenient location (within six feet of unit) between the meter and the unit. 7. Tighten all joints securely. 8. CHECKS A To PREVENT FOLLOWING PROPERTY • THE AND UNIT AND PLACING FIRE, EXCEED GAS UNIT THE GAS HEAT AND EXCHANGE DURING UNIT BE ISOLATED CLOSING TESTING EQUAL MUST ITS MANUAL OF THE MUST PRESSURE OF 1/2 SUPPLY THAN FLAME TESTED THE BEFORE OF EXPLOSION TO TEST FOR HIGHER OVERFIRING VALVE WHICH OR NEVER LEAKS. PRESSURE MAY MAY RESULT IN 1/2 BE DISCONNECTED TESTING OF THAT FROM SYSTEM AT PSIG (s.4sKPA). FROM SHUT-OFF GAS TO OR LESS FIRE, GAS FAILURE. ANY IN EXCESS BE LEAK DANGER FOR TESTING. CAUSE ITS SHUT-OFF SUPPLY MUST OF THE OR OPEN PRESSURES • THIS Rigid metallic pipe and fittings Semirigid metallic tubing and metallic fittings (Aluminum alloy tubing must not be used in exterior locations) Listed gas appliance connectors used in accordance with the terms of their listing that are completely in the same room as the equipment In the prior two methods above the connector or tubing must be protected from physical and thermal damage. Aluminum alloy tubing and connectors must be coated to protect against external corrosion when in contact with masonry, plaster or insulation or are subject to repeated wettings by liquids (water - not rain water, detergents or sewage) BECAUSE AND DUE TO REGARDING TESTING: PRESSURES VALVE INJURY BE PERFORMED CONNECTIONS USE A MATCH PREMATURE The unit must be connected to the building piping by one of the following methods: GAS SPECIFIED DAMAGE TEST PRESSURE ITS OR PERSONAL MUST IN OPERATION. NEVER • THIS DAMAGE INSTRUCTIONS CONNECTIONS CAUTION THE VALVE PIPING GAS SUPPLY DURING SYSTEM ANY SYSTEM BY PRESSURE AT TEST PRESSURES PSIG (3_e KPA). AWARNING To AVOID PROPERTY DAMAGE OR PERSONAL INJURY_ BE SURE THERE NO OPEN FLAME IN THE VICINITY DURING IS AIR BLEEDING. There will be air in the gas supply line after testing for leaks on a new installation. Therefore, the air must be bled from the line by loosening the ground joint union until pure gas is expelled. Tighten union and wait for five minutes until all gas has been dissipated in the air. Be certain there is no open flame in the vicinity during air bleeding procedure. The unit is placed in operation by closing the main electrical disconnect switch for the unit. PROPANE GAS INSTALLATIONS Iio MANUAL AWARNING VAL_ / HUT,OFF "0 AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEA'II"I DUE TO FIRE _DRIP IR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS DETECTING WARNING DEVICE• SINCE RUST CAN REDUCE THE LEVEL LEG //rl_ OF ODORANT IN PROPANE IS THE ONLY RELIABLE _ GROUND (INSTALl CONTACT JOINT UNION _ _AS AHEAD OF GAS VALVE) A LOCAL DETECTING GAS, A GAS DETECTING WAY TO DETECT PROPANE WARNING WARNING A PROPANE GAS SUPPLIER ABOUT DEVICE GAS LEAK. INSTALLING A DEVICE• IMPORTANT NOTE: Propane gas conversion kits must be installed to convert units to propane gas. All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters (See NBFU Manual 58). For satisfactory operation, propane gas supply pressure must be within 9.7 - 10.3 inches W.C. at the manifold with all gas appliances in operation. Maintaining proper gas pressure depends on three main factors: 1. Vaporization rate, which depends on (a) temperature of the liquid, and (b) wetted surface area of the container or containers. Proper Piping Practice NOTE: The unit gas supply entrance is factory sealed with plugs. Keep plugs in place until gas supply is ready to be installed. Once ready, replace the plugs with the supplied grommets and install gas supply line. 2. Proper pressure regulation. 3. Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe size required will depend on length of pipe run and total load of all appliances. 7 TANKS AND PIPING _WARNING Complete information regarding tank sizing for vaporization, recommended regulator settings and pipe sizing is available from most regulator manufacturers and propane gas suppliers. Since propane gas will quickly dissolve white lead or most standard commercial compounds, special pipe dope must be used. Shellac base compounds resistant to the actions of liquefied petroleum gases such as Gasolac ®, Stalactic ®, Clyde's ® or John Crane® are satisfactory. To PREVENT FIRE OR DETECTING IF THE • PROPANE SETTLE GAS IN ANY • PROPANE 5to15 FirstStage EXCEPT IS INSTALLED IS HEAVIER THAN AREAS A WARNING DEVICE LEAK, INJURY INSTALL IN AN EXCAVATED IS REQUIRED AIR AND OR CONFINED MAY FADE, DUE TO A GAS ANY DUE AREA OR A TO: LEAKING GAS CAN SPACES. MAKING THE GAS UNDETECTABLE DEVICE. ELECTRICAL THERMOSTAT Second Stage NOMINAL PIPE SIZE SCHEDULE 40 TUBING SIZE, O.D., TYPE L LOCATION Movement of air must not be obstructed by furniture, door, draperies, etc. The thermostat must not be mounted where it will be affected by drafts, hot or cold water pipes or air ducts in walls, radiant heat from fireplace, lamps, the sun, television, etc. Consult the Instruction Sheet packaged with thermostat for mounting instructions. All units have one stage of heating and one stage of mechanical cooling. Units which will have economizers may use thermostats with one or two stages of cooling. *PG1360***1A ONLY: These models have two stages of mechanical cooling. A 1-stage heat, 2-stage cooling thermostat is recommended for these models. Sizing Between Nrst and Se(_nd Slage Regulator MaXimum propane Capacri_s listed are based on 1 PSIG pressure Drop at 10 PSIG Set_ng Capacfaes in 1,000 BTU/HR PiPE OR WIRING Mount the thermostat approximately five feet above the floor, in an area that has an inside, vibration-free wall and has good air circulation. Typical Propane Gas Piping 3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4" 30 309 700 1,303 2,205 3,394 1,843 3,854 40 265 59_ 1,115 1,887 2,904 1,5(7 3,298 50 235 531 988 1,672 2.574 1,398 2,9"23 60 213 481 896 1,515 2.332 1,267 2,649 70 196 446 824 1,394 2,146 1,165 2,437 80 182 412 767 1,297 1,996 1,084 2,267 90 171 386 719 1,217 1.873 1,017 2,127 100 161 365 679 1,149 1,769 961 2,009 150 130 293 546 923 1,421 /72 1,613 200 111 251 467 790 1,216 660 1,381 250 90 222 414 700 1,078 585 1,224 300 89 201 378 634 976 530 1,109 350 82 185 345 584 898 488 1,020 400 76 172 321 543 836 454 949 _LWARNING The units are designed for operation on 60 hertz current and at voltages as shown on the rating plate. All internal wiring in the unit is complete. It is necessary to bring in the power supply to the contactor as shown on the unit wiring diagram which is supplied with each unit. 24 volt wiring must be connected between the unit control panel and the room thermostat. Multiply by 1 130 Mul_ply by 0 879 st_ng BetweenSingle or SeOmldStage Regulator and Appliance* Ma>3mumpropane Capaci_esLISI_I al_ Based on 1/'2,,W C pr_SSUroDropat 11"WC SetUng Capacdl(_inl.0OOBPJ/HR PiPE OR TUBING PERSONAL GAS PSIG 200 PSIG Maximum To o_nved to Capacit_s at 15 PSIG Se_ngs To conver t to Capacri_s at 5 PSIG SellJngs UNIT A WARNING LOW OR SERIOUS BY A PROPANE DEVICE. GAS ODORANT WITH Conbnuous 11" W.C. TUBING LENGTH, FEET GAS SPACE, DAMAGE CAUSED WARNING PROPANE CONFINED See below for typical propane gas piping. PROPERTY EXPLOSION NOMINAL PIPE SIZE, SCHEDULE 40 TUBING SIZE, O.D., WPE L LENGTH, FEET 3/8" 112" 518" 3/4" 718" 112" 3/4" 1" 1-114" 1-112" 10 49 110 205 348 539 291 6G_ 1,146 2.353 3,525 20 34 76 141 239 368 200 418 ,'88 1,61,' 2,423 30 27 61 114 192 296 161 336 632 1,299 1,946 40 23 52 97 164 253 137 284 541 1,111 1,665 50 20 46 86 146 224 122 255 480 985 4,476 60 19 42 78 132 20_ 110 231 436 892 4,33• 80 16 35 67 113 174 94 19_ 372 764 1,144 1_ 14 32 59 100 154 84 175 330 677 1,014 125 12 28 52 89 137 74 155 29_ 600 899 150 11 26 48 80 124 6• 141 265 544 815 200 10 22 41 69 1_ 58 120 227 465 697 250 9 19 36 61 94 51 10• 201 412 618 30(] 8 18 33 55 85 46 97 48_ 374 560 350 7 15 30 51 78 43 89 167 344 515 4_ • 15 28 47 73 4o 83 155 3_0 479 Ez_g Ez_ *DATA IN ACCORDANCE WiTH NFPA PAMPHLET NO z, = © CRYWG LOW VOLTAGE CONNECTOR 54 Low Voltage Wiring Table 3 - Propane Gas Pipe Sizing 8 "Note:Junction box location shown is optional and is for illustration purposes only. JUNCTION Y_2C BOX R YIWG LOW VOLTAGE CONNECTOR Electrical Power Directly To Junction Box Low Voltage Wiring-*PG1360"*'1A Only Refer to the unit wiring diagram for electrical connections. When installed, the unit must be electrically grounded in accordance with local codes or in the absence of local codes, with the National Electrical Code, ANSI/NFPA No. 70, and/or the CSA C22.1 Electrical Code. Ensure low voltage connections are waterproof. ,_ TO AVOID THE POLARIZED RISK AND OF WARNING ELECTRICAL SHOCK, WIRING TO THE UNIT MUST BE GROUNDED. Electrical Power Routed Through Bottom of Unit i_ To AVOID ONLY PROPERTY COPPER DAMAGE CAUTION OR PERSONAL _,BEL ALL _/ERIFY IMPROPER WIRES PROPER INJURY DUE TO FIRE, UNITVOLTAGE USE CONDUCTORS. i_ O PREVENT Typical Electrical Wiring Unit Voltage PRIOR AND TO OPERATION CAUTION DANGEROUS OPERATION DISCONNECTION AFTER The unit transformer is factory connected for 230V operation. If the unit is to operate on 208V, reconnect the transformer primary lead as shown on the unit wiring diagram. The induced draft blower on some models is equipped with a 230V lead (red) and a 208V lead (black). If equipped, connect the induced draft blower 208V lead (black) in place of the 230V lead (red). Tape the unused 230V lead. WHEN DUE TOWIRING SERVICING ERRORS CONTROLS. SERVICING. For unit protection, use a fuse or HACR circuit breaker that is in excess of the circuit ampacity, but less than or equal to the maximum overcurrent protection device. DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE. HEAT ANTICIPATOR SETTING The heat anticipator is to be set by measuring the load (amperage) atthe "R" circuit. Followthe instructions provided by the thermostat for more details. All line voltage connections must be made through weatherproof fittings. All exterior power supply and ground wiring must be in approved weatherproof conduit. Low voltage wiring from the unit control panel to the thermostat requires coded cable. See below for ground level and rooftop wiring. Typical Thermostat and Unit 24 V Wiring Hookup 9 Down Discharae AoDlications ) Dol y/y2 Cut insulation around bottom openings and remove panels from the bottom of the unit, saving the screws holding the panels in place. DUCTWORK Duct systems and register sizes must be properly designed for the C.EM. and external static pressure rating of the unit. Ductwork should be designed in accordance with the recommended methods of Air Conditioning Contractors of America Manual D (Residential) or Manual Q (Commercial). All ductwork exposed to the outdoors must include a weatherproof barrier and adequate insulation. ....._ Aduct system should be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B. The supply duct from the unit through a wall may be installed without clearance. However, minimum unit clearances as shown in the appendix must be maintained. The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger. A cover should be tightly attached to prevent air leaks. Typical 2-Stage Cool Thermostat and Unit 24 V Wiring Hookup *PG136O***1A Only CIRCULATING AIR AND FILTERS AIRFLOW CONVERSION Units can easily be converted from horizontal to downdischarge airflow delivery. In down_lischarge or high static installations, the installer should measure the total external static and review the blower performance charts before performing the installation. In some installations it will be necessary to change the blower speed to provide proper air flow. For duct flange dimensions on the unit refer to the Unit Dimension illustration in the appendix. For down-discharge applications, the ductwork should be attached to the roof curb prior to installing the unit. Ductwork dimensions are shown in the roof curb installation manual. If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission. Horizontal Air Flow Remove supply and return duct covers which are attached to the unit as shown below. FILTERS A To PREVENT EQUIPMENT PROPERTY EFFICIENCY BUILD UP ON INTERNAL FILTER _emove _e_e for horizontal INSTALLED CAUTION DAMAGE DUE TO FIRE AND LOSS OF OR EQUIPMENT PARTS, NEVER IN THE RETURN DAMAGE DUETODUSTANDLINT OPERATE UNIT WITHOUT AN AIR AIR SYSTEM. Even though a return air filter is not supplied with this unit, there must be a means of filtering all return air. The *PG1336(3A,4A), *PG1342, *PG1348, and *PG1360 models are provided with internal filter racks for down-discharge applications. All units may be externally filtered. Refer to the unit filter size chart in the appendix for filter size information. Filters installed external to the unit should be sized in accordance with their manufacturer recommendations. A covers duct applica_or_ throwaway filter must be sized for a maximum face velocity of 300 feet per minute. Filter Installation Important: When installing a filter, the air flow arrows on the filter must point toward the circulator blower. VENTING NOTE: Venting is self-contained. Remove these panels for downflowduct applications Duct Cover Installation 10 Do not modify or block. FLUE HOOD INSTALLATION Install the flue hood and bug screen prior to operation of the unit. 4. To install the flue hood cover and bug screen: 1. Remove the flue hood and bug screen from inside the heat exchanger compartment. 2. Slide the bug screen over the flanges of the flue hood and attach the flue hood and screen to the unit with the sheet second on delay period. ECM motor will energize at heating speed after the 45 second delay regardless of the status of the main burner flame. The unit delivers heat to the conditioned space until the thermostat is satisfied. 5. The gas valve deenergizes. The induced draft blower continues operation for a 29-second post-purge. 6. Ignition control begins timing the HEAT FAN OFF delay. There is an adjustable HEAT FAN OFF delay of approximately 120/135/150 seconds (factory set at 150). After the H EAT FAN OFF delay time has elapsed, the blower will deenergize. This allows any additional heat in the heat exchanger to be transferred to the conditioned space. *PGI 3(48,60)**'1A ONLY: HEAT FAN OFF delay is fixed at 180 seconds. Airflow level is 50% of nominal heating airflow. metal screws provided. COOLING 1. Thermostat calls for cooling. The compressor and outdoor fan are energized. 2. Approximately seven seconds later, the indoor fan starts. 3. The unit will deliver cooling to the conditioned space until the thermostat is satisfied. 4. The compressor and outdoor fan will be deenergized when the thermostat opens. 5. The indoor fan continues to run for approximately 60 seconds after the thermostat is satisfied. This allows additional cooling from the indoor coil to be transferred to the conditioned space. Then, the indoor fan stops. *PG1348***1A ONLY: 1. Thermostat calls for cooling. Outdoor fan and compressor are energized. ECM motor is energized almost immediately for 30 seconds at 50%ofthe nominal airflow. Airflow then increases to nominal airflow. 2. The unit will deliver cooling to the conditioned space until thermostat is statisfiod. Flue Hood and Bug Screen Installation CONDENSATE CONDENSATE DRAIN DRAIN CONNECTION A 314" NPT drain connection is supplied for condensate piping. An external trap must be installed for proper condensate drainage. DRAIN CONNECTION 3. The outdoor fan and compreesor will be de-energized when thermostat opens. 4. ECM motor continues to operate for approximately 60 seconds at 50% of nominal airflow after thermostat opens. 2.1.1.u.1 1/ ]_J BING-HONE _ *PG1360***1A ONLY: 1. Thermostat calls for low stage cooling. Outdoor fan and low stage compressor are energized. ECM motor is energized almost immediately for 30 seconds at 50% of the nominal low stage airflow. Airflow then increases to nominal low stage airflow. If thermostat calls for high stage cooling, outdoor fan and low and high stage compressor is energized. ECM motor is energized almost immediately for 30 seconds at 50% of the nominal high stage airflow. Airflow then increases to nominal high stage airflow. 2. The unit will deliver cooling to the conditioned space until thermostat is satisfied. 3. The outdoor fan and low stage compressor (or low and high stage compressor) will be de-energized when thermostat opens. 4. ECM motor continues to operate for approximately 60 seconds at 50% of nominal low stage airflow (or high stage airflow if thermostat call was for high stage cooling) after thermostat opens. 3" MINIMUM o , _PA POSITIVE SEAL LIQUID iS REQUIRED Drain Connection NORMAL SEQUENCES OF OPERATION HEATING This unit is equipped with an ignition control that automatically lights the main burner. DO NOT attempt to light the main burners by any other method. 1. Thermostat calls for heat. The induced draft blower energizes for a 15-second pre-purge. 2. The spark igniter and gas valve energizes for 7 seconds. NOTE: The igniter produces a very intense electrical spark that ignites the gas. 3. The 30-second HEAT FAN ON delay time begins. *PGI3(48,6O)***IA ONLY: Heat on delay begins when thermostat calls for heat. ECM motor is energized approximately 45 seconds later. NOTE: ECM motor may operate at approximately 100 CFM or less during the 45 NOTE: A 180-second anti-short cycle is integral to the control and prevents recycling of the compressor. 11 FAN Secondan/Limit ONLY The secondary limit control is located on the top of the blower scroll assembly. This control opens when elevated temperatures are sensed. Elevated temperatures at the control are normally caused by blower failure. The reason for the opening should be determined and repaired prior to resetting. If the power to the unit is interrupted during the heating cycle, it may cause the secondary limit to trip. Once the blower compartment temperature drops below the limit reset temperature, the limit will automatically reset. 1. Thermostat calls for FAN ONLY by energizing "G". 2. Approximately seven seconds later, the indoor fan starts. 3. The indoor fan continues to run for approximately 60 seconds after "G" is de-energized. *PG13(48,6O)***1A ONLY: 1. Thermostat calls for FAN ONLY by energizing "G". 2. ECM motor is energized almost immediately at approximately 30% of the nominal high stage cooling airflow, depending on setting (see "Blower Speed Adjustment" section). 3. EfiM is de-energized almost immediately after =G" is deenergized. STARTUP, ADJUSTMENTS, AND Control CHECKS HEATING STARTUP This unit is equipped with an electronic ignition device to automatically light the main burners. It also has a power vent blower to exhaust combustion products. On new installations, or if a major component has been replaced, the operation of the unit must be checked. Check unit operation as outlined in the following instructions. If any sparking, odors, or unusual sounds are encountered, shut off electrical power and recheck for wiring errors, or obstructions in or near the blower motors. Duct covers must be removed before operating unit. Backof Und Secondary Limit Control Heat AnUcioator Settine Pre-ODeration Checks Set the heat anticipator on the room thermostat to 0.4 amps to obtain the proper number of heating cycles per hour and to prevent the room temperature from overshooting the room thermostat setting. 1. 2. 3. 4. Close the manual gas valve external to the unit. Turn off the electrical power supply to the unit. Set the room thermostat to its lowest possible setting. Remove the heat exchanger door on the side of the unit by removing screws. 5. This unit is equipped with an ignition device which automatically lights the main burner. DO NOT try to light burner by any other method. 6. Move the gas control valve switch to the OFF position. Do not force. Rollout Protection Control The rollout protection device opens, cutting power to the gas valve, if the flames from the burners are not properly drawn into the heat exchanger. The rollout protection device is located on the burner bracket. The reason for elevated temperatures at the control should be determined and repaired prior to resetting this manual reset control. 7. Wait five minutes to clear out any gas. 8. Smell for gas, including near the ground. This is important because some types of gas are heavier than air. If you have waited five minutes and you do smell gas, immediately follow the warnings on page 3 of this manual. If having waited for five minutes and no gas smell is noted, move the gas control valve switch to the ON position. 9. Replace the heat exchanger door on the side of the unit. 10. Open the manual gas valve external to the unit. 11. Turn on the electrical power supply to the unit. 12. Set the thermostat to desired setting. _bWARNING To AVOID PROPERTY OR EXPLOSION, DAMAGE, A QUALIFIED PERSONAL SERVICER THE ROLLOUT PROTECTION DEVICE THE ROLLOUT PROTECTION DEVICE. ./< INJURY MUST TO OPEN OR DEATH INVESTIGATE BEFORE DUE TO THE MANUALLY FIRE REASON FOR RESETTING / _ FRoIIout Protection IN @ White-Rodgers Rollout Protection on Burner Bracket 12 Model 36F22 OUTLET Only small variations in gas flow should be made by means of the pressure regulator adjustment. In no case should the final manifold pressure vary more than plus or minus 0.3 inches water column from the specified nominal pressure. Any major changes in flow should be made by changing the size of the burner orifices. The measured input rate to the furnace must not exceed the rating specified on the unit rating plate. / GasValve Or_Off Selector Switch White-Rodgers For natural gas, the manifold pressure must be between 3.2 and 3.8 inches water column (3.5 nominal). 36G22 For propane gas, the manifold pressure must be between 9.7 and 10.3 inches water column (10.0 nominal). Gas SUDDIVAnd Manifold Check Gas supply pressure and manifold pressure with the burners operating must be as specified on the rating plate. Gas Inout tNatural Gas Onlv_ Check To measure the gas input use a gas meter and proceed as follows: Gas Inlet Pressure Check Gas inlet pressure must be checked and adjusted accordance to the type of fuel being consumed. in With Power And Gas Off: 1. Connect a water manometer or adequate gauge to the inlet pressure tap of the gas valve. Inlet gas pressure can also be measured by removing the cap from the dripleg and installing a predrilled cap with a hose fitting. With Power And Gas On: 2. Put unit into heating cycle and turn on all other gas consuming appliances. Natural Inlet Gas W.C., Pressure Min. 5.0" Max. 10.0" W.C. I Propane Min. 1!.0" W.C., Max. 13.0" W.C. I 1. Turn off gas supply to all other appliances except the unit. 2. With the unit operating, time the smallest dial on the meter for one complete revolution. If this is a 2 cubic foot dial, divide the seconds by 2; if it is a 1 cubic foot dial, use the seconds as is. This gives the seconds per cubic foot of gas being delivered to the unit. 3. INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT Example: Natural gas with a heating value of 1000 BTU per cubic foot and 34 seconds per cubic foot as determined by Step 2, then: Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. NOTE: BTU content of the gas should be obtained from the gas supplier. This measured input must not be greater than shown on the unit rating plate. 4. Relight all other appliances turned off in step 1. Be sure all pilot burners are operating. Main Burner Flame Check Flames should be stable, soff and blue (dust may cause orange tips but they must not be yellow) and extending directly outward from the burner without curling, floating or lifting off. NOTE: Inlet Gas Pressure Must Not Exceed the Maximum Value Shown. If operating pressures differ from above, make necessary pressure regulator adjustments, check piping size, etc., and/ or consult with local utility. v_ _bne To F_ Man_r Measuring Inlet Gas Pressure Alternate Method Manifold Pressure Check The gas valve has a tapped opening to facilitate measurement of the manifold pressure. A"U" Tube manometer having a scale range from 0 to 12 inches of water should be used for this measurement. The manifold pressure must be measured with the burners operating. To adjust the pressure regulator, remove the adjustment screw or cover on the gas valve. Turn out (counterclockwise) to decrease pressure, turn in (clockwise) to increase pressure. Temoerature Rise Check Check the temperature rise through the unit by placing thermometers in supply and return air registers as close to the unit as possible. Thermometers must not be able to sample temperature directly from the unit heat exchangers, or false readings could be obtained. 1. All registers must be open; all duct dampers must be in their final (fully or partially open) position and the unit operated for 15 minutes before taking readings. 2. The temperature rise must be within the range specified on the rating plate. NOTE: Air temperature rise is the temperature difference between supply and return air. With a properly designed system, the proper amount of temperature rise will normally be obtained when the unit is operated at rated input with the recommended blower speed. If the correct amount of temperature rise is not obtained, it may be necessary to change the blower speed. A higher blower speed will lower the temperature rise. A slower blower speed will increase the temperature rise. NOTE: Blower speed MUST be set to give the corTect air temperature rise through the unit as marked on the rating plate. 13 External Static Pressure Check Dipswitch Settings and Corresponding The total external static pressure must be checked on this unit to determine if the airflow is proper. Model GPG13480701* GPG13480901* GPG13481151* GPG13600901* GPG13601151* GPG13601401* Blower SPeed Adjustments I ,_WARNING TO AVOID PERSONAL INJURY E_ECNTER/CMALTPoORWERFROM OR DEATH THE UNIT DUE TO BEFORE ELECTRIC CHANGING SHOCK, SPEED TAPS Model ON THE GPG13480701* GPG13480901* GPG13481151* GPG13600901* GPG13601151* GPG13601401* Cooling-Yellow Lead T4 - Low Speed T5 - High Speed COOL CFM HEAT COOL 1020 1540 1140 1540 1420 1540 1140 1810 1420 1810 1700 1810 The adjustment factors for theADJUST function areA= 1, B = 1.10 (+10%) and C = 0.85 (-15%). The D tap for the ADJUST function has no effect on airflow. Example: Airflow tables indicate 1425 CFM. With the ADJUST set to B tap, the CFM becomes 1.10"1425 CFM = 1568 CFM. Dehumidification The GE ECM motor has the capability to provide increased dehumidification during cooling operation. This is accomplished by lowering the airflow to approximately 85% of the nominal cooling airflow. Example: Unit is operating at 1400 CFM and humidistat calls for dehumidification. Resulting airflow is 0.85* 1400 CFM = 1190 CFM ADJUST COOL 8 OFF OFF OFF OFF OFF OFF *PGI360***1A ONLY: Low stage airflow is approximately 75% of high stage cooling airflow. Example: High stage cooling airflow is 1800 CFM. Low stage cooling airflow is 6.75"1806 CFM = 1350 CFM. To make use of this feature, a 24VAC humidistat which opens on humidity rise is required. Connect humidistat to the HUMIDISTAT/HUM terminal on the low voltage terminal board (see wiring diagram in the appendix). Clip the HUM/ PJ6jumper on the low voltage terminal board. The system is now ready to provide dehumidification. To adjust the HEAT, COOL or ADJUST functions, simply change the ON/OFF position of the appropriate dipswitchos. The table below shows the ON/OFF combinations for the various switches and the corresponding A, B, C, or D taps. Refer to the Product Data Book applicable to your model for airflow tables and temperature rise. The =Dipswitch Position" table below shows the factory dipswitch settings for each model. The =CFM" table below shows the nominal heating and cooling CFM for each model. HEAT 7 OFF OFF OFF OFF OFF OFF NOTE: Heating airflow must be adjusted to provide the temperature rise shown on rating plate. lo,,,,,,,, DELAY DIP SWITCH POSITION 3 4 5 6 OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Unit dipswitches are factory set for each model, see label on blower housing for CFM adjustment next to low voltage terminal connections. *PG13(48, 60)**'1A models are equipped with GE ECM motors. These motors offer greater airflow flexibility as well as dehumidification. The airflow delivery for these models can be adjusted by changing the position of dip switches on a low voltage terminal board. The figure below shows the dipswitch layout on the low voltage terminal board as well as the function of each set of switches. The "HEAT" function (switches 1 and 2) provides airflow adjustment for heating airflow. The "COOL" adjustment function (switches 5 and 6) provides airflow adjustments for cooling airflow. The =ADJUST" function (switches 7 and 8) will adjust the heating AND cooling airflow +10% or - 15%. The "DELAY" function (switches 3 and 4) is not field adjustable. HEAT 2 ON ON OFF ON ON OFF REMOVE Refer to the wiring diagram in the appendix to verity speed tap settings. Blower speeds are to be changed at the ignition control board. Both heat speed and cool speed terminals are supplied on the board along with two unused motor lead terminals. *PG13(48, 60)**'1B, 3A, 4A models are equipped with X-13 motors. X-13 motors are constant torque motors with very low power consumption. This motor is energized by 24V. Adjust the CFM for the unit by changing the 24V low voltage leads to the speed terminal block on the motor. Heating-White Lead T1 - Low Speed T2 - Medium Speed T3 - High Speed 1 ON OFF ON ON OFF ON Tap Limit Check Check limit control operation after 15 minutes of operation by blocking the return air grille(s). 1. After several minutes the main burners must go OFF. Blower will continue to run. 2. Remove air restrictions and main burners will relight after a cool down period of a few minutes. Adjust the thermostat setting below room temperature. 1. Main burners must go OFF. 2. Circulating Air Blower will continue to run for 120, 135 or 150 seconds, depending on the setting. *PGI3(48,6O)***1A ONLY: Circulating Air Blower will continue to run for 180 seconds. ADJUST $ Factory Set, not rmld adJustable • Tap D haS no effect on airflow 14 to ensure the proper refrigerant superheat at the compressor is adjusted for each application. For example, 10 degree refrigerant superheat level is adequate for a 95 degree outdoor ambient temperature and a 78 - 80 degree for indoor return air temperature. As the outdoor ambient temperature rises the superheat decreases and as the outdoor ambient temperature lowers the superheat increases. Proper superheat adjustment optimizes cooling performance. For models equipped with thermostatic expansion valve, charge system to 12-14 degrees of subceoling, adjust expansion valve stem for superheat setting when necessary. NOTE: The expansion valve will not need adjustment for most applications. Ensure system superheat is set between 10-12 degrees after final adjustment. Control Board (Top) NOTE: If necessary, adjust fan OFF delay settings to obtain satisfactory comfort level. _I= THIS UNIT FINISHING USE LOW MAY MUST BE OF RESULT RETURN D_RTY NOT pHASES IN AIR USED AS PREMATURE NOTE: Mechanical cooling cannot be reliably provided at ambient temperatures below 50 ° F. WARNING A "CONSTRUCTION CONSTRUCTION ON A FAILURE TERMPERATURES AND HEATER" NEW OF Coolinn ODeration DURING STRUCTURE. THE UNIT EXPOSURE DUE TO THIS TO THE TYPE 1. Turn on the electrical power supply to the unit. 2. Place the room thermostat selector switch in the COOL position (or AUTO if available, and if automatic changeover from cooling to heating is desired). 3. Set the room thermostat to the desired temperature. OF EXTREMELY CORROSIVE OR VERY ATMOSPHERES. Untt Shutdown TROUBLESHOOTING 1. Set the thermostat to lowest setting. 2. Turn off the electrical power supply to the unit. 3. Remove the heat exchanger door on the side of the unit by removing screws. 4. Move the gas control valve switch to the OFF position. Do not force. 5. Close manual gas shutoff valve external to the unit. 6. Replace the heat exchanger door on the unit. 7. If cooling and/or air circulation will be desired, turn ON the electrical power. COOLING IGNITION CONTROL The following presents probable causes of questionable unit operation. Refer to Diagnostic Indicator Chart for an interpretation of the signal and to this section for an explanation. Remove the control box access panel and note the number of diagnostic LED flashes. Refer to Diagnostic Indicator Chart for an interpretation of the signal and to this section for an explanation. STARTUP NOTE: Check all manual reset limit controls in heating circuit if cooling mode does not operate. Comeressor Protection Devices ABNORMAL _bWARNIN To PREVENT PERSONAL BEFORE INJURY INSPEC'RNG PROToEuCT1 _)Nc_D FEVAICESRESET OR DEATH, OR SERVICING If the integrated ignition control in this unit encounters an internal fault, it will go into a "hard" lockout and turn off the diagnostic LED. If diagnostic LED indicates an internal fault, check power supply to unit for proper voltage, check all fuses, circuit breakers and wiring. Disconnect electric power for five seconds. If LED remains off after restoring power, replace control. AUTOMATICALLY. G ALWAYS DISCONNECT THE UNIT. ALL ENERGIZING OPERA TION - HEATING Internal Control Failure The compressor includes components which are designed to protect the compressor against abnormal operating conditions. POWER ERROR CODES ELECTRICAl Extemal Lockout COMPRESSOR An external lockout occurs if the integrated ignition control determines that a measurable combustion cannot be established within three (3) consecutive ignition attempts. If flame is not established within the seven (7) second trial for ignition, the gas valve is deenergized, 15 second inter-purge cycle is completed, and ignition is reattempted. The control will repeat this routine three times if a measurable combustion is net established. The control will then shut off the induced draft blower and go into a lockout state. If flame is established but lost, the control will energize the circulatorblower at the heat speed and then begin a new ignition sequence. If flame is established then lost on subsequent attempts, the control will recycle for four (4) consecutive ignition attempts (five attempts total) before locking out. THE CONTACTOR Coolino Refriaerant Charoino Check unit charge before putting the cooling section into full operation. The unit is factory charged with R-22 for nominal air flow and static pressure conditions. The unit has a piston flowrater expansion device. NOTE: *PG1360 is equipped with a thermostatic valve expansion device. To ensure the unit is properly charged for the intended application, check the unit refrigerant superheat at the compressor. The refrigerant superheat is a function of outdoor ambient temperature and return air temperature of the conditioned space. It is the installing contractors responsibility 15 The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts or flame dropouts. The integrated control will automatically reset after one hour, or it can be reset by removing the thermostat signal or disconnecting the electrical power supply for over five seconds. If the diagnostic LED indicates an external lockout, perform the following checks: Check the supp/y and manifold pressures Check the gas orifices for debris Check gas valve for proper operation Check secondary limit A dirty filter, excessive duct static, insufficient air flow, a faulty limit, or a failed circulator blower can cause this limit to open. Check filters, total external duct static, circulator blower motor, blower motor speed tap (see wiring diagram), and limit. An interruption in electrical power during a heating cycle may also cause the auxiliary limit to open. The automatic reset secondary limit is located on top of the circulator blower assembly. Check rollout limit If the burner flames are not properly drawn into the heat exchanger, the flame rollout protection device will open. Possible causes are restrictedor blocked flue passages, blocked or cracked heat exchanger, a failed induced draft blower, or insufficient combustion air. The rollout protection device is a manual reset limit located on the burner bracket. The cause of the flame rollout must be determined and corrected before resetting the limit. Check flame sensor A drop in flame signal can be caused by neady invisible coating on the sensor. Remove the sensor and carefully clean with steel wool. Check wiring Check wiring for opens/shorts and miswiring. Important: If you have to frequently reset your gas/electric package unit, it means that a problem exists that should be corrected. Contact a qualified servicer for further information. Flame Detected with Gas Valve Closed If flame is detected with the gas valve deenergized, the combustion and air circulator blowers are energized. The diagnostic fault code is five (5) flashes for this condition. The control can be reset by removing the power supply to the unit or it will automatically reset after one hour. Miswiring is the probable cause for this fault. ABNORMAL OPERA TION - COOLING Short Cycle Compressor Delay The automatic ignition control has a built-in feature that prevents damage to the compressor in short cycling situations. In the event of intermittent power losses or intermittent thermostat operation, the ignition control will delay output to the compressor contactor for three minutes from the time power is restored. (Compressor is off a total of three minutes). The diagnostic LED will flash six (6) times to indicate the compressor contactor output is being delayed. NOTE: Some electronic thermostats also have a built-in compressor short cycle timer that may be longer than the three minute delay given above. If you are using an electronic thermostat and the compressor has not started after three minutes, wait an additional five minutes to allow the thermostat to complete its short cycle delay time. MAINTENANCE .1o. VO,T,O, =1111 &w.....o _lll 1 o° .%AOSE P.OP/ DISCONNECTALL POWERBEFORESERVICINGOR INSTALLINGTHISUNIT. MULTIPLE POWEREOURCESMA_ Pressure Switch Stuck Open Have the gas heating section of the unit checked at least once a year before the heating season begins, to be sure that the combustion air inlet and flue outlet hoods are not blocked by debris, which would prevent adequate combustion air and a prepedy operating vent system. A pressure switch stuck open can be caused by a faulty pressure switch, faultywidng, a disconnected or damaged hose, a blocked or restricted flue, or a faulty induced draft blower. If the control senses an open pressure switch during the prepurge cycle, the induced draft blower only will be energized. If the pressure switch opens after ignition has begun the gas valve is deenergized, the circulator blower heat off cycle begins, and the induced draft blower remains on. The diagnostic fault codeistwoflashes. FILTER REPLACEMENT A return air filter is not supplied with this unit; however, there must be a means of filtering all of the return air. The filter(s) may be located in the return air duct(s), or return air filter grille(s). Consult with your installing dealer for the actual location of the return air filter(s) for your unit. Dirty filters are the most common cause of inadequate heating or cooling performance. Filter inspection should be made at least every two months; more often if necessary because of local conditions and usage. Dirty throwaway filters should be discarded and replaced with a new, clean filter. Dirty permanent filters should be washed with water, thoroughly dried and sprayed with a filter adhesive before being reinstalled. (Filter adhesives may be found at many hardware stores.) Permanent filters should last several years. However, should one become tom or uncleanable, it should be replaced. Pressure Switch Stuck Closed A stuck pressure pressure off. The OR CLEANING closed pressure switch can be caused by a faulty switch or faulty wiring. If the control encounters a switch stuck closed, the induced draft blower remains diagnostic LED code for this fault is three (3) flashes. Ooen Thermal Protection Device If the primary limit switch opens, the gas valve is immediately deenergized, the induced draft and air circulating blowers are energized. The induced draft and air circulator blowers remain energized until the limit switch recloses. The diagnostic fault code for an open limit is four (4) flashes. A primary limit will open due to excessive supply air temperatures. This can be caused by a dirty filter, excessive duct static, insufficient air flow, or a faulty limit. Check filters, total external duct static, blower motor, blower motor speed tap (see widng diagram), and limit. This limit will automatically reset once the temperature falls below a preset level. CABINET FINISH MAINTENANCE Use a fine grade automotive wax on the cabinet finish to maintain the finish's original high luster. This is especially important in installations with extended periods of direct sunlight. 16 CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY) CLEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY) The ceil with the outside air flowing over it should be inspected annually and cleaned as frequently as necessary to keep the finned areas free of lint, hair and debris. 1. Shut off electric power and gas supply to the unit. 2. Remove burner assembly by disconnecting the gas line and removing the manifold bracket from the partition panel. 3. Remove the flue from the induced draft blower and the collector box cover from the partition panel. 4. The primary heat exchanger tubes can be cleaned using a round wire brush attached to a length of high grade stainless steel cable, such as drain cleanout cable. Attach a variable speed reversible drill to the other end of the spring cable. Slowly rotate the cable with the drill and insert it into one of the primary heat exchanger tubes. While reversing the drill, work the cable in and out several times to obtain sufficient cleaning. Use a large cable for the large tube, and then repeat the operation with a small cable for the smaller tube. Repeat for each tube. 5. Whenallheatexchangertubeshavebeencleaned, replace the parts in the reverse order in which they were removed. 6. To reduce the chances of repeated fouling of the heat exchanger, perform the steps listed in =Startup, Adjustments, and Checks". CONDENSER_ EVAPORATOR_AND INDUCED DRAFT MOTORS Bearings on the air circulating blower motor, condenser motor and the combustion fan motor are permanently lubricated. No additional oiling is required. FLAME SENSOR (QUALIFIED SERVICER ONLY) A drop in the flame curTentcan be caused by a nearly invisible coating on the flame sensor. This coating, created by the fuel or combustion air supply, can be removed by carefully cleaning the flame sensor with steel wool. NOTE: After cleaning, the microamp signal should be stable and in the range of 4 - 6 microamps DC. / Flame _ _Sensor MAIN BURNER FLAME (QUALIFIED SERVICER ONLY) Flames should be stable, soft and blue (dust may cause orange tips but must not be yellow). The flames must extend directly outward from the burner without curling, floating or lifting off. Flame Sensor _heck the burner flames for: 1. Good adjustment 2. Stable, son and blue 3. Not curling, floating, or lifting off. FLUE PASSAGES (QUALIFIED SERVICER ONLY) At the start of each heating season, inspect and, if necessary, clean the unit flue passage. Burner Flame _WARNING To AVOID DO NOT PERSONAL REMOVE ADJUSTMENT. FLAME SHOULD ANY INJURY OR INTERNAL CONTACT DEATH DUE TO COMPARTMENT A QUALIFIED SERVICER ELECTRIC COVERS AT ONCE SHOCK, OR ATTEMPT ANY IF AN AeNORMAL DEVELOP. At least once a year, prior to or during the heating season, make a visual check of the burner flames. NOTE: This will involve removing and reinstalling the heat exchanger door on the unit, which is held by two screws. If you are uncertain about your ability to do this, contact a qualified servicer. If a strong wind is blowing, it may alter the airflow pattern within the unit enough that an inspection of the burner flames is not possible. 17 CLEANING ACCESSORIES BURNERS 1. Shut oft electric power and gas supply to the unit. 2. Remove the screws securing the manifold to the burner retention bracket. Remove the manifold and rotate each burner counterclockwise to remove. AND FUNCTIONAL PARTS SHEET METAL ACCESSORIES Additional accessories can be purchased to fit specific application needs. Parts and instructions are available from your distributor. FUNCTIONAL PARTS Burner Bracket ;Ill _[q/Is] _r,jll _uxliary Limit Switch Blower Housing Circulator Blower Motor Blower Wheel Burner Manifold_ Capacitor Compressor 3ondenser Coil Condenser Fan Blade Condenser Fan Motor Contactor Gas Manifold Manifold Assembly 3. Remove the burners. 4. Use a bottle brush to clean burner insert and inside of the burners. LABEL ALL WIRES WIRING ERRORS PRIOR IMPROPER 1_ ALWAYS VERIFY PROPER Functional Parts List GENERAL INFORMATION 1. Refer to the description in Functional Parts List when ordering any of the listed functional parts. Be sure to provide the unit model and serial numbers with the order. CAUTION TO DISCONNECTION CAN CAUSE WHEN SERVICING AND DANGEROUS CONTROLS. 2. Although only functional parts are shown, all sheet metal parts, doors, etc. may be ordered by description. 3. Parts are available from your distributor. OPERATION. CAUTION OPERATION Heat Exchanger High Limit Switch Igniter Ignition Control Induced Draft Blower Pressure Switch Pressure Switch Hose Transformer Evaporator Coil 5. Replace burners and manifold, inspect the burner assembly for proper seating of burners in retention slots. 6. Reconnect electrical power and gas supply. _k __,_:_i. Flame Roll-out Switch Flame Sensor Gas Orifice Gas Valve AFTER SERVICING. For further information on the yearly inspection, consult the User Manual. it is recommended that a qualified servicer inspect and service the unit at least once each year. Turn the unit on at the thermostat. Wait a few minutes, since any dislodged dust will alter the normal flame appearance. Flames should be predominantly blue and directed into the tubes. They should not be yellow. They should extend directly outward from the burner ports without curling downward, floating or lifting off the ports. 18 IGNITION CONTROL Light Signal Off 1 Flash 2 Flashes 3 Flashes 4 Flashes 5 Flashes 6 Flashes DIAGNOSTIC Pressure Switch Stuck Open Pressure Switch Stuck Closed Thermal Protection Device Open Flame Detected with Gas Valve Closed Short Cycle Compressor Delay (Cooling Only) TIMING i On off Gas Valve On CHART Refer to Abnormal Heating or Cooling Operation Sections of this Manual Internal Control Failure External Lockout HEATING Circulator Blower INDICATOR CHART i 100 % 50 % i i Off Igniter On off Induced Draft Blower On off Thermostat On i i i i I i i i i Off Seconds i 0 i i 15 i i 22 45 i i i 52 0 20 i i i 120, 135,150 180"PG1348,60 Legend: --*PG10,12,24-60, *PG1324-42 ........ *PG1348,60 COOLING Circulator Blower ON i OFF _ i OutdoorFan and Compressor ON OFF ON J I I i Legend: -- i I I i i i 1 i 7 30 1 0 100% _% ,'"i ii OFF CHART ..... ii ' ' Thermostat Seconds TIMING i i 0 *PGI O,12,24-60, *PG1324-42 ........ *PG1348,60 19 60 ONLY APPENDIX UNIT DIMENSIONS 47 23/4 BEHIND COMPI:_SSOR ACCESS PANEL RE]URN SUPPLY POWER WIRE ENTRANCE COMBUSTION/_R INLETS SUPPLY RE3URN 2O DIMB_ISION INCHES MEDIUM LARGE A 32 40 B 16 18 C 9 1/2 14 GPG13(24,30,36,42)1A WARNING WIRING DIAGRAM DISCONNECT ALL POWER BEFORE SERVICING ORINSTALLING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE THIS TO HIGH VOLTAGE! DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL R INJURY OR DEATH. R °L? BL Y CH OPTIONAL CONNECTED AT L1, L2 CH OPTIONAL NOTE 4 PU POWER SUPPLY 20_23011!60 T .s BR _B NOTE 5 CAP2 BL NOTE R 7 PU(L2) R LOW [_k B BR BR MED]UM HIGH PU BR ALT 3 SPEED MOTOR I LB PU 4 SPEED MOTOR BL I I k ) ECON F NOTEp6L G GAS VALVE YBL 1 GAS VALVE _ FS ,=_o IIC PU BL I I I I I TO THC I _EETHCFIELDWIRINGBELOW) O NOTE 5 PU R J CAP1 PU PU BR Y B4312003 REV. B Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to.late 21 wiring. GPG13(24,30,36,42)1A WARNING L1 WIRING DIAGRAM DISCONNECT ALLPOWER BEFORE SERVICING ORINSTALLING THIS UNIT. VOLTAGE! MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO I HIGH DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. SUPPLY VOLTAGE 1.2 COMPONENT LEGEND 208-230/1/60 CH ccT__r_<_ NOTE _ _c ALS AU_LLARY LIMIT SWITCH CAP CAPACITOR COMP COMPRESSOR CM CONDENSER MOTOR 4 i_ @ CC CONTACTOR DH CRANKCASE HEATER cApz _ °WIRE SPLICE GVJ_RKED TERMINAL cUNMARKED TERMINAL WIRING LINE VOLTAGE LOW VOLTAGE FIELD INSTALLED POWER FIELD INSTALLED CONTROL EM EVAPORATOR MOTOR FS FLAME SENSOR GV GAS VALVE lID INTEGRATED IGNITION CONTROL IGN IGNITOR LS LIMITSWITCH PL PLUG PS PRESSURESWITCH RS ROLLOUTSWlTCH THC ]I-IERMOSTATHEAT&COOL TRANS TRANSFORMER VM VENTMOTOR (HIGH) ® WIRE CODE B BLACK BL BLUE BR BROWN G GREEN O ORANGE PK PINK PU PURPLE R RED W WHITE Y YELLOW NOTES 1. REPLACEMENT INSULATIOR WIRE MUST BE THE AS ORIGINAL(USE 2. FOR 206 VOLT TRANSFORMER FROM _RMINAL 3. SOME MODELS ®TO SAME SIZE .&NO TYPE OF COPPER CONDUCTOR OPERATION TERMINAL _ON HAVE VENT MOTORS MOVE ONLY). SLACK WIRE ]WANSFORMENo EQUIPPED WITH A 23OV LEAD (RED) AND A 208V (SLACK), IF EQUIPPED, CONNECT VENT MOTOR BLACK LEAD IN PLACE OF RED LEAD AT IIC (DI) FOR 2DSV OPERATION. 4. CRANKCASE HEATER (OPTIONAL). 5. FOR DIFFERENT THAN FACTORY SPEED TAP CHANGE COOLING @ SPEED AT COOL TERMINAL (IIC). CHANGE HEATING SPEED AT HEAT TERMINAL (IIC) 4 SPEED MOTOR B - HIGH SPEED BL - MEDIUM HIGH SPEED Y - MEDIUM LOW SPEED R - LOW SPEED 3 SPEED=MOTOR B - HIGH SPEED BL - MEDIUM SPEED R - LOW SPEED 6, ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS)ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARMEN][ 208-230/1160 TOTHC INSTALLER/SERVICEMAN THC-FIELD TH E STATUS LIGHT ON THE FLIRNACE CONTROL 1_L_YBE L_ED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: STATUS LIGHT EQUIR STATUS THC-NO CHECK ECONOMIZER WIRING 2_NG w ® w ® y ® ® © R Pu ¥ ® @ @ ON NOI_MAL OPERATION OFF NO POWER OR INTERNAL CONTROL FAULT GHECKINPIJTFOWER _ECKFU_ el0_l]_. REPLACE CONTROL - 1 BLINK IGNITION FAILURE OR OPEN ROLLOUT SWITCH OR OPEN AUX. LIMIT SWITCH GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN 2 BLINKS PRESSURE SWITCH OPEN CHECK PRESSURE SWITCH S SLINKS FRESSLRE SWITCHGLOSEJ WITHOUT INDUCER ON CHECK PRESSURE SWITCH 4 SLINKS OPEN LIMIT SWITCH MAIN LIMIT OPEN BAD SWITCH R ® 5 BLINKS FALSE FLAME SENSED STICKINGGAS VN-VE PU ® S BLINKS COMPRESSOR OUTPUT DELAY 3 MIN, COMP ANS].C'fCLE ]]MER BL ® BL TI-IC-W ITH ECONOMIZER OPTION w B4312003 REV. B Wiringis subjectto change. Alwaysrefer to the wiringdiagramon the unitfor the mostup-to.late wiring. 22 GPG13(48)1A WARNING WIRING DIAGRAM DISCONNECT ALLPOWER BEFORE SERVICING ORINSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO HIGH VOLTAGE! ATH._I DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE CH OP I]ONAL CONNEC1ED AT L1, L2 NOTE4 POWER SUpI_y 208_301116D i I ............................ Q 2O8 TRANS 24V TO THC 8L I ALS Pu R G Y R G Y R G W Y Y1 Y2 W y Y NOTE 5 PL PU IIC W R (ALT) HONEYWELL GAS VALVE [ GAS VALVE BL NOTE 3 CAP1 Pu R Pu BR Y Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to.late 23 B431211114 wiring. Rev. A GPG13(48)1A WARNING L1 WIRING DIAGRAM DISCONNECT ALLPOWER BEFORE SERVICING ORINSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO HIGH V OLTAGE ATH.% II I DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE SUPPLy VC_TAGE 208_30tl/60 COMPONENT LEGEND AIS AL_(ILLARy LIMIT S_VlTCH o WtRESPLICE CAP CAPACITOR O COMp COMPRESSOR CM CONDENSER MOTOR CC CH CONTACTOR CRANKCASE HEATER WIRING FS FLAME SENSOR GV G_S VALVE m LINEVOLTAGE ....... LOW VC_TAGE FIELO INSTALLED pOWER FIELD INST_ IIC INTEGRATED IGNITIO N CONTROL IGN MARKED TERMINAL O UNMARKED TERMINAL IGNITOR CONTROL WIRE CCDE LS LIMITSWITCH B PL PLUG BL BLUE PS PRESSURESWITCH BR RS ROLLOUTSWITCH G GREFN I_ 0 ORANGE TERMINAL BLOCK BLACK BROWN MC ITIEt_4OSTATHEAT&COOL TRANS TRANSFORMER PK PINK PU pURPLE VM R VENTMOTOR VSM VAR SPEEDMOTOR RED W WHrlE y YELLOW VSTB VARIABLE SPEED TERM BLOCK NOTES 1 REPLACEMENT WIRE MUST BE THE SAME SIZF AND TYpE OF INSULAtiON AS ORIGINAL (USE COppER CONDUCTOR ONLY) IIC 2 FOR 208 VOLT I_ANSFORMER FROM TERMINAL@TO OpE3_ATION MOVE BLACK WIRE TERMINAL@ ON TRANSFORMER 3 SOME MODES HAVE VENT MOTORS EQUIPPED WrlH A 230V LEAD (RED) AND A 208V (BLACk') IF EQUIPPED, CONNECT VENT MOTOR BLACK LEAD IN pLACE OF rED LEAD AT UII {DI) FOR _ OPERATION 4 CRANKCASE HF_. {_R (OPTIONAl) 5 AOBESSORY ECONOMIZER PLUG {ON S[_E_q MODI LS) ADJACENT TO BLOWER HOUSING IN R_rURN AIR _O Mp.%RMENT 6 TWO STAGE MERMOSTAT OPTION INSTNJ£O S]B CONNECTIONS IF USED WITH ECOI_OMIZER NOTE6 TO THC 208_3_1_0 INSTALLER/SERVICEMAN I_E STATUS UGHT (_N THE FURNACE CONTROL ]ROLIBI FSHOOTING STATUS LIGHT ON ]H_S APPLIANCE STATUS EQUIP NORMAL THC-FIELD WIRING MAy BE USED AS A GUIDE TO UGHT CODES AR_/_ STA PJS TH_NO FOLLOWS: CHECK ECONOMIZER 2 STAGE COOLING W ......... OPERATION G .......... OFF NO pOWER OR FAULT 1 BLINK IGNITION FAILURE OR OPEN ROLLOIJT SWITCH or OPEN AUX LIMIT SWITCH Cp_< INFUI I_0_ G"_< FL_E _ (30NT_qCL RE_LA_E CONIRCL 2 BLINKS pRESSURE SWrlCH OPEN CHECK pIqESSU RE SWITCH 3 BLINKS PRESSURE SWtTO_ C_(3S_ I_ON CHECK pIqESSU RE SWITCH 4 BLINKS OPEN LIMIT SWITCH 5 BLINKS FALSE FLAME SENSED 6 BLINKS COMPRESSOR OU]pLrl DELAy o GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX LIMrl OPEN PU y BL TH_WITH ......... .......... ......... (_ @ (_ ECONOMIZER OPTION MAIN UMIT OPEN BA D SWITCH SlICinG PU ........ W ......... G_S VALME 3 MIN COMP ANTI_;yCLE TIMER BL ......... B4312004 Rev A Wiring is subjectto change. Always refer to the wiringdiagram on the unitfor the most up-to.late wiring. 24 GPG13(60)1A WIRING DIAGRAM HIGH VOLTAGE! WARNING DISCONNECT ALLPOWER BEFORE SERVICING ORINSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Y R .'P: GRD BL BL BL B Y 1 CH OPTIONAL CONNEC -- B-- I I_D AT LI. L_ NOI_ 4 I __ CH (_'_TIONAL i petER SUPPLY BR @ C 2_ 240 nn_d_ls TOTI_ tSE_RaD_'q_ BL R G Y W PU PU Y Y Y NOI_ 5 PU / WWR (ALT) IIC HO N Lc_P_'ELL GAS VALVE ii i BL PU o CAP1 BR Y B4312005 R_. A Wiring is subjectto change. Always refer to the wiringdiagramon the unitfor the most up-to.late wiring. 25 GPG13(60)1A WARNING I WIRING DISCONNECTALLPOWERBEFORESERVICINGORINSTALLINGTHIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO _ HIGH VOLTAGE! DO SO MAY CAUSE PROPERTY L1 DIAGRAM DAMAGE, PERSONAL SUPPLy VOLTAGE 208_3011/60 INJURY OR DE COMPONENT LEGEND A[S AUXILLA}_ UMIT SWITCH CH NOTE 4 o O MARleD TERMINAL COMp COMPRESSOR © UNMAPJ_ED I_RMINAL CM CONDENSER MOTOR CC CH CONTACTOR CRANKCASE HEA I_R GV GAS VALVE IIC INI_GRATED NOTE0 NOTE IGN 2 I I FS WIRE SPLICE CAP CAPACITOR WIRING FS FLAME SE]dSOR FS @ ATH._I IGNmO m LINE VOLTAGE ....... LOW VOLTAGE FIELD INSTALLE_ POWER FIELD INSTALL_ N CONIROL IGNITOR CONTROL WIRE CCOE LS LIMITSWITCH B PL PLUG BL BLUE PS PRESSURESWITCH BR RS ROLLOUTSWlTCH G GREFN SOL SOLENOID (2 STAG[d} O OPJ_NGE T8 PK PINK TERMINAL BLOCK BLACK BROWN ?tic I]4EI_MIOSTATHEAT&COOL PRANS q_ANSFORMER PU pURPLE R RED VM VENT MOTOR W WHITE VSM VAR y Y_LLOW SPEEDMOTOR VSTB VARIAB[E SPEED TB_M BLOCK I NOTES 1 REPLACEMENT WIRE INSULATION AS ORIGINAL 2 FOR 2Og VOLT FROM 3 MUST BE ?tiE (USE I_ANS_ORMER TERMINAl@TO SAME COppER OPERATION TERMINAl@ON SIZE AND TYpE O_NDUCTOR MOVE OF ONLy) 8LACK WIRE ]RANSFO_MER NOME MODELS HAVE VENT MOTORS EQUIppED _ A 230V LEAD (RED) AND A _08V LEAD {BLACK) IF EQIJIpF_D, OONNE_T V[_q MOTOR BLACK LEAD IN PLACE OF RED LEAD AT Ull (D1) FOR 208V OPERATION 4 CRANKCASE HEATER (OPTIONAL) 5 ACCESSORY ECONOMIZBR PLUG (ON S[_ECI _DI I_) ADJACENT TO BLOWER HOUSING IN NEf UI_I AIR _O Mp._NMENT 1B 6 TWO STAGE ITIERMOSTAT OPTION INST_D CONNECTIONS IF USED WITH EC_ZBR 208_3_1_0 INSTALLER/SERVICEMAN I]4E STAI_S UGHT ON *q_E _ I]_D_JD[FSHCOTING ITIIS API_IANCE STA]US LIGHT ON OFF _ STATt._ E(_JIp NORMAL MAY BE _ AS AGUI[3E LIGHT CO[3FS ARE AS Rll THC-FIELDWIRING TO OIA_: SI A]US TH_NO CHECK ECONOMIZER 3 BU_KS W .......... W .......... NO pOWEROR O4BCKINPUT R)t_ R 2 BU_KS ECONOMIZFR OPERATICN FAULT 1 BLINK THC-W_TH IGN113ON FAILURE OR OPEN ROLl OrS1 SWITCH OR OPEN AUX LIMIT SWITCH GAS PLOW PRESSURE G/_ VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AL_ LIMIT Op_ pRESSURE SWITCH OPEN CHECK pRES_RE SWITCH PRESSURE SIhl_:H (3L(3_13) _M]_3UI INBUCD_ON 4 BU_KS OPEN LIMIT SWITCH 5 BLI N_S FALSE FRAME SENSE[} 5 BUi'_KS COMPRESSOR OU]PUT DELAy .......... IN R I _. •...... I:IB_L_:ECQNIR(1 _ CHECK pRES_RE SWITCH FROM TERMINAL BLOCK FROM BE .......... _N J ........ D ECON PLUG MAIN UMIT OPEN BAD SWITCH S1]CI_NG G_ VhL'_ 3 MINt COMp ANTH3y(:&E TIMER B4312005 Rev. A Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to4ate wiring. 26 GPG13(36)3A WIRING DIAGRAM HIGH VOLTAGE! WARNING DISCONNECT ALLPOWER BEFORE SERVICING ORINSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. ) ) 8L BL _ 8L BL _°_ 5k Yk cH OPTIONAL CN OPTIONAL CONNECTED AT L1, L2 NOTE 3 ' I t BK SEE NOTE 3 POWER SUPPLY 208 230/3t60 SEE NOTE 6 BR 208 TR //_ _ NOTE 2 24V BL NOTE 4 2411 RD SPEED 2TOR RD PU BL BK [D B E BR ECON I PU C=9 W R GAS VALVE (ALT) HONEYWELL GAS VALVE FS lie PU BL Y2YICRYWG I I °t=_RD ) II I I TO _ERMOSTAT _=_BK F _BL tt NOTE 94t RD FC Pu PU RD PU BR Wiring is subjectto change. Always refer to the wiringdiagramon the unitfor the most up-to.late wiring. 27 GPG13(36)3A WARNING WIRING UNIT. MULTIPLE POWER Ii DISCONNECT HIGH VOLTAGE{ALL POWER DO SO MAY CAUSE SUPPLy VOLTAGE L2 SOURCES MAY BE PRESENT. FAILURE THIS TO BEFORE SERVICING OR INSTALLING ATH ._I PROPERTY DAMAGE, PERSONAL INJURY OR DE L3 CH _/_v _ COMp COMPRESSOR I CM CONDENSER C CONTACTOR CH CRANKCASE EM EVAPORATOR FC IGN FS _ _ C NOTE2 F AU)0LLARY LIMIT SWITCH ° _ _) FACTORY WIRING ALS T3 T2 c_ LEGEND COMPONENT 208 230/'3/60 NOTE3 DIAGRAM MOTOR VOLTAGE VOLTAGE _)F_llON AL HIGH VOLTAGE HEATER FIELD WIRING MOTOR HIGH VOLTAGE F FUSE FC FAN CAPACITOR LOW VOLTAGE FS FLAME SENSOR WIRE CODE GND EQUIPMENT GROUND BK BLACK GV GAS VALVE BL BLUE IIC IGN INTEGRATE D IGNI]ION CONIROL IGNrl OR BR BROWN GR GREEN LS LIMIT SWITCH or ORANGE PLF FEMALE PLUG/CONNECTOR PK PINK PS pRFSSURE SWITCH PU PURPLE RS ROLLOUT SWITCH RO RED TR TRANSFORMER WH WHILE VM VENT MOTOR YL yELlOW FS NOTES 1 REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYpE OF INSULAllON ALS AS ORIGINAL {USE COPPER CONDUCTOR ONLY) 2 FOR 208 VOLT TRANSFORME3R OPERATION MOVE BLACK WIRE RS FROM TERMINAL 3 TO T_INAL 2 ON TRANSF(]_IER 3 CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS 4 FOR DIFFERENTTHAN FACTORY SPEED TAP CHANGE COOLING SPEED AT COOL TERMINAL (IIC)_ CHANGE HEATING SPEED AT HEAT TERMINAL (IIC) 3 SPEED MOTOR BK HIGH SPEED BL MEDIUM SPEED RD LOW SPEED 5 ACCESSORY ECONOMIZER PLUG (ON SELECT MOD_S) ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARMENT 6 USECOOPERCONDUCTORS _ ONLY USE NECCLASS2WIRE 208 23013/60 THERMOSTAT FIELD WIRING INSTALLER/SERVICEMAN THE STA I_S UGHT ON THE FURJ_CE CGNIROL MAy BE US_ P_ A GU_E TO 1ROIJt_ E_DOTING ITIIS APPLIhNCE STAIUS UGWI CODES ARE _ FOU OWS: STATUS LIGHT EQUIP STATUS NOI_IAL OFF NO POWER OR INTERNAL CON 13_OL OP_ATION FAULT FAILURE OR GPEN ROLLOUT LIMIT At_ pRESSURE SWITCH OPEN pRES_IJRE S_ITOt WI MOUT INDUCER 6 BLINKS FALSE FLAME GR RD RD YL PU BL YL DEtAy BL ® WITHECONC_ZEROPTION LIMIT OpEN CHECK pRESSURE SW]TCH CLOSED ON SENSED COMPRESSOR OUTPUT GR FLAME SENSOR FLAME ROLl OUT BAD SWITCH 4 BLINKS 5 BLINKS FOYER GAS FLOW GAS pRESSURE GAS VALVE SW1TCH 3 BLINKS CIEOKINI_fl REFq_CE IGNITION SW]TCH OR OPEN AUX 2 BLINKS 2 STAGEC00L_G CHECK ON 1 BUNK N0 ECONOWER _ CHECK pRESSURE SW]TCH GR MAIN LIMIT OP_ BAD SWITCH RD S I]O(ING 3 MIN GAS VALVE PU COMp ANTFCYCLE BL I]M_ 0140G00085P Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to.late wiring. 28 GPG13(48,60)3A I1,_ WARNIN G WIRING DIAGRAM DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO HIGH VOLTAGE! ATH._ DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE YL RD BK Pu RD BK BL BL '_KBK CHOPTIONAL CONNECIED ATL1.L2 BL BL YL YL RD L G 8L N 8L RD BL EM NOIE 4 YL r= I I ll_ NOTE 5 YL i SEE NO1E7 IIC pu 8L Y2Y1CRYWG BL TO _ ERMC_TAT RD WH BR Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to.late wiring. 29 GPG13(48,60)3A I1, L1 WARNIN G SUpPLy VOLTAGE WIRING DIAGRAM DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO HIGH VOLTAGE! ATH._ DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE L2 L3 COMPONENT LEGE]_D FACTORY WIRING 208 230/3/60 CH ) _ NOTE 3 T2 c T1 -f--_ C % I1_ FC VMR ) SEF NOIE2 i z FNOTE 7 TR O IGN FS © @ ALS AL_ILLARy UMrr SWITCH _ COMP CM COMPRESSOR CONDENSER MOTOR _ C CONTACTOR CH CRANKCASE HEATER EM EVAPOP,ATOR MOTOR F PC FUSE FAN CA pACITOR FS FLAME SENSOR VOLTAGE _0P:rlONAL HIGH VOLTAGE RELD WIRING HIGH VOLTA(t _<_N VOLTAGE GND EQUII_/_NT GROUND WIRE CODE GV GAS VALVE BK BLACK IIC IN1EGRATED IGNINON CONTROL BL BLUE IGN IGFITOR BR BROWN LS LNIT SWITCH GR GREEN PLF FEMAI E PLUG/CONNECTOR OR ORANGE PS PRESSURES'WITCH PK RNK rs ROLLOUT SWITCH PU PURPLE I_ TRANS_ORM_ RD RED VM VMR VENT MOTOR VENT MOTOR RELAy WH WHrlE YL yELlOW N°TE IIC VOLTAGE NOTFS 1 REPLACEMENT WIRE MUST lIE THE SAME SIZ_/_ND WpE OF INSU[ATIGN AS ORIGINAL(USE 2 F_ VMR 208 VOLT IN_ISFOR_R FROMIERMIN,_k COPpB_ O3NDUCT_ Op[2_TION 3 TO I_I_L ONLY) MOVE BlinK '_RE 2 ON PNr_ISF_I_ 3 CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS 4 FGR DIFP B_BqT THAN FACI CRy SPEB) TAP CHANGE CCOUNG SPEED AT MOT(3R T4 AND T5 TEPJ_INALS CHANGE HEATING SPEED AT MOT(3R T1, T2 AND 13 I_RM I_A LS COOLING SPED T4 LOWSPEED T5 NOTE 5 (YELLOW WIRE) HIGH SPEE]) 12 MED SPED 13 HIGH SPEFD 5 ACCESSORY ECONOMIZER PLUG (ON SELFCI MODELS) ADJACENT TO BLOWER HOUSING iN RETURN AI_ COMPARMENT PLF 6 USE COOPER CONDUCTORS ONLy _ _ USE NEC CL_ 2 WIRE 7 L1 AND L2 ON ICC eONTR_ TOTHE_TAT HEATING SPEE]) (WHITE WIRE) T1 LOWSPEE_ IS 24V INPIXI _ 2_6 230/3/60 THERMOSTAT INSTALLER/SERVICEMAN THE S TATOSLIGHT _N ]HE FURNACE CO@]R(3_MAYBE L_ AS A GUIDE TO TROUB[FSHOO 13NG]H IS _PPLIANCE STATtJS LIGffl COOES _F _S FOLLOWS: STATUS LIGHT _N OFF EC_JIP NORMAL STATUS FIELD WIRING _ 2 STA_EC0(]LIk_ CHECK OPERATION NO pOWER OR O4E(_INPUI GR I_M[_ ar _._ RD FAULT 1 BLINK IGNrl ION FAILU R_ C_ OPEN ROLLO UT SWITCH (3PEN OR AUX LIMIT SWITCH 2 BLINKS 3 BLINKS 4 BLINKS 5 BLINKS 6 BLINKS pRFSSURE LIMIT SWITCH F*_LSE FLAME SENS_ COMpREsSOR C_JTPUT DELAY CONtrOL YL GAS FLOW GAS pRESSURE GAS VALVE FLAME SENSOR FI_,M E ROLLO_JT WffHECO_IZER _PTION AUX SWITCH OPEN pRFS_ JRE _*_*ITCH CLO_EO WITHOUT INDUCER ON OPEN R_ RAC_ LIMIT OPEN CP_CK pRESSURE SWITCH CF_CK pRESSURE SWITCH GR RB MAIN LIMIT OPEN BAD SWrl C_ SlICiNG PU GAS VALVE 3MIN ANTI_,yCLE COMp BL TIM_ 0140G00087 Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to.late wiring. 3O GPG13(36)4A I1, WARNIN G WIRING DIAGRAM DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO HIGH VOLTAGE! ATH._ DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE ,° ) PB_ ) GND BL CN OPTIONAL C_NECl_D AT LI, L2 NOTE 2 BR MMR BE C TR IBR BL BL BK 1 IL PU NOTE 4 PLF YL PU GASVALVE PU GASVALVE PU BL YI C R YW G BL I I I I I I I TD 1}IE F_OS%AT ±± FC RD BK BR Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to.late wiring. 31 GPG13(36)4A I1, L1 WARNIN G WIRING DIAGRAM DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO HIGH VOLTAGE! ATH._ DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE k2 SUPPLYVOLTAGE L3 COMFONENI IF NOTE 5 LEGE]_D FACTORY WIRING ALS AL_(ILLARy LIMIT SWITC H _ COMp COMPRESSOR _ CM CONDENSER C CH CONTACTOR CRANKCASE HEATEr EM EVAPORATOR MOTOR MOTOR VOLTAGE VOLTAGE _:_P-TIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE tOW VOLTAGE F FUSE FC FAN CAPACITOR FS FLAME SE_ISOR WIRE CODE GND EQUIPMENT GROUND 8K BLACK GV GAS VALVE BL BLUE IBR INDOOR BLOWER RELAY 8R BROWN IIC INTEGRATED IGNI nON CONTROL GR GREEN IGN IGNITOR OR ORANGE LS LIMIT SWITCIt PK PINK PLF FEMALE PLUG/CONNECTOR PU PS RS prESSURE SWITCH ROLLOUT SWITCH RD RED WH WHITE TR TRANSFORMER VM VENT MOTOr VMR VENT MOTOr PURPLE YL YELLOW REI Ay NOTES 1 REPLACEMENT WIRE MUST BE THE SAME SIZE AND ]YPE OF INSULATION AS ORIGINAL (USE COPPER CONDUCTOR ONLY) 2 CRANKCASE HEALER NOT SUPPLIED ON ALL UNITS 3 460V UNITS ARE SINGLE SPEED, TO CHANGE FROM HIGH TO LOW SPEED REPLACE TH[ BLACK MOTOR LE._ AT IBR#3 WITH RED LEAD FROM MOTOR 2 SPEED MOTOR BL P_/YL HIGH SpEFD LOW SPEED 4 ACCESSORy ECONOMI_R PLUG (ON S E'LECT MODELS) ADJACENT TO BLOWER HOUSING IN RETURN AIR COMpARMENT 5 L1 AND L2 ON IIC CONTROL IS 24V INPUT 6 USE COOPER CONDUCTORS _ ONLY USE NECCL,_SS2WIRE ±± 460/3/60 THERMOSTAT INSTALLER/SERVICEMAN ]HE STATUS LIGHTON ]HE FURNAC_ CON I_OL MAy BE IJ_ED AS A GUIDETO ]ROIJ BLFSHOOTING THIS APPLIANCE STAI_S LIGHT CODESARE AS FOLLOWS: STA]IJS LIGHT EQUIP STA]HS CN NORMAL OFF NO pOWER OR INT_NAL CON I_OL FAULT 1 BLINK OPERA FAILURE OR (3PEN I_O LLOUT SWITCH OR OPEN AUX LIMIT SWITCH 2 BUNKS 3 BUNKS 4 BLINKS 5 BUNKS 6 BLINKS PRES_URE SWITCH OPEN R_3SSURE SWlT(:H (:LOS_) WITHOUT li'JOUCEr ON OPEN FAL_ LIMITSWITCH FLAME SENSED COMPRESSOR OUTPUT DELAY _ NOECON(]MI_ ff 2 ST_,GECOOUNG 6R Gr RD RD YL Pu Yu CHECK 13ON IGNITION FIELD WIRING (3HEO_INFUI pOM3_ QB}G_J_ REPLACE CC_N]ROL GAS FLOW GAS pRESSUrE GAS VALVE FLAME SENSOR BL _L FLAME RCLLO UT BADSWITCH AUX LIMIT OPEN _; _c) WflH ECON{_IIZER (]PTION CHECK PRESSURE SWITCH CHECK PRESSURE SW113CH GR MAIN LIMIT OPEN BAD SWITCH RD S I]C_ NG G_6 VALVE FU 3 MIN COMp BL AI_I I CYCLE TIM_ 0140G00088 Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to.late wiring. 32 GPG13(48,60)4A Ij, WARNIN G WIRING DIAGRAM DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO HIGH VOLTAGE! ATH._ DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE YL RD BK BK GND BL YL CH OPTIONAL CONNECTED AT L1, L2 NOTE 2 CH OPTIONAL -- BR POWER SUPPLY 460/3/60 SEE NOTE T_R J c 48O _IE NOTE 7 5 TR I E3 BL RD RD RD BL = i YL PU YL Pu IIC PU PU BL Y2YICRYWG IIIIII BL TO THERMOSTAT RD RD OR RD FC PO BL YL WH BR BR Wiring is subjectto change. Always refer to the wiringdiagram on the unitfor the most up-to.late wiring. 33 YL YL RD GPG13(48,60)4A I WARNIN L1 WIRING P_ _'_ II UNIT. MULTIPLE POWER MAY BE PRESENT. FAILURE TO "_ ;IIsGH°vN°NELTcAGELL P°wERSOURCES BEF°RESERVICING °RINSTALLINGTHIS I DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. SUpPLy VOLTAGE 460/3/60 L2 L3 COMPONENT LEGE_iD CH _ c NOTE 2 T2 T1 A_ C _ I_ FC _ VM r SEE NOTE z FNOTE 6 l • TR (_ IGN FS @ Q DIAGRAM IIC FACTORY WIRING ALS AUXILLARY LIMIT SWITCH _ COMp COMPRESSOr _ CM CONI]E NSE3RMOTOR C CH CONTACTOR CRANKCASE HE_IER E_I EVAPORATOR MOTOR F FUSE FC FS FAN CAPACITOR FLAME SENSOR GND EQUII_VENT GROUN D GV GAS VALVE VOLTAGE VOLTAGE _OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE _(_/VOLTAGE WIRF CODE BK BLACK IIC IN I_GRA I_D IGNITION CONTROL BL BLUE IGN IGNITOR Br LS PLF LNIT SWITCH FEMALE pLUG/CONNECTOR GR GREEN OR ORANCE PS PRFSSUrE SWITCH PR PINK RS ROLLOUT SWITCH PU PURPLE TR TRANSFORMER RD RED VM VENT MOTOR WH WHITE VMR VENT MOTOR RELAy BROWN YL YELLOW NOTFS FS© _ 0@_NOTE °,O I 1 REPL&CE3_ENT WIRE MUST BE ME SAME SIZ_ AND _tPE OF @ INSULATION AS ORIGINAL (USE COppER CONDUCTOR ONLy) 2 CRANKCASE HEALER NOT SUPPLIED GN ALL UNITS O_ VMR 3 FOR DIFP ERE]qT THAN FACTORY SPEED TAP CHANGE COOLING SPED AT MOTOr T4 AND T5 _RMINALS CHANGE HEATNNG SPE DAT MOTOr T1, T2 AN D T3 1ERMffqALS CO(lING T4 15 ®1 SPEED (YELLOW WtRE) LOWSpEE]) HIGHSpEFD HEATING SPEFD (wHrl E WIRE) T1 12 LOWSpEE]) MEDSPED T3 HIGH SPEFD 4 ACCESSORy ECONOMIZER PLUG (ON SELECT MODELS) ADJACD_iT TO BLOWER HOUSING IN RETURN AIR COMpAPJ_3qT 5 USE COOPER CONDUCTORS ONLy NOTE 4 6 L1 AND L2 ON ICC CON IROL IS 24V INPU, PLF 7 STEPDOWN TRANSFORMEr 460V PRIMARY INPUT &240V SECONDARy OUTPUT TO THERMOSTAT _ _ _ _) USE NEC CLASS 2 WIRE 4(WN_60 THERMOSTAT FIELD WIRING INSTALLER/SERVICEMAN _ ITIE STATUS UGHT ONTHE FURNACE C(3N]ROL MAy BE USEDAS A GUIDE TO NOEC(_O_IZER TROUBLESHCO]]NG THIS APPLIANCE _IATL_ UGFrl CODES AREAS FC_-LOWS: STATUS LIGHT ON OFF EQ_JIp NORMAL STATUS NO pOWER cr 3 BLINKS FAILURE OR OPEN ROLLOUT SWITCH Cf_ 4 BLINKS 5 BLINKS 6 BLINKS pRESSURE L_IIT SW1TCH OPEN PI_t3SSL_E S_ITCH CL_ WITHOUT INDUCER ON OPEN FALSE LIMIT SWITCH FLAME SENSED COMp RESSC_ C_ITPUT CHECKINPUI GR FOWI_ O_]XFL_OqG_IRI RFpLAC_ _ IGNITION (3PEN AUX SWITCH 2 BLINKS W CHECK OPERATION FAULT 1 BUNK 2 STAGE C00L_'_ D ELAy RD YL GAS FLOW GAS pRESSURE GAS VALVE FLP_E SENSOR FLAME ROLL_JT BL BAD SW1TCH AUX LIMIT OpEN YL _ BL _C) _,_HECONOI_,_R OP lION CHECK pRESSURE SW1TCH CHECK pRESSURE SW1TCH GR MAIN LIMIT OPEN BAD SW1TCH S]]Q(ING RD PU GA_ V_LVE 3 MIN COMp AN11 CYCLE BL 0140G00089 TIME R Wiring is subjectto change. Always refer to the wiringdiagramon the unitfor the most up-to.late wiring. 34 GPG13(48,60)1B WIRING DIAGRAM DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO HIGH VOLTAGE! I_ DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. YL RD RD BK PU BK GND BL YL BK _' B_ 8KSK BK CH OPTIONAL POWER BK SUPPLY 208 23(Y_/60 SEE NOTE 6 PU PJ YL YL RD YL BL BL BL RD YL I llli! _PU YL YL NOTE 5 PLF PU GR Y YL W R GAS VALVE _e_] e _ ] SEE NOTE 7 (ALT) HONEYWELL GAS VALVE IIC PJ L BL YIC RYW BL TOTHERMOSTAT RD RD OR RCCF PU BL YL BR BR LI SUPPLYVOLTAGE L2 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to.late 35 wiring. GPG13(48,60)1B WARNING SUPPLY DIAGRAM uD_ISTC.CNuNETCTLAELL;_/E_RERoBEFOFRs E SERVBICINGE{_R/N.ST_LL/NR_TT_S I HIGH VOLTAGE! DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. ['_ L1 WIRING VOLTAGE COMPONENT LEGEND FACTORY WIRING 20_230/I/60 CH NOTE 3 T2 C ALS AUXILIARY LIMIT SWrl CH CC_p COMPRESSOR CM CONDENSER C CONTACTOR CH CRANKCASE EM EVAPORATOR F FUSE FS FLAME GND EQUIPMENT GV GAS VALVE IIC INTEGI_I_D IGN _MOLT_E _ VOLTAGE MOTOR _'_10 NAL HIGH VCtTAG E HEATER MOTOR FIELD WIRING HIgH SE_OR _k_ VOLTAGE VOLTAGE C4tOUND WIRE CODE IGNITIONC(_ITRI_ BK BLACK IGNITOR BL BLUE LS LIMIT SWITCH BR 13ROWN pkF FEMALE GR GREEN pS PRESSURE SWIII2H OR ORANGE R_F RUN TO R FO R COM PRESSOR/'P,%N pK pINK RS RC_kOUT PU pURPLE TR TRANSFORMER RB RED VM VENT MOTOR WH WHITE VMR VENT MOTOR VMR NOTE 2 [R © I ,G. .o PLUG/CONNECTOR CAPACI SWI I_H _1_¥ _FL yEUC_ NOI_S 1 REPlaCEMENT INSUlaTION 2 WIRE MUST I_RMINAL 3 CRANKCASE 4 FOR DIFFERENT 3 SPEED AT MOTOR SPEED AT MOTOR COOLING SPEED 2 FACTORY MOVE TI, T2 AND I_pE OF ONLY) BLACK WIRE ON ALL UNITS SPEED TAP T4 AND T5 TERMINALS (yELLOW _,ND ON TttANSF_ER NOT SUPPLIEO THAN SI_ CONDUCTOR OPENATION TO T_,tlNAL HEATER SAME COppER FOR 20B VOLT _I,ISFORMER FROM CHANGE CO_ING CHANGE HEATING 13 •EI_IINAkS W1RE) HEATING SPEED T4 LOWSPEED TI LOWSPEED T5 HIGHSPEED T2 MEO 13 HIGH 5 ACCESSORY ECONOMIZER TO BLOWER N(_E BE THE AS ORIGINAk(USE 6 USE COOPER HOUSING PLUG (ON SELECT MODE/S) IN RE I]JRN AIR COMPARM CONDUCTORS 0NHIrE WIRE) SPEED SPEED AD JACI3_IT ENT ONLy • _ USE.ECCLASS2WIRE • L1 AND k2 ON ICC CONI LIGHT ON OFF EQUIP NOP_AL STATUS OR IGNII3ON F_,JLU RE OR OPEN ROLLOLrl SWITCH OPEN OR AUX UMIT SWITCH NOECON(]I/I_ ER _ECI(INI_TI_O_3_ RI3°_C_ AL_ _qt _L_q_ S_IT(:t_I CLOS _ WI MOUT INDUCI3_ ON CHECK pRESSURE SW1TCH 6 BUNKS FALSE FLAME SENSED COMPRESSOR OUTPUT DELAy IN YL _J BL YL BL tilTH ECONO_EROPTIOI_ LIMIT OPEN 3 BUNKS LIMIT SVClTCH GR _R; FLAME RC_I OUT BAD SWITCH CHECK pRESSURE SW1TCH 5 BUNKS 2 STAGE COOUNG CONIRG[ GAS FLOW GAS pRESSURE CAS VALVE FLAME SENSOR PRESSURE SWITCH OPEN OPEN FIELD WIRING CHECK 2 BUNKS 4 BUNKS INpIJI O pERATICN NO pOWER FAULT BLINK IS 24V THERMOSTAT INSTALLER/SERVICEMAN I_IE STATUS LIC-F_ONME FURNACECON_I_DLMAy BE U_D ASA GUIDE TO ]I_OUBLESP:OOTING]HIS APPLIANCE STA]US LIGHT CODES/_RE AS FOLI OWS: STATUS I_L GR MAIN LIMIT OPEN BAD SWITCH PU S]]CKING C._ VhLVE 3 MIN COMp ANTFCYC[E BL TIMI3_ 0140G00267 Wiringis subjectto change. Always refer to the wiringdiagramon the unitfor the mostup-to.late wiring. 36 MINIMUM CLEARANCES 48" MIN 12" MIN 12" MIN 36" MIN (FOR SERVICE) NOTE: Roof overhang should be no more than 36". UNIT Min. Filter Size 2 Ton (1)20x20x1 2 1/2 Ton 3 Ton (1)20x25x11(1)25x25x1 3 1/2- (2)20x20x1 I RECOMMENDED FILTER © 2005 - 2007 Goodman Manufacturing 37 4 Ton SIZES Company, L.E 5 Ton (2)20x25x1
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 37 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Sun Jul 20 21:06:41 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools