R5  |  Part Number: 3E2512  |  1   Installation Note  |  Gallagher T12 ReaderInstallation NoteGallagher T12 Reader The Gallagher T12 ReaderThe Gallagher T12 Reader is a smart card proximity reader.  It can be installed as either an entry reader or exit reader.  It can be mounted on a BS 4662 British Standard square flush box.The reader can read Mifare DESFire EV1, Mifare  Plus and Mifare Classic cards.   The Multi Tech variant can also read 125Khz cards.Gallagher T12 Multi Tech Readers only:  Using dual technology 125/Mifare cards with Gallagher T12 Multi Tech Readers may cause both card technologies to be read, resulting in double card badges and unusual reader feedback.  Gallagher strongly recommends  against using dual technology 125/Mifare cards with Gallagher Multi Tech Readers for sites running pre-Command Centre v7.00 software (due  for  release 2nd half,  2011).   From Command Centre v7.00, a site may specify which technology a Multi Tech reader should read off a dual technology card.This equipment contains components that can be damaged by electrostatic discharge.  Ensure both you and the equipment are earthed before beginning any servicing.
2   |  Part Number: 3E2512  |  R5Installation Note  |  Gallagher T12 ReaderThe reader sends information to the Cardax FT Controller and acts upon information sent from the Cardax FT Controller.  The reader itself does not make any access decisions.The Gallagher T12 Reader uses the “Cardax IV Reader” communications protocol to communicate with the Cardax FT Controller.Before you beginShipment ContentsCheck the shipment contains the following items:1 x Gallagher T12 Reader facia assembly•1 x Gallagher T12 Reader base•1 x M3 Torx Post Security screw•2 x M3.5 Phillips drive fixing screws•4 x 25mm No.6 self tapping, pan head, Phillips drive fixing screws•4 x 40mm No.6 self tapping, pan head, Phillips drive fixing screws•Power SupplyThe Gallagher T12 Reader is designed to operate over a supply voltage range of 9 - 16Vdc measured at the reader terminals.  The operating current draw is dependant on the supply voltage at the reader.  For the Standard variant at 12Vdc the current draw is 89mA (standby).  During card read, beeper and LED activity, the current will momentarily reach 124mA (peak).  For the Multi Tech variant at 12Vdc the current draw is 88mA (standby) and will momentarily reach 140mA (peak).The power source should be linear or a good quality switched-mode power supply.  The performance of the reader may be affected by a low quality, noisy power supply.CablingThe  Gallagher  T12  Reader  requires  a  minimum  cable  size  of  4  core  24  AWG  (0.2mm2) stranded security cable.  This cable allows the transmission of data (2 wires) and power (2 wires).  When using a single cable to carry both power supply and data, both the power supply voltage drop and data requirements must be considered.  Although the reader is specified to operate at 9Vdc, for good engineering design it is recommended that the voltage at the reader should be approximately 12Vdc. Examples of approved cables for connecting a single Gallagher T12 Reader to a Controller and power supply, showing maximum cable lengths for each type of cable and the associated circuits are:
R5  |  Part Number: 3E2512  |  3   Installation Note  |  Gallagher T12 ReaderManufacturer reference Cable format*Combined power and data in a single cableData only in a single cableCAT5E 4 twisted pair Each 2 x 0.2mm2 (24 AWG)100m  (330ft) 300m  (1000ft)SEC472 4 x 0.2mm2 Not twisted pairs (24 AWG)100m  (330ft) 250m  (800ft)SEC4142 4 x 0.4mm2 Not twisted pairs (21 AWG)150m  (500ft) 150m  (500ft)BELDEN 8723 2 twisted pair Each 2 x 0.4mm2 (22 AWG)100m  (330ft) 150m  (500ft)BELDEN 9842 2 twisted pair Each 2 x 0.2mm2 (24 AWG)100m  (330ft) 200m  (650ft)* The matching of wire sizes to equivalent wire gauges are only approximate.Note:  Grounding shielded cable may reduce the obtainable cable length by 25% to 30%.Distance between Proximity ReadersThe distance separating any two proximity readers must not be less than 200mm  (8 inches) in all directions.  200mmWhen mounting a proximity reader on an internal wall, check that any reader fixed to the other side of the wall is not less than 200mm (8 inches) away.         200mm
4   |  Part Number: 3E2512  |  R5Installation Note  |  Gallagher T12 ReaderInstallationThe Gallagher T12 Reader is designed to be mounted on a standard British electrical flush box, or any solid flat surface.  However installation on metal surfaces, particularly those with a large surface area will reduce read range.  The extent to which the range is reduced will depend upon the type of metal used.The recommended mounting height for the reader is 1.1m (3.6ft) from the floor level to the centre of the reader device.  However this may vary in some countries and you should check local regulations for variations to this height.Ensure the building cable has been run out through the flush box.1. If you are not mounting to a flush box, use the drill template at the back of this installation note as a guide, to drill all five holes.  Drill the 13mm (1/2 inch) diameter centre hole (this is the centre hole for which the building cable will exit the mounting surface) and the four fixing holes.Run the building cabling through the reader base.2. Secure the base to the flush box using the two M3.5 screws provided.  It is 3. important the base of the reader is flush with and tight against the mounting surface.If you are not mounting to a flush box, secure the base to the mounting surface using the four fixing screws provided. BaseBuilding  cableM3.5 screwM3.5 screwConnect the reader tail extending from the facia assembly to the building cable.  4. Connect the wires shown below.Note:  Do not cut the ‘Reserved’ wires, as these may be used for future functions.
R5  |  Part Number: 3E2512  |  5   Installation Note  |  Gallagher T12 Reader    Positive RedNegative BlackReserved OrangeReserved GreenReserved BrownCDXIV TX WhiteCDXIV RX BlueCardax IV ReaderFit the facia assembly into the base by clipping the small lip, into the top of 5. the base and holding the top, press the bottom of the facia assembly down into the base.Insert the M3 Torx Post Security screw (using a T10 Torx Post Security screwdriver) 6. through the hole at the bottom of the base to secure the facia assembly.  Note:  The recommended torque for the security screw is 0.7Nm (0.5 lb/ft).  It is important not to exceed the maximum torque of 1.5Nm (1.1 lb/ft).  Facia Reader tailConnection Fit screw to secure  facia to baseRemoval of the facia assembly is a simple reversal of these steps.7. ConnectionsA Gallagher  T12  Reader can  connect  to  one  of  the  following  devices  using  the “Cardax IV Reader” communications protocol:Cardax FT Reader Module (for the Controller 6000)•Cardax FT GBUS Universal Reader Interface (Cardax FT GBUS URI)•Cardax FT Controller 3000-4R or 3000-8R•Cardax FT Universal Reader Interface (Cardax FT URI)•Cardax FT Reader I/O Interface•
6   |  Part Number: 3E2512  |  R5Installation Note  |  Gallagher T12 ReaderConnecting to the Cardax FT Reader Module (for the Controller 6000)Connect the wires to the sockets as shown:-+R1 OutR1 InC123C456R2 OutR2 InCardax FT Reader ModulePositive RedNegative BlackReserved OrangeReserved GreenReserved BrownCDXIV TX WhiteCDXIV RX BlueCardax IV Reader 2Positive RedNegative BlackReserved OrangeReserved GreenReserved BrownCDXIV TX WhiteCDXIV RX BlueCardax IV Reader 1Connecting to the Cardax FT GBUS Universal Reader InterfaceConnect  the  wires  to  the  sockets  as  shown  in  either  of  the  following  diagrams:RLY 2 COMRLY 2 NORLY 2 NCDATA 0DATA 1OUT  1OUT  2COM  ACOM  BTAMPERGNDVOUTGNDVINGNDPin 15 Reader Top RowPin 1Cardax FT GBUS URIPositive RedNegative BlackReserved OrangeReserved GreenReserved BrownCDXIV TX WhiteCDXIV RX BlueCardax IV ReaderRLY 2 COMRLY 2 NORLY 2 NCDATA 0DATA 1OUT  1OUT  2COM  ACOM  BTAMPERGNDVOUTGNDVINGNDPin 15 Reader Top RowPin 1Cardax FT GBUS URIPositive RedNegative BlackReserved OrangeReserved GreenReserved BrownCDXIV TX WhiteCDXIV RX BlueCardax IV Reader
R5  |  Part Number: 3E2512  |  7   Installation Note  |  Gallagher T12 ReaderConnecting to the Cardax FT Controller 3000-4R or 3000-8RThe ports to which the Gallagher T12 Reader can connect are set up as groups, as follows:Two groups (numbered 1 and 2) on the Controller 3000-4R, and•Four groups (numbered 1 to 4) on the Controller 3000-8R•Each group provides connection for two Gallagher T12 Readers.  Refer to the following diagram for the location of the ports on the Cardax FT Controller 3000-8R.
8   |  Part Number: 3E2512  |  R5Installation Note  |  Gallagher T12 ReaderMake  the  connections  from  the  Gallagher  T12  Reader  to  either  the  Cardax  FT Controller 3000-4R or 3000-8R as shown:    PB1 and PA1... to...  PB2 and PA2 (3000-4R)    PB4 and PA4 (3000-8R)Cardax FT Controller 3000-4R or 3000-8RGroup1  V OUT2  0 V1  DATA 02  DATA 13  OUT 14  OUT 2PB PAPositive RedNegative BlackReserved OrangeReserved GreenReserved BrownCDXIV TX WhiteCDXIV RX BlueCardax IV ReaderPositive RedNegative BlackReserved OrangeReserved GreenReserved BrownCDXIV TX WhiteCDXIV RX BlueCardax IV ReaderNote: Within each group, you cannot mix Cardax IV readers with Wiegand Readers.  This is because connecting one Wiegand reader requires all four pins on plug PB.  For example, if you connect a Cardax IV reader to Port 1 of Group 1, Port 2 of Group 1 can only connect to another Cardax IV reader.
R5  |  Part Number: 3E2512  |  9   Installation Note  |  Gallagher T12 ReaderTechnical SpecicationsTechnical SpecicationsRoutine maintenance: Not applicable for this readerCleaning: This reader should only be cleaned with a clean, lint free, damp clothPower required: Voltage:  9Vdc - 16VdcCurrent (at 12Vdc):  89mA (standby) Standard variant   124mA (peak) Standard variant  88mA (standby) Multi Tech variant   140mA (peak) Multi Tech variantEnvironmental: Temperature Range:  -30°C to +70°C Note: Direct sunlight may increase the internal reader temperature above the ambient temperature level.Humidity:  95% non-condensingEnvironmental Protection:  IP68Impact Rating:  IK07Approvals and StandardsThis product complies with the environmental regulations for the Restriction of Hazardous Substances in electrical and electronic equipment  (RoHS).    The  RoHS  directive  prohibits  the  use  of electronic equipment containing certain hazardous substances in the European Union.This symbol on  the product or its packaging indicates that this product must not be disposed of with other waste.  Instead, it is your responsibility to dispose of your waste equipment by handing it over to a designated collection point for the recycling of waste electrical and electronic equipment.  The separate collection and recycling  of  your  waste  equipment  at  the  time  of  disposal  will help conserve natural resources and ensure that it is recycled in a manner that protects human health and the environment.  For more information about where you can drop off your waste equipment for recycling, please contact your local city recycling office or the dealer from whom you purchased the product.          ACN 002 132 943
10   |  Part Number: 3E2512  |  R5Installation Note  |  Gallagher T12 ReaderFCC This device complies with part 15 of the FCC Rules. Operation is  subject  to  the  following  two  conditions:  (1)  This  device  may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.Note:  Changes  or  modifications  not  expressly  approved  by Gallagher Group Limited could void the user’s authority to operate this equipment.
Drill Template35mm (1.38 inches)26mm (1 inch) 29mm (1.41 inches)86mm (3.39 inches)13mm (1/2 inch) diameter hole for cable86mm (3.39 inches)25mm (1 inch)25mm (1 inch)15mm22.3mm (0.88 inches)40mm (1.57 inches)(0.59 inches)