Gallagher Group C30040XA Prox Readers T10 Mifare and T10 Mifare PIV User Manual

Gallagher Group Ltd Prox Readers T10 Mifare and T10 Mifare PIV Users Manual

Users Manual

Download: Gallagher Group C30040XA Prox Readers T10 Mifare and T10 Mifare PIV User Manual
Mirror Download [FCC.gov]Gallagher Group C30040XA Prox Readers T10 Mifare and T10 Mifare PIV User Manual
Document ID3138770
Application IDKEYmFu/bNz9iAG99WGZYew==
Document DescriptionUsers Manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize33.77kB (422178 bits)
Date Submitted2016-09-20 00:00:00
Date Available2016-09-21 00:00:00
Creation Date2016-08-23 12:06:32
Producing SoftwareAdobe PDF Library 15.0
Document Lastmod2016-08-23 12:06:34
Document TitleUsers Manual
Document CreatorAdobe InDesign CC 2015 (Windows)

Gallagher
T10 Reader
Installation Note
T10 Mifare Reader Black: C300400
T10 Mifare Reader White: C300401
T10 PIV Reader Black: C305400
T10 PIV Reader White: C305401
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
Page 1
Disclaimer
This document gives certain information about products and/or services provided by Gallagher Group Limited
or its related companies (referred to as "Gallagher Group").
The information is indicative only and is subject to change without notice meaning it may be out of date at any
given time. Although every commercially reasonable effort has been taken to ensure the quality and accuracy
of the information, Gallagher Group makes no representation as to its accuracy or completeness and it should
not be relied on as such. To the extent permitted by law, all express or implied, or other representations or
warranties in relation to the information are expressly excluded.
Neither Gallagher Group nor any of its directors, employees or other representatives shall be responsible
for any loss that you may incur, either directly or indirectly, arising from any use or decisions based on the
information provided.
Except where stated otherwise, the information is subject to copyright owned by Gallagher Group and you may
not sell it without permission. Gallagher Group is the owner of all trademarks reproduced in this information.
All trademarks which are not the property of Gallagher Group, are acknowledged.
Copyright © Gallagher Group Ltd 2016. All rights reserved.
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
Page 2
Contents
Introduction...................................................................................................................................... 4
Before you begin............................................................................................................................... 4
Distance between readers................................................................................................................ 7
Installation........................................................................................................................................ 7
LED indications.................................................................................................................................. 9
Accessories..................................................................................................................................... 10
Technical specifications................................................................................................................... 10
Approvals and standards................................................................................................................. 11
Mounting dimensions..................................................................................................................... 12
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
Page 3
1
Introduction
The Gallagher T10 Reader is a smart card proximity reader. It can be installed as either an entry reader
or exit reader. The reader sends information to the Gallagher Controller and acts upon information sent
from the Gallagher Controller. The reader itself does not make any access decisions.
The reader is available in four variants. The card technologies for each variant are shown below.
Reader
Product codes
Supported card technologies
T10 Mifare Reader Black
T10 Mifare Reader White
C300400
C300401
Mifare DESFire EV1, Mifare Plus and
Mifare Classic
T10 PIV Reader Black
T10 PIV Reader White
C305400
C305401
PIV, PIV-I, Mifare DESFire EV1, Mifare
Plus and Mifare Classic
The reader can be connected as an HBUS Reader or Cardax IV Reader. An HBUS Reader uses the HBUS
communications protocol to communicate with the Gallagher Controller. A Cardax IV Reader uses the
Cardax IV Reader communications protocol to communicate with the Gallagher Controller.
IMPORTANT: HBUS compatibility
HBUS communications are supported with sites running Gallagher Command Centre vEL7.00 software
(or later).
IMPORTANT: PIV readers
Gallagher PIV readers connect to the Gallagher Controller 6000 High Spec PIV (C305101) only (referred
to as the Controller). Gallagher PIV readers can only be used with sites running Gallagher Command
Centre vEL7.10 software (or later). Gallagher PIV readers are connected as HBUS Readers only.
Before you begin
2.1
Shipment contents
Check the shipment contains the following items:
2.2
•
1 x Gallagher T10 Reader facia assembly
•
1 x Gallagher T10 Reader bezel
•
1 x M3 Torx Post Security screw
•
2 x 25 mm No.6 self tapping, pan head, Phillips drive fixing screws
•
2 x 40 mm No.6 self tapping, pan head, Phillips drive fixing screws
Power supply
The Gallagher T10 Reader is designed to operate over a supply voltage range of 9 - 16 Vdc
measured at the reader terminals. The operating current draw is dependant on the supply
voltage at the reader. The power source should be linear or a good quality switched-mode
power supply. The performance of the reader may be affected by a low quality, noisy power
supply.
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
Page 4
2.3
Cabling
The Gallagher T10 Reader requires a minimum cable size of 4 core 24 AWG (0.2 mm2) stranded
security cable. This cable allows the transmission of data (2 wires) and power (2 wires). When
using a single cable to carry both power supply and data, both the power supply voltage drop
and data requirements must be considered. Although the reader is specified to operate at 9
Vdc, for good engineering design it is recommended that the voltage at the reader should be
approximately 12 Vdc.
HBUS cabling topology
The HBUS communications protocol is based on the RS485 standard and allows the reader to
communicate over a distance of up to 500 m (1640 ft).
The cabling between HBUS devices should be done in a "daisy chain" topology, (i.e. A "T" or
"Star" topology should not be used between devices). Should "Star" or "Home-Run" wiring be
required, the HBUS 4H/8H Modules and the HBUS Door Module allow multiple HBUS devices to
be individually wired to the one physical location.
The end devices on the HBUS cable should be terminated using 120 ohms resistance. To
terminate the Gallagher Controller 6000, connect the supplied on-board termination jumpers
to the Controller. To terminate a reader, connect the orange (termination) wire to the green
(HBUS A) wire. Termination is already included at the HBUS Module, (i.e. each HBUS port is
permanently terminated at the module).
HBUS
Device
HBUS
Device
HBUS
Device
"T" or "Star" circuits are
not permitted between
HBUS devices
HBUS
Device
HBUS
Device
Controller 6000
Connect the on-board
termination jumper
Terminate
HBUS
Device
HBUS
Device
RS485 1
HBUS
Device
Terminate
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
"T" or "Star" circuits are
not permitted between
HBUS devices
RS485 1
Controller 6000
Remove the on-board
termination jumper
HBUS
Device
HBUS
Device
Terminate
Page 5
HBUS
Device
"T" or "Star" circuits are
not permitted between
HBUS devices
Controller 6000
HBUS
Device
H1
H5
HBUS
Device
H4
H8
HBUS
Device
HBUS Module
Terminate
HBUS
Device
Terminate
HBUS
Device
HBUS
Device
Terminate
Terminate
Cable distance
Cable type
Cable format*
CAT 5e or
better**
HBUS
single reader
connected using
data only in a
single cable
Cardax IV
single reader
connected using
data only in a
single cable
HBUS/Cardax IV
single reader
connected using
power and data
in a single cable
4 twisted pair
500 m (1640 ft)
Each 2 x 0.2 mm2
(24 AWG)
200 m (650 ft)
100 m (330 ft)
BELDEN 9842** 2 twisted pair
500 m (1640 ft)
(shielded)
Each 2 x 0.2 mm2
(24 AWG)
200 m (650 ft)
100 m (330 ft)
SEC472
4 x 0.2 mm2
Not twisted
pairs (24 AWG)
400 m (1310 ft)
200 m (650 ft)
100 m (330 ft)
SEC4142
4 x 0.4 mm2
Not twisted
pairs (21 AWG)
400 m (1310 ft)
200 m (650 ft)
150 m (500 ft)
* The matching of wire sizes to equivalent wire gauges are only approximate.
** Recommended cable types for optimal HBUS RS485 performance.
Notes:
•
Shielded cable may reduce the obtainable cable length. Shielded cable should be
grounded at the Controller end only.
•
If other cable types are used, operating distances and performance may be reduced
depending on the cable quality.
•
HBUS allows up to 20 readers to be connected to a single cable. Each reader requires at
least 9 Vdc to function correctly. The cable length and the number of readers connected
will have an impact on the voltage at each reader.
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
Page 6
3
Distance between readers
The distance separating any two proximity readers must not be less than 200 mm (8 in) in all directions.
When mounting a proximity reader on an internal wall, check that any reader fixed to the other side of
the wall is not less than 200 mm (8 in) away.
200 mm
200
mm
Installation
ATTENTION: This equipment contains components that can be damaged by
electrostatic discharge. Ensure both you and the equipment are earthed before
beginning any servicing.
The Gallagher T10 Reader is designed to be mounted on any solid flat surface. However installation on
metal surfaces, particularly those with a large surface area will reduce read range. The extent to which
the range is reduced will depend upon the type of metal surface.
The recommended mounting height for the reader is 1.1 m (3.6 ft) from the floor level to the centre of
the reader device. However this may vary in some countries and you should check local regulations for
variations to this height.
1.
Use the reader bezel as a guide to drill all three holes. Drill the 13 mm (1/2 inch) diameter centre
hole (this is the centre hole for which the building cable will exit the mounting surface) and the
two fixing holes.
2.
Run the building cabling out through the centre hole and through the reader bezel.
3.
Secure the bezel to the mounting surface using the two fixing screws provided. It is important
the bezel of the reader is flush with and tight against the mounting surface.
Note: It is strongly recommended that you use the screws provided. If an alternative screw is
used, the head must be no larger nor deeper than that of the screw provided.
Note: Ensure the centre hole allows the cable to run freely out through the mounting surface, so
that the reader facia can clip into the bezel.
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
Page 7
No. 6 pan head screw
Bezel
Building cable
No. 6 pan head screw
4.
Connect the reader tail extending from the facia assembly to the building cable. Connect the
wires for the appropriate reader you wish to interface, either an HBUS Reader or a Cardax IV
Reader, as shown.
Note: Gallagher PIV readers must be connected as HBUS Readers. Gallagher PIV readers connect
to the Gallagher Controller 6000 High Spec PIV (C305101) only.
An HBUS Reader connects to a Gallagher Controller 6000, Gallagher 4H/8H Module (attached to
a Controller 6000) or a Gallagher HBUS Door Module (connected to a Controller 6000).
A Cardax IV Reader connects to a Gallagher Controller 6000, Gallagher 4R/8R Module (attached
to a Controller 6000), Gallagher GBUS Universal Reader Interface (Gallagher GBUS URI), Gallagher
Controller 3000-8R or 3000-4R, Gallagher Local Bus Universal Reader Interface (Gallagher URI) or
a Gallagher Local Bus Reader I/O Interface.
Positive
Negative
HBUS Termination
HBUS A
HBUS B
CDXIV TX
CDXIV RX
Red
Black
Orange
Green
Brown
White
Blue
HBUS Reader terminated:
HBUS Reader
HBUS Reader
HBUS Reader connection:			
Positive
Negative
HBUS Termination
HBUS A
HBUS B
CDXIV TX
CDXIV RX
Red
Black
Orange
Green
Brown
White
Blue
Note: To terminate an HBUS Reader, connect the Orange (HBUS Termination) wire to the Green
(HBUS A) wire.		
Cardax IV Reader
Cardax IV Reader connection:
Positive
Negative
HBUS Termination
HBUS A
HBUS B
CDXIV TX
CDXIV RX
Red
Black
Orange
Green
Brown
White
Blue
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
Page 8
5.
Fit the facia assembly into the bezel by clipping the small lip, into the top of the bezel and holding
the top, press the bottom of the facia assembly down into the bezel.
6.
Insert the M3 Torx Post Security screw (using a T10 Torx Post Security screwdriver) through the
hole at the bottom of the bezel to secure the facia assembly.
Note: The Torx Post Security screw needs only to be lightly tightened.
Reader tail
Building cable
Facia
Connection
Fit screw to secure facia to bezel
7.
Removal of the facia assembly is a simple reversal of these steps.
8.
Configure the reader in Command Centre. If the reader is connected as an HBUS Reader, refer to
the topic "Configuring HBUS Devices" in the Command Centre Configuration Client Online Help.
If the reader is connected as a Cardax IV Reader, refer to the topic "Creating Readers" in the
Command Centre Configuration Client Online Help.
LED indications
LED (squiggle)
HBUS indication
3 Flash (Amber)
No communications with the Controller.
2 Flash (Amber)
Communications with the Controller, but reader is not configured.
1 Flash (Amber)
Configured to a Controller, but reader is not assigned to a door or elevator car.
On (Green or Red)
Fully configured and functioning normally.
Green = Access mode is Free
Red = Access mode is Secure
Flashes Green
Access has been granted.
Flashes Red
Access has been denied.
Flashes (Blue)
Reading and validating a PIV card.
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
Page 9
6
LED (squiggle)
Cardax IV indication
3 Flash (Amber)
No communications with the Controller.
On (Green or Red)
Fully configured and functioning normally.
Green = Access mode is Free
Red = Access mode is Secure
Flashes Green
Access has been granted.
Flashes Red
Access has been denied.
Accessories
Accessory
Product Code
Accessory
Product Code
T10 Dress Plate, Black, Pk 10
C300320
T10 Spacer, Black, Pk 10
C300300
T10 Bezel, Black, Pk 10
C300280
T10 Spacer, White, Pk 10
C300301
T10 Bezel, White, Pk 10
C300281
T10 Protective Cover Spacer
C300310
T10 Bezel, Silver, Pk 10
C300282
T10 Protective Cover
C300270
T10 Bezel, Gold, Pk 10
C300283
T10 Dress Plate Black - Pack 10
C300320
Technical specifications
Routine maintenance:
Not applicable for this reader
Cleaning:
This reader should only be cleaned with a clean, lint free, damp cloth
Voltage:
9 Vdc - 16 Vdc
Current:
Idle 1
Maximum 2
at 9 Vdc
110 mA
158 mA
at 13.6 Vdc
74 mA
105 mA
Temperature range:
-35 °C to +70 °C Note: Direct sunlight may increase the internal
reader temperature above the ambient temperature level
Humidity:
0 - 95% non-condensing 3
Environmental protection:
IP68
Impact rating:
IK07
Unit dimensions:
Height 115 mm (4.5 inches)
Width 35 mm (1.4 inches)
Depth 12 mm (0.5 inches)
Maximum number of readers
on one HBUS cable:
20
The reader is idle.
Peak current during card read.
Gallagher T Series readers are UL humidity tested and certified to 85% and have been independently
verified to 95%.
Note: The current values stated above have been reported using the default configuration for a reader
in Command Centre. Changing the configuration may vary the current value.
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
Page 10
8
Approvals and standards
This symbol on the product or its packaging indicates that this product must not be disposed
of with other waste. Instead, it is your responsibility to dispose of your waste equipment by
handing it over to a designated collection point for the recycling of waste electrical and electronic
equipment. The separate collection and recycling of your waste equipment at the time of disposal
will help conserve natural resources and ensure that it is recycled in a manner that protects human
health and the environment. For more information about where you can drop off your waste
equipment for recycling, please contact your local city recycling office or the dealer from whom
you purchased the product.
FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
Note: Changes or modifications not expressly approved by Gallagher Limited could void the user's
authority to operate this equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of
the following measures:
•
Reorient or relocate the receiving antenna.
•
Increase the separation between the equipment and receiver.
•
Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
•
Consult the dealer or an experienced radio/TV technician for help.
Industry
Canada
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to
the following two conditions: (1) this device may not cause interference, and (2) this device must
accept any interference, including interference that may cause undesired operation of the device.
Industrie
Canada
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio
exempts de licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil
ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage
radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.
ETSI EN 300 330-2 V1.5.1:2011
EN50130-4:2011
US - Equipment: com, burg and acc reader
CA - Equipment: com, burg reader
Please refer to the document “3E2793 Gallagher Command Centre UL Configuration Requirements” for a guide
to configuring the Gallagher system to the appropriate UL Standard.
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
Page 11
Mounting dimensions
13 mm (1/2") diameter
hole for cable
44 mm (1.73")
40 mm (1.57")
115 mm (4.53")
40 mm (1.57")
22.5 mm (0.89")
35 mm (1.38")
IMPORTANT
This picture is not to scale, therefore use the measurements provided.
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
Page 12

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
XMP Toolkit                     : Adobe XMP Core 5.6-c067 79.157747, 2015/03/30-23:40:42
Instance ID                     : uuid:34dbcf75-fb74-446c-881e-5d70487c353c
Original Document ID            : adobe:docid:indd:f96526b2-a0ce-11df-8595-adfd5648a1ab
Document ID                     : xmp.id:ca8a7d97-32a2-574e-8fb7-7514a545f6bd
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:5e20d0da-9262-b34e-afb8-68e117825b12
Derived From Document ID        : adobe:docid:indd:f96526b2-a0ce-11df-8595-adfd5648a1ab
Derived From Original Document ID: adobe:docid:indd:f96526b2-a0ce-11df-8595-adfd5648a1ab
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CC 2015 (Windows)
History Changed                 : /
History When                    : 2016:08:23 12:06:32+12:00
Create Date                     : 2016:08:23 12:06:32+12:00
Modify Date                     : 2016:08:23 12:06:34+12:00
Metadata Date                   : 2016:08:23 12:06:34+12:00
Creator Tool                    : Adobe InDesign CC 2015 (Windows)
Format                          : application/pdf
Producer                        : Adobe PDF Library 15.0
Trapped                         : False
Page Count                      : 12
Creator                         : Adobe InDesign CC 2015 (Windows)
EXIF Metadata provided by EXIF.tools
FCC ID Filing: M5VC30040XA

Navigation menu