Genie Gcl Mj Owner S Manual
Genie-Gcl-Mh-Owner-S-Manual genie-gcl-mh-owner-s-manual
2014-07-05
: Genie Genie-Gcl-Mj-Owner-S-Manual genie-gcl-mj-owner-s-manual genie pdf
Open the PDF directly: View PDF .
Page Count: 52
Download | |
Open PDF In Browser | View PDF |
111852.501539 GCL-MJ&MH ™ Medium Duty Operator JACKSHAFT/HOIST TensiBelt™ PROPER APPLICATION Door Type Operator Type HP/Max Door Weight Sectional Jackshaft/Hoist (Available in 1/2HP only) (Vertical Lift and Lift Clearance Type Rolling Steel (Sidemount, Chain Couple) Sectional = 620 lbs. Rolling Steel = 580 lbs. NOT FOR RESIDENTIAL USE This Installation Manual provides the information required to install, troubleshoot and maintain a GCL-MJ&MH™ Commercial / Industrial Door Operator. 08-12 Table of Contents Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 How to use this manual .......................................1.1 Safety Information & Instructions.....................2.1 Critical Installation Information........................3.1-3.2 Installation.................................................................4.1-4.7 Rolling Steel-Front of Hood.................................4.1-4.2 Wall Mount ...............................................................4.3 Sectional Side Mount Chain Couple ................4.4-4.6 Clutch and Brake Adjustment............................4.6 Hand Chain Installation........................................4.7 Wiring..........................................................................5.1-5.7 Line Voltage Wiring................................................5.1 Low Voltage Control Wiring................................5.2 External Wire Diagram ..........................................5.3 Wall Control ..............................................................5.4 Interlock Switches ..................................................5.5 Radio Control & Photocell Wiring.................... 5.6 Sensing Edge Wiring .............................................5.7 Important Safety Instructions............................5.8 Operator Setup Procedures ................................6.1-6.8 Control Panel............................................................6.1 Setting Constant Contact ....................................6.2 Setting Limit Travel ................................................6.3 Setting Limit Overrun ...........................................6.4 Monitored Reversing Devices.............................6.5 Max Run Timer.........................................................6.6 Setting the Mid-Stop.............................................6.7 Changing Open & Close Modes ........................6.8 GCL-MJ&MH Medium Duty Operator Section 7 Special Operator Features ..........................................7.1-7.2 Operator Cycle Count & Firmware Version...........7.1 Operator Type..................................................................7 2 Section 8 Troubleshooting.............................................................8.1-8.4 Display Operation ..........................................................8.1 Error Codes.......................................................................8.1-8.2 Run Codes.........................................................................8.2-8.3 LED Indicators .................................................................8.4 STB Indicators..................................................................8.5 Section 9 Service & Maintenance ................................................9.1 Section 10 Appendix A.............................................................. 10.1-10.9 Basic Operator Parts...........................................10.1-10.2 Basic Shaft Assembly Parts..............................10.3-10.4 Basic Electric Box Parts.........................................10.5 Appendix B, Screw Terminal Assignments.........10.6 Appendix C, LCD Display Readouts...................10.7-10.9 Run Codes.................................................................10.7 Error Codes............................................................ ... 10.8-10.9 Section 11 Warranty.........................................................................11.1 www.geniecompany.com 08-12 TOC Section 1: How to use this manual The 11 sections of this Installation Manual provide the information required to install, troubleshoot and maintain an GCL-MJ&MH™ commercial/industrial door operator. Section 2 Provides important defining information related to safety terminology used throughout this manual, as well as safety related instructions which must be followed at all times while doing any steps/tasks/instructions detailed in this manual. Section 3 Details pre-installation concerns/issues/decisions that are recommended to be considered and/or resolved prior to beginning any commercial door operator installation. WARNING Failure to correctly perform all steps in sections 4-6 can result in serious injury or death. Sections 4-6 Provide step by step installation and set-up instructions for the GCL-MJ&MH™ commercial door operator. Each section is written such that it must be followed in a step by step order to complete a successful installation. Sections 7-8 Detail important features and troubleshooting information for typical installation and normal operations that may occur. Sections 9-11 Provide related information on service and maintenance items, operator drawings for use in troubleshooting and service activities, along with important warranty and returned goods policy information. FOR ASSISTANCE CALL 1-800-843-4084 GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 1.1 Section 2: Safety Information & Instructions WARNING Commercial/Industrial Sectional and Rolling Steel Doors are large, heavy objects that move with the help of springs under high tension and electric motors. Since moving objects, springs under tension, and electric motors can cause injuries, your safety and the safety of others depend on you reading the information in this manual. If you have any questions or do not understand the information presented, call your nearest service representative. For the number of your local Genie® Dealer, call 800-OK-GENIE, and for Genie® Factory Technical Advice, call 800-843-4084. In this Manual, the words Danger, Warning, and Caution are used to stress important safety information. The word: DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION indicates a potentially hazardous situation which, if not avoided, may result in injury or property damage. The word NOTE is used to indicate important steps to be followed or important considerations. POTENTIAL HAZARD MOVING DOOR ELECTRICAL SHOCK HIGH SPRING TENSION GCL-MJ&MH EFFECT WARNING Could result in Serious Injury or Death WARNING Could result in Serious Injury or Death WARNING Could result in Serious Injury or Death Medium Duty Operator PREVENTION Do Not operate unless the doorway is in sight and free of obstructions. Keep people clear of opening while door is moving. Do Not allow children to play with the door operator. Do Not change operator control to momentary contact unless an external reversing means is installed. Do Not operate a door that jams or one that has a broken spring Turn off electrical power before removing operator cover. When replacing the cover, make sure wires are not pinched or near moving parts. Operator must be electrically grounded. Do Not try to remove, repair or adjust springs or anything to which door spring parts are fastened, such as, wood block, steel bracket, cable or any other structure or like item. Repairs and adjustments must be made by a trained service representative using proper tools and instructions. www.geniecompany.com IMPORTANT READ PRIOR TO ANY DOOR OPERATION 1. Read manual and warnings carefully. 2. Keep the door in good working condition. Periodically lubricate all moving parts of door. 3. If door has a sensing edge, check operations monthly. Make any necessary repairs to keep it functional. 4. AT LEAST twice a year, manually operate door. The Door should open and close freely. If it does not, the door must be taken out of service and a trained service representative must correct the condition causing the malfunction. 5. The Operator Motor is protected against overheating by an internal thermal protector. If the operator ceases to function because motor protector has tripped, a trained service technician may need to correct the condition which caused the overheating. When motor has cooled, thermal protector will automatically reset and normal operation can be resumed. 6. In case of power failure, the door can be operated manually by pulling the release cable to disconnect the operator drive system 7. Keep instructions in a prominent location near the pushbutton. 08-12 2.1 Section 3: Critical Installation Information Job Site Issues to Consider/Concerns The following list of items should be considered prior to selecting an operator for a given job site. 1-Available power supply. 2-Type of door. 3-Potential operator mounting obstructions. Items to consider include, but are not limited to: side room, room above door shaft, room below door shaft, available mounting surface integrity, power supply location, and convenient chain hoist and release cable positioning. 4-Size of door for appropriate operator torque and door travel speed selection. 5-Operator mounting environment. Items to consider include operator location and dampness, dustiness and corrosiveness of the location. 6-Door activation needs/requirements. Examples include 3 button control stations, 1 button control stations, radio controls, pull cords, loop detectors, photoelectric controls, key switches, etc. See “Entrapment Protection” section below. 7-Interlock switches are required under certain conditions for doors with pass doors and door locks. See page 5.5. 8-Accessory equipment. Examples are reversing edges and/or photocell beams (required for doors set to operate as momentary contact),, auxiliary control relays, warning lights, etc. ENTRAPMENT PROTECTION The installation of a fail safe external reversing device (such as a monitored reversing edge or photocell system, etc.) is required on all momentary contact electronically operated commercial doors. If such a reversing device is not installed, the operator will revert to a constant contact control switch for operation (Closing only). The Reversing Devices currently UL Approved with are: 1) MillerEdge ME, MT and CPT series monitored edge sensors used in combination with Timer-Close Module P/N OPABTCX.S, or OPAKMEIGX.S INTERFACE MODULE. 2) Residential Safe-T-Beam® Monitored Photocells from The Genie® Company, model OSTB-BX (P/N 38176R). 3) Series II Commercial Safe-T-Beam®, Monitored Photocells P/N OPAKPE.S. 4) Series II Commercial Safe-T-Beam®, NEMA4 Monitored Photocells P/N OPAKPEN4GX.S. WARNING: DO NOT apply line voltage until instructed to do so. CAUTION: Check working condition of door before installing the operator. Door must be free from sticking and binding. If equipped, deactivate any door locking device(s). Door repairs and adjustments, including cables and spring assemblies MUST be made by a trained service representative using proper tools and instructions. GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 3.1 ENTRAPMENT PROTECTION Section 3: Critical Installation Information The GCL-MJ&MH™ can be used with the following UL Approved entrapment devices in compliance with UL325 requirements active starting August 29, 2010. UNTIL ONE OF THESE MONITORED EXTERNAL ENTRAPMENT DEVICES IS INSTALLED, THE OPERATOR WILL NOT ALLOW MOMENTARY CONTACT OPERATION IN THE CLOSE DIRECTION. LISTED DEVICES ALLOWABLE DOOR WIDTH MillerEdge ME, MT and CPT series monitored edge sensors used in combination with ANY WIDTH Timer-Close Module or OPAKMEIGX.S Interface Module. 30 FEET 30 FEET 35 FEET Residential Safe-T-Beam® Monitored Photocells model OSTB-BX P/N 38176R. Commercial Photoeye Kit P/N OPAKPE.S NEMA4 Monitored Photocells P/N OPAKPEN4GX.S. Rolling Steel Door Chart (sq. ft.) Model HP L isUL ted STEEL, NON-INSULATED COUNTER DOOR STEEL, INSULATED GRILLES FIRESTAR 2” SLAT STL/SST ALUM. STL/SST 20GA. 126 GCL-MJ&MH 1/2 YES 197 246 246 338 394 394 148 148 197 300 200 N/A Note: Total door weight and not square footage is the critical factor in selecting the proper operator. These Sq.Ft. measurements are based on square doors, e.g. 16' x 16'. 16GA. 18GA. 20GA. 22GA. 24GA. 26GA. 18GA. 20GA. 22GA. ALUM. 126 FIRESTAR 3” SLAT INSULATED FIRESTAR 3” SLAT SHEET DOOR 22GA. 16GA. 18GA. 20GA. 22GA. 20GA. 22GA. 26GA . N/A N/A N/A N/A N/A N/A N/A 256 Unbalanced Fire Shutters have a maximum square footage of 52 for 22GA. steel and 42 for 20GA. steel. Sectional Door Chart (sq. ft.) Model HP UL L is ted GCL-MJ GCL-MH 1/2 Y es Door S eries -> Max. Mounting Door Type Weight (Lbs) TS 620 216 16GA. Flush Steel 170 216 ins. 16GA. Flush Steel Insulated 120 CommercialSteelInsulated&Non-Insulated 220 220 ins. 2415 2415 ins. 2411 20GA. 24GA. Nominal 20GA. 24GA. Ribbed Ribbed 24GA. Ribbed Ribbed Steel Steel Ribbed Steel Steel Insulated Insulated Steel 230 160 270 200 300 2411 ins. Nominal 24GA. Ribbed Steel Insulated 256 Thermomark Aluminum 200-20 5150 5200 451 452 PU/FIP PU/FIP PU/FIP PU/FIP Insulated Insulated Insulated 1/8" Glass 1/4" or 1/2" PU/FIP PU/FIP Raised Raised 2" Glass 1.38" Insulated Insulated Insulated 20GA. Panel Panel 1.38" 2" 1.38" 2" 1.38" Exterior 125 256 Thermospan 150 200 256 240 160 256 256 210 144 T=Trolley S=Jackshaft,SideMount C=Jackshaft,CenterMount Note: Total door weight, and not the square footage, is the critical factor in selecting the proper operator. Square footage measurements are based on "square doors." (Example=16' x 16') NOTE: Doors that require special windloading and wide doors, normally require increased strutting (reinforcement). Strutting doors can significantly increase door weight beyond weight shown. Consult Customer Service for the impact of wind load andstrutting on square foot limits. NOTE: "PU-FIP" stands for "polyurethane, foamed-in-place." If no notation is present, insulation is "polystyrene, layed-iin-place." GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 3.2 Section 3: Critical Installation Information IMPORTANT INSTALLATION INSTRUCTIONS WARNING To reduce the risk of severe injury or death: 1) READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS. 2) Install only on a properly operating and balanced door. A door that is operating improperly could cause severe injury. Have qualified service personnel make repairs to cables, spring assemblies and other hardware before installing the operator. 3) Remove all pull ropes and remove, or make inoperative, all locks (unless mechanically and/or electronically interlocked to the power unit) that are connected to the door before installing the operator. 4) Install the door operator at least 8 feet above the floor if the operator has exposed moving parts. 5) Do not connect the door operator to the power source until instructed to do so. 6) Locate the control station: (a) within sight of the door, (b) a minimum of 5 feet above the floor so that small children cannot reach it, and (c) away from all moving parts of the door. 7) Install the Entrapment Warning Placard next to the control station and in a prominent location. 8) For products having a manual release, instruct the end user on the operation of the manual release. GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 3.3 Section 4: Installation Rolling Steel/Grill Doors Front of Hood The Rolling Steel Door Operator can be assembled for right-hand or lefthand mounting Front of Hood. Each model can also be wall mounted (next pages). 1) Mounting hardware and instruction will be supplied based : on door specifications. (Typical mounting arrangements shown in figures 1 and 2.) 13-7/8" (OUTPUT SHAFT LENGTH) (WIDTH OF OPERATOR) 12" Figure 1 5-1/8" 11" Figure 2 8-3/4" 17" 3-1/2" 3-7/16" (OPERATOR SIDE ROOM REQ'D.)) GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 4.1 Front of Hood (continued) 5) Attach operator assembly to end plate as shown using hardware provided. Fig 3. NOTE: At this time, hand tighten only, the mounting bracket nuts where it attaches to the head plate. This allows for adjustment in order to tension the drive chain. Attach Operator to Door: Front of Hood. 1) Attach 12 tooth sprocket to operator output shaft. 2) Align keyways and insert key into sprocket and output shaft keyway. Do not tighten set screw at this time. 3) Attach door sprocket to door shaft. Do not tighten at this time. 4) Assemble chain using chain master link. 5) Place assembled chain over door shaft sprocket and around the 12 tooth sprocket. 6) Adjust operator position to remove slack from the chain. 7) Tighten operator mounting bracket nuts. 8) Tighten sprocket set screws. 24121C (Hex nut w/lkwshr, 5/16-18) 086420.0506 (Bolt, 5/16-18 x 3/4) 086420.0510 (Bolt, 5/16-18 x 1-1/4) 24121C (Hex nut w/lkwshr, 5/16-18) SOCKET BUTTON HEAD CAP SCREW IS FACTORY WELDED TO THE HEAD PLATE 080352.0714 (Hex nut, 7/16-14) FLAT WASHER Figure 3 112146.0001 (GMX Mounting Bracket) 111983.0001 (GMX Mounting Bracket) GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 4.2 Wall Mount The GCL-MJ&MH™ Rolling Steel unit can be wall mounted where necessary by using an optional “Wall Mount Kit.” (P/N 111011.0001.S). Fig.4. 1) Attach wall mount brackets to operator using the 4 mounting bolts and nuts supplied(Hand-tighten until later). Position the operator in the brackets as shown. 2) Attach 12 tooth sprocket to operator output shaft. 3) Align keyways and insert key into sprocket and output shaft keyway. Do not tighten set screw yet. 4) Attach door sprocket to door shaft. Do not tighten yet. 5) Assemble chain using chain master link. 6) Place assembled chain over door shaft sprocket and operator sprocket. 7) Raise or lower operator to remove slack from the chain. Ensure operator output shaft is parallel with door shaft. 8) Tighten operator mounting bracket nuts. 9) Align chain and secure operator to wall. 10) Tighten operator chain sprocket set screws. 11) Slide operator in the wall bracket mounting holes if necessary for fine adjust of chain tension. 15" (TYPICAL SIDE ROOM) Figure 4. 5" TO 3-3/4" 13-7/8" (OUTPUT SHAFT LENGTH) (WIDTH OF OPERATOR) VERTICALLY ALIGN SPROCKETS/CHAIN LOCK DOWN HOLES MUST BE USED TO ENSURE MAINTAINING OPERATOR POSITION 19-5/8" (HEIGHT OF OPERATOR JACKSHAFT VERSION The release cable must be attached before mounting the unit. RELEASE CORD GCL-MJ&MH Medium Duty Operator LOCK DOWN HOLES MUST BE USED TO ENSURE MAINTAINING OPERATOR POSITION www.geniecompany.com 12-1/4" TO 11" 08-12 4.3 Sectional Doors—Chain Couple The Wall Mount Operator can be assembled for right hand mounting above or below the door shaft. Fig.5A. NOTE: The operator output shaft extends 3-7/8" on each side of the operator frame. 1) Attach 12 tooth sprocket to operator output shaft. 2) Align keyways and insert key into sprocket and output shaft keyway. Do not tighten set screw at this time. 3) Attach door sprocket to door shaft. Do not tighten at this time. 4) Assemble chain using chain connecting link. 5) Place assembled chain over door shaft sprocket and operator sprocket. 6) Raise or lower operator to remove slack from the chain. 7) Be certain operator output shaft is parallel with door shaft. 8) Align chain and secure operator to wall or mounting pad. Fig.5B. 9) Tighten operator sprocket set screws. INSTALLATION TIP: While sprocket set screws are loose, if possible, manually operate door to help align chain. A properly tensioned drive chain should deflect no more than 1/2" when thumb pressure is applied mid-way between the 2 sprockets. While there is no hard and fast rule governing chain tension, it must be tight enough to prevent clicking, popping and jumping the teeth of the sprocket. The 1/2" guideline will insure sufficient tension. NOTE: If using slotted mounting holes to mount unit, you must use at least 2 lockdown holes in opposite corners to firmly mount unit to wall. Fig. 5B Figure 5A Figure 5B . GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 4.4 Chain Couple I For Hollow Counterbalance Door Shaft: 1) Use non-threaded hole in door shaft sprocket as a guide and drill a 3/8" diameter hole through one side of the door shaft. Fig. 6A. 2) Insert clevis pin through sprocket and shaft to hold sprocket in position. 3) Drill through opposite side of shaft to obtain proper hole alignment. Fig. 6B. 4) Insert clevis pin through both holes and secure with cotter pin. Fig. 6C. Figure 6A For Solid Counterbalance Door Shaft: L 1) Insert key into door shaft keyway. 2) Slide sprocket into place and secure with set screws. To Complete the Installation: If needed, realign operator sprocket with door sprocket. If you have excessive door shaft movement, an optional chain tension plate is available. Fig. 7A & 7B, pg 4.6. Figure 6B Figure 6C GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 4.5 Chain Couple Spreader Bracket Bracket is available as an optional kit, P/N 111005.0001.S Installation of optional chain spreader bracket: Fig 7A & 7B. 1) Place sprocket, upper plate and bearing assembly on door shaft as shown. 2) Place lower plate, bearing assembly and sprocket on operator shaft as shown. 3) Install door and operator sprockets and chain assembly as described on page 4.4. 4) Install bolts and nuts through plates. 5) Tighten and align chain and plate and secure operator to wall. 6) Tighten spreader bracket bolts. SPROCKET GOES ON FIRST DOOR SHAFT OPERATOR SHAFT SPROCKET GOES ON LAST Figure 7A GCL-MJ&MH PL Medium Duty Operator Figure 7B www.geniecompany.com 08-12 4.6 Clutch Adjustment Fig. 8 The o perators have a friction style clutch that can be adjusted. NOTE: The clutch is intended to provide protection for the door, the operator and associated equipment. It is not intended for entrapment protection. To Adjust the Clutch 1) Decrease the tension on the clutch until the operator will not lift the door. Turning the adjustment castle nut counter-clockwise will decrease tension and clockwise will increase tension. 2) Gradually increase tension until the operator will perform a complete open and close cycle without clutch slippage. 3) Insert a cotter pin through the adjustment castle nut and bend a leg of the cotter pin to hold it in place. NOTE: Periodically check the system for proper clutch action. If clutch starts to slip after working properly for some time , check manual operation of door BEFORE adjusting clutch. The door may not be operating freely or the counterbalance spring may need adjusting. Repairs and adjustments must be performed by a trained service representative using proper tools and instructions. Brake Adjustment Fig. 9 1) Loosen the Adjustment Bracket Lock Nut/Bolt. 2) Slide the Adjustment Bracket as needed to reach the desired spring tension. When properly adjusted, the pivot arm should move with very little effort. 3) Re-tighten the Adjustment Bracket Lock Nut/Bolt. GCL-MJ&MH Figure 8 Medium Duty Operator www.geniecompany.com Figure 9 BRAKE ADJUSTMENT LOCK NUT AND BOLT 08-12 4.7 Hand Chain & Keeper 1) Route the hand chain through the chain guide, around the pocket wheel and back through the chain guide. Fig.10. 2) Connect the hand chain ends together as shown in Fig 11. by twisting open the last link on one end of the chain, and slipping the last link on the opposite end onto the open link. 3) Twist open link closed again. 4) Mount chain keeper to wall in line with chain approximately 4 feet from floor. 5) Loop chain around keeper as shown. Fig. 12. Optional Padlock not provided. 6) Install release cable. Fig. 13. NOTE: To insure smooth operation, make sure there are no twist in the hand chain before connecting the link ends together. Figure 10 RELEASE CORD Figure 11 GCL-MJ&MH Medium Duty Operator Figure 13 Figure 12 www.geniecompany.com 08-12 4.8 Section 5: Wiring Line Voltage Wiring Fig. 1 WARNING • DO NOT apply power to operator until instructed to do so. • The Genie® Company recommends that line voltage wiring be performed by a qualified electrician. • Be sure that electrical power has been disconnected from the input power wires being connected to the operator prior to handling these wires. An appropriate lock-out / tag-out procedure is recommended. • Line voltage wiring must meet all local building codes. • Make sure operator voltage, phase and frequency nameplate ratings are identical to the job site line voltage ratings. • Input power wiring must be properly sized for the operators amperage rating located on the nameplate. • To reduce the risk of electric shock, make sure the chassis of this unit is properly grounded. LINE INPUT TERMINALS LINE GROUND Figure 1 1) Remove LINE VOLTAGE INPUT PLUG and install proper fittings and 1/2"conduit. 2) Route proper LINE VOLTAGE wires into operator. 3) Locate LINE INPUT terminals on circuit board. Using correct connectors, attach wires to LINE INPUTS, and GROUND terminal. Fig. 2. • Keep low voltage and line voltage wires separate. • Route all line voltage wires as shown. • Plug all unused conduit holes. GCL-MJ&MH Medium Duty Operator www.geniecompany.com HIGH VOLTAGE INPUT PLUGS LINE IN POWER CONNECTIONS L1/ 1 ROUTE LINE VOLTAGE WIRING IN SHADED AREA AS SHOWN Figure 2 N/ L2 120V LINE (HOT) NEUTRAL 240V LINE 1 LINE 2 GND 08-12 5.1 Low Voltage Control Wiring (general) Fig. 3 1) Connect all LOW VOLTAGE control circuit wires to this side of unit using 1/2" conduit or flexible convoluted tubing. Keep low voltage and line voltage wires separate. Route all low voltage control wiring as shown. This includes all control circuit wires such as wall controls, timers and single button input devices as well as radio control and safety circuit wiring. See Figs 2 through 13 in this section. RADIO CONTROL TERMINALS LOW VOLTAGE CONTROL WIRE TERMINALS % G% G C P C GP C GP H %O GH % O U N %U N Plug all unused conduit holes. NOTE: For a detailed description of control wire terminals see Appendix B. LOW VOLTAGE INPUT PLUGS ROUTE LOW VOLTAGE WIRING IN SHADED AREA AS SHOWN Figure 3 GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 5.2 External Wire Diagram PWR 20-40 VDC @ 315mA MAX CURRENT See Appendix B for detailed description of terminals. LINE IN CONTROL SIGNAL TERMINAL STRIP POWER CONNECTIONS L1/ L1 CLASS 2 SUPPLY 0-40 VDC OPEN N/ L2 120V LINE (HOT) NEUTRAL 240V LINE 1 LINE 2 CLOSE STOP GND ODC STB 1-BTN ODC STB N-O SAFETY N-O SAFETY EXT INTLK EXT INTLK EXTERNAL RADIO TERMINAL STRIP CLASS 2 SUPPLY 0-40 VDC PWR RAD GND 1-BTN STATION N/O REMOVE JUMPER IF STOP BUTTON IS USED GND REMOVE JUMPER WHEN INSTALLING EXTERNAL INTERLOCK KEY SWITCH STATION RELAY NOM + 24VDC N/O GND RADIO CARD READER OPEN N/O MULTIPLE 3-BUTTON STATION INSTALLATIONS REQUIRE THE STOP BUTTON TO BE WIRED IN SERIES. See Fig. 5, pg 5.4 SENSING EDGE SWITCH (DO NOT CONNECT 2-WIRE MONITORED SENSING EDGE SWITCH TO THESE INPUTS) O/C PULL SWITCH N/O + CLOSE 3-BUTTON STATION GCL-MJ&MH - OPAKMEIGX.S INTERFACE MODULE STOP + - THRU-BEAM PHOTOCELLS SERIES II SAFE-T-BEAM ® (STB) (CONNECT STB WIRES TO EITHER TERMINAL) Medium Duty Operator www.geniecompany.com MONITORED SENSING EDGE 08-12 5.3 Wall Control 1) For one 3 - button installation, make connections as shown in Fig. 4. 2) For a multiple 3 - button installations, make connections as shown in Fig. 5. 3) For single button accessory controls, make connections as shown in Fig. 6. NOTE: If an External STOP button is NOT being installed, a jumper wire must be installed between the "STOP" AND "GND" terminals as shown in Fig. 6. NOTE: Long Distance Relay Kit wiring is not required for long distance control runs and should not be used WARNING: Wall Control(s) must be located so that the door is within sight of the user and far enough from the door, or positioned, such that the user is prevented from coming in contact with the door while operating the controls. Attach the Warning placard adjacent to the Wall Control. Fig. 4A . Attach the Caution label adjacent to the Wall Control. Fig. 4B. Figure 5 WARNING: If momentary contact control is to be used, a monitored external reversing device such as a photocell system or sensing edge switch must be used. See pages 5.6-5.7 for installation of entrapment protection devices. Figure 4B Figure 4A Figure 4 Figure 6 Entrapment Warning Placard CAUTION This door is operated by a limited-duty operator. To prevent the motor protector from tripping, do not exceed 15 cycles of opening and closing per hour. NOT FOR RESIDENTIAL USE GCL-MJ&MH 11 735 Medium Duty Operator www.geniecompany.com 08-12 5.4 Interlock Switches CONTROL SIGNAL TERMINAL STRIP 1) Optional external interlock switches are required with some Sectional or Rolling Steel Doors to prevent the door from operating under certain conditions including the following: If the door is equipped with a functioning door lock, an interlock switch must be installed to prevent electric operation when the lock is engaged. If the door is equipped with a pedestrian pass-through door, an interlock switch must be installed at the pass-through door in order to prevent electrical operation when the pass-through door is open. OPEN CLOSE STOP GND 1 BTN ODC STB ODC STB NO SAFETY NO SAFETY EXT INTLK EXT INTLK SWITCH (N.O.) Pass door interlock: Should be open when door is open. Closed when door is closed. ANGLE NOTE: If External Interlock is used, THE JUMPER WIRE BETWEEN THE EXT INTLK TERMINALS MUST BE REMOVED. Switches must be set in the field. SWITCH (N.C.) GCL-MJ&MH Side lock interlock: Should be open when door is locked. Closed when door is unlocked. Medium Duty Operator Figure 7 www.geniecompany.com TRACK 08-12 STANDARD SLIDELOCK 5.5 Radio Control Installation Figure 8 1) For a 3-wire radio control installation, make connections as shown in Fig. 8. NOTE: PWR terminal supplies 20 – 40VDC. Radios used must be compatible with this voltage range. NOTE: If no voltage is present at PWR terminal, check fuse on circuit board. Series II Safe-T-Beam® Monitored Photocells 1) Monitored SERIES II (STB) photocells can be installed as shown in Fig. 9. Wiring to these photocells can be connected to either terminal (they are not polarity sensitive). (Troubleshooting in Section 8) NOTE: Monitored Sensing device must be installed or unit will be Constant Contact Close. WARNING : Actuating operator using constant contact on the CLOSE button will override external reversing devices, including photocells. Figure 9 CONNECT WIRES TO EITHER TERMINAL. (NOT POLARITY SENSITIVE) CONTROL SIGNAL LOCATED OUTSIDE ELECTRIC BOX PWR 20-40 VDC @ 300mA MAX CURRENT TERMINAL STRIP ODC ODC STB STB EXTERNAL RADIO TERMINAL STRIP CLASS 2 SUPPLY 20-40 VDC PWR RAD GND SERIES II (STB) RESDENTIAL SAFE-T-BEAM RELAY NOM +24VDC GND DOOR RADIO 2) To Mount Photocells: (Kit includes detailed Instructions). Determine location for mounting. They do not need to be directly adjacent to the door but must be somewhere along the wall where there will be an unobstructed line between them. Fig 10. Screws provided for mounting on soft material (wood, drywall, etc.) They must extend out away from the wall sufficiently that no door hardware breaks the plane of the photo-beam. Figure 10 Top o to flo f lens or. WARNING GCL-MJ&MH Medium Duty Operator www.geniecompany.com Figure 11 Blue N-O N-O SAFETY SAFETY REL NOM 24VDC + RECE VER PWR 20 40 VDC @ 250mA MAX CURRENT Yellow Commercial Non-Monitored Photocells 1) Nominal 24 Volt DC Commercial photocells with normally open contacts can be connected as shown in Fig. 11. NOTE: Blue wire supplies 20 – 40VDC. Photocells used must be compatible with this voltage range. NOTE: If no voltage is present at Blue wire, check fuse on circuit board. EXT RADIO CONNECTOR CONTROL SIGNAL TERMINAL STRIP Orange : Photocell systems provide entrapment protection when mounted near the doorway in such a way that the lower portion of an individual’s leg will break the photocell beam during normal walking conditions. RADIO GND + - TRANSM TTER - THRU-BEAM PHOTOCELLS 08-12 5.6 Sensing Edge Switch Installation Figure 12 shows an example of a typical sensing edge installation. Left hand side is shown but right hand is a mirror image of this. 1A) If wiring from sensing edge switch to operator is coiled cord or 2 wire jacketed cord: • Install junction box 12” above the center of the door opening on same side as sensing switch. • Secure one end of cord to junction box using a cable clamp. 1B) If connection is to be made through a take up reel cord: • Install on same side as sensing edge switch and above door opening and slightly to the side. • Install junction box adjacent to take up reel and route the stationary cord from the reel to the box and secure with a cable clamp. NOTE: Do not use a take-up-reel on a monitored edge. They have slip connections in them that momentarily break contact which causes false reversals. 2) Secure other end of cord (straight, coiled or reel) to sensing edge switch enclosure using a cable clamp. 3) Connect wires of cord to sensing edge switch using wire nuts or other suitable wire connectors. 4) Run a straight 2 wire cord from the junction box (Step 1) to the operator electrical box. • Secure using cable clamp on each end. 5) Join wires in cord from operator to wires in cord from switch using wire nuts or other suitable wire connectors. 6A) Monitored sensing or reversing edge connects to optional Timer-Close Module terminals shown in Fig. 13A. 6B) Monitored sensing edge connects to main cirsuit board ODC STB terminals using the optional OPAKMEIGX.S as shown in Fig. 13B. 7) Operate the door to make certain cord is free to travel and does not become snared during door opening or closing. • Check sensing edge switch for proper operation. WARNING: Actuating the operator using constant contact on the CLOSE button will override external reversing devices, including sensing edges or reversing edges. GCL-MJ&MH Medium Duty Operator www.geniecompany.com Figure 12 COIL TO CONTROL BOX SENSING EDGE JUNCTION BOX Figure 13A TIMER-CLOSE MODULE TERMINAL STRIP NOTE Monitored 2-wire sensing or reversing edge can only be used in combination with a Timer-Close Module. MON EDGE GND SENSING EDGE SWITCH Figure 13B MAIN CIRCUIT BOARD ODC ODC STB STB NOTE: Monitored sensing edge connects to main circuit board ODC STB terminals using optional OPAKMEIGX.S INTERFACE MODULE. NTERFACE MODULE 08-12 SENSING EDGE SWITCH 5.7 IMPORTANT SAFETY INSTRUCTIONS WARNING To reduce the risk of severe injury or death: 1) READ AND FOLLOW ALL INSTRUCTIONS. 2) Never let children operate or play with door controls. Keep the remote control (where provided) away from children. 3) Personnel should keep away from a door in motion and keep the moving door in sight until it is completely closed or opened. NO ONE SHOULD CROSS THE PATH OF A MOVING DOOR. 4) Test the door’s safety features at least once a month. After adjusting either the force or the limit of travel, retest the door operator’s safety features. 5) For products having a manual release, if possible, use the manual release only when the door is closed. Use caution when operating the release while the door is open. Weak or broken springs may cause the door to fall rapidly, causing severe injury or death. 6) KEEP DOOR PROPERLY OPERATING AND BALANCED. See Door Manufacturer’s Owner’s Manual. An improperly operating or improperly balanced door could cause severe injury or death. Have only trained door systems technicians make repairs to cables, spring assemblies and hardware. 7) SAVE THESE INSTRUCTIONS. GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 5.8 Section 6: Operator Setup Procedure Control Panel These operators include a full function control panel including a liquid crystal display (LCD), calibration keys and Open, Close and Stop keys for on board operator control.See Fig.1. The open, close and stop keys function as a 3-button wall control. The Display will show current operator conditions and calibration information. Due to limited character space,some displays will be abbreviated. See Appendix C (pgs.10.7-10.9) for full display descriptions. Operation Keys, operates unit like a 3-button wall station. Operator includes a non-volatile memory. The unit will remember all calibration settings plus error code and run code logs, if power is removed from unit. OPEN LCD DISPLAY NOTE: During Setup, refer to Caution Label for limited use (pictured on page 5.4). DANGER: After power is supplied to the operator, Do Not make contact with components inside the control panel except for the Keypad Keys. Fig. 1. CLOSE STOP Calibration & Run Mode Toggle Key. Control Operating Modes Operator control boards operate in two modes: Run Mode and Calibration Mode. The control board should normally operate in the Run Mode. The operator is calibrated in Calibration Mode. With the operator standing idle PRESS CAL/RUN TO TOGGLE BETWEEN OPERATING MODES. >***” (*** = current operating mode). CAL RUN Display Backlighting Toggle Key. SCROLL SET CLEAR SCROLL Scroll Keys, used in Calibration Mode. Set/Clear Key, used to reset and adjust calibration settings. Figure 1 NOTE: The CAL/RUN key will not toggle between operator modes while the operator is running. GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 6.1 Setting Constant Contact These operators are shipped from the factory with both open and close operating modes set to constant contact – stop (C – STP) If your unit is set to Momentary Contact (MOM) Open and/or CLOSE, reset the operating modes by taking the following steps: 1) Press CAL/RUN to enter calibration mode. Fig. 2. 2) Press SET/CLEAR until display reads “OPEN MODE > C-STP.” Fig. 3. 3) Press SCROLL (DN) until display reads “CLOSE MODE.” Fig. 4. 4) Press SET/CLEAR until display reads “CLOSE MODE > C-STP.” Fig. 5. OPEN MODE C-STP Figure 3 WARNING: If a monitored external reversing device is not used, then the operator will run Constant Contact Close. CLOSE MODE MOM Verify close mode is set to “C-STP”and NOT “C-REV”or “MOM” before continuing. 5) Press CAL/RUN to return to run mode. Figure 4 IDLE DOWN LIMIT CLOSE MODE C-STP Door closed operator standing by Figure 5 Figure 2 GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 6.2 Setting Limit Travel UP LIMIT TRAVEL NUT 1) Engage door to Operator. NOTE: Verify open and close operating modes are set to constant contact – Stop (C-STP). See page 6.2 for details. 2) Press CAL/RUN until operator is in run mode. 3) Press and hold OPEN Key on Control Panel. Run door to desired open position, release OPEN Key. 4) Push LIMIT LOCKING BAR away from Limit Sensors and turn Open Limit Travel Nut until travel nut arrow and open limit sensor arrow are aligned and the display reads “IDLE>UP LIMIT.” 5) Release the LIMIT LOCKING BAR and make sure bar seats completely into both Travel Nuts. Fig. 6. 6) Press and hold CLOSE key on Control Panel. Run door to within 2" above floor, release Close button. NOTE: If the operator stops while trying to set limits and the display reads “GDO shutdown>MRT / Hit key to reset,” see page 6.6 "Resetting Max Run Timers". 7) Push LIMIT LOCKING BAR away from Limit Sensors and turn Close Limit Travel Nut until travel nut arrow and close limit sensor arrow are aligned and the display reads “IDLE > DOWN LIMIT.” Fig. 7. 8) Run door fully Open and Closed with Open & Close Keys on control panel and make final adjustments as necessary to make sure that door opens fully and closes no more than 2" above the floor. GCL-MJ&MH Medium Duty Operator www.geniecompany.com LIMIT LOCKING BAR L MIT SENSOR ALIGNMENT ARROWS Figure 6 IDLE DOWN LIMIT Figure 7 08-12 6.3 Setting Limit Overrun WARNING: The Limit Overrun function will override external reversing devices, including photocells and sensing edges or reversing edges. Therefore,any externally connected devices will be disabled during that portion of the door travel controlled by the Limit Overrun function. The Down Limit Overrun function should be used to close the door no more than the final 2". A) The Limit Overrun setting is a matter of trial and error. The goal is to adjust the Limit Overrun until an appropriate seal is obtained between the bottom edge of the door and the floor. B) The Limit Overrun setting can be varied between 0 and 9. 0 - disables the Limit Overrun so that the door stops at the down limit switch setting. 9 - causes the greatest amount of door travel beyond the limit switch setting. Door should close gently with light tension on door cables,or minimal stacking on rolling steel slats. 1) Press CAL-RUN to enter calibration mode 2) Press scroll ( ) until the display reads “LIMIT OVERRUN >(0-9).” Fig. 8. 3) Press SET/CLEAR until the display reads the desired value. 4) Press the OPEN key to open the door a few feet,then release 5) Press the CLOSE key to close the door and hold until the operator stops. 6) Check the door seal and repeat steps 3-5 until the appropriate seal is obtained between the door and the floor. LIMIT OVERRUN 0 Figure 8 CAUTION: If proper seal cannot be obtained at a setting of 9, Reset the Limit Overrun back to 0 and reset the Down Limit position as described on pg. 6.3. Then adjust the Limit Overrun as instructed above. 7) Press CAL-RUN to return to run mode. GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 6.4 Monitored Reversing Devices ODC Safe-T-Beams® (OPTIONAL) 1) If operator is in RUN mode, press CAL/RUN RUNCAL to enter calibration mode. 2) Press SCROLL SCROLL (up or down) until display reads “ODC STB>ON” or “ODC STB>OFF” Figure 9. SET 3) Press SET/CLEAR CLEAR key to toggle between ON and OFF. 4) Press SCROLL SCROLL (up or down) to shift to a new function and lock setting. 5) Press CAL/RUN RUNCAL to return to run mode. NOTE: Installation of Series II Monitored Photocells DOES NOT make the operator unit legal for residential use. WARNING: Photocell systems provide entrapment protection when mounted near the doorway in such a way that the lower portion of an individuals leg will break the photocell beam during normal walking through the doorway. If an alternative mounting location is chosen, it must be approved by the facility owner. Current UL Approved Monitored Reversing Devices (See page 5.7) 1) MillerEdge ME and MT series monitored edge sensors used in combination with Timer-Close Module P/N OPABTCX.S or OPAKMEIX.S INTERFACE MODULE. 2) MillerEdge ME and MT series monitored edge sensors (Direct connect through STB inputs). (Direct connect through STB inputs). 3) Residential Safe-T-Beam® Monitored Photocells from The Genie® Company, model OSTB-BX (P/N 38176R). 4) Monitored Photocells (P/N OPAKPEN4GX.S.). GCL-MJ&MH Medium Duty Operator www.geniecompany.com OPEN ODC STB ON CLOSE STOP CAL RUN SCROLL SET CLEAR SCROLL Figure 9 08-12 6.5 Max Run Timer This operator will automatically set its maximum run timers (MRT) when the unit is run two full cycles from limit to limit, without stopping, in the run mode. The Max Run Timer is a feature that prevents the unit from running continuously in the event of a slipping clutch, etc. NOTE: The MRT’s are set to the time required to run from one limit to the other, plus 5 seconds (nominal). When the MRT is exceeded, the operator stops and may reverse. The operator will not respond to any command until it is reset by pressing one of the calibration keys or by cycling power to the unit. MAX RUN TMR CLR Resetting the Max Run Timers The Maximum Run timers can be reset using this procedure: 1) Press CAL/RUN to enter calibration mode. 2) Press Scroll ( ) until display reads “MAX RUN TMR > SET.” 3) Press SET/CLEAR until display reads “MAX RUN TMR > CLEAR.” FIG. 10. 4) Press CAL/RUN to return to run mode. 5) Cycle door fully open and fully closed (two full cycles) without stopping. Figure 10 NOTE: The Max Run Timers must be reset each and every time the travel limits are adjusted. CAUTION: The Mid-Stop feature must be turned off to properly set the maximum run timers. GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 6.6 Setting the Mid-Stop This operator includes a programmable Mid-Stop. This feature allows the operator to stop at a user selectable point when opening. It is used when operating very tall doors that seldom open to their full height. The Mid-Stop does not affect the operator when closing. 1) To operate door to full open position from mid-stop, press open button again. MID-STOP CLR NOTE: Setting of the MID-STOP should only be performed AFTER Travel Limit and Max Run Timer settings have been made. To set the Mid-Stop: 1) Press CAL/RUN to enter calibration mode. 2) Press the CLOSE key to close the door to the down limit. 3) Press SCROLL ( ) until the display reads “MID-STOP > CLEAR.” Fig. 11. NOTE: If the display reads MID-STOP > SET at this point, first clear the MID-STOP as described below then repeat steps 1-3 and continue. 4) Press the OPEN key to open the door and release the key when the door is at the desired Mid-Stop height. 5) Press the SET/CLEAR until the display reads “MID-STOP > SET.” 6) Press CAL/RUN to return to run mode. To clear the Mid-Stop: 1) Press CAL/RUN to enter calibration mode. 2) Press SCROLL ( ) until the display reads MID-STOP > SET. 3) Press SET/CLEAR until the display reads MID-STOP > CLR 4) Press CAL/RUN to return to run mode. GCL-MJ&MH Medium Duty Operator www.geniecompany.com Figure 11 08-12 6.7 Changing Open and Close Modes NOTE: Once the travel limit and safety modes have been set, the OPEN and CLOSE modes may be set for Momentary Contact if desired. OPEN MODE MOM WARNING If momentary contact control is to be used, a monitored external reversing device such as a photocell system or sensing edge switch must be used. NOTE: The radio control input will not operate when the open or close mode is set in the Constant Contact mode. Operating modes affect all control inputs and keys. . To set the OPEN mode: Fig. 12 1) Press CAL/RUN to enter the calibration mode. 2) Press SCROLL ( ) or ( ) until display reads “OPEN MODE > .” This displays current setting. 3) Press SET/CLEAR until the display reads the desired operating mode: C-STP = Constant contact is required to open door. Door will stop if button or key is released before operator reaches its limit. MOM = Momentary contact will cause door to open to limit. 4) Press CAL/RUN to return to run mode. To set the CLOSE mode: Fig. 13. 1) Press CAL/RUN to enter the calibration mode. 2) Press SCROLL ( ) or ( ) until display reads “CLOSE MODE > “. This displays current setting. 3) Press SET/CLEAR until the display reads the desired operating mode: C-STP = Constant contact is required to close door. Door will stop if button or key is released before operator reaches its limit. C-REV = Constant contact is required to close the door. Door will reverse automatically if close button or key is released before door reaches down limit. MOM = Momentary contact will cause door to close to limit. 4) Press CAL/RUN to return to run mode. GCL-MJ&MH Medium Duty Operator www.geniecompany.com Figure 12 CLOSE MODE MOM Figure 13 08-12 6.8 Section 7: Special Operator Features Operator Cycle Count Fig. 1 These operators include a built-in cycle counter that store the count with or without power to the operator. CYCLES 1 To view the Cycle Count: 1) Press CAL/RUN to enter calibration mode. 2) Press SCROLL ( ) or ( ) until display reads “CYCLES > .” This will display current cycle count. 3) Press CAL/RUN to return to run mode. Figure 1 Circuit Board Firmware Version Fig. 2 These operators can display the version number of the firmware used in the on-board micro-controller. GDO V# 4.00.1 To view this version number: 1) Press CAL/RUN to enter calibration mode. 2) Press SCROLL ( ) or ( ) until the display reads “GDO V# > .” This will display the current firmware version number. 3) Press CAL/RUN to return to run mode. GCL-MJ&MH Figure 2 Medium Duty Operator www.geniecompany.com 08-12 7.1 Operator Type Fig. 3 These operators are available for use in jackshaft or trolley configurations. The same control board is used for either configuration, however the control board must be set for the appropriate GDO configuration. A board set for trolley mode will not work in a jackshaft operator and vice-versa. NOTE: The GDO type is factory set. The installer should not have to set this feature. However, if the GDO type is inadvertently changed, or if a board needs to be replaced in the field, follow these instructions to set GDO type. GDO TYPE J-SHAFT 1) Press CAL/RUN to enter calibration mode. 2) Press SCROLL ( ) or ( ) until display reads “GDO TYPE > .” This will display the current GDO type. 3) Press SET/CLEAR until display indicates correct GDO type ( J-SHAFT or TROLLEY) 4) Press CAL/RUN to return to run mode. GCL-MJ&MH Medium Duty Operator www.geniecompany.com Figure 3 08-12 7.2 Section 8: Troubleshooting Display Operation in Run Mode The operators display their status on the LCD display. Each time the operator runs, stops, reverses or refuses to run, the display will indicate why the action did, or did not, take place. Once an error code has been generated, the operator will continue to display the error code while the operator is not running. This error code can be cleared by pressing the STOP button or STOP key on the keypad. The error code will automatically clear when the operator stops at the down limit. Error codes will continue to be stored in the operator’s Error Code Memory after they have been cleared from the display in the Run Mode. ERROR CODE 1 41 Figure 1 Error Codes To aid in troubleshooting problems, the operators include an error code memory that stores the last 10 error events.These codes are stored with or without power. The last error code detected is also displayed on the LCD until the stop button or key is pressed or the operator stops at the down limit. REV ONE BUTTON The error code memory stores the last 10 error codes in sequence. Once 10 codes are stored, the oldest code is erased to make room for the newest code. These codes are displayed in calibration mode. The display will flash the number of the error code and the 2-digit error code followed by a description of the error code. Fig. 1 & 2. Figure 2 GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 8.1 Error Codes (cont’) To view the error code memory: (Fig. 1 & 2) 1) Press CAL/RUN to enter calibration mode. 2) Press SCROLL ( ) or ( ) until display reads “ERROR CODE 1 >.” The display will begin flashing the error code number and 2-digit error code followed by its description. Reminder: Error code number 1 is the latest code generated. 3) Press SET/CLEAR. The display will now read “ERROR CODE 2 >.” (This is the error code which was generated before error code 1.) 4) Repeat step 3 until all 10 error codes have been displayed or move on to step 5 when ready. 5) Press CAL/RUN to return to run mode. RUN CODE 1 3C Figure 3 NOTE: For all error codes see Appendix C, Pages 10.8 - 10.9. Run Codes These operators also include a run code memory that stores the last 10 run events. These codes are stored with or without power. Each time the operator runs or stops, it generates a code that it stores in this memory (Why the operator ran or stopped). Used together with the error code memory, it becomes a powerful troubleshooting aid. The run code memory stores the last 10 error codes in sequence. Once 10 codes are stored, the oldest code is erased to make room for the newest code. These codes are displayed in calibration mode.The display will flash the number of the run code and the 2-digit run code followed by a description of the run code. Fig. 3 & 4. GCL-MJ&MH Medium Duty Operator www.geniecompany.com HALT DOWN LIMIT Figure 4 08-12 8.2 Run Codes (cont’) To view the run code memory: (Fig. 3 & 4) 1) Press CAL/RUN to enter calibration mode. 2) Press SCROLL ( ) or ( ) until display reads “RUN CODE 1 > .” The display will begin flashing the run code number and code followed by its description. Remember: run code number 1 is the latest code generated. 3) Press SET/CLEAR. The display will now read “RUN CODE 2 > .” (This is the run code which was generated before run code 1.) 4) Repeat step 3 until all 10 run codes have been displayed or move on to step 5 when ready. 5) Press CAL/RUN to return to run mode. NOTE: For all run codes see Appendix C, Page 10.7. TROUBLESHOOTING EXAMPLE USING RUN AND ERROR CODE MEMORIES. Fig. 5. 1. In Calibration Mode, display and write down each Run Code and Error Code stored in memory. 2. List as shown below. 3. Refer to Appendix C to interpret the codes. In this example, the operator was opened using the OPEN key on the keypad and stopped at the up limit. The OPEN wall button was then activated, causing the “6D” code to be generated since the operator could not open when it is already at the up limit. The CLOSE wall button was then activated, causing the operator to close. While closing, the Normally-Open (N-O) Safety Input was activated, causing the operator to stop and then reverse, stopping at the up limit. GCL-MJ&MH Medium Duty Operator Figure 5 ERROR CODES NUMBER CODE 1 2 3 4 5 45 6D 00 RUN CODES CODE REVERSED DUE TO ACTIVE N-O SAFETY INPUT STOPPED AT UP LIMIT WOULD NOT OPEN — ALREADY AT UP LIMIT STOPPED DUE TO ACTIVE N-O SAFETY INPUT CLOSED FROM CLOSE WALL BUTTON 00 STOPPED AT UP LIMIT 8 00 00 00 00 OPENED FROM OPEN KEY ACTIVATION 9 10 6 7 3D 35 20 3D 14 NUMBER 1 2 3 4 5 00 00 00 6 7 00 00 9 00 00 10 OPERATOR STORES “00” CODES IN UNUSED RUN AND ERROR CODE MEMORY LOCATIONS FROM THE FACTORY. AS ERROR OR RUN CODES ARE RECORDED, THE “00” CODES ARE REPLACED WITH VALID CODES 8 00 www.geniecompany.com 08-12 8.3 LED Indicators Fig. 6 These operators include a self-diagnostic circuit board using troubleshooting LED indicators to signal the technician of a problem. TROUBLESHOOTING LED’s HOIST EXTERNAL + 24 VOLTS STB INTERLOCK INTERLOCK DC ENABLE OFF ON TROUBLESHOOTING LED S STB ENAB + 24 VAC S B E AB + 24 V C E T I T K HO T I T K EXT INTLK HOIST INTLK DETAIL ON ON ON OFF ON ON OFF OFF ON OFF OFF OFF INDICATION STB DISABLED STB ENABLED NORMAL OPERATING CONDITION HOIST INTERLOCK SWITCH OPEN: 1) HOIST RELEASE NEEDS RESET. 2) HOIST INTERLOCK CONNECTOR NOT PLUGGED IN. 3) HOIST INTERLOCK DEFECTIVE. EXTERNAL INTERLOCK OPEN POWER SUPPLY PROBLEM: 1) CHECK AC POWER SUPPLY. 2) CHECK MAIN POWER FUSE. 3) CHECK SECONDARY FUSE (2A). Figure 6 GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 8.4 Monitored Photocell Self-diagnostic Troubleshooting Chart SOURCE (RED LED) SENSOR (GREEN LED) INDICATED CONDITION ON ON NORMAL OPERATION 1. POWER HEAD NOT POWERED OFF OFF 2. WIRING FROM POWER HEAD BAD ON 1. WIRING TO SOURCE MISSING OR BAD 2. POWER HAS BEEN INTERRUPTED 2 BLINKS, PAUSE (REPEAT) ON 1. BEAM NOT ALIGNED 2. BEAM OBSTRUCTED 3. SENSOR DEFECTIVE 2 BLINKS, PAUSE (REPEAT) OFF 3 BLINKS, PAUSE (REPEAT) ON 4 BLINKS, PAUSE (REPEAT) ON OFF REQUIRED ACTION NONE REQUIRED 1. CHECK BREAKERS, FUSES, PLUGS 2. CHECK WIRING FOR OBVIOUS SHORTS 1. CHECK WIRING 2. REMOVE POWER AND REAPPLY 1.CHECK ALIGNMENT 2. CHECK FOR OBSTRUCTION 3. CALL CUSTOMER SERVICE 1. WIRE TO SENSOR MISSING OR BAD 1. CHECK WIRING 2. CALL CUSTOMER SERVICE 2. SENSOR DEFECTIVE 1. SENSOR RECEIVING INTERFERENCE 1. ATTEMPT TO DETERMINE SOURCE OF INTERFERENCE 2. CALL CUSTOMER SERVICE 1. CALL CUSTOMER SERVICE 1. SOURCE NOT SENDING PULSES 2. CALL CUSTOMER SERVICE 2. SOURCE DEFECTIVE WARNING: Actuating the operator by using constant contact on the CLOSE button will override external reversing devices, including photocells. GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 8.5 Maintenance Schedule Section 9: Service and Maintenance The following table provides a schedule of recommended Service and Maintenance items to be completed by a trained service representative. CAUTION: Failure to perform the recommended Service & Maintenance may result in premature failure of the operator. SERVICE ITEM SERVICE INTERVAL (FREQUENCY) EVERY 6 MO. EVERY 12 MO. EVERY 36 MO. OR OR OR 5,000 CYCLES 10,000 CYCLES 30,000 CYCLES MANUAL OPERATION OF DOOR DRIVE CHAIN TENSION PHOTOCELL/ *SENSING EDGE OPERATION CLUTCH ADJUSTMENT BRAKE ADJUSTMENT CHECK FOR LOSE OR MISSING HARDWARE CHECK LIMIT POSITION GEAR TRAIN WEAR * ALL EXTERNAL REVERSING DEVICES SHOULD BE CHECKED MONTHLY. GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 9.1 Section 10: Appendix A PARTS LIST Basic Hoist Operator Parts 23 138 22 ITEM NO. PART NUMBER 1 167 159 164 161 160 21 135 137 21 168 37 165 127 133 22 23 37 39 125 127 128 129 130 131 132 133 134 135 136 137 138 159 160 161 164 165 167 168 110380.0001 110380.0002 110847.0001 110847.0002 110450.0001 110449.0001 108190.0001 110443.0001 110503.0001 110807.0001 111007.0001 8115B17 110809.0001 110807.0001 107978.0001 110502.0001 110522.0001 110521.0001 110808.0001 110549.0001 110824.0001 111051.0001 111051.0002 110803.0001 110804.0001 110805.0001.S 110425.0001 110425.0002 DESCRIPTION ELECTRIC MOTOR, 1/2HP, 120V ELECTRIC MOTOR, 1/2HP, 240V BRAKE SOLENOID, 115V BRAKE SOLENOID, 230V BRAKE BAND BRAKE RELEASE LEVER INTERLOCK SWITCH BRAKE PULLEY BRAKE RELEASE LINK BRAKE PIVOT BRACKET BRAKE RELEASE—CLEVIS PIN BRAKE RELEASE—SPEED NUT BRAKE RELEASE ROD RIVET BRAKE RELEASE ARM BRACKET RELEASE PULLEY HANDWHEEL RELEASE ARM BRAKE POST—FLOATING BRAKE POST—FIXED BRAKE ADJUSTMENT PLATE BRAKE SOLENOID COVER BRAKE RELEASE SPRING OPERATOR CHASSIS LEFT OPERATOR CHASSIS RIGHT OPERATOR CHASSIS SUPPORT BRACE SUPPORT BRACKET WIRE GUARD BRACKET LEFT MOUNTING BRACKET RIGHT MOUNTING BRACKET 129 39 134 136 1 GCL-MJ&MH Medium Duty Operator 161 132 130 131 125 www.geniecompany.com 128 08-12 10.1 Section 10: Appendix A Basic Jackshaft Operator Parts 23 138 22 PARTS LIST ITEM NO. PART NUMBER 1 SEE SEPARATE ILLUSTRATED PARTS BREAKDOWN FOR OUTPUT SHAFT ASSY 167 159 164 161 160 21 135 137 21 SEE SEPARATE ILLUSTRATED PARTS BREAKDOWN FOR INTERMEDIATE SHAFT ASSY 168 37 133 39 134 136 1 GCL-MJ&MH Medium Duty Operator 161 132 130 131 176 www.geniecompany.com 22 23 37 39 128 130 131 132 133 134 135 136 137 138 159 160 161 164 166 167 168 176 110380.0001 110380.0002 110847.0001 110847.0002 110450.0001 110449.0001 108190.0001 110443.0001 110815.0001 110867.0001 111143.0001 107978.0001 18586A04.S 110522.0001 110521.0001 110808.0001 110549.0001 110824.0001 111051.0001 111051.0002 110803.0001 111804.0001 110803.0001 110425.0001 110425.0002 110805.0001 DESCRIPTION ELECTRIC MOTOR, 1/2HP, 120V ELECTRIC MOTOR, 1/2HP, 240V BRAKE SOLENOID, 115V BRAKE SOLENOID, 230V BRAKE BAND BRAKE RELEASE LEVER INTERLOCK SWITCH BRAKE PULLEY BRACKET PIVOT RELEASE SPRING RELEASE BRACKET RELEASE PULLEY COLD HEADED PIN BRAKE POST—FLOATING BRAKE POST—FIXED BRAKE ADJUSTMENT PLATE BRAKE SOLENOID COVER BRAKE RELEASE SPRING OPERATOR CHASSIS LEFT OPERATOR CHASSIS RIGHT OPERATOR CHASSIS SUPPORT BRACE MOTOR MOUNT SUPPORT BRACE LEFT MOUNTING BRACKET RUGHT MOUNTING BRACKET WIRE GUARD 128 08-12 10.2 Appendix A (cont’) Basic Shaft Assembly Parts PARTS LIST 40 42 41 44 38 45 46 47 48 CLUTCH KIT 99 94 29 150 104 29 119 153 116 115 106 153 INTERMEDIATE SHAFT ASSEMBLY (HOIST) GCL-MJ&MH Medium Duty Operator ITEM NO. PART NO. 7 29 32 34 38 40 41 42 44 45 46 47 48 91 92 94 96 99 102 104 105 106 115 116 119 150 151 152 153 110478.0003 110813.0001 106064.0001 110872.0001 111125.0001 080401.0624 075197.0000 110472.0001 086649.0029 108015.0001 075193.0000 111037.0001 110881.0001 107967.0001 110876.0001 080415.0025 110313.0010 110463.0001 080340.0074 110543.0001 110545.0001 110391.0001 110313.0008 110818.0001 110313.0010 110465.0001.S 110482.0001 110819.0002 110819.0001 DESCRIPTION OUTPUT SHAFT INTERMEDIATE SHAFT BEARINGS OUTPUT SHAFT BUSHINGS HANDWHEEL CLUTCH PULLEY COTTER PIN CLUTCH SPRING SLOTTED CLUTCH NUT CLUTCH THRUST WASHER MOVABLE CLUTCH PLATE CLUTCH LINING CLUTCH DISC DOWEL PIN CHAIN GUARD BUSHING, .627 ID E-RING SPRING PIN, .250 X .188 INTERMEDIATE SHAFT SQUARE KEY STOCK, 3/16 SPRKT, 25T-40T, #35CH, 3/8P HANDWHEEL SPRING SPACER WASHER SPRING PIN, .188 DIA. x 1 38 WAVE WASHER SPRING PIN SPRCKT, 23T, #25CH, 1/4P, W/KEY SPRKT, 40T, #35CH, 3/8P PLAIN WASHER PLAIN WASHER www.geniecompany.com 32 7 106 104 106 151 102 106 32 152 150 102 OUTPUT SHAFT ASSEMBLY (DIRECT) 106 91 92 34 106 96 105 HANDWHEEL KIT 08-12 10.3 Appendix A (cont’) Basic Shaft Assembly Parts 3 4 5 6 7 8 9 10 11 12 PARTS LIST 13 INTERMEDIATE SHAFT ASSEMBLY (JACKSHAFT) ITEM NO. PART NO. 2 1 9 OUTPUT SHAFT ASSEMBLY (INDIRECT) 19 20 21 24 25 GCL-MJ&MH Medium Duty Operator 15 16 13 14 22 23 22 17 18 20 8 15 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 110472.0001 080401.0624 075197.0000 111324.0001.S 110881.0001.S 075193.0000 111037.0001 110819.0001 086649.0029 110392.0001 110387.0001 110817.0001 110813.0001 108015.0001 080415.0021 110818.0001 110389.0001 110816.0001 110460.0003 110819.0002 110478.0003 106064.0001 110482.0003 080415.0025 110818.0002 DESCRIPTION SLOTTED NUT, 5/8-11 COTTER PIN CLUTCH SPRING CLUTCH PULLEY ASSY DOWEL PIN CLUTCH LINING CLUTCH DISC PLAIN WASHER PLAIN WASHER INTERMEDIATE SHAFT SLIDER SPRKT & ENGAGEMENT PLATE BEARING MOVABLE CLUTCH DISC E-RING WAVE WASHER RELEASE SPRING ROUND END KEY, .188 X 1.500 SPRKT, 23T, #25CH, 1/4P, W/KEYWAY PLAIN WASHER OUTPUT SHAFT, W/KEYWAY BUSHING SPRKT, 40T, #35CH, 3/8P, W/KEYWAY E-RING WAVE WASHER 24 www.geniecompany.com 08-12 10.4 Appendix A (cont’) Basic Electric Box Parts 21 22 23 24 25 26 35 20 26 25 24 23 21 27 139 PARTS LIST 140 ITEM NO. PART NO. WIRING LAYOUT - HOIST 2 139 JACKSHAFT DIFFERENCE OR 13 2 17 12 GCL-MJ&MH 19 Medium Duty Operator www.geniecompany.com 110405.0001 110405.0002 12 112365.0001.S 13 110846.0001 110846.0002 17 110957.0001 19 110830.0001 110830.0002 20 111048.0001 21 109876.0003 22 110818.0003 23 077538.0000 24 110823.0001 25 110550.0001 26 110459.0001 27 601332.0001 35 111851.0001 15 080415.0021 139 110423.0001 140 110870.0001 08-12 DESCRIPTION ELEC BOX ASSY, 115V ELEC BOX ASSY, 230V KIT, PCB TRANSFORMER, 120V TRANSFORMER, 240V FUSE KIT CAPACITOR, 115V CAPACITOR, 230V LIMIT SHAFT E-RING WAVE WASHER BUSHING, 3/8/ID PUSH-ON RETAINING RING LIMIT TRIGGER TRAVEL NUT SPRKT, 14T, 1/4P, 3/8 BORE COVER ASSY, ELEC BX E-RING E-BOX HINGE E-BOX LATCH 10.5 Section 10: Appendix B Screw Terminal Assignments FUNCTION INPUT 11-POSITION TERMINAL BLOCK INSIDE ELECTRIC BOX OPEN CLOSE STOP GND 1-BTN ODC STB ODC STB N-O REVERSE N-O REVERSE EXT INTLK EXT INTLK 2-POSITION TERMINAL BLOCK (INSIDE ELECTRIC BOX) L1 / L1 N / L2 CONNECTION TYPE Causes door to open if not at Up Limit. Causes a closing door to reverse. Causes door to close if not at Down Limit. Causes a moving door to stop. Prevents the operator from running. Common ground connection for Open, Close, Stop &1-Btn Inputs. Causes door to open if not at Up Limit or Mid-Stop Limit. Causes door to close if at Up Limit or Mid-Stop Limit. Causes door to stop if opening. Causes a closing door to reverse. Reverses a closing door if photocell beam is blocked. NOTE: STB's must be enabled in Calibration Mode. Reverses a closing door if photocell beam is blocked. NOTE: STB's must be enabled in Calibration Mode. Causes a closing door to reverse. NOTE: Will not open a stopped door. Causes a closing door to reverse. NOTE: Will not open a stopped door. Causes a moving door to stop. Prevents the operator from running when contact is open. Operates even if microcontroller is non-functional. Causes a moving door to stop. Prevents the operator from running when contact is open. Operates even if microcontroller is non-functional. Power to operator. Power to operator. Normally-Open Dry Contact to GND. Normally-Open Dry Contact to GND. Normally-Closed Dry Contact to GND. Normally-Open Dry Contact to GND. ODC Series II Safe-T-Beams® ONLY to these inputs. (not polarity sensitive) ODC Series II Safe-T-Beams® ONLY to these inputs. (not polarity sensitive) Normally-Open 2-Wire Non-Monitored Edge Sensor. (not polarity sensitive) Normally-Open 2-Wire Non-Monitored Edge Sensor. (not polarity sensitive) Normally-Closed dry contacts. (board will energize these contacts at nominal +24VDC). Normally-Closed dry contacts. (board will energize these contacts at nominal +24VDC). 120VAC: Connect to Line (Hot) / 240VAC: Connect to Line 1. 120VAC: Connect to Neutral / 240VAC: Connect to Line 2. Other Connections RADIO AND ACCESSORIES PIGTAIL PLUG CONNECTIONS INSIDE ELECTRIC BOX Power for radio & other accessories. +20 to +40VDC, fused at 250mA (F1). Causes door to open if not at Up Limit or Mid-Stop Limit. Causes door to close if at Up Limit or Mid-Stop Limit. (Radio Input Control) Causes a closing door to reverse. Common ground connection for PWR and RAD terminals. GND EXPANSION PORT Connects accessory modules to operator. TRANSFORMER Connects main transformer to control board. Connects brake solenoid to control board. BRAKE Connects motor and capacitor to control board. MOTOR Causes moving door to stop. Prevents the operator from running. HOIST INTLK Operates even if microcontroller is non-functional. Causes door to stop at top and bottom of normal travel. LIMIT SENSOR PWR RAD GCL-MJ&MH Medium Duty Operator www.geniecompany.com Connect to radio or other accessory's power input. Connect to radio or other accessory's signal (output). Connect to radio or other accessory's ground input. Accessory Module Ribbon Cable. Transformer Plug. Brake Solenoid Plug. Motor Plug. Hoist Interlock Plug or Jumper. Limit Sensor Plug. 08-12 10.6 Section 10: Appendix C Display Run Codes Condition Code 0C 0D 0E 0F 10 11 12 13 14 20 21 22 24 2A 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F DISPLAY IDLE > DOWN LIMIT IDLE > UP LIMIT IDLE > MID STOP IDLE > NO LIMIT OPENING > OPEN BTN OPENING > ONE BTN OPENING > RADIO OPENING > AUX OPEN OPENING > OPEN KEY CLOSING > CLOSE PB CLOSING > ONE BTN CLOSING > RADIO CLOSING > CLOSE KP CLOSING > TCM CLS HALT > WALL BUTTON HALT > ONE BUTTON HALT > RADIO HALT > AUX. OPEN HALT > KEYPAD KEY HALT > N-O SAFETY HALT > ODC STB HALT > N-C SAFETY HALT > MON. EDGE HALT > DOOR FORCE HALT > LOSS OF C/C HALT > SHUTDOWN HALT > DOWN LIMIT HALT > UP LIMIT HALT > MID STOP HALT > MODULE FAIL GCL-MJ&MH Condition Code Description STANDING BY AT DOWN LIMIT (NOTE: THIS MESSAGE IS DISPLAYED IF BOTH LIMITS ARE ACTIVE) STANDING BY AT UP LIMIT STANDING BY AT MID-STOP LIMIT STANDING BY BETWEEN LIMITS OPENING FROM OPEN BUTTON OPENING FROM 1 BUTTON OPENING FROM RADIO OPENING FROM AUXILIARY OPEN INPUT OPENING FROM KEYPAD OPEN KEY CLOSING FROM CLOSE BUTTON CLOSING FROM 1 BUTTON CLOSING FROM RADIO CLOSING FROM KEYPAD CLOSE KEY CLOSING FROM TIMER CLOSE MODULE GDO STOPPED BECAUSE STOP OR OPEN BUTTON WAS ACTIVATED, POSSIBLY STARTING A REVERSAL GDO STOPPED BECAUSE 1 BUTTON WAS ACTIVATED, POSSIBLY STARTING A REVERSAL GDO STOPPED BECAUSE RADIO INPUT WAS ACTIVATED, STARTING A REVERSAL GDO STOPPED BECAUSE AUXILIARY OPEN INPUT WAS ACTIVATED, STARTING A REVERSAL GDO STOPPED BECAUSE KEYPAD STOP OR OPEN KEY WAS ACTIVATED, POSSIBLY STARTING A REVERSAL GDO STOPPED BECAUSE N-O REVERSING INPUT WAS ACTIVATED, STARTING A REVERSAL GDO STOPPED BECAUSE ODC STB WAS BLOCKED, STARTING A REVERSAL GDO STOPPED BECAUSE N-C REVERSING INPUT WAS ACTIVATED, STARTING A REVERSAL GDO STOPPED BECAUSE MONITORED EDGE SENSOR INPUT WAS ACTIVATED, STARTING A REVERSAL GDO STOPPED BECAUSE THE FORCE REQUIRED TO OPERATE THE DOOR WAS TOO HIGH, POSSIBLY STARTING A REVERSAL GDO STOPPED BECAUSE CONSTANT CONTACT ON THE CONTROL WAS REMOVED BEFORE REACHING A LIMIT, POSSIBLY STARTING A REVERSAL GDO STOPPED BECAUSE THE GDO DETECTED A FAULT SUCH AS AN OPEN INTERLOCK, OVERHEATED MOTOR, ETC. GDO STOPPED BECAUSE IT REACHED THE DOWN LIMIT GDO STOPPED BECAUSE IT REACHED THE UP LIMIT GDO STOPPED BECAUSE IT REACHED THE MID-STOP LIMIT GDO STOPPED BECAUSE AN EXPANSION MODULE WAS NOT WORKING PROPERLY Medium Duty Operator www.geniecompany.com 08-12 10.7 Display Condition Error Codes Code 40 41 42 43 44 45 46 47 48 49 4A 4B 4F 50 51 52 57 58 59 5A 5C 5D 60 61 62 63 64 65 66 67 68 69 6C 6D 6E 6F DISPLAY REV > REV > REV > REV > REV > REV > REV > REV > REV > REV > REV > REV > OPEN BUTTON ONE BUTTON RADIO AUX OPEN OPEN KEY N-O SAFETY ODC STB N-C SAFETY MON. EDGE DOOR FORCE LOSS OF C/C MAX RUN TMR REV > EXP MOD FAIL STOP > HOT MOTOR STOP > OPEN MRT STOP > CLOSE MRT STOP > OPEN INTLK STOP > WRONG GDO STOP > DOOR FORCE STOP > WRONG LIMIT STALL > DOWN LIMIT STALL > UP LIMIT CHECK STOP BTN TCM DISABLED NO RADIO >> C/C CHECK AUX OPEN CHECK STOP KEY CHECK N-O SAFETY CHECK ODC STB CHECK N-C SAFETY CHECK MON. EDGE OVERHEATED MOTOR NO RUN > DOWN LIM NO RUN > UP LIMIT NO RUN > MID STOP EXP MODULE FAIL GCL-MJ&MH Section 10: Appendix C Condition Code Description GDO REVERSED BECAUSE THE OPEN BUTTON WAS ACTIVATED GDO REVERSED BECAUSE THE 1 BUTTON WAS ACTIVATED GDO REVERSED BECAUSE THE RADIO INPUT WAS ACTIVATED GDO REVERSED BECAUSE THE AUXILIARY OPEN INPUT WAS ACTIVATED GDO REVERSED BECAUSE THE KEYPAD OPEN KEY WAS ACTIVATED GDO REVERSED BECAUSE THE N-O REVERSING INPUT WAS ACTIVATED GDO REVERSED BECAUSE THE ODC STB WAS BLOCKED GDO REVERSED BECAUSE THE N-C REVERSING INPUT WAS ACTIVATED GDO REVERSED BECAUSE THE MONITORED EDGE SENSOR WAS ACTIVATED GDO REVERSED BECAUSE THE FORCE REQUIRED TO CLOSE THE DOOR WAS TOO HIGH GDO REVERSED BECAUSE CONSTANT CONTACT ON THE CONTROL WAS REMOVED BEFORE REACHING THE DOWN LIMIT GDO REVERSED BECAUSE THE CLUTCH SLIPPED OR SOME OTHER FAULT OCCURRED THAT ALLOWED THE GDO TO RUN TOO LONG GDO REVERSED BECAUSE AN EXPANSION MODULE WAS NOT WORKING PROPERLY GDO STOPPED BECAUSE THE MOTOR WAS OVERHEATED GDO STOPPED BECAUSE THE CLUTCH SLIPPED OR SOME OTHER FAULT OCCURRED THAT ALLOWED THE GDO TO RUN OPEN TOO LONG GDO STOPPED BECAUSE THE CLUTCH SLIPPED OR SOME OTHER FAULT OCCURRED THAT ALLOWED THE GDO TO RUN DOWN TOO LONG GDO STOPPED BECAUSE THE HOIST INTERLOCK OR EXTERNAL INTERLOCK IS OPEN GDO STOPPED BECAUSE THE BOARD IS SET FOR JACKSHAFT MODE, BUT INSTALLED IN A TROLLEY OPERATOR GDO STOPPED BECAUSE THE FORCE REQUIRED TO OPEN THE DOOR WAS TOO HIGH GDO STOPPED BECAUSE THE UP LIMIT ACTIVATED WHEN CLOSING OR THE DOWN LIMIT ACTIVATED WHEN OPENING GDO STOPPED BECAUSE IT COULDN'T LEAVE THE DOWN LIMIT DUE TO A SLIPPING CLUTCH OR OTHER PROBLEM GDO STOPPED BECAUSE IT COULDN'T LEAVE THE UP LIMIT DUE TO A SLIPPING CLUTCH OR OTHER PROBLEM GDO WON'T RUN BECAUSE THE STOP BUTTON IS ACTIVE TIMER CLOSE WON'T WORK BECAUSE NO SAFETIES ARE ENABLED RADIO INPUT WON'T WORK WITH OPEN OR CLOSE FUNCTION IN CONSTANT CONTACT MODE GDO WON'T CLOSE BECAUSE AUXILIARY OPEN INPUT IS ACTIVE GDO WON'T RUN BECAUSE THE KEYPAD STOP KEY IS ACTIVE GDO WON'T CLOSE BECAUSE THE N-O REVERSING IS ACTIVE GDO WON'T CLOSE BECAUSE THE ODC STB IS BLOCKED GDO WON'T CLOSE BECAUSE THE N-C REVERSING INPUT IS ACTIVE GDO WON'T CLOSE BECAUSE THE MONITORED EDGE SENSOR IS ACTIVE GDO WON'T RUN BECAUSE THE MOTOR IS OVERHEATED GDO WON'T CLOSE BECAUSE ITS ALREADY AT THE DOWN LIMIT GDO WON'T OPEN BECAUSE ITS ALREADY AT THE UP LIMIT GDO WON'T RUN BECAUSE ITS AT OR ABOVE THE MID-STOP LIMIT & CAN'T RUN UP & A REVERSING INPUT IS PREVENTING IT FROM CLOSING GDO WON'T RUN BECAUSE AN EXPANSION MODULE FAILURE IS PREVENTING IT Medium Duty Operator www.geniecompany.com 08-12 10.8 Display Error Codes (cont’) Condition Code 70 71 74 75 76 77 80 81 82 83 84 85 86 88 8A 8E 8F 90 A0 A1 A2 A3 A4 A5 A6 A7 AA DISPLAY BOARD FAILURE 70 BOARD FAILURE 71 BOARD FAILURE 74 BOARD FAILURE 75 BOARD FAILURE 76 BOARD FAILURE 77 BOARD FAILURE 80 BOARD FAILURE 81 BOARD FAILURE 82 BOARD FAILURE 83 BOARD FAILURE 84 EXP PORT PROBLEM BOARD FAILURE 86 TCM FAILURE AOM FAILURE REV INTERRUPTED LIMIT MOD. FAIL DIAGNOSTIC MODE OPEN BTN BAD > PU CLOSE BTN BAD > PU ONE BTN BAD > PU RADIO BAD > PWR UP AUX OPEN BAD > PU OPEN KEY BAD > PU CLOSE KEY BAD > PU MULT KEYS BAD > PU TCM BAD > POWER UP GCL-MJ&MH Section 10: Appendix C Condition Code Description CONTROL BOARD FAILURE 70, CONTACT FACTORY TECHNICAL SERVICE DEPT. CONTROL BOARD FAILURE 71, CONTACT FACTORY TECHNICAL SERVICE DEPT. CONTROL BOARD FAILURE 74, CONTACT FACTORY TECHNICAL SERVICE DEPT. CONTROL BOARD FAILURE 75, CONTACT FACTORY TECHNICAL SERVICE DEPT. CONTROL BOARD FAILURE 76, CONTACT FACTORY TECHNICAL SERVICE DEPT. CONTROL BOARD FAILURE 77, CONTACT FACTORY TECHNICAL SERVICE DEPT. CONTROL BOARD FAILURE 80, CONTACT FACTORY TECHNICAL SERVICE DEPT. CONTROL BOARD FAILURE 81, CONTACT FACTORY TECHNICAL SERVICE DEPT. CONTROL BOARD FAILURE 82, CONTACT FACTORY TECHNICAL SERVICE DEPT. CONTROL BOARD FAILURE 83, CONTACT FACTORY TECHNICAL SERVICE DEPT. CONTROL BOARD FAILURE 84, CONTACT FACTORY TECHNICAL SERVICE DEPT. EXPANSION PORT IS SHORT CIRCUITED, TRY DISCONNECTING EXPANSION MODULES OR CONTACT FACTORY TECHNICAL SERVICE DEPT. CONTROL BOARD FAILURE 86, DISCONNECT EXPANSION MODULES. IF NO CHANGE, CONTACT FACTORY TECHNICAL SERVICE DEPT. TIMER CLOSE MODULE (TCM) HAS FAILED AUXILIARY OUTPUT MODULE (AOM) HAS FAILED GDO LOST POWER OR ENCOUNTERED ANOTHER PROBLEM DURING THE REVERSAL PROCESS, REVERSAL IS COMPLETING NOW GDO WON'T RUN, LIMIT MODULE HAS FAILED GDO IS IN DIAGNOSTIC MODE, NORMAL FUNCTIONS ARE NOT ALLOWED OPEN & CLOSE BUTTONS WON'T WORK, THE OPEN BUTTON WAS ACTIVE WHEN THE GDO WAS POWERED-UP OPEN & CLOSE BUTTONS WON'T WORK, THE CLOSE BUTTON WAS ACTIVE WHEN THE GDO WAS POWERED-UP 1 BUTTON WON'T WORK, THE 1 BUTTON WAS ACTIVE WHEN THE GDO WAS POWERED-UP RADIO INPUT WON'T WORK, THE RADIO INPUT WAS ACTIVE WHEN THE GDO WAS POWERED-UP AUXILIARY OPEN INPUT WON'T WORK, THE AUXILIARY OPEN INPUT WAS ACTIVE WHEN THE GDO WAS POWERED-UP KEYPAD OPEN & CLOSE KEYS WON'T WORK, THE OPEN KEY WAS ACTIVE WHEN THE GDO WAS POWERED-UP KEYPAD OPEN & CLOSE KEYS WON'T WORK, THE CLOSE KEY WAS ACTIVE WHEN THE GDO WAS POWERED-UP 1 OR MORE KEYPAD CALIBRATION KEYS WON'T WORK, 1 OR MORE WERE ACTIVE WHEN THE GDO WAS POWERED-UP TIMER CLOSE MODULE WON'T CLOSE DOOR, IT WAS ACTIVE WHEN THE GDO WAS POWERED-UP Medium Duty Operator www.geniecompany.com 08-12 10.9 THIS PAGE LEFT BLANK GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 11.1 SIGNATURE OF SELLER: DATE OF INSTALLATION: FACTORY ORDER #: SELLER S ADDRESS: SELLER: INSTALLATION ADDRESS ORIGINAL PURCHASER Claims under this warranty must be made promptly after discovery within the applicable warranty period and in writing to the Seller or to the authorized distributor or installer whose name and address appear below. The purchaser must allow Seller a reasonable opportunity to inspect any Product claimed to be defective prior to removal or any alteration of its condition. Proof of the purchase and/or installation date and identification as the original purchaser may be required. IN NO EVENT SHALL SELLER BE RESPONSIBLE FOR OR LIABLE TO ANYONE FOR SPECIAL INDIRECT COLLATERAL PUNITIVE INCIDENTAL OR CONSEQUENTIAL DAMAGES even if Seller has been advised of the possibility of such damages. Such excluded damages include but are not limited to loss of goodwill loss of profits loss of use cost of any substitute product interruption of business or other similar indirect financial loss. THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ANY OTHER WARRANTIES EITHER EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. This warranty is made to the original purchaser of the Product only and is not transferable or assignable. This warranty does not apply to any unauthorized alteration or repair of the Product or to any Product or component which has been damaged or deteriorated due to misuse neglect accident failure to provide necessary maintenance normal wear and tear or acts of God or any other cause beyond the reasonable control of Seller. Seller’s obligation under this warranty is specifically limited to repairing or replacing at its option any part which is determined by Seller to be defective during the applicable warranty period. Any labor charges are excluded and will be the responsibility of the purchaser. Two (2) years or When the Operator exceeds 20 000 cycles of operation as measured by the integrated cycle counter contained in the Operator. The Genie Company ("Seller") warrants to the original purchaser of this commercial door operator (“Product”) subject to all of the terms and conditions hereof that the Product and all components thereof will be free from defects in materials and workmanship under normal use for the following period(s) measured from the date of installation Commercial Operator Limited Warranty THIS PAGE LEFT BLANK GCL-MJ&MH Medium Duty Operator www.geniecompany.com 08-12 One Door Dr. Mt. Hope, OH 44660
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Has XFA : No Page Count : 52EXIF Metadata provided by EXIF.tools