Goodman Mfg Gpg13 Users Manual
GPG13 to the manual 08f66362-d64c-446f-88b9-cf19b5583914
2015-02-02
: Goodman-Mfg Goodman-Mfg-Gpg13-Users-Manual-429708 goodman-mfg-gpg13-users-manual-429708 goodman-mfg pdf
Open the PDF directly: View PDF .
Page Count: 40
Download | |
Open PDF In Browser | View PDF |
INSTALLATION & OPERATING INSTRUCTIONS for GPG13 SINGLE PACKAGE GAS-ELECTRIC HEATING & COOLING UNIT Affix this manual and Users Information Manual adjacent to the unit. ® C US This Forced Air Central Unit Design Complies With Requirements Embodied in The American National Standard / National Standard of Canada Shown Below. ANSI Z21.47•CSA-2.3 Central Furnaces RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION. ATTENTION INSTALLING PERSONNEL Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During installation or repair, caution is to be observed. It is your responsibility to install the product safely and to educate the customer on its safe use. These installation instructions cover the outdoor installation of single package gas electric heating and cooling units. See the Product Data Book applicable to your model* for information regarding accessories. IO-288B 07/08 *NOTE: Please contact your distributor or our website for the applicable product data book referred to in this manual. Goodman Manufacturing Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com © 2005 - 2008 Goodman Manufacturing Company, L.P. INDEX Replacement Parts ............................................................................................................................................................. 3 ORDERING PARTS .............................................................................................................................................. 3 Safety Instructions ............................................................................................................................................................. 3 Unit location ........................................................................................................................................................................ 4 ALL INSTALLATIONS: ........................................................................................................................................... 4 GROUND LEVEL INSTALLATIONS ONLY: .................................................................................................................. 4 ROOFTOP INSTALLATIONS ONLY: ........................................................................................................................... 4 ROOF CURB INSTALLATIONS ONLY: ....................................................................................................................... 5 General Information ........................................................................................................................................................... 5 TRANSPORTATION DAMAGE ................................................................................................................................... 6 Rigging Details ................................................................................................................................................................... 6 Gas piping ........................................................................................................................................................................... 6 HIGH ALTITUDE DERATE (U.S. INSTALLATIONS ONLY) ............................................................................................... 6 PIPING ............................................................................................................................................................. 6 GAS PIPING CHECKS .......................................................................................................................................... 7 Propane Gas Installations .................................................................................................................................................. 7 TANKS AND PIPING ............................................................................................................................................. 8 Electrical Wiring ................................................................................................................................................................. 8 THERMOSTAT LOCATION ....................................................................................................................................... 8 UNIT VOLTAGE ................................................................................................................................................... 9 HEAT ANTICIPATOR SETTING .................................................................................................................................. 9 Circulating Air and Filters ................................................................................................................................................ 10 AIRFLOW CONVERSION ...................................................................................................................................... 10 DUCTWORK ...................................................................................................................................................... 10 FILTERS .......................................................................................................................................................... 10 Venting ............................................................................................................................................................................... 11 FLUE HOOD INSTALLATION ...................................................................................................................................11 Condensate Drain .............................................................................................................................................................. 11 CONDENSATE DRAIN CONNECTION ........................................................................................................................11 Normal sequences of operation ....................................................................................................................................... 11 HEATING ..........................................................................................................................................................11 COOLING .........................................................................................................................................................11 FAN ONLY ...................................................................................................................................................... 12 Startup, Adjustments, and Checks .................................................................................................................................. 12 HEATING STARTUP ............................................................................................................................................ 12 COOLING STARTUP ........................................................................................................................................... 15 Troubleshooting ................................................................................................................................................................ 15 IGNITION CONTROL ERROR CODES ...................................................................................................................... 15 ABNORMAL OPERATION - HEATING .................................................................................................................... 16 ABNORMAL OPERATION - COOLING ................................................................................................................... 16 Maintenance ..................................................................................................................................................................... 17 FILTER REPLACEMENT OR CLEANING .................................................................................................................... 17 CABINET FINISH MAINTENANCE ........................................................................................................................... 17 CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY) ............................................................................................. 17 CONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS ..................................................................................... 17 FLAME SENSOR (QUALIFIED SERVICER ONLY) ...................................................................................................... 17 FLUE PASSAGES (QUALIFIED SERVICER ONLY) ..................................................................................................... 17 CLEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY) ...................................................................................... 17 MAIN BURNER FLAME (QUALIFIED SERVICER ONLY) .............................................................................................. 18 CLEANING BURNERS ......................................................................................................................................... 18 Accessories and Functional Parts ................................................................................................................................... 18 SHEET METAL ACCESSORIES .............................................................................................................................. 18 FUNCTIONAL PARTS .......................................................................................................................................... 18 GENERAL INFORMATION ..................................................................................................................................... 18 Ignition Control Diagnostic Indicator Chart .................................................................................................................... 19 Heating Timing Chart ....................................................................................................................................................... 19 Cooling Timing Chart ....................................................................................................................................................... 19 APPENDIX ......................................................................................................................................................................... 20 Wiring Diagrams .......................................................................................................................................................... 21-36 Minimum Clearances ....................................................................................................................................................... 37 Recommended Filter Sizes ............................................................................................................................................. 37 2 REPLACEMENT PARTS WARNING ORDERING PARTS THIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate. MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM. Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact: WARNING HEATING UNIT SHOULD NOT BE UTILIZED WITHOUT REASONABLE, ROUTINE, INSPECTION, MAINTENANCE AND SUPERVISION. IF THE BUILIDNG IN WHICH ANY SERVICE PARTS DEPARTMENT GOODMAN MANUFACTURING COMPANY, L.P. 5151 SAN FELIPE, SUITE 500 HOUSTON, TEXAS 77056 (713) 861 – 2500 SUCH DEVICE IS LOCATED WILL BE VACANT, CARE SHOULD BE TAKEN THAT SUCH DEVICE IS ROUTINELY INSPECTED, MAINTAINED AND MONITORED. IN THE EVENT THAT THE BUILDING MAYBE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACANT, ALL WATER-BEARING PIPES SHOULD BE DRAINED, THE BUILDING SHOULD BE PROPERLY WINTERIZED, AND THE WATER SOURCE SAFETY INSTRUCTIONS CLOSED. IN THE EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACANT, ANY HYDRONIC COIL UNITS SHOULD TO THE INSTALLER BE DRAINED AS WELL AND, IN SUCH CASE, ALTERNATIVE HEAT SOURCES SHOULD BE UTILIZED. Before installing this unit, please read this manual to familiarize yourself on the specific items which must be adhered to, including maximum external static pressure to unit, air temperature rise, minimum or maximum CFM and motor speed connections. WARNING TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO NOT USE TO THE OWNER THIS UNIT IF ANY PART HAS BEEN UNDER WATER. IMMEDIATELY CALL A A warranty certificate is provided with the unit. Read the warranty carefully and note what is covered. Keep the warranty certificate in a safe place so you can find it when necessary. QUALIFIED SERVICE TECHNICIAN TO INSPECT THE FURNACE AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN UNDER WATER. Keep this literature in a safe place for future reference. WARNING WARNING IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL THIS UNIT MUST NOT BE USED AS A "CONSTRUCTION HEATER" DURING THE FINISHING PHASES OF CONSTRUCTION ON A NEW STRUCTURE. THIS TYPE OF INJURY OR LOSS OF LIFE. USE MAY RESULT IN PREMATURE FAILURE OF THE UNIT DUE TO EXTREMELY – LOW RETURN AIR TERMPERATURES AND EXPOSURE TO CORROSIVE OR VERY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND DIRTY ATMOSPHERES. LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE. – WHAT TO DO IF YOU SMELL GAS: • DO NOT TRY TO LIGHT ANY APPLIANCE. • DO NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE IN YOUR BUILDING. • IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR’S PHONE. FOLLOW THE GAS SUPPLIER’S INSTRUCTIONS. • IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE DEPARTMENT. – INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER, WARNING SERVICE AGENCY OR THE GAS SUPPLIER. TO PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH, WARNING DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE. SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY. WARNING DO NOT CONNECT TO OR USE ANY DEVICE THAT IS NOT DESIGN CERTIFIED BY GOODMAN FOR USE WITH THIS UNIT. SERIOUS PROPERTY DAMAGE, PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND/OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF SUCH NON-APPROVED DEVICES. 3 • • • CARBON MONOXIDE POISONING HAZARD Special Warning for Installation of Furnaces or Air Handling Units in Enclosed Areas such as Garages, Utility Rooms or Parking Areas Carbon monoxide producing devices (such as an automobile, space heater, gas water heater, etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is operated therein, there must be adequate, direct outside ventilation. • To avoid possible illness or death of the building occupants, do NOT locate outside air intake device (economizer, manual fresh air intake, motorized fresh air intake) too close to an exhaust outlet, gas vent termination, or plumbing vent outlet. For specific distances required, consult local codes. Allow minimum clearances from the enclosure for fire protection, proper operation, and service access (see appendix). These clearances must be permanently maintained. The combustion air inlet and flue outlet hoods on the unit must never be obstructed. If used, do not allow the economizer/manual fresh air damper/ motorized fresh air damper to become blocked by snow or debris. In some climates or locations, it may be necessary to elevate the unit to avoid these problems. When the unit is heating, the temperature of the return air entering the unit must be between 50° F and 100° F. GROUND LEVEL INSTALLATIONS ONLY: • This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area. Carbon monoxide emissions can be (re)circulated throughout the structure if the furnace or air handler is operating in any mode. • CO can cause serious illness including permanent brain damage or death. When the unit is installed on the ground adjacent to the building, a level concrete (or equal) base is recommended. Prepare a base that is 3” larger than the package unit footprint and a minimum of 3” thick. The base should also be located where no runoff of water from higher ground can collect in the unit. B10259-216 UNIT LOCATION WARNING TO PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT. IMPORTANT NOTE: Remove wood shipping rails prior to installation of the unit. ALL INSTALLATIONS: • • • For proper flame pattern within the heat exchanger and proper condensate drainage, the unit must be mounted level. The flue outlet hood must be at least 12 inches from any opening through which flue gases could enter a building, and at least three feet above any forced air inlet located within ten feet. The economizer/manual fresh air intake/ motorized fresh air intake and combustion air inlet mounted on the unit are not affected by this restriction. To avoid possible corrosion of the heat exchanger, do not locate the unit in an area where the outdoor air (i.e. combustion air for the unit) will be frequently contaminated by compounds containing chlorine or fluorine. Common sources of such compounds include swimming pool chemicals and chlorine bleaches, paint stripper, adhesives, paints, varnishes, sealers, waxes (which are not yet dried) and solvents used during construction and remodeling. Various commercial and industrial processes may also be sources of chlorine/fluorine compounds. Outside Slab Installation ROOFTOP INSTALLATIONS ONLY: NOTE: To ensure proper condensate drainage, unit must be installed in a level position. • 4 To avoid possible property damage or personal injury, the roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structural engineer to determine the weight capabilities of the roof. Rooftop Installation • • The unit may be installed directly on wood floors or on Class A, Class B, or Class C roof covering material. To avoid possible personal injury, a safe, flat surface for service personnel should be provided. ROOF CURB INSTALLATIONS ONLY: • • • Roof Curb Installation Sufficient structural support must be determined prior to locating and mounting the curb and package unit. Ductwork must be constructed using industry guidelines. The duct work must be placed into the roof curb before mounting the package unit. Curb insulation, cant strips, flashing and general roofing material are furnished by the contractor. GENERAL INFORMATION WARNING TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DUE TO FIRE, EXPLOSIONS, SMOKE, SOOT, CONDENSATION, ELECTRIC SHOCK OR CARBON MONOXIDE, THIS UNIT MUST BE PROPERLY INSTALLED, REPAIRED, OPERATED, AND MAINTAINED. This unit is approved for outdoor installation ONLY. To assure that your unit operates safely and efficiently, it must be installed, operated, and maintained in accordance with these installation and operating instructions, all local building codes and ordinances, or in their absence, with the latest edition of the National Fuel Gas Code NFPA54/ANSI Z223.1 and National Standard of Canada CAN/CSA B149 Installation Codes. The heating and cooling capacities of the unit should be greater than or equal to the design heating and cooling loads of the area to be conditioned. The loads should be calculated by an approved method or in accordance with A.S.H.R.A.E. Guide or Manual J Load Calculations published by the Air Conditioning Contractors of America. Obtain from: American National Standards Institute 1430 Broadway New York, NY 10018 5 TRANSPORTATION DAMAGE GAS PIPING Check the carton upon arrival for external damage. If damage is found, a request for inspection by carrier agent should be made in writing immediately. IMPORTANT NOTE: This unit is factory set to operate on natural gas at the altitudes shown on the rating plate. Carefully inspect the unit for damage including damage to the cabinetry. Any bolts or screws which may have loosened in transit must be re-tightened. In the event of damage, the receiver should: 1. Make notation on delivery receipt of any visible damage to shipment or container. 2. Notify carrier promptly and request an inspection. 3. In case of concealed damage, carrier should be notified as soon as possible-preferably within 5 days. 4. File the claim with the following supporting documents: a. Original Bill of Lading, certified copy, or indemnity bond. b. Original paid freight bill or indemnity in lieu thereof. c. Original invoice or certified copy thereof, showing trade and other discounts or reductions. d. Copy of the inspection report issued by carrier representative at the time damage is reported to the carrier. The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage. WARNING TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH WHEN EITHER USING PROPANE GAS ALONE OR AT HIGHER ALTITUDES, OBTAIN AND INSTALL THE PROPER CONVERSION KIT(S). FAILURE TO DO SO CAN RESULT IN HIGH ALTITUDE UNSATISFACTORY OPERATION AND/OR EQUIPMENT DAMAGE. KITS ARE FOR IN U.S. INSTALLATIONS ONLY AND ARE NOT APPROVED FOR USE CANADA. The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. Conversion to LP gas is permitted with the use of the factory authorized conversion kit LPT-00A. Inlet Gas Pressure Natural Propane Min. 5.0" W.C., Max. 10.0" W.C. Min. 11.0" W.C., Max. 13.0" W.C. Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in Table Above. The minimum supply pressure should not vary from that shown in the table above because this could prevent the unit from having dependable ignition. In addition, gas input to the burners must not exceed the rated input shown on the rating plate. Overfiring of the unit could result in premature heat exchanger failure. NOTE: When inspecting the unit for transportation damage, remove all packaging materials. Recycle or dispose of the packaging material according to local codes. RIGGING DETAILS HIGH ALTITUDE DERATE (U.S. INSTALLATIONS ONLY) IMPORTANT NOTE: The gas/electric units naturally derate with altitude. Do not attempt to increase the firing rate by changing orifices or increasing the manifold pressure. This can cause poor combustion and equipment failure. At all altitudes, the manifold pressure must be within 0.3 inches W.C. of that listed on the nameplate for the fuel used. At all altitudes and with either fuel, the air temperature rise must be within the range listed on the unit nameplate. Refer to the Installation Manual provided with the LP kit for conversion from natural gas to propane gas and for altitude adjustments. WARNING TO PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT POSITION DURING ALL RIGGING AND MOVING OPERATIONS. TO FACILITATE LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE SLING. Important: If using bottom discharge with roof curb, ductwork should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in roof curb installation instructions. PIPING IMPORTANT NOTE: To avoid possible unsatisfactory operation or equipment damage due to under firing of equipment, do not undersize the natural/propane gas piping from the meter/tank to the unit. When sizing a trunk line, include all appliances on that line that could be operated simultaneously. The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. The gas line installation must comply with local codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1. Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual. Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end. Natural Gas Connection Natural Gas Capacity of Pipe in Cubic Feet of Gas Per Hour (CFH) Nominal Black Pipe Size (inches) Length of Pipe in Feet 1 1/2 3/4 1 1/4 1 1/2 10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 980 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure = .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based on 0.60 Specific Gravity Gas) CFH = Rigging 6 BTUH Furnace Input Heating Value of G as (BT U/Cubic Foot) GAS PIPING CHECKS Refer to the Proper Piping Practice drawing for the general layout at the unit. The following rules apply: 1. Use black iron pipe and fittings for the supply piping. The use of a flex connector and/or copper piping is permitted as long as it is in agreement with local codes. 2. Use pipe joint compound on male threads only. Pipe joint compound must be resistant to the action of the fuel used. 3. Use ground joint unions. 4. Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long. 5. Use two pipe wrenches when making connection to the gas valve to keep it from turning. 6. Install a manual shut-off valve in a convenient location (within six feet of unit) between the meter and the unit. 7. Tighten all joints securely. 8. The unit must be connected to the building piping by one of the following methods: • Rigid metallic pipe and fittings • Semirigid metallic tubing and metallic fittings (Aluminum alloy tubing must not be used in exterior locations) • Listed gas appliance connectors used in accordance with the terms of their listing that are completely in the same room as the equipment • In the prior two methods above the connector or tubing must be protected from physical and thermal damage. Aluminum alloy tubing and connectors must be coated to protect against external corrosion when in contact with masonry, plaster or insulation or are subject to repeated wettings by liquids (water - not rain water, detergents or sewage) CAUTION TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, THE FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS CONNECTIONS AND PRESSURE TESTING: • THE UNIT AND ITS GAS CONNECTIONS MUST BE LEAK TESTED BEFORE PLACING IN OPERATION. BECAUSE OF THE DANGER OF EXPLOSION OR FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS. NEVER EXCEED SPECIFIED PRESSURES FOR TESTING. HIGHER PRESSURE MAY DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN PREMATURE HEAT EXCHANGE FAILURE. • THIS UNIT AND ITS SHUT-OFF VALVE MUST BE DISCONNECTED FROM THE GAS SUPPLY DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1/2 PSIG (3.48 KPA). • THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY SYSTEM BY CLOSING ITS MANUAL SHUT-OFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (3.48 KPA). WARNING TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY, BE SURE THERE IS NO OPEN FLAME IN THE VICINITY DURING AIR BLEEDING. There will be air in the gas supply line after testing for leaks on a new installation. Therefore, the air must be bled from the line by loosening the ground joint union until pure gas is expelled. Tighten union and wait for five minutes until all gas has been dissipated in the air. Be certain there is no open flame in the vicinity during air bleeding procedure. The unit is placed in operation by closing the main electrical disconnect switch for the unit. PROPANE GAS INSTALLATIONS MANUAL SHUT-OFF VALVE WARNING TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS DETECTING WARNING DEVICE. SINCE RUST CAN REDUCE THE LEVEL DRIP LEG OF ODORANT IN PROPANE GAS, A GAS DETECTING WARNING DEVICE IS THE ONLY RELIABLE WAY TO DETECT A PROPANE GAS LEAK. CONTACT A LOCAL PROPANE GAS SUPPLIER ABOUT INSTALLING A GROUND JOINT UNION (INSTALLED AHEAD OF GAS VALVE) GAS DETECTING WARNING DEVICE. IMPORTANT NOTE: Propane gas conversion kits must be installed to convert units to propane gas. All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters (See NBFU Manual 58). For satisfactory operation, propane gas supply pressure must be within 9.7 - 10.3 inches W.C. at the manifold with all gas appliances in operation. Maintaining proper gas pressure depends on three main factors: 1. Vaporization rate, which depends on (a) temperature of the liquid, and (b) wetted surface area of the container or containers. 2. Proper pressure regulation. 3. Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe size required will depend on length of pipe run and total load of all appliances. GROMMET Proper Piping Practice NOTE: The unit gas supply entrance is factory sealed with plugs. Keep plugs in place until gas supply is ready to be installed. Once ready, replace the plugs with the supplied grommets and install gas supply line. 7 TANKS AND PIPING WARNING Complete information regarding tank sizing for vaporization, recommended regulator settings and pipe sizing is available from most regulator manufacturers and propane gas suppliers. Since propane gas will quickly dissolve white lead or most standard commercial compounds, special pipe dope must be used. Shellac base compounds resistant to the actions of liquefied petroleum gases such as Gasolac®, Stalactic®, Clyde’s® or John Crane® are satisfactory. TO PREVENT PROPERTY DAMAGE OR SERIOUS PERSONAL INJURY DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS DETECTING WARNING DEVICE. IF THE PROPANE GAS UNIT IS INSTALLED IN AN EXCAVATED AREA OR A CONFINED SPACE, A WARNING DEVICE IS REQUIRED DUE TO: PROPANE GAS IS HEAVIER THAN AIR AND ANY LEAKING GAS CAN • PROPANE GAS ODORANT MAY FADE, MAKING THE GAS UNDETECTABLE SETTLE IN ANY LOW AREAS OR CONFINED SPACES. See below for typical propane gas piping. EXCEPT WITH A WARNING DEVICE. 5 to 15 PSIG (20 PSIG Max.) First Stage Regulator • ELECTRICAL WIRING Continuous 11" W.C. THERMOSTAT LOCATION 200 PSIG Maximum Second Stage Regulator Mount the thermostat approximately five feet above the floor, in an area that has an inside, vibration-free wall and has good air circulation. Movement of air must not be obstructed by furniture, door, draperies, etc. The thermostat must not be mounted where it will be affected by drafts, hot or cold water pipes or air ducts in walls, radiant heat from fireplace, lamps, the sun, television, etc. Consult the Instruction Sheet packaged with thermostat for mounting instructions. All units have one stage of heating and one stage of mechanical cooling. Units which will have economizers may use thermostats with one or two stages of cooling. *PG1360***1A ONLY: These models have two stages of mechanical cooling. A 1-stage heat, 2-stage cooling thermostat is recommended for these models. Typical Propane Gas Piping Sizing Between First and Second Stage Regulator Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10 PSIG Setting. Capacities in 1,000 BTU/HR NOMINAL PIPE SIZE, SCHEDULE 40 TUBING SIZE, O.D., TYPE L 3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4" 30 309 700 1,303 2,205 3,394 1,843 3,854 40 265 599 1,115 1,887 2,904 1,577 3,298 50 235 531 988 1,672 2,574 1,398 2,923 60 213 481 896 1,515 2,332 1,267 2,649 70 196 446 824 1,394 2,146 1,165 2,437 80 182 412 767 1,297 1,996 1,084 2,267 90 171 386 719 1,217 1,873 1,017 2,127 100 161 365 679 1,149 1,769 961 2,009 150 130 293 546 923 1,421 772 1,613 200 111 251 467 790 1,216 660 1,381 250 90 222 414 700 1,078 585 1,224 300 89 201 378 634 976 530 1,109 350 82 185 345 584 898 488 1,020 400 76 172 321 543 836 454 949 The units are designed for operation on 60 hertz current and at voltages as shown on the rating plate. All internal wiring in the unit is complete. It is necessary to bring in the power supply to the contactor as shown on the unit wiring diagram which is supplied with each unit. 24 volt wiring must be connected between the unit control panel and the room thermostat. To convert to Capacities at 15 PSIG Settings -- Multiply by 1.130 To convert to Capacities at 5 PSIG Settings -- Multiply by 0.879 Sizing Between Single or Second Stage Regulator and Appliance* Maximum Propane Capacities Listed are Based on 1/2" W.C. Pressure Drop at 11" W.C. Setting. Capacities in 1,000 BTU/HR NOMINAL PIPE SIZE, SCHEDULE 40 3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4" 1" 1-1/4" 1-1/2" 10 49 110 206 348 539 291 608 1,146 2,353 3,525 20 34 76 141 239 368 200 418 788 1,617 2,423 30 27 61 114 192 296 161 336 632 1,299 1,946 40 23 52 97 164 253 137 284 541 1,111 1,665 50 20 46 86 146 224 122 255 480 985 1,476 60 19 42 78 132 203 110 231 436 892 1,337 80 16 36 67 113 174 94 198 372 764 1,144 100 14 32 59 100 154 84 175 330 677 1,014 125 12 28 52 89 137 74 155 292 600 899 150 11 26 48 80 124 67 141 265 544 815 200 10 22 41 69 106 58 120 227 465 697 250 9 19 36 61 94 51 107 201 412 618 COOL B18099-18 HEAT L2 TUBING SIZE, O.D., TYPE L K4 L2 PIPE OR TUBING LENGTH, FEET 1068-83-400A PIPE OR TUBING LENGTH, FEET 18 33 55 85 46 97 182 374 560 350 7 16 30 51 78 43 89 167 344 515 400 7 15 28 47 73 40 83 156 320 479 L2 L2 L1 L1 DI MODEL 1068-400 FS 2 ECON 120 135 P3 150 P2 T2 C22 Low Voltage Wiring 8 3 3 2 1 F1 FUSE 3 AMP MAX *DATA IN ACCORDANCE WITH NFPA PAMPHLET NO. 54 Table 3 - Propane Gas Pipe Sizing 1 9 6 3 6 6 2 5 5 4 1 4 4 P1 12 9 9 12 11 8 8 11 10 7 10 7 10 11 12 Y W G 7 ANSI Z21.20 AUTOMATIC IGNITION SYSTEM 24VAC 50/60Hz 400mA MAX. LOW VOLTAGE CONNECTOR R T1 SPEED-UP 8 CR Y WG K2 K1 BREAK FOR TWO STAGE COMPRESSOR 300 UNUSED K3 Note:Junction box location shown is optional and is for illustration purposes only. B18099-18 L2 HEAT COOL 1068-83-400A L2 K4 JUNCTION BOX FS 3 1 1 2 2 2 5 5 4 1 4 4 7 3 6 9 6 6 9 12 12 9 8 7 11 11 10 8 10 11 12 10 7 Y W G P1 R 3 K1 ECON F1 FUSE 3 AMP MAX BREAK FOR TWO STAGE COMPRESSOR 120 135 P3 150 P2 SPEED-UP LOW VOLTAGE CONNECTOR K2 ANSI Z21.20 AUTOMATIC IGNITION SYSTEM 24VAC 50/60Hz 400mA MAX. Y/Y2 C R Y1 W G DI MODEL 1068-400 L1 L1 L2 L2 UNUSED K3 T2 C22 T1 Electrical Power Directly To Junction Box Low Voltage Wiring-*PG1360***1A Only Refer to the unit wiring diagram for electrical connections. When installed, the unit must be electrically grounded in accordance with local codes or in the absence of local codes, with the National Electrical Code, ANSI/NFPA No. 70, and/or the CSA C22.1 Electrical Code. Ensure low voltage connections are waterproof. WARNING TO AVOID THE RISK OF ELECTRICAL SHOCK, WIRING TO THE UNIT MUST BE POLARIZED AND GROUNDED. CAUTION Electrical Power Routed Through Bottom of Unit Typical Electrical Wiring Unit Voltage TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE ONLY COPPER CONDUCTORS. UNIT VOLTAGE The unit transformer is factory connected for 230V operation. If the unit is to operate on 208V, reconnect the transformer primary lead as shown on the unit wiring diagram. The induced draft blower on some models is equipped with a 230V lead (red) and a 208V lead (black). If equipped, connect the induced draft blower 208V lead (black) in place of the 230V lead (red). Tape the unused 230V lead. CAUTION TO PREVENT IMPROPER AND DANGEROUS OPERATION DUE TO WIRING ERRORS, LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. VERIFY PROPER OPERATION AFTER SERVICING. For unit protection, use a fuse or HACR circuit breaker that is in excess of the circuit ampacity, but less than or equal to the maximum overcurrent protection device. DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE. All line voltage connections must be made through weatherproof fittings. All exterior power supply and ground wiring must be in approved weatherproof conduit. Low voltage wiring from the unit control panel to the thermostat requires coded cable. See below for ground level and rooftop wiring. HEAT ANTICIPATOR SETTING The heat anticipator is to be set by measuring the load (amperage) at the “R” circuit. Follow the instructions provided by the thermostat for more details. G Y R W From Unit R W Y G Typical Thermostat and Unit 24 V Wiring Hookup 9 Down Discharge Applications Cut insulation around bottom openings and remove panels from the bottom of the unit, saving the screws holding the panels in place. NOTE: Single phase models require installation of horizontal duct kit #20464501PDGK (medium chassis) and #20464502PDGK (large chassis). Y/Y2 G Y R W From Unit DUCTWORK Y/Y2 R W Y1 G Duct systems and register sizes must be properly designed for the C.F.M. and external static pressure rating of the unit. Ductwork should be designed in accordance with the recommended methods of Air Conditioning Contractors of America Manual D (Residential) or Manual Q (Commercial). All ductwork exposed to the outdoors must include a weatherproof barrier and adequate insulation. A duct system should be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B. The supply duct from the unit through a wall may be installed without clearance. However, minimum unit clearances as shown in the appendix must be maintained. The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger. A cover should be tightly attached to prevent air leaks. For duct flange dimensions on the unit refer to the Unit Dimension illustration in the appendix. For down-discharge applications, the ductwork should be attached to the roof curb prior to installing the unit. Ductwork dimensions are shown in the roof curb installation manual. If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission. Typical 2-Stage Cool Thermostat and Unit 24 V Wiring Hookup *PG1360***1A Only CIRCULATING AIR AND FILTERS AIRFLOW CONVERSION Units can easily be converted from horizontal to downdischarge airflow delivery. In down-discharge or high static installations, the installer should measure the total external static and review the blower performance charts before performing the installation. In some installations it will be necessary to change the blower speed to provide proper air flow. Horizontal Air Flow (Applies to 3 phase models) Single phase models are shipped without horizontal duct covers. If needed, these kits may be ordered through Goodman’s Service Parts department. Remove supply and return duct covers which are attached to the unit as shown below. FILTERS CAUTION TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS, NEVER OPERATE UNIT WITHOUT AN AIR FILTER INSTALLED IN THE RETURN AIR SYSTEM. Even though a return air filter is not supplied with this unit, there must be a means of filtering all return air. The *PG1336(3A,4A), *PG1342, *PG1348, and *PG1360 models are provided with internal filter racks for down-discharge applications. All units may be externally filtered. Refer to the unit filter size chart in the appendix for filter size information. Filters installed external to the unit should be sized in accordance with their manufacturer recommendations. A throwaway filter must be sized for a maximum face velocity of 300 feet per minute. Remove these covers for horizontal duct applications Filter Installation Important: When installing a filter, the air flow arrows on the filter must point toward the circulator blower. Duct Cover Installation 10 3. The 30-second HEAT FAN ON delay time begins. *PG13(48,60)***1A ONLY: Heat on delay begins when thermostat calls for heat. ECM motor is energized approximately 45 seconds later. NOTE: ECM motor may operate at approximately 100 CFM or less during the 45 second on delay period. ECM motor will energize at heating speed after the 45 second delay regardless of the status of the main burner flame. 4. The unit delivers heat to the conditioned space until the thermostat is satisfied. 5. The gas valve deenergizes. The induced draft blower continues operation for a 29-second post-purge. 6. Ignition control begins timing the HEAT FAN OFF delay. There is an adjustable HEAT FAN OFF delay of approximately 120/135/150 seconds (factory set at 150). After the HEAT FAN OFF delay time has elapsed, the blower will deenergize. This allows any additional heat in the heat exchanger to be transferred to the conditioned space. *PG13(48,60)***1A ONLY: HEAT FAN OFF delay is fixed at 180 seconds. Airflow level is 50% of nominal heating airflow. VENTING NOTE: Venting is self-contained. Do not modify or block. FLUE HOOD INSTALLATION Install the flue hood and bug screen prior to operation of the unit. To install the flue hood cover and bug screen: 1. Remove the flue hood and bug screen from inside the heat exchanger compartment. 2. Slide the bug screen over the flanges of the flue hood and attach the flue hood and screen to the unit with the sheet metal screws provided. COOLING 1. Thermostat calls for cooling. The compressor and outdoor fan are energized. 2. Approximately seven seconds later, the indoor fan starts. 3. The unit will deliver cooling to the conditioned space until the thermostat is satisfied. 4. The compressor and outdoor fan will be deenergized when the thermostat opens. 5. The indoor fan continues to run for approximately 60 seconds after the thermostat is satisfied. This allows additional cooling from the indoor coil to be transferred to the conditioned space. Then, the indoor fan stops. *PG1348***1A ONLY: 1. Thermostat calls for cooling. Outdoor fan and compressor are energized. ECM motor is energized almost immediately for 30 seconds at 50% of the nominal airflow. Airflow then increases to nominal airflow. 2. The unit will deliver cooling to the conditioned space until thermostat is statisfied. 3. The outdoor fan and compressor will be de-energized when thermostat opens. 4. ECM motor continues to operate for approximately 60 seconds at 50% of nominal airflow after thermostat opens. Flue Hood and Bug Screen Installation CONDENSATE DRAIN CONDENSATE DRAIN CONNECTION A 3/4” NPT drain connection is supplied for condensate piping. An external trap must be installed for proper condensate drainage. DRAIN CONNECTION UNIT 2" MINIMUM FLEXIBLE TUBING-HOSE OR PIPE *PG1360***1A ONLY: 1. Thermostat calls for low stage cooling. Outdoor fan and low stage compressor are energized. ECM motor is energized almost immediately for 30 seconds at 50% of the nominal low stage airflow. Airflow then increases to nominal low stage airflow. If thermostat calls for high stage cooling, outdoor fan and low and high stage compressor is energized. ECM motor is energized almost immediately for 30 seconds at 50% of the nominal high stage airflow. Airflow then increases to nominal high stage airflow. 2. The unit will deliver cooling to the conditioned space until thermostat is satisfied. 3. The outdoor fan and low stage compressor (or low and high stage compressor) will be de-energized when thermostat opens. 4. ECM motor continues to operate for approximately 60 seconds at 50% of nominal low stage airflow (or high stage airflow if thermostat call was for high stage cooling) after thermostat opens. 3" MINIMUM A POSITIVE LIQUID SEAL IS REQUIRED Drain Connection NORMAL SEQUENCES OF OPERATION HEATING This unit is equipped with an ignition control that automatically lights the main burner. DO NOT attempt to light the main burners by any other method. 1. Thermostat calls for heat. The induced draft blower energizes for a 15-second pre-purge. 2. The spark igniter and gas valve energizes for 7 seconds. NOTE: The igniter produces a very intense electrical spark that ignites the gas. 11 NOTE: A 180-second anti-short cycle is integral to the control and prevents recycling of the compressor. Rollout Protection FAN ONLY 1. Thermostat calls for FAN ONLY by energizing “G”. 2. Approximately seven seconds later, the indoor fan starts. 3. The indoor fan continues to run for approximately 60 seconds after “G” is de-energized. *PG13(48,60)***1A ONLY: 1. Thermostat calls for FAN ONLY by energizing “G”. 2. ECM motor is energized almost immediately at approximately 30% of the nominal high stage cooling airflow, depending on setting (see “Blower Speed Adjustment” section). 3. ECM is de-energized almost immediately after “G” is deenergized. Rollout Protection on Burner Bracket Secondary Limit Control The secondary limit control is located on the top of the blower scroll assembly. This control opens when elevated temperatures are sensed. Elevated temperatures at the control are normally caused by blower failure. The reason for the opening should be determined and repaired prior to resetting. If the power to the unit is interrupted during the heating cycle, it may cause the secondary limit to trip. Once the blower compartment temperature drops below the limit reset temperature, the limit will automatically reset. STARTUP, ADJUSTMENTS, AND CHECKS HEATING STARTUP This unit is equipped with an electronic ignition device to automatically light the main burners. It also has a power vent blower to exhaust combustion products. On new installations, or if a major component has been replaced, the operation of the unit must be checked. Check unit operation as outlined in the following instructions. If any sparking, odors, or unusual sounds are encountered, shut off electrical power and recheck for wiring errors, or obstructions in or near the blower motors. Duct covers must be removed before operating unit. Secondary Control Limit Heat Anticipator Setting Set the heat anticipator on the room thermostat to 0.4 amps to obtain the proper number of heating cycles per hour and to prevent the room temperature from overshooting the room thermostat setting. Rollout Protection Control The rollout protection device opens, cutting power to the gas valve, if the flames from the burners are not properly drawn into the heat exchanger. The rollout protection device is located on the burner bracket. The reason for elevated temperatures at the control should be determined and repaired prior to resetting this manual reset control. Back of Unit Secondary Limit Control Pre-Operation Checks 1. 2. 3. 4. WARNING TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION, A QUALIFIED SERVICER MUST INVESTIGATE THE REASON FOR THE ROLLOUT PROTECTION DEVICE TO OPEN BEFORE MANUALLY RESETTING 5. THE ROLLOUT PROTECTION DEVICE. 6. 7. 8. 12 Close the manual gas valve external to the unit. Turn off the electrical power supply to the unit. Set the room thermostat to its lowest possible setting. Remove the heat exchanger door on the side of the unit by removing screws. This unit is equipped with an ignition device which automatically lights the main burner. DO NOT try to light burner by any other method. Move the gas control valve switch to the OFF position. Do not force. Wait five minutes to clear out any gas. Smell for gas, including near the ground. This is important because some types of gas are heavier than air. If you have waited five minutes and you do smell gas, immediately follow the warnings on page 3 of this manual. 9. 10. 11. 12. If having waited for five minutes and no gas smell is noted, move the gas control valve switch to the ON position. Replace the heat exchanger door on the side of the unit. Open the manual gas valve external to the unit. Turn on the electrical power supply to the unit. Set the thermostat to desired setting. Gas Line Gas Shutoff Valve Gas Line To Furnace Gas Valve On/Off Selector Switch Open To Atmosphere Drip Leg Cap With Fitting INLET OUTLET Manometer Hose White-Rodgers Model 36F22 Manometer Measuring Inlet Gas Pressure Alternate Method OUTLET INLET Manifold Pressure Check The gas valve has a tapped opening to facilitate measurement of the manifold pressure. A “U” Tube manometer having a scale range from 0 to 12 inches of water should be used for this measurement. The manifold pressure must be measured with the burners operating. To adjust the pressure regulator, remove the adjustment screw or cover on the gas valve. Turn out (counterclockwise) to decrease pressure, turn in (clockwise) to increase pressure. Only small variations in gas flow should be made by means of the pressure regulator adjustment. In no case should the final manifold pressure vary more than plus or minus 0.3 inches water column from the specified nominal pressure. Any major changes in flow should be made by changing the size of the burner orifices. The measured input rate to the furnace must not exceed the rating specified on the unit rating plate. For natural gas, the manifold pressure must be between 3.2 and 3.8 inches water column (3.5 nominal). For propane gas, the manifold pressure must be between 9.7 and 10.3 inches water column (10.0 nominal). Gas Valve On/Off Selector Switch White-Rodgers 36G22 Gas Supply And Manifold Check Gas supply pressure and manifold pressure with the burners operating must be as specified on the rating plate. Gas Inlet Pressure Check Gas inlet pressure must be checked and adjusted in accordance to the type of fuel being consumed. With Power And Gas Off: 1. Connect a water manometer or adequate gauge to the inlet pressure tap of the gas valve. Inlet gas pressure can also be measured by removing the cap from the dripleg and installing a predrilled cap with a hose fitting. Gas Input (Natural Gas Only) Check With Power And Gas On: To measure the gas input use a gas meter and proceed as follows: 1. Turn off gas supply to all other appliances except the unit. 2. With the unit operating, time the smallest dial on the meter for one complete revolution. If this is a 2 cubic foot dial, divide the seconds by 2; if it is a 1 cubic foot dial, use the seconds as is. This gives the seconds per cubic foot of gas being delivered to the unit. 3. INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT Example: Natural gas with a heating value of 1000 BTU per cubic foot and 34 seconds per cubic foot as determined by Step 2, then: Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. NOTE: BTU content of the gas should be obtained from the gas supplier. This measured input must not be greater than shown on the unit rating plate. 4. Relight all other appliances turned off in step 1. Be sure all pilot burners are operating. 2. Put unit into heating cycle and turn on all other gas consuming appliances. Inlet Gas Pressure Natural Propane Min. 5.0" W.C., Max. 10.0" W.C. Min. 11.0" W.C., Max. 13.0" W.C. NOTE: Inlet Gas Pressure Must Not Exceed the Maximum Value Shown. If operating pressures differ from above, make necessary pressure regulator adjustments, check piping size, etc., and/ or consult with local utility. 13 Main Burner Flame Check (switches 1 and 2) provides airflow adjustment for heating airflow. The “COOL” adjustment function (switches 5 and 6) provides airflow adjustments for cooling airflow. The “ADJUST” function (switches 7 and 8) will adjust the heating AND cooling airflow +10% or - 15%. The “DELAY” function (switches 3 and 4) is not field adjustable. Flames should be stable, soft and blue (dust may cause orange tips but they must not be yellow) and extending directly outward from the burner without curling, floating or lifting off. Temperature Rise Check Check the temperature rise through the unit by placing thermometers in supply and return air registers as close to the unit as possible. Thermometers must not be able to sample temperature directly from the unit heat exchangers, or false readings could be obtained. 1. All registers must be open; all duct dampers must be in their final (fully or partially open) position and the unit operated for 15 minutes before taking readings. 2. The temperature rise must be within the range specified on the rating plate. NOTE: Air temperature rise is the temperature difference between supply and return air. With a properly designed system, the proper amount of temperature rise will normally be obtained when the unit is operated at rated input with the recommended blower speed. If the correct amount of temperature rise is not obtained, it may be necessary to change the blower speed. A higher blower speed will lower the temperature rise. A slower blower speed will increase the temperature rise. NOTE: Blower speed MUST be set to give the correct air temperature rise through the unit as marked on the rating plate. O N To adjust the HEAT, COOL or ADJUST functions, simply change the ON/OFF position of the appropriate dipswitches. The table below shows the ON/OFF combinations for the various switches and the corresponding A, B, C, or D taps. Refer to the Product Data Book applicable to your model for airflow tables and temperature rise. The “Dipswitch Position” table below shows the factory dipswitch settings for each model. The “CFM” table below shows the nominal heating and cooling CFM for each model. HEAT 1 2 A OFF OFF B ON OFF C OFF ON D ON ON ‡ Factory Set; not field adjustable * Tap D has no effect on airflow External Static Pressure Check The total external static pressure must be checked on this unit to determine if the airflow is proper. DELAY‡ 3 4 OFF OFF ON OFF OFF ON ON ON COOL 5 OFF ON OFF ON 6 OFF OFF ON ON ADJUST 7 8 OFF OFF ON OFF OFF ON ON* ON* Dipswitch Settings and Corresponding Tap Model Blower Speed Adjustments GPG13480701* GPG13480901* GPG13481151* GPG13600901* GPG13601151* GPG13601401* WARNING TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, REMOVE ELECTRICAL POWER FROM THE UNIT BEFORE CHANGING SPEED TAPS ON THE 1 ON OFF ON ON OFF ON 2 ON ON OFF ON ON OFF DIP SWITCH POSITION 3 4 5 6 OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF 7 OFF OFF OFF OFF OFF OFF 8 OFF OFF OFF OFF OFF OFF BLOWER MOTOR. Model Refer to the wiring diagram in the appendix to verify speed tap settings. Blower speeds are to be changed at the ignition control board. Both heat speed and cool speed terminals are supplied on the board along with two unused motor lead terminals. *PG13(48, 60)***1B, 3A, 4A models are equipped with X-13 motors. X-13 motors are constant torque motors with very low power consumption. This motor is energized by 24V. Adjust the CFM for the unit by changing the 24V low voltage leads to the speed terminal block on the motor. Heating-White Lead Cooling-Yellow Lead T1 - Low Speed T4 - Low Speed T2 - Medium Speed T5 - High Speed T3 - High Speed *PG13(48, 60)***1A models are equipped with GE ECM motors. These motors offer greater airflow flexibility as well as dehumidification. The airflow delivery for these models can be adjusted by changing the position of dip switches on a low voltage terminal board. The figure below shows the dipswitch layout on the low voltage terminal board as well as the function of each set of switches. The “HEAT” function GPG13480701* GPG13480901* GPG13481151* GPG13600901* GPG13601151* GPG13601401* CFM HEAT COOL 1020 1540 1140 1540 1420 1540 1140 1810 1420 1810 1700 1810 Unit dipswitches are factory set for each model, see label on blower housing for CFM adjustment next to low voltage terminal connections. NOTE: Heating airflow must be adjusted to provide the temperature rise shown on rating plate. *PG1360***1A ONLY: Low stage airflow is approximately 75% of high stage cooling airflow. Example: High stage cooling airflow is 1800 CFM. Low stage cooling airflow is 0.75*1800 CFM = 1350 CFM. The adjustment factors for the ADJUST function are A = 1, B = 1.10 (+10%) and C = 0.85 (-15%). The D tap for the ADJUST function has no effect on airflow. Example: Airflow tables indicate 1425 CFM. With the ADJUST set to B tap, the CFM becomes 1.10*1425 CFM = 1568 CFM. 14 Dehumidification COOLING STARTUP The GE ECM motor has the capability to provide increased dehumidification during cooling operation. This is accomplished by lowering the airflow to approximately 85% of the nominal cooling airflow. Example: Unit is operating at 1400 CFM and humidistat calls for dehumidification. Resulting airflow is 0.85* 1400 CFM = 1190 CFM. To make use of this feature, a 24VAC humidistat which opens on humidity rise is required. Connect humidistat to the HUMIDISTAT/HUM terminal on the low voltage terminal board (see wiring diagram in the appendix). Clip the HUM/ PJ6 jumper on the low voltage terminal board. The system is now ready to provide dehumidification. NOTE: Check all manual reset limit controls in heating circuit if cooling mode does not operate. Compressor Protection Devices The compressor includes components which are designed to protect the compressor against abnormal operating conditions. WARNING TO PREVENT PERSONAL INJURY OR DEATH, ALWAYS DISCONNECT ELECTRICAL POWER BEFORE INSPECTING OR SERVICING THE UNIT. ALL COMPRESSOR PROTECTION DEVICES RESET AUTOMATICALLY, ENERGIZING THE CONTACTOR Limit Check AND OUTDOOR FAN. Check limit control operation after 15 minutes of operation by blocking the return air grille(s). 1. After several minutes the main burners must go OFF. Blower will continue to run. 2. Remove air restrictions and main burners will relight after a cool down period of a few minutes. Adjust the thermostat setting below room temperature. 1. Main burners must go OFF. 2. Circulating Air Blower will continue to run for 120, 135 or 150 seconds, depending on the setting. *PG13(48,60)***1A ONLY: Circulating Air Blower will continue to run for 180 seconds. Cooling Refrigerant Charging Check unit charge before putting the cooling section into full operation. The unit is factory charged with R-22 for nominal air flow and static pressure conditions. The unit has a piston flowrator expansion device. NOTE: *PG1360 is equipped with a thermostatic valve expansion device. 1 10 To ensure the unit is properly charged for the intended application, check the unit refrigerant superheat at the compressor. The refrigerant superheat is a function of outdoor ambient temperature and return air temperature of the conditioned space. It is the installing contractors responsibility to ensure the proper refrigerant superheat at the compressor is adjusted for each application. For example, 10 degree refrigerant superheat level is adequate for a 95 degree outdoor ambient temperature and a 78 - 80 degree for indoor return air temperature. As the outdoor ambient temperature rises the superheat decreases and as the outdoor ambient temperature lowers the superheat increases. Proper superheat adjustment optimizes cooling performance. For models equipped with thermostatic expansion valve, charge system to 12-14 degrees of subcooling, adjust expansion valve stem for superheat setting when necessary. 11 5 8 2 11 R31 2 6 9 12 3 12 3 9 6 K1 C27 D7 FS D5 R10 R25 R38 D3 C13 R8 R22 D9 R29 K2 D1 Z1 D10 L1 R34 R3 R35 L1 L2 UNUSED C20 L2 K3 D14 K4 R11 D11 COOL L2 R42 D12 HEAT R4 L2 R36 LED 1068-83-400A NOTE: The expansion valve will not need adjustment for most applications. Ensure system superheat is set between 10-12 degrees after final adjustment. Control Board (Top) NOTE: If necessary, adjust fan OFF delay settings to obtain satisfactory comfort level. Cooling Operation WARNING T H IS NOTE: Mechanical cooling cannot be reliably provided at ambient temperatures below 50° F. U NIT M U S T N O T BE U S ED AS A "C ON S TR U CTION H E A TER " D U R IN G TH E FIN IS H IN G PH A S ES O F CO N STR UC TIO N O N A N EW S TR UC TU R E. T HIS TYP E O F U SE M A Y R ES U LT IN PR EM A TU R E FAILUR E O F T HE U N IT DU E TO E XTR E ME LY 1. Turn on the electrical power supply to the unit. 2. Place the room thermostat selector switch in the COOL position (or AUTO if available, and if automatic changeover from cooling to heating is desired). 3. Set the room thermostat to the desired temperature. LO W RE TU R N A IR T ER M PE R ATUR E S AND EX PO SU R E T O C O R R OSIVE O R VE R Y D IR TY A TM OS PH ER E S. Unit Shutdown 1. Set the thermostat to lowest setting. 2. Turn off the electrical power supply to the unit. 3. Remove the heat exchanger door on the side of the unit by removing screws. 4. Move the gas control valve switch to the OFF position. Do not force. 5. Close manual gas shutoff valve external to the unit. 6. Replace the heat exchanger door on the unit. 7. If cooling and/or air circulation will be desired, turn ON the electrical power. TROUBLESHOOTING IGNITION CONTROL ERROR CODES The following presents probable causes of questionable unit operation. Refer to Diagnostic Indicator Chart for an interpretation of the signal and to this section for an explanation. Remove the control box access panel and note the number of diagnostic LED flashes. Refer to Diagnostic Indicator Chart for an interpretation of the signal and to this section for an explanation. 15 ABNORMAL OPERATION - HEATING Pressure Switch Stuck Open A pressure switch stuck open can be caused by a faulty pressure switch, faulty wiring, a disconnected or damaged hose, a blocked or restricted flue, or a faulty induced draft blower. If the control senses an open pressure switch during the prepurge cycle, the induced draft blower only will be energized. If the pressure switch opens after ignition has begun the gas valve is deenergized, the circulator blower heat off cycle begins, and the induced draft blower remains on. The diagnostic fault code is two flashes. Internal Control Failure If the integrated ignition control in this unit encounters an internal fault, it will go into a “hard” lockout and turn off the diagnostic LED. If diagnostic LED indicates an internal fault, check power supply to unit for proper voltage, check all fuses, circuit breakers and wiring. Disconnect electric power for five seconds. If LED remains off after restoring power, replace control. External Lockout Pressure Switch Stuck Closed An external lockout occurs if the integrated ignition control determines that a measurable combustion cannot be established within three (3) consecutive ignition attempts. If flame is not established within the seven (7) second trial for ignition, the gas valve is deenergized, 15 second inter-purge cycle is completed, and ignition is reattempted. The control will repeat this routine three times if a measurable combustion is not established. The control will then shut off the induced draft blower and go into a lockout state. If flame is established but lost, the control will energize the circulator blower at the heat speed and then begin a new ignition sequence. If flame is established then lost on subsequent attempts, the control will recycle for four (4) consecutive ignition attempts (five attempts total) before locking out. The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts or flame dropouts. The integrated control will automatically reset after one hour, or it can be reset by removing the thermostat signal or disconnecting the electrical power supply for over five seconds. If the diagnostic LED indicates an external lockout, perform the following checks: • Check the supply and manifold pressures • Check the gas orifices for debris • Check gas valve for proper operation • Check secondary limit A dirty filter, excessive duct static, insufficient air flow, a faulty limit, or a failed circulator blower can cause this limit to open. Check filters, total external duct static, circulator blower motor, blower motor speed tap (see wiring diagram), and limit. An interruption in electrical power during a heating cycle may also cause the auxiliary limit to open. The automatic reset secondary limit is located on top of the circulator blower assembly. • Check rollout limit If the burner flames are not properly drawn into the heat exchanger, the flame rollout protection device will open. Possible causes are restricted or blocked flue passages, blocked or cracked heat exchanger, a failed induced draft blower, or insufficient combustion air. The rollout protection device is a manual reset limit located on the burner bracket. The cause of the flame rollout must be determined and corrected before resetting the limit. • Check flame sensor A drop in flame signal can be caused by nearly invisible coating on the sensor. Remove the sensor and carefully clean with steel wool. • Check wiring Check wiring for opens/shorts and miswiring. Important: If you have to frequently reset your gas/electric package unit, it means that a problem exists that should be corrected. Contact a qualified servicer for further information. A stuck closed pressure switch can be caused by a faulty pressure switch or faulty wiring. If the control encounters a pressure switch stuck closed, the induced draft blower remains off. The diagnostic LED code for this fault is three (3) flashes. Open Thermal Protection Device If the primary limit switch opens, the gas valve is immediately deenergized, the induced draft and air circulating blowers are energized. The induced draft and air circulator blowers remain energized until the limit switch recloses. The diagnostic fault code for an open limit is four (4) flashes. A primary limit will open due to excessive supply air temperatures. This can be caused by a dirty filter, excessive duct static, insufficient air flow, or a faulty limit. Check filters, total external duct static, blower motor, blower motor speed tap (see wiring diagram), and limit. This limit will automatically reset once the temperature falls below a preset level. Flame Detected with Gas Valve Closed If flame is detected with the gas valve deenergized, the combustion and air circulator blowers are energized. The diagnostic fault code is five (5) flashes for this condition. The control can be reset by removing the power supply to the unit or it will automatically reset after one hour. Miswiring is the probable cause for this fault. ABNORMAL OPERATION - COOLING Short Cycle Compressor Delay The automatic ignition control has a built-in feature that prevents damage to the compressor in short cycling situations. In the event of intermittent power losses or intermittent thermostat operation, the ignition control will delay output to the compressor contactor for three minutes from the time power is restored. (Compressor is off a total of three minutes). The diagnostic LED will flash six (6) times to indicate the compressor contactor output is being delayed. NOTE: Some electronic thermostats also have a built-in compressor short cycle timer that may be longer than the three minute delay given above. If you are using an electronic thermostat and the compressor has not started after three minutes, wait an additional five minutes to allow the thermostat to complete its short cycle delay time. 16 MAINTENANCE CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY) The coil with the outside air flowing over it should be inspected annually and cleaned as frequently as necessary to keep the finned areas free of lint, hair and debris. CONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS Bearings on the air circulating blower motor, condenser motor and the combustion fan motor are permanently lubricated. No additional oiling is required. Have the gas heating section of the unit checked at least once a year before the heating season begins, to be sure that the combustion air inlet and flue outlet hoods are not blocked by debris, which would prevent adequate combustion air and a properly operating vent system. FLAME SENSOR (QUALIFIED SERVICER ONLY) A drop in the flame current can be caused by a nearly invisible coating on the flame sensor. This coating, created by the fuel or combustion air supply, can be removed by carefully cleaning the flame sensor with steel wool. NOTE: After cleaning, the microamp signal should be stable and in the range of 4 - 6 microamps DC. FILTER REPLACEMENT OR CLEANING A return air filter is not supplied with this unit; however, there must be a means of filtering all of the return air. The filter(s) may be located in the return air duct(s), or return air filter grille(s). Consult with your installing dealer for the actual location of the return air filter(s) for your unit. Dirty filters are the most common cause of inadequate heating or cooling performance. Filter inspection should be made at least every two months; more often if necessary because of local conditions and usage. Dirty throwaway filters should be discarded and replaced with a new, clean filter. Dirty permanent filters should be washed with water, thoroughly dried and sprayed with a filter adhesive before being reinstalled. (Filter adhesives may be found at many hardware stores.) Permanent filters should last several years. However, should one become torn or uncleanable, it should be replaced. Flame Sensor Flame Sensor CABINET FINISH MAINTENANCE FLUE PASSAGES (QUALIFIED SERVICER ONLY) Use a fine grade automotive wax on the cabinet finish to maintain the finish’s original high luster. This is especially important in installations with extended periods of direct sunlight. At the start of each heating season, inspect and, if necessary, clean the unit flue passage. CLEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY) 1. Shut off electric power and gas supply to the unit. 2. Remove burner assembly by disconnecting the gas line and removing the manifold bracket from the partition panel. 3. Remove the flue from the induced draft blower and the collector box cover from the partition panel. 4. The primary heat exchanger tubes can be cleaned using a round wire brush attached to a length of high grade stainless steel cable, such as drain cleanout cable. Attach a variable speed reversible drill to the other end of the spring cable. Slowly rotate the cable with the drill and insert it into one of the primary heat exchanger tubes. While reversing the drill, work the cable in and out several times to obtain sufficient cleaning. Use a large cable for the large tube, and then repeat the operation with a small cable for the smaller tube. Repeat for each tube. 5. When all heat exchanger tubes have been cleaned, replace the parts in the reverse order in which they were removed. 6. To reduce the chances of repeated fouling of the heat exchanger, perform the steps listed in “Startup, Adjustments, and Checks”. 17 MAIN BURNER FLAME (QUALIFIED SERVICER ONLY) CAUTION Flames should be stable, soft and blue (dust may cause orange tips but must not be yellow). The flames must extend directly outward from the burner without curling, floating or lifting off. LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. CAUTION ALWAYS VERIFY PROPER OPERATION AFTER SERVICING. For further information on the yearly inspection, consult the User Manual. It is recommended that a qualified servicer inspect and service the unit at least once each year. Turn the unit on at the thermostat. Wait a few minutes, since any dislodged dust will alter the normal flame appearance. Flames should be predominantly blue and directed into the tubes. They should not be yellow. They should extend directly outward from the burner ports without curling downward, floating or lifting off the ports. Check the burner flames for: 1. Good adjustment 2. Stable, soft and blue 3. Not curling, floating, or lifting off. Burner Flame ACCESSORIES AND FUNCTIONAL PARTS WARNING TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, SHEET METAL ACCESSORIES DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY ADJUSTMENT. Additional accessories can be purchased to fit specific application needs. Parts and instructions are available from your distributor. CONTACT A QUALIFIED SERVICER AT ONCE IF AN ABNORMAL FLAME SHOULD DEVELOP. At least once a year, prior to or during the heating season, make a visual check of the burner flames. NOTE: This will involve removing and reinstalling the heat exchanger door on the unit, which is held by two screws. If you are uncertain about your ability to do this, contact a qualified servicer. If a strong wind is blowing, it may alter the airflow pattern within the unit enough that an inspection of the burner flames is not possible. FUNCTIONAL PARTS FUNCTIONAL PARTS Auxliary Limit Switch Flame Roll-out Switch Blower Housing Flame Sensor Circulator Blower Motor Gas Orifice Blower Wheel Gas Valve Burner Heat Exchanger Capacitor High Limit Switch Compressor Igniter Condenser Coil Ignition Control Condenser Fan Blade Induced Draft Blower Condenser Fan Motor Pressure Switch Contactor Pressure Switch Hose Gas Manifold Transformer Evaporator Coil CLEANING BURNERS 1. Shut off electric power and gas supply to the unit. 2. Remove the screws securing the manifold to the burner retention bracket. Remove the manifold and rotate each burner counterclockwise to remove. Burner Burner Bracket Functional Parts List GENERAL INFORMATION 1. Refer to the description in Functional Parts List when ordering any of the listed functional parts. Be sure to provide the unit model and serial numbers with the order. 2. Although only functional parts are shown, all sheet metal parts, doors, etc. may be ordered by description. 3. Parts are available from your distributor. Manifold Manifold Assembly 3. Remove the burners. 4. Use a bottle brush to clean burner insert and inside of the burners. 5. Replace burners and manifold, inspect the burner assembly for proper seating of burners in retention slots. 6. Reconnect electrical power and gas supply. 18 IGNITION Light Signal Off 1 Flash 2 Flashes 3 Flashes 4 Flashes 5 Flashes 6 Flashes CONTROL DIAGNOSTIC Gas Valve CHART Refer to Abnormal Heating or Cooling Operation Sections of this Manual Internal Control Failure External Lockout Pressure Switch Stuck Open Pressure Switch Stuck Closed Thermal Protection Device Open Flame Detected with Gas Valve Closed Short Cycle Compressor Delay (Cooling Only) HEATING TIMING Circulator Blower INDICATOR CHART 100 % 50 % On Off On Off Igniter On Off Induced Draft Blower On Off Thermostat On Off 0 Seconds Legend: 15 22 45 52 0 29 120, 135,150 180*PG1348,60 ONLY *PG10,12,24-60, *PG1324-42 *PG1348,60 COOLING Circulator Blower TIMING CHART 100 % 50 % ON OFF Outdoor Fan and Compressor Thermostat ON OFF ON OFF Seconds Legend: 0 7 30 0 *PG10,12,24-60, *PG1324-42 *PG1348,60 19 60 APPENDIX UNIT DIMENSIONS 47 51 18 7/16 16 FLUE EXHAUST 1 3/8 C A 5 1/2 16 7 15/16 B 2 3/4 SUCTION/LIQUID PRESSURE PORTS BEHIND COMPRESSOR ACCESS PANEL RETURN B HEAT EXCHANGE ACCESS PANEL 4 3/4 GAS SUPPLY ENTRANCE CONDENSATE DRAIN CONNECTION 3/4" NPT FEMALE SUPPLY 3 EVAPORATOR/CONTROL PANEL ACCESS PANEL 16 1/8 19 1/8 OF ER Y NT VIT E C RA G 7 5/16 DIMENSION DIMENSION INCHES 7 7/8 20 (INCHES) A B 24 C POWER WIRE ENTRANCE A B C MEDIUM LARGE SMALL MEDIUM LARGE 27 16 7 1/2 32 16 32 16 9 1/2 9 1/2 40 40 18 18 14 14 CONTROL WIRE ENTRANCE HOOD FLUE EXHAUST 5 1/4 BLOWER ACCESS PANEL COMBUSTION AIR INLETS 11 5 3/4 22 22 11 SUPPLY RETURN 20 GPG13(24,30,36,42)1A WIRING DIAGRAM P HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. R Y R B PU GRD B S R C T1 BL BL B R BL COMP BL B T2 L1 B CC Y Y L2 B B CH OPTIONAL CONNECTED AT L1, L2 NOTE 4 CH OPTIONAL PU BR POW ER SUPPLY 208-230/1/60 B 1 C PU 2 208 3 240 B NOTE 2 TRANS CM 24V R PU CAP2 NOTE 5 BL R LS PU(L2) R HIGH 12345 EM PU BR GR EM MEDIUM B BR BR LOW BL R 3 SPEED OPTIONAL R Y CAP.2 BL B ALT. 3 SPEED MOTOR PU 4 SPEED MOTOR BL Y R ALS B PU B PS Y PU Y RS ECON G NO TE 6 PL Y 3 6 2 5 1 4 BL PU PU Y W. R. GAS VALVE PU MV PU Y R BL IIC W Y G GV GV BL FS (ALT.) HONEYWELL GAS VALVE BL MV O Y2 Y1 C R Y W G BL R Y R R TO THC B VM NOTE 3 IGN FS B PU O PU R NOTE 5 CAP1 PU F R H C R PU BR Y B4312003 REV. B Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 21 GPG13(24,30,36,42)1A WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. B4312003 REV. B Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 22 GPG13(48)1A WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. R R B Y PU GRD B S R C T1 BL T2 BL B R BL COMP Y BL B L1 B CC L2 B CH OPTIONAL CONNECTED AT L1, L2 NOTE 4 CH OPTIONAL B PU BR POWER SUPPLY 208-230/1/60 B PU 1 2 3 C 208 240 CM B NOTE 2 TRANS 24V E/W1 W/W2 O OTC OT1 OT2 C OUTDOOR PU R C R G Y BL R G Y LS Y1 Y2 R Y BL TB Y1 G Y1/Y2 R Y1 24 VAC C R HUMIDISTAT HUM G W BL W R TH ERMOSTAT HEATER 7 8 HEATPUMP 3 4 5 6 OFF CONDENSER DIP SWITCH 1 2 ON VSM R YCON COM O W2 ED W1 W2 VSTB R R TO THC (SEE THCFIELDWIRINGBELOW) G BL PU BL W Y Y G R Y Y W G B Y W B ALS R G Y B W PU PU PU BL Y R PS Y PU Y RS ECON G NOTE 5 PL R Y 10 5 8 11 6 9 12 BL 4 4 7 1 R 3 5 2 6 2 1 3 Y PU PU PU Y R Y Y FS (ALT.) HONEYWELL GAS VALVE BL BL MV UNUSED MV O GV GV R HEAT R NOTE 3 IGN FS B COOL VM PU O B L2 PU L1 GAS VALVE IIC DI W. R. B PU R CAP1 PU F R H C R PU BR Y B4312004 Rev. A Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 23 GPG13(48)1A WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. L1 L2 SUPPLY VOLTAGE 208-230/1/60 CH CC C NOTE 4 T2 R T1 L1 L2 C COMP H S CC CAP1 F L1 C L1 H L1 D1 COMPONENT LEGEND CM NOTE 5 L2 VSM NOTE 3 VM L2 TRANS L1 ALS AUXILLARY LIMIT SWITCH WIRE SPLICE CAP CAPACITOR COMP COMPRESSOR MARKED TERMINAL UNMARKED TERMINAL CM CONDENSER MOTOR WIRING CC CONTACTOR CH CRANKCASE HEATER LINE VOLTAGE FS GV IIC IGN FIELD INSTALLED CONTROL FLAME SENSOR GAS VALVE INTEGRATED IGNITION CONTROL IGNITOR B BLACK PL PLUG BL BR G O PK BLUE BROWN GREEN ORANGE PINK PU R W Y PURPLE RED WHITE YELLOW RS ROLLOUT SWITCH TB TERMINAL BLOCK NOTE 2 1 THC THERMOSTAT HEAT & COOL TRANS TRANSFORMER 2 VM VENT MOTOR VSM VAR. SPEED MOTOR IGN FUSE FS FS WIRE CODE LS LIMIT SWITCH PS PRESSURE SWITCH L2 LOW VOLTAGE FIELD INSTALLED POWER VSTB VARIABLE SPEED TERM. BLOCK 4 LS 5 ALS NOTES RS 3 GV 1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY). IIC 6 ECON 7 9 PS 2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER. 8 10 CC 12 3. SOME MODELS HAVE VENT MOTORS EQUIPPED WITH A 230V LEAD (RED) AND A 208V (BLACK). IF EQUIPPED, CONNECT VENT MOTOR BLACK LEAD IN PLACE OF RED LEAD AT UII (DI) FOR 208V OPERATION. 11 4. CRANKCASE HEATER (OPTIONAL). TB R G W Y C VSTB R G W/W2 Y/Y2 C R G W Y C Y1 Y1 NOTE 5 PL Y2 Y2 5. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARMENT. 6 5 4 3 2 1 6. TWO STAGE THERMOSTAT CONNECTIONS IF USED WITH ECONOMIZER OPTION INSTALLED. NOTE 6 TO THC 208-230/1/60 INSTALLER/SERVICEMAN THC-FIELD WIRING THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: STATUS LIGHT EQUIP. STATUS ON NORMAL OPERATION THC-NO ECONOMIZER CHECK 2 STAGE COOLING W W W G G G G R R R R Y Y PU Y1 BL C Y Y2 BL C - NO POWER OR INTERNAL CONTROL FAULT CHECK INPUT POWER CHECK FUSE ON CONTROL REPLACE CONTROL IGNITION FAILURE OR OPEN ROLLOUT SWITCH OR OPEN AUX. LIMIT SWITCH GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN 2 BLINKS PRESSURE SWITCH OPEN CHECK PRESSURE SWITCH W W 3 BLINKS PRESSURE SWITCH CLOSED WITHOUT INDUCER ON CHECK PRESSURE SWITCH G G 4 BLINKS OPEN LIMIT SWITCH MAIN LIMIT OPEN BAD SWITCH R R 5 BLINKS FALSE FLAME SENSED STICKING GAS VALVE PU Y1 6 BLINKS COMPRESSOR OUTPUT DELAY 3 MIN. COMP. ANTI-CYCLE TIMER BL C OFF 1 BLINK W THC-WITH ECONOMIZER OPTION B4312004 Rev. A Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 24 GPG13(60)1A WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Y R R B Y PU Y S R C GRD B T1 BL T2 BL B COMP R BL SOL Y BL BL B L1 B CC L2 B CH OPTIONAL CONNECTED AT L1, L2 NOTE 4 CH OPTIONAL B PU BR POWER SUPPLY 208-230/1/60 B PU 1 2 3 C 208 240 CM B NOTE 2 TRANS 24V PU C R G R LS BL BL R Y/Y2 W Y1 R G Y PU W Y BL BL TB Y1 G Y1/Y2 R 24 VAC Y1 R HUMIDISTAT HUM G Y1 BL W R THERMOSTAT HEATER E/W1 W/W 2 O OTC OT1 OT2 C OUTDOO R HEATPUMP 3 4 5 6 7 8 OFF CONDENSER DIP SWITCH 1 2 ON VSM R YCON COM O W2 ED W1 W2 C VSTB R R Y TO THC (SEETHCFIELDWIRINGBELOW) G BL PU BL W PU B Y Y W G R Y Y PU G Y W B ALS R Y G B W PU PU PU BL Y R PS Y PU Y G NOTE 5 PL ECON R RS Y 7 10 8 11 6 9 12 R Y 4 3 1 BL 5 5 2 2 4 6 1 3 PU PU PU Y R Y Y FS (ALT.) HONEYWELL BL BL MV O GV R HEAT R NOTE 3 IGN FS B COOL VM PU O B L2 MV UNUSED PU L1 GAS VALVE GV IIC DI W. R. GAS VALVE B PU R CAP1 PU F R H C R PU BR Y B4312005 Rev. A Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 25 GPG13(60)1A WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. L1 L2 SUPPLY VOLTAGE 208-230/1/60 CH CC L1 C NOTE 4 T2 R T1 L2 C COMP H S CC CAP1 F L1 C L1 H L1 COMPONENT LEGEND CM NOTE 5 L2 VSM NOTE 3 D1 VM L2 TRANS L1 ALS AUXILLARY LIMIT SWITCH WIRE SPLICE CAP CAPACITOR MARKED TERMINAL COMP COMPRESSOR UNMARKED TERMINAL CM CONDENSER MOTOR WIRING CC CONTACTOR CH CRANKCASE HEATER LINE VOLTAGE FS GV IIC IGN FIELD INSTALLED CONTROL FLAME SENSOR GAS VALVE INTEGRATED IGNITION CONTROL IGNITOR B BLACK PL PLUG BL BR G O PK PU R BLUE BROWN GREEN ORANGE PINK PURPLE RED RS ROLLOUT SWITCH nd SOL SOLENOID (2 STAGE) NOTE 2 TB TERMINAL BLOCK 2 1 THC THERMOSTAT HEAT & COOL TRANS TRANSFORMER VM VENT MOTOR IGN FUSE FS FS VSM VAR. SPEED MOTOR 4 WIRE CODE LS LIMIT SWITCH PS PRESSURE SWITCH L2 LOW VOLTAGE FIELD INSTALLED POWER W WHITE Y YELLOW VSTB VARIABLE SPEED TERM. BLOCK LS 5 ALS NOTES RS 3 GV 1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY). IIC 6 ECON 7 9 PS 2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER. 8 10 CC 12 3. SOME MODELS HAVE VENT MOTORS EQUIPPED WITH A 230V LEAD (RED) AND A 208V LEAD (BLACK). IF EQUIPPED, CONNECT VENT MOTOR BLACK LEAD IN PLACE OF RED LEAD AT UII (D1) FOR 208V OPERATION. 11 SOL 4. CRANKCASE HEATER (OPTIONAL). TB R G W Y/Y2 C Y1 VSTB R G W/W2 Y/Y2 C Y1 R G W C Y1 Y2 5. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARMENT. NOTE 5 PL Y1 6 5 4 3 2 1 6. TWO STAGE THERMOSTAT CONNECTIONS IF USED WITH ECONOMIZER OPTION INSTALLED. NOTE 6 TO THC 208-230/1/60 INSTALLER/SERVICEMAN THC-FIELD WIRING THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: THC-NO ECONOMIZER STATUS LIGHT EQUIP. STATUS CHECK ON NORMAL OPERATION - OFF NO POWER OR INTERNAL CONTROL FAULT CHECK INPUT POWER CHECK FUSE ON CONTROL REPLACE CONTROL IGNITION FAILURE OR OPEN ROLLOUT SWITCH OR OPEN AUX. LIMIT SWITCH GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN 2 BLINKS PRESSURE SWITCH OPEN CHECK PRESSURE SWITCH 3 BLINKS PRESSURE SWITCH CLOSED WITHOUT INDUCER ON CHECK PRESSURE SWITCH 4 BLINKS OPEN LIMIT SWITCH MAIN LIMIT OPEN BAD SWITCH 5 BLINKS FALSE FLAME SENSED 6 BLINKS COMPRESSOR OUTPUT DELAY 1 BLINK THC-WITH ECONOMIZER W W W G G G W G R R R R PU Y1 PU Y1 Y Y2 Y Y2 BL C BL C STRIPPED LEAD STRIPPED LEAD FROM TERMINAL BLOCK FROM ECON. PLUG STICKING GAS VALVE 3 MIN. COMP. ANTI-CYCLE TIMER B4312005 Rev. A Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 26 GPG13(36)3A WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. YL RD RD BK PU BK T3 T2 T1 T1 BL T2 T3 L2 L3 GND BL BK YL BL COMP L1 BL BK C YL BK BK BK CH OPTIONAL CONNECTED AT L1, L2 NOTE 3 CH OPTIONAL SEE NOTE 3 POWER SUPPLY 208-230/3/60 SEE NOTE 6 PU BR BK PU 1 2 3 C 208 240 CM BK TR NOTE 2 24V PU RD RD BL NOTE 4 LS RD EM PU 3 SPEED BR MOTOR FC RD BK PU BL BK RD ALS BL PU BK PS BR BL YL PU YL ECON GR RS NOTE 5 PLF YL 7 10 8 11 6 9 12 4 3 1 PU 5 5 2 2 4 6 1 3 BL PU PU YL WH GV YL BL YL GR BK BK RD BL COOL OR FS RD RD TO THERMOSTAT IGN OR HEAT Y2 Y1 C R Y W G VM IIC UNUSED BL MV RD L1 MV PU L2 PU GV BL FS (ALT.) HONEYWELL GAS VALVE DI W. R. GAS VALVE RD PU NOTE 4 PU FC PU F RD C PU BR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 27 RD GPG13(36)3A WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. L1 SUPPLY VOLTAGE L2 L3 CH NOTE 3 C T3 C T1 L1 COMP L3 T2 T2 T1 C T3 FC L2 C F FC CM IIC L1 C L1 H L1 D1 (MED) NOTE 4 EM L2 VM L1 3 2 L2 1 L2 NOTE 2 1 2 TR IGN F ALS AUXILLARY LIMIT SWITCH LINE VOLTAGE COMP COMPRESSOR LOW VOLTAGE CM CONDENSER MOTOR C CONTACTOR OPTIONAL HIGH VOLTAGE FIELD WIRING CH CRANKCASE HEATER EM EVAPORATOR MOTOR HIGH VOLTAGE F FUSE LOW VOLTAGE FC FAN CAPACITOR FS FLAME SENSOR GND EQUIPMENT GROUND GV IIC IGN GAS VALVE INTEGRATED IGNITION CONTROL IGNITOR LS LIMIT SWITCH PLF FEMALE PLUG/CONNECTOR PS RS PRESSURE SWITCH ROLLOUT SWITCH PU PURPLE TR TRANSFORMER VM VENT MOTOR WH WHITE YL YELLO W WIRE CODE BK BLACK BL BLUE BR BROWN GR G REEN OR O RANGE PK PINK RD RED FS FS NOTES 4 LS 1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF 5 INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY). ALS 2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE RS 3 FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER. GV IIC 3. CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS. 6 PS 4. FOR DIFFERENT THAN FACTORY SPEED TAP. CHANGE CO OLING 8 SPEED AT COOL TERMINAL (IIC). CHANGE HEATING SPEED AT HEAT ECON 9 FACTORY WIRING COMPONENT LEG END 208-230/3/60 7 10 TERMINAL (IIC) 12 3 SPEED MOTOR C 11 BK - HIGH SPEED BL - MEDIUM SPEED NOTE 5 RD - LOW SPEED PLF R G W Y1 Y2 Y C 6 5 4 3 2 1 5. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARMENT. 6. USE COOPER CONDUCTORS ONLY. USE NEC CLASS 2 WIRE. TO THERMOSTAT 208-230/3/60 INSTALLER/SERVICEMAN THERMOSTAT FIELD WIRING THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: STATUS LIGHT ON OFF 1 BLINK 2 BLINKS 3 BLINKS EQUIP. ST ATUS NORMAL OPERATION NO POWER OR INTERNAL CONTROL FAULT CHECK CHECK INPUT POWER CHECKFUSEONCONTROL REPLACE CONTROL WH W WH W GR G GR G RD R RD R YL Y PU Y1 BL C YL Y2 BL C IGNITION FAILURE OR OPEN ROLLOUT SWITCH OR OPEN AUX. LIMIT SWITCH GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN PRESSURE SWITCH OPEN CHECK PRESSURE SWITCH WH W CHECK PRESSURE SWITCH GR G MAIN LIMIT OPEN BAD SWITCH RD R STICKING GAS VALVE PU Y 3 MIN. COMP. ANTI-CYCLE TIMER BL C PRESSURE SWITCH CLOSED WITHOUT INDUCER ON 4 BLINKS OPEN LIMIT SWITCH 5 BLINKS FALSE FLAME SENSED 6 BLINKS 2 STAGE COOLING NO ECONOMIZER COMPRESSOR OUTPUT DELAY WITH ECONOMIZER OPTION 0140G00085P Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 28 GPG13(48,60)3A WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. YL RD RD BK PU BK T3 T2 T1 T1 BL T2 T3 GND YL BL BK YL COMP L1 BK CH OPTIONAL CONNECTED AT L1, L2 NOTE 3 L2 C BK L3 BK BK BL PU BR CH OPTIONAL PU PU BK BK POWER SUPPLY 208-230/3/60 SEE NOTE 6 BK PU CM BK NOTE2 BK 2 3 208 240 3 4 TR PU BL 1 C LS GR 1 BL VMR RD C L G N 2 24V RD BL BL BL RD RD RD YL YL PU WH EM T1 T2 T3 T4 T5 RD WH NOTE 4 C22 T2 T1 BREAK FOR TWO STAGE COMPRESSOR P2 SPEED-UP ALS MOUNT SCREW REQUIRED YL OR 150 P3 135 FUSE 3 AMP MAX 120 10 8 11 9 12 2 5 YL RD BL UNUSED 4 YL SEE NOTE 7 MV PU YL RD BL WH YL GR BL BL IIC HEAT COOL PU L2 (ALT.) HONEYWELL GAS VALVE WH BL L1 BL PU W. R. GAS VALVE RD DI 6 FS 3 1 PU F1 7 3 YL YL WH RD GR RS BL 6 YL NOTE 5 PLF WH YL YL YL BR 5 PU 2 YL GR 4 PS PU RD 1 RD BL P1 RD ECON PU GV GV BL MV Y2 Y1 C R Y W G BL TO THERMOSTAT VM FS RD IGN OR RD YL WH RD FC PU BL RD YL WH BR BR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 29 RD GPG13(48,60)3A WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. L1 L2 SUPPLY VOLTAGE 208-230/3/60 CH C T1 COMPONENT LEGEND NOTE 3 C L2 T2 T1 COMP L3 T3 T3 FC L C CM N VMR EM 2 3 2 VM SEE NOTE 2 4 1 NOTE 7 L1 NOTE 7 FS L2 IIC FS T5 C T4 H T3 EM COMPRESSOR CONDENSER MOTOR CONTACTOR CRANKCASE HEATER EVAPORATOR MOTOR LOW VOLTAGE OPTIONAL HIGH VOLTAGE F FC FUSE FAN CAPACITOR HIGH VOLTAGE FS FLAME SENSOR D1 1 4 LOW VOLTAGE GND EQUIPMENT GROUND WIRE CODE GV IIC GAS VALVE INTEGRATED IGNITION CONTROL BK BLACK IGN IGNITOR LS LIMIT SWITCH FEMALE PLUG/CONNECTOR BL BLUE BR BROWN GR GREEN OR ORANGE PK PINK PU PURPLE PRESSURE SWITCH TR ROLLOUT SWITCH TRANSFORMER VM VMR VENT MOTOR VENT MOTOR RELAY RD RED WH WHITE YL YELLOW NOTES 3 1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY). VMR LS FIELD WIRING C T2 T1 2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE 5 ALS IIC CM C CH EM RS IGN F LINE VOLTAGE PLF PS TR FACTORY WIRING AUXILLARY LIMIT SWITCH ALS COMP T2 L1 L3 FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER. RS 3 3. CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS. GV 4. FOR DIFFERENT THAN FACTORY SPEED TAP. CHANGE COOLING 6 SPEED AT MOTOR T4 AND T5 TERMINALS. CHANGE HEATING PS ECON 9 7 SPEED AT MOTOR T1, T2 AND T3 TERMINALS. 8 10 12 C 11 NOTE 5 G W Y1 Y2 Y C HEATING SPEED (WHITE WIRE) T4 - LOW SPEED T5 - HIGH SPEED T1 - LOW SPEED T2 - MED. SPEED T3 - HIGH SPEED 6 5 4 5. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARMENT. 3 2 1 6. USE COOPER CONDUCTORS ONLY. USE NEC CLASS 2 WIRE. PLF R COOLING SPEED (YELLOW WIRE) 7. L1 AND L2 ON ICC CONTROL IS 24V INPUT. TO THERMOSTAT 208-230/3/60 INSTALLER/SERVICEMAN THERMOSTAT FIELD WIRING THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: STATUS LIGHT EQUIP. STATUS 2 STAGE COOLING NO ECONOMIZER CHECK WH W WH W GR G GR G RD R RD R YL Y PU Y1 BL C YL Y2 BL C ON NORMAL OPERATION OFF NO POWER OR INTERNAL CONTROL FAULT CHECK INPUT POWER CHECKFUSEONCONTROL REPLACE CONTROL IGNITION FAILURE OR OPEN ROLLOUT SWITCH OR OPEN AUX. LIMIT SWITCH GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN 2 BLINKS PRESSURE SWITCH OPEN CHECK PRESSURE SWITCH WH W 3 BLINKS PRESSURE SWITCH CLOSED WITHOUT INDUCER ON CHECK PRESSURE SWITCH GR G 4 BLINKS OPEN LIMIT SWITCH MAIN LIMIT OPEN BAD SWITCH RD R 5 BLINKS FALSE FLAME SENSED STICKING GAS VALVE PU Y 6 BLINKS COMPRESSOR OUTPUT DELAY 3 MIN. COMP. ANTI-CYCLE TIMER BL C 1 BLINK - WITH ECONOMIZER OPTION 0140G00087 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 30 GPG13(36)4A WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. YL RD RD BK GND PU BK T3 T2 T1 T1 T2 T3 L2 L3 BL BK YL YL BL COMP L1 BK CH OPTIONAL CONNECTED AT L1, L2 NOTE 2 C BK BK BL BK BK CH OPTIONAL POWER SUPPLY 460/3/60 SEE NOTE 6 PU BR BK BK RD PU PU CM 3 1 C 480 FC BL 2 VMR 3 2 BL 1 TR LS BR BR 24V BK RD SEE NOTE 3 EM RD BL GR 2 GR RD RD IBR WH 3 BL 1 PU BK BK RD/YL RD OR ALS ECON RD PU GR RD 7 10 BL 2 5 8 11 PU 3 6 9 12 YL YL YL RD GR FS RS 2 5 1 4 YL BL BL BL MV BL MV PU YL RD BL WH YL BL GR BL COOL PU RD HEAT (ALT.) HONEYWELL GAS VALVE IIC RD SEE NOTE 5 L2 W. R. GAS VALVE UNUSED PU RD WH L1 6 DI 3 YL PU YL WH YL NOTE 4 PLF 4 YL 1 PS PU RD GR GR GV GV Y2 Y1 C R Y W G BL TO THERMOSTAT VM FS RD IGN OR FC RD RD BK BR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 31 BK GPG13(36)4A WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. L1 SUPPLY VOLTAGE 460/3/60 CH L2 C T2 T1 COMPONENT LEGEND NOTE 2 T2 C L3 L2 T1 COMP L1 T3 L3 T3 FC FC C CM (LOW) EM (HIGH) VM 1 3 1 3 1 IBR VMR 3 TR NOTE 5 NOTE 5 L1 L2 IGN H IBR FS FS F IIC C D1 4 FACTORY WIRING ALS AUXILLARY LIMIT SWITCH LINE VOLTAGE COMP COMPRESSOR LOW VOLTAGE CM CONDENSER MOTOR OPTIONAL HIGH VOLTAGE C CONTACTOR CH CRANKCASE HEATER EM EVAPORATOR MOTOR FIELD WIRING HIGH VOLTAGE LOW VOLTAGE F FUSE FC FAN CAPACITOR FS FLAME SENSOR WIRE CODE GND EQUIPMENT GROUND BK BLACK GV IBR GAS VALVE INDOOR BLOWER RELAY BL BLUE BR BROWN IIC IGN INTEGRATED IGNITION CONTROL IGNITOR LS LIMIT SWITCH PLF FEMALE PLUG/CONNECTOR GR OR PK PU PS PRESSURE SWITCH RS ROLLOUT SWITCH TR VM TRANSFORMER VMR VENT MOTOR RELAY GREEN ORANGE PINK PURPLE RD RED WH WHITE YL YELLOW VENT MOTOR VMR LS 5 NOTES ALS 1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF RS 3 INSUL ATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY). GV IIC 2. CRANKCASE HEATER NOT SUPPLIED ON AL L UNITS. 6 PS 3. 460V UNITS ARE SINGLE SPEED, TO CHANGE FROM HIGH TO LOW 8 SPEED REPLACE THE BLACK MOTOR LEAD AT IBR#3 WITH RED ECON 9 7 LEAD FROM MOTOR. 10 12 2 SPEED MOTOR C 11 BL - HIGH SPEED RD/YL - LOW SPEED 4. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT NOTE 4 6 5 4 3 2 1 TO BLOWER HOUSING IN RETURN AIR COMPARMENT. PLF R G W Y1 Y2 Y C 5. L1 AND L2 ON IIC CONTROL IS 24V INPUT. 6. USE COOPER CONDUCTORS ONLY. USE NEC CLASS 2 WIRE. TO THERMOSTAT 460/3/60 INSTALLER/SERVICEMAN THERMOSTAT FIELD WIRING THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: STATUS LIGHT EQUIP. STATUS 2 STAGE COOLING NO ECONOMIZER CHECK W WH W GR G GR G RD R RD R YL Y PU Y1 BL C YL Y2 BL C WH ON NORMAL OPERATION OFF NO POWER OR INTERNAL CONTROL FAULT CHECK INPUT POWER CHECKFUSE ONCONTROL REPLACE CONTROL IGNITION FAILURE OR OPEN ROLLOUT SWITCH OR OPEN AUX. LIMIT SWITCH GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN 2 BLINKS PRESSURE SWITCH OPEN CHECK PRESSURE SWITCH WH W 3 BLINKS PRESSURE SWITCH CLOSED WITHOUT INDUCER ON CHECK PRESSURE SWITCH GR G 4 BLINKS OPEN LIMIT SWITCH MAIN LIMIT OPEN BAD SWITCH RD R 5 BLINKS FALSE FLAME SENSED STICKING GAS VALVE PU Y 6 BLINKS COMPRESSOR OUTPUT DELAY 3 MIN. COMP. ANTI-CYCLE TIMER BL C 1 BLINK - WITH ECONOMIZER OPTION 0140G00088 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 32 GPG13(48,60)4A WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. YL RD RD BK PU T3 T2 T1 BK T1 BL BK COMP T2 T3 GND YL BL BK YL L1 CH OPTIONAL CONNECTED AT L1, L2 NOTE 2 PU BR BK L3 L2 C BK BK BL BK POW ER SUPPLY 460/3/60 SEE NOTE 5 PU PU BK BK CH OPTIONAL CM PU BK RD PU 1 H1 H3 H2 H4 X2 X3 3 480 3 C SEE NOTE 7 TR X4 2 2 TR LS X1 24V RD 1 BL VMR PU BK GR RD BL RD RD BL BL BK PU YL WH BL C L G N EM T1 T2 T3 T4 T5 WH NOTE 3 YL OR ALS 8 11 9 12 YL RD BL UNUSED 4 YL BL WH YL GR BL BL RD SEE NOTE 6 IIC HEAT COOL RD PU L2 MV WH BL L1 BL (ALT.) HONEYW ELL GAS VALVE PU 7 5 DI 6 2 YL W. R. GAS VAL VE 10 RD PU PU YL YL WH FS 3 1 6 YL YL GR RS BL 3 NOTE 4 PLF WH 5 YL 2 PU YL GR 4 BR YL RD 1 PS PU P1 RD RD BL ECON PU GV GV BL MV Y2 Y1 C R Y W G BL TO THERMOSTAT VM FS RD IGN OR RD YL WH RD FC PU BL RD YL WH BR BR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 33 YL RD GPG13(48,60)4A WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. SUPPLY VOLTAGE 460/3/60 L1 CH C L2 ALS COMP NOTE 2 T2 L1 CM C CH EM C T2 T1 COMPONENT LEGEND L3 L2 T1 COMP L3 T3 T3 FC CM H1 EM L C H4 VMR TR SEE NOTE 7 X4 VM 3 1 X1 N 3 1 TR NOTE 6 NOTE 6 L1 L2 IIC IGN FS FS F C T4 H T3 EM C LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING EVAPORATOR MOTOR FUSE FAN CAPACITOR FS FLAME SENSOR GND EQUIPMENT GROUND WIRE CODE GV GAS VALVE BK BLACK IIC INTEGRATED IGNITION CONTROL IGN IGNITOR BL BLUE BR BROWN LS PLF LIMIT SWITCH FEMALE PLUG/CONNECTOR GR GREEN PS PRESSURE SWITCH RS ROLLOUT SWITCH TR TRANSFORMER OR PK PU RD VM VENT MOTOR VENT MOTOR RELAY WH WHITE YL YELLOW HIGH VOLTAGE LOW VOLTAGE ORANGE PINK PURPLE RED 1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF D1 INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY). 4 VMR LS 2. CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS. 5 3. FOR DIFFERENT THAN FACTORY SPEED TAP. CHANGE COOLING ALS IIC RS SPEED AT MOTOR T4 AND T5 TERMINALS. CHANGE HEATING GV 3 SPEED AT MOTOR T1, T2 AND T3 TERMINALS. 6 PS ECON 7 8 10 T1 - LOW SPEED T2 - MED. SPEED T3 - HIGH SPEED 5. USE COOPER CONDUCTORS ONLY. PLF W HEATING SPEED (WHITE WIRE) T4 - LOW SPEED T5 - HIGH SPEED 4. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARMENT. C NOTE 4 G COOLING SPEED (YELLOW WIRE) 12 11 R COMPRESSOR CONDENSER MOTOR CONTACTOR CRANKCASE HEATER NOTES T2 T1 9 LINE VOLTAGE F FC VMR T5 FACTORY WIRING AUXILLARY LIMIT SWITCH Y1 Y2 Y C 6 5 4 6. L1 AND L2 ON ICC CONTROL IS 24V INPUT. 3 2 1 7. STEPDOWN TRANSFORMER 460V PRIMARY INPUT & 240V SECONDARY OUTPUT USE NEC CLASS 2 WIRE. TO THERMOSTAT 460/3/60 INSTALLER/SERVICEMAN THERMOSTAT FIELD WIRING THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: STATUS LIGHT ON EQUIP. STATUS NORMAL OPERATION 2 STAGE COOLING NO ECONOMIZER CHECK WH W WH W GR G GR G RD R RD R YL Y PU Y1 BL C YL Y2 BL C - NO POWER OR INTERNAL CONTROL FAULT CHECK INPUT POWER CHECKFUSEONCONTROL REPLACE CONTROL IGNITION FAILURE OR OPEN ROLLOUT SWITCH OR OPEN AUX. LIMIT SWITCH GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN 2 BLINKS PRESSURE SWITCH OPEN CHECK PRESSURE SWITCH WH W 3 BLINKS PRESSURE SWITCH CLOSED WITHOUT INDUCER ON CHECK PRESSURE SWITCH GR G 4 BLINKS OPEN LIMIT SWITCH MAIN LIMIT OPEN BAD SWITCH RD R 5 BLINKS FALSE FLAME SENSED STICKING GAS VALVE PU Y 6 BLINKS COMPRESSOR OUTPUT DELAY 3 MIN. COMP. ANTI-CYCLE TIMER BL C OFF 1 BLINK WITH ECONOMIZER OPTION 0140G00089 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 34 GPG13(48,60)1B WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. YL RD RD BK PU BK S R C T1 BL T2 GND YL BL BK COMP C L1 BK YL L2 BK CH OPTIONAL CONNECTED AT L1, L2 NOTE 3 PU CH OPTIONAL BK BK BL BK BK BK POWER SUPPLY 208-230/1/60 SEE NOTE 6 PU PU BR PU BK CM NOTE 2 BK LS L G N C 2 3 208 240 3 4 TR PU GR BL 1 C 2 24V RD 1 BL VMR RD BL BL BL RD RD RD PU YL YL WH EM T1 T2 T3 T4 T5 RD WH NOTE 4 C22 T2 T1 BREAK FOR TWO STAGE COMPRESSOR P2 SPEED-UP MOUNT SCREW REQUIRED YL OR 150 P3 ALS 135 FUSE 3 AMP MAX 120 F1 8 11 9 12 RD BL RD WH DI BL RD BL UNUSED BL L1 5 4 FS 2 1 SEE NOTE 7 RD PU YL BL WH YL GR BL BL IIC HEAT COOL MV L2 (ALT.) HONEYWELL GAS VALVE PU 7 6 YL 6 YL W. R. GAS VALVE OR YL WH RD PU PU 10 3 YL 5 BL YL YL GR RS 3 2 YL GR 4 PU YL NOTE 5 PLF WH BR YL RD 1 PS PU P1 RD RD BL ECON PU GV GV BL MV Y2 Y1 C R Y W G BL TO THERMOSTAT VM FS RD IGN OR RD YL WH RD RCCF PU BL F H C RD YL WH BR BR L1 SU PPLY VOLTAGE YL L2 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 35 RD YL GPG13(48,60)1B WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. SUPPLY VOLTAGE 208-230/1/60 CH L1 L2 ALS COMP NOTE 3 C T2 C T1 R L1 L2 C COMP H RCCF C S F CM L N EM VMR 4 VM 2 NOTE 2 2 3 1 TR L1 NOTE 7 NOTE 7 L2 IIC IGN FS FS F T5 C AUXILLARY LIMIT SWIT CH LINE VOLTAGE COMPRESSOR LOW VOLTAGE CM C CONDENSER MOTOR OPTIONAL HIGH VOLTAGE CH CRANKCASE HEAT ER CONTACTOR FIELD WIRING EM EVAPORATOR MOTOR F FS FUSE HIGH VOLTAGE FLAME SENSOR LOW VOLTAGE GND EQUIPMENT GROUND GV GAS VALVE WIRE CODE IIC INTEGRATED IGNITION CONTROL BK BLACK IGN IGNITOR BL BLUE LS PLF LIMIT SWITCH FEMALE PLUG/CONNECTOR BR BROWN PS PRESSURE SWITCH OR ORANGE RCCF RUN CAPACITOR FOR COMPRESSOR/FAN PK PINK RS ROLLOUT SWITCH PU PURPLE TR TRANSFORMER RD RED VM VENT MOTOR WH WHITE VMR VENT MOTOR RELAY GR GREEN YL YELLOW T4 EM H C T3 T2 T1 D1 1 4 NOTES 1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF 3 INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY). VMR LS 2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE 5 FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER. ALS IIC RS 3. CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS. GV 3 4. FOR DIFFERENT T HAN FACTORY SPEED TAP. CHANGE COOLING SPEED AT MOTOR T4 AND T5 TERMINALS. CHANGE HEATING 6 PS ECON 9 FACTORY WIRING COMPONENT LEGEND 7 SPEED AT MOTOR T1, T2 AND T3 TERMINALS. 8 10 12 C 11 COOLING SPEED (YELLOW WIRE) HEATING SPEED (WHITE WIRE) T4 - LOW SPEED T1 - LOW SPEED T5 - HIGH SPEED T2 - MED. SPEED T3 - HIGH SPEED NOTE 5 PLF R G W Y1 Y2 Y C 6 5 4 3 2 1 5. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARMENT. 6. USE COOPER CONDUCTORS ONLY. USE NEC CLASS 2 WIRE. 7. L1 AND L2 ON ICC CONT ROL IS 24V INPUT. TO THERMOSTAT 208-230/1/60 INSTALLER/SERVICEMAN THERMOSTAT FIELD WIRING THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: STATUS LIGHT EQUIP. STATUS 2 STAGE COOLING NO ECONOMIZER CHECK W WH W G GR G RD R RD R YL Y PU Y1 BL C YL Y2 BL C WH ON NORMAL OPERATION OFF NO POWER OR INTERNAL CONTROL FAULT IGNITION FAILURE OR OPEN ROLLOUT SWITCH OR OPEN AUX. LIMIT SWITCH CHECK INPUT POWER CHECKFUSEONCONTROL REPLACE CONTROL GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN 2 BLINKS PRESSURE SWITCH OPEN CHECK PRESSURE SWITCH WH W 3 BLINKS PRESSURE SWITCH CLOSED WITHOUT INDUCER ON CHECK PRESSURE SWITCH GR G 4 BLINKS OPEN LIMIT SWITCH MAIN LIMIT OPEN BAD SWITCH RD R PU Y BL C 1 BLINK - 5 BLINKS FALSE FLAME SENSED STICKING GAS VALVE 6 BLINKS COMPRESSOR OUTPUT DELAY 3 MIN. COMP. ANTI-CYCLE TIMER GR WITH ECONOMIZER OPTION 0140G00267 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 36 MINIMUM CLEARANCES 48" MIN 12" MIN 3" MIN . 12" MIN 36" MIN (FOR SERVICE) NOTE: Roof overhang should be no more than 36". UNIT Min. Filter Size 2 Ton 2 1/2 Ton 3 Ton 3 1/2 -/ 4 Ton 5 Ton (1)20 x 20 x 1 (1)20 x 25 x 1 (1)25 x 25 x1 (2)20 x 20 x 1 (2)20 x 25 x 1 RECOMMENDED FILTER SIZES 37 THIS PAGE LEFT BLANK INTENTIONALLY 38 THIS PAGE LEFT BLANK INTENTIONALLY 39 NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE Quality Makes the Difference! All of our systems are designed and manufactured with the same high quality standards regardless of size or efficiency. We have designed these units to significantly reduce the most frequent causes of product failure. They are simple to service and forgiving to operate. We use quality materials and components. Finally, every unit is run tested before it leaves the factory. That’s why we know. . .There’s No Better Quality. • • • Visit our website at www.goodmanmfg.com for information on: Products • Parts Warranties • Contractor Programs and Training Customer Services • Financing Options © 2005 - 2008 Goodman Manufacturing Company, L.P. 40
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes XMP Toolkit : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39 Modify Date : 2008:07:24 09:35:46-05:00 Create Date : 2008:07:23 14:52:50-05:00 Metadata Date : 2008:07:24 09:35:46-05:00 Format : application/pdf Title : untitled Producer : Acrobat Distiller 8.1.0 (Windows) Document ID : uuid:b729cb5a-fff1-4b99-9691-eeb5ed8b0dba Instance ID : uuid:915f257f-0cb8-4a70-9338-bdb159182ba7 Page Count : 40EXIF Metadata provided by EXIF.tools