Combination

FIRE SMOKE DAMPERS
Model FSD-M211

Application

Model FSD-M211 is a combination fire smoke damper with 3V style
blades. The FSD-M211 has been qualified to 10.2 m/s and 1 kPa for
operation and dynamic closure in emergency fire smoke situations.
Model FSD-M211 may be installed vertically (with blades running
horizontal) or horizontally and is rated for airflow and leakage in
either direction.
Model FSD-M211 has also been tested in accordance with BS476 to
4 hours at Warrington Fire, UK, and is approved for fire partitions of
4 hours or less where British Standards are required.

Ratings

UL 555 Fire Resistance Rating
	
Fire Rating:	
11⁄2 Hours
	
Dynamic Closure Rating: Actual ratings are size dependant
	
Maximum Velocity:	
10.2 m/s
	
Maximum Pressure:	
1 kPa
UL 555S Leakage Rating
	
Leakage Class:	
I
	
Operational Rating: Actual ratings are actuator dependant
	
Maximum Velocity:	
10.2 m/s
	
Maximum Pressure:	
1 kPa
	
Max. Temperature: 	
177°C —Depending on actuator

Steel 3V Blades
UL 555S Leakage Class I
UL555 11⁄2 Hour Fire Resistance Rating
4 Hour Fire Resistance Rating (BS476)
Model FSD-M211 meets the requirements for fire
dampers, smoke dampers and combination fire
smoke dampers established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
ICBO Uniform Building Codes
SBCCI Standard Building Codes
British Standard BS476
Tested to 4 hours at Warrington Fire, UK
“UL CLASSIFIED (see complete marking on
product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
	
Standard 555 & 555S (Listing #R13317)

BS476 Fire Resistance Rating
	
Fire Rating:	
4 hours
AIR

Standard Construction
	

Frame:		
	
	
	
	
	
	
Blades:	
		
		
Seals:	
	
		
		
	
Closure Device:	
	
Linkage:	
	
Axles:	
	
Bearings:	

Size Limitations

	
Minimum Size:	
	
Maximum Size:
	
Single Section: 	
		
	
Multiple Section:	
		
		

PERFORMANCE

127mm x 25mm galv. steel hat
channel with reinforced corners . A
low profile head and sill are used on
sizes less than 432mm high to
maximize free area and
performance.
1.5mm galvanized steel, reinforced
with 3 longitudinal structurally
designed vee’s.
Extruded silicone rubber blade
seals. Flexible stainless steel jamb
seals.
74°C RRL
Concealed in jamb.
13mm diameter plated steel
Bronze sleeve type.

AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC. ®

Greenheck Kunshan Co. Ltd. and Greenheck Fan
Corporation certifies that the model FSD-M211
shown herein is licensed to bear the AMCA Seal. The
ratings shown are based on tests and procedures
performed in accordance with AMCA Publication
511 and comply with the requirements of the AMCA
Certified Ratings Programs. The AMCA Certified
Ratings Seal applies to air performance ratings only.

W

101mm W x 101mm H
813mm W x 1270mm H
or 914mm W x 914mm H
3251mm W x 2540mm H Vertical
or 3658mm W x 2438mm H
Horizontal

RH

H

Optional Features

• Stainless steel bearings
• 100°C, and 177°C RRL available (UL only)
• 69°C fusible link (BS476)
• Electric or pneumatic actuators to accomplish smoke
management and system functions.
• Sleeve with Integral flange on both sides available
• RRL/OCI (open close indication)
• TOR (remote override of 74°C or 100°C closure allows damper to
perform smoke management functions during a fire emergency)

LH
*	W & H dimensions furnished approximately 6mm undersize.
	 (Add sleeve thickness for overall sleeved damper dimension)
	 Right hand drive is shown. Left hand drive is available upon request.

Installation instructions available at www.greenheck.com

Pressure Drop Data	

FSD-M211

This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All
data has been corrected to represent standard air at a density of 1.201 kg/m3.
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an
analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC
system.

AMCA Test Figures

Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations
because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.
Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than
Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.
Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high
entrance and exit losses due to the sudden changes of area in the system.

5D

6D

5D

D

4 (W) (H)
3.14

Figure 5.3

AMCA 5.2 Pressure Drop	

FSD-M211
5D

4 (W) (H)
3.14

D=
Figure 5.2

7&-0$*5:7413&4463&%301

13&4463&%3011"4$"-4







Y



NNYNN
NNYNN
NNYNN
NNYNN
NNYNN









Y









Y











Y



Figure 5. 5





Y















'"$&7&-0$*5:.&5&344&$0/%
".$"

305mm x 305mm

610mm x 610mm

Velocity
(m/s)

Pressure
Drop (Pa)

Velocity
(m/s)

2.5

10

5.1

35

7.7

914mm x 914mm

305mm x 1219mm

Pressure
Drop (Pa)

Velocity
(m/s)

2.6

3

5.1

10

42

7.6

Pressure
Drop (Pa)

Velocity
(m/s)

2.5

5

5.2

17

80

7.8

1219mm x 305mm

Pressure
Drop (Pa)

Velocity
(m/s)

Pressure
Drop (Pa)

2.5

3

2.5

8

5.1

15

5.1

27

22

7.6

32

7.7

57

10

135

10.3

72

10.2

42

10.3

57

10.3

105

12.6

207

12.9

115

12.7

65

12.9

90

12.9

164

15.5

311

15.4

162

15.3

95

15.3

125

15.6

242

17.8

411

18.1

224

17.7

127

18

174

17.9

316

20.8

561

20.8

296

20.3

167

20.5

227

20.7

424

R

Greenheck Kunshan Co. Ltd. and Greenheck Fan
Corporation certifies that the model FSD-M211 shown
herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed
in accordance with AMCA Publication 511 and comply
with the requirements of the AMCA Certified Ratings
Programs. The AMCA Certified Ratings Seal applies to
air performance ratings only.

AMCA 5.3 Pressure Drop	

FSD-M211

5D

6D

Figure 5.3

7&-0$*5:7413&4463&%301


5D

D=

4 (W) (H)
3.14







Y











Y






Y





13&4463&%3011"4$"-4

Figure 5.2

NNYNN
NNYNN
NNYNN
NNYNN
NNYNN





Y









Y







Figure 5. 5









'"$&7&-0$*5:.&5&344&$0/%
".$"
305mm x 305mm
Velocity
(m/s)

610mm x 610mm

Pressure
Drop (Pa)

Velocity
(m/s)

2.4

5

5.1

22

7.8

914mm x 914mm

305mm x 1219mm

Pressure
Drop (Pa)

Velocity
(m/s)

Pressure
Drop (Pa)

Velocity
(m/s)

2.5

3

2.5

3

5

10

5.1

8

52

7.7

22

7.6

10.3

92

10.3

40

12.9

145

12.8

62

15.4

209

15.5

17.7

274

17.9

20.8

379

20.8

167

R

1219mm x 305mm

Pressure
Drop (Pa)

Velocity
(m/s)

2.5

3

2.5

5

5.1

10

5.1

20

15

7.7

25

7.6

40

10.1

27

10.3

42

10.1

72

12.8

42

12.9

67

12.7

112

92

15.3

62

15.7

100

15.3

164

122

17.7

82

18.7

140

18

227

20.3

107

20.9

174

20.6

299

Greenheck Kunshan Co. Ltd. and Greenheck Fan
Corporation certifies that the model FSD-M211 shown
herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed
in accordance with AMCA Publication 511 and comply
with the requirements of the AMCA Certified Ratings
Programs. The AMCA Certified Ratings Seal applies to
air performance ratings only.

Pressure
Drop (Pa)

4 (W) (H)
3.14

D

AMCA 5.5 Pressure Drop	

FSD-M211

VELOCITY VS. PRESSURE DROP
1000

305mm x 305mm
610mm x 610mm
914mm x 914mm

5

0
91 30
4 5
x x
91 12
4 19

30

1219mm x 305mm

61

61

0

x

5

x

30
x

19
12

5

100

30

PRESSURE DROP- PASCALS

305mm x 1219mm

10

2

5

10

30

FACE VELOCITY- METERS/SECOND
AMCA 5.5
305mm x 305mm

610mm x 610mm

Velocity
(m/s)

Pressure
Drop (Pa)

Velocity
(m/s)

2.5

13

5

55

914mm x 914mm

Pressure
Drop (Pa)

Velocity
(m/s)

2.5

8

5

35

305mm x 1219mm

Pressure
Drop (Pa)

Velocity
(m/s)

2.5

8

5.1

30

1219mm x 305mm

Pressure
Drop (Pa)

Velocity
(m/s)

Pressure
Drop (Pa)

2.6

8

2.5

1

5.1

32

5

42

7.5

122

7.6

75

7.7

67

7.7

75

7.7

95

10.2

222

10.3

140

10.2

115

10.2

130

10.3

172

12.7

349

12.8

217

12.9

184

12.7

202

12.7

264

15.4

508

15.3

309

15.5

269

15.5

301

15.3

381

17.9

688

17.7

409

18.1

354

18.1

416

17.9

521

20.6

907

20.8

568

20.6

471

20.6

536

20.8

707

R

Greenheck Kunshan Co. Ltd. and Greenheck
Fan Corporation certifies that the model FSDM211 shown herein is licensed to bear the AMCA
Seal. The ratings shown are based on tests and
procedures performed in accordance with AMCA
Publication 511 and comply with the requirements
of the AMCA Certified Ratings Programs. The AMCA
Certified Ratings Seal applies to air performance
ratings only.

Damper Sizing Information
The following figures show maximum damper section size.

38mm ma

Single Section
W

95mm

152mm
.

H

Varies

127mm
.

A

137mm

A

*
305mm

127mm

Sleeve Length

Damper Sleeve Dimensional Data

The drawings below and corresponding table show the position of the FSD-M211 damper when mounted in a factory sleeve.
The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for installation
of retaining angles and duct connections.

38mm max.

The "A" dimension is the location of the damper mounted
in a factory sleeve. The table below shows the Standard,
Minimum, and Maximum “A” dimensions.

95mm

"A" Dimension

in. (mm)
152mm

LH

All Dampers*

Varies
137mm

When H is 11 in. (279mm) or
less with OCI, RRL, or TOR

RH
Right hand drive is shown
Left hand drive available upon request

A

127mm

Standard

Maximum

7 3/16 (183)

12 (305)

12 (305)

12 (305)

*With the exception of dampers 10 in. high (254mm) or less.
NOTE: Entire damper frame is not required to be installed within the
wall. The damper blades, when closed should be contained within
the wall.

Sleeve Length

Specifications
Combination Fire Smoke Dampers meeting the following specifications shall
be furnished and installed where shown on plans and/or as described in
schedules. Dampers shall meet the requirements of the latest edition of NFPA
80, 90A, 92A, 92B, 101, and 105.
T*

Dampers shall be tested , rated and labeled in accordance with the latest
S
edition of UL Standards 555 and 555S. Dampers shall have a UL 555 fire rating
of 11⁄2 hours. Each damper shall be equipped with a heat responsive device
which has been tested and approved for use with the damper assembly in
accordance with UL 555. The heat responsive device shall have a temperature
rating of (specifier select one of the following) 74°C, 100°C, or 177°C. Dampers
shall be UL labeled for use in dynamic systems. The damper shall have a
dynamic closure airflow rating equal to or greater than the airflow at the
damper’s installed location and a dynamic closure pressure rating of 1 kPa.
Dampers shall have a UL 555S Leakage rating of Class I and a Temperature
rating of 177°C. Dampers shall have a UL 555S operational airflow rating equal
to or greater than the airflow at its installed location and an operational pressure
rating of 996 Pa. Damper actuators shall be factory mounted and qualified for
use with the damper in accordance with UL 555S. Damper actuators shall
be (specifier select one of the following) electric type for 120 (24 or 230) volt
operation or pneumatic type for 25 psi minimum (30 psi maximum) operation.
Manufacturers submittal data shall indicate B*
actuator space requirements
around the damper.

All UL 555 and 555S Dynamic Closure Ratings, Operational Ratings and
Leakage Ratings shall be qualified for airflow and pressure in either direction
through the damper. UL ratings shall allow for mounting damper vertically (with
blades running horizontal) or horizontally.
The Damper Manufacturers submittal data shall certify all air performance
pressure drop data is licensed in accordance with the AMCA Certified Ratings
Program for Test Figures 5.2, 5.3 and 5.5. Damper air performance data shall
be developed in accordance with the latest edition of AMCA Standard 500-D.
Dampers shall be labeled with the AMCA Air Performance Seal.
Damper blades shall be 1.5mm galvanized steel 3V type with three longitudinal
grooves for reinforcement. Blades shall be completely symmetrical relative to
their axle pivot point, presenting identical resistance to airflow and operation in
either direction through the damper (blades that are non-symmetrical relative to
their axle pivot point or utilize blade stops larger than 13mm are unacceptable).
Damper frames shall be galvanized steel formed into a structural hat channel
shape with reinforced corners. Bearings shall be sintered bronze sleeve type
rotating in extruded holes in the damper frame. Jamb seals shall be stainless
steel compression type.
Basis of design is Greenheck Model FSD-M211.

GREENHECK
Greenheck Kunshan Co Ltd.
17 Qunyi Minying District • Kunshan Economic &
Technical Development Zone
Kunshan, Jiangsu, China 215300
Tel: 0512-573-66666 • Fax: 0512-573-78633
www.greenheck.com

Copyright © 2008 Greenheck Fan Corporation
FSD-M211 Rev. 6 January 2008



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : 3.1-702
Create Date                     : 2008:10:22 15:08:26-05:00
Metadata Date                   : 2008:10:23 07:36:41-05:00
Modify Date                     : 2008:10:23 07:36:41-05:00
Creator Tool                    : Adobe InDesign CS3 (5.0.2)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 12632 bytes, use -b option to extract)
Instance ID                     : uuid:916f3aa1-cbcc-4841-99a3-239694f18125
Document ID                     : adobe:docid:indd:ceb1e7dd-c9d7-11dc-bbb6-de73c397c805
Rendition Class                 : proof:pdf
Derived From Instance ID        : 93fa508e-a1de-11dc-bc5d-c1600478f0c8
Derived From Document ID        : adobe:docid:indd:8b155768-d84b-11d9-b474-c1fd45b03ec2
Manifest Link Form              : ReferenceStream, ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 72.00, 72.00, 72.00
Manifest Placed Y Resolution    : 72.00, 72.00, 72.00
Manifest Placed Resolution Unit : Inches, Inches, Inches
Manifest Reference Instance ID  : uuid:4a7b0a5a-381c-423d-b6d1-bc1e04be6e57, uuid:c72b7063-bf92-4a99-af8d-d900194c4c40, uuid:42ff821a-900d-457d-a42a-2da4dcc82216
Manifest Reference Document ID  : uuid:f2c0832d-66bf-406f-a711-bdbc67f9a7e2, uuid:ded0ca52-5f88-45f9-bff9-6ad59c0a6837, uuid:ab3b2803-5ffb-497e-8855-7bd5cf9adefb
Format                          : application/pdf
Producer                        : Adobe PDF Library 8.0
Trapped                         : False
Page Count                      : 6
Creator                         : Adobe InDesign CS3 (5.0.2)
EXIF Metadata provided by EXIF.tools

Navigation menu