Greenheck Fan Ductmate 35 Users Manual
35 to the manual da8cbf8e-d81b-487a-9fc9-7238d8065165
2015-02-09
: Greenheck-Fan Greenheck-Fan-Ductmate-35-Users-Manual-562541 greenheck-fan-ductmate-35-users-manual-562541 greenheck-fan pdf
Open the PDF directly: View PDF .
Page Count: 1
Application and Design
Ductmate® is used to connect a damper sleeve to
a rectangular duct when a tight duct connection is
required. The Ductmate connector gives a nearly
airtight cross connection without the use of slip joints,
and is an acceptable breakaway connection when
installed properly.
Particular attention should be given to the length of
the sleeve extending beyond the wall or floor. The
determining factor is dependent on whether or not
there is an actuator and/or access door. If there is
no actuator and/or factory mounted access door, the
maximum is 6 inches (152mm) extending beyond the
wall or floor. If there is an actuator or factory access
door on the side of the wall, the maximum is 16 inches
(406mm).
Versa-cleats are available in packages of 10, 25, or
50. See installation instructions for spacing of cleats
(468502 Quick Connect Breakaway Supplement).
Standard Construction
Flange: 20 ga. (1mm) galvanized
Corner Clips: Galvanized
Gasket: Extruded butyl for use between mating
flanges (not supplied by Greenheck)
Sleeve: Maximum thickness - 16 ga. (1.5mm)
galvanized steel
Mounting Options
One side: Actuator side (FSD/SMD series)
K side (DFD/FD series)
Both Sides: Actuator or K side attached/ Opposite side
unattached or both sides mechanically
fastened
Size Limitations
FSD/SMD series: Minimum damper size is 8 in. W x 6 in. H
(203mm x 152mm) Maximum width is
based on model limitations. Maximum
height is limited to 84 inches (2133mm).
FD/DFD series: Minimum damper size is 6in. W x 6 in. H
(152mm x 152mm) Maximum width and
height is based on model limitiations.
DUCTMATE® 35
Copyright © 2007 Greenheck Fan Corporation
Ductmate® 35 Rev. 4 May 2007
Screw Spacing Schedule (per Ductmate instructions)
Duct wall size
inches (mm)
0-4 in. wg
(0 - 1 kPa)
6 in. wg
(1.5 kPa)
0-24
(0 - 610)
1 screw each corner 1 screw each corner
25-48
(635 - 1219)
1 screw each corner
plus 1 @ center
1 screw each corner
plus 1 @ center
49 and over
(1245 and over)
1 screw each corner
plus 1 screw each
24 inches (610mm)
2 screws each
corner plus 1 screw
each 24 inches
(610mm)