General Safety Information
Only qualified personnel should install this unit.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards. Other
considerations may be required if seismic activity
is present. If more information is needed, contact a
licensed professional engineer before moving forward.
1. Follow all local electrical and safety codes, as well
as the National Electrical Code (NEC), the National
Fire Protection Agency (NFPA), where applicable.
Follow the Canadian Electric Code (CEC) in
Canada.
DANGER
Always disconnect power before working on or
near a unit. Lock and tag the disconnect switch or
breaker to prevent accidental power up.
CAUTION
When servicing the unit, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
Installation, Operation and Maintenance Manual
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.
®
Installation, Operation and Maintenance Manual
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.
®
Part #473380
Grease Grabber™ H2O
Auto-Cleaning Hood
1Model GGH20 Grease Grabber Auto-Cleaning Hood ®
Model GGH2O
2Model GGH2O ®
The unit should be stored at least 3½ in. (89 mm) off
the floor on wooden blocks covered with moisture
proof paper or polyethylene sheathing. Aisles between
parts and along all walls should be provided to permit
air circulation and space for inspection.
Inspection and Maintenance during Storage
While in storage, inspect once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated.
REMOVING FROM STORAGE — As units are removed
from storage to be installed in their final location,
they should be protected and maintained in a similar
fashion, until the equipment goes into operation.
Prior to installing the unit and system components,
inspect the unit assembly to make sure it is in working
order.
Receiving
Upon receiving the product check to make sure all
items are accounted for by referencing the bill of
lading to ensure all items were received. Inspect
each crate for shipping damage before accepting
delivery. Notify the carrier if any damage is noticed.
The carrier will make notification on the delivery
receipt acknowledging any damage to the product.
All damage should be noted on all the copies of the
bill of lading which is countersigned by the delivering
carrier. A Carrier Inspection Report should be filled out
by the carrier upon arrival and the Traffic Department.
If damaged upon arrival, file claim with carrier. Any
physical damage to the unit after acceptance is not
the responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative
to arrange for obtaining missing parts. Sometimes it
is not possible that all items for the unit be shipped
together due to availability of transportation and truck
space. Confirmation of shipment(s) must be limited to
only items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting
brackets provided or by the skid when a forklift is
used. Location of brackets varies by model and size.
Handle in such a manner as to keep from scratching
or chipping the coating. Damaged finish may reduce
ability of unit to resist corrosion.
Storage
Units are protected against damage during shipment.
If the unit cannot be installed and operated
immediately, precautions need to be taken to prevent
deterioration of the unit during storage. The user
assumes responsibility of the unit and accessories
while in storage. The manufacturer will not be
responsible for damage during storage. These
suggestions are provided solely as a convenience to
the user.
The ideal environment for the storage of units and
accessories is indoors, above grade, in a low humidity
atmosphere which is sealed to prevent the entry of
blowing dust, rain, or snow. Temperatures should
be evenly maintained between 30°F (-1°C) and
110°F (43°C) (wide temperature swings may cause
condensation and “sweating” of metal parts). All
accessories must be stored indoors in a clean, dry
atmosphere.
Remove any accumulations of dirt, water, ice, or snow
and wipe dry before moving to indoor storage. To
avoid “sweating” of metal parts allow cold parts to
reach room temperature. To dry parts and packages
use a portable electric heater to get rid of any
moisture build up. Leave coverings loose to permit air
circulation and to allow for periodic inspection.
3
Model GGH2O
®
Greenheck GGH2O hoods are designed for three
primary functions:
• Capture and contain the effluent produced by the
cooking process.
• Remove grease and other contaminants from the
airstream with two stages of mechanical filters
(Primary Grease X-Tractor filters and secondary
Grease Grabber filters).
• Wash the filters and other surfaces within the
exhaust plenum to remove contaminants.
NOTE
The wash sequence of the hood is not designed for
fire suppression and will not engage in the event of
a fire.
NOTE
The functions listed above require the control center
to be wired to the exhaust fan(s) and the hood
plumbed.
NOTE
For a complete list of functions, please refer to the
sequence of operations.
Normal Exhaust Operation and
Contaminant Collection
The system’s exhaust fan is manually controlled by
a press-button switch (FAN ON/OFF) on the graphic
keypad (included with hood). The exhaust system
operates until the FAN ON/OFF button is pressed. The
wash cycle can be manually engaged to run on a pre-
programmed control sequence by pressing the CLEAN
HOOD button or automatically engaged to run at the
same time each day through a programmable timer.
Grease Grabber™ H2O System
Function
Table of Contents
Grease Grabber™ H2O System Function .................... 3
Cleaning Cycle
Manual and Automatic Engagement ........................ 4
Fire Mode ...................................................................... 4
System Components
Hood .......................................................................... 5
Grease Grabber H2O Control Cabinet ...................... 5
Graphic Keypad ........................................................ 5
Unpacking ..................................................................... 6
Hood Widths and Base Weights .................................. 6
Installation Overview
Filler Panels ............................................................... 7
Back Supply Plenum ................................................. 7
Hood Hanging Height................................................ 8
Double Island Style ................................................... 8
Installing U-Channel Strip ...................................... 8
Continuous Capture Plenum ................................. 8
Ductwork ................................................................... 9
External Supply Plenums ..................................... 9-10
Supply Plenum Clip ............................................... 9
Uni-Strut ............................................................... 10
Threaded Rod ...................................................... 10
Supply Duct Collar .................................................. 10
UL Listed Fastener .................................................. 11
Back Supply Plenum .......................................... 11-12
Supply Duct Collar ............................................... 11
Hanging the Back Supply Plenum ................. 11-12
Hanging the Hood ................................................ 12
Air Diffusers ............................................................. 12
Enclosure Panels ..................................................... 13
End Skirts ................................................................ 13
Backsplash Panels .................................................. 14
Duct Collar ............................................................... 15
Plumbing
Pump Installation .................................................... 16
Connections ............................................................ 16
Detergent Tank ........................................................ 17
Electrical
Wiring ....................................................................... 17
Timer Programming – 24 Hour / 7 Day
Programming / Operation ....................................... 18
Initial System Start-Up ............................................... 19
Sequence of Operation .............................................. 20
Airflow Testing Procedure .......................................... 21
Wiring Schematic
Amerex® .................................................................. 22
Ansul® ..................................................................... 23
Wiring Diagram ........................................................ 24
Maintenance
Filters ....................................................................... 25
Floats ....................................................................... 25
Troubleshooting .......................................................... 26
Replacement Parts ..................................................... 26
Grease Grabber H2O Start-Up Checklist ................... 27
Maintenance Log ...........................................Backcover
Warranty .........................................................Backcover
4Model GGH2O ®
Fire Mode
In the event of a fire, the hood exhaust fan(s) will turn
on at full power and the supply fan will turn off (default
setting controlled by others) regardless of current fan
operation. If the hood is in a wash cycle, the hood will
drain and the fans will turn on.
NOTE
The wash sequence of the hood is not designed for
fire suppression and will not engage in the event of
a fire.
Cleaning Cycle
Manual Engagement
The wash function is triggered by pressing the Clean
Hood button after the exhaust fans are shut down at
the end of each day’s cooking operations (pressing
the Fans On/Off button).
Hot water and detergent will fill the hood reservoir.
The soapy water will then be cycled through the hood
by the attached recirculation pump, cleaning both the
filter banks and the exhaust plenum area on a timed
cycle.
When the cleaning cycle is complete, the water
is purged from the reservoir by the pump and the
reservoir will again fill with clean hot water.
A rinse cycle will then run on a timed cycle and the
water will again be purged by the pump.
When the cycle is complete, the controller runs the
exhaust fans briefly to remove steam and excess
moisture from the exhaust system.
Automatic Engagement
The hood is equipped with an automatic timer. The
timer will automatically initiate the wash sequence
at the programmed time each day. All other washing
functionality will be the same as the manual
engagement sequencing.
5
Model GGH2O
®
NOTE
If the GGH2O is being used with the Melink Intelli-
Hood system, there will be two keypads. The Melink
Keypad will control the fans and lights. The GGH2O
Keypad will control the wash system.
NOTE
For information on PLC programming, please
consult the factory.
NOTE
If the GGH2O is being used with the Vari-Flow Air
Management system, there will be an additional
FAN 100% button for sending fan speeds to 100%.
For detailed information on the Vari-Flow Air
Management system, please refer to the Greenheck
website, www.greenheck.com
Graphic Keypad
The graphic keypad is the interface between the
control functions of the GGH2O hood and the user.
This keypad is typically mounted on the Grease
Grabber H2O control cabinet, but can also be shipped
loose for remote mounting. The keypad consists
of three main buttons: hood lights, fan on/off and
clean hood. The keypad also has system fault and fill
detergent indicator lights to alert of any fault in the
system or when the detergent tank is low.
GGH2O Keypad
CLEAN
HOOD
472619
SYSTEM
FAULT
FILL
DETERGENT
After pressing “CLEAN HOOD”, Fans will automatically stop.
In case of emergency, the wash cycle can be stopped by pressing “CLEAN HOOD”.
HOOD
LIGHTS
FAN
ON/OFF
GGH2O and Vari-Flow Keypad
SYSTEM
FAULT
FILL
DETERGENT
After pressing “CLEAN HOOD”, Fans will automatically stop. 472620
In case of emergency, the wash cycle can be stopped by pressing “CLEAN HOOD”.
CLEAN
HOOD
HOOD
LIGHTS
FAN
ON/OFF
FAN
100%
SYSTEM
FAULT
FILL
DETERGENT
After pressing “CLEAN HOOD”, Fans will automatically stop.
In case of emergency, the wash cycle can be stopped by pressing “CLEAN HOOD”.
CLEAN
HOOD
GGH2O and Melink® Intelli-Hood® Keypad
SETUP
%
100%
Listed 33 x 7
LUCES VENTILADORES
FANS
LIGHTS
CLEAN
FAULT
RESET
HOOD
Melink Customer Service USA: 877-477-4190
System Components
Hood
The hood is shipped from the factory pre-piped and
ready to install. All wash components within the hood
are complete and ready for connection to hot water,
sanitary sewer drain and the electrical sources. Wiring
from the control panel to the hood (for lights) is by
Greenheck. All plumbing and wiring must conform to
plumbing and electrical codes. Duct collars are factory
mounted unless specified otherwise.
Grease Grabber H2O Control Cabinet
The control cabinet contains all of the water and
electrical components, and connections including
the Programmable Logic Controller (PLC), that
controls the wash sequencing and operations. The
control cabinet also includes the detergent reservoir,
detergent pump, recirculation pump, solenoid valves
and other water piping.
NOTE
The recirculation pump is shipped loose with the
hood. See pages 16 for installation details.
NOTE
Filters are shipped loose with the hood and installed
in the field. See page 25 for installation details.
6Model GGH2O ®
Unpacking
Hood Width and Base Weights
Hood Width Base Weight
without Water
Base Weight
with Water
inches
(cm)
lbs.
(kg)
lbs.
(kg)
48
(121.92)
440
(199.58)
488
(221.35)
51
(129.54)
449
(203.66)
497
(225.44)
54
(137.16)
457
(207.29)
505
(229.06)
57
(144.78)
465
(210.92)
513
(232.69)
60
(152.40)
474
(215.00)
522
(236.78)
63
(160.02)
483
(219.09)
531
(240.86)
66
(167.64)
491
(222.71)
539
(244.49)
69
(175.26)
499
(226.34)
547
(248.12)
72
(182.88)
508
(230.43)
556
(252.20)
DANGER
The maximum weight (weight with water) should be
used for the maximum weight of the hood to ensure
the ceiling structure can support the weight of the
hood when filled with water.
CAUTION
To ensure proper structural support, all hanger
brackets must be used for hanging the hood.
1
2
3
Front Lifting
Skid
Profile of Hood
Profile of Hood
Profile of Hood
Profile of Hood
Remove side, back and top lumber.
Remove 3-inch lag screws.
Holding the front lifting skid in
place and position the skid in
front of bottom skid.
Carefully rotate hood
as shown.
Carefully slide the hood
onto the lifting skid.
The lifting skid should be used to
life the hood into it’s final position.
If the lifting skid is not used, the
hood will be damaged during the
installation process.
1
2
3
Front Lifting
Skid
Profile of Hood
Profile of Hood
Profile of Hood
Profile of Hood
Remove side, back and top lumber.
Remove 3-inch lag screws.
Holding the front lifting skid in
place and position the skid in
front of bottom skid.
Carefully rotate hood
as shown.
Carefully slide the hood
onto the lifting skid.
The lifting skid should be used to
life the hood into it’s final position.
If the lifting skid is not used, the
hood will be damaged during the
installation process.
1
2
3
Front Lifting
Skid
Profile of Hood
Profile of Hood
Profile of Hood
Profile of Hood
Remove side, back and top lumber.
Remove 3-inch lag screws.
Holding the front lifting skid in
place and position the skid in
front of bottom skid.
Carefully rotate hood
as shown.
Carefully slide the hood
onto the lifting skid.
The lifting skid should be used to
life the hood into it’s final position.
If the lifting skid is not used, the
hood will be damaged during the
installation process.
Remove side, back
and top lumber.
Remove 3-inch
lag screws while
holding the front
lifting skid in place.
Base weight is based on 48 inches (121.92 cm) hood
length. For each additional foot of hood in length, add
55 lb/ft (24.95 kg/m) in weight of hood and 67lb/ft
(30.39 kg/m) in weight of hood filled with water.
Example of a 10 foot hood:
Dry: 48 inch width x 120 inch length
= 440 lbs. + (6 ft. x 55 lb/ft)
= 440 lbs. + 330 lbs.
= 770 lbs.
With Water: 48 inch width x 120 inch length
= 488 lbs. + (6 ft. x 67 lb/ft)
= 488 lbs. + 402 lbs.
= 890 lbs.
1
2
3
Front Lifting
Skid
Profile of Hood
Profile of Hood
Profile of Hood
Profile of Hood
Remove side, back and top lumber.
Remove 3-inch lag screws.
Holding the front lifting skid in
place and position the skid in
front of bottom skid.
Carefully rotate hood
as shown.
Carefully slide the hood
onto the lifting skid.
The lifting skid should be used to
life the hood into it’s final position.
If the lifting skid is not used, the
hood will be damaged during the
installation process.
When front lifting
skid is detached,
position it in front
of bottom skid.
Carefully slide the
hood onto the lifting
skid. The lifting skid
should be used to lift
the hood into its final
position. If the lifting
skid is not used,
the hood will be
damaged during the
installation process.
Carefully rotate
the hood as
shown.
7
Model GGH2O
®
Hood
Hood
Hood
Right Filler Panel
Bottom Filler Panel
Tack-welded to
hood back
5/16 inch x 3/4 inch bolts
with washers and nuts
Filler Panels
1. Unpack the hood and lay it on the lifting skid.
2. Bolt the filler panels together with 5/16 in. bolts
provided in the hardware package.
3. Position the filler panels to the hood back, and
tack-weld them into place.
4. To allow for ease of cleaning, caulk the external
seams with NSF Approved silicone caulk
(GESCS1000, or its equivalent). The caulk is not
provided. After the hood is secured, make the exhaust duct
connections. The fire system distributor must be
contacted at this time. After the fire system has been
installed, mount the enclosures, then the supply
plenums. If an Horizontal Supply Plenum is provided,
it should be installed before the enclosures. The hood
and accessories are now installed.
Finally, make the electrical connections from the
controls to the fans and complete the fire system
circuits as required by the job specification (job
specific wiring diagram located inside the cabinet
cover).
Installation Overview NOTE
If you have a Back Supply Plenum (BSP), this must
be installed before the hood. Refer to page 11 for
instructions on installing the BSP.
NOTE
All hanger brackets must be used and the hood
must be properly supported while lifting to prevent
damage or distortion to the hood. The hood must be
hung level to operate properly.
8Model GGH2O ®
NOTE
For multiple hood systems that have more than
14 lights total (incandescent or fluorescent), the
hood lights must be wired to multiple circuits.
Each circuit must have less than 14 lights total.
Light bulbs are not provided. Standard light bulbs
up to 100 watts may be used.
Double Island Style Hoods
A double island hood is created by installing two
wall style hoods back to back. Use the installation
procedure for single island hoods; install and level
both hoods. After leveling, secure the hoods together
by tack-welding and/or bolting the rear mounting
brackets. Caulk this joint with NSF Approved silicone
caulk (GE SCS1000 or its equivalent). The caulk is not
provided.
Hood
Bolt
Caulk
U-Clip
Acorn Nut
H
oo
d
F
ro
nt
H
oo
d
F
ro
nt
1. Remove support angle on open end panel.
2. Raise all hoods into appropriate location and support per construction plans.
3. Fasten top angles together using 1/4 in. bolts and nuts (by others).
4. Fasten hoods together using u-clips, 1/4 inch bolts and cap nuts as indicated.
5. Caulk all seams as necessary.
Hood
Bolt
Caulk
U-Clip
Acorn Nut
H
oo
d
F
ro
nt
H
oo
d
F
ro
nt
1. Remove support angle on open end panel.
2. Raise all hoods into appropriate location and support per construction plans.
3. Fasten top angles together using 1/4 in. bolts and nuts (by others).
4. Fasten hoods together using u-clips, 1/4 inch bolts and cap nuts as indicated.
5. Caulk all seams as necessary.
Continuous Capture Plenum Hoods
Remove the support angles on the open end panels.
Use the installation procedure described for single
island hoods; install and level both hoods. After
leveling, secure the hoods together by tack-welding
and/or bolting the top angles. Fasten the hoods
together using u-clips and bolts. Caulk this joint with
NSF Approved silicone caulk (GE SCS1000 or its
equivalent). The caulk is not provided.
NOTE
Before hanging the hoods, please verify the hood
marks to make sure the correct hood is hung on the
correct side.
Installing U-Channel Strip
1. After the hood is hung in position and leveled,
apply caulk to the inside edge of the double island
clip.
2. Position and install the clip by tapping into
position along clip (friction fit).
3. Caulk edges to seal out grease and allow for ease
of cleaning. Caulk with NSF Approved silicone
caulk, GE SCS1000, or its equivalent. The caulk is
not provided.
Hood Hanging Height
The hood hanging height is critical. Hanging the hood
at the incorrect height may significantly reduce the
ability for the hood to function properly and may be in
violation of codes. The hood hanging height (typically,
78 in. (198.12 cm) above the finished floor) is given on
the UL label located on the inside of the hood on the
end panel. The hood must be hung level to operate
properly.
NOTE
The installation of the canopy hoods shall be
in accordance with NFPA 96 (latest edition),
Standard for Ventilation Control & Fire Protection of
Commercial Cooking Operations.
NOTE
Greenheck does not recommend walking or
standing on the hood top as damage can result. If
you must walk on the hood top, protect the hood
with additional support or planks for flooring.
Ho
o
d
-
1
B
Ho
o
d
-
1A
Ho
o
d
Fro
n
t
Double Island Clip
DETAIL A
Double Island Clip
Silicone Caulk
Hood-1A
Hood-1B
Installation Instructions.
1. After hood is hung in position and leveled…
2. Apply silicone caulk to inside of double island clip.
3. Position and install clip by tapping into position along clip (friction fit).
4. Caulk edges to seal out grease and allow for ease of cleaning.
Ho
o
d
-
1
B
Ho
o
d
-
1A
Ho
o
d
Fro
n
t
Double Island Clip
9
Model GGH2O
®
NOTE
For hoods with fire dampers in the exhaust and
supply duct collars, an access panel for cleaning
and inspection shall be provided in the duct. This
panel shall be as close to the hood as possible but
should not exceed 18 in. (45.72 cm).
SUPPLY PLENUM SHELL
HOOD FRONT
HANGING CLIP
2.120
1.000 147.0°
57.4°
1.000
1.000
Form Down 147°
Form Up 57°
1.375
2.1251.000
3.000
0.563
0.563
0.750
0.750
4.500
.500 x .375
SLOT (3 PLACES)
0.625
1.500
0.625
Supply Plenum Clip
Installing External Supply Plenums
Using the Supply Plenum Clip - Option #1
1. Bolt the hanging clip to the supply plenum. Two
clips are needed for plenums less than 96 in.
(243.84 cm) long and three for plenums greater
than 96 in. (243.84 cm). The
third clip is located in the
center of the plenum length.
If there is a utility cabinet,
the hanging clip should be
23.5 in. (59.69 cm) from the
end to the hood.
2. Using the c-clamps provided, clamp the supply
plenum hanging clip to the hood standing seam.
Option: Drill and bolt a 1/4-20 SS bolt through the
clip and hood standing seam.
NOTE
The supply plenum is provided with plenum clips
that assist in hanging the plenum. The plenum
should not be hung only with the plenum clips;
threaded rod or uni-strut must also be used.
Ductwork
Exhaust
As specified in NFPA 96, Ch. 7.5 (latest edition),
exhaust duct systems must be constructed in the
following manner:
Materials: Ducts shall be constructed of and
supported by carbon steel not less than 1.37 mm
(0.054 in.) (No. 16 MSG) in thickness or stainless steel
not less than 1.09 mm (0.043 in.) (No. 18 MSG)
in thickness.
Installation: All seams, joints, penetrations, and duct
to hood collar connections shall have a liquid-tight
external weld. If you have an Automatic Fire Damper
please refer to that manual for installation instructions
now.
Supply
Supply ductwork (where applicable) should be
connected to the hood in a manner approved by the
local code authorities.
For proper installation of duct collars when they are
shipped unattached see Installing Duct Collars on
page10.
Hood
UTILITY
CABINET
TOP VIEW
HOOD
TOP VIEW
SUPPLY PLENUM
SUPPLY PLENUM SHELL
END VIEW
HOOD FRONT
Option #2
Uni-Strut supplied by others
Option #3
Threaded Rod
supplied by others
Threaded Rod
‘C’ Clamp Hood Standing Seam
Hanging Clip bolted to plenum shell
Hanging Clip
Option #2
The uni-strut (U channel) that holds the hood up,
cantilevers over the end of the hood and is
mounted to the Air Curtain Supply Plenum (ASP)
hanger brackets
Option #1
For plenums < than or = 96 inches
Two (2) clips are needed.
For plenums > than 96 inches
Three (3) clips are needed.
The third clip is located in the
center of the plenum length.
Option #1
Attach hanging clip to hood
standing seam with the
supplied ‘C’ clamps.
Optional: Drill and bolt a
1/4-20 SS bolt through the
clip and hood standing seam
Option #1
Hanging clip could be 23.5 inches from end if there is a utility cabinet on the
end of the hood.
Option #1 : Hanging Clip
Hanger Bracket
Note: Supply plenums are standardly supplied with hanging clips (Option #1).
If Option #1 is not applicable, use Options #2 or #3
Hanging methods for supply plenums
ASP: Air Curtain Supply Plenum
FSP: Face Supply Plenum
VSP: Variable Supply Plenum
Option #1: Hanging Clip
Option #2: Uni-Strut
Option #3: Threaded Rod
11.5
23.5
Hood
UTILITY
CABINET
TOP VIEW
HOOD
TOP VIEW
SUPPLY PLENUM
SUPPLY PLENUM SHELL
END VIEW
HOOD FRONT
Option #2
Uni-Strut supplied by others
Option #3
Threaded Rod
supplied by others
Threaded Rod
‘C’ Clamp Hood Standing Seam
Hanging Clip bolted to plenum shell
Hanging Clip
Option #2
The uni-strut (U channel) that holds the hood up,
cantilevers over the end of the hood and is
mounted to the Air Curtain Supply Plenum (ASP)
hanger brackets
Option #1
For plenums < than or = 96 inches
Two (2) clips are needed.
For plenums > than 96 inches
Three (3) clips are needed.
The third clip is located in the
center of the plenum length.
Option #1
Attach hanging clip to hood
standing seam with the
supplied ‘C’ clamps.
Optional: Drill and bolt a
1/4-20 SS bolt through the
clip and hood standing seam
Option #1
Hanging clip could be 23.5 inches from end if there is a utility cabinet on the
end of the hood.
Option #1 : Hanging Clip
Hanger Bracket
Note: Supply plenums are standardly supplied with hanging clips (Option #1).
If Option #1 is not applicable, use Options #2 or #3
Hanging methods for supply plenums
ASP: Air Curtain Supply Plenum
FSP: Face Supply Plenum
VSP: Variable Supply Plenum
Option #1: Hanging Clip
Option #2: Uni-Strut
Option #3: Threaded Rod
11.5
23.5
10 Model GGH2O ®
Using the Uni-Strut - Option #2
1. The uni-strut (supplied by others) that holds the
hood up cantilevers over the end of the hood and
is mounted to the supply plenum hanger brackets.
ATTACHED AIR CURTAIN CANOPY STYLE HOOD ATTACHED AIR CURTAIN CANOPY STYLE HOOD
BACKSUPPLY BACKSHELF HOODBACKSUPPLY CANOPY STYLE HOODBACKSUPPLY CANOPY STYLE HOOD
VARIABLE SUPPLY PLENUM CANOPY STYLE HOOD
Air Curtain Supply Plenum
(ASP)
ATTACHED AIR CURTAIN CANOPY STYLE HOOD ATTACHED AIR CURTAIN CANOPY STYLE HOOD
BACKSUPPLY BACKSHELF HOODBACKSUPPLY CANOPY STYLE HOODBACKSUPPLY CANOPY STYLE HOOD
VARIABLE SUPPLY PLENUM CANOPY STYLE HOOD
Variable Supply Plenum
(HSP or VSP)
Using the Threaded Rod - Option #3
1. Insert 1/2 in. (12.7 mm) diameter threaded rod (by
others) into hanger brackets on the supply plenum
top. Raise and hang the external supply plenum
from adequate roof or ceiling supports.
2. The external supply plenum should be resting
lightly against the hood. The hood is used to
position the plenum only, it is not intended to
support the plenum. All hanger brackets must be
used and the plenum must be properly supported
while lifting to prevent damage or distortion. The
supply plenum must be hung level to operate
properly.
(Optional fastening of supply plenum to hood. See
directions).
3. It is recommended that caulk be applied at the
mating seams and surfaces of the plenum, the
hood, and the wall. If the supply plenum is next
to a wall, you will also need to caulk around the
surface next to the wall. Caulk the joints with
NSF Approved silicone caulk (GE SCS1000, or its
equivalent). The caulk is not provided.
Installing the Supply Duct Collar to the
Plenum
1. Place the duct collar(s) over the opening, fastening
with tack-welds at 1 to 2 in. (2.54 to 5.08 cm)
intervals, or sheet metal screws at 3 to 6 in.
(7.62to 15.24 cm) intervals.
External Supply Plenum Weights, Dimensions and Supply Rates
External Supply
Plenum Type
Weight Width Height Length per
section Recommended
Supply Rate
(lbs/ft) (kg/ft) (in) (mm) (in) (mm) (ft) (m)
Back Supply 35.0 15.878 6 152.4 Variable Variable 3 to 16 .91 to
4.88
145 cfm/ft
(246.36 m3/hr)
Air Curtain Supply
• 14 inch 9.5 4.31 14 355.6 10 254 3 to 16 .91 to
4.88
110 cfm/ft
(186.89 m3/hr)
Air Curtain Supply
• 24 inch 12.5 5.67 24 609.6 10 254 3 to 16 .91 to
4.88
145 cfm/ft
(246.36 m3/hr)
Variable Supply 16.0 7.26 12 304.8 18 457.20 3 to 16 .91 to
4.88
curtain 0-80 cfm/ft
(0-135.92 m3/hr)
face 80-160 cfm/ft
(135.92 -271.84 m3/hr)
Horizontal Supply 14.0 6.35 12 304.8 18 457.20 3 to 16 .91 to
4.88
150 cfm/ft
(254.85 m3/hr)
Hood
UTILITY
CABINET
TOP VIEW
HOOD
TOP VIEW
SUPPLY PLENUM
SUPPLY PLENUM SHELL
END VIEW
HOOD FRONT
Option #2
Uni-Strut supplied by others
Option #3
Threaded Rod
supplied by others
Threaded Rod
‘C’ Clamp Hood Standing Seam
Hanging Clip bolted to plenum shell
Hanging Clip
Option #2
The uni-strut (U channel) that holds the hood up,
cantilevers over the end of the hood and is
mounted to the Air Curtain Supply Plenum (ASP)
hanger brackets
Option #1
For plenums < than or = 96 inches
Two (2) clips are needed.
For plenums > than 96 inches
Three (3) clips are needed.
The third clip is located in the
center of the plenum length.
Option #1
Attach hanging clip to hood
standing seam with the
supplied ‘C’ clamps.
Optional: Drill and bolt a
1/4-20 SS bolt through the
clip and hood standing seam
Option #1
Hanging clip could be 23.5 inches from end if there is a utility cabinet on the
end of the hood.
Option #1 : Hanging Clip
Hanger Bracket
Note: Supply plenums are standardly supplied with hanging clips (Option #1).
If Option #1 is not applicable, use Options #2 or #3
Hanging methods for supply plenums
ASP: Air Curtain Supply Plenum
FSP: Face Supply Plenum
VSP: Variable Supply Plenum
Option #1: Hanging Clip
Option #2: Uni-Strut
Option #3: Threaded Rod
11.5
23.5
Hanger Bracket
Exhaust Plenum
Duct cut out area
Duct cut out area
Hood Length
Hood
Width
Exhaust Duct
Connection
Exhaust duct connection is to be
a continuous liquid-tight weld to hood.
Supply Duct
Connection
Supply duct connection to be
tack-welded with 1 to 2 inch
tacks or sheet metal screws
at 3 to 6 inch spacing to hood.
Front of Hood
Exhaust Plenum
8.0 8.0
8.0
3.0
3.0
14.0
8.0
1.0
12.0
NOTE: 1. Exhaust duct connection to be located within 48 inches from center of hood length to center of duct connection.
2. UL Listed hood assembly to be used only with Greenheck Fan Corp. labelled subassembly for exhaust hood without exhaust damper part no. DC
TOP VIEW
BACK VIEW
Top of Hood
Dimensions are shown in inches.
11
Model GGH2O
®
Using the UL Listed Fastener Provided
1. Drill a 9/32 in. hole for the 1/4 in. bolt from the
inside of the supply plenum to inside the hood.
Fasteners are to be located max. 6 in. (15.24cm)
from the end of the hood with max. spacing
between bolts 36 in. (91.44 cm)
DO NOT iNcluDe uTiliTy cabiNeTs Or fillers wheN
figuriNg bOlT placemeNT.
DO NOT bOlT The supply pleNum TO a fire/uTiliTy
cabiNeT.
2. Push bolt through hole, attach the washer and nut.
3. Hand tighten; then use a wrench until fully
tightened. Caulk around bolts from inside of hood
as necessary.
Hole size 9/32-inch
Installation instructions for the AC3 fastener:
1) Create a 9/32 in. hole for ºî bolt.
2) Install bolt through hole.
3) Install appropriate washer (1/4 in.)
4) Install nut
7) Hand tighten, then use a wrench until tightened.
Hood
1/4 - 20 UNC - 2A
SS Bolt 1/4 inch SS Nut
SS Flat Washer
L (MODULE LENGTH)
L/2
L/2
L/2
L (MODULE LENGTH)
L/4
L/4
STEP 1
CENTERED ON WIDTH OF THE SUPPLY,
CUT (2) 4 in. X 24 in. OPENINGS AT
THE SUGGESTED LOCATIONS ABOVE
(IF MODULE > 6 ft.)
THE SUGGESTED LOCATION ABOVE
CUT (1) 4 in. X 24 in. OPENING AT
CENTERED ON WIDTH OF THE SUPPLY,
(IF MODULE < 6 ft.)
STEP 1
4 in. TO 6 in.
FASTEN WITH SCREWS, OR TACK WELDS EVERY
PLACE THE DUCT COLLAR OVER THE OPENING,
STEP 2
The 4 in. (10.16 cm)
high duct collar is to
be attached to the
back supply.
L (MODULE LENGTH)
L/2
L/2
L/2
L (MODULE LENGTH)
L/4
L/4
STEP 1
CENTERED ON WIDTH OF THE SUPPLY,
CUT (2) 4 in. X 24 in. OPENINGS AT
THE SUGGESTED LOCATIONS ABOVE
(IF MODULE > 6 ft.)
THE SUGGESTED LOCATION ABOVE
CUT (1) 4 in. X 24 in. OPENING AT
CENTERED ON WIDTH OF THE SUPPLY,
(IF MODULE < 6 ft.)
STEP 1
4 in. TO 6 in.
FASTEN WITH SCREWS, OR TACK WELDS EVERY
PLACE THE DUCT COLLAR OVER THE OPENING,
STEP 2
L (MODULE LENGTH)
L/2
L/2
L/2
L (MODULE LENGTH)
L/4
L/4
STEP 1
CENTERED ON WIDTH OF THE SUPPLY,
CUT (2) 4 in. X 24 in. OPENINGS AT
THE SUGGESTED LOCATIONS ABOVE
(IF MODULE > 6 ft.)
THE SUGGESTED LOCATION ABOVE
CUT (1) 4 in. X 24 in. OPENING AT
CENTERED ON WIDTH OF THE SUPPLY,
(IF MODULE < 6 ft.)
STEP 1
4 in. TO 6 in.
FASTEN WITH SCREWS, OR TACK WELDS EVERY
PLACE THE DUCT COLLAR OVER THE OPENING,
STEP 2
Installing the Back Supply Plenum
Installing the Supply Duct Collar
1. Find the center of the back supply plenum.
2. If the back supply plenum is less than 9 ft. 10 in.
(299.72 cm) long, cut opening at the suggested
location, centering the opening over the center of
the back supply plenum.
3. If the back supply plenum is greater than 9 ft.
10 in. (299.72 cm) long, divide the length of the
back supply by four. This will give you the center
of each half. Cut openings at the suggested
location, centering the duct collar over the center
measurement of each half.
4. Place the duct collar(s) over the opening, fastening
with screws or tack-welds every 4 to 6 in. (10.16 to
15.24 cm).
Hanging the Back Supply Plenum
5. Hang the back supply plenum from the ceiling.
The back supply plenum needs to be mounted
31.25 in. (79.375 cm) above the floor (based
upon a canopy hood that will be hung at 78in.
(198.12cm) above the finished floor. This is
measured from the lowest rear edge of the back
supply plenum to the finished floor. Leave 6 to
10inches (15.24 to 25.4 cm) of space below the
plenum for access to the air diffusers.
12 Model GGH2O ®
6. Fasten the back supply to the wall, going through
the lower back supply wall.
These fasteners are to help maintain the location
of the Back Supply, and are not intended to hold
the weight of the back supply unit.
The fasteners should not interfere with the
removable air diffusers.
The 31.25 in. (79.375 cm) height is based upon
the canopy hood hanging height of 78 in.
(198.12 cm)
STEP 3 Furnished by Others
0.500 in. Threaded &
0.500 in. Threaded Nuts
(Furnished by Others)
Hanger Bracket Detail
1) Hang Backsupply Modules from the
ceiling (the example shows the module
being supported with threaded rod)
The backsupply is to be 31.25 in. from the
floor. This is measured from the lowest
rear edge of the backsupply module to the
finished floor.
2) Fasten backsupply to wall through the
lower backsupply wall. These fasteners
are to help maintain location of the
backsupply, and are NOT intended to hold
any weight of the unit. Fasteners should
not interfere with the removable air diffuser.
31.25 in.
Critical
Dimension
Fasteners holding the
back supply to the wall
HANG THE HOOD
EYEBROW STYLE HOOD
CANOPY STYLE HOOD
INSTRUCTIONS, THE HOOD MAY BE FASTENED TO THE BACKSUPPLY.
SEAMS/SURFACES OF THE BACKSUPPLY, THE HOOD, AND THE WALL.
5. CONNECT REMAINING DUCTWORK FOR THE BACKSUPPLY AND THE
HOOD. CAULK IS RECOMMENDED TO BE APPLIED AT THE MATING
4. LIFT THE HOOD; POSITION IT SO THE TOP OF THE
HOOD IS LEVEL WITH THE TOP OF THE BACKSUPPLY; AFTER
THE HOOD IS HUNG FROM THE CEILING AS PER IT'S INSTALLATION
1. THE HOOD IS TO BE HUNG AS PER THE HOODS INSTALLATION
SHOULD BE CONNECTED BEFORE THE HOOD IS HUNG.
3. DUCTWORK FOR THE BACKSUPPLY; IF IT WILL NOT INTERFERE,
2. BEFORE THE HOOD IS HUNG THE BACKSUPPLY MUST BE SECURED
INSTRUCTIONS AND THE FOLLOWING.
PROPERLY, AS DESCRIBED IN "STEP 3 in.
STEP 4
5. Connect the remaining ductwork for the back
supply and the hood. It is recommended that
caulk be applied at the mating seams and
surfaces of the back supply, the hood, and the
wall.
Air Diffusers
The air diffusers, located at the bottom of the back
supply, will need to be cleaned as often as the
application dictates. Inspect periodically to determine
the cleaning schedule.
1. To clean the air diffusers, unfasten the screws.
Remove the air diffusers from the back supply
unit, and wash in the sink or dishwasher.
2. Insert the air diffusers at an angle from the bottom,
and rotate so the forms are downward. Rest the
diffuser on the internal angles.
3. Refasten with the stainless steel screws.
Canopy Style Hood
Removable Air Diffusers
Step 5 / Air Diffusers
a. Insert the air diffusers at an angle from the bottom.
b. Rotate the diffusers so teh forms are downward.
c. Rest the diffuser on the internal angles.
Proximity Style Hood
Hanging the Hood
Before hanging the hood according to the hood
installation instructions, please check the following:
1. Make sure the back supply plenum is properly
secured, as described in steps 5 and 6.
2. If the ductwork for the back supply plenum will not
interfere with the hood installation, it should be
connected now.
3. Any filler panels should be attached to the hood
before the hood installation.
4. Lift the hood, and position it so the filler panels
are resting lightly on the top outside edges of the
back supply. The back supply is used to position
the hood only. It is not intended to hold any hood
weight.
Canopy Style Hood
Removable Air Diffusers
Step 5 / Air Diffusers
a. Insert the air diffusers at an angle from the bottom.
b. Rotate the diffusers so teh forms are downward.
c. Rest the diffuser on the internal angles.
Proximity Style Hood
13
Model GGH2O
®
Installing Enclosure Panels
Before installing the enclosure panels, make sure
the hood is hung in position with all the ductwork
attached, electrical connections and fire system
connections completed.
1. Position the end enclosure panels on the hood,
and clamp into place with clamps provided or
tack-weld the panels into place.
2. Fasten the end enclosure panels to the wall,
method depends on wall construction. (Fasteners
are not provided).
If the hood is a double island, bolt the end
enclosure panels together. (Fasteners are not
provided).
3. Position the front enclosure panel(s) on the hood,
and bolt to the end enclosure panels with the
5/16in. bolts provided in the hardware package.
4. Tack-weld or clamp the front enclosure panel(s)
to the hood. If clamps are used, they must be
positioned 4 in. (100 mm) from the ends, and in the
center of the front enclosure panel.
5. To allow for ease of cleaning, caulk the external
seams with NSF Approved silicone caulk
(GESCS1000, or its equivalent). The caulk is not
provided.
Note: Installation instructions may not be applicable
for concrete ceilings.
Installing End Skirts
1. After the hood is hung in position, slide the
hemmed form on top of the end skirt onto the end
panels of the hood.
2. Drill a hole in the hood end panel to line up with
the hole in the end skirt. Attach the end skirt with
a 1/4 in. bolt and cap nut to the inside of the hood,
or tack-weld the end skirt to the hood.
3. Position the end skirt against the wall and attach.
The method depends on the wall construction.
(Fasteners for this are not provided).
4. Caulk the internal joint formed by the end skirt and
the hood end panel with NSF Approved silicone
caulk (GE SCS1000 or its equivalent). The caulk is
not provided.
5. To allow for ease in cleaning, also caulk all the
external seams.
End Enclosure
Panel
Front Enclosure Panel
End Enclosure
Panel
Attach to wall.
Fasteners by others
Clamp panels to hood standing seam with hardware.
Supplied by mfg.
Bolt panels together with 5/16-inch bolts.
Supplied by mfg.
HOO
D
T
O
P
H
OOD
BA
C
K
H
OOD FR
O
NT P
ANE
L
Attach to wall
Fasteners by others
Full End Skirt
Hemmed Edge
Exploded
view
below
Holes drilled by installer
1/4-inch bolt and cap nut
Supplied by mfg.
Exploded View
14 Model GGH2O ®
Installing Backsplash Panels
Flat backsplash panel
Material gauge – Stainless
Insulated backsplash panel
Material gauge – Stainless
Insulation – 1 inch (25.4 mm)
NOTE
Panels up to 47 inches (119.4 cm) wide ship in one
piece. Over 47 inches (119.4 cm) in multiple pieces.
NOTE
Panels up to 45 inches (114.3 cm) wide ship in one
piece. Over 45 inches (114.3 cm) in multiple pieces.
MATERIAL GAUGE — STAINLESS
MATERIAL GAUGE — STAINLESS
INSULATION — 1 IN. (25.4 MM)
FLAT BACKSPLASH PANEL
INSULATED BACKSPLASH PANEL
Wall
Wall
NOTE: PANELS UP TO 46 IN. (1168.4 MM) WIDE SHIP IN ONE PIECE; OVER 46 IN. (1168.4 MM) IN MULTIPLE PIECES.
NOTE: PANELS UP TO 48 IN. (1219.2 MM) WIDE SHIP IN ONE PIECE; OVER 48 IN. (1219.2 MM) IN MULTIPLE PIECES.
Length
1 inch (25.4 mm)
Heigth
Length
Height
MATERIAL GAUGE — STAINLESS
MATERIAL GAUGE — STAINLESS
INSULATION — 1 IN. (25.4 MM)
FLAT BACKSPLASH PANEL
INSULATED BACKSPLASH PANEL
Wall
Wall
NOTE: PANELS UP TO 46 IN. (1168.4 MM) WIDE SHIP IN ONE PIECE; OVER 46 IN. (1168.4 MM) IN MULTIPLE PIECES.
NOTE: PANELS UP TO 48 IN. (1219.2 MM) WIDE SHIP IN ONE PIECE; OVER 48 IN. (1219.2 MM) IN MULTIPLE PIECES.
Length
1 inch (25.4 mm)
Heigth
Length
Height
1. After the hood is hung in position, slide the flat
flange of the backsplash panel behind the back of
the hood.
Note: If the backsplash panel length is greater
than 45 in. (114.3 cm), it will be shipped in multiple
pieces.
2. After the backsplash panel has been positioned,
drill holes in the panel and fasten to the wall.
(Fasteners provided by others).
Note: The holes should be spaced to adequately
secure the panel to the wall.
3. Caulk the joints between the hood and the
backsplash panel with NSF Approved silicone
caulk (GE SCS1000, or its equivalent). The caulk is
not provided.
4. Caulk the joint between the backsplash panels
when multiple panels are required, with NSF
Approved silicone caulk (GE SCS1000, or its
equivalent). The caulk is not provided.
Hood End Panel Hood Front Panel
Backsplash Panel
Slide flange
behind back
of the hood.
Section view of
backsplash panel
overlap
Holes should be spaced
to adequately secure the
panel to the wall studs.
(Hole spacing and fasteners
provided by others).
15
Model GGH2O
®
1. The exhaust duct connection needs to be located
within 48 in. (121.92 cm) from the center of the
hood length to the center of the duct connection.
2. The exhaust duct connection is to be a continuous
liquid-tight weld. Weld with a non-ferrous filler
wire, such as silicon bronze or stainless steel filler
wire. Protect all stainless steel areas from weld
splatter.
Hanger Bracket
Exhaust Plenum
Duct cut out area
Duct cut out area
Hood Length
Hood
Width
Exhaust Duct
Connection
Exhaust duct connection is to be
a continuous liquid-tight weld to hood.
Supply Duct
Connection
Supply duct connection to be
tack-welded with 1 to 2 inch
tacks or sheet metal screws
at 3 to 6 inch spacing to hood.
Front of Hood
Exhaust Plenum
8.0 8.0
8.0
3.0
3.0
14.0
8.0
1.0
12.0
NOTE: 1. Exhaust duct connection to be located within 48 inches from center of hood length to center of duct connection.
2. UL Listed hood assembly to be used only with Greenheck Fan Corp. labelled subassembly for exhaust hood without exhaust damper part no. DC
TOP VIEW
BACK VIEW
Top of Hood
Dimensions are shown in inches.
Installing Duct Collar
Overview of exhaust and supply plenum locations
16 Model GGH2O ®
Plumbing
1. Connect the inlet and outlet piping on the
recirculation pump to the respective piping in the
cabinet via the threaded 1 in. unions.
2. Bring the inlet water piping to the connection
located on the top of the hood and connect to the
threaded connection on the 3/4 in. solenoid valve.
A ball valve needs to be placed in the connection
line before the 3/4 in. solenoid valve. Depending
on water pressure, the inlet valve might need to
be closed slightly to reduce water pressure. Water
temperature should be 140°F.
3. Bring the drain piping connection to the 1 in.
solenoid valve in the control cabinet and connect
to the threaded connection. This is a pressurized
drain system and needs a properly sized drain to
accommodate the pressurized drain water.
NOTE
As the suggested detergent is non-caustic and
biodegradable, waste water from the hood can be
drained in any typical grease trap.
A. One-inch unions
B. Detergent tank
C. Mounting plate
D. Isolators (qty of four)
E. Detergent pump
Position pump on
(4) isolators and attach
using provided nuts.
Field
connect
1-inch
unions
1-inch female NPT
Connect to drain
Connect to control
cabinet per
Wiring Diagram
in panel
Once the hood is hung, the recirculation pump and
detergent tank (both shipped loose) must be installed
in the controls cabinet.
Pump Installation
• Remove bolts from pump mounting plate in cabinet.
• Place the pump on the isolators located on the
mounting plate with the bolts removed.
• Secure the pump to the mounting plate with the four
previously removed bolts.
• Wire pump motor to the control cabinet per wiring
diagram on the cabinet.
• The wires to power the motor are already connected
to the pump motor. It only needs to be wired to the
control cabinet.
Plumbing Connections
A
A
B
C
D
E
Inlet Solenoid
Connection
17
Model GGH2O
®
Electrical
Electrical Wiring
All wiring must be done according to NEC (National
Electrical Code NFPA #70) and local building codes.
Two sources of power need to be brought into
the electrical control cabinet. A 120 volt, 30 amp
service with 12 gauge wire needs to be connected
to terminals L1 on the disconnect switch and N. A
120volt, 15 amp service with 14 gauge wire needs to
be brought into the electrical cabinet and connected
to terminal L2 on the disconnect switch and N1.
The main recirculating pump needs to be wired after it
is installed in the hood. There are three 12 gauge wires
in flexible conduit wired to the pump. Wiring to the
pump is complete from the factory. The whip from the
pump needs to be wired into the control cabinet.
NOTE
The wash control station will provide a dry contact
for a fan starter so the fans can be controlled by the
PLC. The fan starter is not provided with the wash
control station.
Detergent Requirements
The detergent brand Formula G-510 (by 2010
Products, Inc.) is recommended by Greenheck for use
in the wash system. Use Formula G-510 full strength.
This product is biodegradable, non-caustic, and safe
for kitchen staff to use. If G-510 detergent is not
used, the cleanliness of the exhaust plenum and filters
cannot be guaranteed.
Preventative Maintenance
The following practices will prolong the life of the
detergent pump:
• Keep detergent tank filled.
Avoid spilling detergent on the exterior of the
pump.
Clean the detergent tank at least every six
months.
Clean the detergent line strainer at least every six
months.
• Check tightness of all fittings periodically.
The detergent pump motor has sealed bearings which
do not require lubrication.
NOTE
G-510 is manufactured by 2010 Products, Inc., Food
Service Division, Salem, Oregon 97303. For details
and ordering information, call 800-286-2010.
Detergent Tank Installation
The detergent tank is located as shown in the photo.
When installing the detergent tank, the low detergent
indicator float and the detergent pump inlet tubing will
need to be lifted. Once the tank is in position, the low
detergent indicator float and detergent inlet tube must
be lowered into place inside the tank.
A. One-inch unions
B. Detergent tank
C. Mounting plate
D. Isolators (qty of four)
E. Detergent pump
18 Model GGH2O ®
Timer Programming –
24 Hour / 7 Day
Setting the Clock
1. Press and hold the CLOCK button.
2. Press and hold the DAY button until the display
shows the current day.
3. Press the HOUR button until the display shows the
current hour.
4. Press the MIN (minute) button until the display
shows the current minute.
Setting the Programs
1. Press the PROG (program) button once. You will
now set the time in which you want the wash to
start. The number 1 in the lower left hand corner
indicates that you are now programming Event 1.
2. Press the DAY button repeatedly until the display
shows the day(s) when you want the timer to turn
on. The options are:
- Days of the week
MO, TU, WE, TH, FR, SA, SU
- Individual days of the week
MO etc.
- Weekdays only
MO, TU, WE, TH, FR
- Weekends only
SA, SU
3. Press the HOUR and MIN (minute) buttons to set
the time when you want the timer to turn on.
4. Press the PROG (program) button again.
5. Repeat steps 2-4 to set the OFF time for Event 1.
This should be set one minute after the ON time.
6. When programming is complete, press the CLOCK
button to display the current time.
Things you should know about programming events:
You can repeat the ON and OFF programming
procedures outlined above for up to seven (7)
events as needed.
NOTE
While setting events, the timer may prematurely turn
on the load, if you press the MODE button.
Three kinds of settings can cause the timer to
work in an unexpected way:
a. Set up events in progressive order of time, for
example:
8:00 pm ON, 9:00 pm ON, 10:00 pm ON
Not 8:00 pm ON, 10:00 pm ON, 9:00 pm ON
b. Do not overlap event times, for example:
8:00 pm ON / 12:00 pm OFF and
9:00 pm ON / 11:00 pm OFF
c. Set the OFF time for one minute after the ON
time.
Reviewing Events Programmed
In your current time display, press the PROG (program)
button repeatedly to check your settings.
When finished, press the CLOCK button to return the
display to the time of day.
Clearing (Deleting an Event)
1. Press the PROG (program) button as many times
as necessary to locate the setting you want to
clear.
2. Press and hold the MODE button.
3. Press the PROG button to clear the setting.
4. When finished, press the CLOCK button to return
the display to the time of day.
Operating the Time Switch
Press the MODE button repeatedly to set the timer to
Automatic, Random or Manual mode.
NOTE
For the time switch to run programmed events, it
must be set to AUTO mode.
AUTO runs all events automatically according to the
schedule you have set. The word AUTO appears in
the display.
RND (random) runs all events in a RANDOM mode.
This is a security feature in which ON and OFF
times randomly differ +/- 15 minutes from the
programmed times, creating a more “lived-in” look.
The word RND appears on the display.
NOTE
Do NOT set this timer to RND mode. It will not wash
at the exact time you programmed.
MANUAL turns ON and OFF only when the user
presses the ON or OFF button. The display is blank,
showing neither RND or AUTO.
Overriding Timer Settings
The ON or OFF buttons override the current
programmed events. To override the current program
(either ON or OFF), press the ON or OFF button.
19
Model GGH2O
®
Initial System Start-Up
1. Check electrical power (see wiring diagram)
• Correct supply voltage
Proper connections to fire
suppression system
2. Check to make sure the
disconnect switch on the
electrical control cabinet is
switched to the “ON” position.
3. Prime the recirculation pump. Remove the plug on
top of pump and use a funnel to add water to the
pump. This only needs to be done one time prior to
initial start-up.
4. Add detergent to the detergent tank in the cabinet.
5. Clean the control cabinet of any debris that may
have entered the cabinet during installation.
6. Close the cabinet doors and press the Fan On/Off
button.
7. Check the exhaust and supply air volumes.
8. Press the Fan On/Off button to turn the fans off.
9. Press the Clean Hood button.
When the hood is filling, check to ensure water is not
leaking through the edges of the access doors. If so,
the inlet water pressure is too high. Slowly close ball
valve located before the inlet solenoid on the hood top
until no water leaks pasT the access doors.
After the hood fills with water and starts washing the
primary filters, open water valve slowly until water
mist is felt above equipment. Then slowly close valve
until water mist is no longer felt above equipment.
Once the valve is set it will not need to be moved
again.
Verify the Grease Grabber H2O sequence of operation
(see the diagram of wash sequence on page 20)
during the detergent pump cycle.
Daily Operation of the GGH2O Hood
Pressing the FAN ON/OFF button will start/stop the
exhaust and supply fans if interlocked.
Pressing the HOOD LIGHTS button will turn on/off the
hood lights.
Initiating the wash cycle:
The Grease Grabber H2O has an automatic timer
that can be set to control the wash schedule and
automatically start the cycle. See Timer Programming
on page 18.
To initiate the wash cycle manually, press the CLEAN
HOOD button on the keypad. If you press this button
while the fans are running, the system will stop the
fans and then start the wash cycle. When the wash is
completed, the system will automatically reset itself.
If the fans are controlled by a building management
system (BMS), the steps above still apply unless a
special program is requested to bypass having to
initiate the wash cycle by pushing the FAN ON/OFF
and CLEAN HOOD buttons.
Refer to the Grease Grabber™ H2O Hood checklist
on page 27 for detailed instructions on start-up
operations.
Interior of Cabinet
A. Recirculating pump
B. Detergent tank
C. Water valve to adjust front primary filter nozzles
D. Pump plug for priming
E. Detergent pump
AB
C
D
E
20 Model GGH2O ®
Temperature Interlock Exhaust Mode in Fire -- STOP Exhaust Mode in Fire -- RUN
No
Yes
Shut OFF exhaust fan(s)
Turn ON exhaust fan(s)
Turn OFF exhaust fan(s)
Stage 1:
Fill hood tank (hot water)
Stage 2:
Wash primary filters
Detergent pump ON
Stage 3:
Wash secondary filters
Detergent pump ON
Stage 5:
Wash secondary filters
Detergent pump OFF
Stage 6:
Drain soapy/dirty water
Stage 10:
Drain rinse water
Stage 4:
Wash primary filters
Detergent pump OFF
2 minute delay for
water settling
Spray for 5 minutes
Spray for 5 minutes
Fan(s) will run
Exhaust Fan(s)
will turn ON
START FAN Fan(s) OFF
Temperature
> 95°F.
(Adjustable)
NORMAL FAN OPERATION
SEQUENCE OF OPERATION - GREASE GRABBER H2O
FIRE
Exhaust
Fan(s) remain
ON
WASH
Yes
Fan(s) will run
START FAN
FIRE
Hot Water Recovery:
(0 min.) Adjustable
RINSE DRY
Exhaust
Fan(s) will
turn OFF
Spray for 5 minutes
Spray for 5 minutes
Stage 7:
Fill hood tank (hot water)
Stage 8:
Rinse primary filters
Detergent pump OFF
Stage 9:
Rinse secondary filters
Detergent pump OFF
Spray for 5 minutes
Spray for 5 minutes
20 minute dry time
Wash, rinse & dry complete
No
Temperature Interlock Exhaust Mode in Fire -- STOP Exhaust Mode in Fire -- RUN
No
Yes
Shut OFF exhaust fan(s)
Turn ON exhaust fan(s)
Turn OFF exhaust fan(s)
Stage 1:
Fill hood tank (hot water)
Stage 2:
Wash primary filters
Detergent pump ON
Stage 3:
Wash secondary filters
Detergent pump ON
Stage 5:
Wash secondary filters
Detergent pump OFF
Stage 6:
Drain soapy/dirty water
Stage 10:
Drain rinse water
Stage 4:
Wash primary filters
Detergent pump OFF
2 minute delay for
water settling
Spray for 5 minutes
Spray for 5 minutes
Fan(s) will run
Exhaust Fan(s)
will turn ON
START FAN Fan(s) OFF
Temperature
> 95°F.
(Adjustable)
NORMAL FAN OPERATION
SEQUENCE OF OPERATION - GREASE GRABBER H2O
FIRE
Exhaust
Fan(s) remain
ON
WASH
Yes
Fan(s) will run
START FAN
FIRE
Hot Water Recovery:
(0 min.) Adjustable
RINSE DRY
Exhaust
Fan(s) will
turn OFF
Spray for 5 minutes
Spray for 5 minutes
Stage 7:
Fill hood tank (hot water)
Stage 8:
Rinse primary filters
Detergent pump OFF
Stage 9:
Rinse secondary filters
Detergent pump OFF
Spray for 5 minutes
Spray for 5 minutes
20 minute dry time
Wash, rinse & dry complete
No
Sequence of Operation - Grease Grabber™ H2O
Normal Fan Operation
21
Model GGH2O
®
Airflow Testing Procedure
NOTE
The constants 4.846 and 2.47 are factory derived for
use with the Grease Grabber™ H2O.
Calculation Example:
Five (5) inlet slot velocity readings (minimum)
Average Velocity (FPM) =
(175 + 210 + 250 + 190 + 160) 5 = 197 FPM
Hood Exhaust Rate (CFM) =
[(96 x 4.846) x (197 x 2.47)] 144 = 1572 CFM
After the appropriate number of readings have been
taken from the inlet slot of the hood, an average
reading can be calculated by summing the velocity
readings and dividing the total value by the number of
readings taken.
Next calculate the total hood airflow volume (CFM) by
using the following equation:
Hood CFM = [(Length of Hood in inches x 4.846) x
(Average inlet slot velocity x 2.47)] 144
Average Velocity = Sum of Velocity Readings
Number of Readings
Hood Length 48 to 72
inches
72 to 120
inches
120 to 192
inches
Minimum Number
of Test Locations 357
For measuring exhaust airflow rates (cubic feet per
minute = CFM), use a short ridge meter to measure
velocities along the inlet slot of the hood. To ensure
accurate data, all appliances should be on. Multiple
locations need to be tested as outlined below to
ensure an accurate reading.
To take velocity readings along the length of the hood,
the edge of the short ridge meter must start/stop six
(6) inches from the end of the hood. Vertical placement
of the short ridge meter along the inlet is shown.
Hood Length 96 inches
Test Location
(off left; in inches) 6 27 48 69 90
Velocity Reading (fpm) 175 210 250 190 160
Short Ridge Meter Components
22 Model GGH2O ®
POWER SOURCE MANUAL RESET RELAY
MICROSWITCH
MICROSWITCH
ELECTRIC GAS VALVE
INSTALLER PROVIDED JUNCTION BOXES
PRM
BASIC WIRING DIAGRAM
RED (COMMON)
POWER SOURCE
MANUAL RESET RELAY
YELLOW (N.O)
BLACK (N.C.)
GAS VALVE
MICROSWITCH
BASIC WIRING DIAGRAM
RED (COMMON)
MANUAL RESET RELAY
YELLOW (N.O)
BLACK (N.C.)
GAS VALVE
SEE NOTE 3
NOTE: DO NOT USE YELLOW WIRE ON MICROSWITCH IN NORMAL
INSTALLATION. THE YELLOW WIRE IS TO BE USED ONLY FOR
EXTINGUISHER ALARM, LIGHTS, CIRCUITS, ETC.
L1
L2
PUSHBUTTON SWITCH
120V/60HZ
K1
Ka
K1b
CURRENT DRAW MAX:
8A RESISTIVE
8A INDUCTIVE
120VAC
NOTES:
1. DENOTES FIELD INSTALLATION
2. DENOTES FACTORY INSTALLATION
3. GAS VALVE: UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL OR LP GAS AS NEEDED OF
APPROPRIATE PRESSURE AND TEMPERATURE RATING, 110V/60HZ OR AMEREX GAS VALVES, PN 12870, 12871,
12872, 12873, 12874, 12875 and 12876.
4. K1a and K1b ARE N.0. WHEN K1 IS DE-ENERGIZED.
Amerex® Wiring Plan View
23
Model GGH2O
®
Ansul® Wiring Plan View
TEMPERATURE RATING, 110V/60HZ OR ANSUL GAS VALVES, PART NUMBERS 13707, 13708, 13709, 13710. AND 17643.
GAS VALVES: "UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL, OR LP GAS AS NEEDED OF APPROPRIATE PRESSURE AND
DO NOT USE BLACK WIRE ON SNAP-ACTION SWITCH IN NORMAL INSTALLATION. (USED ONLY FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC.
DENOTES FACTORY INSTALLATION
DENOTES FIELD INSTALLATION
TYPICAL WIRING SCHEMATIC ELECTRIC EQUIPMENT SHUTDOWN
4.
1.
2.
3.
AUTOMAN IN THE COCKED POSITION)
(SWITCH CONTACTS SHOWN WITH ANSUL
13 AMP, 28 VDC
1/3 HP, 10 AMP, 120 VAC
1/2 HP, 10 AMP, 240 VAC
MANUAL RESET RELAY
ANSUL SNAP-ACTION SWITCH
RESET
BA
RELAY COIL
ELECTRICAL RATING
PART NO. 426151
6
9
3
4
7
1
SCREW
INDICATOR
POWER
RED
GND
5
4
3
2
1
BLACK
RED
BROWN
110V/60HZ
NEUTRAL
HOT
1
L
2
L
NOTE:
ANSUL file name: Typicalwiringschematicelectricgasshut-offvalveshutdowndetail.ai / File received on August 4, 2010
(CUSTOMER SUPPLIED)
AND TEMPERATURE RATING, 110V/60HZ OR ANSUL GAS VALVES, PART NUMBERS 13707, 13708, 13709, 13710. AND 17643.
GAS VALVES: "UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL, OR LP GAS AS NEEDED OF APPROPRIATE PRESSURE
DO NOT USE BLACK WIRE ON SNAP-ACTION SWITCH IN NORMAL INSTALLATION. (USED ONLY FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC.
DENOTES FACTORY INSTALLATION
DENOTES FIELD INSTALLATION
TYPICAL WIRING SCHEMATIC ELECTRICAL EQUIPMENT SHUTDOWN
4.
1.
2.
3.
TO HEATING
ELEMENT LOAD
13 AMP, 28 VDC
1/3 HP, 10 AMP, 120 VAC
1/2 HP, 10 AMP, 240 VAC
MANUAL RESET RELAY
RESET
BA
RELAY COIL
ELECTRICAL RATING
PART NO. 426151
6
9
3
4
7
1
(CUSTOMER
SUPPLIED)
SWITCH OR
THERMOSTAT
CONTACTOR
SCREW
INDICATOR
POWER
RED
GND
5
4
3
2
1
BROWN
TO POWER SUPPLY
220V/440V
110V/60HZ
AUTOMAN IN THE COCKED POSITION)
(SWITCH CONTACTS SHOWN WITH ANSUL
ANSUL SNAP-ACTION SWITCH
BLACK
RED
NEUTRAL
HOT
1
L
2
L
NOTE:
ANSUL file name: Typicalwiringschematicelectricequipmentshutdowndetail.ai / File received on August 4, 2010
TEMPERATURE RATING, 110V/60HZ OR ANSUL GAS VALVES, PART NUMBERS 13707, 13708, 13709, 13710. AND 17643.
GAS VALVES: "UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL, OR LP GAS AS NEEDED OF APPROPRIATE PRESSURE AND
DO NOT USE BLACK WIRE ON SNAP-ACTION SWITCH IN NORMAL INSTALLATION. (USED ONLY FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC.
DENOTES FACTORY INSTALLATION
DENOTES FIELD INSTALLATION
TYPICAL WIRING SCHEMATIC ELECTRIC EQUIPMENT SHUTDOWN
4.
1.
2.
3.
AUTOMAN IN THE COCKED POSITION)
(SWITCH CONTACTS SHOWN WITH ANSUL
13 AMP, 28 VDC
1/3 HP, 10 AMP, 120 VAC
1/2 HP, 10 AMP, 240 VAC
MANUAL RESET RELAY
ANSUL SNAP-ACTION SWITCH
RESET
BA
RELAY COIL
ELECTRICAL RATING
PART NO. 426151
6
9
3
4
7
1
SCREW
INDICATOR
POWER
RED
GND
5
4
3
2
1
BLACK
RED
BROWN
110V/60HZ
NEUTRAL
HOT
1
L
2
L
NOTE:
ANSUL file name: Typicalwiringschematicelectricgasshut-offvalveshutdowndetail.ai / File received on August 4, 2010
(CUSTOMER SUPPLIED)
AND TEMPERATURE RATING, 110V/60HZ OR ANSUL GAS VALVES, PART NUMBERS 13707, 13708, 13709, 13710. AND 17643.
GAS VALVES: "UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL, OR LP GAS AS NEEDED OF APPROPRIATE PRESSURE
DO NOT USE BLACK WIRE ON SNAP-ACTION SWITCH IN NORMAL INSTALLATION. (USED ONLY FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC.
DENOTES FACTORY INSTALLATION
DENOTES FIELD INSTALLATION
TYPICAL WIRING SCHEMATIC ELECTRICAL EQUIPMENT SHUTDOWN
4.
1.
2.
3.
TO HEATING
ELEMENT LOAD
13 AMP, 28 VDC
1/3 HP, 10 AMP, 120 VAC
1/2 HP, 10 AMP, 240 VAC
MANUAL RESET RELAY
RESET
BA
RELAY COIL
ELECTRICAL RATING
PART NO. 426151
6
9
3
4
7
1
(CUSTOMER
SUPPLIED)
SWITCH OR
THERMOSTAT
CONTACTOR
SCREW
INDICATOR
POWER
RED
GND
5
4
3
2
1
BROWN
TO POWER SUPPLY
220V/440V
110V/60HZ
AUTOMAN IN THE COCKED POSITION)
(SWITCH CONTACTS SHOWN WITH ANSUL
ANSUL SNAP-ACTION SWITCH
BLACK
RED
NEUTRAL
HOT
1
L
2
L
NOTE:
ANSUL file name: Typicalwiringschematicelectricequipmentshutdowndetail.ai / File received on August 4, 2010
24 Model GGH2O ®
U1 (FX-14)
42 - DO1
21 - DI
COM
26 - DI4
41 - DO1 COM
24VAC
120VAC
S1 120 VAC
Fill
Fire System
Hood Lights
Hood Lights
N
TR1 (N)
(H)
(H)
FS FC
83 - 24V (H) 82 - 24V (C)
23 - DI2
Clean Hood PB3
24 - DI3
Start-Stop Fan PB2
45 - DO2
S2 120 VAC
Nozzle 1
48 - DO3
S3 120 VAC
Nozzle 2
52 - DO4
55 - DO5
S4 120 VAC
Drain
58 - DO6
C1 120 VAC
Recirc Pump
A2A1
62 - DO7
R1 24 VAC
Fan
A1A2
65 - DO8
R2 24 VAC
Detergent Pump
A1
A2
68 - DO9
44 - DO2
COM
47 - DO3 COM
51 - DO4 COM
54 - DO5 COM
57 - DO6 COM
61 - DO7
COM
64 - DO8 COM
67 - DO9 COM
25 - DI
COM
27 - DI5
Tank Full
FL1
28 - DI6
Tank Low
FL2
Det Low
FL4
R3 24 VAC
Det Low
A1
A2
Low Det Indicator
R4 24 VAC
Fire Mode
A1A2
R4
Fire Mode
R3
Det Low
AR 24 VAC
32
AR
L4
S1 N
S2
S3 N
M1
S4 N
SC F1
F2
F4 C
R1
Fan
Interlock
P2
Detergent
Pump
Motor
R2
N
RP
NO
21
24
21
P1
Recirculating
Pump
Motor
C1 120VAC
Recirculating
Pump
Contactor
14 11
BK
WHT
BK
WHT
32 - DI9
Clean Hood
Indicator
L3
6
Lights On/O
PB1
Fan Indicator
L2
L1
Lights Indicator
R5
3 - Ext V 1 - AI COM
R111
R3
N1
H1
DP
L1
L2
L3
R5 120 VAC
Hood Lights
LED Relay
72 - AO1
73 - AO COM
V1
VC
GGH20/VAV Fan Mode
Interlock Connection
0VDC - Fan Auto
5VDC - Fan OFF
10VDC - Fan On for Dry
+VDC
COM
M2
22 - DI1
C1
Overload
96
A1
A2
L2 L3
PR
BK
BK
BK
BK
BK
BL
BL
BL
BL
BK
BK
OR
OR
OR OR
OR
OR
OR
OR
OR
BL
BL
PR
BK
BL
WHT
WHT
WHT
WHT
WHT
WHT
RD
RD
RD
PR
RD
RD
RD
YW
YW
BL
BK
YW
YW
BR
YW
BL
YW
PR
BK
RD
12 GA
12 GA
12 GA
18 GA
18 GA 18 GA
18 GA
BK
BK
BK
BK
NWHT
BL
BL
PR
PR
PR
PR
PR
BR
PR
PR
PR
18 GA
YW
YW
YW
12 GA
18 GA
PR
PR
R6 120 VAC
Wash Timer
Relay
A1A2
T1 T2
Timer
Contact
BK RD
BK
NWHT
RD
R6
Wash Timer
11
PR PR
5
10 13
11
1
6
2
3
15 14
NWHT
36 - DI12
Safety
FL3
F3
PR
E2
14 GA
14 GA
E1
2 - AI1
4 - AI COM
TS
TC
OR
BR
81 - Earth
5 - AI2
6 - AI COM
I1
IC
OR
BR
Temp Sensor
(Freeze
Protection)
(If used)
Temp Sensor
(IMC Interlock)
(If used)
PR BK
12 GA
WHT
BK
RD
WHT
BK
RD
7 - AI3
6 - AI COM
Temp Sensor
(IMC Interlock)
(If used)
OR
BR
I2
IC
Recirculating Pump Size FLA
1.0 HP 17
1.5 HP 22
Brown
White
Blue
Orange
Yellow
RP
N
Recirculating Pump
Motor Wiring
Hood Lights
T3 T3T2 T2L1 T1 T1
14
1114
1114
24
24
14
C
95
WHT
WIRED FROM MOTOR
ON RECIRCULATING
PUMP
21
MOLEX PLUG FOR KEYPAD
(IF KEYPAD IS REMOTE MOUNTED, PLUG IS FIELD CONNECTED)
FIELD INSTALLED WIRING
Melink Fan Stop
Melink Fan
Stop Common
120VAC 1PH. 30 AMPS
SUPPLY POWER
WATER WASH
120VAC 1PH. 15AMPS
SUPPLY POWER
HOOD LIGHTS
FAN INTERLOCK
CONTACT
L1
L1
L1
41
41
41
41
41
41
41 T2 NN
N
N
83
83
83
83
83
83
83 14
82
82
82
82
82
82
LF3
DP
RP
LF1
F4
FS
60
20
30
67
67
67
67
67
51 52
N
N
N
N
N
95
58
62
65
68
25
27
28
36
72
73
2
4
5
6
42
45
48
55
83
1
1
21
21
21
21
22
26
32
23
24
E2E1
E1
H1
H1
L2
L1
N1
7
6
DISC
FU2
FU1
FU3
3POLE 32 AMPS
5 AMP
25 AMP
3 AMP
ECO
P.O.BOX 410 SCHOFIELD, WISCONSIN 54476-0410
CAD DRAWING NO. REV.
PART NO.
-
IAN31295
LADDER DIAGRAM,
GGH2O
473596
Wiring Diagram
Wiring diagram is located on the inside cover of the control cabinet located on the end of the hood.
25
Model GGH2O
®
Maintenance
Capture Tank
The interior surfaces of the hood capture tank should
be wiped down weekly.
Filters
The Grease Grabber filters (bead filters) require
visually inspection (not removed from hood) two
weeks after start-up, then once a month thereafter to
make certain the filters are positioned correctly in the
plenum. Positioned correctly means there are no gaps
between the filters.
To inspect the bead filters, remove the fasteners
holding the access doors; each door has five (5)
fasteners. Remove every other door to inspect the
filters.
After inspecting the filters, put the access doors
back on and put the fasteners back in. Be careful not
to over-tighten or cross thread the fasteners when
putting them back in.
The Grease Grabber filters
(bead filters) need to be
removed from the hood
once every three months to
visually inspect and ensure
the filters are structurally
sound.
Remove all the doors
and remove the filters for
inspection. Depending on
the equipment under the
hood, it will probably be
easier to remove the filters
from the right side of each
hood. Slide the other filters
down to the end access
door for removal.
After inspecting the filters,
place them back in the
hood. Be careful to install
the filters with the handles
up and make sure not to
hit the fire detection line
when removing or installing
the filters. Ensure no gaps
are between filters after
installation.
If any filter appears damaged, consult factory for
replacement.
Floats
The floats need to be
inspected two weeks after
start-up and then once a
month thereafter.
The float can be inspected
by first turning the
disconnect switch on the
control cabinet to the ‘OFF’
position. Then remove the
large access panel door.
Once the access panel
is removed, you will have
access to the floats.
Slide each float (Low Float,
High Float and Safety Float)
up the stem to its stop with
your finger and let go. If float
slides freely down the stem
with minimal resistance, the
float is operating as it should.
Put the access panel back
on and turn the disconnect
switch to the ‘ON’ position.
If the float does not slide
freely down the stem, the
stem and floats are dirty
and need to be wiped off with a clean cloth. Cleaning
the stem involves removing all the clips (stops). Slide
floats up and down on the shaft as required to access
and clean the entire length of the shaft. Return floats
to their location and reinstall stops.
Make sure all float stops are securely located in their
grooves and floats are located in their designated
spots.
If for some reason the floats
get taken off the stem, the
stamped circle on the top
side of the float needs to
face up.
Access Panel Door
Safety Float
High Float
Low Float
NOTE
Be careful when handling the float stops. These are
small clips and can easily be dropped. If you loose
one of these clips, consult factory for a replacement.
Float Installed
26 Model GGH2O ®
Troubleshooting Replacement Parts
Hood is not cleaning
If the hood does not seem to be adequately cleaned,
look for the following:
Detergent tank — is it empty or filled with wrong
detergent?
Detergent pump — is the detergent pump running?
Is there power to the pump? Is the detergent level
low? If the hood plenum area is not sufficiently
cleaning, consult factory for information on
increasing duration of wash cycle and detergent
pump.
Nozzles — are any of them clogged? If so, they can
be removed and cleared using a small wire.
Water temperature — is it at least 140°F.
Hardness of water — test water for hardness level.
It is recommended that soft water be used.
Hood not draining properly — plugged drain.
Ensure all floats have stamped circles facing up.
Water leaks — water leaking through the access
panels when filling. Ensure access panels are securely
in place. If leak persists, partially close inlet water ball
valve (by others) upstream of fill solenoid to reduce
water pressure.
Condensation in the hood — large amounts of
condensation while hood is washing. Hood should
be washed after the hood and equipment is warm,
not hot. The warm equipment helps reduce the
condensation that forms in the hood.
Approved wash detergent
Formula G-510 from 2010 Products, Inc.
Phone: 800-286-2010
(Not provided by Greenheck).
Greenheck
Part
Number
Grainger®
Part
Number
Wash Nozzles
Above GG Filters 472806
Below GG Filters 472795
Before First Stage Filters 472805
Repair Kits
Solenoid Model 1A579 K-1180
Solenoid Model 1A578 K-1172
When ordering parts, please be prepared to provide
us with your cabinet and hood system model
number, and serial number from labels on the hood
and cabinet. See the chart below to identify the
replacement parts needed.
27
Model GGH2O
®
o Wash Mode
• See sequence of operations on page 20.
If using 24 hour / 7 day timer, wash cycle will start
at scheduled time after “Fan On/Off” push button
has been pressed. (Refer to page 18 for details on
programming 24 hour / 7 day timer). If 24 hour / 7
day timer is not being used, press “Clean Hood”
push button after pressing “Fan On/Off” push
button.
Clean hood LED indicator should be lit.
_________ Record water pressure
(Should be between 30-50 psi)
_________ Record water temperature
(Should be between 140-160°F.)
o Stop Mode
At end of wash cycle, system returns to Fan On
for 20 minutes dry cycle.
System resets to stop mode.
Hood lights off. Deactivate “Hood Lights” push
button.
All lights on face of keypad(s) should be off.
o Fire Mode
Trip fire system microswitch or remove wire
from terminal FS or FC. (Water will not spray in
fire mode, fans will run. If wash cycle is running
during fire system trip, hood will drain and fan(s)
will run).
System fault LED indicator should be on.
Fan LED indicator should be lit.
o Low Detergent Mode
Fill detergent tank with appropriate detergent.
Low detergent LED indicator should go off.
Miscellaneous
o Hood Access
Panels should fit tightly to prevent water spraying
out.
When front nozzles are washing, adjust ball valve
in cabinet to reduce water pressure and minimize
overspray.
o Cleaning
Is the hood cleaning properly?
If not, refer to troubleshooting guide on page 26.
Grease Grabber™ H2O Start-Up
Checklist
Check boxes when item has been verified and gone
over with customer.
Hook-Up
o Electrical Connected
120V/1 30A to terminals L1 and N for wash
controls
120V/1 15A to terminals L2 and N1 for hood lights
Fans to terminals E1 and E2 (dry contact)
If using variable volume controls, Melink will also
require connection to terminals M1 and M2, Vari-
Flow will only require connection to terminals V1
and VC.
• Fire system microswitch to terminals FS and FC.
Recirculating pump wired to cabinet terminals
RP and N.
If keypad is shipped loose, connection completed
between keypad and cabinet with supplied cable.
If additional cable is required, consult factory for
ordering.
o Plumbing Connected
Two 1-inch unions to recirculating pump
connected.
Hot water supply line, 3/4-inch connection.
Pressurized drain connection, 1-inch connection.
Hot water supply ball valve open. Located up
stream of the inlet water solenoid valve.
o Detergent
Suction tubing and strainer to bottom of detergent
tank.
Low detergent sensor in bottom of detergent tank.
Detergent tank filled with proper detergent.
o Timer, 24 hours / 7 day
Programmed - see instructions on page 18.
Start-Up
o Cooking Mode
See sequence of operations on page 20.
Hood lights on. Activate “Hood Lights” push
button.
Hood light LED indicator should be lit.
Fans on. Hold “Fan On/Off” push button for one-
half second.
Fan LED indicator should be lit.
Appliances on (gas and/or electric).
o Stop Mode
See sequence of operations on page 20.
Fans off. Hold “Fan On/Off” push button for one-
half second.
LED indicator turns off.
28 473380 • Grease Grabber™ H2O Auto Cleaning Hood, Rev. 1, August 2010 Copyright 2010 © Greenheck Fan Corporation
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from
the shipment date. Any units or parts which prove defective during the warranty period will be replaced at our option
when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of
one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the
nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Greenheck catalog GGH2O provides additional information
describing the equipment, fan performance, available
accessories, and specification data.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
Warranty
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be
obtained from AMCA International, Inc. at www.amca.org.
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________