HONEYWELL Controls And HVAC Accessories Manual L0011084
User Manual: HONEYWELL HONEYWELL Controls and HVAC Accessories Manual HONEYWELL Controls and HVAC Accessories Owner's Manual, HONEYWELL Controls and HVAC Accessories installation guides
Open the PDF directly: View PDF .
Page Count: 12
Download | |
Open PDF In Browser | View PDF |
Honeywell hronotherm ® IV DeluxeProgrammable HeatPumpThermostats TRADELINE® APPLICATION The T8611G Chmnothern'_ IV Deluxe Programmable Heat Pump Thermostats provide electronic control of 24 Vac alngid*zone heat pump systems. Refer to Table 1 for a general description of the thermostats. All T8611 thermostats require a common wire to supply power, Table 1. Description of T8611 Thermostats. 13611 G Changeover System Selection Fan Selection Automatic Em Heat-Heat-Off'Cool Auto On-Auto RECYCLING NOTICE If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Contact your lOCal waste management for instructions regarding recycling disposal of the old thermostat, authority and the proper INSTALLATION When Installingthis Product... 1, Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. Installer must be a trained, experienced service technician. 4. After completing installation, use these instructions to check out the product operation. System and fan selections are done by keyboard. WallplateInstallation The thermostat can be mounted horizontally on the wall or on a 2 in. x 4 in. wiring box. Position wallptste hodzordally on the wail or on a 2 in, x 4 in. widng box. 1. Position and level the waitplate (for appearan¢_ only). The thermostat will func_on properly even when not level. 2. Use a ppnciJ to mark the mounting hoJes.See Fig. 2. 3. Remove the wallptata from the wall and ddfl two 3/16 inch holes in the wall (if drywall) as marked. For firmer material such as plaster, ddll two 7/32 inch holes. Gently tap anchors (provided) into the drilled holes until flush with the wall. 4. Position the wallplate over the holes, pulling wires through the wiring opening. 6. Loosely insert the mounting screws into the holes. 6. Tighten mounting screws. WIRING All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 for typlcst hookup. A letter code is located near each terminal for identification. Location CAUTION Install the thermostat about 5 II (t .Sin) above the floor in an area with good air circulation at average temperature, See Fig. 1, DO not install the thermostat where it can be affected by: -drafts, or dead sppts behind doors and in cornere. -hot or cold air from ducts. -radiant heat from sun or appliances, m concealed pipes and chimneys. -unheatad (unccoled) areas such as an outaide wall behind the thermostat. _u,s, Registered Trademark CopyrightO1997Honeywelllnc, Comments Disconnect power before wiring to prevent electrical shock or equipment damage. 1. Loosen the terminal screws connect the system wires, See on the wallplate and Fig. 4. MUMII • t_/ • AII Rights Reserved 69-0936-1 _ I_ _ONOTHERM mIV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS 1 1 1 ' (15 METERS] J / Fig. 1. l_/plcat location of thermostat. THE_ISTAT Fig. 3._plcat hookup of TSE11G in a heat pump system. Fig. 2. Mounting tim wallplate, IMPORTANT Use 18 gauge, color-coded thermostat cabl6 for proper wiring. 2. Securely tighten each terminal screw, 3. Push excess wire back into the hole. 4, Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat 69-0936_1 2 T8611G CHRONOTHERM _ IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS Using ThermostatKeys The thermostat keys are used to: set cu[rent day and time, program times and setpoints for heating and cooling, temporarily override program temperatures, display present setting, configure installer Setup, check System-Test, disptay outdoor temperature (select models), set the system operation, set the fan operation. See Fig, 6 for the location of the keys. :OR WRAPAROUND INSERTIONS/RIp NOTE: 5/16 IN (SMM) 7/16 IN (11 MM} M,4826 Always press the keys with your fingertip or similar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard. Fig. 4. Proper wiring technique. SETrlNGS MountingThermostat 1. Engoge tabs at tha top of tha thermostat and wallplate. See Fig. 5. 2. Press tower edge of case to cfose and latch. NOTE: System and Fen Settings The system defeult setting is Heat and the fan default setting is Auto. Use the System and Fan keys to change the settings, See Fig, 7. The fan settings can be set for each program period individually.The system selection is for all the program periods. To remove the thermostat from the wall, first pull out at the bottom of the thermostat; remove top last. A. ENGAGE TABS AT TOP OF THERMOSTAT System settings control the thermostat operation as follows: Em Heat: Emergency heat relay Is on conttnuousty. Thermostat cycles highest stage of heat. Cooling system is off. Compressor is de*energized. Heat: The thermostat controls the beating. Off: Both the heating and cooling are off. Cool:The thermostat controls the cooling. Auto:The thermostat automatically changes between heating and cooling operation, depending on the indoortomporature. AND WALL=LATE, B. PRESSLOWEREDGEOF CA,_ETOLATCH¸ Fan settings control the system fan as follows: On: Fan operates continuously. Auto: Fan operates with equipment. LED Indication Two LED indicators are located in the upper right of the thermostat.They indicate when a CHECK or FAIL signal is sent to the thermostat from the system. See Fig. 3. _ M1_3 TemperatureSettings Rg. 5. Mounting thermostat Refer toTable 2 for the pefauif program. If the daytime energy savings pedod is not used, press the period key (Leave or Refum) until the gme is blank. The fen setting feature is available on seleCt thermostat models. See Owners Guide, form number 69-0940, for complete instructions on changing the program. on weflplata, 3 69"0936--1 7"8611G CHRONOTHERIVP IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS SET WAKE TIMES SETllNQ OR SCROLL FORWARD THROUGH INSTALLER SETUp OPTIONS BACKWARD THROUGH INSTALLER SETUp OPTLC_N8 SETCURRENT DAy AND TIME _ RETURN TO NORMAL OPERATIONS ENTER INDEFINITE OR_MED TIMESAND OPERA.ON SET CURRENT OR SELECT SYSTEM OPERATION CHANGE BETWEEN DAYLIGHT _VINGS AND Sl HEATING AND COOLING DAy TO ANOTHER DA_ DECREASE_ME SL_fNG OR SCRCLLBACKWARD THRC4JGHINSTALLER SETUPANDSELF_EST Fig. 6.1"8611G key locations and descriptions. Table 2. Default Program Settings. )erlod Rg. 7,T8611G System and 69-0936--1 Cool Setpolnt Fan Setting Wake 6:00 AM 70°F (21°C) 78°F (25.5°C) Auto .eave 8:00 AM 62°F (1E.5°C) B5°F (29.5°C) Auto Return 6:00 PM 7O°F (21 °C) 78°F (28.5°C) Auto Sleep 10:00 PM 62°F (t6.5°C) B2°F (28°C) Auto NOTE: INO_CATORS 8. LEDs Heat Setpotnt INSTALLER SETUP Fan key locations. TWO LED Rg. Time For most applications, the thermostat factorysettings will not need to be changed. Review the factory settings in Table 2 and if no changes are necessary, go to the Installer System-Test section. The Installer Setup is used to customize the thermostat to specific systems. Some of the options include temperature display, changeover and outdoor temperature display. Installer Setup numbers are listed in Table 3. The table includes all the configuration options and the factory-settings for the T8611. location. 4 7"8611G CHRONOTHERM _ IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS A combination of key presses are required to use the Installer Setup feature. To entar the Installer Setup, press and beld the Information [] key with the increase • and decrease • keys until the first number is displayed. All display segments appear for approximately three seconds before the number is displayed. See Fig. 9 and 10. -To advance to the next Installer Setup, press the Time _ key. -To change a setting, use the increase • or decrease • key. -To scroll the Installer Setup numbers backwards, press the Time _7 key. -TO exit the Installer Setup, press Run Program. [ _StartTirne _Temporary t INSTALLER SETUpj NUMBER DISpLAy (COLUMN 2 OF TABLE 3) FACTORY SET13_Git I --,j OR OTHER CHOICE _ DISPLAY (COLUMN OR 5 OF TABLE 3) Fig. 10. Display of Installer Setup number and setting. SettingEn_JI Hold for AM i_ O Say =BBBB; E .. " w .-..w % ,"u°°;; WakeLeaveReturnSleep In Recovery Auto Repl Batt --System............... , DST ,-Fan ......... MonTueWedrhuFriSatSun Heat Cool• Outdoor Em Heat_OffCoot_Auto ', Wait • OQ_.: _)¢')OnAuto IMPORTANT On/yc_r,gurab_e numbe_areshownonthedev_. E_an_.' ti thermostatdoesnofhavea systamk_, /_ SetupNunfosr12wi/Inotbe dtsp!ayed RewewTable3 factoty-smtir_js andrnatkany d_ired changesin _e Aof_al_ttlr_ _umn, Whenlnstal_rSetupis comp_e, t_ew _e settingstocon_rm_at theymatch_e _atam. ulo_s Fig. 9. Display of all the segments of the LCD. Table 3. Thermoofat Inslaller Setup Options. Select got used -taating cycle Not used Installer Setup Number (Press Time ; Ll key to change) Other Choices (Press • or • key to change) Factory-Setting Display Descdptlon Display Description I thru 4 5 6 6 (Not used) -- 7 9 Stage 2 3,6or9 -- -- Emergency heat 3, 6 or 9 cph used for last stage of heat pump systems 9_9 cph used for electric heat 8thru 11 -- 12 1 Manual changeover Adaptive Intelligent ReCoveryTM control 13 0 Adaptive Intelligent ReCovery TM control is activated (system starts early so setpoint is reached by start of program period) 1 Conventional recovery (system starts recovery at programmed time) Degree temperature display 14 0 Temperature is displayed in °F 1 Temperature is displayed in °C N_used 15 Clock format 16 0 12-hour clock format 1 24-hour clock format 17and 18 .... t9 0 No extended fan operation after the call for heat ends 1 Fan operation Is extended 90 seconds after the call for heat ends. Extended fan operation in heating -- 3---3 cph Systemsetting adjustment Not used ActUal settln -0 or 2 O---Auto changeover 2--Fixed auto changeover .... (Continued) 5 69-0936---1 T8611G CHRONOTHERM _ IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS Table 3.Thermostat InstallerSetup Options(Continued). Select Extended fan operation in cooling Not used Outdoor temperature display models with OT terminals) Not used Instalts{ Setup Number (press Time key to change) Other Choices (Press • or • key to change) Display Description Factory-Setting Display Description 20 0 21 thru 23 .... 24 0 No extended fan operation after the call for cool ends 1 Fan operation is extended 90 seconds after the call for cool ends. NO outdoor temperature is displayed t Outdoor temperature is displayed. Needs a C7089Bt000 Outdoor Sensor to operate, t O/B terminal is energized for reversing valve in heating 4 thru 10 Heating and cooling setpoints can be set no closer than the chosen value: 4--4OF (2oc) 5--5OF (2.goc) 25 thru 28 .... O/B terminal energized in heating or cooling 29 0 O/B terminal is energized for reversing valve in cooling Deadpend 30 3 Heating end cooling setpoints can be set no closer than 3°F (1.5°C) _°F (3°C) 7--7OF (3.5_C) 8---8OF (4oC) 9_9°F (4,5oc) 10---10OF (5oC) Not used 31 and 32 Minimum off time for the compressor 33 5 5 minute minimum off time for the compressor 0 thru 4 Temperature range stops in heating 34 Temperature range stops in cooling 90 Highest setpoint heating can be set to 40 to 89 I Temperature range (1OF I increments) heating setpoint can be set to 35 45 Lowest setpeint cooling can he set to 46 to 99 Temperature range (1 °F increments) cooling setpoint can be set to Not used 36 .... 'Temperature display adjustment 37 69_936--1 O NO difference in displayed temperature and actual room temperature 6 -3 thru 3 Minimum number of minutes (O thru 5) the compressor will be oft between calJsfor the compressor 1--Display adjusts to 1°F higher than actual room temperature 2_Display adjusts to 2°F higher than actutu room temperature 3_Display adjusts to 3°F higher than actual room temperature -l--OispJay adjusts to I°F lower than actual room temperature -2--Display adjusts to 2°F lower thanactual room temperature -3_Display adjusts to 3°F lower than actual room temperature Actual Setting 7"8611G CHRONOTHERM e IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS INSTALLERSYSTEM-TEST IMPORTANT Review the settings to confirm that they match the system. Press Bun Program to exit the fostal/er Setup. The thermostat has saved the installer Setup changes and irlitiated a reset in order to operate using the new settings. Be sure to set the current day and time immediately Use the Instalter System-Test to check the thermostat operation. Refer to Table 4 for a list of the available system-tasts. To start the system-test: Setting Current Dayand Time CAUTION 1. Press Set Current Day/Time. NOTE_ The minimum off time for compressors Is bypassed during the Installer System-Test. Equipment damage can occur if the compressor is cycled too quickly. On initial power up or after an extended power loss, 1:00 pm flashes on the display until a key is pressed. Press and hold the increase • and decrease • keys at the same time until 10 appears. All segments of the display will be displayed before the 10 appears. See Fig. 11 and 12. m M1_12 Table 4.Tests Available InThe Installer System-Test. 2. Press Day until the current day is displayed. NOTE: Test Number Sun=Sunday, Mon=Monday, Tue=Tuesday, Wed=Wednesday, Thu=Thureday, Fd=Fdday, Sat=Saturday= T= _0g. M1_13 3. Press Time A or Time _7 until the current time i_ displayed• NOTE: 20-29 Emergency heat equipment can be turned on and off 30*39 Coofing equipment can be turned on and off 40-49 Fan equipment can be turned on and off. O to 19 70-79 Keyboard keys test Thermostat information including date code and software versions are displayed ] _StartTinte_TernporarySet_ng Holdfor I_ 15= T_ O Enrg I Sav I r_m_=llt I_ll _ gl=,l PM I_J l_ll|l_%Humid I MonTueWedThu FriSatSun • Heat COOl• Outdoor WakeLeaveReturnSleep In Recovery Auto Repl Batl --System ............... . DST .-Fan ......... ErnHeat_OffCool_Auto ; Wait O_•I _¢.)OnAuto MI0314 NOTE: Description Heating equipment can be turned on and off 60 60 Tapping the Set Current Day/Time wilt change the time in one hour increments. Systsm-Test 10-1 g If the current time is Daylight Savings Time, press Daylight Time until DST is displayed. MI_S Fig. 11. Display of all the segments of the LCD. 6=IS_ I£/ M1_15 4. Press Run Program. _,- 1-EST NUMBER MI C_TA Fig. 12. Display o1 test number. MI0316 7 69_936-_1 78611G CHRONOTHERM _ IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS Refer to Table 5 for the directions and results of the specific tests. NOTE: Press Time z_ to advance to the next test and Time V to go back to the previous test, Press Run Program to exff the system-tast. Table g. Installer Syatem-Test Options. Key Press to I Number Test I Description Heating Equipment Syatem-Teat Time L_ • 10 11 Enter heating equipment system-test. Stage-one heat comes on. The system fan is also energized, • • • 12 11 10 Stage-two heat comes on. Stage-one heat and system fan remain on. Stage-two heat turns off. Stage-one heat and system fan turn off, Emergency Heating Equipment System-Teat Time Z_ 20 Change from heating to emergency heating equipment system-test. • • 21 20 Emergency heat come on. Emergency heat turn off. Dooling Equipment Syatem-Teat Time _, 30 Change from heating or emergency .heating to cooling equipment cystem-test. • • 31 30 Cool and system fan come on. Cool and system fan turn off. Fan Equipment System-Teat Time A • 40 41 Change from cooling to fan equipment system-tast. Fan comes on. • 40 Fan turns off. Key Operation System-Teat TJme_. NOTE: II 60 2 _ Change from fan to key opera,on syst Eu3%_st. I Press any key and the disptaysd numbers will change. Press Time ? to go to the previous test and the Time _. to go to the next test. The Run Program Key wilt not exit this test, To exit, press Time _ or Time _7 and then the Run Program key. 3. Press the increase • key again to displey the software identification code. (Example: 02 = software tD code 2) THERMOSTAT INFORMATION 1. PresstheTime_ information. key to access the tbermostat ]D 4. Press the increase • key again to display the software revision number (Example: 001=Revision number t ). M4_4 2. Press the increase • key to display the production date code. The first two large digits are the month and the third digit is the last digit of the year (Example: 027=February 1997). 60-0936--1 5. Press the increase • key again to display the EEPROM ider_tificstioncode. (Example: 314 = EEPROM ID 314) T8611G CHRONOTHERM _ IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS 6. Press the.Run Program key to exit the system-test, The system-test times out after four minutes without any key presses. CHECKOUT OutdoorTemperatureSensor (select models) Allow the outdoor temperature sensor to soak in the outdoor air for a minimum of five minutes before taking a reading. TROUBLESHOOTING GUIDE Symptom Display will not come on, Pol_ltde Cause Thermostat is not being _owere¢l. Action Check for 24 Vac between R and C terminals. -- If missing 24 Vac: check if the circuit breaker is tripped---reset the circuit breaker, -check if the system fuse is blown--replace the fuse. -check if the power switch on the HVAC equipment is in the Off position--set to the On position, -check wiring between thermostat and HVAC equipment--replace any broken wires and tighten any loose connections. If 24 Vac is present, proceed wffh troubleshooting, -Temperature Room temperature display has display is incorrect. :een reconfigured. Enter Installer Setup number 37 and reconflgure the display. Fherrnosttu is configured for °F 3r °C display. Enter installer Setup number 14 and reconfigure the display. Bad thermostat location. Relocate the thermostat. Temperature settings will not change. (Example: Cannot set the rhe upper or lower temperature imits were reached, Check the temperature setpointa; Heating limits are 40 to 90°F (4.5 to 32°C) Cooling limits are 48 to 99°F (7 to 37°C) heating higher or the cooling lower.) The setpoint temperature range Check InStaller Setup numbers 34 and 35 and reconfigure the _tops were configured, setpoint stops. Heating will not come on. No power to the thermostat, Check for 24 Vac between R and C terminals. -- --_ If missing 24 Vac: -check if the circuit breaker is t ripped_reset the circuit breaker, check if the system fuse is blown--replace the fuse. -check if the power switch on the HVAC equipment is in the Off position_sst to the On position. check widng between thermostat and HVAC equipment--replace any broken wires and tighten any loose connections, If 24 Vac is present, proceed with troubleshooting, Thermostat minimum off time is Wait up to five minutes for the system to respond. activated. System selection is not set to Heat. Set system selection to Heat, Heating setpoint is below room temperature, Check heating setpoint. Set heating setpoJnt to desired temperature, (Contthued) 9 69-0936--1 7"8611G CHRONOTHERM s IV DELUXE PROGRAMMABLE Troubteshootlng " Symptom Cocting will not come OR. Possible Cause No power to the thermostat, HEAT PUMP THERMOSTATS (Continued). Action Check for 24 Vac between R and C. -If missing 24 Vac: -check if the circuit breaker is tripped--reset the circuit breaker, -check if the system fuse is blown--replace the fuse. -check if the power switch on the HVAC equipment is in the Off pesition_sst to the On position. -check wiring between thermostat and HVAC eduipment--replace any broken wires and tighten any loose connectk_ns. -If 24 Vac is present, proceed with troubleshooting. Thermostat minimum Offtime is • Wait up to five minutes for the system te respond. activated. • Enter Installer Setup number 33. Reconfigure minimum off time (if required). Heating or cooling come on momentarily and shut off System selection is not set to Cool, Set system selection to Cool, Cool setpct nt is above room temperature. Check cooling setpntnt, Set cooling setpoint to desired temperature. Heat or cool circuit is opening up or becoming high impedance_ Add resistor in parallel with load or install interface relay. System on indicator Hesting or cooling equipment is Verify operation of heating or cooIthg equipment In self-test, flame=heat, not operating. snowflake=cool) is displayed, but no warm or cool air is coming from the registers. Outdoor temperature not dispteyeda Option not activated, Enter Installer Setup number 24 and set to 1, Thermostat must have OT terminals and a C7089B1000 installed, Outdoor temperature Outdoor sensor is connscted incorrectly. Refer to C7089B1000 installation instructions and check wiring between the then'nostat and sensor, display is incorrecta Wrong sensor. Replace sensor with C7089B1000 sensor, Select models. 69-09_6_1 10 11 69"0936_1 Uon l Home and Building Control Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408_9524 69-0936--1 J.H Ray. 6-97 Home and Building Control Honeywell Limited-Honeywell Limit_e 155 Gordon Baker Road North York, Ontario M2H 3N7 PrlntBdinTaiwan[:LO.C. Helping You Control Your World _
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 12 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 12:00:39 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools