HONEYWELL Controls And HVAC Accessories Manual L0011084

User Manual: HONEYWELL HONEYWELL Controls and HVAC Accessories Manual HONEYWELL Controls and HVAC Accessories Owner's Manual, HONEYWELL Controls and HVAC Accessories installation guides

Open the PDF directly: View PDF PDF.
Page Count: 12

Honeywell
TRADELINE®
hronotherm ®IV
DeluxeProgrammable
HeatPumpThermostats
APPLICATION
The T8611G Chmnothern'_ IV Deluxe Programmable Heat Pump Thermostats provide electronic control of 24 Vac
alngid*zone heat pump systems. Refer to Table 1for a general description of the thermostats. All T8611 thermostats
require a common wire to supply power,
Table 1. Description of T8611 Thermostats.
13611 Changeover System Selection Fan Selection Comments
Auto System and fan selections are done by keyboard.
G Automatic Em Heat-Heat-Off'Cool -On-Auto
RECYCLING NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash.
Contact your lOCal waste management authority
for instructions regarding recycling and the proper
disposal of the old thermostat,
INSTALLATION
When Installingthis Product...
1, Read these instructionscarefully. Failure to follow
the instructions can damage the product or cause
a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check outthe product operation.
Location
Install the thermostat about 5 II (t .Sin) above the floor in
an area with good air circulation at average temperature,
See Fig. 1,
DO not install the thermostat where it can be affected by:
-- drafts, or dead sppts behind doors and incornere.
-- hot or cold air from ducts.
-- radiant heat from sun or appliances,
mconcealed pipes and chimneys.
-- unheatad (unccoled) areas such as an outaide wall
behind the thermostat.
WallplateInstallation
The thermostat can be mounted horizontally on the wall
or on a 2 in. x 4 in.wiring box. Position wallptste
hodzordally on the wail or on a 2 in, x 4 in. widng box.
1. Position and level the waitplate (for appearan¢_
only). The thermostat will func_on properly even
when not level.
2. Use a ppnciJ to mark the mounting hoJes.See
Fig. 2.
3. Remove the wallptata from the wall and ddfl two
3/16 inch holes inthe wall (if drywall) as marked.
For firmer material such as plaster, ddll two 7/32
inch holes. Gently tap anchors (provided) into the
drilled holes until flushwith the wall.
4. Position the wallplate over the holes, pulling wires
through the wiring opening.
6. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
WIRING
All wiring must comply with local electrical codes and
ordinances. Refer to Fig. 3 for typlcst hookup. A letter
code is located near each terminal for identification.
CAUTION
Disconnect power before wiring to prevent
electrical shock or equipment damage.
1. Loosen the terminal screws on the wallplate and
connect the system wires, See Fig. 4.
_u,s, Registered Trademark
CopyrightO1997Honeywelllnc, t_/ AII Rights Reserved
MUMII
69-0936-1
_I_ _ONOTHERM mIV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
1
' (15 METERS]
1
/
1
J
Fig. 1. l_/plcat location of thermostat.
THE_ISTAT
Fig. 2. Mounting tim wallplate,
IMPORTANT
Use 18 gauge, color-coded thermostat cabl6 for
proper wiring.
2. Securely tighten each terminal screw,
3. Push excess wire back into the hole.
4, Plug the hole with nonflammable insulation to
prevent drafts from affecting the thermostat
Fig. 3._plcat hookup of TSE11G
in a heat pump system.
69-0936_1 2
T8611G CHRONOTHERM _IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
:OR WRAPAROUND
INSERTIONS/RIp 5/16 IN (SMM)
7/16 IN (11 MM} M,4826
Fig. 4. Proper wiring technique.
MountingThermostat
1. Engoge tabs at tha top of tha thermostat and
wallplate. See Fig. 5.
2. Press tower edge of case to cfose and latch.
NOTE: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; remove
top last.
A. ENGAGE TABS AT TOP OF THERMOSTAT AND WALL=LATE,
B. PRESSLOWEREDGEOF CA,_ETOLATCH¸
_M1_3
Rg. 5. Mounting thermostat on weflplata,
UsingThermostatKeys
The thermostat keys are used to:
set cu[rent day and time,
program times and setpoints for heating and cooling,
temporarily override program temperatures,
display present setting,
configure installer Setup,
check System-Test,
disptay outdoor temperature (select models),
set the system operation,
set the fan operation.
See Fig, 6 for the location of the keys.
NOTE: Always press the keys with your fingertip or
similar blunt tool. Sharp instruments like a pen
or pencil point can damage the keyboard.
SETrlNGS
Systemand FenSettings
The system defeult setting is Heat and the fan default
setting is Auto. Use the System and Fan keys to change
the settings, See Fig, 7. The fan settings can be set for
each program period individually.The system selection is
for all the program periods.
System settings control the thermostat operation as
follows:
Em Heat: Emergency heat relay Is on conttnuousty.
Thermostat cycles highest stage of heat. Cooling
system is off.Compressor is de*energized.
Heat: The thermostat controls the beating.
Off: Both the heating and cooling are off.
Cool:The thermostat controls the cooling.
Auto:The thermostat automatically changes between
heating and cooling operation, depending on the
indoortomporature.
Fan settings control the system fan as follows:
On: Fan operates continuously.
Auto: Fan operates with equipment.
LED Indication
Two LED indicators are located in the upper right of the
thermostat.They indicate when a CHECK or FAIL signal
is sent to the thermostat from the system. See Fig. 3.
TemperatureSettings
Refer toTable 2 for the pefauif program. If the daytime
energy savings pedod is not used, press the period key
(Leave or Refum) until the gme is blank. The fen setting
feature is available on seleCt thermostat models. See
Owners Guide, form number 69-0940, for complete
instructionson changing the program.
3 69"0936--1
7"8611GCHRONOTHERIVP IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
SET WAKE TIMES
SETCURRENT
DAy AND TIME _
RETURN TO
NORMAL
OPERATIONS
ENTER
INDEFINITE
OR_MED
SETllNQ OR SCROLL
FORWARD THROUGH
INSTALLER SETUp OPTIONS
BACKWARD THROUGH
INSTALLER SETUp OPTLC_N8
TIMESAND
OPERA.ON
SET CURRENT OR
CHANGE BETWEEN
DAYLIGHT _VINGS
AND Sl HEATING AND COOLING
SELECT SYSTEM
OPERATION
DAy TO ANOTHER DA_ DECREASE_ME SL_fNG
OR SCRCLLBACKWARD
THRC4JGHINSTALLER
SETUPANDSELF_EST
Fig. 6.1"8611G key locations and descriptions.
Table 2. Default Program Settings.
Heat Cool Fan
)erlod Time Setpotnt Setpolnt Setting
Wake 6:00 AM 70°F 78°F Auto
(21°C) (25.5°C)
.eave 8:00 AM 62°F B5°F Auto
(1E.5°C) (29.5°C)
Return 6:00 PM 7O°F 78°F Auto
(21 °C) (28.5°C)
Sleep 10:00 PM 62°F B2°F Auto
(t6.5°C) (28°C)
Rg. 7,T8611G System and Fan key locations.
TWO LED
INO_CATORS
Rg. 8. LEDs location.
INSTALLER SETUP
NOTE: For most applications, the thermostat factory-
settings will not need to be changed. Review the
factory settings in Table 2 and if no changes are
necessary, go to the Installer System-Test
section.
The Installer Setup is used to customize the thermostat
to specific systems. Some of the options include
temperature display, changeover and outdoor
temperature display. Installer Setup numbers are listed in
Table 3. The table includes all the configuration options
and the factory-settings for the T8611.
69-0936--1 4
7"8611G CHRONOTHERM _IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
A combination of key presses are required to use the
Installer Setup feature.
To entar the Installer Setup, press and beld the
Information [] key with the increase and
decrease keys until the first number is displayed.
All display segments appear for approximately three
seconds before the number is displayed.
See Fig. 9 and 10.
-- To advance to the next Installer Setup, press the
Time _key.
-- To change a setting, use the increase or
decrease • key.
-- To scroll the Installer Setup numbers backwards,
press the Time _7 key.
-- TOexit the Installer Setup, press Run Program.
[_StartTirne _Temporary SettingEn_JI
Holdfor .AM i_ O Say
E." w .-..w %,"u°°;;
=BBBB;
MonTueWedrhuFriSatSun Heat Cool• Outdoor
WakeLeaveReturnSleep In Recovery Auto Repl Batt
--System............... ,DST ,-Fan .........
EmHeat_OffCoot_Auto ',Wait OQ_.: _)¢')OnAuto
ulo_s
Fig. 9. Display of all the segments of the LCD.
t
INSTALLER SETUpj FACTORY SET13_Git
NUMBER DISpLAy IOR OTHER CHOICE
--,j
(COLUMN 2 _ DISPLAY (COLUMN
OF TABLE 3) OR 5 OF TABLE 3)
Fig. 10. Display of Installer Setup
number and setting.
IMPORTANT
On/yc_r,gurab_enumbe_areshownonthedev_.
E_an_.' ti thermostatdoesnofhavea systamk_,
/_ SetupNunfosr12wi/Inotbe dtsp!ayed
RewewTable3 factoty-smtir_jsandrnatkany
d_ired changesin _e Aof_al_ttlr_ _umn,
Whenlnstal_rSetupis comp_e, t_ew _e
settingstocon_rm_at theymatch_e _atam.
Select
got used
-taating cycle
Not used
Systemsetting
adjustment
Adaptive
Intelligent
ReCoveryTM
control
Degree
temperature
display
N_used
Clock format
Not used
Extended fan
operation in
heating
Table 3. Thermoofat Inslaller Setup Options.
Installer
Setup
Number
(Press
Time
;Ll key to
change)
I thru 4
Factory-Setting
Display Descdptlon
Other Choices
(Press or key to change)
Display Description
56Stage 23,6or9
6(Not -- -- --
used)
7 9 Emergency heat 3, 6
or 9
8thru 11 -- -- --
3---3 cph
cph used for last stage of
heat pump systems
9_9 cph used for electric
heat
12
13
14
1 Manual changeover
0Adaptive Intelligent
ReCovery TM control is
activated (system
starts early so setpoint
is reached by start of
program period)
0Temperature is
displayed in°F
0or 2 O---Auto changeover
2--Fixed auto changeover
1 Conventional recovery (system
starts recovery at programmed
time)
1Temperature is displayed in °C
15 ....
16 0 12-hour clock format 1 24-hour clock format
17and 18 ....
t 9 0 No extended fan 1 Fan operation Is extended
operation after the 90 seconds after the call for
call for heat ends heat ends.
ActUal
settln
(Continued)
5 69-0936---1
T8611G CHRONOTHERM _IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
Table3.ThermostatInstallerSetup Options(Continued).
Instalts{
Setup
Number
(press
Time Other Choices
key to Factory-Setting (Press or key to change)
Select change) Display Description Display Description
Extended fan 20 0No extended fan 1 Fan operation is extended
operation in operation after the 90 seconds after the call for
cooling call for cool ends cool ends.
Not used 21 thru 23 ....
Outdoor 24 0 NO outdoor tOutdoor temperature is
temperature temperature is displayed. Needs a C7089Bt000
display displayed Outdoor Sensor to operate,
models with
OT terminals)
Not used 25 thru 28 ....
O/B terminal 29 0 O/B terminal is t O/B terminal is energized for
energized in energized for reversing valve in heating
heating or reversing valve in
cooling cooling
Deadpend 30 3 Heating end cooling 4 thru Heating and cooling setpoints
setpoints can be set 10 can be set no closer than the
no closer than 3°F chosen value:
(1.5°C) 4--4OF (2oc)
5--5OF (2.goc)
_°F (3°C)
7--7OF (3.5_C)
8---8OF (4oC)
9_9°F (4,5oc)
10---10OF (5oC)
Not used 31 and 32
Minimum off 33 5 5 minute minimum 0 thru Minimum number of minutes (O
time for the off time for the 4 thru 5) the compressor will be oft
compressor compressor between calJsfor the compressor
Temperature 34 90 Highest setpoint 40 to I Temperature range (1OF
range stops in heating can be set to 89 I increments) heating setpoint
heating can be set to
Temperature 35 45 Lowest setpeint 46 to Temperature range (1°F
range stops in cooling can he set to 99 increments) cooling setpoint
cooling can be set to
Not used 36 ....
'Temperature 37 O NO difference in -3 thru
display displayed temperature 3
adjustment and actual room
temperature
1--Display adjusts to 1°F higher
than actual room temperature
2_Display adjusts to 2°F higher
than actutu room temperature
3_Display adjusts to 3°F higher
than actual room temperature
-l--OispJay adjusts to I°F lower
than actual room temperature
-2--Display adjusts to 2°F lower
thanactual room temperature
-3_Display adjusts to 3°F lower
than actual room temperature
Actual
Setting
69_936--1 6
7"8611GCHRONOTHERM eIV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
IMPORTANT
Review the settings to confirm that they match
the system. Press Bun Program to exit the
fostal/er Setup. The thermostat has saved the
installer Setup changes and irlitiated a reset in
order to operate using the new settings. Be sure
to set the current day and time immediately
Setting Current Dayand Time
1. Press Set Current Day/Time.
NOTE_ On initial power up or after an extended
power loss, 1:00 pm flashes on the
display until a key is pressed.
m
M1_12
2. Press Day until the current day is displayed.
NOTE: Sun=Sunday, Mon=Monday,
Tue=Tuesday, Wed=Wednesday,
Thu=Thureday, Fd=Fdday, Sat=Saturday=
_0g.
T=
M1_13
3. Press Time Aor Time _7 until the current time i_
displayed•
NOTE: Tapping the Set Current Day/Time wilt
change the time in one hour increments.
I_ 15=
T_
MI0314
NOTE: If the current time is Daylight Savings
Time, press Daylight Time until DST is
displayed.
6=IS_
M1_15
4. Press Run Program.
MI0316
INSTALLERSYSTEM-TEST
Use the Instalter System-Test to check the thermostat
operation. Refer to Table 4 for alist of the available
system-tasts.
To start the system-test:
CAUTION
The minimum off time for compressors Is
bypassed during the Installer System-Test.
Equipment damage can occur if the compressor
is cycled too quickly.
Press and hold the increase and decrease • keys at
the same time until 10 appears. All segments of the
display will be displayed before the 10 appears. See
Fig. 11 and 12.
Table 4.Tests Available InThe Installer System-Test.
Test
Number Systsm-Test Description
10-1 g Heating equipment can be turned on
and off
20-29 Emergency heat equipment can be turned
on and off
30*39 Coofing equipment can be turned on
and off
40-49 Fan equipment can be turned on and off.
60 Oto Keyboard keys test
60 19
70-79 Thermostat information including date
code and software versions are displayed
]_StartTinte_TernporarySet_ng Enrg I
Holdfor O Sav
I r_m_=lltI_ll _gl=,l PM I_J l_ll|l_%Humid I
MonTueWedThuFriSatSun Heat COOl• Outdoor
WakeLeaveReturnSleep In Recovery Auto Repl Batl
ErnHeat_OffCool_Auto ; Wait O_•I _¢.)OnAuto
--System ............... .DST .-Fan .........
MI_S
Fig. 11. Display of all the segments of the LCD.
I£/
_,- 1-EST NUMBER MI C_TA
Fig. 12. Display o1 test number.
769_936-_1
78611G CHRONOTHERM _IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
Refer to Table 5 for the directions and results of the NOTE: Press Time z_ to advance to the next test and
specific tests. Time Vto go back to the previous test, Press
Run Program to exff the system-tast.
Table g. Installer Syatem-Test Options.
Key to I Test IPress Number Description
Heating Equipment Syatem-Teat
Time L_ 10 Enter heating equipment system-test.
11 Stage-one heat comes on. The system fan is also energized,
12 Stage-two heat comes on. Stage-one heat and system fan remain on.
11 Stage-two heat turns off.
10 Stage-one heat and system fan turn off,
Emergency Heating Equipment System-Teat
Time Z_ 20 Change from heating to emergency heating equipment system-test.
21 Emergency heat come on.
20 Emergency heat turn off.
Dooling Equipment Syatem-Teat
Time _, 30 Change from heating or emergency .heating to cooling equipment cystem-test.
31 Cool and system fan come on.
30 Cool and system fan turn off.
Fan Equipment System-Teat
Time A 40 Change from cooling to fan equipment system-tast.
41 Fan comes on.
40 Fan turns off.
Key Operation System-Teat
TJme_. I60 2 _Change from fan to key opera,on syst Eu3%_st.
I I
NOTE: Press any key and the disptaysd numbers will
change. Press Time ? to go to the previous test
and the Time _. to go to the next test. The Run
Program Key wilt not exit this test, To exit, press
Time _ or Time _7 and then the Run Program
key.
THERMOSTATINFORMATION
1. PresstheTime_ key to access the tbermostat
information.
]D
M4_4
2. Press the increase key to display the production
date code. The first two large digits are the month
and the third digit is the last digit of the year
(Example: 027=February 1997).
3. Press the increase key again to displey the
software identification code. (Example: 02 =
software tD code 2)
4. Press the increase key again to display the
software revision number (Example: 001=Revision
number t ).
5. Press the increase • key again to display the
EEPROM ider_tificstioncode. (Example: 314 =
EEPROM ID 314)
60-0936--1
T8611G CHRONOTHERM _IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
6. Press the.Run Program key to exitthe system-test,
The system-test times out after four minutes
without any key presses.
CHECKOUT
OutdoorTemperatureSensor
(select models)
Allow the outdoor temperature sensor to soak in the
outdoor air for a minimum of five minutes before
taking a reading.
TROUBLESHOOTINGGUIDE
Symptom
Display will not
come on,
Pol_ltde Cause
Thermostat is not being
_owere¢l.
Heating will not
come on.
Action
Check for 24 Vac between Rand C terminals.
-- If missing 24 Vac:
check if the circuit breaker is tripped---reset the
circuit breaker,
-- check if the system fuse is blown--replace the
fuse.
-- check if the power switch on the HVAC equipment
is in the Off position--set to the On position,
-- check wiring between thermostat and HVAC
equipment--replace any broken wires and tighten
any loose connections.
-- If 24 Vac is present, proceed wffh troubleshooting,
Enter Installer Setup number 37 and reconflgure the display.Temperature Room temperature display has
display is incorrect. :een reconfigured.
Fherrnosttu is configured for °F Enter installer Setup number 14 and reconfigure the display.
3r °C display.
Bad thermostat location. Relocate the thermostat.
Temperature rhe upper or lower temperature Check the temperature setpointa;
settings will not imits were reached, Heating limits are 40 to 90°F (4.5 to 32°C)
change. (Example: Cooling limits are 48 to 99°F (7 to 37°C)
Cannot set the
heating higher or The setpoint temperature range
the cooling lower.) _tops were configured,
No power to the thermostat,
Check InStaller Setup numbers 34 and 35 and reconfigure the
setpoint stops.
Check for 24 Vac between R and C terminals.
-- If missing 24 Vac:
-- check if the circuit breaker is t ripped_reset the
circuit breaker,
check if the system fuse is blown--replace the
fuse.
-- check if the power switch on the HVAC equipment
is inthe Off position_sst to the On position.
check widng between thermostat and HVAC
equipment--replace any broken wires and tighten
any loose connections,
--_ If 24 Vac is present, proceed with troubleshooting,
Thermostat minimum off time is Wait up to five minutes for the system to respond.
activated.
System selection is not set to Set system selection to Heat,
Heat.
Heating setpoint is below room Check heating setpoint. Set heating setpoJnt to desired
temperature, temperature,
(Contthued)
969-0936--1
7"8611G CHRONOTHERM sIV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
" Symptom
Cocting will not
come OR.
Troubteshootlng (Continued).
Possible Cause Action
No power to the thermostat, Check for 24 Vac between R and C.
Thermostat minimum Offtime is
activated.
System selection is not set to
Cool,
Cool setpct nt is above room
temperature.
Heating or cooling Heat or cool circuit is opening
come on up or becoming high
momentarily and impedance_
shut off
System on indicator Hesting or cooling equipment is
flame=heat, not operating.
snowflake=cool) is
displayed, but no
warm or cool air is
coming from the
registers.
Outdoor Option not activated,
temperature
not dispteyeda
Outdoor Outdoor sensor is connscted
temperature incorrectly.
display is incorrecta Wrong sensor.
Select models.
-- If missing 24 Vac:
-- check if the circuit breaker is tripped--reset the
circuit breaker,
-- check if the system fuse is blown--replace the
fuse.
-- check if the power switch on the HVAC equipment
is in the Off pesition_sst to the On position.
-- check wiring between thermostat and HVAC
eduipment--replace any broken wires and tighten
any loose connectk_ns.
-- If 24 Vac is present, proceed with troubleshooting.
Wait up to five minutes for the system te respond.
Enter Installer Setup number 33. Reconfigure minimum off
time (if required).
Set system selection to Cool,
Check cooling setpntnt, Set cooling setpoint to desired
temperature.
Add resistor in parallel with load or install interface relay.
Verify operation of heating or cooIthg equipment In self-test,
Enter Installer Setup number 24 and set to 1, Thermostat must
have OT terminals and a C7089B1000 installed,
Refer to C7089B1000 installation instructions and check wiring
between the then'nostat and sensor,
Replace sensor with C7089B1000 sensor,
69-09_6_1 10
11 69"0936_1
Home and Building Control Home and Building Control
Honeywell Inc. Honeywell Limited-Honeywell Limit_e
Honeywell Plaza 155 Gordon Baker Road
P.O. Box 524 North York, Ontario
Minneapolis, MN 55408_9524 M2H 3N7
69-0936--1 J.H Ray. 6-97 PrlntBdinTaiwan[:LO.C.
Uon l
Helping You Control Your World _

Navigation menu