Honeywell 025010 PC-502.2 User Manual PC 502 2 v1 0 DS

INNCOM International Inc. PC-502.2 PC 502 2 v1 0 DS

Users Manual

Download: Honeywell 025010 PC-502.2 User Manual PC 502 2  v1 0 DS
Mirror Download [FCC.gov]Honeywell 025010 PC-502.2 User Manual PC 502 2  v1 0 DS
Document ID1221066
Application IDoSvbwrBGVIaEk991Q8kq+w==
Document DescriptionUsers Manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize26.78kB (334796 bits)
Date Submitted2009-12-30 00:00:00
Date Available2009-12-30 00:00:00
Creation Date2009-12-30 14:15:00
Producing SoftwareAcrobat Distiller 7.0 (Windows)
Document Lastmod2009-12-30 12:03:03
Document TitleMicrosoft Word - PC-502 2 v1 0 DS
Document CreatorPScript5.dll Version 5.2
Document Author: ryan.gardner

INNCOMȱPCȬ502.2ȱDatasheetȱ
Overviewȱ
The INNCOM PC-502.2 wall mounted module can be used to expand the
range of a Layer-2 RF network or provide the protocol gateway from
INNCOM S5-bus to Layer-2 RF protocol.
In the Layer-2.2 802.15.4 Zigbee 2006 mesh network, the PC-502.2 is
designed to patch areas within the network where signal strength is lost
due to distance limitations or interference. It also serves to create multiple
pathways, increasing the redundancy of the mesh communications to
ensure maximum network reliability.
Featuresȱ
Small wall mountable form factor
2.4Ghz IEEE 802.15.4 compliant RF transceiver (CC2430 radio
core)
Medium and long range variants available
Industrial temperature ratings 0-65 degrees C
FCC Part 15b listed
Figure 1 PC-502.2
Specificationȱ
Parameterȱ
RF Data Rate
Antenna Type
Indoor Range
Outdoor/ RF line-of-sight range
Transmit Power
Receive Sensitivity
Frequency Band
Encryption
Protocol
Frequency Channels
Input Voltage
Current Consumption
Operating Ambient Temperature
LED /Switch
PCȬ502.2ȱ
250kbps
SMT
100ft
1000ft+
10mW10dBm
(+18dBm)
-94.6dBm
2.405-2.475GHz
AES-128
802.15.4
15
12VDC
100mA (Peak)
40 ° C
0-40℃,0-95%RH
Reset indication, blinks when unit is connected to an RF
network. Rapid blink during binding association.
INNCOM PC-502.2 Datasheet
Page |2
Ranges are determined by performing an RF link quality test using e528.3G thermostats as the
transmitter and the PC-502.2 as the receiver. The maximum distance threshold is based on a 95%
overall link quality. Outdoor ranges were conducted in a low noise, free air environment. Indoor
ranges are for reference. Indoor ranges are affected by the ambient environmental noise floor and
building construction materials.
NetworkȱTopologyȱ
Figure 2 PC-502 Layer-2 Topology
In this application, the PC-502.2 in participation with the e529.RF provides the Layer-1 to Layer-2
RF Bridge where both wireless in-room and wireless back-end networking are required. The PC502.2 can also patch areas within the Layer-2 network where signal strength is lost due to distance
limitations or interference.
INNCOM PC-502.2 Datasheet
Page |3
Commissioningȱ
The PC-502.2 must be bound to the controlling device (e.g., the E529.RF in Figure 2 above) to
receive configuration information. On the E529.RF in service mode
Open the run menu and press Off/Auto
Set the value to 3 and press Display
When Display is pressed, the e529.RF sends Layer-2 configurations to the PC-502.2. (This
function does not offer any feedback on the screen so it is recommended that the Display
button be pressed 3 or 4 times to ensure configuration.)
Safety/Regulatoryȱ
Parameterȱ
FCC
Conditionȱ
Part 15b
Statusȱ
02-9994 is FCC listed. 02-9894, and 02-9927 FCC listings are pending.
PCȬ502.2ȱDimensionsȱ
ȱ
HeaderȱandȱConnectionsȱ
H3ȱ(InȱSystemȱProgramming)ȱ
Pinȱ
1-8
Functionȱ
Programming
Typeȱ
Minȱ
Maxȱ
H4ȱ/ȱH5ȱ(S5ȬbusȱIn/Out)ȱ
Pinȱ
1-GND
2-12VDC
Functionȱ
Common
Input voltage
Typeȱ
In
Minȱ
11.75
Maxȱ
12.25
INNCOM PC-502.2 Datasheet
3-S5-bus
Page |4
Multi-drop
In/Out
H6ȱ(SystemȬ5)ȱ
Pinȱ
1-GND
2-12VDC
3-S5-bus
4–InOut1
5-InOut2
Functionȱ
Common
Input voltage
Multi-drop
TTL
TTL
Typeȱ
In
In/Out
In/Out
In/Out
Minȱ
11.75
Maxȱ
12.25
3-pin to 3-pin harness for 12VDC and S5bus connection
OrderingȱInformationȱ
PartȱNumberȱ
01-5010.2
OPNȱ
PC-502.2
Descriptionȱ
PC-502 with 02-9894 20db Radio
DocumentȱRevisionȱHistoryȱ
Revisionȱ
0.1
0.2
1.0
DateȱIssuedȱ
27-Mar-2009
31-Mar-2009
07-Apr-2009
ȱReasonȱ
FCC for PC-502
Edited for content and format
Released
Warning
Any Changes or modifications not expressly approved by the party responsible for
compliance could void the user's authority to operate the equipment.
This device complies with part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference, and (2)
this device must accept any interference received, including interference that may
cause undesired operation.
IMPORTANT NOTE:
FCC Radiation Exposure Statement:
This equipment complies with FCC radiation exposure limits set forth for an
uncontrolled environment .This equipment should be installed and operated with
minimum distance 20 cm between the radiator& your body
Note: This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the
following measures:
—Reorient or relocate the receiving antenna.
—Increase the separation between the equipment and receiver.
—Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
—Consult the dealer or an experienced radio/TV technician for help.

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Producer                        : Acrobat Distiller 7.0 (Windows)
Create Date                     : 2009:12:30 14:15+08:00
Modify Date                     : 2009:12:30 12:03:03-08:00
Metadata Date                   : 2009:12:30 12:03:03-08:00
Creator Tool                    : PScript5.dll Version 5.2
Document ID                     : uuid:DA2FC9A20AF5DE1188B89C727E5C2BD4
Instance ID                     : uuid:81da2b26-fcaa-4b6c-8626-b3ab1d48c936
Derived From Instance ID        : uuid:993e1c49-d001-4499-9607-463ea8978069
Derived From Document ID        : uuid:61a74408-5611-4bd0-ba35-285f894b46d4
Format                          : application/pdf
Title                           : Microsoft Word - PC-502 2  v1 0 DS
Creator                         : ryan.gardner
Page Count                      : 5
Author                          : ryan.gardner
EXIF Metadata provided by EXIF.tools
FCC ID Filing: GTC025010

Navigation menu