Honeywell BOTAC01 IdentIPoint User Manual BOTAC Intelligent Smartcard System

Honeywell Inc IdentIPoint BOTAC Intelligent Smartcard System

Users Manual

Honeywell Honeywell IdentIPoint Intelligent Smartcard Readers QUICK INSTALLATION GUIDE  95-7771 1  WARNING: This equipment generates, uses, and can radiate radio frequency energy, and if not installed and used in accordance with the Instructions Manual, may cause interference with radio communication. It has been tested and found to comply with the limits for a Class B computing device pursuant to Subpart J of Part 15 of FCC Rules, that are designed to provide reasonable protection against such interference when operated in a residential and commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case, users at their own expense will be required to take whatever measures may be required to correct the interference. Any unauthorized modification of this equipment may result in the revocation of the owner's authority to continue its operation.  WARNING: Fire Safety and Liability Notice: Never connect card readers to any critical entry, exit door, barrier, elevator or gate without providing an alternative exit in accordance with all fire and life safety codes pertinent to the installation. These fire and safety codes vary from city to city and you must get approval from local fire officials whenever using an electronic product to control a door or other barrier. Use of egress buttons, for example, may be illegal in some cities. In most applications, single action exit without prior knowledge of what to do is a life safety requirement. Always make certain that any required approvals are obtained in writing. Verbal approvals are not valid. Wiring of door strikes and locks would also accordingly follow either a fail-safe or fail-secure configuration.   WARNING:  Earth ground all enclosures for proper installation. It is mandatory to use body earth on the terminal of the fingerprint reader.  WARNING: Exit switch wiring must be completed within the protected area or not readily accessible outside the protected area.  WARNING: Use suppressors on all door locks. Use 14507020-001 diode suppression network. Honeywell recommends only DC locks.   CAUTION: If the bus wiring enters or exits the building, the protectors listed in Installation Manual must be used. Bus length for RS485 must not exceed 500m end-to-end.  This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment .This equipment should be installed and operated with minimum distance 20cm between the radiator& your body.
Honeywell IdentIPoint Intelligent Smartcard Readers  CAUTION: Electro-static discharge (ESD) can damage CMOS integrated circuits and modules. Tprevent damage always followprocedures: o  6 these  7.  Resistors – 2K (Color Code: RED-BLACK-RED-GOLD; 0.5W axial type, 5% tolerance) – 3   Use static shield packaging and containers to transport all electronic components, including completed reader assemblies.  Handle all ESD sensitive components at an approved static controlled workstation.  BEFORE INSTALLATION  1.  Verify the mounting locations with the job drawings. 2.  Unpack the IdentIPoint reader, IOM and accessories and check them. Report any damaged or missing components to a Honeywell representative. A claim must be filed with the commercial carrier responsible.  Parts Reader box  1.  Intelligent Reader Unit – 1  2.  Mounting Plate – 1  3.  Mounting Hardware - Screws and Wall Anchors – 6 each 4.  Extra Tamper Resistant Screws – 2  5.  Tool for Tamper Resistant Screw – 1  .  Connector with cable – 2 (9 and 10 pin) 8.  Resistors – 1K (Color Code: BROWN-BLACK-RED-GOLD; 0.5W axial type, 5% tolerance) – 3  9.  Square ferrite clip – 1 10. Round ferrite clip – 1 11. Quick Installation Guide – 1   IOM box  1.  Input / Output Module Unit – 1  2.  Mounting Hardware - Screws and Wall Anchors – 3 each  3.  Extra Tamper Resistant Screws – 2 4.  Tool for Tamper Resistant Screw – 1  5.  Connectors for termination – 12 x 2 connections; 3 x 3 connections 6.  Resistors – 2K (Color Code: RED-BLACK-RED-GOLD; 0.5W axial type, 5% tolerance) – 4 7.  Resistors – 1K (Color Code: BROWN-BLACK-RED-GOLD; 0.5W axial type, 5% tolerance) – 4 8.  Quick Installation Guide – 1 95-7771  2
Honeywell IdentIPoint Intelligent Smartcard Readers ASSEMBLY, MOUNTING AND INSTALLATION  Notes:   The reader and IOM can be mounted either on a drywall or on a concrete wall using conduits and a gang-box.   The drywall and gang-boxes shown here are just representations of the actual hardware. During installation, use the hardware as per the required dimensions and availability.   Reader Drywall Mounting  1.  Fig.1 and Fig.2 show the parts of the IdentIPoint reader. Use the back-plate of the reader to mark out the position of the reader on the drywall. Mark the positions of the mounting screws and the opening for routing the cables.  2.  Cut the cable opening on the drywall using suitable tools and punch an adequate number of holes for the mounting screws. It is advisable to use at least four screws for fixing the reader. Use the wall anchors for additional holding strength. See Fig.3. 3.  Hold the back-plate in position on the drywall. Align the mounting screws with their holes and fasten the back-plate securely on the drywall using the screws. See Fig.3. 4.  Route the field wires including the Ethernet cable (if required) from behind the drywall through the cable opening and bring them to the front of the mounting surface. Clip the square ferrite clip on the reader’s Ethernet pigtail. See Fig.6. Connect the field wiring to the correct Molex pigtails. See Fig.5. For reader connection details see Fig.10. Plug the Molex terminal(s) in ports J9 and J10 at the back of the reader. See Fig.6. Clip (with two turns wrapped) the round ferrite clip on the field Ethernet cable. See Fig.5. Plug the RJ45 connector of the field Ethernet cable into the Ethernet port of the reader at the end of the pigtail. See Fig.6. Drop the excess lengths of Molex and Ethernet wires behind the drywall. Set the S1 DIP switch if the reader is to be connected to an IOM via RS485. See Fig.10 and appendix for more details. 5.  Once all the connections and settings are done, hold the reader against the back-plate, aligning the mounting slots at the back of the reader with their corresponding catches on the back-plate and push it downwards until it hooks into place firmly. See Fig.7 and Fig.8.  6.  Use the Allen wrench to tighten the tamper-resistant screw at the bottom of the reader. See Fig.9.  Gang-box (concrete wall) Mounting  1.  Fig.1 and Fig.2 show the parts of the IdentIPoint reader. Ensure that the correct sized gang-box is securely embedded in the concrete wall. The holes provided in the gang-box for the screws should align properly with at least two of the holes provided in the reader back-plate for the screws. 2.  Hold the back-plate in position over the gang-box. Align the mounting screws with their holes and fasten the back-plate securely on the gang-box using the screws. See Fig.4.  95-7771 3
Honeywell IdentIPoint Intelligent Smartcard Readers 3.  Route the field wiring including the Ethernet cable (if required) from the conduits into the gang-box. Clip the square ferrite clip on the reader’s Ethernet pigtail. See Fig.6. Connect the field wiring to the correct Molex pigtails. See Fig.5. For reader connection details see Fig.10. Route the Molex terminal(s) through the cable opening on the back-plate towards the front of the mounting surface (see Fig.5) and plug them in ports J9 and J10 at the back of the reader. See Fig.6. Clip (with two turns wrapped) the round ferrite clip on the field Ethernet cable. See Fig.5. Plug the RJ45 connector of the field Ethernet cable into the Ethernet port of the reader provided at the end of the pigtail. Accommodate the Molex and Ethernet pigtails inside the gang-box. Set the S1 DIP switch if the reader is to be connected to an IOM via RS485. See Fig.10 and appendix for more details. 4.  Once all the connections and settings are done, hold the reader against the back-plate, aligning the mounting slots at the back of the reader with their corresponding catches on the back-plate and push it downwards until it hooks into place firmly. See Fig.7 and Fig.8.  5.  Use the Allen wrench to tighten the tamper-resistant screw at the bottom of the reader. See Fig.9.             Fig.1. Parts of IdentIPoint reader – Front of reader and Back-plate BACK-PLATECATCHES FOR HOLDING READER ON BACK-PLATE (4)READER STATUS LEDKEYPADREADER FRONT MOUNTING SCREW HOLES (10)OPENING FOR ROUTING CABLES (1)1234567890#LCDBACK-PLATECATCHES FOR HOLDING READER ON BACK-PLATE (4)READER STATUS LEDKEYPADREADER FRONT MOUNTING SCREW HOLES (10)OPENING FOR ROUTING CABLES (1)LCD1234567890#1234567890#95-7771  4
Honeywell IdentIPoint Intelligent Smartcard Readers  95-7771 5 READER MOUNTING SLOTS (4)STATUS LEDS (3)DIP SWITCH S1READER BACK10/100ActivityPowerETHERNET TERMINAL (EPOXY POTTED FOR IP65 COMPLIANCE)FACTORY RESET SWITCHOPTICAL TAMPER SENSORWIRING TERMINAL PORTS J9, J10HOLE FOR TAMPER-RESISTANT SCREWCAT5 PIGTAILHOLE FOR HOLDING RUBBER COVER (SHOWN IN CALLOUT)RJ45 TERMINAL PLUGModel: BTSTDIdentIPoint Standard IndoorPower 10-28 VDC, PoEMAC ID Eth ernet   0 040840AF33EMAC ID Wi-fi 00408-IOAF33FManufactured:              2009 .07.13                      MADE IN CHINA12341234ON POSITIONON POSITIONREADER MOUNTING SLOTS (4)STATUS LEDS (3)DIP SWITCH S1READER BACK10/100ActivityPowerETHERNET TERMINAL (EPOXY POTTED FOR IP65 COMPLIANCE)FACTORY RESET SWITCHOPTICAL TAMPER SENSORWIRING TERMINAL PORTS J9, J10HOLE FOR TAMPER-RESISTANT SCREWCAT5 PIGTAILHOLE FOR HOLDING RUBBER COVER (SHOWN IN CALLOUT)RJ45 TERMINAL PLUGModel: BTSTDIdentIPoint Standard IndoorPower 10-28 VDC, PoEMAC ID Eth ernet   0 040840AF33EMAC ID Wi-fi 00408-IOAF33FManufactured:              2009 .07.13                      MADE IN CHINA12341234123412341234ON POSITIONON POSITIONON POSITIONON POSITIONFig.2. Parts of IdentIPoint reader – Back of reader
Honeywell IdentIPoint Intelligent Smartcard Readers 95-7771  6 Fig.4. Fixing reader back-plate to concrete wall USE THE SCREWS PROVIDED TO FIX THE READER BACK-PLATE TO THE EMBEDDED GANGBOX.NOTE: USE A MINIMUM OF 2 SCREWS IN THE HOLES CIRCLED IN RED TO FASTEN THE BACK-PLATEGANGBOX EMBEDDED IN WALLUSE THE SCREWS PROVIDED TO FIX THE READER BACK-PLATE TO THE EMBEDDED GANGBOX.NOTE: USE A MINIMUM OF 2 SCREWS IN THE HOLES CIRCLED IN RED TO FASTEN THE BACK-PLATEGANGBOX EMBEDDED IN WALLFig.3. Fixing reader back-plate to drywall USE THE SCREWS PROVIDED TO FIX THE BACK-PLATE TO THE DRYWALL.NOTE: USE A MINIMUM OF 4 SCREWS IN THE HOLES CIRCLED IN REDCUT AN OPENING IN THE DRYWALL FOR ROUTING THE WIRES. THE OPENING MUST HAVE THE SAME DIMENSIONS AS THAT IN THE BACK-PLATE.PUNCH AN ADEQUATE NUMBER OF HOLES IN THE DRYWALL FOR THE SCREWSUSE THE SCREWS PROVIDED TO FIX THE BACK-PLATE TO THE DRYWALL.NOTE: USE A MINIMUM OF 4 SCREWS IN THE HOLES CIRCLED IN REDCUT AN OPENING IN THE DRYWALL FOR ROUTING THE WIRES. THE OPENING MUST HAVE THE SAME DIMENSIONS AS THAT IN THE BACK-PLATE.PUNCH AN ADEQUATE NUMBER OF HOLES IN THE DRYWALL FOR THE SCREWS
Honeywell IdentIPoint Intelligent Smartcard Readers    ROUTE THE RJ45 CONNECTOR (IF REQUIRED) AND MOLEX TERMINALS FROM BEHIND THE DRYWALL OR THROUGH THE CONDUITS (IN CASE OF CONCRETE WALL) AND BRING THEM TOWARDS THE FRONT SIDE OF THE MOUNTING SURFACE THROUGH THE OPENING ON THE READER’S BACK-PLATE. PLUG THE RJ45 CONNECTOR INTO THE ETHERNET PORT OF THE READER AT THE END OF THE PIGTAIL. PLUG THE MOLEX TERMINALS INTO THE J9 AND J10 PORTS OF THE READERCLIP ROUND FERRITE CLIP ON THE FIELD ETHERNET CABLE WITH TWO TURNS WRAPPEDROUTE THE RJ45 CONNECTOR (IF REQUIRED) AND MOLEX TERMINALS FROM BEHIND THE DRYWALL OR THROUGH THE CONDUITS (IN CASE OF CONCRETE WALL) AND BRING THEM TOWARDS THE FRONT SIDE OF THE MOUNTING SURFACE THROUGH THE OPENING ON THE READER’S BACK-PLATE. PLUG THE RJ45 CONNECTOR INTO THE ETHERNET PORT OF THE READER AT THE END OF THE PIGTAIL. PLUG THE MOLEX TERMINALS INTO THE J9 AND J10 PORTS OF THE READERCLIP ROUND FERRITE CLIP ON THE FIELD ETHERNET CABLE WITH TWO TURNS WRAPPEDFig.5. Routing the wires before plugging the connectors into the reader  95-7771 7
Honeywell IdentIPoint Intelligent Smartcard Readers  HOLD THE 9 AND 10-PIN MOLEX TERMINALS PERPENDICULAR TO THE BACK OF THE READER AND ALIGN THEM CORRECTLY WITH PORTS J9 AND J10PUSH THE 9 AND 10-PIN MOLEX TERMINALS FIRMLY INTO THE READER PORTS J9 AND J10 RESPECTIVELY. ENSURE THAT ALL 9 AND 10 PINS GO INSIDE THE HOLES OF THEIR RESPECTIVE TERMINALS AND THAT THE SPECIAL PROTRUSIONS ON THE TERMINALS MATE WITH THE SPECIAL SLOTS PROVIDED ON THE PORTS. THIS ENSURES THAT THE TERMINALS CANNOT BE PLUGGED INTO WRONG PORTS.PLUG RJ45 CONNECTOR (IF REQD.) IN THE RJ45 TERMINAL PLUGPIN 9PIN 1PORT J9PIN 1PIN 10PORT J1010/100ActivityPowerTO PIN 9TO PIN 19-PIN MOLEX TERMINAL 10-PIN MOLEX TERMINALTO PIN 1TO PIN 10Model: BTSTDIdentIPoint S tandar d IndoorPower 10-28 VDC, PoEMAC ID Etherne t   004 0840AF 33EMAC ID Wi-fi 004 08-IOAF33 FManufactured:              2009.0 7.13                      MA DE IN CHINAON POSITIONON POSITIONON POSITIONON POSITION12341234123412341234CLIP SQUARE FERRITE CLIP TO THE PIGTAILHOLD THE 9 AND 10-PIN MOLEX TERMINALS PERPENDICULAR TO THE BACK OF THE READER AND ALIGN THEM CORRECTLY WITH PORTS J9 AND J10PUSH THE 9 AND 10-PIN MOLEX TERMINALS FIRMLY INTO THE READER PORTS J9 AND J10 RESPECTIVELY. ENSURE THAT ALL 9 AND 10 PINS GO INSIDE THE HOLES OF THEIR RESPECTIVE TERMINALS AND THAT THE SPECIAL PROTRUSIONS ON THE TERMINALS MATE WITH THE SPECIAL SLOTS PROVIDED ON THE PORTS. THIS ENSURES THAT THE TERMINALS CANNOT BE PLUGGED INTO WRONG PORTS.PLUG RJ45 CONNECTOR (IF REQD.) IN THE RJ45 TERMINAL PLUGPIN 9PIN 1PORT J9PIN 1PIN 10PORT J1010/100ActivityPowerTO PIN 9TO PIN 19-PIN MOLEX TERMINAL 10-PIN MOLEX TERMINALTO PIN 1TO PIN 10Model: BTSTDIdentIPoint S tandar d IndoorPower 10-28 VDC, PoEMAC ID Etherne t   004 0840AF 33EMAC ID Wi-fi 004 08-IOAF33 FManufactured:              2009.0 7.13                      MA DE IN CHINAON POSITIONON POSITIONON POSITIONON POSITION12341234123412341234CLIP SQUARE FERRITE CLIP TO THE PIGTAILBOTH MOLEX TERMINALS SHOULD FIT FIRMLY INSIDE THEIR RESPECTIVE PORTS AT THE BACK OF THE READER AS SHOWNBOTH MOLEX TERMINALS SHOULD FIT FIRMLY INSIDE THEIR RESPECTIVE PORTS AT THE BACK OF THE READER AS SHOWNFig.6. Plugging the connectors into the IdentIPoint reader ALIGN THE MOUNTING SLOTS BEHIND THE READER WITH THEIR CORRESPONDING CATCHES ON THE BACK-PLATE10/100ActivityPowerModel: BTSTDIdentIP oint  Stan dard  Indoo rPower 10-28 VDC, PoEMAC ID Ethernet   0040840AF33EMAC ID Wi- fi 00408- IOAF3 3FManufactured:                2009.07 .13                       MADE IN  CHINAON POSITIONON POSITIONON POSITIONON POSITION12341234123412341234ALIGN THE MOUNTING SLOTS BEHIND THE READER WITH THEIR CORRESPONDING CATCHES ON THE BACK-PLATE10/100ActivityPowerModel: BTSTDIdentIP oint  Stan dard  Indoo rPower 10-28 VDC, PoEMAC ID Ethernet   0040840AF33EMAC ID Wi- fi 00408- IOAF3 3FManufactured:                2009.07 .13                       MADE IN  CHINAON POSITIONON POSITIONON POSITIONON POSITION12341234123412341234 Fig.7. Aligning IdentIPoint reader with back-plate before fixing it 95-7771  8
Honeywell IdentIPoint Intelligent Smartcard Readers            READER ASSEMBLY –SIDE VIEWALIGN THE MOUNTING SLOTS BEHIND THE READER WITH THEIR CORRESPONDING CATCHES ON THE BACK-PLATE. PUSH THE READER DOWNWARDS UNTIL IT HOOKS INTO PLACE FIRMLY1234567890 #1234567890 #READER ASSEMBLY –FRONT VIEWREADER ASSEMBLY –SIDE VIEWALIGN THE MOUNTING SLOTS BEHIND THE READER WITH THEIR CORRESPONDING CATCHES ON THE BACK-PLATE. PUSH THE READER DOWNWARDS UNTIL IT HOOKS INTO PLACE FIRMLY1234567890 #1234567890 #READER ASSEMBLY –FRONT VIEWFig.8. Fixing the IdentIPoint reader on the back-plate 10/100ActivityPowerModel: BTSTDIdentIPoint S tandard  IndoorPower 10-28 VDC, PoEMAC ID Ethernet   0040840AF33EMAC ID Wi-fi 00408-IOAF33FManufactured:             2009.07.13                       MADE IN CHINAON POSITIONON POSITIONON POSITIONON POSITION12341234123412341234USE THE ALLEN WRENCH TO SECURE THE READER TO THE BACK-PLATE WITH THE TAMPER-RESISTANT SCREW1234567890#1234567890#10/100ActivityPowerModel: BTSTDIdentIPoint S tandard  IndoorPower 10-28 VDC, PoEMAC ID Ethernet   0040840AF33EMAC ID Wi-fi 00408-IOAF33FManufactured:             2009.07.13                       MADE IN CHINAON POSITIONON POSITIONON POSITIONON POSITION12341234123412341234USE THE ALLEN WRENCH TO SECURE THE READER TO THE BACK-PLATE WITH THE TAMPER-RESISTANT SCREW1234567890#1234567890#1234567890#1234567890#Fig.9. Securing the IdentIPoint reader to the back-plate   95-7771 9
Honeywell IdentIPoint Intelligent Smartcard Readers  10/100ActivityPowerModel: BTSTDIdentIPoint Standard IndoorPower 10-28 VDC, PoEMAC ID Ethernet   0040840AF33EMAC ID Wi-fi 00408-IOAF33FManufactured:             2009.07.13                     MADE IN CHINAON POSITIONON POSITIONON POSITIONON POSITION1234123412341234123410/100ActivityPowerModel: BTSTDIdentIPoint Standard IndoorPower 10-28 VDC, PoEMAC ID Ethernet   0040840AF33EMAC ID Wi-fi 00408-IOAF33FManufactured:             2009.07.13                     MADE IN CHINAON POSITIONON POSITIONON POSITIONON POSITION12341234123412341234Marking Color Description10/100 Green Onwhennetworkis100MBitActivity Orange FlashesonnetworkactivityPower Blue OnifpoweronMarking Color Description10/100 Green Onwhennetworkis100MBitActivity Orange FlashesonnetworkactivityPower Blue OnifpoweronJ9 PIN PIN J10SAI‐1‐GND 91Power‐OUTSAI‐182Power‐GNDSAI‐0‐GND 7 3 RS485‐ASAI‐064RS485‐BRelay‐NO 5 5 RS485‐GNDRelay‐NC 4 6 DORelay‐C37DOGndPower‐GND 2 8 SAI‐2Power‐IN 19SAI‐2‐GND10 Frame‐GNDJ9 PIN PIN J10SAI‐1‐GND 91Power‐OUTSAI‐182Power‐GNDSAI‐0‐GND 7 3 RS485‐ASAI‐064RS485‐BRelay‐NO 5 5 RS485‐GNDRelay‐NC 4 6 DORelay‐C37DOGndPower‐GND 2 8 SAI‐2Power‐IN 19SAI‐2‐GND10 Frame‐GNDPosition Effectwhen“ON”(PositionLeft)1RS485‐Apullup2RS485termination3RS485‐Bpulldown4WifiDisablePosition Effectwhen“ON”(PositionLeft)1RS485‐Apullup2RS485termination3RS485‐Bpulldown4WifiDisableDIP SWITCH S1CONNECTORS AT THE BACKLED INDICATORS AT THE BACKFACTORY RESET SWITCHOPTICAL ALARM TAMPER Fig10. Reader connections 95-7771  10
Honeywell IdentIPoint Intelligent Smartcard Readers  95-7771 11 INPUT/OUTPUT MODULE Drywall Mounting  1.  The IOM is a clamshell plastic case. The back half of the case has the electronic circuit board fastened to it while the front case cover swings open to allow access to the electronics and wiring. Pull open the front cover. This reveals the mounting holes and other components inside the IOM. See Fig.11 and Fig.12. 2.  Use the back half to mark out the position of the IOM on the drywall. Also mark the positions of the mounting screws and the openings for routing the cables. See Fig.13.  3.  Cut the two cable openings on the drywall using suitable tools. The openings should be aligned with the knock-out holes provided on the back half for routing the cables. Also punch three holes at suitable places in the drywall for the mounting screws. Use the wall anchors for additional holding strength. See Fig.13. 4.  Ensure that the knock-out holes on the back half have been opened up. (Knock-out holes are also provided on both sides of the IOM enclosure in case field conditions require routing the wires from the sides.) Hold the back half in position on the drywall. Align the mounting screws with their holes and fasten the back half securely on the drywall using the three screws. See Fig.13.  5.  Route the field wires from behind the drywall through the cable opening and bring them inside the IOM via the knock-out holes. Connect the wire terminals to the ends of the wires and plug the wire terminal(s) in their correct slots on the PCB. See Fig.15. For IOM connection details see Fig.17. Drop the excess wire lengths behind the drywall. Set the S1 DIP switch if the IOM is to be connected to a reader via RS485. See Fig.17 and appendix for more details. 6.  Set the IOM address as per Fig.17 and appendix. Once all connections and settings are done, close the IOM enclosure by pressing the front case cover over the back half. See Fig.15.  7.  Use the Allen wrench to tighten the tamper-resistant screw at the top of the IOM enclosure. See Fig.16. Gang-box (concrete wall) Mounting  1.  The IOM is a clamshell plastic case. The back half of the case has the electronic circuit board fastened to it while the front case cover swings open to allow access to the electronics and wiring. Pull open the front cover. This reveals the mounting holes and other components inside the IOM. See Fig.11 and Fig.12. 2.  Ensure that the correct sized gang-box is securely embedded in the concrete wall. One of the holes provided in the gang-box for the screws should align properly with at least the top hole provided in the IOM's back half for the screw. For the remaining screws punch additional holes at the correct places directly in the concrete wall. Use the wall anchors for additional holding strength. The gang-box itself should be large enough to cover both the knock-out cable holes at the back of the IOM. See Fig.14.
Honeywell IdentIPoint Intelligent Smartcard Readers 3.  Route the field wires from the conduits into the gang-box and bring them inside the IOM via the knock-out holes.  4.  The IOM can now be mounted on the wall. Hold the back half in position over the gang-box and wall. Align the three mounting screws with their holes and fasten the back half securely on the gang-box and wall using the screws. See Fig.14. 5.  Connect the wire terminals to the ends of the wires and plug the wire terminal(s) in their correct slots on the PCB. See Fig.15. For IOM connection details see Fig.17. Accommodate any excess wire lengths inside the gang-box. Set the S1 DIP switch if the IOM is to be connected to a reader via RS485. See Fig.17 and appendix for more details. 6.  Set the IOM address as per Fig.17 and appendix. Once all connections and settings are done, close the IOM enclosure by pressing the front case cover over the back half. See Fig.15.  7.  Use the Allen wrench to tighten the tamper-resistant screw at the top of the IOM enclosure. See Fig.16. 95-7771  12
Honeywell IdentIPoint Intelligent Smartcard Readers PowerDataTamperPOWER, DATA AND TAMPER INDICATION LEDSFRONT COVER OF THE IOM HINGE AT THE BOTTOM HOLDING THE TWO PARTS TOGETHERBACK HALF OF THE IOM SIDE KNOCK-OUTS FOR CABLE HOLESPowerDataTamperPOWER, DATA AND TAMPER INDICATION LEDSFRONT COVER OF THE IOM HINGE AT THE BOTTOM HOLDING THE TWO PARTS TOGETHERBACK HALF OF THE IOM SIDE KNOCK-OUTS FOR CABLE HOLESFig.11. Outer structure of IOM – Front and side view  95-7771 13
Honeywell IdentIPoint Intelligent Smartcard Readers PRINTED CIRCUIT BOARDBACK KNOCK-OUTS FOR CABLE HOLES (2)WIRING TERMINALS –2 WIRE (13)WIRING TERMINALS –3 WIRE (3)IOM FRONT COVER - OPENHOLE FOR TAMPER-RESISTANT SCREWIOM BACK HALF - OPENHOLE FOR TAMPER-RESISTANT SCREWLIGHT GUIDESCABLE GUIDES (6)COVER TAMPER DETECTION SWITCHPULL OPEN THE FRONT COVER OF THE IOM AND ALLOW IT TO HANG FROM THE HINGEMOUNTING SCREW HOLES (3)PRINTED CIRCUIT BOARDBACK KNOCK-OUTS FOR CABLE HOLES (2)WIRING TERMINALS –2 WIRE (13)WIRING TERMINALS –3 WIRE (3)IOM FRONT COVER - OPENHOLE FOR TAMPER-RESISTANT SCREWIOM BACK HALF - OPENHOLE FOR TAMPER-RESISTANT SCREWLIGHT GUIDESCABLE GUIDES (6)COVER TAMPER DETECTION SWITCHPULL OPEN THE FRONT COVER OF THE IOM AND ALLOW IT TO HANG FROM THE HINGEMOUNTING SCREW HOLES (3)Fig.12. Internal structure and components of IOM  95-7771  14
Honeywell IdentIPoint Intelligent Smartcard Readers  95-7771 15    Fig.13. Fixing the IOM on a drywall  CUT OPENINGS IN THE DRYWALL FOR ROUTING THE WIRES. THE OPENINGS MUST HAVE THE SAME DIMENSIONS AS THAT IN THE BACK HALF OF THE IOM. Fig.13. Fixing the IOM on a drywall USE THE SCREWS PROVIDED TO FIX THE BACK HALF OF THE IOM TO THE DRYWALL.NOTE: USE ALL THREE HOLES TO FASTEN THE IOMPUNCH THREE HOLES IN THE DRYWALL FOR THE SCREWSCUT OPENINGS IN THE DRYWALL FOR ROUTING THE WIRES. THE OPENINGS MUST HAVE THE SAME DIMENSIONS AS THAT IN THE BACK HALF OF THE IOM.USE THE SCREWS PROVIDED TO FIX THE BACK HALF OF THE IOM TO THE DRYWALL.NOTE: USE ALL THREE HOLES TO FASTEN THE IOMPUNCH THREE HOLES IN THE DRYWALL FOR THE SCREWS
Honeywell IdentIPoint Intelligent Smartcard Readers    USE THE SCREWS PROVIDED TO FIX THE BACK HALF OF IOM TO THE GANGBOX AND THE WALL.NOTE: USE ALL 3 SCREWS TO FASTEN THE IOMGANGBOX EMBEDDED IN WALLPUNCH ADDITIONAL HOLES IN THE WALL FOR THE OTHER SCREWSUSE THE SCREWS PROVIDED TO FIX THE BACK HALF OF IOM TO THE GANGBOX AND THE WALL.NOTE: USE ALL 3 SCREWS TO FASTEN THE IOMGANGBOX EMBEDDED IN WALLPUNCH ADDITIONAL HOLES IN THE WALL FOR THE OTHER SCREWSFig.14. Fixing the IOM on a concrete wall using gang-box and conduit 95-7771  16
Honeywell IdentIPoint Intelligent Smartcard Readers  95-7771 17  Fig.15. Routing the wires and connecting them to the IOM PCB ROUTE THE WIRES THROUGH THE KNOCKED OUT HOLES AND FIX THEM TO THE CORRECT TERMINALS ON THE PCB USING THE PROVIDED WIRE TERMINAL BLOCKSAFTER WIRING AND OTHER HARDWARE CONFIGURATIONS ARE DONE, SHUT THE FRONT COVER OF THE IOMROUTE THE WIRES THROUGH THE KNOCKED OUT HOLES AND FIX THEM TO THE CORRECT TERMINALS ON THE PCB USING THE PROVIDED WIRE TERMINAL BLOCKSAFTER WIRING AND OTHER HARDWARE CONFIGURATIONS ARE DONE, SHUT THE FRONT COVER OF THE IOMAFTER WIRING AND OTHER HARDWARE CONFIGURATIONS ARE DONE, SHUT THE FRONT COVER OF THE IOM
Honeywell IdentIPoint Intelligent Smartcard Readers 95-7771  18 PowerDataTamperUSE THE ALLEN WRENCH TO SECURE THE FRONT COVER OF THE IOM TO THE BACK HALF WITH TAMPER-RESISTANT SCREWPowerDataTamperPowerDataTamperUSE THE ALLEN WRENCH TO SECURE THE FRONT COVER OF THE IOM TO THE BACK HALF WITH TAMPER-RESISTANT SCREW     Fig.16. Securing the front cover onto the back half of the IOM
Honeywell IdentIPoint Intelligent Smartcard Readers DIPswitch‐ S1Position Effectwhen“ON”(PositionUp)1RS485‐Apullup2RS485termination3RS485‐Bpulldown4ReservePosition Effectwhen“ON”(PositionUp)1RS485‐Apullup2RS485termination3RS485‐Bpulldown4ReserveSwitch DescriptionS1 RS485TerminationControlDIPswitchS2 InitializationButtonS3 IOMAddresssetupDIPswitchS4 CovertamperdetectionswitchSwitch DescriptionS1 RS485TerminationControlDIPswitchS2 InitializationButtonS3 IOMAddresssetupDIPswitchS4 CovertamperdetectionswitchS2:InitializationButtonDIPswitchS3 ‐IOMaddressPosition Description1 Addressvalue12 Addressvalue23 Addressvalue44 Addressvalue85 Addressvalue166 Addressvalue327 Addressvalue648ForIOMsetup,normallysettoOFFPosition Description1 Addressvalue12 Addressvalue23 Addressvalue44 Addressvalue85 Addressvalue166 Addressvalue327 Addressvalue648ForIOMsetup,normallysettoOFFS4:Covertamperdetectionswitch Fig.17. IOM connections  95-7771 19
Honeywell IdentIPoint Intelligent Smartcard Readers APPENDIX  WIRING DIAGRAMS      Fig.18. Single reader with REX and without IOM Power – Min . 18 AW GPower Gnd –Min. 18 AWGEth ern et – CAT5 Power/Signal – Min. 18 AWGSignal –Min. 18 AWGSignal –Min. 18 AWGLEGENDPosition Effect “OtoRS485 whenth N”ht) llup  (slideeRig1‐RS485 Aputerm‐ 2 RS485 ination Bpulldown 34WifiDisableDC–Power12to24VIfPOEisnotused2KΩToDoorSensor1KΩ1Power‐OUTSAI‐1‐GND92Power‐GNDSAI‐183RS485‐ASAI‐0‐GND74RS485‐BSAI‐065RS485‐GNDRelay‐NO 56DORelay‐NC47DOGndRelay‐C38SAI‐2Power‐GND29SAI‐2‐GNDPower‐IN1Frame‐GNDJ10PINPINJ9S1ToDoorLockToDoorLockToLANToLAN EthernetToREXSwitchToREXSwitch2KΩ1KΩIdentIPointreader1095-7771  20
Honeywell IdentIPoint Intelligent Smartcard Readers   EthernetToDoorLockToLANIdentIPointReaderDI‐0GNDGND DO‐0DI‐1GNDGND D1‐0SAI‐0GNDGND ILK‐0SAI‐1GNDGND ILK‐1SAI‐2485‐GNDGND 485‐BSAI‐3485‐AGND N.CSAO N.OGND RLO‐C12V N.CGND N.OFGND RL1‐CDI‐0GNDGND DO‐0DI‐1GNDGND D1‐0SAI‐0GNDGND ILK‐0SAI‐1GNDGND ILK‐1SAI‐2485‐GNDGND 485‐BSAI‐3485‐AGND N.CSAO N.OGND RLO‐C12V N.CGND N.OFGND RL1‐CIOmoduleSeparatePowerSupplycanalsobeusedforIOM1KΩ2KΩToREXSwitch1KΩ2KΩToDoorSensorS1S11Power‐OUTSAI‐1‐GND92Power‐GNDSAI‐183RS485‐ASAI‐0‐GND74RS485‐BSAI‐065RS485‐GNDRelay‐NO 56DORelay‐NC47DOGndRelay‐C38SAI‐2Power‐GND29SAI‐2‐GNDPower‐IN1Frame‐GNDJ10PINPINJ910DC–Power12to24VIfPOEisnotusedSignal/Power – Min. 18 AWGPower – Min. 18 AWGPower Gnd – Min. 18 AWGEthernet – CAT5Signal – Min. 18 AWGSignal – Min. 18 AWGComm. – Min. 18 AWGComm. – Min. 18 AWGComm. – Min. 18 AWGLEGENDSignal/Power – Min. 18 AWGPower – Min. 18 AWGPower Gnd – Min. 18 AWGEthernet – CAT5Signal – Min. 18 AWGSignal – Min. 18 AWGComm. – Min. 18 AWGComm. – Min. 18 AWGComm. – Min. 18 AWGLEGEND  Fig.19. Single reader with REX and IOM (S1 DIP switch settings shown)  95-7771 21
Honeywell IdentIPoint Intelligent Smartcard Readers 95-7771  22       EthernetIdent IPointReaderGND12VGNDSAOGNDSAI‐3GNDSAI‐2GNDSAI‐1GNDSAI‐0GNDGNDGND12VGNDSAOGNDSAI‐3GNDSAI‐2GNDSAI‐1GNDSAI‐0GNDDI‐1GNDDI‐0IOmoToDoorSensor 1KΩ2KΩConnectionsonINsideDC–Power12to24VIfPOEisnotusedDC–Power12to24VIfPOEisnotused1Power‐OUTSAI‐1‐GND92Power‐GNDSAI‐183RS485‐ASAI‐0‐GND74RS485‐BSAI‐065RS485‐GNDRelay‐NO 56DORelay‐NC47DOGndRelay‐C38SAI‐2Power‐GND29SAI‐2‐GNDPower‐IN1Frame‐GNDJ10PINPINJ9101Power‐OUTSAI‐1‐GND92Power‐GNDSAI‐183RS485‐ASAI‐0‐GND74RS485‐BSAI‐065RS485‐GNDRelay‐NO 56DORelay‐NC47DOGndRelay‐C38SAI‐2Power‐GND29SAI‐2‐GNDPower‐IN1Frame‐GNDJ10PINPINJ910FGNDPo wer – Min. 1 8 AWGPo wer Gnd  – Min. 18 AWGCAT5Sig nal/Power – Min. 18 AWGSig n al – Min . 18 AWGSig n al – Min . 18 AWGCo mm. – Min. 18 AWGCo mm. – Min. 18 AWGCo mm. – Min. 18 AWGPo wer – Mi n. 18 AWGPo wer Gnd  – Min. 18 AWGCo mm. – Min . 18 AWGLEGENDCo mm. – Min . 18 AWGS1Note: For Dual Reader setup the Door Sensor (Connection to IN Reader) is always connected to SAI3. * This drawing continues on the opposite page Fig.20. Two readers with IOM (S1 DIP switch settings shown)
Honeywell IdentIPoint Intelligent Smartcard Readers  EthernetIdentIPointRead erToLANRL1‐CN.ON.CRLO‐CN.ON.C485‐A485‐B485‐GNDILK‐1GNDILK‐0GNDD1‐0GNDDO‐0GNDRL1‐CN.ON.CRLO‐CN.ON.C485‐A485‐B485‐GNDILK‐1GNDILK‐0GNDD1‐0GNDDO‐0GNDoduleConnectionsonOUTside1Power‐OUTSAI‐1‐GND92Power‐GNDSAI‐183RS485‐ASAI‐0‐GND74RS485‐BSAI‐065RS485‐GNDRelay‐NO 56DORelay‐NC47DOGndRelay‐C38SAI‐2Power‐GND29SAI‐2‐GNDPower‐IN1Frame‐GNDJ10PINPINJ9101Power‐OUTSAI‐1‐GND92Power‐GNDSAI‐183RS485‐ASAI‐0‐GND74RS485‐BSAI‐065RS485‐GNDRelay‐NO 56DORelay‐NC47DOGndRelay‐C38SAI‐2Power‐GND29SAI‐2‐GNDPower‐IN1Frame‐GNDJ10PINPINJ9102KΩ2KΩ1KΩ1KΩToEMLDoorLockS1S1 95-7771 23
Honeywell IdentIPoint Intelligent Smartcard Readers     DC–Power12to24VIfPOEisnotusedRL1‐CN.OGNDN.C12VRLO‐CGNDN.OSAON.CGND485‐ASAI‐3485‐BGND485‐GNDSAI‐2ILK‐1GNDGNDSAI‐1ILK‐0GNDGNDSAI‐0D1‐0GNDGNDDI‐1DO‐0GNDGNDDI‐0RL1‐CN.OGNDN.C12VRLO‐CGNDN.OSAON.CGND485‐ASAI‐3485‐BGND485‐GNDSAI‐2ILK‐1GNDGNDSAI‐1ILK‐0GNDGNDSAI‐0D1‐0GNDGNDDI‐1DO‐0GNDGNDDI‐0IOmoduleRL1‐CN.OGNDN.C12VRLO‐CGNDN.OSAON.CGND485‐ASAI‐3485‐BGND485‐GNDSAI‐2ILK‐1GNDGNDSAI‐1ILK‐0GNDGNDSAI‐0D1‐0GNDGNDDI‐1DO‐0GNDGNDDI‐0RL1‐CN.OGNDN.C12VRLO‐CGNDN.OSAON.CGND485‐ASAI‐3485‐BGND485‐GNDSAI‐2ILK‐1GNDGNDSAI‐1ILK‐0GNDGNDSAI‐0D1‐0GNDGNDDI‐1DO‐0GNDGNDDI‐0IOmoduleRL1‐CN.OGNDN.C12VRLO‐CGNDN.OSAON.CGND485‐ASAI‐3485‐BGND485‐GNDSAI‐2ILK‐1GNDGNDSAI‐1ILK‐0GNDGNDSAI‐0D1‐0GNDGNDDI‐1DO‐0GNDGNDDI‐0RL1‐CN.OGNDN.C12VRLO‐CGNDN.OSAON.CGND485‐ASAI‐3485‐BGND485‐GNDSAI‐2ILK‐1GNDGNDSAI‐1ILK‐0GNDGNDSAI‐0D1‐0GNDGNDDI‐1DO‐0GNDGNDDI‐0IOmoduleDC–Power12to24VDC–Power12to24VDC–Power12to24VIOM 1 IOM 2 IOM 31Power‐OUTSAI‐1‐GND92Power‐GNDSAI‐183RS485‐ASAI‐0‐GND74RS485‐BSAI‐065RS485‐GNDRelay‐NO56DORelay‐NC47DOGndRelay‐C38SAI‐2Power‐GND29SAI‐2‐GNDPower‐IN110Frame‐GNDJ9PINPINJ10EthernetBOTACreaderS11234OFFON1Power‐OUTSAI‐1‐GND92Power‐GNDSAI‐183RS485‐ASAI‐0‐GND74RS485‐BSAI‐065RS485‐GNDRelay‐NO56DORelay‐NC47DOGndRelay‐C38SAI‐2Power‐GND29SAI‐2‐GNDPower‐IN110Frame‐GNDJ9PINPINJ10EthernetBOTACreaderS11234OFFONIdentIPoint Reader1Power‐OUTSAI‐1‐GND92Power‐GNDSAI‐183RS485‐ASAI‐0‐GND74RS485‐BSAI‐065RS485‐GNDRelay‐NO 56DORelay‐NC47DOGndRelay‐C38SAI‐2Power‐GND29SAI‐2‐GNDPower‐IN1Frame‐GNDJ10J9 PIN PIN10FGND FGND FGNDPo wer – Min . 18 AW GPower Gnd –Min. 18 AWGComm. – Min. 18 AWGComm. – Min. 18 AWGComm. – Min. 18 AWGLEGENDS1S1 S1 S1Fig.21. Reader with three IOMs on a RS485 bus (S1 DIP switch settings shown) 95-7771  24
Honeywell IdentIPoint Intelligent Smartcard Readers  95-7771 25  Power  – Min . 18 AWGPower Gnd –Min. 18 AWGLEGENDFig.23. IOM and strike latch Power – Min. 18 AWGPower Gn d – Min . 18 AWGLEGENDRL1‐CN.OGNDN.C12VRLO‐CGNDN.OSAON.CGND485‐ASAI‐3485‐BGND485‐GNDSAI‐2ILK‐1GNDGNDSAI‐1ILK‐0GNDGNDSAI‐0D1‐0GNDGNDDI‐1DO‐0GNDGNDDI‐0IOmodule StrikeLatchDC–Power12VDC/24VDCFGNDFig.22. Reader and strike latchStrikeLatchEth er netIdentIPointReaderS11234OFFON1Power‐OUTSAI‐1‐GND92Power‐GNDSAI‐183RS485‐ASAI‐0‐GND74RS485‐BSAI‐065RS485‐GNDRelay‐NO 56DORelay‐NC47DOGndRelay‐C38SAI‐2Power‐GND29SAI‐2‐GNDPower‐IN1Frame‐GNDJ10J9 PIN PINDC–Power12VDC/24VDC10S1
Honeywell IdentIPoint Intelligent Smartcard Readers                    Fig.24. Reader and magnetic lock Po wer – Min. 18 AW GPower Gn d – Min. 18 AWGLEGENDEthernetS11234OFFONMagneticLockIdentIPointReader1Power‐OUTSAI‐1‐GND92Power‐GNDSAI‐183RS485‐ASAI‐0‐GND74RS485‐BSAI‐065RS485‐GNDRelay‐NO 56DORelay‐NC47DOGndRelay‐C38SAI‐2Power‐GND29SAI‐2‐GNDPower‐IN1Frame‐GNDJ10J9 PIN PINDC–Power12VDC/24VDC10S1Fig.25. IOM and magnetic lock Po wer – Mi n. 18 AW GPower Gnd – Min. 18 AWGLEGENDRL1‐CN.OGNDN.C12VRLO‐CGNDN.OSAON.CGND485‐ASAI‐3485‐BGND485‐GNDSAI‐2ILK‐1GNDGNDSAI‐1ILK‐0GNDGNDSAI‐0D1‐0GNDGNDDI‐1DO‐0GNDGNDDI‐0DC–Power12VDC/24VDCFGNDIOmodule MagneticLock95-7771  26
Honeywell IdentIPoint Intelligent Smartcard Readers  95-7771 27 SAI-nSAI-n GND1KΩ2KΩSensor SwitchSAI-nSAI-n GND1KΩ2KΩSensor SwitchFig.26. Supervisory Analog InputsNote:Doorsenseisconsideredopenwhensensorswitchisopen 112233EACHDOORSTRIKEREQUIRESA14507020‐001DIODESUPPRESSIONNETWORK.DOORSTRIKEMAYDRAWAMAXIMUMCURRENTOF2A;REGULATED12/24VDC.DOORSTRIKEMUSTBEULLISTED.EXITSWITCH:WIRINGMUSTBECOMPLETEDWITHINTHEPROTECTEDAREAORNOTREADILYACCESSIBLEOUTSIDETHEPROTECTEDAREA.44ALLWIRINGMUSTCONFORMTOAPPLICABLELOCALCODES,ORDINANCES,ANDREGULATIONSDOORCONTACTSMUSTBEULLISTED.MAXIMUMWIRELENGTH500FT(152M).WIRETYPE18AWG(0.8SQMM),50OHM60mAMAXIMUM.55DONOTROUTECOMMUNICATIONWIRESWITHPOWERORLOCKINGDEVICES.NOTE:FORCOMMUNICATIONCIRCUITSANDOTHERAPPLICABLEWIRINGCIRCUITSWHEREWIRINGENTERSANDEXITSTHEBUILDING,REFERTOLIGHTNINGPROTECTORTABLEFORAPPROPRIATELIGHTNINGPROTECTORUSAGE.       
Honeywell IdentIPoint Intelligent Smartcard Readers RS485 COMMUNICATION AND TERMINATION SETTING Both IdentIPoint readers and IOMs are equipped with a termination circuit and do not need an external termination resistor. Setting the DIP switch 2 on S1 to ON introduces a termination resistor on the RS485 line. The units that sit physically on both ends of an RS485 bus should have their RS485 termination turned on. It is also recommended to turn on the pull-up and pull-down resistors in the IdentIPoint reader (master).            Termination OFFTermination ON Termination ONIOM (Slave 1)Termination OFFReader (Master)Termination ONPull-up ONPull-down ONIOM (Slave 2)Termination ONTermination OFFTermination ON Termination ONIOM (Slave 1)Termination OFFReader (Master)Termination ONPull-up ONPull-down ONIOM (Slave 2)Termination ONTermination OFFTermination ON Termination ONIOM (Slave 1)Termination OFFReader (Master)Termination ONPull-up ONPull-down ONIOM (Slave 2)Termination ONTermination ON Termination OFF Termination ONIOM (Slave 1)Termination OFFReader (Master)Termination ONPull-up ONPull-down ONIOM (Slave 2)Termination ONFig.27. DIP Switch S1 settings on reader and IOMs for RS485 termination95-7771  28
Honeywell IdentIPoint Intelligent Smartcard Readers IOM ADDRESS SET UP Each IOM should have its own address.  The address could range from 1 to 127.  Never use zero as IOM address as zero is reserved for the master device. Note: It is recommended not to attach more than 4 IOM units to the RS485 bus to maintain a reasonable signal/response time delay between the reader and IOMs. Hence IOM addresses must be from 1 to 4 only.                                            To work out the address, select a combination of bit locations on the DIP switch. Each bit has its own value representation. The RS485 address is obtained by adding all ON-bit values. E.g. Decimal value 37 will be obtained by turning ON bits 1, 3 and 6 which equivalents to 1+4+32.  NOTE: Please refer to IdentIPoint Hardware Installation Manual (doc. no. 95-7767) for more details on the following items:    Overall system architecture   Power supply installation   Detailed wiring descriptions for readers, IOM and peripheral devices  Power-over-Ethernet wiring         RS485 ID                                                                     +   1   +   2   +   4   +   8   +  16   +  32   +  64                RS485 ID                                                                                         +   1   +   2   +   4   +   8   +  16   +  32   +  64                 SUMallONbitvalues Neveruseaddresszero   SUMallONbitvalues Neveruseaddresszero  RS485 ID                                                                                         +   1   +   2   +   4   +   8   +  16   +  32   +  64                RS485 ID                                                                                        +   1   +   2   +   4   +   8   +  16   +  32   +  64                 SUMallONbitvalues Neveruseaddresszero   SUMallONbitvalues Neveruseaddresszero  Fig.28. IOM Address set up  95-7771 29
Honeywell IdentIPoint Intelligent Smartcard Readers CERTIFICATIONS  Readers  CE   C-tick    IP-65 (Basic Outdoor Version Only) United States   FCC 47 CFR Part 15, Subpart B, sections 107(a) & 109(a) Class B   Section 201 to Section 205, section 207, section 209, section 215c, section 247 and section 35c  European Union  EN 55022:2006; EN61000-3-2:2006  EN 61000-6-3:2007  EN 50130-4:1995+A1:1998+A2:2003  EN 50133-1:1997  EN 50133-2-1:2000  EN 50134-1:2000  EN 50134-3:2001  EN 60950-1:2001   EN 301 489-01 V1.6.1   EN 301 489-03 V1.4.1   EN 300 330-02 V1.3.1 IOM  CE  C-tick United States   FCC 47 CFR Part 15, Subpart B, sections 107(a) & 109(a) Class B   Section 201 to Section 202, section 207 European Union   EN 55022:2006EN 60950-1:2001 (CERTIFICATIONS ARE IN PROGRESS)      WARNING: Any Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.  This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:  This device may not cause harmful interference.  This device must accept any interference received, including interference that may cause undesired operation. 95-7771  30
Honeywell IdentIPoint Intelligent Smartcard Readers  Notice  This document contains Honeywell proprietary information. Information contained herein is to be used solely for the purpose submitted, and no part of this document or its contents shall be reproduced, published, or disclosed to a third party without the express permission of Honeywell International, Sarl.  While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a purpose and makes no express warranties except as may be stated in its written agreement with and for its customer.   In no event is Honeywell liable to anyone for any direct, special, or consequential damages.  The information and specifications in this document are subject to change without notice.  Copyright 2009 – Honeywell International, Sarl.   Honeywell Trademarks  Honeywell Enterprise Buildings IntegratorTM (EBI) and IdentIPointTM are U.S. registered trademarks of Honeywell, Inc.       Other Trademarks  Trademarks that appear in this document are used only to the benefit of the trademark owner, with no intention of trademark infringement.  Support and other contacts  For technical assistance, call your nearest Honeywell office.  Feedback  Honeywell appreciates your comments about this manual. Please visit us on the web at https://buildingsolutions.honeywell.com to post your comments.     95-7771 31
Honeywell IdentIPoint Intelligent Smartcard Readers www.honeywell.com/buildingsolutions    © 2009 Honeywell International Inc.  95-7771 10-09    Honeywell Building Solutions  North America: 1985 Douglas Drive North Golden Valley, MN 55422-3992 +1-800-345-6770, ext. 606  Europe, Middle East, Africa & India: Honeywell House Arlington Business Park Bracknell, United Kingdom RG12 1EB +44 (0)870 600 1659  North Asia: Zhang Jiang Hi-Tech Park No. 430 Li Bing Rd., Pudong New Area, Shanghai, 201203, China +86-21-2894-2000  South Asia Pacific: 2 Richardson Place Sydney NSW 2113 +612-9353-7000

Navigation menu