VisionPRO® 8000
Thermostats
INSTALLER SETUP AND
SYSTEM TEST POCKET GUIDE
INSTALLER SYSTEM TEST
The Installer Test is part of the Installer Setup Menu.
Enter the Installer System Test by entering the Installer
Setup and pressing t repeatedly until “Test” appears.
DONE
M24083
Use arrow to change test and system status as
required.
DONE
M24085
TEST NUMBER SYSTEM STATUS
Press DONE to exit.
1.
2.
3.
SYSTEM TESTS
Test the system’s heating, cooling, fan and emergency heat.
Available tests vary by thermostat and system type.
Table 2. Installer System Test
System Test
Number
Test Type System Status Number
and Description
Test 1 Cooling System
Test
0 Off
1 Compressor and
fan on
2 Second stage
compressor on
Test 2 Fan System
Test
0 Off
1 Fan on
Test 3 Heating System
Test
0 Off
1 Heat on
2 Second stage heat
(Aux. heat) on
3 Third stage heat
(Auxiliary heat) on
Test 4 Emergency
Heat Test
0 Off
1 Em. Heat and fan on
2 Auxiliary heat on
Press the DONE button to exit the Installer System Test.
caution
EQUIPMENT DAMAGE HAZARD.
Compressor protection is bypassed during testing. To
prevent equipment damage, avoid cycling the compres-
sor quickly.
Table 1. Installer Setup
Setup functions Setting & Options (factory
default in bold)
0520 U/V lamp change
reminder
0 Off
1 365 calendar days
0530 Adaptive Intel-
ligent RecoveryTM
1 On
0 Off
0540 Program periods 4 4 periods (Wake,
Leave, Return, Sleep)
2 2 periods (Wake, Sleep)
0580 Compressor
protection
5 5-minute compressor
off time
[Other options: 0–4
minutes]
0600 Heat temperature
range stop
90 Max. heat temperature
setting is 90°F (32°C)
[Other options: 40-89°F
(4°C to 32°C)]
0610 Cool temperature
range stop
50 Min. cool temperature
setting is 50°F (10°C)
[Other options: 51-99°F
(11°C to 37°C)]
0640 Clock format 12 12-hour time
24 24-hour time
0650 Extended fan
timer (heat)
0 Off
90 Fan runs for 90 seconds
after call for heat ends
0660 Extended fan
timer (cool)
0 Off
90 Fan runs for 90 seconds
after call for cooling ends
0670 Keypad Lockout 0 Unlocked
1 Partially locked
2 Fully locked
Table 1. Installer Setup
Setup functions Setting & Options (factory
default in bold)
0680 Heat temperature
control
2 Standard temperature
control (recommended)
1 Select if inside tempera-
ture is consistently over
setting
3 Select if inside tempera-
ture is consistently under
setting
0690 Cool temperature
control
2 Standard temperature
control (recommended)
1 Select if inside tempera-
ture is consistently over
setting
3 Select if inside tempera-
ture is consistently under
setting
0700 Temperature
display offset
0 No offset
[Other options: -3, -2,
-1, 1, 2, 3°F (-1.5°C to
1.5°C)]
0710 RESET 0 No reset
1 Reset installer options
& program schedule to
factory default
69-1871-1
INSTALLER SETUP
Press SYSTEM.
SCHED HOLD
FAN
ON
AUTO
AM
SYSTEM
HEAT
Inside
M24079
1.
2345
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
http://yourhome.honeywell.com
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
® U.S. Registered Trademark
© 2006 Honeywell International Inc.
US Patent No. 6595430, D509151; other
Patents Pending. All Rights Reserved
69-1871-1 M.S. Rev. 09-06
Press and hold these two blank buttons until the
display changes.
DONE CANCEL
SYSTEM
HEAT
M24080
Use arrows to change settings as required.
DONE
FUNCTION SETTING
M24082
Press DONE to exit and save settings.
INSTALLER SETUP FUNCTIONS
Available option and default settings vary by thermostat.
Table 1. Installer Setup
Setup functions Setting & Options (factory
default in bold)
0120 Year (rst two
digits)
20 (2000-2099)
21 (2100-2178)
0130 Year (second two
digits)
06 (2006) [Other options 0-99]
0140 Month 6 [Other options 1-12]
0150 Day 15 [Other options 1-31]
0160 Schedule format 4 7-day programming
0 Non-programmable
2.
3.
4.
Table 1. Installer Setup
Setup functions Setting & Options (factory
default in bold)
0170 System type 1 1 heat / 1 cool Conv.
2 1 heat / 1 cool heat
pump (no Aux. heat)
3 Heat only (2 wire)
4 Heat only with fan
5 Hot water Series 20
6 Cool only
7 2 heat / 1 cool heat
pump (with Aux. heat)
8 2 heat / 2 cool multistage
9 2 heat / 1 cool multistage
10 1 heat / 2 cool multistage
11 2 heat / 2 cool heat pump
(no Aux. heat)
12 3 heat / 2 cool heat
pump (with Aux. heat)
0180 Fan control
(heating)
0 Gas/Oil heat (equipment
controls heating fan)
1 Electric furnace (thermo-
stat controls heating fan)
0190 Changeover valve
(O/B terminal)
0 Controls valve in cooling
1 Controls valve in heating
0200 Auxiliary heat 0 Electric backup heat
1 Fossil fuel backup heat
0210 External fossil
fuel kit
1 External fossil fuel kit
controls backup heat
0 Thermostat controls
backup heat (outdoor
sensor required)
0220 First stage
compressor cycle
rate
3 Recommended
[Other options: 1–6]
0230 Second stage
compressor cycle
rate
3 Recommended
[Other options: 1–6]
Table 1. Installer Setup
Setup functions Setting & Options (factory
default in bold)
0240 First stage heat
cycle rate
5 Gas or oil furnaces of
less than 90%
efciency
1 Steam or gravity
3 Hot water systems or fur-
naces of 90%+ efciency
9 Electric furnaces
[Other options: 1–12]
0250 Second stage
heat cycle rate
5 Gas or oil furnaces of
less than 90% efciency
1 Steam or gravity
3 Hot water systems or fur-
naces of 90%+ efciency
9 Electric furnaces
[Other options: 1–12]
0260 Third stage heat
cycle rate
9 Electric auxiliary heat
or electric furnaces
1 Steam or gravity
3 Hot water systems or fur-
naces of 90%+ efciency
5 Gas or oil furnaces of
less than 90% efciency
[Other options: 1–12]
0270 Emergency heat
cycle rate
9 Electric auxiliary heat
or electric furnaces
1 Steam or gravity
3 Hot water systems or fur-
naces of 90%+ efciency
5 Gas or oil furnaces of
less than 90% efciency
[Other options: 1–12]
0280 Backlight 0 Backlight on keypress
1 Continuous backlight (re-
quires 24VAC connection)
0300 Manual/auto
changeover
0 Manual changeover
(Heat/Cool/Off)
1 Automatic changeover
(Heat/Cool/Auto/Off)
Table 1. Installer Setup
Setup functions Setting & Options (factory
default in bold)
0310 Auto changeover
deadband
3 Heat/cool tempera-
ture 3°F apart (1.5°C)
[Other options: 2-9 (2°F-
9°F/1°C-5°C)]
0320 Temperature
display
0 Fahrenheit
1 Celsius
0330 Daylight savings 1 Auto-change to daylight
savings time (through
2006)
2 Auto-change to daylight
savings time (2007 and
beyond)
0 Daylight savings time is
turned off
0340 Remote sensor 0 No remote sensor
1 Outdoor sensor (display
only)
2 Outdoor sensor for con-
trol (select heat pumps)
3 Indoor sensor
0350 Heat pump com-
pressor lockout
0 Off
[Other options: 15, 20,
25, 30, 35, 40°F (-9.5°C
to 7°C)]
0360 Heat pump auxil-
iary lockout
0 Off
[Other options: 40, 45,
50, 55, 60°F (4.5°C to
15.5°C)]
0380 Dehumidication
Control
0 Off
1 A/C runs to help
dehumidify
0500 Furnace lter
change reminder
0 Off
1 10-day run time
(about 1 month)
2 30-day run time
(about 3 months)
3 60-day run time
(about 6 months)
4 90-day run time
(about 9 months)
5 120-day run time
(about 1 year)
6 365-day run time
(about 3 years)
0510 Humidier pad
change reminder
0 Off
1 90 calendar days
2 180 calendar days
3 365 calendar days