T6380 Series
Electronic Fan Coil Thermostats
PRODUCT DATA

FEATURES
• 	 Electronic temperature sensing provides energy­
efficient, precision operation for maximum comfort.

•	
•	
•	
•	
•	

APPLICATION
The T6380 series of electronic fan coil thermostats provide
precision line voltage control of fan-forced Heating, Ventilat­
ing and Air Conditioning equipment. Models are available for
cooling-only, manual heat-cool changeover, or remote heat­
cool changeover systems. Hydronic source heat-cool
systems may be two or four-pipe configuration with 0, 1, or 2
valves. Fan control options include constant, cycled, or user­
selectable "On-Auto" operation. Manual fan speed selection
is standard. All models feature an “Off” switch.

Contemporary white sculpted styling.
Vertical or horizontal mounting configurations.
Adjustment ranges 55° to 90°F or 13° to 32°C.
Easy-to-use set point knob.
LED system status indicator. "OFF" de-energizes all
connected loads.

•	
•	

Three level fan speed selection.

•	

Models for manual or remote heat-cool changeover,
heating-only, or cooling-only systems.

•	
•	

Models for 2 or 4-pipe systems.

•	
•	

Screw terminal block connections.

•	
•	

Range stops and cover locking kit available.

Constant, cycled, or on-auto selectable fan operation
available.

Rugged molded thermoplastic housing with captive
mounting screws, mounts on single-gang NEMA­
standard (U.S.) electrical box.

Suitable for inductive-rated loads such as valves,
relays, contactors and fans.

UL Listed. CSA Certified.

Contents
Specifications .................................................................. 2

Ordering Information ....................................................... 2

Installation ....................................................................... 3

Wiring .............................................................................. 3

Operations .................................................................... 5

Check-out ..................................................................... 5


M.O'D. 8/98 © Honeywell Ltd.—Honeywell Ltée. 1998 Printed in Canada Form Number 95C-10758

T6380 - SPECIFICATIONS, ORDERING INFORMATION


SPECIFICATIONS
MODELS:

Operating range:
32 	to + 104 F [0 to +40 C], 5 to 95% RH, non-condensing.

3-Speed Fan Operation

Fan Coil System

Constant

Cycled

On-Auto

T6383A
Fig. 2a

T6381A
Fig. 5a

T6387A
Fig. 8a

T6383A
Fig. 2b

T6381A
Fig. 5b

T6387A
Fig. 8a

T6383B
Fig. 3
T6383A
Fig. 2c

T6381B
Fig. 6
T6381A
Fig. 5c

N/A

T6383B
Fig. 4b

T6381B
Fig. 7b

N/A

T6383B
Fig. 4a

T6381B
Fig. 7a

N/A

2-pipe System
• 	Cooling only
• 	Heating only
2-pipe Heat-Cool
• 	Manual Change/Over
• 	Seasonal, auto C/O
• 	Seasonal, auto C/O
with aux. electric heat
4-pipe Heat-Cool
• 	Manual C/O

Performance Specifications:
Precision: ±1°F temperature swing [0.9°C differential].
Accuracy: 2°F [1°C] droop with 4 A load.
Dimensions:
See Fig. 1 - Nominal Dimensions.
Mounting:
Direct mounting on single-gang NEMA 2" x 3" flush-mount
or 2" x 4" surface-mount electrical box, or on 4" x 4" box
Models available for vertical or horizontal mount.

T6387A
Fig. 8c

Wiring Connections:
Screw terminal block suitable for 1 – 14 AWG, 2 – 18 AWG,
or 1 – 1.5 mm2 copper wire.
Approvals:
CSA Certified LR1322

Underwriters Laboratories Listed E47434.


Electrical Ratings:
T6380 Series - Power Supply: 110-130 or 208-277 Vac
+10/-15%, 50-60 Hz.
T6381, T6387 - Output Rating, cycled (“Auto”) fan control
50-60 Hz
Full Load Amps*
Locked Rotor
Pilot Duty
*	

120 V
3.8
22.8

208 V
2.1
12.6
125 VA

230 V
1.9
11.4

Accessories:
272824A-T6380 Range stop/cover locking kit.
272827A-T6380 replacement cover with Cool-Warmer

277 V
1.6
9.5

Fig. 1 — Nominal dimensions in inches and
millimetres

Equivalent to NEMA 1/8 horsepower rating for a hermetically-sealed
motor such as a compressor. Allowable connected load must be
determined by adding nameplate full load and locked rotor (inrush) ratings
of all loads.

T6383 – Output Rating, constant fan operation
Thermostat (Heat and Cool outputs):
50-60 Hz
Full Load Amps
Locked Rotor A
Pilot Duty
Resistive (heat only)

120 V
3.8
22.8
10.0 A

208 V
2.1
12.6
125 VA
N/A

230 V
1.9
11.4

277 V
1.6
9.5

N/A

5.6

220-240V
2.9
17.4

277 V
2.4
14.4

Fan (Air Handler):
50-60 Hz
Full Load Amps**
Locked Rotor

110-130V
5.8
34.8

208 V
3.2
19.2

**	 Equivalent to NEMA 1/4 horsepower rating for a hermetically-sealed
motor. Allowable load must be determined from fan nameplate
ratings .
† North American national electrical codes require all ungrounded

conductors to electric resistance heating to be broken at the thermostat

OFF setting. The 208V and 230V resistive ratings are not UL approved.

The 230V rating is site-approveable in Canada on 416V 4-wire Wye

distributed systems. The non-inductive rating for 230V “a.c. mains”

with one ungrounded conductor is 6.0A.


ORDERING INFORMATION
Before ordering please determine the following:
1. The body type: 2-way or 3-way
2. The actuator voltage : 24V/50-60Hz
3. The pipe fitting, size, and flow capacity rating (Cv) required.
4. Order Specification Number
5. Accessories, if desired.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (please check the white pages of your phone directory).
2. Honeywell Limited, 155 Gordon Baker Rd., North York, ON M2H 3N7.
In U.S.A. - Honeywell Inc., 1885 Douglas Drive North, Minneapolis, Minnesota 55422-4386 (612) 951-1000. International Sales and Service
Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain,
Taiwan, United Kingdom, U.S.A.

2


T6380 - INSTALLATION, WIRING


Fig. 2c – T6383A: 2-pipe, heat/cool, seasonal auto-changeover,
constant fan

INSTALLATION
MOUNTING:
Mount the thermostat on an inside wall 4’ to 5' [1.5 m] above
the floor. Do not mount where thermostat can be affected by
drafts, radiant heat from the sun, or other sources of heat.
T6380's mount on NEMA standard 2"x3" single gang flush or
2"x4" surface mount electrical box, or on 4"x4" box with mud
ring adaptor (not provided).

.

T6383A
FAN

AQUASTAT

W
Cool (YEL)

R

Heat (ORG)

TOHEAT/COOL
VALVE

B

2 (BLU) MED
1 (RED) LO

Off

WIRING


FAN

3(BRN) HI

1

(VIO)

3Internal schematic and external wiring connections are

shown in Fig. 2a through Fig. 8c. Wiring connections may be

made to the 8 position screw terminal block with 1- 14 AWG,

or 2- 18 AWG, solid or stranded copper wires.

BLK

WHT

L1(HOT)

L2
(NEUTRAL)


1

External jumper

Fig. 2a – T6383A for 2-pipe, constant fan, cooling only

T6383A
Fig. 3 – T6383B: 2-pipe, heat/cool, manual changeover, constant
fan

FAN

Heat (ORG)
3 (BRN)
2 (BLU)
1 (RED)

Off

TO COOLING
VALVE

T6383B
SYSTEM

External jumper

Cool (YEL)

HI
MED
LO

TOHEATING/
COOLING
VALVE

FAN

Cool (YEL)

Cool

(VIO)

External jumper

Heat (ORG)

Off
Heat

L1(HOT)

WHT

Hi (BRN)

HI
MED
LO

Med (BLU)

L2
(NEUTRAL)

Lo (RED)

BLK

To internal heat/cool
circuits

WHT

L1(HOT)

Fig. 2b – T6383A for 2-pipe, constant fan, heating only

FAN

FAN

BLK

L2(NEUTRAL)

T6383A
FAN
Cool (YEL)

1 (RED)

Off

(VIO)

HI
MED
LO

T6383B
SYSTEM
Cool (YEL)

TO COOLING
VALVE

External jumper
Cool

BLK

Heat (ORG)

Off
Heat

WHT

TO HEATING
VALVE

FAN
Hi (BRN)

L1(HOT)

L2
(NEUTRAL)

Med (BLU)
Lo (RED)

BLK
L1(HOT)

3


WHT
L2(NEUTRAL)

HI
MED
LO

FAN

3 (BRN)
2 (BLU)

TO HEATING
VALVE

FAN

Heat (ORG)

Fig. 4a – T6383B: 4-pipe, heat/cool, manual changeover,
constant fan

To internal heat/cool
circuits

T6380

Fig. 4b – T6383B: 2-pipe, heat/cool, auto changeover, with aux.
electric heat, constant fan

Fig. 5c – T6381A: 2-pipe, heat/cool, auto-changeover, cycled fan

.

W

AQUASTAT

T6381A

R
.

SYSTEM

W

TO HEAT/ COOL
VALVE

FAN

B

Cool (YEL)

R

Cool (YEL)

W
R
Cool

Heat (ORG)

Off
Heat

B

TO SUPPLEMENTARY
HEAT

B

3(BRN)

FAN

HI
MED
LO

2 (BLU)
HI
MED
LO

Med (BLU)
Lo (RED)

Off

FAN

Hi (BRN)

L1 (HOT)

Heat (ORG)

1 (RED)

WHT

FAN

T6383B

L2 (NEUTRAL)

(VIO)
BLK
L1(HOT)

To internal heat/cool
circuits

WHT

External jumper

L2(NEUTRAL)

TO HEATING
/COOLING VALVE

Fig. 6 – T6381B: 2-pipe, heat/cool, manual changeover, cycled
fan

Fig. 5a – T6381A: 2-pipe, cooling only, cycled fan

T6381A

T6381B

FAN

.

L1 (HOT)

Heat (ORG)
3(BRN)
2 (BLU)

TO HEATING/COOLING
VALVE

Cool

HI
MED
LO

1 (RED)

WHT

External jumper

Heat (ORG)

Off
Heat

FAN
(BRN)

HI
MED
LO

(BLU)

L2
(NEUTRAL)

(RED)

FAN

Off

Cool (YEL)

FAN

Cool (YEL)

SYSTEM

(VIO)

BLK

External jumper

BLK

WHT

L1(HOT)

L2(NEUTRAL)

TO COOLING
VALVE

Fig. 5b – T6381A: 2-pipe, heating only, cycled fan

Fig. 7a – T6381B: 4-pipe, heat/cool, manual changeover, cycled
fan

T6381A
T6381B
FAN

.

SYSTEM

Cool (YEL)

Cool (YEL)

Off

1 (RED)

WHT
BLK

HI
MED
LO

Cool
Off

TO HEATING
VALVE

FAN

L2
(NEUTRAL)

(BRN)
(BLU)

(VIO)

(RED)

BLK
L1(HOT)

4

Heat (ORG)

Heat

External jumper

TO HEATING
VALVE

TO COOLING
VALVE

WHT
L2(NEUTRAL)

HI
MED
LO

FAN

Heat (ORG)
3(BRN)
2 (BLU)

FAN

L1 (HOT)

T6380 - OPERATION

Fig. 7b – T6381B: 2-pipe, heat/cool, auto-changeover, cycled fan
with
aux. heat

Fig. 8c – T6387A: 2-pipe, heat/cool, auto-changeover, on–
auto fan

T6387A

.

W

SYSTEM

R

Cool (YEL)

W

.

SYSTEM

TO HEAT/ COOL
VALVE

B

Heat (ORG)

Off
Auto

Cool (YEL)

R

W

Heat (ORG)

Off
Heat

B
TO SUPPLEMENTARY
HEAT

(BRN)

(RED)

FAN

HI
MED
LO

Lo (RED)

(VIO)

FAN

Hi (BRN)

BLK
L1(HOT)

BLK

WHT

1

External jumper

L2(NEUTRAL)

To internal heat/cool
circuits

WHT

L1(HOT)

HI
MED
LO

(BLU)

B

Med (BLU)

TOHEAT/COOL

VALVE


FAN

R
Cool

AQUASTAT

On

FAN

T6381B

L2(NEUTRAL)

!

Fig. 8a – T6387A: 2-pipe, cooling only on–auto fan

T6387A

CAUTION
1. Disconnect power supply before connecting
wiring to prevent electrical shock and equipment
damage.
2. Never jumper the supply wires or actuator terminals
even temporarily. This may damage the thermostat.

SYSTEM
On

Cool (YEL)

Off
Auto

TO COOLING
VALVE

OPERATION

Heat (ORG)

As the temperature changes, the thermostat makes to
open a valve and/or power a blower to provide heating or
cooling. The speed at which the air is circulated is con­
trolled by the FAN switch. Continuous (ON) or intermittent
(AUTO) fan operation is determined by model number.

(BRN)

HI
MED
LO

(BLU)
(RED)

FAN

FAN

(VIO)

CHECK-OUT

External jumper

BLK

WHT

L1(HOT)

Turn power on. Check out operation according to the
SYSTEM switch present.
• SYSTEM switch OFF de-energizes valve and fan
circuits.
Models T6381B,: T6383B
• SYSTEM: HEAT - OFF - COOL
Set the SYSTEM switch to HEAT. Rotate the
thermostat knob clockwise to energize the heating
valve and/or fan (fan auto/cycled mode). The
system LED on the thermostat will light when the
heating circuit is energized.
Set the SYSTEM switch to COOL. Rotate the thermo
stat knob counter-clockwise to energize the cooling
valve and/or fan (fan auto/cycled mode). The
system LED on the thermostat will light.
Model T6387A
• SYSTEM: ON -AUTO - OFF
• Set the SYSTEM switch to ON. 	The valve will
operate on heating or cooling cycle depending on
whether hot or chilled water is being supplied. The
fan will run continuously.
Set the SYSTEM to AUTO. The fan will cycle with the
heating or cooling operation.

L2(NEUTRAL)

Fig. 8b – T6387A: 2-pipe, heating only on–auto fan

T6387A
SYSTEM
On

Cool (YEL)

Off
Auto

Heat (ORG)

TO HEATING
VALVE

(BRN)
(BLU)
(RED)

HI
MED
LO

FAN

FAN

(VIO)
External jumper

BLK
L1(HOT)

WHT
L2(NEUTRAL)

5

T6380

Models: T6381A; T6383A
• SYSTEM: HI-OFF-MED-LO
• Set the SYSTEM switch to HI. Rotate the thermostat
knob clockwise to energize the heating\cooling valve
and/or fan ( constant or cycled fan). The system
LED on the thermostat will light when the heating or
cooling circuit is energized.
SETTING:

The T6380 temperature scale is marked 55 to 90°F or 13 to

32°C, depending on the model. Set the dial indicator marker

to the desired temperature.

CALIBRATION:

T6380 thermostats are accurately calibrated at the factory

under controlled conditions. Do not attempt to field calibrate

this device.This thermostat has line voltage connections.


Home and Building Control
Honeywell Ltd.
155 Gordon Baker Road
North York, Ontario M2H 3N7
Printed in Canada

In U.S.A.
Honeywell Inc.
1985 Douglas Drive North
Golden Valley, MN 55422-3992

Helping You Control Your World



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Encryption                      : Standard V4.4 (128-bit)
User Access                     : Print, Copy, Extract, Assemble, Print high-res
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Producer                        : Acrobat Distiller 4.05 for Macintosh
Modify Date                     : 2007:05:08 11:53:22-05:00
Create Date                     : 2004:03:09 13:21:50Z
Creator Tool                    : PageMaker 6.0
Metadata Date                   : 2007:05:08 11:53:22-05:00
Document ID                     : uuid:c2e6a383-1609-48bc-8162-3c406cf3fab2
Instance ID                     : uuid:fd33899c-2585-4dc9-9d6f-ccd7533b7352
Format                          : application/pdf
Title                           : 95C-10758 - T6380 Series Electronic Fan Coil Thernostat
Creator                         : Honeywell ECC
Description                     : Product Data
Page Count                      : 6
Subject                         : Product Data
Author                          : Honeywell ECC
EXIF Metadata provided by EXIF.tools

Navigation menu