ANN-RLY Relay Module
Installation Instructions

Mounting in FACP Main Board Chassis
ANN-RLY module standoffs

The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compatible
FACP (Fire Alarm Control Panel). This document
is provided as a quick reference. For more detailed
information, refer to the appropriate FACP installation manual.
Note: Installation and wiring of this device must be
done in accordance with NFPA 72 and local
ordinances.

Specifications
Table 1: ANN-RLY Module Specifications
Operating Voltage
Max. Current @
24 VDC

24 VDC
Alarm

75 mA

Standby

15 mA

Operating Temperature

0o to 49o C
(32o to 120o F)

Max. Wiring Distance from
FACP (with 12 AWG wire)

1,250 ft.
(380 m)

Relay Contact Ratings

2 amps @ 30 VDC
(resistive)
0.5 amps @ 30 VAC
(resistive)

R1

R3

R5

(top)

R7 R9

R1

R3

R5

R2

R4

R6 (bottom) R8 R10

R7 R9

ground
wire

ANN-RLY module mounting hooks

1. Install the two supplied snap-in standoffs into the
backside of the ANN-RLY circuit board in
locations indicated in illustration above.
2. Using supplied hardware, attach the ground wire
using a screw and nut to location indicated in
illustration above. Be sure to position the ground
wire as shown to facilitate ANN-RLY installation.
3. Position the ANN-RLY module in the chassis so
that the two standoffs in the module are positioned over the wider portion of the mounting
holes in the chassis and the mounting hooks on
the module are sticking through the module
mounting slots in the bottom of the chassis.
4. Slide the ANN-RLY module to the right to lock
the module into place.
5. Attach the ground wire installed in step 2 to the
chassis in the location indicated below.
chassis

Indoor Use in Dry Location Only

Mounting
The ANN-RLY module may be mounted inside the
FACP main circuit board chassis or in the battery
area of the enclosure using mounting bracket P/N:
ANN-MBRLY. Refer to the following illustrations
for installation information.
Note:
1. ANN-RLY module can be installed without
removing the main circuit board or chassis.
2. ANN-MBRLY mounting bracket must be used
for the MS-9200UDLS.

ANN-RLY Module

Document # 53033 Rev. B

ANN-RLY module
mounting holes

ANN-RLY module
mounting slots

10/10/07

ECN 07-744

ground
wire

1

Mounting in FACP Main Board Chassis
Using the ANN-MBRLY bracket
1. Placing the ANN-MBRLY mounting bracket flat
against the inside back wall of the FACP
backbox, position both bracket mounting tabs
above the two embossed protrusions in the
backbox and slide the tabs down into the protrusions as illustrated below.

embossed
protrusion

tab

embossed
protrusion

tab

3. Install the ANN-RLY Relay Module on the
ANN-MBRLY mounting bracket by positioning
the four module mounting holes over the four
standoffs on the mounting bracket.
4. Install one of the four supplied mounting screws
and the supplied grounding strap in the top left
mounting hole of the ANN-RLY module as
illustrated below.
5. Secure the ANN-RLY module to the
ANN-MBRLY bracket with the remaining three
supplied mounting screws and tighten all mounting screws.
6. Attach the other end of the grounding strap to the
backbox grounding stud, securing it with a nut as
illustrated below.

ANN-MBRLY
Mounting Bracket

FACP Backbox

2. Secure the ANN-MBRLY mounting bracket to
the backbox by installing the supplied self-tapping
screw into the top embossed protrusion/tab as
illustrated below.

grounding stud

mounting screws

grounding strap
ANN-RLY Module
mounting screws

FACP Backbox
self-tapping
screw

embossed
protrusion

IMPORTANT! Only 7 AH or 18 AH batteries will
fit in the FACP backbox when the ANN-MBRLY
mounting bracket is installed. If 12 AH batteries
are to be used, they must be installed in an external
UL listed battery box such as the BB-17F.

FACP Backbox

2

ANN-RLY Module

Document # 53033 Rev. B

10/10/07

ECN 07-744

Wiring ANN-RLY Module to FACP

Setting DIP Switches

Refer to Table 2 and Figure 3 for wiring
connections.

Each ANN-BUS device requires a unique address.
ANN-RLY relay module DIP switch SW1 is used
to set the address for the annunciator.

ANN-RLY Terminals (TB1)

FACP ANN-BUS Terminals

Terminal 4 (-)

(-)

Terminal 3 (+)

(+)

Terminal 2 (A)

A (ANN-BUS)

Terminal 1 (B)

B (ANN-BUS)

Table 2: Wiring ANN-RLY Module to FACP

A maximum of 8 devices can be connected to the
FACP ANN-BUS communication circuit. ANNBUS device addresses do not need to be sequential
and can be set to any number between 01 and 08.
Note that 00 is not a valid address. The following
illustrates the DIP switch settings for each address
(ID Number):

ID Number
(Address)

C
NC
NO

DIP Switch SW1

(not valid) 00

C
NC
NO

01
02
03
ANN-RLY Relay Module

04

Figure 3: Wiring ANN-RLY Module to an FACP

Notes:

05

1. All connections/sources are to be power-limited
and supervised.
2. 12 - 18 AWG (0.75 - 3.25 mm2) wire for 24
VDC circuit is acceptable. Refer to the
appropriate FACP manual.
3. Power wire distance limitation is set by 1.2 volt
maximum line drop from source to end of
circuit.
4. Maximum distance from FACP to last ANNBUS device must not exceed 1,250 feet
(380 m). Refer to Wiring Distance Table in
appropriate FACP manual for wire gauge and
distance limitations.
5. Common, Normally Closed and Normally Open
terminals for each relay follow the same
pattern as illustrated above.

06

ANN-RLY Module

Document # 53033 Rev. B

07
08

One Fire-Lite Place
Northford, CT 06472
USA TEL: (203) 484-7161
www.firelite.com
© 2006 Fire-Lite Alarms P/N: 53033

10/10/07

ECN 07-744

3



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Encryption                      : Standard V2.3 (128-bit)
User Access                     : Print, Extract, Print high-res
XMP Toolkit                     : 3.1-702
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Creator Tool                    : PageMaker 7.0
Modify Date                     : 2007:12:03 08:06:37-05:00
Create Date                     : 2007:10:10 09:45:13-04:00
Metadata Date                   : 2007:12:03 08:06:37-05:00
Format                          : application/pdf
Title                           : 53033-B0.pmd
Creator                         : E651696
Document ID                     : uuid:41100d87-0c73-4faa-8376-5953c8ad0a8c
Instance ID                     : uuid:8b3c2611-12f9-468d-bcb6-bbd209ec6df7
Page Count                      : 3
Author                          : E651696
EXIF Metadata provided by EXIF.tools

Navigation menu