Centrale
Controller

Manuel de l’utilisateur

301C
User Manual
M-510324
7/10

Controller Unit

301C
User Manual
M-510324
7/10

Notices and Trademarks
Copyright by Honeywell International Inc.
July 2010
While this information is presented in good faith and believed to be accurate,
Honeywell disclaims the implied warranties of merchantability for a particular
purpose and makes no express warranties except as may be stated in its
written agreement with and for its customers.
In no event is Honeywell liable to anyone for any indirect, special or
consequential damages. The information and specifications in this document
are subject to change without notice.
This manual covers software version 3.086.

Honeywell Analytics
405 Barclay Boulevard
Lincolnshire, Illinois 60069

M-510324
7/10

301C User Manual
Honeywell

iii

Symbol Definitions
The following table lists the symbols used in this document to denote
certain conditions:

Symbol

Definition
ATTENTION: Identifies information that requires
special consideration
TIP: Identifies advice or hints for the user, often
in terms of performing a task
REFERENCE _ INTERNAL: Identifies an
additional source of information within the
bookset.

CAUTION

Indicates a situation which, if not avoided, may
result in equipment or work (data) on the system
being damaged or lost, or may result in the
inability to properly operate the process.
CAUTION: Indicates a potentially hazardous
situation which, if not avoided, may result in minor
or moderate injury. It may also be used to alert
against unsafe practices.
CAUTION: Symbol on the equipment refers the
user to the product manual for additional
information. The symbol appears next to required
information in the manual.
WARNING: Indicates a potentially hazardous
situation which, if not avoided, could result in
serious injury or death.
WARNING symbol on the equipment refers the
user to the product manual for additional
information. The symbol appears next to required
information in the manual.

M-510324
7/10

301C User Manual
Honeywell

v

INTRODUCTION ............................................................11
Intended Use ......................................................................................... 11
Receiving and Unpacking ...................................................................... 11

Installation Instructions ...................................................................... 12
Basic Guidelines .................................................................................... 12
Surface Mount Installation..................................................................... 13

Wiring Details .................................................................................... 14
Power Connections ........................................................................... 16
Communication Connections ............................................................ 16
Settings for Specific Transmitters ...................................................... 16
Relay Output ..................................................................................... 17
Jumper Use Instructions ........................................................................ 18

GETTING STARTED ......................................................19
Initial Startup ......................................................................................... 19
Datalogger (SDcard) ............................................................................. 19

Programming Interface...................................................................... 20
Keypad Functions .................................................................................. 20
LED Definitions ...................................................................................... 21
System Operation .................................................................................. 21

SYSTEM PROGRAMMING ............................................22
Tx Info Menu ..................................................................................... 25
Ident Menu ............................................................................................ 26

Product and Sensor Types ..................................................... 27
COM Menu ............................................................................................ 29
Scale Menus (1 and 2) .......................................................................... 30
Detection Menu ..................................................................................... 31
Display Menu ......................................................................................... 32
Alarm A, B and C Menus ....................................................................... 33
Servicing and Operating Menus ............................................................ 34
Status Code ........................................................................................... 35
Erase Current Tx ................................................................................... 35
Change Tx Address ............................................................................... 36

Groups Menu ..................................................................................... 37
Creating Groups .................................................................................... 38
Deleting Groups .................................................................................... 39
M-510324
7/10

301C User Manual
Honeywell

vii

Event Menu .......................................................................................40
Action Menu ...........................................................................................42
Delays Menu .......................................................................................... 43

Latch Mode ............................................................................. 44
Conditions ..............................................................................................45
Status .....................................................................................................49
Database................................................................................................ 49

Acquisition Menu ...............................................................................50
Starting and Stopping Tx Logging ..........................................51
Starting and Stopping Event Logging .....................................52
Copy Menu ........................................................................................53
Configuration .....................................................................................53
Parameters ............................................................................................54
System Log Menu ..................................................................................55

Config Menu ......................................................................................56
Network Menu ...................................................................................61
Remote Calibration ................................................................................63

Tests Menu ........................................................................................65
Test Sequence .......................................................................................67
Normal Mode .........................................................................................69
Single Tx Mode ......................................................................................69
Debug Mode ..........................................................................................69
Simulation Mode ....................................................................................70
Bacnet Menu ..........................................................................................72

Changing BACNet values .......................................................75
Wireless Network Menu .....................................................................77
Parameters Menu ..................................................................................78

Changing PAN ID or RF Channel ...........................................80
Diagnostics Menu ..................................................................................82
Nodes Menu ...........................................................................................83
New Node Menu ....................................................................................87
Hibernate Menu .....................................................................................88
Reset Network Menu .............................................................................88
Status Log Menu ....................................................................................89
Consolidate Route Menu .......................................................................89

BACnet/IP MODULE .........................................................................91
Specifications .........................................................................................91
BACnet Objects .....................................................................................91

Analog Input ...........................................................................92
viii

301C User Manual
Honeywell

M-510324
7/10

Analog Value .......................................................................... 92
Binary Input ............................................................................ 92
Binary Output ......................................................................... 93
Binary Value ........................................................................... 93
Device .................................................................................... 93
Object Names ......................................................................... 94
Protocol Implementation Conformance Statement ............................ 99
BACnet Protocol Implementation Conformance Statement .................. 99

Specifications .................................................................................. 105

LIMITED WARRANTY .................................................107
Limited Warranty ................................................................................. 107
Re-Stocking Policy .............................................................................. 107
Exclusions ........................................................................................... 108
Warranty Limitation and Exclusion ..................................................... 108
Disclaimer of Unstated Warranties ...................................................... 109
Limitation of Liability ............................................................................ 109

M-510324
7/10

301C User Manual
Honeywell

ix

Introduction

Introduction
The 301C controllers act as nerve centers for gas detection networks,
providing continuous monitoring for up to 96 connected units (plus 1
301ADI). Since the controllers are factory programmed to the owner’s
specifications, installation is limited simply to mounting and connecting
them. Once installed and connected, the controllers allow the user to
monitor, adjust, or reconfigure an entire network of units.
The 301C has a supplementary option of the wireless coordinator that
enables this controller to communicate with and manage up to 25
wireless gas detection devices in addition to its regular capabilities.

Intended Use
The controller is intended to monitor an entire gas detection network
around the clock. The unit offers logging capabilities, creating log files
of all transmitter concentrations and alarms for analysis. The unit is
also equipped with grouping or zoning capabilities that allow users to
query and monitor specific groups of transmitters or specific transmitter
zones.

Receiving and Unpacking
Upon receiving the controller unit:
•
•
•

Check that the package is undamaged
Carefully open the package.
Locate the packing slip or purchase order and verify that all items
on the order are present and undamaged

Note: If the package or any of its contents are damaged, please refer to
the Warranty section at the back of the manual for instructions.

M-510324
7/10

301C User Manual
Honeywell

11

Introduction
Installation Instructions

Installation Instructions
Basic Guidelines
Follow these instructions to the letter to ensure that the equipment will
function properly. Failure to respect these guidelines will release
Honeywell Analytics from any responsibility in the event of improper
functioning:
•
•
•
•
•

12

Locate all units in areas easily accessible for service.
Avoid locations where instruments are subject to vibrations
Avoid locating units near sources of electromagnetic interference
Avoid locating units in areas subject to significant temperature
swings
Verify local requirements and existing codes that may impact
choice of location.

301C User Manual
Honeywell

M-510324
7/10

Introduction
Installation Instructions

Surface Mount Installation
It is recommended that controllers be installed 5 feet (1.5 m) above the
floor, at approximate eye level.
Ø .5cm
¼”

17.4 cm
6 13/32”

26.8 cm
10 9/16”

1.5m
5’

Mark the holes as shown:
•
•
•
•

Height markers 6 13/32” apart
Width markers 10 9/16” apart
Pre-drill 1/4” mounting holes as needed
Securely mount the 301C using the appropriate screws

Wiring for the unit must be passed through the knock-outs provided at
the bottom of the unit.

M-510324
7/10

301C User Manual
Honeywell

13

Introduction
Wiring Details

Wiring Details
The diagram below provides the details required to connect the 301C
with the wireless communication module (coordinator). This module
allows the controller to communicate with and manage the 301W
wireless gas detectors.
Details concerning power supply, cables, capacities, etc., are provided
in the Specifications section at the back of this manual.
9XOFDLQ,QF
9$&:35% 
0DGHLQ&DQDGD

.
/

-

-

SD Card

-

1& 12

Wireless
communication module
/('

-3
5(6(7

5(/$<

'

'

-

5(/$<

.

-

12

-

/('

$/$50B$

/('

6,/(1&(

%=

/

6:

$/$50B%
/('

LCD screen

-
5
/('
5

5

-

5&

$/$50B&
/('

End-of-line jumper
position
/('

/('

-

-

)$8/7
/('

5,*+7 0$'(,1&$1$'$

6:

6:

6:

(6&

5

6:

&

(2/

5

-

5&

(7+(51(702'8/(

'2:1

5&

5

9RXW

(2/

(2/

9LQ

5&

5&

5(/$<

3&%&:5$
/()7

5(/$<

5(6(7

-

-

.

.

/('

6:

-



(2/

6+'1

32:(5

(17(5

83

6:

End-of-line specification:
The E.O.L. jumper for
channels 1-2-3-4 must
always be in E.O.L.
position.

7;
/('

5;

/('

5 -

-

-

-

9 9 9 9

-

$ % $ %

6+,(/'

6+,(/'

B4
Channel 4 (not used)
A4

A 2 Channel 2
B1
Channel 1
A1
VNEXT
V+

12

$ % $ %

B2

V+
PREVIOUS
V-

B3
A 3 Channel 3

6

Grounding screw

4

5

Always respect minimum
voltage requirements at device
RISK OF ELECTRIC SHOCK

1&

12

1&

RELAY OUTPUTS
2

3

Normally
open

3+5
4+6

Normally
1 closed

1+3
2+4

RISK OF ELECTRIC SHOCK

COMMUNICATION

BacNet/IP MODULE (-BIP option)

Communication Wire Gauge:
2-24 AWG (Belden 9841)
Twisted and shielded cable
2000 feet (600 m) per channel
T-tap: 65 feet (20 m) / T-tap
130 feet (40 m) total

Wireless Communication:
ISM worldwide
Indoor range 30m

Ethernet: 10/100-compatible with 10Base-T
interface, RJ-45
Visual Indicators:
Green LED LINK
Yellow LED ACT

Channel Specifications:
Channel 1-2: Modbus,Vulbus protocol
Channel 3: Modbus protocol only
Communicates only with Vulcain
transmitters
Channel 4: Modbus output
Communicates only with VA301BDCM

14

301C User Manual
Honeywell

M-510324
7/10

Introduction
Wiring Details

The connectors, or ports, on the PCB allow various wiring to be
connected to the controller. The wiring includes power, communication,
BACNet and relays, each with an assigned position (and number) on
the board:
J22 Power Input:

Connect the power supply to the controller
(see Wiring Details for cabling diagrams)
J23, J24 Communication
inputs:
Connect communication cables to channels 1
through 3.
Relay Outputs 1-4:
Depending on the desired configuration,
connect the relay cables to either N.O. or N.C.
SHDN jumper
Place the jumper over the Shutdown header
pins to reset or restart the system.
EOL Resistors 1-4:
Place the jumper over the header pins to
create the connection to attenuate
communication echoes.

M-510324
7/10

301C User Manual
Honeywell

15

Introduction
Power Connections

Power Connections
The 301C requires a power range of 17-27 Vac, 50/60 Hz (8.64 VA),
18-36 Vdc, 350 mA @24 Vdc (8.4 VA). Polarization is not important in
either AC or DC mode. The system must be grounded on the
transformer and a dedicated circuit breaker must be used.

Communication Connections
Communication cables must be grounded using the shield terminal,
using twisted and shielded pair Belden 2-24 AWG #9841 cable (or
equivalent).
The network cabling can extend up to a limit of 2000 feet (609 m) per
channel.
The length of a T-tap can reach 65 feet (20 m), up to a maximum of 130
feet (40 m) for all T-taps.
All wireless devices associated to the controller will automatically be
detected and communicate with the controller using wireless
communication protocols.

Settings for Specific Transmitters
Honeywell Sensepoint XCD Transmitters must be configured for 9600
baud, no parity, and a unique address. Honeywell XNX Universal
Transmitters must be configured for 9600 baud and a unique address.
Information on configuring each transmitter is in the associated
technical manual.

16

301C User Manual
Honeywell

M-510324
7/10

Introduction
Relay Output

Relay Output
The relay output can withstand up to 5A at 30Vdc or 250Vac (resistive
load only). Relays can be used to activate horns and strobes. Although
each relay is programmed with a default setting (below), they can be
configured using the controller programming menu.

RELAY OUTPUTS

N.O.

COMM

Normally open

N.C.

Normally closed

If relays are set to Normally closed, the relay is powered up with the
controller and the device linked to the relay is functioning. The relay will
shut down when the specified alarm condition is reached.
If the relay is set to normally open, the relay will remain off when the
controller is powered up and the device connected to the relay will only
be activated when the specified alarm condition is reached.
Note: These functions are reversed if the controller Failsafe mode has
been activated.

M-510324
7/10

301C User Manual
Honeywell

17

Relay Output

Jumper Use Instructions
The jumpers on the controller PCB allow a variety of operations to be
performed manually:
EOL 1-4: Enables the user to add End-Of-Line jumpers that improve
communication signals. Put the jumper in R position (as
shown on wiring diagram) to activate the End-of-Line
termination. (R provides a resistance termination and RC
provides resistance and condensator termination.)
SHDN:
Enables the microcontroller to be reset or temporarily shut
down. This function is used mainly when system wiring
adjustments are needed (power off for safety).
Relays
These jumpers allow the relay to be tested by activating it
J29-J32 without having any effect on Events.

18

301C User Manual
Honeywell

M-510324
7/10

Getting Started
Relay Output

Getting Started
The controller units are customized to the purchaser’s specifications but
they can be further programmed using the following menu options.

Initial Startup
Make sure that all wiring has been completed according to
specifications in the wiring details before powering up the unit. When
all is secure, remove the SHDN jumper to power-up the unit. It should
only take a few seconds until the unit is fully operative.

Datalogger (SDcard)
The DLC (Data Logger Card) option for the controller collects data and
stores it on a digital Flash memory card (SDCard). In the event that the
card memory becomes full:
•
•
•

Information logging is stopped
No SDcard flag is displayed on-screen
The SDcard LED blinks

See the Acquisition section for more details on starting and stopping the
datalogging function.
CAUTION

M-510324
7/10

Always deactivate datalogging function before removing the
SDcard. Never remove the card when its LED is on.

301C User Manual
Honeywell

19

Getting Started
Programming Interface

Programming Interface
The front panel of the 301C provides a programming keypad (buttons)
and LEDs.
301C front panel Keypad

Keypad Functions
Each unit has 7 keypad keys, or buttons:
Arrows:

ESC:
Enter:
Silence:

20

Used to move the cursor through the various programming
fields (Up, Down, Left and Right), or to adjust the display
contrast (press and hold the up or down arrow until desired
contrast is reached and release).
Used to exit the programming menu or to cancel a change or
input.
Used to access the programming menu and to modify
programming fields.
Turns off the controller’s buzzer.

301C User Manual
Honeywell

M-510324
7/10

Getting Started
Programming Interface

LED Definitions
The controller is equipped with 7 LEDs that provide a status for each
function related to that indicator:
Alarm A: A blinking red light indicates that an event has been
activated. A constant red light indicates that one or more
transmitters has reached Alarm A or Alarm 1.
Alarm B When the red indicator is on, one or more transmitters has
reached Alarm B or Alarm 2.
Alarm C When the red indicator is on, one or more transmitters has
reached Alarm C.
Power:
Green indicates that the unit is powered up and functional
Fault:
When the amber LED is on, it indicates a fault (i.e. a
communication, maintenance or device problem)
Tx:
When the amber LED is blinking, it indicates that the
controller is sending information or requests on the
communication channel.
Rx:
When the green LED is blinking, it indicates that the
controller is receiving information.
Each of these functions is linked to parameters programmed in the
control unit, which we will discuss in the following section.

System Operation
The system operates in four different modes that allow it to use,
analyze, debug, and simulate the actions that the system can perform.
These modes are: Normal, Single Tx, Debug and Simulate. The default
system operation mode is Normal. The other modes are available
through the Tests menu (option 8 from the Main Menu).
Note: Systems services may be disrupted by some menu operations.

M-510324
7/10

301C User Manual
Honeywell

21

System Programming
Programming Interface

System Programming
The system’s Normal programming mode offers several menu options
that are accessible from the main menu screen:
Tx Info:
Groups:
Events:
Acqui:
Copy:

Allows transmitter parameters to be programmed
Allows groups of transmitters to be set up
Allows events and event behavior to be programmed
Allows the datalogging feature to be activated or deactivated
Allows data or parameters to be copied from the (controller)
configuration to parameters
Config:
Allows system parameters and password to be set
Network: Allows actions on the network to be performed,
communication statistics to be consulted, and remote
calibrations to be performed
Tests:
Allows each device to be tested sequentially (inputs, outputs,
communications, events, etc.) and operation of various
parameters to be validated
BACNet: Allows a device’s BACNet parameters to be set
Wireless: Allows a network of wireless gas detection devices to be
configured, monitored, and modified.
Note: Access to the programming functions is password protected.
The default password is 2967.
The screen display shown below appears initially. This display can be
configured to scroll among the information screens for each device
connected to the controller.

VA301C
Ad: 1
2007-01-17

Gr:0

Ver. 3.00
Ev:0
13:18:18

If one or more of the connected devices is in an alarm mode, the
controller will only scroll between the main information screen and the
screens for device(s) in alarm mode. In this case, you must scroll
manually to view screens for other devices.
22

301C User Manual
Honeywell

M-510324
7/10

System Programming
Programming Interface

The information screen also displays icons representing certain system
functions. Here is a list of possible icons and their meaning:

Icon

Description
BACNet: Indicates that there is a BACNet module present
and that it is communicating with the controller.
BACNet error: Indicates that a BACNet module is present
but communication with the controller has failed (error)
Debug: Indicates whether the controller is in debug mode
(Single TX, Debug or Simulation modes). When in
simulation mode, SIM appears next to this icon.
Log: Indicates that either “Tx Logging” or “Event logging” is
enabled.
Log error: Indicates that an error occured during TX or
Event logging. All logging functions are stopped.
SDC: Indicates that an SDcard is present and functionning.
The icon “fills” (from white to black) progressively as
memory is used. A white icon indicates empty memory
and black indicates full memory.
SDC error: If this symbol persists for more than 5 seconds,
an SD card card is present but not functioning properly.
Wireless network: Indicates that the wireless network
coordinator (wireless communication module) is present
and communicating with the controller.
Wireless network error: Indicates that the wireless network
coordinator (wireless communication module) is present
but is not communicating with the controller.

M-510324
7/10

301C User Manual
Honeywell

23

System Programming
Programming Interface

Since the controller’s programming functions are password protected, it
is necessary to access the login screen:
•
•
•

Press Enter to access the programming options. The password
screen appears:
Use the keypad Up or Down arrows to increase or decrease the
value, one digit at a time, starting with the first digit
When all the digits of the password are correct, press Enter to
access the programming functions.
PASSWORD
____

The first MENU options screen appears. Use the keypad arrows to
navigate through multiple screens to the desired function and press
Enter to access it.

MENU
1. Tx Info
2. Groups

3. Events
4. Aqui

MENU
5. Copy
6. Config

7. Network
8. Tests

MENU
9. BACNet
10. Wireless

24

301C User Manual
Honeywell

M-510324
7/10

System Programming
Tx Info Menu

Tx Info Menu
Tx Info is the menu option that is dedicated to transmitter information
and contains several sub-menu options. The exact list of screens will
vary depending on the transmitter type. A summary is presented below
with details on the following pages
Ident:

COM:

Allows the network component’s
identification information to be
viewed.
Allows the communication
protocol to be viewed or changed

Detection
or Scale(1)
and
Scale(2):

Allows the detection range and
the unit of measurement
parameters to be viewed and
changed

Display:

Allows the label (or name) of a
specific component to be
changed

Alarms:

Allow alarm thresholds to be
viewed and sometimes changed.
There can be significant
variations in this screen
depending on transmitter type.

Status
Displays:

Transmitter and node status
(in hexadecimal values)

Erase or
Erases or changes the
Current Tx: Tx address

M-510324
7/10

301C User Manual
Honeywell

25

System Programming
Tx Info Menu

Ident Menu
The Ident, or identification menu allows a component’s network ID to be
consulted:

1. Tx Info
-Ident-

001

NotVul
CO2 (IR)

The upper right corner of the screen shows the component’s address. If
the address of the device whose information must be viewed is known:
•
•
•
•

Use the arrows to move the cursor arrow to the on-screen address
Press Enter (the value can be edited while the number is flashing)
Use the up or down arrows to increase or decrease the value
Press Enter again to validate the entry and display the information
for the desired device.

The bottom left corner of the display shows the transmitter name (ex.:
301D2 - product name) and the sensor type (ex.: CH4 - methane
sensor). These values can also be changed for Group or Vulbus
product types. The procedure is identical for both fields:
Programming or changing a product or sensor type
•
•
•

26

Use the arrows to move the cursor to the product type field.
Press Enter to select the field (the value can be modified when
flashing)
Use the arrows to scroll through the list of product types and press
Enter when the desired product or sensor appears

301C User Manual
Honeywell

M-510324
7/10

System Programming
Tx Info Menu

Product and Sensor Types
This is a list of all the (preprogrammed) product types available from the
Identification option in the Tx Info menu.
1. Tx Info
-Ident-

121

301W
CO2 (IR)

The order of the products below is not necessarily the order in which
they will appear in the controller
Product Types
Addresses 1-96

VA301D2
90DM3R
VA301IRF
IRT100
EC-F9
VA201T2
VA301T
GsPnt
RgRt3

VA301AP
VASQN8X
VA301EM
VA301EMRP
GsPnt2
S301RLC
(Std.Device)*
VA901T

XNX
XCD
VA201R
VA201T
90DM2
VA201D
VA301D
NotVul

Product Types
Addresses 97-120
Addresses 121-170
301ADI
(?)

(?)
301W
301RW
301RPT

* E3Point and 420MDBS are examples of standard devices.
Note: When Group is selected as a product type, the remaining Tx
INFO screens are not accessible (because each product in the
group has already been individually programmed). Only the Ident
and Erase current Tx screens will be available.
M-510324
7/10

301C User Manual
Honeywell

27

System Programming
Tx Info Menu

The sensor type list applies to address ranges 1-96 and is not
dependent on the type of product selected. Devices in the address
range from 97-170 will display a BACNet object identifier, rather than a
sensor type.
*An additional Product Type, simply called “Group”, represents a group
created in the Groups Menu in the controller. When scrolling through
the available product type list, this name will appear as many times as
there are groups created in the controller (example: Group 1, Group 2,
Group 3, etc.). If a group is selected as the product type, then the
sensor type options are limited to MIN, MAX and MEAN.

28

301C User Manual
Honeywell

M-510324
7/10

System Programming
Tx Info Menu

COM Menu
This screen displays the selected communication protocol for device
addresses from 1 to 96. Each transmitter’s protocol is defined by the
controller (see Network Auto-configuration section)
.
1. Tx Info
-COMMdbs RTU 8D 1S EP
9600 bauds

001

If a transmitter is compatible with several different protocols, it can be
modified using to one of the following options:
•
•
•
•
•

Vulbus
Mdbs ASCII 7D 2S NP 9600 bauds
Mdbs RTU 8D 2S NP 9600 bauds
Mdbs RTU 8D 1S NP 9600 bauds
Mdbs RTU 8D 1S OP 9600 bauds

When a transmitter is configured with the Modbus communication
protocol, the transmitters automatically sends the programmable
parameters to the controller.
Note: Vulbus transmitter parameters must be programmed manually.

M-510324
7/10

301C User Manual
Honeywell

29

System Programming
Tx Info Menu

Scale Menus (1 and 2)
These menus appear only for certain devices. Scale(1) allows the
detection range, minimum and maximum, to be defined for the selected
device. Whatever value is specified is the value that will appear at the
device display (if applicable). The Minimum value is generally left at 0.
Parameters for the XNX and XCD gas detectors can be viewed here
but can be changed only at the transmitter.

1.

Tx Info
001
-Scale(1)Max
00250
Min
00000

Scale(2) allows the factor by which to divide the scale (between 0 and
65535) and the unit of measurement for the selected scale to be
determined.

1.

Tx Info
001
-Scale(2)Factor
00010
Units
%

The factor allows precise scale limits for detection to be set. By dividing
the maximum scale value in the first Scale screen (250 in this example)
by 10, a scale value of 25.0 can then be displayed.
The “Units” allow the unit of measurement for the device to be selected:
°F:
°C
%RH
mV
V
mA
%
ppm
30

Sets degree Farenheit as the unit of measurement
Sets degree Centigrade as the unit of measurement
Sets Relative Humidity as the unit of measurement
Sets millivolts as the unit of measurement
Sets volts as the unit of measurement
Sets milliamps as the unit of measurement
Sets the percentage of gas as the point unit of measurement
Sets parts per million of gas as the point unit of
measurement
301C User Manual
Honeywell

M-510324
7/10

System Programming
Tx Info Menu

Detection Menu
The detection menu (available only for devices with addresses between
1 and 96) displays the detection range (scale: 0-100.0) and the unit of
measurement (unit: %) for the selected component. If a transmitter
uses the Modbus protocol, the detection parameters are automatically
defined during network configuration and are not editable. Vulbus
protocols must be manually defined by the programmer.
The detection scale is between 0 and the maximum value (0.00) and
the unit of measurement is either ppm or percent (% for oxygen and %
LEL for combustibles).
The detection menu is not available for the VA301R or VA301AP.

1. Tx Info
-Detectionscale: 0-0.00
unit: %

001

Programming or modifying the scale range or unit:
•
•
•

Use the arrows to move the cursor to the scale or unit option
Press Enter and use the arrow to increase or decrease the value
Press Enter when the desired value is obtained

M-510324
7/10

301C User Manual
Honeywell

31

System Programming
Tx Info Menu

Display Menu
This option allows a specific label or name to be assigned to the
selected component (transmitters, relay modules, annunciators). Up to
20 characters, including spaces, can be used in the label (example:
BOILER ROOM). The default Modbus transmitter labels are composed
of the component (or transmitter) name, sensor type and address.
Vulbus transmitter labels contain 20 blank characters (spaces).

edit
301D2

32

1. Tx Info
001
-Display(20 char.max)
CH4
Ad001

301C User Manual
Honeywell

M-510324
7/10

System Programming
Tx Info Menu

Alarm A, B and C Menus
The screens for viewing alarm thresholds are combined in this manual.
There will be either two or three levels, depending on transmitter type.
If present, separate “MIN” and “MAX”levels permit manual control of the
hysteresis of each alarm. Normally, the “MAX” level is set greater than
“MIN.” However, alarms can be made to trigger on falling concentration
(as with oxygen) by setting the “MAX” threshold smaller than the “MIN”
threshold.
With certain transmitters, only one threshold will be displayed.
Additionally, with certain transmitters, the alarm thresholds are readonly at the controller. These thresholds can be set only at the
transmitter.
These are typical screens:

Typical screen for viewing alarms A or B on XCD and XNX transmitters

Typical screen for viewing or changing alarm A, B, or C thresholds on
other transmitters.

M-510324
7/10

301C User Manual
Honeywell

33

System Programming
Tx Info Menu

Servicing and Operating Menus
These functions vary depending on the transmitter type. These displays
show the total time the device has been in service and the amount of
time remaining until the next required calibration or replacement.

34

301C User Manual
Honeywell

M-510324
7/10

System Programming
Tx Info Menu

Status Code
These screens display transmission or node status and sensor status
for the selected transmitter. This read-only information can assist
service personnel in troubleshooting.
The XNX and XCD gas detectors will report the warning or fault number
(iFaultWarnNumber) in hexidecimal on the third line. These transmitters
will also report the monitoring state (iMonitoringState) in the fourth line.
See the transmitter documentation for interpretation of fault numbers
and monitoring states.

Typical display for XNX or XCD

Typical display for other transmitters

Erase Current Tx
This function allows the configuration to be erased or the Tx address for
the displayed component to be changed.
Note: Selecting erase current Tx only erases the current device entry
Tx Info configuration. No other data is erased.
1. Tx Info

001

erase current Tx
Change Tx Address

M-510324
7/10

301C User Manual
Honeywell

35

System Programming
Tx Info Menu

Change Tx Address
Selecting Change Tx Address allows users to move a device from one
TX address to another:
•
•
•

Use the arrows to scroll to Change Tx Address and press Enter to
select
In the next screen, scroll to the address number and press Enter to
select
Use the up or down arrows to increase or decrease the address
value and press Enter to validate the new address.

The Change Tx address option is only available (active) for device
address 1 to 96 and if there is a Modbus device connected.
If the address is valid, the screen will display “Processing”.
If the address is invalid, the screen will display “Invalid Tx” and return
to the Change Tx Address screen (the address for GasPoint devices
cannot be changed)
A final screen will display either “Error” or “Success” (re-start procedure
if Error is displayed).
1. Tx Info

001

erase current Tx
Change Tx Address
1. Tx Info
To address:

001

001

1. Tx Info

001

Processing...

Note: If a device address is changed to one already associated with
another device, the existing data will be overwritten. Customers
should know their network’s address assignments and be careful
when changing a Tx address. Delete the original Tx address to
avoid duplicate entries.This feature is not supported with XNX
and XCD transmitters.
36

301C User Manual
Honeywell

M-510324
7/10

System Programming
Groups Menu

Groups Menu
Programming groups of transmitters allows several units to be
combined which then enables actions (events) to be taken based on a
series of units rather than each unit, individually.

MENU
1. TxInfo
2. Groups

3. Events
4. Acqui

2. Groups
 [----] [----]
[----]
[----] [----]
empty all groups

001
[----]
[----]

A group is a stack containing the addresses from each of the
transmitters included in the group.
Groups are displayed in a single line; if a group contains more than four
components, the arrows must be used to scroll left and right of the
display window to view all members of a group.
The cursor in the Group screen is represented by the blinking brackets
(). Any information between the brackets can be edited.

M-510324
7/10

301C User Manual
Honeywell

37

System Programming
Groups Menu

Creating Groups
•
•
•
•
•

Use the arrows to move the cursor to a group line and press Enter
The field can be edited when the brackets stop blinking and the
word “end” blinks
Use the up or down arrows to scroll through the list of all units
connected to the 301C, until the desired address is displayed .
Press Enter again to validate the address.
The address is added to the group and the  bracket is
shifted one position to the right.

The process can be repeated until all the desired transmitters in the
group (up to 126) have been added. The address for each transmitter
added in the Tx Info menu is available when creating groups.
Note: Groups created in the Groups menu will appear in the product
type list (Tx Info - Ident screen) as “Group xx” (the number
assigned to the group when it was created).

38

301C User Manual
Honeywell

M-510324
7/10

System Programming
Groups Menu

Deleting Groups
Use the empty all groups command to delete all groups previously
programmed in the controller.
Single groups can be deleted with a simple procedure:
•
•
•

Scroll to the first transmitter in the group list,
Select the transmitter (its address blinks) and scroll to  (
erases the entry and  marks the end of the stack)
Press enter and the group is emptied.

This procedure makes it possible to delete one, several or all entries
previously included in a group.
Note: Up to 126 groups, with a maximum of 128 members each, can be
created.

39
7/10

Honeywell

System Programming
Event Menu

Event Menu
Though the controller has a default setting for Event configuration (as
shown below), the Event menu is programmable. Event programming
lets specific actions to be defined:
Action:
Delay:

Conditions:
Coverage
period:
Status:
disabled:
Database:

40

What will be done if programmed criteria are reached
Defines the length of time to wait before taking an
action on an event and time to wait after an event
has returned to normal before the action output is
returned to normal state.
AND, OR or none (---); equations that allow more
detailed control of an event
Determines the period during which the event is
applicable
Disables or enables a programmed Event
Erases the selected event or all events

301C User Manual
Honeywell

M-510324
7/10

System Programming
Event Menu

3. Events
-ActionTarget: Ctrl
Relay: #01
3. Events
-DelaysBefore:
99min
After:
01min

1/3
=

3. Events
Gr036
2.01%

001

001

001
AND

3. Events
001
-Coverage PeriodAll day
All week
3. EVENEMENT
-Status : disabledEnable event
.
3. Events
-DatabaseErase current event
Erase all events

M-510324
7/10

001

001

301C User Manual
Honeywell

41

System Programming
Event Menu

Action Menu
Actions are comprised of two parameters:

3. Events
-ActionTarget: Ctrl
Relay: #01

Target

Relay

001

Indicates which component is responsible for the action to
be taken;
Tx (transmitter)
Re (Relay/Annunciator)
Ctrl (Controller)
Indicates which of three possible outputs will be activated
when the event is true;
#XX (activates the component’s #xx relay), Buzzer (activates
the component’s audible alarm)
ALL (activates the relays and audible alarms)

Example: Tx 007 detects a concentration exceeding the set values.
The target (controller) triggers relay 1 connected to that event (a fan
perhaps).

42

301C User Manual
Honeywell

M-510324
7/10

System Programming
Event Menu

Delays Menu
This option allows Before and After settings that will delay the activation
or deactivation of an action to be programmed.
Before

After

Delays the action for the specified length of time. If the
condition persists beyond this delay, the defined action is
executed.
The time to wait after an event has returned to normal before
returning action output to normal state. The after delay also
offers a Latch option, described below.
3. Events
-DelaysBefore:
99min
After:
01min

001

Before and After delays can be configured at either 30 or 45 seconds or
from 1 to 99 minutes, in one minute increments. Five dashes (-----)
indicates that no delay has been programmed.
•
•
•
•

Use the keypad arrows to scroll to the desire option
Press Enter to select the option
Use the keypad arrows to scroll through the second or minute
settings
Press Enter at the desired setting. The delay is set.

M-510324
7/10

301C User Manual
Honeywell

43

System Programming
Event Menu

Latch Mode
•
•
•
•
•

The Latch function is executed on an Event state
It is possible to select the Latch mode by changing the after delay
to “
”
The Event stays active until the Silence keypad button is pressed
The Silence keypad button has two functions: Silence the buzzer
and unlatch the event.
When the Silence keypad button is pressed, events in Latch mode
are unlatched and reevaluated. If the Event condition persists, the
Event remains active and returns to Latch mode. If the condition
does not persist, the event is deactivated.

Note: If the Event has a Before delay and the Silence button is pressed
while the Event conditions are still true, the buzzer will be
silenced only for the length of the programmed delay.

44

301C User Manual
Honeywell

M-510324
7/10

Event Menu

Conditions
Conditions are the parameters that define what makes an Event true.
Each condition is defined by four elements and can be combined with
other conditions to provide greater flexibility. A condition, as in the
example provided below, defines:
IF at least 1/3 of group 36 detects concentrations greater than 2.01% of
specified gas AND all of group 03 detects a concentration greater than
2.99% of gas, then the specified action (Actions were set at the first
Event screen) for that Event will be triggered.
Since the display screens offer limited space, scroll left and right to view
and edit further information.
Condition programming screens

AND

3. Events
Gr036
2.01%

001

1/3
>

3. Events
Gr003
2.99%

001

all
>

AND

The portion of the Events condition screen that is within the brackets is
divided into four editable list fields:

45
7/10

Honeywell

System Programming
Event Menu

The top left portion contains the statistic quantifier (available only for
Groups) that take only the specified part of the group into the equation.
Options available in this field are:
all:
mean:
max:
min:
1/4:

includes all transmitters in the group
includes the average concentration for the group’s transmitters
includes the group’s maximum concentration
includes the group’s minimum concentration
includes at least a quarter of the group’s transmitters that
meets set conditions
1/3:
includes at least a third of the group’s transmitters that meets
set conditions
1/2:
includes at least half of the group’s transmitters that meets set
conditions
2/3:
includes at least two thirds of the group’s transmitters that
meets set conditions
3/4:
includes at least three quarters of the group’s transmitters that
meets set conditions
1 or +: at least one or more than one of the group’s transmitters that
meets set conditions

46

301C User Manual
Honeywell

M-510324
7/10

System Programming
Event Menu

The bottom left portion contains the logic, or operator, quantifier that
determines how conditions are calculated. Options available in this field
are:

Operator
Symbol
--=
<=
<
>=
>
!=
max
min

Meaning
No operator
Equal to
Equal to or smaller than
Smaller than
Equal to or larger than
Larger than
Not equal to
When the maximum value is reached, an action is triggered. It
will not be deactivated until levels fall below minimum value
When concentrations fall below minimum value, an action is
triggered. It will not be deactivated until concentrations rise
above set maximum value

The top right portion contains the source, which defines what device or
group of devices the Event will be based on. The list provides the
following options:
GrAll:
Includes all transmitters (see note)
Gr_ _ _: Includes only the devices in the specified group (see note)
Tx000: Includes only the specified transmitter (connected to the controller)
Clock:
Includes only information gathered between the specified
times. Selecting clock sets a condition that is applied only
between the start and end time frame. It is possible to set
one condition screen to specific parameters and the second
to clock, which means that the specified condition will trigger
an event only if it occurs during the set time period.
Note: Clicking on the magnifying glass to the right of a Group number
on the display opens a view of the Group for consultation or
editing. Press Esc to close the group view and return to the
Event condition screen.
M-510324
7/10

301C User Manual
Honeywell

47

System Programming
Event Menu

The bottom right portion contains the operand, which defines what
device or group of devices on which the Event will be based. The list
provides the following options:
OFF
ON:
Fault:

Used for status on binary inputs (ex.: used with 301ADI)
Used for status on binary inputs (ex.: used with 301ADI)
Bases trigger on maintenance alarm, communication failure or
device failure
Alrm A: If the chosen device or group has an Alarm A or Alarm 1, an
event will be triggered.
Alrm B: If the chosen device or group has an Alarm B or Alarm 2, an
event will be triggered
Alrm C: If the chosen device or group has an Alarm C, an event will be
triggered.
The Coverage Period screen allows the period that will be covered by
the Event to be defined. (The time frames for each of these periods
can be defined in the controller Config menu.) This option provides two
further selection fields:
Day definition field: allows All day, Daytime, or Nighttime to be selected
Week definition field: Weekend, Working Days, All week
3. Events
001
-Coverage PeriodAll day
All week

1. Use the keypad up or down arrows to scroll to either All day or All
week
2. Press Enter to select. The value can now be changed
3. Use the keypad up ro down arrows to scroll through options (see
above)
4. Press Enter to select.

48

301C User Manual
Honeywell

M-510324
8/10

System Programming
Event Menu

Status
This screen displays the current event status and allows it to be either
enabled or disabled, depending on the current status.
Enable event:This is a “toggle” switch; press Enter to change the value
from Enable to Disable and vice versa
3. EVENT
-Status : disabledEnable event
.

001

After going through all the steps and programming an event, this screen
will display “Enable event”. Press Enter to activate all the parameters
and enable the Event.
If an existing Event is being consulted, this screen would display
“Disable event”. Press Enter to disable an Event (it will not be deleted
but will not function). The programming of this Event is always present,
which means that it easily can be reactivated by scrolling to this screen
and pressing Enter.

Database
This screens displays the options linked to the database:
Erase current event:Lets user erase the current event
Erase all events:Lets user erase all events

3. Events
-DatabaseErase current event
Erase all events

M-510324
7/10

301C User Manual
Honeywell

001

49

System Programming
Acquisition Menu

Acquisition Menu
The Acquisition mode is only accessible when there is an SD card
present (controllers with the Data Logging, or DLC function). It is used
to enable or disable the logging of system Events or transmitter
information. The information is logged (or recorded) on an SD card.
Intervals or conditions must be defined before using this option.

4. Acquisition
10% threshold mode
Start Tx logging
Start event logging

The first line of the Acquisition screen offers either :
Delay mode:
Threshold mode:

Allows for delay intervals of 10 to 59 seconds
or 1 to 60 minutes.
Allows log values to be set according to set
variation thresholds (based on last reading) of
3% or more, 5% or more or 10% or more of
last detected concentration.

If a 3% threshhold is selected, the system will not log a value at 3% but
will log a value of 3.1%. Remember that the sampling rate (system
refresh rate) may have an impact on logging.
Here is an example of threshold logging. The logs a semi-colon
delineated text files.

2005-04-27
2005-04-27
2005-04-27
2005-04-27
2005-04-27
2005-04-27

50

11:05:20;1_CO2_ppm;574;-normal-:
11:06:02;1_CO2_ppm;503;-normal-:
11:06:15;1_CO2_ppm;562;-normal-:
11:06:28;1_CO2_ppm;645;-normal-:
11:06:39;1_CO2_ppm;557;-normal-:
11:30:45;1_CO2_ppm;715;-normal-:

301C User Manual
Honeywell

M-510324
7/10

System Programming
Acquisition Menu

Starting and Stopping Tx Logging
In the previous step, “Acquisition”, the frequency at which Tx logs would
be recorded can be configured. To start the logging function:
When “Start Tx logging” appears on the display, it indicates that the
acquisition, or logging, mode is inactive. When “Stop Tx logging”
appears, it indicates that Tx data is being logged. The log message is
displayed on the screen according to the chosen mode and LED 1 will
light up.
Press the Enter keypad button to stop or start Tx logging.
When Tx data is logged, the system creates files named
tayymmdd.log, tbyymmdd.log and tcyymmdd.log, each representing
one third of the network. The record includes the transmitter’s date,
time and address, the sensor type, the concentration read, as well as
the alarm status. Here is a sample of what a Tx log looks like:
2004-01-23 17;54;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;1.5;-normal-;003_CO_ppm;0;-normal2004-01-23 17;55;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;0.5;-normal-;003_CO_ppm;0;-normal2004-01-23 17;56;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;0.5;-normal-;003_CO_ppm;0;-normal2004-01-23 17;57;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;1.0;-normal-;003_CO_ppm;0;-normal2004-01-23 17;58;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;1.5;-normal-;003_CO_ppm;0;-normal-

The first column of the Tx log displays the date (yyyy-mm-dd) and the
time (hh:mm:ss) of the log. In this example, the “Delay mode” was set
to one minute intervals.
The third column of the Tx log displays the transmitter address and the
fourth displays the gas type, gas concentration and unit of
measurement.
The display then lists the next transmitter address with its gas type,
concentration and unit of measurement, and so on until all the
transmitters have been listed.

M-510324
7/10

301C User Manual
Honeywell

51

System Programming
Acquisition Menu

Starting and Stopping Event Logging

The Acquisition menu offers an event logging option. Event Logging
records controller transactions, events, Tx and alarm flags and relay
status.
When “Start Event logging” appears on the display, it indicates that the
acquisition, or logging, mode is inactive. When “Stop Event logging”
appears, it indicates that Event data is being logged.
Press the Enter keypad button to stop or start Event logging.
When Event data is logged, the system creates a file named
evyymmdd.log. The record includes the date, time and the event.
Here is a sample of what an Event log looks like:

2004-01-23 17:54:25: Event logging enable
2004-01-23 17:55:25: Event logging enabled
2004-01-23 19:05:47; Simulation sequence activated
2004-01-23 19:05:48; Tx 6 communication no more in fault
2004-01-23 19:05:48; Tx 8 communication no more in fault

The first column of the Event log displays the date (yyyy-mm-dd) and
time (hh:mm:ss) of the log. Column A displays the date and time of the
log. In this example, the event’s “Delay mode” was set to one minute
intervals.
The system logs the following types of events:
•
•
•

Event Log
Event status changed
Alarm A, B, C, Fault, and X status changed

Note: New log files are created when the existing files reach 32 000
lines or at the start of a new week (0h00 Sunday)

52

301C User Manual
Honeywell

M-510324
7/10

System Programming
Copy Menu

Copy Menu
The Copy menu allows programmed parameters to be copied and
transferred. Data from the SD card can be transferred to a controller or
from a controller to the SD card or copy parameters from one device to
the next. The Copy option offers three screens: Configuration,
Parameters and System Log.

Configuration
If the controller is equipped with an SD card, the configuration function
allows data to be transferred either from the 301C to the SD card or the
reverse. This makes it possible to transfer the controller’s programming
to a computer or from a computer to the controller.
5. Copy
-ConfigurationConfig to SDcard
SDcard to Config

The first option in the configuration screen is 301C to SDcard.
Selecting this option copies the controller’s configuration and
parameters into a “config.ini” file 1.
The second option is SDcard to 301C allows the configuration and
parameters of the “config.ini” file on an SDcard to be copied to the
controller.
Note: The “config.ini” file contents can be modified at any time and from
any computer.

1. When transferring data, the system will automatically search for an existing “config.ini”
file before proceeding. If one exists, the system searches for a “config.bak” file. If
found, the file is deleted. Then, the pre-existing “config.ini” file is renamed “config.bak”,
making it possible to save the new “config.ini” file and keep a backup copy of the previous one.
After inserting an SD card into the controller, the controller’s system looks for an existing “config.ini” file that contains an “autoload” tag equal to 1 (yes). If the tag is found,
the system loads the contents of the file and resets “autoload” to 0 (no). This is a useful
feature for editing the file on a computer without having any impact on the controller
(such as recorded Events).

M-510324
7/10

301C User Manual
Honeywell

53

System Programming
Configuration

Parameters
The “parameters” function allows one transmitter’s configuration to be
copied to another or one event’s parameters to be copied to another
event. This allows several devices that share identical or similar
parameters to be quickly configured.

5. Copy
-parametersTxInfo to TxInfo
Event to Event

The options within this screen are:
Tx Info to Tx Info copies transmitter parameters from one device to
another.
Event to Event copies parameters from Event to Event.
The process is identical for both options:
•
•
•
•
•

Select source, (the data to be copied) using the up/down keypad
arrows and press Enter.
When the transmitter address is flashing, use the up/down keypad
buttons to search for the desired device address.
Press Enter to select the new address
Select the target address (where the data is to be copied to) in
exactly the same way as source
Select COPY and press Enter. The parameters have been copied.
TxInfo to TxInfo
source tx001
target
tx113
COPY

Event to Event
source #001
target
#013
COPY

54

301C User Manual
Honeywell

M-510324
7/10

System Programming
Configuration

System Log Menu
The controller will record log information to its internal memory. If the
controller is equipped with an SD card, the system log function allows
users to save system log information to the memory card in text format.

5. Copy
-System LogSysLog to SDcard

When this option is selected, a log of all the last actions performed on
the controller is copied to the SDcard, with the filename slyymmdd.log.
This file can contain up to a maximum of 64Kb of information in text
format. Once the memory card is full, the oldest log entries are erased
and replaced by new entries.
Here is an example of a system log:

--- START of system log dump : 2007-04-18 13:19:05 --2007-04-04 18:42:06;Accessing menu;
2007-04-04 18:43:47;Event 1 definition modified;
2007-04-04 18:48:12;Exiting menu;
2007-04-04 18:54:49;System power-down;
2007-04-04 18:56:40;System power-up;
2007-04-04 19:02:44;Accessing menu;
2007-04-04 19:03:07;Event 6 definition modified;
2007-04-04 19:03:21;Exiting menu;
2007-04-05 10:51:28;Accessing menu;
2007-04-05 10:54:59;Database reset;
2007-04-05 10:55:18;Tx 25 parameters modified;
2007-04-05 10:55:29;Group 0 definition modified;
2007-04-05 10:55:36;Group 0 definition modified;
2007-04-05 10:55:46;Group 0 definition modified;
2007-04-05 10:55:55;Group 4 definition modified;
2007-04-05 10:55:57;Exiting menu;
2007-04-05 10:56:02;Accessing menu;
2007-04-05 10:56:19;Tx 24 parameters modified;

M-510324
7/10

301C User Manual
Honeywell

55

System Programming
Config Menu

Config Menu
The Config menu contains several main configuration screens and is
used to program the controller display mode, adjust the date and time,
select the display language, change the controller access password,
modify the Slave Port configuration, set the Relay Configuration, and
select the AP Broadcast mode.
Each main screen offers further programming options, as shown.
MENU
5. Copy
6. Config

7. Network
8. Tests

6. Config
Manual scroll mode
Set Date and Time
Menu français
Date and Time
2005-11-21
11:47:36
(ISO 8601 standard)
6. Config
Set User Password
- 2967 Slave Port Cnfg
Slave Port Cnfg
Address: 001
38400 bauds
Mdbs RTU 8D 2S NP
6. Config
Relay Configuration
AP Brdcst: auto
Honeywell
Relay Configuration
-FailsafeAll relays
Inactive

Relay Configuration
-Silence1
2
3
4
dis
ena dis
dis

6. Config
Day definition
Week definition
Day definition
-Daytimesta:
08:00
end:
17:00
Week definition
-Working Dayssta:
Monday
end:
Friday

56

301C User Manual
Honeywell

M-510324
7/10

Config Menu

Selecting the first line of the first screen allows selection from three
display modes: Manual scroll, 3-second scroll, 5-second scroll. If
Manual scroll mode is chosen, the screen will only advance if you press
on the arrow keypad buttons. If either 3 or 5 second scroll mode is
chosen, the screens will automatically scroll display readings for all
devices connected to the controller after 3 or 5 seconds.

6. Config
Manual scroll mode
Set Date and Time
Menu français

3 or 5 second scroll modes do not prevent the keypad arrows to be used
to return to a previous screen or move ahead through the screens
manually.
Selecting the second line allows the date and time in a new screen to
be adjusted; Date and Time. When a number is flashing, the value can
be changed using the up/down keypad arrows. The year, month, day
and the hour, minute and second values can be changed.
The controller does not manage Daylight Savings Time, therefore,
users must manually adjust any time changes.
Date and Time
2005-11-21
11:47:36
(ISO 8601 standard)

Selecting the third line allows the display language to be changed. If the
display is already in English, it will then display the Menu français option
(and vice-versa). Simply scroll to the line and press Enter to change the
language.

M-510324
7/10

301C User Manual
Honeywell

57

Config Menu

The second main screen in the Config menu allows a new user
password to be set and the slave port configuration to be modified.

6. Config
Set User Password
- 2967 Slave Port Cnfg

The default password is 2967. Select Set User Password to change the
password:
•
•
•

When the first digit blinks, change the value by using the up/down
keypad arrows to increase or decrease the number
Use the left/right keypad arrows to move from one digit to the next.
When the desired password has been set, press Enter to validate it
and exit the editing mode.

Note: Contact Honeywell technical support for help with lost passwords
at 1-800-563-2967.

58

301C User Manual
Honeywell

M-510324
7/10

System Programming
Config Menu

Scroll through the main Config menu screens using the left (previous) or
right (next) keypad arrows.
The third main screen in the Config menu allows the relay configuration
to be set, the AP broadcast mode and to select from four separate
manufacturers for the given controller.

6. Config
Relay Configuration
AP Brdcst: auto
Honeywell

When Relay Configuration is selected, two further options to configure
the relays are available: The first screen, Failsafe, appears allowing
the failsafe to be activated for all relays using the Enter keypad button.
This function is used in case of a power failure: if power is cut, the relay
will activate the connected device (ex. a light) to signal the problem.

Relay Configuration
-FailsafeAll relays
Inactive

Scrolling to the right displays the “Silence” screen that enables or
disables the silence option for each relay, using the Enter keypad
button.

Relay Configuration
-Silence1
2
3
4
dis
ena dis
dis

M-510324
7/10

301C User Manual
Honeywell

59

System Programming
Config Menu

The fourth screen in the Config menu allows a definition of a day and a
week to be programmed.

6. Config
Day definition
Week definition

Day and Week definition allows hours (time frames) to be defined for
either Daytime and Working Days respectively.

Day definition
-Daytimesta:
08:00
end:
17:00

Week definition
-Working Dayssta:
Monday
end:
Friday

Note: Remember, the controller uses a 24 hour clock (0:00 to 23:59).
Any time changes (DST) must be made manually or through
BACNet time synchronisation (BACNet module required).

60

301C User Manual
Honeywell

M-510324
7/10

System Programming
Network Menu

Network Menu
The Network menu allows network device information to be either
scanned or reset.
This menu offers four options, divided into two screens; the first screen
contains three options:
Reset Database:

Network Scan:

Reset and Scan:

Resets all network device Tx information in the
database. This only resets the Tx infomation
for the network device. It does not affect
programmed Groups or Events.
Begins an auto-detect of all network devices
that allows the system to configure the Tx
database for network devices (i.e. it will scan
and add new devices but will not overwrite or
erase the old database)
Performs both previous functions
simultaneously.
7. Network
Reset Database
Scan Network
Reset and Scan

Note: Once one of these options has been set, wait until the controller
completes the process. Do not interrupt or stop the process once
it has begun.

M-510324
7/10

301C User Manual
Honeywell

61

System Programming
Network Menu

The second Network screen offers the Statistics and Calibration
options.

7. Network
Statistics
Calibration

Selecting Statistics from the Network menu displays a screen
containing the statistics for the selected device address.

Statistics
Valid
16
Errors
0
Timeouts
0

001
100%
0%
0%

Valid:

Indicates the number of valid responses for the last 16
requests
Errors:
Indicates the number of errors in the response for the last 16
requests
Timeouts: Indicates the number of timeouts (no response) for the last
16 requests

62

301C User Manual
Honeywell

M-510324
7/10

System Programming
Network Menu

Remote Calibration
The network menu also offers a Calibration option for use with devices
that support network calibration.
7. Network
Statistics
Calibration

The Calibration screen contains four (4) lines of information:

Calib
007
S301M
Status:
Normal
Set Zero
Set Span
246
PPM

Line 1:

Line 2:
Line 3:
Line 4:

Indicates the mode (Calib, meaning calibration), the
(Modbus) address of the device to calibrate (001) and the
type of device to calibrate (301D2)
Indicates the status (Normal or In calib…) of the specified
device
Displays the function to perform (Set Zero)
Displays the function to perform (Set Span) and the span
gas concentration value (246 ppm)

5. On the first line, scroll to the device address and press Enter
6. Scroll through the devices to display the desired device* and press
Enter to select.
7. The second line displays the device’s status
8. Scroll to select the desired function, Set Zero to set the device's
zero, and press Enter to select.
9. Upon pressing Set Zero, the controller requests confirmation.
Calib
007
S301M
Status:
Normal
Set Zero
Set Span
246
PPM

*The device must be configured in the 301C’s database in order to be
included in the device addresses displayed on screen.

M-510324
7/10

301C User Manual
Honeywell

63

System Programming
Network Menu

10. Press Enter to confirm or Esc to cancel. If confirmed, the controller
calibrates the sensor’s Zero. This takes only a few moments and
the display returns to the default calibration screen.
Note: Never calibrate any unit’s Zero with ambient air. Always use
Nitrogen (N2) at the calibration port to calibrate the Zero.
11. To calibrate the device, scroll to Set Span** and change the span
gas calibration value using this procedure;
Calib 001 : 301D2
Status : Normal
Set Zero
Set Span
2.60 ppm

a. Using the right arrow, move the cursor to xxx PPM (span
value field). Press Enter to select the field (it is editable when
flashing).
b. Use the up or down arrows to increase or decrease the
value, press Enter to validate the new value.
c. Move the cursor back to Set Span and press Enter to start
the calibration.
Calib 001 : 301D2
Status : In calib...
Set Zero
Set Span
2.60 ppm

The device Span is being calibrated. The screen will display the
device’s status as “In calib...” until the calibration is complete.
**When selecting Set Span, make sure that the device has been
supplied with the appropriate calibration gas before and during the
calibration process.

64

301C User Manual
Honeywell

M-510324
7/10

System Programming
Tests Menu

Tests Menu
The Tests menu allows a variety of tests to be performed on
components and on the network communications. It also allows the
system to be operated in four different modes which, in turn, provide
different functionalities.
MENU
5. Copy
6. Config

7. Network
8. Tests

8. Tests
Test sequence
Start Sim Sequence
Maximum load

1

Test sequence
Relays activated
Any key to continue
Esc to quit

2

Test sequence
BUZZER activated
Any key to continue
Esc to quit

3

Test sequence
LEDs activated
Any key to continue
Esc to quit

4

Test sequence
Press ‘left’
Esc to quit

5

Test sequence
Display test
Any key to continue
Esc to quit

6

Test sequence
Test Network comm.
9600 bauds
Channel 1 PASSED

7

Test sequence
Test done
Any key to continue

Simulation Sequence
Start with
Tx001
Confirm
8. Tests
Oprt Mode: normal

M-510324
7/10

301C User Manual
Honeywell

65

System Programming
Tests Menu

The Tests menu provides four main options, divided between two
screens. Each of these options offers different capabilities.
The first screen presents three options:

8. Tests
Test sequence
Start Sim Sequence
Maximum load

Test sequence:

Start Sim
Sequence:

Maximum load:

Enables each output to be activated and validates
operation of each controller keypad buttons, display
pixels, and various communication protocols.
This options starts or stops the Simulation mode,
which allows a simulation of a gas concentration
over an associated scale range on all transmitters.
The simulated gas concentration values are local (on
the controller) and do not affect logging functions.
(Events will be activated for the simulation but
detection devices are not affected.)
Activates all controller components

The second screen option is “Oprt Mode”, which offers three separate
operation settings: Normal, Single Tx or Debug.

8. Tests
Oprt Mode: normal

Normal
Single Tx:
Debug:

66

Normal controller operation mode
Activates the polling mode on a single transmitter.
Activates the service mode to perform a calibration
and to test Events without triggering actions.

301C User Manual
Honeywell

M-510324
7/10

System Programming
Tests Menu

Test Sequence
When test sequence is selected from the main Tests menu, the
controller will display the Test sequence screen.

Test sequence
Relays activated
Any key to continue
Esc to quit

If Esc is pressed on the keypad, the main Tests menu screen will be
displayed. However, to perform system tests, press any key to proceed
to the first test screen.

Test sequence
BUZZER activated
Any key to continue
Esc to quit

This screen tests each component individually and will advance only to
the next component when a key is pressed. This option will display 13
screens. Screens 1, 2 and 3 test Relays, BUZZER and LEDs.
The following six screens prompt the user to press the keypad buttons,
in turn: left, right, up, down, Silence, Enter and Esc. The system will not
advance until a key is pressed.

Test sequence
Press ‘left’
Esc to quit

M-510324
7/10

301C User Manual
Honeywell

67

System Programming
Tests Menu

The system then moves to the Display test. When the blank screen is
displayed, it is testing for display pixels. Press any key to proceed to the
next step.
Test sequence
Display test
Any key to continue
Esc to quit

The final test that the system performs is a network communication
test:

Test sequence
Test Network comm.
9600 bauds
Channel 1 PASSED

Once these tests have begun, do not interrupt or stop them. The
system tests all five bauds (communication speed: 9600, 19200,
38400, 57600, 115200) and each of the 4 channels per baud.
When the system has completed the test, it displays the final Tests
screen. Press any key to return to the main Tests menu.

Test sequence
Test done
Any key to continue

68

301C User Manual
Honeywell

M-510324
7/10

System Programming
Tests Menu

Normal Mode
This is the system’s normal (default) operation mode. When the system
is in normal mode, some values can be changed without interrupting
services. When a value has been changed in any of the menu fields,
the change will take effect upon returning to the main menu screen.

Single Tx Mode
This mode allows transmitters to be analyzed one at a time. The
controller polls only the selected device, which subsequently has its
information updated. This mode does not interfere with Event
Evaluation functions.

Debug Mode
This mode allows complete system operation to be evaluated and
tested without affecting operations (outside of debug mode). Events
are evaluated and displayed as necessary but no action is
triggered.

M-510324
7/10

301C User Manual
Honeywell

69

System Programming
Tests Menu

Simulation Mode
This mode deactivates network communication Information Updates. It
can be combined with any of the three previous modes (example: using
the Simulation mode when in Debug mode allows the user to test the
entire system [groups, events, etc] without triggering any actions or
using any additional material such as gases). It allows gas
concentrations to be simulated over an associated scale for each
transmitter, sequentially:
Alarm levels A, B and C are evaluated according to the simulated gas
concentration and events are evaluated and actions are taken.
This type of alarm simulation at the controller does not work with
certain transmitters with falling alarms. In these cases, an alarm can be
simulated at the transmitter.
While in simulation mode, the controller is unaware of the device’s
actual network status. This mode can be stopped at any time in the
Test menu (see Normal System Operation).
If one of these modes has been activated, the system will automatically
return to Normal Mode after 12 hours of inactivity. (No changes will be
lost.)

70

301C User Manual
Honeywell

M-510324
7/10

System Programming
BACnet Menu

BACnet Menu
The BACNet menu offers several main menu screens to configure the
BACNET IP connection, DHCP, server, time zone information and more.

M-510324
8/10

301C User Manual
Honeywell

71

System Programming
Bacnet Menu

The first of these screens allows the identification and address to be
configured:
9. BACNet
-DeviceBACnet ID : 1
Static IP address

BACnet ID:

(Building Automation and Control Networks) is the
device ID number assigned to this particular
controller on a network.

Static IP address: This is an address that is used when DHCP is
disabled.
Changing BACNet values

•
•

Use the keypad arrows to scroll down to select the desired line and
press Enter to select it.
Selecting BACnet ID activates the field. The ID value (0-4194303)
can be increased or decreased using the up or down keypad
arrows

If the Static IP address option is selected, the following screen appears.
All controllers are shipped with a preset IP address as shown in the
example below.
-IP address192.168.
1.254
-Network mask255.255.255.
0

72

301C User Manual
Honeywell

M-510324
7/10

System Programming
Bacnet Menu

The next screen allows the device DHCP (Dynamic Host Configuration
Protocol) to be enabled or disabled.

9. BACNet
-DHCP : disabledEnable DHCP

•

Simply press Enter to change the field value. Consult the IT
department for details concerning this option.

M-510324
7/10

301C User Manual
Honeywell

73

System Programming
Bacnet Menu

The next main BACNet screen allows modification of the SNTP (Simple
Network Time Protocol) server IP address and configure the frequency
at which the system will make SNTP server requests. Honeywell has
made these options available to better adapt to the building’s network
protocol, however Honeywell does not provide configuration or support
for these options.

9. BACNet
- SNTP Client SNTP server
SNTP request :
1min

Selecting Server request activate the minute The SNTP server option
opens another screen that allows the SNTP server IP address to be
changed
The SNTP server option opens a secondary screen that allows the
SNTP server’s IP address to be modified. Consult the IT

department for details concerning these settings

10.

SNTP server
4. 1. 12

scrolling through 0 to 60 minutes to set the frequency at which the
system will perform SNTP server synchronizations.

74

301C User Manual
Honeywell

M-510324
7/10

Bacnet Menu

The next main menu screen is the Date and Time screen. This screen
allows the system’s time zone to be defined (if it differs from universal
time) and whether daylight savings time is applicable.
If the Time Zone field is selected, use the keypad arrows to scroll
through the available times (from 0:00 to +13:00 and -12:00 to 0:00)

9. BACNet
-Time ZoneTime Zone :
0:00
DST: OFF

The Device Name screen allows a specific name to be assigned to the
BACNet device.

9. BACNet
-Device Nameedit
(20 char.max)
301C:1

The next screens allow users to configure BACNet communication
between different systems on a network (subnets), specifically with
Foreign Device Registration and BBMD.

M-510324
7/10

301C User Manual
Honeywell

75

Bacnet Menu

The Foreign Device Registration (FDR) allows users to enable the FDR
and to set a specific Time To Live (in seconds).
9. BACNet
-ForeignDevReg:disEnable FDR
TTL: 43200 sec

A Foreign Device is a BACNet device that has an IP subnet address
different from those on the BACNet/IP network it seeks to join.
The TTL (Time-To-Live) parameter is the registration duration supplied
to the BBMD at the time of registration. Devices must re-register within
this specified interval to remain connected.
The BBMD Info screen lets users specify the address for the BBMD to
which the device will try to connect (or register).
9. BACNet
-BBMD InfoIP:
192.168. 1.100
Port: 0xBAC0

For more information on this subject, please consult the ASHRAE
standard number 135-2001, Annex J, section J5.

76

301C User Manual
Honeywell

M-510324
7/10

System Programming
Wireless Network Menu

Wireless Network Menu
The wireless menu allows wireless communication parameters to be
set, wireless network diagnostics to be consulted, and the various
aspects of the wireless nodes (sensors) to be accessed.
Wireless Network
1. Parameters
2. Diagnostics
3. Nodes
4. New Node
5. Hibernate
6. Reset Network
7. Status Log NoLog
8. Consolidate route

Parameters
1.
7B7177EFACE0049
2. WC Version
3. PAN ID
4. RF channel
5. Log Mode No Log
6. Association
Ina
7. Nodes
0
8. Max nodes
0
9. Max hops
0
10. Power
0
11. AHFO
0
12. BO
0
13. SUO
0
14. LCO
18
15. LTO
0
16. MMO
0
17. BMO
0
18. KNSRO
0
19. FNSRO
0
20. Clone WC

Diagnostics
1. Weak Link Report
2. Lost Link Report

System Menu
Invalid Option
Log Mode
Log
Association
Ina
PAN ID
VAL : 1B05
MAX : FFFF
MIN : 0001
MAC 1st part
VAL : 00155F00
MAX : FFFFFFFF
MIN : 00000000
System Menu
No Node Found
or

Nodes
1. ID
121 (79h)
2.
7B7177EFACE0049
3. Product
VA301W
4. Link Quality
1
5. Op Mode
Log
6. Net Addr
9
7. SWU slot
1
8. # of parents
1
9. DP Id
0
10. DP Net Addr
0
11. DP LQ1
2
12. DP Retries
(?)
13. DP BM
0
14. DP LC
256
15. AP1 ID
(?)
16. AP1 Net Addr (?)
17. AP1 LQ1
16
18. AP1 Retries
128
19. AP1 BM
(?)
20. AP1 LC
27132032
21. AP2 ID
2
22. AP2 Net Addr 31756
23. AP2 LQ1
198
24. AP2 Retries
190
25. AP2 BM
0
26. AP2 LC
56320
27. LSU
661
28. Status
Alive
29. Freshness
2
30. Version
A14
31. Hibernate
32. Replace
33. Remove
34. Consolidate Route
35. Failsafe
ON

Nodes
1. ID
121 (79h)
2.
7B7177EFACE0049
3. Product
VA301W
The “ Nodes” menu appearing under
both Weak and Lost link reports is
identical to the “Nodes” (option 3) in
the Wireless Network menu

System Menu
Invalid Option

Hibernate
Enter to confirm
Esc to cancel

New Node
VAL : 121
MAX : 180
MIN : 121
Hibernate
Enter to confirm
Esc to cancel
Status Log
No Log
Consolidate Route
VAL : 00060
MAX : 65535
MIN : 00000

M-510324
7/10

301C User Manual
Honeywell

Status Log
Enter to confirm
Esc to cancel
Conslidate Route
Enter to confirm
Esc to cancel

77

System Programming
Wireless Network Menu

Parameters Menu
When Parameters is selected from the Wireless Network main menu
options, all the coordinator parameters are displayed in order.
The screen can only display three items at one time. Use the up or
down arrows to scroll through the list of parameters.

Parameters
1.
7B7177EFACE0049
2. WC Version
3. PAN ID
4. RF channel
5. Log Mode No Log
6. Association
Ina
7. Nodes
0
8. Max nodes
0
9. Max hops
0
10. Power
0
11. AHFO
0
12. BO
0
13. SUO
0
14. LCO
18
15. LTO
0
16. MMO
0
17. BMO
0
18. KNSRO
0
19. FNSRO
0
20. Clone WC

System Menu
Invalid Option
Log Mode
Log
Association
Ina
PAN ID
VAL : 00000
MAX : 65535
MIN : 00001
MAC 1st part
VAL : 00155F00
MAX : FFFFFFFF
MIN : 00000000

Note: When data is provided for information purposes only, it is not
editable. When an item that is not editable is selected, the
screen will briefly display the “System Menu - Invalid Option”
screen (as shown above).

78

301C User Manual
Honeywell

M-510324
7/10

System Programming
Wireless Network Menu

Changing PAN ID or RF Channel
When the PAN ID or the RF channel is changed, using the Parameters
menu option within the Wireless Network menu, the system needs
confirmation at more than one option, as described below:
To change the PAN ID:
•
•
•
•
•

•
•

Select Parameters from the Wireless Network menu
Scroll down (using the arrows) to hightlight option 3, PAN ID
Press Enter to select
Change the PAN ID values, as desired and press Enter
The next screen requests either confirmation or cancellation. Press
Enter to confirm (If Esc is pressed, no changes will be made and
the screen returns to the main Wireless Network menu)
The system displays the RF channel screen; press Enter to
proceed (or to record changed values)
The next screen requests confirmation or cancellation. Press Enter
to confirm. If Esc is pressed at this point, the changes to the
PAN ID will not be made.
Parameters
1.
7B7177EFACE0049
2. WC Version
3. PAN ID

PAN ID
VAL : FF07
MAX : FFFF
MIN : 0001

PAN ID
Enter to confirm
Esc to cancel

RF channel
VAL : 011
MAX : 255
MIN : 001

RF Channel
Enter to confirm
Esc to cancel

Note: Whenever changes are made to the PAN ID or the RF channel,
the network must rebuild itself. Losing the network (entire network
in Fault mode) during this process is normal and should only last
approximately 10 minutes.

M-510324
7/10

301C User Manual
Honeywell

79

System Programming
Wireless Network Menu

The following table provides the list of parameters displayed for the
coordinator (wireless communication module). Use the up or down
keypad arrows to navigate the entire list.

#
1.
2.
3.

Title
Value
7B177A7EFACE0049
WC Version
A10
PAN ID
FF07

4.
5.

RF channel
Log Mode

6.

Association

11
No
Log
Ina

7.

Nodes

0

8.

Max nodes

0

9.

Max hops

0

10.

Power

0

11.

AHFO

0

12.

BO

0

13.

SUO

0

14.

LCO

18

15.

LTO

0

80

Description
Coordinator MAC address
Wireless coordinator firmware version
The hexadecimal ID number assigned
to the coordinator
Radio frequency channel
Displays whether debug mode is
activated
Defines whether new nodes can join the
network
Displays the number of nodes
associated to the wireless coordinator.
Defines the maximum nodes that can
reside in the network (1-60)
Defines the maximum number of hops a
node can make on a communication
route to the wireless coordinator
Sets the transmission power amplifier
value
Defines the time between wake-up
cycles
Sets the time between transmission of
two consecutive beacons by a node to
establish and maintain synchronization
Defines the status update period; time
between 2 consecutive status update
packets sent from node to coordinator
Packet sent from the coordinator to the
node, confirming to the node that it is
registered on the network at the
coordinator
The number of status update packets
that can be missed before a “leave
indication” is triggered

301C User Manual
Honeywell

M-510324
7/10

System Programming
Wireless Network Menu
#
16.

Title
MMO

Value
0

17.

BMO

0

18.

KNSRO

0

19.

FNSRO

0

20.

Clone WC

M-510324
7/10

Description
Defines the bandwidth of the message
retry measurement
Defines the bandwidth of the missed
beacons measurement
Defines the frequency at which a node
updates information from known
neighbors
Defines the frequency at which a node
will scan for new neighbors
Although accessible, this option is not
available (will be used for future
advanced use features).

301C User Manual
Honeywell

81

System Programming
Wireless Network Menu

Diagnostics Menu
The diagnostics menu allows both Weak Link and Lost Link reports to
be consulted. These reports consist of the multiple-item node
information list (as it appears in the Nodes menu). If there are no weak
or lost links, the system will return the message “System Menu No
Node Found”.
If more than one node appears in this section, use the left or right
keypad arrows to scroll through nodes.

Diagnostics
1. Weak Link Report
2. Lost Link Report
Nodes
1. ID
121 (79h)
2.
7B7177EFACE0049
3. Product
VA301W

82

301C User Manual
Honeywell

M-510324
7/10

System Programming
Wireless Network Menu

Nodes Menu
The Nodes menu displays a multiple-item node information list. Use the
left and right keypad arrows to scroll between nodes and then use the
up or down keypad arrows to scroll through the information list for each
node.

Nodes
1. ID
121 (79h)
2.
7B7177EFACE0049
3. Product
VA301W

Each line represents specific information, as shown in the screen
(above):
Line 1 displays the device’s network identification (the last two digits of
a hexadecimal ID, example 79) and controller reference number
(121) for the specific transmitter.
Line 2 displays the device’s MAC address
Line 3 displays the type of product (VA301W).
The screen can display only three items at one time, so the up or down
arrows must be used to scroll through the list

M-510324
7/10

301C User Manual
Honeywell

83

System Programming
Wireless Network Menu

The following table provides the list of data displayed for each node.
Use the right or left keypad arrows to navigate the possible nodes, then
use the up or down keypad arrows to navigate the entire list of data for
the selected node.
#
4.

Title
Link Quality

Value
1

5.

Log Mod

Log

6.

Net Addr

0009

7.

SWU slot

1

8.

# of Parents

1

9.

DP Id

0

10.

DP Net Addr

0

11.

DP LQI

2

12.

DP Retries

(?)

13.

DP BM

0

14.

DP LC

256

15.

AP1 ID

(?)

16.

AP1 Net Addr

(?)

17.

AP1 LQI

16

84

Description
Percentage of signal strength (0-100%) for
a node, relative to parent signal quality
Indicates whether the node is in debug
mode
Displays the node’s (hexadecimal) network
address (seen in 1st screen)
Displays the SWU slot used to transmit
beacon
Displays the number of current parents for
a given node, from 0 - 3.
Displays the ID associated to the default
parent
Displays the default parent network
address
Displays the link quality with the default
parent:
0 = no useful link/1 = weak link/2 = strong
link
Displays the number of default parent
retries
Displays the number of parent beacons
missed over last beacon period
Displays the time since lasct
communication to default parent (in
milliseconds)
Displays the ID associated to the
alternative parent 1
Displays the alternative parent 1 network
address
Displays the link quality with alternative
parent 1:
0 = no useful link/1 = weak link/2 = strong
link

301C User Manual
Honeywell

M-510324
7/10

System Programming
Wireless Network Menu
#
18.

Title
AP1 Retries

Value
128

19.

AP1 BM

(?)

20.

AP1 LC

21.

AP2 ID

27132
032
2

22.

AP2 Net Addr

31756

23.

AP2 LQI

198

24.

AP2 Retries

190

25.

AP2 BM

0

26.

AP2 LC

56320

27.

LSU

661

28.

Status

Alive

29.

Freshness

2

30.
31.
32.
33.

Version
Hibernate
Replace
Remove

A14

34.

Consolidate Route

35.

Failsafe

M-510324
7/10

ON

Description
Displays the number of alternative parent 1
retries
Displays the number of alternative parent 1
beacons missed over last beacon period
Displays the time since last communication
to alternative parent 1 (in milliseconds)
Displays the ID associated to alternative
parent 2
Displays the alternative parent 2 network
address
Displays the link quality with alternative
parent 2:
0 = no useful link/1 = weak link/2 = strong
link
Displays the number of alternative parent 2
retries
Displays the number of alternative parent 2
beacons missed over last beacon period
Displays the time since last communication
to alternative parent 2 (in milliseconds)
Displays the time at which the system was
last updated
Displays whether the node is activated or
off
Displays the number of status updates that
can be missed before a “leave indication” is
triggered
Node (device) firmware version
Selecting these options displays a
confirmation screen. If confirmed, the
selected function will be executed (see
descriptions below).
Enabling this option forces the node to take
the best route to the controller using an
alternate parent.
This option is only available only when
there is a relay module in the network. It
allows users to specify relay failsafe
settings for a wireless relay module.

301C User Manual
Honeywell

85

System Programming
Wireless Network Menu

Options 1 through 29 are for information purposes only and cannot be
modified.
Options 16 through 21 are only displayed if the selected node has a
second parent (a parent is any other node to which a node may
connect to create a link to the controller).
Option 22 through 27 are only displayed if the node has a third parent.
Options 31 through 33 allow the Hibernate, Replace, or Remove nodes
to be selected:
Hibernate Places the node in hibernation (power down). This mode is
used for maintenance or to change the battery.
Replace

Allows a node to be replaced by another without changing
the MAC address or node ID (enables a free node with a
different [or same] MAC address to be mapped to the current
node ID).

Remove Removes the node from the network and erases the node
data from the coordinator memory and from the 301C
database.
Option 34, Consolidate Route, allows the user to force the node to find
the best route to the controller using an alternate parent.

86

301C User Manual
Honeywell

M-510324
7/10

System Programming
Wireless Network Menu

New Node Menu
The New Node menu allows users to add new nodes to the existing
network, assigning a specific ID number to its MAC address.

Wireless Network
4. New Node
5. Hibernate
6. Reset Network

New Node
VAL : 121
MAX : 180
MIN : 121
MAC 1st part
VAL : 00155F00
MAX : FFFFFFFF
MIN : 00000000
MAC 2nd part
VAL : 80000024
MAX : FFFFFFFF
MIN : 00000000

•
•
•
•
•
•
•

Scroll to highlight New Node and press Enter to select
In the New Node window, enter the desired ID value in the VAL field
and press Enter
Press Enter to confirm
When the MAC 1st part screen appears, enter the first 8 digits of
the new node’s MAC address* and press Enter
Press Enter to confirm
When the MAC 2nd part screen appears, enter the last 8 digits of
the new node’s MAC address and press Enter
Press Enter to confirm

*The node’s MAC address is printed on the node’s housing.
Note: If an ID number that already exists is assigned, this function will
not be completed.

M-510324
7/10

301C User Manual
Honeywell

87

System Programming
Wireless Network Menu

Hibernate Menu
The hibernate menu allows users to shut down the entire network of
wireless nodes, to prevent any damage when maintenance is needed.

Wireless Network
4. New Node
5. Hibernate
6. Reset Network

Hibernate
Enter to confirm
Esc to cancel

Reset Network Menu
This function, which should only be used by authorized, fully
qualified technicians, resets the wireless network parameters to zero,
enabling nodes to look for a new controller in Association mode.

Wireless Network
4. New Node
5. Hibernate
6. Reset Network

CAUTION

88

Reset Network
Enter to confirm
Esc to cancel

This function resets the nodes; once reset, nodes may change
IDs, and thus render controller Events and Groups inoperable.

301C User Manual
Honeywell

M-510324
7/10

System Programming
Wireless Network Menu

Status Log Menu
The Status Log file, named wyymmddq.log, that will be recorded on
the SD card contains 27 columns of information (as in the sample
above) that correspond to each of the first 27 fields in the Nodes Menu.

Wireless Network
5. Hibernate
6. Reset Network
7. Status Log
NoLog

Status Log
Log

Status Log
Enter to confirm
Esc to cancel

The resulting file can then be copied to a computer and consulted or
printed, as needed.

Consolidate Route Menu
Although nodes will always look for the best route to the controller, this
command forces all nodes to search for the shortest communication
route, with the least hops, to the controller using an alternate parent.

Wireless Network
6. Reset Network
7. Status Log
NoLog
8. Consolidate Route

M-510324
7/10

Consolidate Route
VAL : 00060
MAX : 65535
MIN : 00000

301C User Manual
Honeywell

Consolidate Route
Enter to confirm
Esc to cancel

89

System Programming
Wireless Network Menu

90

301C User Manual
Honeywell

M-510324
7/10

BACnet/IP MODULE

BACnet/IP MODULE
(BIP option)

Specifications
Ethernet Port : 10/100-compatible with 10 Base-T interface, RJ-45
Visual Indicators :

Green LED
Yellow LED

LINK
ACT

Network Configuration: See 301C BACnet menu section.
BACnet/IP protocol
UDP Port: 47808. This value is not modifiable using the 301C.
The module has been developed as per ANSI/ASHRAE Standard 1352001 : BACnet®— A Data Communication Protocol for Building
Automation and Control Networks. The Data Link Layer option is per
BACnet/IP (Annex J).

http://www.ashrae.org/
BACnet Objects
BACnet objects represent any information available through the 301C
sub network. Each available value is represented by one object of a
specific type. There are currently 6 object types supported :
Analog Input
Analog Value
Binary Input
Binary Output
Binary Value
Device

M-510324
7/10

represented by ‘AI’
represented by ‘AV’
represented by ‘BI’
represented by ‘BO’
represented by ‘BV’
represented by ‘DEV’

301C User Manual
Honeywell

91

BACnet/IP MODULE

Analog Input
The Analog Input object type defines a standardized object whose
properties represent the externally visible characteristics of an analog
input, such as a gas sensor.
Supported properties for the Analog Input object type are :
Object_Identifier, Object_Name, Object_Type, Status_Flags,
Event_State, Reliability, Present_Value, Out_of_Service and Units.
Analog Value
The Analog Value object type defines a standardized object whose
properties represent the externally visible characteristics of an analog
value. An "analog value" is a control system parameter residing in the
memory of the BACnet Device, such as a gas alarm level.
Supported properties for the Analog Value object type are :
Object_Identifier, Object_Name, Object_Type, Status_Flags,
Event_State, Reliability, Present_Value and Units.
Binary Input
The Binary Input object type defines a standardized object whose
properties represent the externally visible characteristics of a binary
input. A "binary input" is a physical device or hardware input that can be
in only one of two distinct states, such as the 301ADI digital inputs.
Supported properties for the Binary Input object type are :
Object_Identifier, Object_Name, Object_Type, Status_Flags,
Event_State, Reliability, Present_Value, Polarity, Inactive_Text and
Active_Text and Out_of_Service.

92

301C User Manual
Honeywell

M-510324
7/10

BACnet/IP MODULE

Binary Output
The Binary Output object type defines a standardized object whose
properties represent the externally visible characteristics of a binary
output. A "binary output" is a physical device or hardware output that
can be in only one of two distinct states, such as a relay or a switchable
power output.
Supported properties for the Binary Output object type are :
Object_Identifier, Object_Name, Object_Type, Status_Flags,
Event_State, Reliability, Present_Value, Polarity, Inactive_Text,
Active_Text, Priority_Array, Relinquish_Default and Out_of_Service.
Binary Value
The Binary Value object type defines a standardized object whose
properties represent the externally visible characteristics of a binary
value. A "binary value" is a control system parameter residing in the
memory of the BACnet Device.
Supported properties for the Binary Value object type are :
Object_Identifier, Object_Name, Object_Type, Status_Flags,
Event_State, Reliability, Present_Value, Inactive_Text, Active_Text,
Priority_Array, and Relinquish_Default.
Device
The Device object type defines a standardized object whose properties
represent the externally visible characteristics of a BACnet Device.
There is only one Device object to represent the BACnet Module.
Supported properties for the Device object are : Object_Identifier,
Object_Name, Object_Type, System_Status, Vendor_Name,
Vendor_Identifier, Model_Name, Firmware_Revision,
Application_Software_Version, Protocol_Version, Protocol_Revision,
Protocol_Services_Supported, Protocol_Object_Types_Supported,
Object_List, Max_APDU_Length_Accepted, Segmentation_Supported,
APDU_Timeout, Number_Of_APDU_Retries,
Device_Address_Binding, Database_Revision, Local_Time,
Local_Date, UTC_Offset, Daylight_Savings_Status and
Out_of_Service.
M-510324
7/10

301C User Manual
Honeywell

93

BACnet/IP MODULE

Honeywell Products and BACnet Objects
Object Names
Object names are constructed in two parts, as follows:
Part one: The device display label (product name) for the network in
which the object resides. This value is editable only when
using the 301C controller.
Part two: Unique tag label among all the objects for the same device.
Ex : “301D2 CO2 AD:14.CO2” where ‘301D2 CO2 AD:14’ is the
device display label and ‘CO2’ is the unique tag label that identifies the
object as a CO2 sensor.
Vulcain Object Tag Labels

Table 1:
Tag Labels
‘Gas label’
.Alrm
Amin /Amax
Bmin /Bmax
Cmin /Cmax
relx
buzz
.outx
.AIx
.BIx
.RH
.Temp

94

Description
Gas sensor
Simple alarm level
Alarm level A and hysteresis
Alarm level B and hysteresis
Alarm level C and hysteresis
Relay output X (1 to 8)
Buzzer output
Output X (1 to 3)
Analog input X (1 to 16)
Binary Input X (1 to 12)
Relative Humidity sensor
Temperature sensor

301C User Manual
Honeywell

Object
Type
AI
AV
AV
AV
AV
BO
BO
BO or BV
AI
BI
AI
AI

M-510324
7/10

BACnet/IP MODULE
Object Table For Honeywell Network Devices
Objects residing in Honeywell network devices
Device GP2

301IRF

301EM

201T2/vulbus 90DM3R

.GAZ

.GAZ

.GAZ

.GAZ

.GAZ

.Amin

.Amin

.Amin

.Amin

.Alrm

.Amax

.Amax

.Amax

.Amax

.Bmin

.Bmin

.Bmin

.Bmin

.Bmax

.Bmax

.Bmax

.Bmax

.Cmin

.Cmin

.Cmin

.Cmin

.Cmax

.Cmax

.Cmax

.Cmax

.rel1

.rel1

.rel1 (snsr1) .rel1

.rel2

.rel2

.rel2 (snsr1)

.rel3

.rel3 (snsr1)
.rel4 (snsr1)

Objects

.out1
(snsr1)

M-510324
7/10

.out2
(snsr1)
.out3
(snsr1)

301C User Manual
Honeywell

95

BACnet/IP MODULE
Object Table For Honeywell Network Devices
Objects residing in Honeywell network devices
Device

301AP

301C

301R

301ADI

901T

.rel1

.rel1

.rel1

.AI1 to .AI16 .GAZ

.rel2

.rel2

.rel2

.BI1 to .BI12 .Amin

.rel3

.rel3

.rel3

.Amax

.buzz

.rel4

.rel4

.Bmin

.buzz

.rel5

.Bmax

.rel6

.Cmin

.rel7

.Cmax

Objects

.rel8

96

301C User Manual
Honeywell

M-510324
7/10

BACnet/IP MODULE
Object Table For Honeywell Network Devices
Objects residing in Honeywell network devices
Device

ECF9

S301RLC

301W

301RW

Std.Device*

.GAZ

.GAZ

.GAZ

.rel1

.GAZ

.Amin

.Amin

.Amin

.rel2

.Amin

.Amax

.Amax

.Amax

.rel3

.Amax

.Bmin

.Bmin

.Bmin

.rel4

.Bmin

.Bmax

.Bmax

.Bmax

.rel5

.Bmax

.Cmin

.Cmin

.Cmin

.rel6

.Cmin**

.Cmax

.Cmax

.Cmax

.rel7

.Cmax**

Objects

.rel8

* Std.Device refers to the following products: S301M, 420MDBS and
90DM4
** The values .Cmin and .Cmax apply only to the 90DM4.

M-510324
7/10

301C User Manual
Honeywell

97

BACnet/IP MODULE

Object Examples
In the first example, we see the CO2 gas sensor input for a 301D2
Vulcain network device:
Name : “301D2 CO2 AD:14.CO2”
Value :
600
Units :
PPM
Object : 1.AI2*
Description : Analog Input
* 1 is the 301C unique device instance, AI is the object type and 2 is the
unique instance of the object in this device. We identify this object as
“Analog Input 2 of BACnet device 1”.
In this example, we can see the output status for relay 2 of the same
Vulcain network device, but with a different device display label:
Name : “Floor 01 Sensor 02 .rel2”
Value :
OFF
Units :
Object : 1.BO4*
Description : Binary Output
*We identify this object as “Binary Output 4 of BACnet device 1”.
Example 3 where we can see the first 24V output status of a 301EM
Vulcain network device.
Name : “301EM CO AD:25.out1”
Value :
OFF
Units :
Object : 1.BV1
Description : Binary Value*
*We identify this object as “Binary Value 1 of BACnet device 1”.

98

301C User Manual
Honeywell

M-510324
7/10

Protocol Implementation Conformance Statement

Protocol Implementation Conformance
Statement
(Normative)

BACnet Protocol Implementation Conformance
Statement
Date : August 1, 2005
Vendor Name : Honeywell Analytics
Product Name : 301C -BIP
Product Model Number: N/A
Applications Software Version : 1.0
Firmware Revision : 1.0
BACnet Protocol Revision : 1.0
Product Description:

The 301C -BIP has a module that uses BACnet communication. As
such, the components of a Vulcain network can be connected to a
BACnet network via the 301C controller.
BACnet Standardized Device Profile (Annex L)

 BACnet Operator Workstation (B-OWS)
 BACnet Building Controller (B-BC)
 BACnet Advanced Application Controller (B-AAC)
 BACnet Application Specific Controller (B-ASC)
 BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)

M-510324
7/10

301C User Manual
Honeywell

99

Protocol Implementation Conformance Statement
List all BACnet Interoperability Building Blocks Supported (Annex K)

Data Sharing
 Data Sharing-ReadProperty-A (DS-RP-A)
 Data Sharing-ReadProperty-B (DS-RP-B)
 Data Sharing-ReadPropertyMultiple-A (DS-RPM-A)
 Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)
 Data Sharing-ReadPropertyConditional-A (DS-RPC-A)
 Data Sharing-ReadPropertyConditional-B (DS-RPC-B)
 Data Sharing-WriteProperty-A (DS-WP-A)
 Data Sharing-WriteProperty-B (DS-WP-B)
 Data Sharing-WritePropertyMultiple-A (DS-WPM-A)
 Data Sharing-WritePropertyMultiple-B (DS-WPM-B)
 Data Sharing-COV-A (DS-COV-A)
 Data Sharing-COV-B (DS-COV-B)
 Data Sharing-COVP-A (DS-COVP-A)
 Data Sharing-COVP-B (DS-COVP-B)
 Data Sharing-COV-Unsolicited-A (DS-COVU-A)
 Data Sharing-COV-Unsolicited-B (DS-COVU-B)
Scheduling
 Scheduling-A (SCHED-A)
 Scheduling-Internal-B (SCHED-I-B)
 Scheduling-External-A (SCHED-E-B)
Trending
 Viewing and Modifying Trends-A (T-VMT-A)
 Trending-Viewing and Modifying Trends-Internal-B (T-VMT-I-B)
 Trending-Viewing and Modifying Trends-External-B (T-VMT-E-B)
 Trending-Automated Trend Retrieval-A (T-ATR-A)
 Trending-Automated Trend Retrieval-B (T-ATR-B)

100

301C User Manual
Honeywell

M-510324
7/10

Protocol Implementation Conformance Statement

Network Management
 Network Management-Connection Establishment-A (NM-CE-A)
 Network Management-Connection Establishment-B (NM-CE-B)
 Network Management-Router Configuration-A (NM-RC-A)
 Network Management-Router Configuration-B (NM-RC-B)
Alarm and Event Management
 Alarm and Event-Notification-A (AE-N-A)
 Alarm and Event-Notification Internal-B (AE-N-I-B)
 Alarm and Event-Notification External-A (AE-N-E-B)
 Alarm and Event-ACK-A (AE-ACK-A)
 Alarm and Event-ACK-B (AE-ACK-B)
 Alarm and Event-Alarm Summary-A (AE-ASUM-A)
 Alarm and Event-Alarm Summary-B (AE-ASUM-B)
 Alarm and Event-Enrollment Summary-A (AE-ESUM-A)
 Alarm and Event-Enrollment Summary-B (AE-ESUM-B)
 Alarm and Event-Information-A (AE-INFO-A)
 Alarm and Event-Information-B (AE-INFO-B)
 Alarm and Event-LifeSafety-A (AE-LS-A)
 Alarm and Event-LifeSafety-B (AE-LS-B)
Device Management
 Device Management-Dynamic Device Binding-A (DM-DDB-A)
 Device Management-Dynamic Device Binding-B (DM-DDB-B)
 Device Management-Dynamic Object Binding-A (DM-DOB-A)
 Device Management-Dynamic Object Binding-B (DM-DOB-B)
 Device Management-DeviceCommunicationControl-A (DM-DCC-A)
 Device Management-DeviceCommunicationControl-B (DM-DCC-B)
 Device Management-Private Transfer-A (DM-PT-A)
 Device Management-Private Transfer-B (DM-PT-B)
 Device Management-Text Message-A (DM-TM-A)
 Device Management-Text Message-B (DM-TM-B)
 Device Management-TimeSynchronization-A (DM-TS-A)
 Device Management-TimeSynchronization-B (DM-TS-B)
 Device Management-UTCTimeSynchronization-A (DM-UTC-A)
 Device Management-UTCTimeSynchronization-B (DM-UTC-B)
M-510324
7/10

301C User Manual
Honeywell

101

Protocol Implementation Conformance Statement

 Device Management-ReinitializeDevice-A (DM-RD-A)
 Device Management-ReinitializeDevice-B (DM-RD-B)
 Device Management-Backup and Restore-A (DM-BR-A)
 Device Management-Backup and Restore-B (DM-BR-B)
 Device Management-List Manipulation-A (DM-LM-A)
 Device Management-List Manipulation-B (DM-LM-B)
 Device Management-Object Creation and Deletion-A (DM-OCD-A)
 Device Management-Object Creation and Deletion-B (DM-OCD-B)
 Device Management-Virtual Terminal-A (DM-VT-A)
 Device Management-Virtual Terminal-B (DM-VT-B)
Segmentation Capability :
 Segmented requests supportedWindow Size
 Segmented responses supportedWindow Size : Take maximum
Windows size supported by the other device
Standard Object Types Supported :

Analog Input
Analog Output
Analog Value
Binary Input
Binary Output
Binary Value
Device

For all objects
1) cannot be dynamically createable using Create
Object service
2) cannot be dynamically deletable using DeleteObject
sercice
3) No additionnal writable properties exist
4) No proprietary properties exist
5) No range restriction

Data Link Layer Options
 BACnet IP, (Annex J)
 BACnet IP, (Annex J), Foreign Device
 ISO 8802-3, Ethernet (Clause 7)
 ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
 ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)
 MS/TP master (Clause 9), baud rate(s):
102

301C User Manual
Honeywell

M-510324
7/10

Protocol Implementation Conformance Statement

 MS/TP slave (Clause 9), baud rate(s):
 Point-To-Point, EIA 232 (Clause 10), baud rate(s):
 Point-To-Point, modem, (Clause 10), baud rate(s):
 LonTalk, (Clause 11), medium:
 Other:
Device Address Binding :
Is static device binding supported? (This is currently necessary for twoway communication with MS/TP slaves and certain other devices.)
Yes  No
Networking Options
 Router, BACnet / Modbus.
 Annex H, BACnet Tunneling Router over IP
 BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices?
 Yes  No
Character Sets Supported
Indicating support for multiple character sets does not imply that they
can all be supported simultaneously.
 ANSI X3.4 IBM/Microsoft DBCS
 ISO 8859-1
 ISO 10646 (UCS-2) ISO 10646 (UCS-4)
 JIS C 6226
If this product is a communication gateway, describe the types of nonBACnet equipment/networks(s) that the gateway supports :

M-510324
7/10

301C User Manual
Honeywell

103

Specifications

Specifications
Power requirements 301C
Operating temperature range
Operating humidity range
Operating altitude
Network capacity

Communication
(length of lines)
Wireless communication
range:
Wireless communication
User interface
Visual indicators

Outputs
Output rating
Audible alarm
Time delays
Battery
Enclosure
Dimensions (HxWxD)
Certifications

M-510324
8/10

17-27 Vac, 50/60 Hz, 8.64 VA
18-36 Vdc, 350mA @ 24 Vdc (8.4 VA)
-20°C to 50°C (-4°F to 122°F)
0 to 95% RH (non-condensing)
Up to 3000 m (9843 ft)
Up to 96 transmitters, 32 per channel
Channels 1, 2 = Modbus and Vulbus
Channel 3 = Modbus only
Channel 4 = slave communication (i.e.
BACNet use)
Up to 609m (2,000 ft) per channel
T-tap maximum = 20m (65 ft) per t-tap,
overall total of 40m (130 feet)
30m (98.5 ft)
ISM worldwide, range 30 m indoor
Graphic 122 x 32 dot matrix backlit display
User friendly keypad
Power
Green LED
Alarm A, B, C Red LED
Fault
Amber LED
Tx
Amber LED
Rx
Green LED
4 DPDT relays
5A, 30Vdc or 250 Vac (resistive load)
65dBA at 1 m (3 ft)
Programmable Before and After delays
3 volt lithium battery
NEMA 4X, ABS-polycarbonate - indoor use
28 x 20.3 x 7cm (7.99” x 11.02” x 2.76”)
ANSI/UL 61010-1
CAN/CSA C22.2 No. 61010-1
ETL 116662

301C User Manual
Honeywell

105

Limited Warranty

Limited Warranty
Limited Warranty
Honeywell Analytics, Inc. warrants to the original purchaser and/or
ultimate customer ("Purchaser") of Vulcain products ("Product") that if
any part thereof proves to be defective in material or workmanship
within twelve (12) months, such defective part will be repaired or
replaced, free of charge, at Honeywell Analytics' discretion if shipped
prepaid to Honeywell Analytics at 4005 Matte Blvd., Unit G, Brossard,
Quebec, J4Y 2P4, in a package equal to or in the original container.
The Product will be returned freight prepaid and repaired or replaced if
it is determined by Honeywell Analytics that the part failed due to
defective materials or workmanship. The repair or replacement of any
such defective part shall be Honeywell Analytics' sole and exclusive
responsibility and liability under this limited warranty.
Re-Stocking Policy
The following restocking fees will apply when customers return products
for credit:
•

15% restocking fee will be applied if the product is returned within 1
month following the shipping date

•

30% restocking fee will be applied if the product is returned within 3
months following the shipping date

A full credit (less restocking fee) will only be issued if the product is in
perfect working condition. If repairs are required on the returned
product, the cost of these repairs will be deducted from the credit to be
issued.
No credits will be issued beyond the three month period.

M-510324
7/10

301C User Manual
Honeywell

107

Limited Warranty

Exclusions
A. If Gas sensors are part of the Product, the gas sensor is
covered by a twelve (12) month limited warranty of the manufacturer.
B. If gas sensors are covered by this limited warranty, the gas
sensor is subject to inspection by Honeywell Analytics for extended
exposure to excessive gas concentrations if a claim by the Purchaser is
made under this limited warranty. Should such inspection indicate that
the gas sensor has been expended rather than failed prematurely, this
limited warranty shall not apply to the Product.
C. This limited warranty does not cover consumable items, such
as batteries, or items subject to wear or periodic replacement, including
lamps, fuses, valves, vanes, sensor elements, cartridges, or filter
elements.
Warranty Limitation and Exclusion
Honeywell Analytics will have no further obligation under this limited
warranty. All warranty obligations of Honeywell Analytics are
extinguishable if the Product has been subject to abuse, misuse,
negligence, or accident or if the Purchaser fails to perform any of the
duties set forth in this limited warranty or if the Product has not been
operated in accordance with instructions, or if the Product
serial number has been removed or altered.

108

301C User Manual
Honeywell

M-510324
7/10

Limited Warranty

Disclaimer of Unstated Warranties
The warranty printed above is the only warranty applicable to this
purchase. All other warranties, express or implied, including, but not
limited to, the implied warranties of merchantability or fitness for a
particular purpose are hereby disclaimed.
Limitation of Liability
It is understood and agreed that Honeywell Analytics’ liability, whether
in contract, in tort, under any warranty, in negligence or otherwise shall
not exceed the amount of the purchase price paid by the purchaser for
the product and under no circumstances shall Honeywell Analytics be
liable for special, indirect, or consequential damages. The price stated
for the product is a consideration limiting Honeywell Analytics' liability.
No action, regardless of form, arising out of the transactions under this
warranty may be brought by the purchaser more than one year after the
cause of actions has occurred.

M-510324
7/10

301C User Manual
Honeywell

109

Centrale

301C
Manuel de l’utilisateur
M-510324
7/10

Avis et marques de commerce
Tous droits réservés par Honeywell International Inc.
Juillet 2010
Quoique cette information est présentée en bonne foi et est présumée exacte,
Honeywell décline la garantie tacite de la qualité marchande pour un emploi
particulier et offre aucune garantie exprès, è l’exception des conventions écrites
avec et pour ses clients.
Honeywell ne sera, sous aucune circonstance, responsable à qui que ce soit
pour des dommages spéciaux ou indirectes. Les informations et les
spécifications dans ce document sont susceptibles d’être modifiées sans
préavis.

Ce manuel traite de la version logicielle 3.086.

Honeywell Analytics
405 Barclay Blvd.
Lincolnshire, IL 60069

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

iii

Définitions des symboles
Le tableau suivant contient la liste des symboles utilisés dans ce
document pour indiquer certaine conditions :

Symbole

Définition
ATTENTION: Identifie une information demandant
une attention spéciale
Truc: Identifie un conseil ou un truc pour
l’utilisateur, souvent concernant une tâche
RÉFÉRENCE- INTERNE Indique une source
d’information supplémentaire à l’intérieur du
document.

ATTENTION

Indique une situation à éviter pouvant entraîner des
dommages au système ou la perte de travail
(documents) ou pouvant prévenir l’opération
normale du système.
ATTENTION : Indique une situation potentiellement
dangereuse qui peut entraîner des blessures
mineures ou modérées si pas évité. Peut
également signaler des actions dangereuses
ATTENTION: Un symbole sur l’équipement qui
réfère l’utilisateur à la documentation pour de plus
amples informations. Ce symbole apparaît à côté
des informations nécessaires dans le manuel.
AVERTISSEMENT : Indique une situation
potentiellement dangereuse qui peut entraîner des
blessures majeures ou la mort si pas évité.
AVERTISSEMENT Un symbole sur l’équipement
qui réfère l’utilisateur à la documentation pour de
plus amples informations. Ce symbole apparaît à
côté des informations nécessaires dans le manuel.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

v

INTRODUCTION ............................................................11
Utilisation ........................................................................................... 11
Réception et vérification .................................................................... 11
Note:Instructions d’installation ........................................................... 12
Directives de base ................................................................................. 12
Installation murale ................................................................................. 13

DÉTAILS DE CONNEXION ............................................14
•Connexions d’alimentation ............................................................... 16
•Connexions de communication ........................................................ 16
Note:Paramètres d'émetteurs spécifiques ........................................ 16
Note:Sortie relais ............................................................................... 17
Note:Instructions pour cavaliers ........................................................ 18

DÉMARRAGE ................................................................19
Premier démarrage ............................................................................... 19

Note:Enregistrement de données (sdcard) ....................................... 19
•Interface de programmation ............................................................. 20
•Fonctions du clavier ......................................................................... 20
•Definitions des DEL ......................................................................... 21
•Operation du système ...................................................................... 21

PROGRAMMATION DU SYSTÈME ...............................22
•Menu INFO Tx ................................................................................. 26
Menu Ident ............................................................................................ 27
Types de produit et types de sondes .................................................... 28
COM ...................................................................................................... 30
Echelle (1 et 2) ...................................................................................... 31
Détection ............................................................................................... 32
Affichage ............................................................................................... 33
Alarme A, B et C .................................................................................... 34
Entretien et Exploitation des Menus ...................................................... 35
Code d’Etat ............................................................................................ 36
Effacer Tx courant ................................................................................. 36
M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

vii

Note:Menu groupes ...........................................................................38
Créer des groupes .................................................................................39
Supprimer des groupes ..........................................................................39

•Menu événement .............................................................................40
Action .....................................................................................................42
Délais .....................................................................................................43

Délais mode latch ...................................................................44
Conditions ..............................................................................................45
Statut ......................................................................................................49

4.Menu acquisition .............................................................................50
Débuter et arrêter log even. ...................................................................52

Note:Menu copie ...............................................................................53
Configuration ..........................................................................................53
Paramètres ............................................................................................54
Journal Sys ............................................................................................55

•Menu config ......................................................................................56
Note:Menu Réseau ............................................................................62
7.Menu Tests......................................................................................67
Sequence de test ................................................................................... 69
Mode Normal .........................................................................................71
Mode Tx unique ..................................................................................... 71
Mode débogage .....................................................................................71
Mode Simulation ....................................................................................72

7.Menu BACNet .................................................................................73
Changer les valeurs BACNet ..................................................74
•Menu reseau sans-fil ........................................................................79
Parametres ............................................................................................80

Modifier le PAN ID ou le Canal RF .........................................81
Diagnostics ............................................................................................84
Noeuds ...................................................................................................85
Nouveau noeud...................................................................................... 90
Menu Hiberner .......................................................................................91
Menu RAZ reseau ..................................................................................91
Menu Log Statut .....................................................................................92
Menu Consolider Acces .........................................................................92
Spécifications .........................................................................................95
Configuration de réseau ........................................................................ 95
Protocole BACnet/IP ............................................................................. 95

Objets BACNet .................................................................................96
viii

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Entrée analogique .................................................................. 96
Valeur analogique .................................................................. 96
Entrée binaire ......................................................................... 97
Sortie binaire .......................................................................... 97
Valeur binaire ......................................................................... 97
Dispositif ................................................................................. 98
Produits Vulcain et objets BACnet ....................................................... 98

ÉNONCÉ DE CONFORMITÉ D'IMPLÉMENTATION DE
PROTOCOLE ...............................................................105
Description du produit ........................................................................ : 105

Options Couche liaison de données ..................................... 109
Association d'adresse de dispositif ...................................... 109
Options de réseautage ......................................................... 109
Jeux de caractères supportés .............................................. 109

SPÉCIFICATIONS ........................................................111
GARANTIE LIMITÉE ....................................................113
Garantie limitée ................................................................................... 113
Politique de Retour .............................................................................. 113
Exclusions ........................................................................................... 114
Limitation et exclusion de la garantie .................................................. 114
Dénégation de responsabilité d’autres garanties ................................ 115
Limitation de responsabilité ................................................................. 115

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

ix

Introduction
Utilisation

Introduction
La centrale 301C agit de centrale pour réseaux de détection de gaz,
offrant une surveillance continue sur un maximum de 96 unités (avec
un 301ADI) connectées. Puisque la centrale est configuré selon vos
besoins, l’installation demande simplement le montage et la connexion.
Aussitôt installée, la centrale vous permet de monitorer, d’ajuster ou de
configurer un réseau complet d’unités.
Le 301C comporte l’option du coordonnateur sans-fil qui permet à la
centrale de communiquer avec et de gérer les détecteurs de gaz sansfil (jusqu’à 60), tout en conservant toutes ses fonctionnalités
précédentes.

Utilisation
Le 301C est une centrale créée pour monitorer la totalité d’un réseau
de détection de gaz vingt quatre heures sur vingt quatre. La centrale
offre la possibilité d’enregistrement de données, de création de fichiers
journal pour toutes les concentrations et alarmes de transmetteurs aux
fins d’analyse. Ces unités sont également munies de fonctions de
groupes et de zones qui vous permettent d’interroger et de monitorer
certains groupes ou certaines zones de transmetteurs.

Réception et vérification
Lorsque vous recevez votre commande:
•
•
•

Vérifiez le colis pour assurer qu’il n’y a aucun dommage.
Ouvrez le colis avec soin.
Trouvez le bordereau de marchandise ou le bon de commande et
vérifiez que tout les articles apparaissant sur la liste sont bien dans
le colis et ne sont pas endommagés.

Note: Si le colis ou la marchandise est endommagé, veuillez vous
référer à la section Garantie à la fin de ce guide.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

11

Introduction
Instructions d’installation

Instructions d’installation
Directives de base
Suivre les instructions minutieusement pour assurer le bon
fonctionnement de l’équippement. À défaut de respecter les directives,
Honeywell Analytics sera libéré de toute responsabilité :
•
•
•
•
•

12

Installer les unités dans des endroits facilement accessible pour
l’entretien
Éviter les endroits où les unités pourraient être exposées aux
vibrations
Éviter d’installer les unités près de sources de perturbations
électromagnétique
Éviter d’installer les unités dans des endroits sujets à de grandes
variations de température
Consultez les réglementations et normes locales en vigueur, car
celles-ci ont un impacte sur le choix d’emplacement.

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Introduction
Instructions d’installation

Installation murale
Nous recommandons d’installer les centrales à 1.5m (5 pi.) du sol.
Mesurer les distances tel qu’indiqué :
Ø .5cm
¼”

17.4 cm
6 13/32”

26.8 cm
10 9/16”

1.5m
5’

•
•
•
•

Distance en hauteur 6 13/32” entre les trous
Distance en largeur entre les trous 10 9/16”
Perçer les trous 1/4 po
Fixer la centrale avec les vis appropriées

Le câblage de l’unité doit être enfiler dans les trous des pastilles
poinçonnées (knock-out) situées en dessous de l’unité.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

13

Détails de connexion
Instructions d’installation

Détails de connexion
Le dessin ci-dessous démontre la connexion pour la centrale. Les
descriptions de connecteurs et de connexions se trouvent dans les
pages suivantes. Ce module permet à la centrale de communiquer
avec et de gérer les détecteurs de gaz sans-fil 301W.
Les détails de câblage, alimentation, capacités, etc. se trouvent à la
section Spécifications de ce guide.

(ne pas utilser)

14

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Détails de connexion
Instructions d’installation

Les connecteurs, ou ports, de la carte (PCB) permettent d’effectuer la
connexion du câblage à la centrale. Le câblage inclut l’alimentation, la
communication, la connexion BACNet et les relais, chacun avec une
position (et un chiffre) assignée sur la carte :
J22 Alimentation :
J23, J24 Entrées
Communication :

Sorties relais 1-4 :
Cavalier SHDN :

EOL Resistors 1-4 :

M-510324
7/10

Connecter l’alimentation à la centrale (voir
Connexions d’alimentation pour les détails)
Connecter les câbles de communication aux
canaux 1 à 3. Le canal 4 est utilisé pour
communication esclave de Modbus
Selon la configuration désirée, connecter le
câblage soit aux bornes N.O ou N.C.
Placer le cavalier d’interruption d’alimentation
sur les connecteurs pour réinitialiser le
système.
Placer le cavalier sur les connecteurs pour
créer une connexion et atténuer les échos de
communication.

Manuel de l’utilisateur 301C
Honeywell

15

Détails de connexion
Connexions d’alimentation

Connexions d’alimentation
La centrale 301C nécessite une plage d’alimentation de 17-27 Vca, 50/
60 Hz (8.64 VA), 18-36 Vcc, 350 mA @24 Vcc (8.4 VA). La polarisation
n’importe pas, que ce soit en mode CA ou CC. Le système doit être mis
à la terre sur le transformateur et un circuit dédié doit être utilisé.

Connexions de communication
Les câbles de communication doivent être mis à la terre sur le terminal
blindé avec les fils torsadés et blindés paire Belden 2-24 AWG #9841
(ou équivalent).
Le câblage de réseau peut atteindre jusqu’à 609 m (2000 pi.) par canal.
La longueur d’une dérivation peut atteindre 20 m (65 pi.), jusqu’à un
maximum de 40m (130 pi.) pour toutes les dérivations.
Note: Canal 4 est le port de communication esclave : aucun
transmetteur ne peut y être connecté. Ex. : Canal 4 peut être
utilisé pour la connexion (esclave) BACnet.
Tous les dispositifs sans fils associés à la centrale seront
automatiquement détectés et utiliseront les protocoles de
communication sans fils pour communiquer avec la centrale.

Paramètres d'émetteurs spécifiques
Les émetteurs Sensepoint XCD de Honeywell doivent être configurés
pour un débit de 9 600 bauds, avec une adresse unique et sans
aucune parité, tandis que les émetteurs universels XNX de Honeywell
doivent être configurés pour un débit de 9 600 bauds et avec une
adresse unique (la parité étant toujours paire pour ce type
d'émetteurs). Vous trouverez des informations sur la configuration de
chaque émetteur dans le manuel technique associé.

16

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Détails de connexion
Sortie relais

Sortie relais
La sortie relais supporte jusqu’à 5A à 30 Vcc ou 250 Vca (charge
résistive seulement). Les relais peuvent activer les alarmes sonores et
les lampes stroboscopiques. Consulter le dessin pour instructions de
connexion. Chaque relais est configuré avec des valeurs par défaut,
cependant, la configuration des relais peut être modifiée depuis le
menu de programmation de la centrale.

SORTIES RELAIS
6

4

5

2

3

Normalement 3+5
ouvert
4+6
Normalement 1+3
1 fermé
2+4

RISQUE DE CHOC ÉLECTRIQUE

Si le relais est réglé à Normalement fermé, le relais est mis sous
tension en même temps que la centrale et le dispositif connecté au
relais est en fonction. Le relais se fermera lorsque la condition d’alarme
précisée est atteinte.
Si le relais est réglé à Normalement ouvert, le relais demeure fermé
lors de la mise sous tension de la centrale. Le dispositif connecté au
relais fonctionnera seulement lorsque la condition d’alarme précisée est
atteinte.
Note: Ces fonctions sont inversées lorsque le mode de sécurité
intégrée (Failsafe) est activé sur la centrale.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

17

Instructions pour cavaliers

Instructions pour cavaliers
Les divers cavaliers de la carte (PCB) permettent d’effectuer certaines
opérations manuellement :
EOL 1-4 : Permet l’ajout de cavaliers de fin de ligne pour améliorer les
signaux de communication. Mettre le cavalier en position R
pour activer la terminaison fin-de-ligne. (Position R offre une
terminaison à résistance, tandis que RC offre une
terminaison de condensateur.)
SHDN : Permet de réinitialiser ou de temporairement couper
l’alimentation de la centrale. Cette fonction est utile pour
effectuer des ajustements au câblage du système
(alimentation interrompue pour sécurité).
Relays
Permettent d’effectuer des tests sur les relais sans aucun
J29-J32 : impact sur les événements.

18

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Démarrage
Enregistrement de données (sdcard)

Démarrage
Quoique la centrale est configurer selon vos besoins, la programmation
peut toujours être modifiée par l’entremise de ses menus. Cette section
du manuel vous guidera dans les options du menu de programmation.

Premier démarrage
Assurer que tout le câblage est terminé et effectué selon les
spécifications et les détails de connexion avant de mettre la centrale
sous tension. Lorsque tout est sécuritaire, enlever le connecteur du
cavalier SHDN pour alimenter l’unité (il y aura un délai de quelques
secondes).

Enregistrement de données (sdcard)
L’option d’enregistrement de données (DLC) de la centrale collecte
automatiquement les données et les enregistre sur une carte mémoire
Flash (SDcard). Si la mémoire de la carte atteint sa capacité :
•
•
•

L’enregistrement des données s’arrête
Aucun avis n’est affiché à l’écran
Le DEL de la carte clignote (le boîtier doit être ouvert pour le voir)

Consulter la section Acquisition pour de plus amples détails sur le
démarrage et l’arrêt de la fonction enregistrement de données.
ATTENTION

M-510324
7/10

Toujours désactiver la fonction d’enregistrement de données
avant d’enlever la carte mémoire. Jamais enlever la carte
lorsque le DEL est allumé.

Manuel de l’utilisateur 301C
Honeywell

19

Démarrage
Interface de programmation

Interface de programmation
Le panneau avant du 301C comporte un clavier de boutons poussoirs
puis des indicateurs DEL.
Panneau 301C

Fonctions du clavier
La centrale comporte 7 touches de clavier, soit :
Flèches : Utilisées pour naviguer les divers menus de programmation
(haut, bas, gauche, droite), ou pour ajuster le contraste de
l’affichage (appuyer et maintenir enfoncé une touche de
flèche (haut = plus clair, bas=plus sombre). Relâcher lorsque
le contraste est satisfaisant.
ESC :
Permet de quitter un menu de programmation ou pour
annuler une entrée ou une modification.
Enter :
Permet d’accéder au menu de programmation et de modifier
(valider) les champs de configuration.
Silence : Désactive l’alarme sonore de la centrale.

20

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Démarrage
Definitions des DEL

Definitions des DEL
La centrale comporte 7 DEL indiquant le statut de chaque fonction :
Alarm A : Le DEL rouge clignotant indique qu’un événement est activé.
Le DEL rouge continu indique qu’un ou plusieurs
transmetteurs ont atteint un niveau d’alarme programmé.
Alarm B Le DEL rouge indique qu’un ou plusieurs transmetteurs ont
et C :
atteint un niveau d’alarme programmé
Power : Le DEL vert indique que l’unité est sous tension et
fonctionnelle
Fault :
Le DEL jaune indique une faute (de communication,
d’entretien ou un problème avec l’unité)
Tx :
Le DEL jaune clignotant indique que la centrale transmet des
requêtes sur le canal de communication.
Rx :
Le DEL vert clignotant indique que la centrales reçoit des
données.
Les fonctions sont liées aux paramètres configurés dans la centrale, ce
que nous discuterons dans la section suivante.

Operation du système
Le système peut opérer en quatre (4) modes différents permettant
d’utiliser, d’analyser, de déboger et de simuler les actions du système.
Ces modes sont : Normal, Tx simple, Débogage et Simulation. Le
mode d’opération par défaut est Normal. Les autres modes sont
accessible par le menu de programmation Tests (option 8 du Menu
principale).
Note: Les services du systèmes peuvent êtres interrompus par
certaines des opérations du menu.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

21

Programmation du système
Operation du système

Programmation du système
Le mode de programmation Normal offre huit options de menu, tous
accessibles du menu principale :
Info Tx :
Groupes :
Evene :
Acqui :
Copy :

Config :
Network :
Tests :

BACNet:
Wireless:

Permet de configurer les paramètres des
transmetteurs
Permet de configurer des groupes de transmetteurs
Permet de configurer des événement et les actions
liées aux événements
Permet d’activer ou de désactiver la fonction
d’enregistrement de données
Permet de copier des données ou des paramètres de
la centrale à un ordinateur (et vice-versa) ou de
transmetteur à transmetteur
Permet de régler les paramètres du système et de
modifier le mot de passe.
Permet d’éffectuer des actions sur le réseau Vulcain
et de consulter les statistiques de communication.
Permet d’éffectuer un essais sur les entrées et sorties
(communication, événement, etc) et de valider
l’opération de divers paramètres.
Permet de configurer les paramètres BACNet d’un
dispositif
Permet de configurer, monitorer et de modifier un
réseau de détecteurs de gaz sans-fil.

Note: L’accès aux fonctions est protégé par mot de passe (par défaut
est 2967).

22

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Operation du système

Lorsqu’en opération normale, le système affiche l’écran ci-dessous et
déroule des écrans d’informations pour chaque dispositif connecté à la
centrale:
301C
Ad: 1
2006-05-17

Gr:0

Ver. 3.0
Ev:0
13:18:18

Si un ou plusieurs appareils connectés à la centrale sont en mode
d’alarme, la centrale affichera seulement l’écran principal et les écrans
pour les appareils en mode d’alarme. Le cas échéant, il est nécessaire
d’utiliser les flèches pour dérouler les écrans de tout autre dispositif.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

23

Programmation du système
Operation du système

L’écran d’information affiche également des icônes représentant
certaines fonctions. Voici la liste des icônes et leurs descriptions :

Icône

Description
BACNet : Indique la présence d’un module BACNet en
communication avec la centrale.
Erreur BACNet : Indique la présence d’un module BACNet, mais
que la communication avec la centrale est en faute (erreur)
Débogage : Indique que la centrale est en mode débogage
(modes de TX unique, Débogage ou Simulation). SIM apparaît
avec cette icône lorsque en mode de simulation.
Log : Indique que soit le « Log Tx » ou le « Log even » est activé.
Erreur de log : Indique qu’une erreur est survenue lors de
l’enregistrement de Tx ou Even. Toutes fonctions
d’enregistrements sont arrêtées.
SDC : Indique la présence d’une carte mémoire (SDcard) en
fonction. L’icône se rempli (de blanc à noir) selon la quantité de
mémoire utilisée. Une icône blanche indique une mémoire vide
et une icône noire indique une mémoire pleine.
Erreur SDC : Si ce symbole persiste pendant plus de 5
secondes, une carte SD est présent mais ne fonctionne pas
correctement.
Réseau sans-fil : Indique qu’un coordonnateur de réseau sans-fil
(module de communication sans-fil) est présent et en
communication avec la centrale.
Réseau sans-fil : Indique qu’un coordonnateur de réseau sans-fil
(module de communication sans-fil) est présent, mais que la
communication avec la centrale est en faute.

24

Manuel de l’utilisateur 301C
Honeywell

M-510324
8/10

Programmation du système
Operation du système

Puisque les fonctions de programmation de la centrale sont protégées
par mot de passe, il est nécessaire d’accéder à l’écran de mot de
passe :
•
•
•
•

Appuyer sur Enter pour afficher l’écran « Mot de passe »
Utiliser les flèches haut ou bas pour augmenter ou diminuer la
valeur du premier chiffre
Utiliser la flèche de droite pour passer au prochain chiffre
Lorsque tous les chiffres sont exactes, appuyer sur Enter pour
valider le mot de passe et accéder aux fonctions de programmation.
Mot de passe
____

Le premier des écrans MENU apparaît. Utiliser les flèches pour
naviguer les divers écrans. Lorsque la fonction désirée est affichée,
déplacer le curseur (petite flèche à l’écran) à gauche de l’option puis
appuyer sur Enter pour y accéder.

MENU
1. InfoTx
3. Evene
2. Groupes
4. Acqui

MENU
5. Copie
6. Config

7. Reseau
8. Tests

MENU
9. BACNet
10. Reseau sans-fil

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

25

Programmation du système
Menu INFO Tx

Menu INFO Tx
INFO Tx est l’option de menu dédiée aux informations de
transmetteurs et contient plusieurs autres options qui peuvent varier
selon l’adresse (ou le type) d’appareil. Certains appareils afficheront
les options Tx INFO suivantes :
Ident :

COM :

Permet de consulter ou modifier
l’information d’identification de
la composante de réseau.
Permet de consulter ou de
modifier le protocole de
communication

Detection
Permet de visionner ou de
ou Echelle(1)modifier la plage de détection
et Echelle(2): et l’unité de mesure

Affichage :

Permet de consulter ou de
modifier l’identification (nom)
d’une composante

Alarmes:

Seuils d'alerte permettra d'être
visionnées et parfois changé. Il
ne peut y avoir des variations
importantes dans cet écran en
fonction de l'émetteur de type.

Codes
d’Etat:

Indique les codes d’états aux
fins de dépannage (dans les
valeurs hexadécimales)

Effacer ou
en cours Tx: Efface ou modifie l'adresse Tx
26

Manuel de l’utilisateur 301C
Honeywell

001



001





INFO Tx 001
- Detection plage: ( ) - ( ) . ( )
unte: ppm





1. INFO Tx 001
- Echelle(1) MAX
01000
MIN
00000





1. INFO Tx 001
- Echelle(2) Facteur
00010
Unites
%





1. INFO Tx 001 
- Affichage edition
(20car .max)



INFO Tx 001 
- Alarme B MIN
MAX
0 . 00ppm
0 . 00ppm



1. INFO Tx 001 
- Alarme C MIN
MAX
0 . 00ppm
0 . 00ppm



INFO Tx 001 
- Code d’Etat Etat Tx:
---Etat Sonde:
----

1.

INFO Tx
- Ident -

(?)
Aucune Sonde




1.

INFO Tx
- COM Aucun Tx

1.

1.

1.

1.

INFO Tx

001

Effacer Tx courant
Changer l’adresse

M-510324
7/10

Programmation du système
Menu INFO Tx

Menu Ident
Le menu Ident, ou identification, permet de consulter ou de modifier
l’identification de réseau de la composante sélectionnée :
1. InfoTx
-Ident-

001

NotVul
CO2 (IR)

La partie supérieure droit de l’écran affiche l’adresse de réseau de la
composante. Sélectionner le champs pour inscrire l’adresse à consulter
(si elle est connue) :
•
•
•
•

Utiliser les flèches pour déplacer le curseur à la gauche de
l’adresse
Appuyer sur Enter (l’adresse est en mode édition lorsqu’elle
clignote)
Utiliser les flèches haut et bas pour augmenter ou diminuer la
valeur
Appuyer sur Enter pour valider l’adresse et afficher les
informations de cette composante.

La partie inférieure de gauche affiche le nom du transmetteur (ex. :
301D2 - nom du produit) et le type de sonde (ex. : CH4 - méthane).
Ces valeurs peuvent également être modifiées pour le type de produit
Vulbus ou groupe:
Programmer ou modifier le type de produit ou de sonde
•
•
•

Utiliser les flèches pour déplacer le curseur à la gauche du champ
de produit ou de sonde.
Appuyer sur Enter pour sélectionner le champ (en mode édition
lorsque le champs clignote)
Utiliser les flèches pour dérouler la liste de types de produit ou de
sondes et appuyer sur Enter lorsque le produit ou la sonde
approprié est affiché.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

27

Programmation du système
Menu INFO Tx

Types de produit et types de sondes
Voici une liste de tous les types de produits (preprogrammés)
disponibles à partir de l’option -Ident- du menu INFO Tx.

Types de produit
Adresses 1-96

VA301D2
90DM3R
VA301IRF
IRT100
EC-F9
VA201T2
VA301T
GsPnt
RgRt3

VA301AP
VASQN8X
VA301EM
VA301EMRP
GsPnt2
S301RLC
(Std.Device)*
VA901T

XNX
XCD
VA201R
VA201T
90DM2
VA201D
VA301D
NotVul

Types de produit
Adresses 97-120
Adresses 121-170
301ADI
(?)

(?)
301W
301RW
301RPT

* Le produit « Std.Device » comprend les produits suivants: S301M,
90DM4, 420MDBS et 301ADI.
Note: Lorsque le type de produit est un groupe, les autres écrans INFO
TX ne seront pas disponibles (puisque chaque produit à déjà été
configuré dans la centrale). Seul les écrans Ident, Affichage et
Effacer Tx courant seront disponibles.
28

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu INFO Tx

Voici une liste de tous les types de sondes (preprogrammés)
disponibles à partir de l’option -Ident- du menu INFO Tx
Types de sondes
CH4
CO
NH3
NO2
HCL
R11
R12
R22
R134A
R125
R123
F2
HF
Comb

CH4
CO
CO
H2
SO2
H2S
ETO
NO
Cl2
SIH4
HCN
O3
HBr
BCl3

COCl2
B2H6
H2
AsH3
ClO2
PH3
CO
Unknown IR sensor
Comb (IR)
R11 (IR)
R12 (IR)
R22 (IR)
R134A (IR)
R125 (IR)

R123 (IR)
Comb (IR)
CO2 (IR)
CO2 (IR)
R245A (IR)
FE227 (IR)
R404A (IR)
R507A (IR)
R401A (IR)
R13B1 (IR)
R23 (IR)
No sensor
*

La liste de type de sonde s’applique aux adresses 1 à 96 et ne dépend
pas de la sélection de type de produit. Les dispositifs dans la plage
d’adresses de 97 à 170 affichent un identificateur BACNet.
* Un type de produit supplémentaire, intitulé « Groupe », représente les
groupes créés dans le menu Groupe de la centrale. Lors du
déroulement dans la liste de types de produits disponible, ce type
apparaîtra pour chaque groupe créé (Groupe 1, Groupe 2, Groupe 3,
etc.). Si le type de produit sélectionné est un groupe, les types de
sondes disponibles seront uniquement MIN, MAX et MOY.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

29

Programmation du système
Menu INFO Tx

COM
Cet écran affiche le protocole de communication de la composante
sélectionnée pour les adresses de 1 à 96. Le protocole de chaque
transmetteur est défini par la centrale (voir la section Auto-configuration
du réseau)..
1. InfoTx
-COMMdbs RTU 8D 1S EP
9600 bauds

001

Si un transmetteur est compatible avec plusieurs protocoles, il est
possible de sélectionner un autre protocole parmi les options
suivantes :
•
•
•
•
•

Vulbus
Mdbs ASCII 7D 2S NP 9600 bauds
Mdbs RTU 8D 2S NP 9600 bauds
Mdbs RTU 8D 1S NP 9600 bauds
Mdbs RTU 8D 1S OP 9600 bauds

Lorsqu’un transmetteur est configuré avec le protocole de
communication Modbus, le transmetteur envoi automatiquement les
paramètres de programmation à la centrale.
Note: Les paramètres de transmetteurs Vulbus doivent être configurer
manuellement.

30

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu INFO Tx

Echelle (1 et 2)
Ces menus apparaîssent uniquement pour certains dispositifs. Echelle
(1) permet de modifier la plage de détection, minimum et maximum,
pour l’appareil sélectionné.
1.

INFO Tx
-Echelle(1)Max
00250
Min
00000

121

Echelle (2) permet de configurer le facteur de division de la plage (entre
0 et 65535) et de modifier l’unité de mesure pour la plage sélectionnée.
1.

INFO Tx
121
-Echelle(2)Facteur
00001
Unites
ppm

Le facteur permet des limites de plages plus précises pour la détection.
En divisant la valeur de plage maximum dans le premier écran Echelle
(250 dans cet exemple) par 10, il est possible de détecter une valeur de
plage de 25.0.
Les « Unités » permettent de régler l’unité de mesure de chaque
appareil :
°F
°C
%RH
mV
V
mA
%
ppm

M-510324
7/10

Règle l’unité de mesure en degrés Farenheit
Règle l’unité de mesure en degrés Celcius
Règle l’unité de mesure au pourcentage d’humidité relative
Règle l’unité de mesure du point en millivolts
Règle l’unité de mesure du point en volts
Règle l’unité de mesure du point en milliamps
Règle l’unité de mesure du point au pourcentage du gaz
Règle l’unité de mesure du point en parties par million du
gaz

Manuel de l’utilisateur 301C
Honeywell

31

Programmation du système
Menu INFO Tx

Détection
Le menu Détection (disponible uniquement pour les adresses de 1 à
96) affiche la plage de détection (plage: 0 à 0.00) ainsi que l’unité de
mesure (unité : %) pour le transmetteur sélectionné. La plage de
détection est entre 0 et la valeur maximale (0.00) et l’unité de mesure
est soit ppm ou pourcent (%). Si le transmetteur utilise le protocole
Modbus, les paramètres de détection sont définis de façon automatique
lors de la configuration du réseau et ne peuvent être modifiés. Les
protocoles Vulbus doivent être définis par une programmeur.
Le menu de détection n’est pas disponible pour les appareils 301R ou
301AP.
1. InfoTx
-Detectionplage: 0-0.00
unite: %

001

Programmer ou modifier la plage ou l’unité de détection :
•
•
•

32

Utiliser les flèches pour déplacer le curseur à l’option plage ou
unité
Appuyer sur Enter et utiliser les flèches haut et bas pour
augmenter ou diminuer la valeur
Appuyer sur Enter pour valider la valeur désireé

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu INFO Tx

Affichage
Cette option permet de donner une étiquette ou un nom à la
composante sélectionnée (transmetteur, relais et annonciateurs).
L’étiquette peut contenir jusqu’à 20 caractères, incluant les espaces (ex.
: CHAMBRE GICLEURS). Les étiquettes de transmetteurs Modbus
sont assignés par défaut et sont composés du nom de la composante,
le type de sonde et l’adresse.
Les étiquettes de transmetteur Vulbus contiennent 20 espaces blancs.

edition
301D2

M-510324
7/10

1. INFO Tx
001
-Affichage(20 car.max)
CH4
Ad001

Manuel de l’utilisateur 301C
Honeywell

33

Programmation du système
Menu INFO Tx

Alarme A, B et C
Puisque les écrans d’affichage sont identiques pour chacun des
alarmes, ils ont été regroupés aux fins de ce manuel. Cependant,
chaque alarme doit être configuré séparément selon vos besoins.
Cette option permet de configurer des niveaux d’alarme minimum et
maximum pour les alarmes A, B et C. Ceci crée une plage de
tolérance où aucune action n’est effectuée. Toutefois, si les
concentrations de gaz dépassent le niveau maximum, un alarme est
activé. L’alarme ne sera pas désactivé avant que la concentration de
gaz revienne en dessous du niveau minimum précisé.
•
•
•
•

Utiliser les flèches du clavier pour déplacer le curseur à la gauche
de soit MIN ou MAX
Appuyer sur Enter pour sélectionner le champs à modifier
Utiliser les flèches haut et bas pour augmenter ou diminuer la
valeur
Appuyer sur Enter pour valider la valeur affichée

Ceux-ci sont des écrans typiques:

1. INFO Tx

026

-Alarme BLevel
60.0 %LEL

Typiques de screen pour la visualisation des alarmes A ou B de XCD et
XNX transmetteurs.

1. INFO Tx

001

-Alarme A-

MIN
0.00%

MAX
0.00%

Typiques de screen pour la visualisation ou changer des alarmes A, B,
ou les seuils C seuils sur d'autres transmetteurs.

34

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu INFO Tx

Entretien et Exploitation des Menus
Ces fonctions varient selon le type d'émetteur. Ces écrans montrent le
temps total du dispositif a été mis en service et le temps restant jusqu'à
la prochaine calibration nécessaires ou de remplacement.
1. INFO Tx
001
-Entretien4002h en fonction
15514h avant entr.

1. INFO Tx
121
-Temps d’OperationTemps de Vie: 00000
Depuis calib: 00730



M-510324
7/10

1. INFO Tx 026
- Temps d’operation Sensor life left:
1804 days

Manuel de l’utilisateur 301C
Honeywell



35

Programmation du système
Menu INFO Tx

Code d’Etat
Cet écran affiche l’état de la transmission (Tx) ou du noeud (seulement
pour les appareils sans-fil) et l’état de la sonde pour l’adresse du
dispositif sélectionné, en valeurs hexadécimales. Cet écran est aux fins
d’informations seulement; les données affichées ne peuvent pas être
modifiées.
1. INFO Tx

026

-Code d’EtatEtat Tx:
0000
Etat Monitor: 0001

L'étalage typique pour X ou Y

1. INFO Tx
-Code d’EtatEtat Tx:
12FAh
Etat Sonde: 4407h

121

Étalage typique pour d'autres transmetteurs
Note: L’écran Code d’Etat contient des informations importantes pour
les techniciens qualifiés lors du dépannage.

Effacer Tx courant
Cette fonction permet de supprimer la configuration (InfoTx seulement)
de la composante sélectionnée.

1. INFO Tx

001

Effacer Tx courant
Changer l’adresse

Note: Cette fonction efface seulement les données InfoTx. Aucune
autre information n’est effacée.

36

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu INFO Tx

L’option Changer l’adresse permet de modifier l’adresse d’un dispotif :
•
•
•

Utiliser les flèches pour dérouler à Changer l’adresse pui appuyer
sur Enter pour sélectionner
À l’écran suivant, dérouler à l’adresse puis appuyer sur Enter pour
sélectionner
Utiliser les flèches haut ou bas pour augmenter ou diminuer la
valeur puis appuyer sur Enter pour valider la nouvelle adresse.

L’option Changer l’adresse est seulement disponible pour les adresses
de 1 à 96 et s’il y a un appareil Modbus connecté.
Si l’adresse est valide, l’écran affichera « En cours... ».
Si l’adresse est invalide, l’écran affichera « Tx invalide » et reviendra à
l’écran Changer l’adresse (il n’est pas possible de changer l’adresse de
dispositifs GasPoint).
Un dernier écran affichera soit « Succes » ou « Erreur » (en cas
d’erreur, recommencer le processus).

1. INFO Tx

001

Effacer Tx courant
Changer l’adresse
1. INFO Tx
Change a:

001

001

1. INFO Tx

001

En cours...

Note: Si une adresse est changée à une adresse déjà associé à un
dispositif, les données existantes seront écrasées. Les clients
doivent connaître les adresses attribuées de leurs réseaux et
porter une attention spécial lors de changement d’adresse.
Ne pas oublier de supprimer l’adresse d’origine pour éviter toutes
duplications de données.
M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

37

Programmation du système
Menu groupes

Menu groupes
La programmation de groupes de transmetteurs permet de regrouper
des unités, ce qui permet d’agir (événements) en réponse à un groupe
d’unités plutôt que sur chaque unité, individuellement.

MENU
1. InfoTx
3. Evene
2. Groupes
4. Acqui

2. GROUPE
001
 [----] [----] [----]
[----]
[----] [----] [----]
vider les groupes

Un groupe est un bloc contenant les adresses de chaque transmetteurs
du groupe.
Les groupes sont affichés sur une seule ligne; si le groupe contient plus
de quatre composantes, il faudra utiliser les flèches gauche et droite
pour visionner la liste de tous les transmetteurs du groupe (puisque un
écran peut contenir seulement 20 caractères).
Le curseur de l’écran Groupe est représenté par les parenthèses
clignotantes (). Les informations entre les parenthèses peuvent
être modifiées.

38

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu groupes

Créer des groupes
•
•
•
•
•
•

•
•

Utiliser les flèches pour déplacer le curseur à la gauche du numéro
de groupe
Appuyer sur Enter puis changer le numéro
Appuyer sur Enter pour valider (créer)
Utiliser les flèches pour placer le curseur sur une ligne de groupe et
appuyer sur Enter
Le champ est en mode édition lorsque le  clignote
Uitliser les flèches haut et bas pour dérouler dans la liste d’unités
connectées à la centrale jusqu’à l’obtention de l’adresse
appropriée.
Appuyer sur Enter pour valider l’adresse.
L’adresse est ajouter au groupe et le curseur est déplacé vers la
droite.

Répéter le processus pour ajouter tous les transmetteurs désirés
(jusqu’à 126 par groupe). L’adresse de chaque transmetteur configuré
dans le menu InfoTx est disponible pour créer des groupes.
Note: Les groupes créés dans ce menu apparaîtront dans la liste de
types de produits (menu INFO Tx, option Ident) et seront
identifiés « Groupe xx » (xx est le numéro assigné au groupe lors
de la création).

Supprimer des groupes
La commande vider les groupes permet de supprimer tous les groupes
configurés dans la centrale.
Pour supprimer des groupes individuellement :
•
•

•

Afficher le premier transmetteur du groupe
Sélectionner le transmetteur (l’adresse clignote) et utiliser les
flèches pour dérouler les options et sélectionner  (l’option
 supprime l’entrée et l’option  indique la fin du bloc.
Appuyer sur Enter et le groupe est vidé.

Cette procédure permet de supprimer un, plusieurs ou tous les
transmetteurs du groupe.
M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

39

Programmation du système
Menu événement

Menu événement
Quoique la centrale est expédiée avec des configurations d’événement
par défaut (exemple ci-dessous), le menu Évenement offre la flexibilité
de modifier les paramètres. La programmation d’événement permet de
définir des actions précises :
Action :

Quelle action sera activée si les critères configurés
sont atteints
Delais :
Définition du délais à attendre avant de démarrer
une action et à attendre après qu’un événement soit
revenu à normal avant de remettre la sortie en état
normal
Conditions :
ET, OU ou --- (aucun); sont les opérandes
permettant un contrôle précis d’un événement
Periode couverte :Définit la période durant laquelle l’événement est
valide (actif)
Statut : active : Active ou désactive un événement
Base de donnee: Permet d’effacer l’évenement sélectionné ou
d’effacer tous les évenements.

40

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu événement

3. EVENEMENT
-ActionCible:
Ctrl
Relais: #01

001

3. EVENEMENT
-DelaisAvant:
99min
Apres:
01min

001

3. EVENEMENT
1/3
Gr036
=
2.01%

001
ET

3. EVENEMENT
-Periode couverteToute la journee
Toute la semaine

001

3. EVENEMENT
-Statut : desactiveActive evenement
.

001

3. EVENEMENT
-Base de donneeEffacer evenement
Eff. Tous les even.

001

Les valeurs par défaut du système pour les actions à effectuer :
•
•
•
•
•

Relais No. 1 sera activé lorsque le niveau d’alarme A est atteint sur
n’importe quel transmetteur connecté au réseau
Relais No. 2 sera activé lorsque le niveau d’alarme B est atteint sur
n’importe quel transmetteur connecté au réseau
Relais No. 3 sera activé lorsque le niveau d’alarme C est atteint sur
n’importe quel transmetteur connecté au réseau
Appuyer sur la touche Silence pour reconnaitre les événements et
arrêter l’alarme sonore.
Relais No. 4 sera activé lorsque n’importe quel transmetteur
connecté au réseau est en faute.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

41

Programmation du système
Menu événement

Action
Les Actions comprennent deux paramètres :

3. EVENEMENT
-ActionCible:
Ctrl
Relais: #01

Cible

Relais

42

001

Indique quelle composante est responsable de l’action à
effectuer, soit :
Tx (transmetteur)
Re (relais/annonciateur)
Ctrl (centrale)
Indique quelle des trois sorties sera activé lorsque
l’événement est vrai :
#XX (active le relais #xx de la composante), Alarme sonore
(active l’alarme sonore de la composante)
ALL (active tous les relais et les alarmes sonores)

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu événement

Délais
Cette option permet de configurer les paramètres Avant et Après qui
retardent l’activation ou la désactivation d’une action.
Avant

Après

Retarde une action pour la durée de temps précisée. Si la
condition persiste après le délai précisé, un alarme est activé
et l’action précisée est effectuée.
Retarde la désactivation d’une action; l’action continuera
jusqu’à l’épuisement du temps de délais précisé et si
l’événement n’est plus vrai. Il est également possible de
sélectionner l’option “latch” dans le champs de délais après.
3. EVENEMENT
-DelaisAvant:
99min
Apres:
01min

001

Les délais Avant et Après peuvent être programmés à soit 30 ou 45
secondes ou de 1 à 99 minutes, en incrément de 1 minute. L’option à
cinq traits d’union indique qu’il n’y a aucun délai configuré.
•
•
•
•

Utiliser les flèches pour déplacer le curseur à l’option désirée
Appuyer sur Enter pour sélectionner l’option
Utiliser les flèches pour dérouler dans la liste de secondes ou
minutes
Appuyer sur Enter pour valider le délais désiré.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

43

Programmation du système
Menu événement

Délais mode latch
La fonction Latch, disponible depuis le menu déroulant du délais Après,
est exécuté sur un état d’événement. Essentiellement, c’est un circuit
de verrouillage, c’est à dire qu’une intervention humaine est nécessaire
pour déverrouiller l’action de l’événement.
L’événement demeure actif jusqu’au moment de pression sur la touche
Silence. Cette touche arrête l’alarme sonore et relâche l’événement.
Lors de l’appui sur la touche Silence, les événements sont relâchés et
réévalués. Si la condition de l’événement est toujours vrai,
l’événement demeure actif et revient en mode Latch. Si la condition ne
persiste pas, l’événement est désactivé.
Note: Si un événement est configuré avec un délais Avant et que la
touche Silence est enfoncée lorsque les conditions de
l’événement sont toujours vraies, l’alarme sonore sera fermé
seulement pour la durée du délais précisé.

44

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu événement

Conditions
Les Conditions sont les paramètres de définition (de calculs) qui
décident si un événement est vrai ou non. Chaque condition est définie
par quatres éléments. Il est également possible de lier deux conditions
pour obtenir une plus grande flexibilité. Une condition défini :
Si au moins 1/3 du groupe 36 détecte des concentrations supérieures à
2.01% du gaz précisé ET tout les éléments du groupe 03 détectent une
concentration supérieure à 2.99% de gaz, l’action précisée (configurée
dans le premier écran événement) pour cette événement sera
déclencher.
Puisque l’affichage offre une espace limitée, il est nécessaire de
naviguer à gauche et à droite pour configurer ou consulter tous les
paramètres de condition.
Écrans de programmation de conditions
3. EVENEMENT
1/3
Gr036
>
2.01%

ET

001
ET

3. EVENEMENT
tous Gr003
>
2.99%

001

La partie de l’écran de condition événement entre parenthèses est
divisée en quatres champs éditables :

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

45

Programmation du système
Menu événement

La partie supérieur de gauche contient le quantificateur de statistique
(disponible seulement pour les groupes). Cette option permet de
choisir quelle partie du groupe à inclure dans l’équation. Les options
de ce champs sont :
tous :
moy :
max :
min :
1/4 :

inclus tous les transmetteurs du groupe
inclus la concentration moyenne des transmetteurs du groupe
inclus la concentration maximum du groupe
inclus la concentration minimum du groupe
inclus au moins un quart des transmetteurs du group ayant
atteint les conditions
1/3 :
inclus au moins un tiers des transmetteurs du group ayant
atteint les conditions
1/2 :
inclus au moins la moitié des transmetteurs du group ayant
atteint les conditions
2/3 :
inclus au moins deux tiers des transmetteurs du group ayant
atteint les conditions
3/4 :
inclus au moins trois quarts des transmetteurs du group ayant
atteint les conditions
1 or + : au moins un ou plusieurs des transmetteurs du groupe ayant
atteint les conditions

46

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu événement

La partie inférieure à gauche de l’écran contient le quantificateur de
logique, ou l’opérateur, qui détermine comment les conditions sont
calculées. Les options disponibles dans ce champs sont :
Symbole
opérateur
--=
<=
<
>=
>
!
max./min

Description
Aucun opérateur
Égal à
Égal à ou inférieur à
Plus petit que
Égal à ou supérieur à
Plus grand que
Pas égal
Lorsque la valeur maximum est atteinte, une action est
déclenchée. L’action ne sera pas désactiver sans que les niveaux
baissent en dessous de la valeur minimum
Lorsque que les concentrations descendent plus bas que la valeur
minimum, une action est déclenchée. L’action ne sera pas
désactivé sans que les niveaux remontent au dessus de la valeur
maximum précisée

La partie supérieure droite de l’écran contient la source, ce qui défini
sur quel unité ou groupe d’unités l’événement sera basé. Les options
disponibles dans ce champs sont :
GrTous :Inclus tous les transmetteurs (voir note)
Gr000 : Inclus seulement les unités dans le groupe précisé (voir note)
Tx000 : Inclus seulement le transmetteur précisé (connecte à la
centrale)
Heure : Inclus seulement les informations recueillies dans la plage
horaire précisée. La sélection de l’horloge configure une condition applicable seulement entre l’heure de début et l’heure de
fin. Il est possible de configurer un écran de condition avec
des paramètres particuliers et l’autre écran de condition avec
une plage horaire : la condition précisée déclenchera un événement seulement si elle se produit dans la plage précisée.
Note: Cliquer sur la loupe à droite d’un groupe pour accéder à l’écran
du groupe (consultation ou modification). Appuyer sur ESC pour
fermer l’écran et revenir à l’écran de condition.
M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

47

Programmation du système
Menu événement

La partie inférieure à droite de l’écran contient l’opérande, qui défini
quel statut déclenchera un événement. Les options disponibles dans
ce champ sont :
OFF :
ON :
Faute :
Alrm A:
Alrm B:
Alrm C:

Utilisé pour le statut des entrées binaires (ex. : utilisé avec le
301ADI)
Utilisé pour le statut des entrées binaires (ex. : utilisé avec le
301ADI)
Base le déclenchement sur un alarme d’entretien, de communication ou de faute d’unité
Si le dispositif ou le groupe choisi éprouve une Alarme A ou
Alarme 1, un événement sera déclenché.
Si le dispositif ou le groupe choisi éprouve une Alarme B ou
Alarme 2, un événement sera déclenché.
Si le dispositif ou le groupe choisi éprouve une Alarme C, un
événement sera déclenché.

L’écran Période couverte permet de définir la période couverte par
l’événement. Ce champ offre deux options supplémentaires :
Champ de définition de jour : permet de sélectionner soit Toute la
journée, Jour ou Nuit
Champ de définition de semaine : permet de sélectionner soit Toute la
semaine, Jours ouvrables ou Fin de semaine

3. EVENEMENT
-Periode couverteToute la journee
Toute la semaine

001

1. Utiliser les touches de flèches haut ou bas pour naviguer soit à
Toute la journee ou à Toute la semaine.
2. Appuyer sur Enter pour sélectionner
3. Utiliser les touches de flèches haut ou bas pour dérouler les
options
4. Appuyer Enter pour sélectionner l’option affichée

48

Manuel de l’utilisateur 301C
Honeywell

M-510324
8/10

Programmation du système
Menu événement

Statut
Cet écran affiche le statut de l’évenement sélectionné et permet soit
d’activer ou de désactiver, selon le statut actuel.
Active
evenement

Appuyer sur Enter pour sélectionner Active
evenement ou Desactive evenement
3. EVENEMENT
-Statut : desactiveActive evenement
.

001

Lorsque tous les détails d’un événement sont inscrits, le dernier écran
de configuration affiche « Active evenement ». Appuyer sur Enter pour
valider les paramètres et activer l’événement.
Lors de consultation d’un événement existant, la première ligne de cet
écran afficherait « Désactive evenement ». Appuyer sur Enter sur cette
ligne permet de basculer entre l’activation et la désactivation. L’appui
sur la touche Enter (pour désactiver) ferme simplement l’événement et
ne supprime pas l’événement. L’événement sera toujours disponible
pour réactivation.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

49

Programmation du système
Menu acquisition

Menu acquisition
Le mode Acquisition est seulement disponible lorsque la centrale est
munie d’une carte SD (option d’enregistrement de données). Cette
fonction permet d’activer ou de désactiver l’enregistrement des
événements du système ou les informations des transmetteurs.
L’information est enregistrée sur une carte de mémoire « SD ».
L’utilisateur doit configurer les intervales et les conditions
d’enregistrement nécessaires à cette fonction.

4. Acquisition
Mode seuil 10%
Debuter log Tx
Debuter log even.

La première ligne de l’écran Acquisition permet de sélectionner soit :
Mode delai :
Mode seuil :

Permet de préciser des intervalles d’enregistrement
de 10 à 59 secondes ou de 1 à 60 minutes.
Permet de configurer l’enregistrement selon les seuil
de variation depuis la dernière lecture, soit de 3% ou
plus, 5% ou plus ou de 10% ou plus de la dernière
concentration détectée.

La sélection du seuil 3% ne signifie pas qu’une variation de 3% sera
détectée mais qu’une variation 3.1% le sera. La fréquence de saisie
(fréquence de rafraîchissement) peut affecter l’enregistrement de
données.
Voici un exemple de l’enregistrement en mode seuil. Ces fichiers sont
des fichiers textes séparés par des points-virgules :

2005-04-27
2005-04-27
2005-04-27
2005-04-27
2005-04-27
2005-04-27

50

11:05:20;1_CO2_ppm;574;-normal-:
11:06:02;1_CO2_ppm;503;-normal-:
11:06:15;1_CO2_ppm;562;-normal-:
11:06:28;1_CO2_ppm;645;-normal-:
11:06:39;1_CO2_ppm;557;-normal-:
11:30:45;1_CO2_ppm;715;-normal-:

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu acquisition

Debuter et arreter log Tx
L’étape précédente traitait la fréquence d’enregistrement de données.
Maintenant, il faut débuter le processus :
Lorsque « Debuter log Tx » est affiché, le mode acquisition
(enregistrement) est inactif. Lorsque « Arreter log Tx » est affiché, les
données sont en cours d’enregistrement. Un message
d’enregistrement est affiché à l’écran et le DEL de la carte SD s’allume.
Appuyer sur Enter pour Débuter ou Arrêter l’enregistrement.
Lorsque les données Tx sont enregistrées, le système crée des fichiers
taaammjj.log, tbaammjj.log et tcaammjj.log. Ces fichiers
contiennent, respectivement, le tiers des données des transmetteurs.
Le registre comprend la date et l’heure, l’adresse du transmetteur, le
type de sonde, la concentration à la lecture ainsi que le statut de
l’alarme.
Voici un exemple d’un registre de log Tx :

2004-01-23 17;54;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;1.5;-normal-;003_CO_ppm;0;-normal2004-01-23 17;55;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;0.5;-normal-;003_CO_ppm;0;-normal2004-01-23 17;56;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;0.5;-normal-;003_CO_ppm;0;-normal2004-01-23 17;57;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;1.0;-normal-;003_CO_ppm;0;-normal2004-01-23 17;58;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;1.5;-normal-;003_CO_ppm;0;-normal-

La première colonne affiche la date (aaaa-mm-jj) et l’heure (hh:mm:ss)
de l’enregistrement. Cet exemple indique un délai configuré à un
intervalle d’une minute.
La troisième colonne affiche l’adresse du transmetteur et le type de
sonde et la quatrième colonne indique la concentration et l’unité de
mesure.
Les colonnes se répètent pour chaque transmetteur, séparées par des
traits d’union. La liste continue ainsi jusqu’au dernier transmetteur dans
la liste.
M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

51

Programmation du système
Menu acquisition

Débuter et arrêter log even.
Le menu Acquisition offre l’option d’enregistrement d’événements.
L’enregistrement d’événements enregistre les transactions de la
centrale, les événements, les avertisseurs de Tx et d’alarmes et le
statut de relais.
Lorsque « Debuter log even. » est affiché, le mode acquisition
(enregistrement) est inactif. Lorsque « Arreter log even. » est affiché,
les données sonten cours d’enregistrement.
Appuyer sur Enter pour débuter ou arrêter l’enregistrement.
Lorsque les données d’événements sont enregistrées, le système crée
un fichier evaammjj.log. Ce registre indique la date, l’heure et
l’événement. Voici un exemple d’un registre d’événement :

2006-01-23 17;54:25; Log evenement active
2006-01-23 17;55:25; Arrêt système
2006-01-23 19:05:47; Sequence de simulation active
2006-01-23 19:05:48; Tx 6 communication n’est plus en faute
2006-01-23 19:05:48; Tx 8 communication n’est plus en faute

La première colonne du registre indique la date (aaaa-mm-jj) et l’heure
(hh:mm:ss) de l’enregistrement. L’exemple ci-haut démontre des
intervalles de délais d’une minute.
Le système enregistre ces types d’événements :
•
•
•

Journal événement
Changement de statut d’événement
Changement de statut pour alarmes A, B, C, faute

Note: De nouveaux fichiers « log » seront créés lorsque le fichier actuel
atteint 32,000 lignes ou le dimanche à 0h.

52

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu copie

Menu copie
L’option Copie du menu Info TX permet de copier ou de transférer les
paramètres programmés. Il est possible de transférer des données
d’une carte SD de la centrale à un ordinateur et vice versa ou de copier
des paramètres d’un transmetteur à un autre. L’option Copie offre trois
écrans : Configuration, Paramètres et Journal Sys.

Configuration
Si la centrale est munie d’une carte mémoire, la fonction Configuration
permet de transférer les données soit du 301C à la carte SD ou vice
versa. Ceci permet de transférer la programmation de la centrale sur un
ordinateur ou d’un ordinateur à la centrale.

5. Copie
-parametresInfoTx vers InfoTx
Evene. vers Evene.

La première option de l’écran, 301C vers SDcard, copie la configuration
et les paramètres de la centrale dans un fichier « config.ini » 1. La
deuxième option, SDcard vers 301C, permet de copier la configuration
et les paramètres du fichier « config.ini » à la carte SD de la centrale.
Note: Le fichier «config.ini» peut être modifié en tout temps de
n’importe quel ordinateur.

1. Lors de transfert de données, le système cherche automatiquement un fichier existant
nommé « config.ini » avant de procéder. Si un tel fichier existe, le système cherche le
fichier « config.bak ». Si le fichier est trouvé, il est supprimé. Le fichier « config.ini »
existant est renommé « config.bak ». Il est maintenant possible d’enregistrer le
nouveau fichier « config.ini », tout en conservant une copie du fichier précédant.
Lors de l’insertion d’une carte mémoire dans la centrale, le système de la centrale
cherche automatiquement un fichier « config.ini » existant contenant le label
« Autoload » égal à 1. Si le label est trouvé, le système télécharge le contenu du fichier et réinitialise le « Autoload » à 0. Cette fonction est utile pour éditer la configuration
sur un ordinateur sans affecter la centrale (tels les événements enregistrés).
M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

53

Programmation du système
Menu copie

Paramètres
La fonction paramètres permet de copier la configuration d’un
transmetteur à un autre ou de copier les paramètres d’un événement à
un autre. Ceci permet une configuration plus rapide pour les unités
partageant des paramètres identiques ou similaires.

5. Copie
-parametresInfoTx vers InfoTx
Evene. vers Evene.

Les options de cette écran sont :
InfoTx vers InfoTx copie les paramètres de transmetteur d’un unité à
l’autre.
Evene. vers Evene. copie les paramètres d’un événement à l’autre.
Le processus est identique pour chaque option :
•
•
•
•
•

Utiliser les flèches pour sélectionner la source, (les données à
copier) et appuyer sur Enter.
Lorsque l’adresse du transmetteur clignote, utiliser les flèches haut
et bas pour naviguer et sélectionner l’adresse désirée.
Appuyer sur Enter pour valider l’adresse
Sélectionner l’adresse cible (où copier les données) de même
façon que la sélection de la source
Sélectionner COPIER et appuyer sur Enter. Les paramètres sont
copiés.
InfoTx vers InfoTx
source tx001
cible
tx113
COPIER

Evene. vers Evene.
source #001
cible
#013
COPIER

54

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu copie

Journal Sys
La centrale enregistre les données du journal dans sa mémoire interne.
Si la centrale est munie d’une carte mémoire, la fonction Journal Sys
permet d’enregistrer les informations de journal du système en format
texte sur la carte de mémoire flash (SD card).

5. Copie
-Journal SysJournal vers SDcard

Lorsque sélectionnée, cette option créé un registre de toutes les
dernières actions de la centrale sur la carte de mémoire, dans un fichier
nommé « slaammjj.log ». Ce fichier peut contenir jusqu’à 64Ko
d’information en format texte. Lorsque la carte de mémoire atteint sa
capacité, les nouvelles informations remplacent les plus vieilles (qui
sont effacées).
Voici un exemple du fichier de journal :
--- START of system log dump : 1980-01-22 17:23:51 --1980-01-19 22:07:26;Accessing menu;
1980-01-19 22:07:41;Chargement config depuis carte SD;
1980-01-19 22:07:45;Sortie du menu;
1980-01-19 22:13:05;Accès au menu;
1980-01-19 22:13:16;Édition paramètres Tx 1;
1980-01-19 22:18:29;Sortie du menu;
1980-01-19 23:07:14;Accès au menu;
1980-01-19 23:07:40;Édition événement 1;
1980-01-19 23:07:43;Sortie du menu;
1980-01-19 23:08:10;Accès au menu;
1980-01-19 23:09:07;Édition événement 2;
1980-01-19 23:09:13;Sortie du menu;
1980-01-20 00:06:42;Accès au menu;
1980-01-20 00:06:52;Sortie du menu;
1980-01-20 00:07:49;Accès au menu;
1980-01-20 00:07:55;Sortie du menu;
1980-01-22 17:23:46;Accès au menu;
--- END of system log dump : 1980-01-22 17:23:51 ---

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

55

Programmation du système
Menu config

Menu config
Le menu Config, avec quatres écrans principaux, permet de configurer
le mode d’affichage de la centrale, d’ajuster la date et l’heure, de
sélectionner le langage d’affichage , de changer le mot de passe
d’accès à la centrale, de modifier le port esclave, régler la configuration
des relais, sélectionner le mode d’émission AP.
Chaque écran principale offre des options de programmation
supplémentaires.
MENU
5. Copie
6. Config

7. Reseau
8. Tests

6. Config
Defilement manuel
Regle Date et heure
English menu
Date et heure
2005-11-21
(norme ISO 8601)

11:47:36

6. Config
Mot de passe usage
- 2967 Cnfg port esclave
Cnfg port esclave
Adresse: 001
38400 bauds
Mdbs RTU 8D 2S NP
6. Config
Configurat. relais
Emission AP: auto
Honeywell
Configuration relais
-FailsafeTous les relais
Inactif

Configuration relais
-Silence1
2
3
4
ina
act
ina
ina

6. Config
Definition jour
Definition semaine
Definition Jour
-Jourdeb:
08:00
fin:
17:00
Definition semaine
-jours ouvrablesdeb:
Lundi
fin:
Vendredi

56

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu config

La sélection de la première ligne (du premier écran) offre le choix de
trois modes d’affichage : Defilement manuel, Defilement 3 sec,
Defilement 5 sec. Ces réglages contrôlent la présence et la fréquence
d’affichage des données à l’écran de la centrale. Le mode de
défilement manuel signifie que l’utilisateur doit appuyer sur les flèches
pour visionner le statut de chaque unité connectée à la centrale. Les
mode de défilement 3 secondes et 5 secondes effectuent le
déroulement automatique des données, en fréquence de changement
d’écran de soit 3 ou 5 secondes.

6. Config
Defilement manuel
Regle Date et heure
English menu

Note: Il est toujours possible de dérouler dans les écrans d’affichage en
appuyant sur les flèches, peut importe le mode sélectionné.
La deuxième ligne permet d’ajuster la date et l’heure depuis un nouvel
écran, Date et heure. Lorsqu’un chiffre clignote, il est en mode édition.
Utiliser les flèches pour dérouler à la valeur désirée. Il est possible de
modifier l’année, le mois, le jour et l’heure, les minutes et les secondes.
La centrale ne gère pas les changement d’heure (telle l’heure avancée).
Tout changement d’heure doit être effectué manuellement.
Date et heure
2005-11-21
(norme ISO 8601)

11:47:36

La troisième ligne du premier écran Config permet de changer le
langage d’affichage. Si le menu est en anglais, l’écran indiquera Menu
français (et vice versa). Déplacer le curseur à la gauche du champ et
appuyer sur Enter pour changer le langage.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

57

Programmation du système
Menu config

Le deuxième écran principale de configuration permet de modifier le
mot de passe et de modifier la configuration du port esclave.

6. Config
Mot de passe usage
- 2967 Cnfg port esclave

Le mot de passe par défaut est 2967. Sélectionner Mot de passe
usager pour modifier le mot de passe :
•
•

•

Lorsque le premier chiffre clignote, utiliser les flèches pour
augmenter ou diminuer la valeur, ensuite
Utiliser les flèches droite et gauche pour déplacer le curseur une
espace et répéter le processus de changement pour chaque chiffre
désiré
Lorsque le mot de passe désiré est afficher, appuyer sur Enter pour
le valider et quitter le mode d’édition.

Note: Communiquer avec le soutien technique de Honeywell pour
assistance concernant les mots de passe perdus au 1-800-5632967.

58

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu config

Pour changer l’adresse, le débit en bauds ou pour visionner le protocole
de communication du port esclave :
Déplacer le curseur à gauche de Cnfg port esclave et appuyer sur
Enter.

Cnfg port esclave
Adresse: 001
38400 bauds
Mdbs RTU 8D 2S NP

•
•
•
•

Déplacer le curseur à la gauche du paramètre désiré (adresse ou
débit en bauds)
Appuyer sur Enter pour sélectionner le paramètre
Utiliser les flèches pour dérouler dans la liste de configurations
disponibles
Appuyer sur Enter pour valider le nouveau paramètre et quitter le
mode édition.

Naviguer dans les écrans du menu Config avec les flèches gauche
(précédent) et droite (suivant).

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

59

Programmation du système
Menu config

Le troisième écran principale permet de régler la configuration des
relais, le mode d’émission AP et de choisir parmi quatre fabricants pour
la centrale.

6. Config
Configurat. relais
Emission AP: auto
Honeywell

La sélection Configurat. relais offre deux options supplémentaires pour
la configuration des relais :
La première option, Failsafe, permet d’activer (ou désactiver) tous les
relais en appuyant sur la touche Enter. Cette fonction est utilisée en cas
de panne d’électricité: en cas de panne, le relais déclenche le dispositif
connecté (ex. une lampe) pour signaler un problème.

Configuration relais
-FailsafeTous les relais
Inactif

La deuxième option, Silence, permet d’activer ou désactiver l’option
Silence de chaque relais. Déplacer le curseur à gauche du relais et
appuyer sur Enter pour basculer la valeur (act ou ina).

Configuration relais
-Silence1
2
3
4
ina
act
ina
ina

60

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu config

Le quatrième écran de configuration permet de programmer une
définition d’un jour et d’une semaine.

6. Config
Definition jour
Definition semaine

Les définitions de jour ou de semaine permettent de définir les plages
d’heures représentées par Jour et les plages de journées représentées
par Semaine.

Definition Jour
-Jourdeb:
08:00
fin:
17:00

Definition semaine
-jours ouvrablesdeb:
Lundi
fin:
Vendredi

Note: Ne pas oublier que la centrale fonctionne sur une horloge de 24
heures (0:00 à 23:59). La centrale ne gère pas les changement
d’heure (telle l’heure avancée). Tout changement d’heure doit
être effectué manuellement ou depuis la synchronisation d’heure
BACNet (module BACNet nécessaire).

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

61

Programmation du système
Menu Réseau

Menu Réseau
Le menu Reseau permet soit de réinitialiser ou de balayer les
informations de dispositifs de réseau.
Ce menu offre plusieurs options supplémentaires, en deux écrans. Le
premier écran contient trois options :
RAZ base de
donnee :

Réinitialise toutes les informations de dispositifs de
réseau dans la base de données. Ceci réinitilise
seulement les données de dispositif de réseau. Il n’y
a aucun impacte sur les groupes ou les événements.
Balayage reseau :Démarre l’auto-détection de tous les dispositifs de
réseau, ce qui permet au système de configurer la
base de données de transmission pour les dispositifs
de réseau.
RAZ et balayage : Effectue un balayage et une réinitialisation
simultanément.
7. Reseau
RAZ base de donnees
Balayage reseau
RAZ et balayage

Note: Lorsqu’une de ces options est activée, il faut attendre la fin du
processus. Il est impossible d’interrompre le processus.
Le deuxième écran de Reseau présente les options Statistiques et
Etalonnage.

7. Reseau
Statistiques
Etalonnage

62

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu Réseau

La sélection de statistiques affichent les statistiques pour l’adresse
précisée.

Statistiques
Valide
16
Erreurs
0
Sans rep
0

100%
0%
0%

Valide:

Indique le nombre de réponses valides pour les 16 dernières
requêtes.
Erreurs: Indique le nombre d’erreur de réponse pour les 16 dernières
requêtes.
Sans rep: Indique le nombre d’erreurs de temporisation (pas de
réponse) pour les 16 dernières requêtes.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

63

Programmation du système
Menu Réseau

Etalonnage
Le menu Reseau offre également l’option Etalonnage permettant
d’effectuer un étalonnage à distance pour les dispositifs qui supportent
l’étalonnage en réseau.

7. Reseau
Statistiques
Etalonnage

L'écran d'étalonnage contient quatre (4) lignes d'information:

Calib 001 : 301D2
Statut : Normal
Etal Zero
Etal plage
246 ppm

Ligne 1:

Ligne 2:
Ligne 3:
Ligne 4:

64

Indique le mode (Calib, ce qui signifie étalonnage),
l'adresse (Modbus) de l'unité à étalonner (007) et le type
d'unité à étalonner (301D2)
Indique le statut (Normale ou En Etalon...) de l'unité
sélectionnée
Affiche la fonction à effectuer (Etal Zero)
Affiche la fonction à effectuer (Etal Plage) et la valeur de
concentration de gaz d'étalonnage (246 ppm)

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu Réseau
1.

Déplacer le curseur à la gauche de l'adresse de l'unité sur la
première ligne et appuyer sur Enter
Etalon 001 : 301D2
Statut : Normal
Etal Zero
Etal plage 246 ppm

2.

Dérouler la liste pour afficher l'adresse de l'unité désirée* puis
appuyer sur Enter pour sélectionner.
3. La deuxième ligne affiche le statut de l'unité
4. Déplacer le curseur à la gauche de la fonction désirée, Etal Zero
pour étalonner le zéro de l'unité, et appuyer sur Enter pour
sélectionner.
5. Lors de la sélection d'Etal Zero, la centrale demande la
confirmation.
Calib 001 : 301D2
Etalonner Zero?
Etal Zero
Etal plage
246 ppm

*L'unité doit être configurée dans la base de donnée du 301C pour
figurer dans la liste d'adresses d'unités affichée à l'écran.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

65

Programmation du système
Menu Réseau
6.

Appuyer sur Enter pour confirmer ou Esc pour annuler. Si confirmé,
la centrale procède à l'étalonnage du zéro de l'unité. Le processus
nécessite seulement quelques instant, puis l'écran affiche de
nouveau l'écran d'étalonnage.
Note: Ne jamais étalonner le zéro de l’unité avec de l’air ambiante
seulement. Toujours utiliser de l’azote (N2) au port d’étalonnage
pour étalonner le zéro.
7. Pour effectuer l'étalonnage de l'unité, déplacer le curseur à la
gauche de Etal Plage** et changer la valeur d'étalonnage avec la
procédure suivante :
Calib 001 : 301D2
Statut : Normal
Etal Zero
Etal plage
246 ppm

a. Utiliser la flèche droite pour déplacer le curseur à la gauche de
xxx ppm (champ de valeur d'étalonnage). Appuyer sur Enter
pour sélectionner le champ (la valeur est éditable lorsqu'elle
clignote).
b. Utiliser les flèches haut et bas pour augmenter ou diminuer la
valeur. Appuyer sur Enter pour valider.
c. Déplacer le curseur à la gauche de la fonction Etal Plage et
appuyer sur Enter pour démarrer l'étalonnage.
L'étalonnage de la plage démarre. L'écran affiche le statut de l'unité,
« En etalon... » jusqu'à la terminaison de l'étalonnage.
**Lors de la sélection d'Etal Plage, assurer que l'unité est exposée au
gaz d'étalonnage approprié avant et pendant le processus
d'étalonnage.

66

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu Tests

Menu Tests
Le menu Tests permet d’effectuer une gamme de vérifications sur les
composantes et sur les communications de réseau. Ce menu permet
également d’opérer le système dans quatre modes différents, chacun
offrant des fonctionalités particulières.
MENU
5. Copie
6. Config

7. Reseau
8. Tests

8. Tests
Sequence de test
Debuter sequ. Sim.
Charge maximum

1

2

3

4

Sequence de test
Relais actives
Appuyez une touche
ESC pour quittter
Sequence de test
Alarme sonore
Appuyez une touche
ESC pour quitter
Sequence de test
DEL active
Appuyez une touche
ESC pour quitter
Sequence de test
Presser ‘gauche’
ESC pour quitter

5

6

7

Sequence de test
Test affichage
Pressez une touche
ESC pour quitter
Sequence de test
Test comm. reseau
9600 bauds
Channel 1 SUCCES
Sequence de test
Test termine
Pressez une touche
Sequence simulation
Debuter avec
Tx001
Confirmer

8. Tests
Mode fct: normal

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

67

Programmation du système
Menu Tests

Le menu Tests offre quatre options principales, disponibles sur deux
écrans. Chacune de ces options offres des fonctionnalités
supplémentaires.
Le premier écran présente trois options :
8. Tests
Sequence de test
Debuter sequ. Sim.
Charge maximum

Sequence de test : Permet d’activer chaque sortie et de valider
l’opération de chaque touche de clavier, des pixels
d’affichage et les divers protocoles de
communication de la centrale.
Debuter sequ sim :Démarre ou arrête le mode de simulation,
permettant de simuler une concentration de gaz sur
la plage associée à chaque transmetteur, l’un après
l’autre. Les concentrations simulées sont locales
(dans la centrale). (Les événements seront activés
pour la simulation, mais les unités de détection ne
sont pas affectées.)
Charge maximum :Active toutes les composantes de la centrale
L’option au deuxième écran, « Mode fct », permet de sélectionner le
mode de fonctionnement, soit : Normal, Tx unique or debogage.

8. Tests
Mode fct: normal

Normal :
Tx unique :
Debogage :

68

Mode d’opération normal de la centrale
Active le mode d’interrogation d’un seul
transmetteur.
Active le mode de service permettant d’effectuer
l’étalonnage et de tester les événements sans
déclencher des actions.
Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu Tests

Sequence de test
Lors de la sélection de cette option, la centrale affiche l’écran de
Séquence de test. Appuyer sur ESC à n’importe quelle étape pour
revenir à l’écran principale du menu Tests.

Sequence de test
Relais actives
Appuyez une touche
ESC pour quittter

Appuyer sur n’importe quelle touche pour procéder aux tests du
système.
Sequence de test
Alarme sonore
Appuyez une touche
ESC pour quitter

Cette fonction comprend treize écrans de test pour chaque composante
de la centrale. Les trois premiers écrans effectuent l’essais des relais
de l’alarme sonore et des DEL.
Les six prochains écrans demande la pression sur les touches gauche,
droite, haut, bas, Silence, Enter et ESC. Le système avance seulement
lors de la pression sur une touche.

Sequence de test
Presser ‘gauche’
ESC pour quitter

Le système essaye ensuite l’écran d’affichage; un écran en blanc est
affiché. Appuyer n’importe quelle touche pour procéder à l’écran
suivant.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

69

Programmation du système
Menu Tests

Sequence de test
Test affichage
Pressez une touche
ESC pour quitter

Le dernier test est l’essais de communication de réseau :

Sequence de test
Test comm. reseau
9600 bauds
Channel 1 SUCCES

Assitôt ces essais commencés, il n’est pas possible de les interrompre
ou de les arrêter. Le système essaye chacun des cinq bauds (vitesse
de communication : 9600, 19200, 38400, 57600, 115200) et chacun
des quatre canaux par baud.
Aussitôt les essais terminés, le système affiche l’écran de sortie du
mode Séquence de test. Appuyer sur n’importe quelle touche pour
revenir à l’écran principale du menu Tests.

Sequence de test
Test termine
Pressez une touche

70

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu Tests

Mode Normal
Ceci est le mode d’opération normal (par défaut) du système. Lorsque
le système est en mode normal, certaines valeurs peuvent être
modifiées sans interruption de services. Toute modification est validée
et effectuée lors du retour à l’écran principale.

Mode Tx unique
Ce mode permet d’effectuer l’analyse de transmetteurs, un à la fois. La
centrale interroge seulement le transmetteur précisé, ce qui met à jour
seulement les données de ce transmetteur. Ce mode n’entrave pas les
fonctions d’évaluation d’événements.

Mode débogage
Ce mode permet d’évaluer et d’effectuer des essais complets
d’opération de système sans affecter les opérations (hors le mode
débogage). Les événements sont évalués et affichés, si
nécessaire, mais aucune action n’est activée.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

71

Programmation du système
Menu Tests

Mode Simulation
Ce mode désactive les mises à jour d’information de communication de
réseau. Ce mode peut être employé, peu importe quel est le mode
d’opération actuel du système (exemple: l’emploi du mode Silumlation
simultanément avec le mode Débogage permet d’évaluer le système
au complet [groupes, événements, etc.] sans déclencher des actions
ou sans utilisation de matériel supplémentaire). Il permet de simuler
des concentrations de gaz sur une plage associée à chaque
transmetteur, en séquence :
Les niveaux d’alarme A, B et C sont évalués selon la concentration de
gaz et les événements sont évalués et les actions sont déclenchées.
Penrant la simulation, la centrale ne connait pas l’état actuel de la
composante de réseau. Il est possible d’arrêter ce mode en tout temps
depuis le menu Tests (voir Mode Normal) .
Si l’un de ces modes est activé, mais qu’il n’y a aucune activité le
système retourne à son opération normal après douze heures
d’inactivité (de clavier). Auncune information n’est perdue

72

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu BACNet

Menu BACNet
Le menu BACNet offre plusieurs écrans d’options permettant de
configurer la connexion IP de BACNet, l’information du serveur et
l’information du fuseau horaire.

MENU



 9. BACNet
10. Reseau sans-fil

9. BACNet
- Appareil BACnet ID : 1



9. BACNet
- DHCP : desactive Active DHCP



9. BACNet

- Static IP Address 1 .254
192. 168.



9. BACNet

- Static Netmask 0
255 .255 .255.



9. BACNet

- Static Gateway 1
192 . 168 . 1 .





9. BACNet


- SNTP Client Serveur SNTP
Requete SNTP :
0min
9. BACNet

- Fuseau horair : 0:00
Fuseau
HA : INACT







9. BACNet
- Nom Appareil edition (20car .max)
VA301C : 1

 10 .

Serveur SNTP
4. 1. 12

9. BACNet


- ForeignDevReg : des Active FDR
TTL : 43200 sec


9. BACNet
- BBMD Info IP : 192 . 168 .
1 . 100
Port : 0xBAC0

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

73

Programmation du système
Menu BACNet

Le premier écran permet de configurer l’identification et l’adresse :

9. BACNet
-AppareilBACnet ID : 1
Adresse statique IP

BACnet ID :

(Building Automation and Control Networks) est le
numéro assigné à une centrale sur le réseau.
9. BACNet
-Static IP Address192.168. 1.254

Adresse
Statique IP :

Ceci est une adresse qui est toujours assignée à une
centrale en particulier (plutôt que recyclé et
réassigné lorsque la centrale ne l’utilise plus)

Changer les valeurs BACNet
•
•

Utiliser les flèches pour déplacer le curseur à gauche du paramètre
désiré puis appuyer sur Enter pour le sélectionner.
La sélection de BACnet ID active le mode édition du champs .
Utiliser les flèches pour augmenter ou diminuer la valeur ID (0419303)

La sélection de l’option Adresse statique IP ouvre l’écran de
modification de l’adresse IP. Toutes les centrales sont configurées avec
une adresse par défaut.

-Adresse IP192.168.
1.254
-Masque du reseau255.255.255.
0

74

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu BACNet

Le deuxième écran permet d’activer ou de désactiver le protocole
DHCP (Dynamic Host Configuration Protocol).

9. BACNet
-DHCP : desactiveActive DHCP

•

Appuyer sur la touche Enter pour basculer le champs Activer ou
Desactiver DHCP. Consulter votre service de TI pour de plus
amples informations sur le DHCP.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

75

Programmation du système
Menu BACNet

Le prochain écran principale BACNet permet de modifier l’adresse du
serveur SNTP et de configurer la fréquence à laquelle le système
effectuera des requêtes de serveur SNTP. Honeywell offre ces options
pour que nos produits s’adaptent mieux à vos protocoles de réseau,
cependant, nous ne’offrons ni la configuration, ni le soutien technique
pour ces options.
(SNTP=Simple Network Time Protocol, )

9. BACNet
-SNTP ClientServeur SNTP
Requete SNTP
:

1min

L’option Serveur SNTP ouvre un écran secondaire permettant de
modifier l’adresse IP du serveur SNTP. Consulter votre service de TI
pour de plus amples détails sur cette configuration.

10.

-Adresse IP4. 1. 12

Les options Requete SNTP activent le champs et permettent de
dérouler la liste de 0 à 60 minute, et de régler la fréquence à laquelle le
sytème effectuera des synchronisations de serveur SNTP.

76

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu BACNet

Le prochain écran est l’écran Fuseau horaire. Cet écran permet de
définir le fuseau horaire de votre système (S’il y a une différence entre
celui de votre système et le temps universel) et si le système est dans
une zone utilisant l’heure avancée.
La sélection du champs fuseau permet d’utiliser les flèches pour
dérouler dans une liste d’heures disponibles (de 0 :00 à +13 :00 et
-12 :00 à 0 :00)

9. BACNet
-Fuseau horaireFuseau
:
0:00
HA
: INACT

Le dernier écran du menu BACNet permet de préciser un nom pour
l’appareil BACNet.

9. BACNet
-Nom Appareiledition
(20car.max)
301C:1

Les écrans suivants permettent de configurer la communication
BACNet entre les différents systèmes (sous-réseaux) sur un réseau en
utilisant le Foreign Device Registration et le BBMD.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

77

Programmation du système
Menu BACNet

L’écran Foreign Device Registration (FDR) permet d’activer le FDR et
de préciser une durée de vie (TTL, ou Time To Live) en secondes.
9. BACNet
-ForeignDevReg:desActive: FDR
TTL: 43200 sec

Un « Foreign Device » est un dispositif BACNet dont l’adresse IP du
sous-réseau est différente du réseau BACNet/IP auquel le dispositif
veut se joindre.
Le paramètre TTL (Time-To-Live, ou durée de vie) est la durée de vie
(et l’intervalle) de l’enregistrement envoyé au BBMD lors de
l’inscription. Les enregistrements des dispositifs doivent être refaits
avant l’expiration de la durée de vie pour que ceux-ci demeurent
connectés au réseau.
L’écran BBMD Info permet de préciser l’adresse du BBMD auquel le
dispositif se connectera (ou s’enregistrera).
9. BACNet
-BBMD InfoIP:
192.168. 1.100
Port: 0xBAC0

Consulter la norme ASHRAE 135-2001, Annex J, section J5 pour de
plus amples informations sur ce sujet.

78

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu reseau sans-fil

Menu reseau sans-fil
Le réseau sans fil (disponible seulement dans le 301C-W, version 3 et
plus du 301C) permet de configurer les paramètres de communication
sans-fil, de consulter les diagnostics du réseau et de travailler avec les
divers aspects des noeuds sans-fil (sondes).
Reseau sans-fil
1. Parametres
2. Diagnostics
3. Noeuds
4. Nouveau noeud
5. Hiberner
6. RAZ reseau
7. Log Statut NoLog
8. Consolider accès

Parametres
1.
7B7177EFACE0049
2. WC Version
3. PAN ID
4. Canal RF
5. Mode Log No Log
6. Association
Ena
7. Noeuds
0
8. Max noeuds
0
9. Max sauts
0
10. Puissance
0
11. AHFO
0
12. BO
0
13. SUO
0
14. LCO
18
15. LTO
0
16. MMO
0
17. BMO
0
18. KNSRO
0
19. FNSRO
0
20. Clone WC

Diagnostics
1. Rprt liens faibles
2. Rprt liens perdus
Noeuds
1. ID : TxRef
9:121
2.
7B7177EFACE0049
3. Produit
VA301W
4. Qualité lien
1
5. Mode d’op.
Log
6. Adr reseau
9
7. Fenetre SWU
1
8. # de parents
1
9. DP Id
0
10. DP Adr res
0
11. DP LQ1
2
12. DP Retries
(?)
13. DP BM
0
14. DP LC
256
15. AP1 ID
(?)
16. AP1 Adr res
(?)
17. AP1 LQ1
16
18. AP1 Retries
128
19. AP1 BM
(?)
20. AP1 LC
27132032
21. AP2 ID
2
22. AP2 Adr res 31756
23. AP2 LQ1
198
24. AP2 Retries
190
25. AP2 BM
0
26. AP2 LC
56320
27. LSU
661
28. Statut
Alive
29. Fraicheur
2
30. Version
A14
31. Hiberner
32. Remplacer
33. Enlever
34. Consolider acces
35. ‘Failsafe’
N/A

Menu Systeme
Option Invalide
Mod Log
Log
Association
Ena
PAN ID
VAL : 00000
MAX : 65535
MIN : 00001
MAC 1ere partie
VAL : 00155F00
MAX : FFFFFFFF
MIN : 00000000
Menu Systeme
Aucun nœud trouve
ou

Noeuds
1. ID : TxRef
9:121
2.
7B7177EFACE0049
3. Produit
VA301W
Le menu «Nœuds» affiché dans les
rapports de liens faible et de liens
perdus est identique au menu
«Nœuds» (option 3) du menu Reseau
sans-fil

Menu Systeme
Option Invalide

Hiberner
Enter pour confirmer
Esc pour annuler

Nouveau noeud
VAL : 09
MAX : 3A
MIN : 09
RAZ reseau
Enter pour confirmer
Esc pour annuler
Log Statut
Log
Consolider acces
VAL : 00060
MAX : 65535
MIN : 00000

M-510324
7/10

Log Statut
Enter pour confirmer
Esc pour annuler
Consolider acces
Enter pour confirmer
Esc pour annuler

Manuel de l’utilisateur 301C
Honeywell

79

Programmation du système
Menu reseau sans-fil

Parametres
Lors de la sélection de l’option Parametres depuis le menu Sans-fil, les
paramètres sont affichés en ordre.
Puisque l’écran peut seulement afficher 3 items à la fois, il est
nécessaire de dérouler la liste de paramètres en utilisant les flèches
haut et bas.

Parametres
1.
7B7177EFACE0049
2. WC Version
3. PAN ID
4. Canal RF
5. Mode Log No Log
6. Association
Ena
7. Noeuds
0
8. Max noeuds
0
9. Max sauts
0
10. Puissance
0
11. AHFO
0
12. BO
0
13. SUO
0
14. LCO
18
15. LTO
0
16. MMO
0
17. BMO
0
18. KNSRO
0
19. FNSRO
0
20. Clone WC

Menu Systeme
Option Invalide
Mod Log
Log
Association
Ena
PAN ID
VAL : 00000
MAX : 65535
MIN : 00001
MAC 1ere partie
VAL : 00155F00
MAX : FFFFFFFF
MIN : 00000000

Note: Certaines données sont affichées aux fins d’information
seulement et ne ne sont pas modifiables. Lors de la sélection
d’une de ces données, l’écran affiche brièvement « Menu
Systeme - Option invalide » (tel qu’indiqué ci-haut).

80

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu reseau sans-fil

Modifier le PAN ID ou le Canal RF
Lorsque le PAN ID ou le Canal RF est modifié depuis l’option
Parametres du menu Reseau sans-fils, il est nécessaire de confirmer
les modifications à plusieurs étapes. Les instructions ci-dessous sont
identiques, que ce soit pour modifier le PAN ID ou le Canal RF :
•
•
•
•
•

•

•

Sélectionner Parametres depuis le menu Reseau sans-fil
Dérouler (avec les flèches) pour surligner l’option 3, PAN ID(ou 4,
Canal RF)
Appuyer sur Enter pour sélectionner
Modifier les valeurs PAN ID (ou Canal RF) au besoin puis appuyer
sur Enter
L’écran suivant demande une confirmation. Appuyer sur Enter pour
confirmer (l’appui sur Esc quitte l’option sans enregistrer les
modifications et l’écran revient au menu Reseau sans-fil)
Le système affiche ensuite l’écran Canal RF (ou PAN ID); appuyer
sur Enter pour procéder (ou pour enregistrer les modifications s’il y
a lieu)
L’écran suivant demande une confirmation. Appuyer sur Enter pour
confirmer. L’appui sur Esc à cette étape annule les
modifications au PAN ID (ou Canal RF) et quitte le menu
Parametres
Parametres
1.
7B7177EFACE0049
2. WC Version
3. PAN ID

PAN ID
VAL : FF07
MAX : FFFF
MIN : 0001

PAN ID
Enter pour confirmer
Esc pour annuler

Canal RF
VAL : 011
MAX : 026
MIN : 011

Canal RF
Enter pour confirmer
Esc pour annuler

Note: Le réseau doit se reconstruire lorsqu’il y a une modification du
PAN ID ou du Canal RF. Donc, la perte du réseau complet (le
réseau entier en mode Faute) est normal et le réseau devrait se
rétablir après 10 minutes.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

81

Menu reseau sans-fil

Le tableau ci-dessous contient la liste de paramètres affichés pour le
coordonnateur (module de communication sans fil). Utiliser les flèches
haut et bas pour dérouler la liste.
#
1.
2.

Titre
Valeur
7B177A7EFACE0049
WC Version
A10

3.

PAN ID

FF07

4.

Canal RF

11

5.
6.

Mode Log
Association

Log
Ina

7.

Noeuds

0

8.

Max noeuds

0

9.

Max sauts

0

10.

Puissance

0

11.

AHFO

0

12.

BO

0

13.

SUO

0

14.

LCO

18

82

Description
Adresse MAC du coordonnateur
Version du micrologiciel du
coordonnateur sans fil
L’indificateur hexadécimal assigné au
coordonnateur
Canal de radiofréquence du
coordonateur
Indique si le mode débogage est activé
Détermine si de nouveaux noeuds
peuvent se joindre au réseau
Affiche le nombre de noeuds dans le
réseau
Détermine le nombre maximum de
noeuds permis sur le réseau (1-60)
Détermine le nombre maximum de sauts
permis à u noeud pour atteindre un
coordonnateur sans fil
Règle la valeur d’amplification de
puissance de transmission
Détermine le lapse de temps entre les
cycles de réveil
Règle le lapse de temps entre la
transmission de deux balises
consécutives par un noeud pour établir
et maintenir la synchrinisation
Défini la période de mise à jour de statut;
temps entre 2 paquets de mise à jour de
statut consécutifs envoyés par un node
au coordonnateur
Paquet envoyé du coordonnateur au
noeud pour indiquer au noeud qu’il est
enregistré sur le réseau au
coordonnateur

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu reseau sans-fil
#
15.

Titre
LTO

Valeur
0

16.

MMO

0

17.

BMO

0

18.

KNSRO

0

19.

FNSRO

0

20.

Clone WC

M-510324
7/10

Description
Le nombre de paquets de mise à jour de
statut qui peuvent être manqués sans
qu’un “leave indication” n’est lancé
Défini la bande passante de la mesure
de la relance de message
Défini la bande passante de la mesure
des balises manquées
Défini la fréquence à laquelle le noeud
met à jour les informations de voisins
connus
Défini la fréquence à laquelle le noeud
cherchera de nouveaux voisins
Quoique ce menu est accessible, il
n’effectue aucune fonctions. Il servira
pour des fonctions avancées à venir

Manuel de l’utilisateur 301C
Honeywell

83

Programmation du système
Menu reseau sans-fil

Diagnostics
Le menu diagnostics permet de consulter des rapports de liens faibles
et de liens perdus. Lors de la sélection d’une de ces options, l’écran
affiche une liste d’information pour le noeud (cette liste est identique à
celle de l’option 3, Noeuds, du menu principal Sans-fil). S’il n’y a pas
de liens faibles ou de liens perdus, l’écran affiche brièvement « Menu
Systeme - Aucun noeud trouve » .
Si le rapport de lien faible ou de lien perdu contient plus d’un noeud,
utiliser les flèches de gauche ou de droite pour naviguer d’un noeud à
l’autre et ensuite utiliser les flèches haut et bas pour dérouler la liste
d’informations pour le noeud.

Diagnostics
1. Rprt liens faibles
2. Rprt liens perdus

Menu Systeme
Aucun nœud trouve
ou

Noeuds
1. ID :
121 (79h)
2.
7B7177EFACE0049
3. Produit
VA301W

84

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu reseau sans-fil

Noeuds
Le menu Noeuds contient toutes les informations sur un noeud. Utiliser
les touches de clavier gauche et droite pour naviguer entre les noeud,
puis les flèches haut et bas pour dérouler les informations de chaque
noeud.

Noeuds
1. ID :
121 (79h)
2.
7B7177EFACE0049
3. Produit
VA301W

Chaque ligne représente une information précise, tel qu’indiqué dans
l’image (ci-haut) :
Ligne 1

Ligne 2
Ligne 3

affiche l’identification du dispositif (les deux derniers chiffres
d’un identificateur hexadécimal, exemple 09) et le numéro de
référence de la centrale (121) pour le transmetteur en
question.
affiche l’adresse MAC du dispositif
affiche le type de produit (301W).

L’écran peut seulement afficher trois lignes d’information à la fois, il est
nécessaire d’utiliser les flèches haut et bas pour dérouler la liste.
Consulter le tableau des informations du menu Noeuds ci-dessous pour
connaître les informations et leurs descriptions :

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

85

Programmation du système
Menu reseau sans-fil

Le tableau suivant contient la liste des données affichées pour chaque
noeud. Utiliser les flèches de gauche ou de droite pour naviguer de
noeud en noeud, ensuite utiliser les flèches haut et bas pour dérouler la
liste pour le noeud sélectionné.

#
4.

Titre
Qualité lien

Valeur
1

5.

Mode d’op.

Log

6.

Adr reseau

0009

7.

1

8.

Fenetre
SWU
# de parents

1

9.

DP Id

0

10.

DP Adr res

0

12.

DP LQI

2

12.

DP Retries

(?)

13.

DP BM

0

14.

DP LC

256

15.

AP1 ID

(?)

16.

AP1 Adr res

(?)

86

Description
Pourcentage de la puissance de signal (0100%) d’un noeud, relatif à la qualité de
signal du parent
Enregistre toutes les données d’activité du
dispositif sans-fil sélectionné (dans le
coordonnateur) .
Affiche l’adresse de réseau hexadécimale du
noeud
Affiche la fenêtre SWU utilisée pour
transmettre la balise
Affiche le nombre de parents actuels pour le
noeud, de 0 à 3.
Affiche l’identificateur associé au parent par
défaut
Affiche l’adresse réseau pour le parent par
défaut
Affiche la qualité du lien avec le parent par
défaut :
0 = pas de lien/1 = lien faible/2 = lien fort
Affiche le nombre de relancements du parent
par défaut
Affiche le nombre de balises de parent
manqué sur la dernière période de balise
Affiche le temps depuis la dernière
communication avec le parent par défaut (en
millisecondes)
Affiche l’identificateur associé au parent
alternatif 1
Affiche l’adresse réseau du parent alternatif
1

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu reseau sans-fil
#
17.

Titre
AP1 LQI

Valeur
16

18.

AP1 Retries

128

19.

AP1 BM

(?)

20.

AP1 LC

27132
032

21.

AP2 ID

2

22.

AP2 Adr res

31756

23.

AP2 LQI

198

24.

AP2 Retries

190

25.

AP2 BM

0

26.

AP2 LC

56320

27.

LSU

661

28.
29.

Statut
Freshness

Actif
2

30.

Version

A14

M-510324
7/10

Description
Affiche la qualité du lien avec le parent
alternatif 1 :
0 = pas de lien/1 =lien faible/2 = lien fort
Affiche le nombre de relancements du parent
alternatif 1
Affiche le nombre de balises de parent
alternatif 1 manqué sur la dernière période
de balise
Affiche le temps depuis la dernière
communication avec le parent alternatif 1 (en
millisecondes)
Affiche l’identificateur associé au parent
alternatif 2
Affiche l’adresse réseau du parent alternatif
2
Affiche la qualité du lien avec le parent
alternatif 2 :
0 = pas de lien/1 =lien faible/2 = lien fort
Affiche le nombre de relancements du parent
alternatif 2
Affiche le nombre de balises de parent
alternatif 2 manqué sur la dernière période
de balise
Affiche le temps depuis la dernière
communication avec le parent alternatif 2 (en
millisecondes)
Affiche l’heure de la dernière mise à jour du
système
Indique si le noeud est actif ou inactif
Affiche le nombre de mise à jour de statut qui
peuvent être manqué sans qu’un “leave
indication” n’est lancé
Version du micrologiciel de l’appareil

Manuel de l’utilisateur 301C
Honeywell

87

Programmation du système
Menu reseau sans-fil
#
31.
32.
33.

Titre
Hiberner
Remplacer
Enlever

Valeur

34.

Consolider accès

35.

’Failsafe’

N/A

Description
La sélection d’une de ces options ouvre un
écran de confirmation. Lors de la
confirmation, l’appareil est msi en sommeil
profond (hors tension) pour pouvoir effectuer
des réparations, pour effectuer des
réparations, pour remplacer ou pour enlever
le noeud.
Cette option force le noeud d’emprunter le
meilleur chemin vers la centrale en utilisant
un parent alternatif.
Cette option est seulement disponible
lorsqu’il y a un module de relais dans le
réseau. Permet de préciser la configuration
de relais sécurisé pour une module de relais
sans-fil.

Les options 1 à 29 sont aux fins d’information seulement et ne sont pas
modifiables.
Les options 16 à 21 sont affichées seulement si le noeud sélectionné a
un deuxième parent (un parent est un noeud auquel un autre noeud
peut se connecter pour créer un lien à la centrale).
Les options 22 à 27 sont seulement affichées si le noeud a un
troisième parent.

88

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu reseau sans-fil

Les options 31 à 33 permettent de mettre le détecteur en mode
d’hibernation (hors tension) pour effectuer des réparations, pour
remplacer ou pour enlever le noeud.
Hiberner

Remplacer

Enlever

Met le noeud en hibernation (hors tension). Ce
mode est utilisé aux fins d’entretien ou de
remplacement de pile.
Permet de remplacer un noeud sans changer
l’adresse MAC ni l’identificateur (permet à un noeud
libre avec une adress MAC différente [ou identique]
de se mapper à l’identificateur du noeud actuel).
Enlève le noeud du réseau et efface les données du
noeud de la mémoire du coordonnateur et de la base
de données de la centrale.

Option 34, Consolider acces, permet de forcer le noeud de trouver le
meilleur chemin vers la centrale en utilisant un parent alternatif.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

89

Programmation du système
Menu reseau sans-fil

Nouveau noeud
Le menu Nouveau noeud permet d’ajouter un nouveau noeud dans le
réseau et de préciser le numéro d’identificateur assigné à l’adresse
MAC.
Reseau sans-fil
4. Nouveau noeud
5. Hiberner
6. RAZ reseau

Nouveau noeud
VAL : 09
MAX : 3A
MIN : 09
MAC 1ere partie
VAL : 00155F00
MAX : FFFFFFFF
MIN : 00000000
MAC 2e partie
VAL : 80000024
MAX : FFFFFFFF
MIN : 00000000

•
•
•
•
•
•
•

Dérouler à l’option Nouveau noeud puis appuyer sur Enter pour
sélectionner
Dans l’écran Nouveau noeud, changer le numéro d’identificateur
dans le champs VAL puis appuyer sur Enter
Appuyer sur Enter pour confirmer
Dans l’écran MAC 1ere partie, inscrire les 8 premiers chiffres de
l’adresse MAC* puis appuyer sur Enter
Appuyer sur Enter pour confirmer
Dans l’écran MAC 2e partie, inscrire les 8 derniers chiffres de
l’adresse MAC puis appuyer sur Enter
Appuyer sur Enter pour confirmer

*L’adresse MAC du noeud est imprimer sur le boîtier du noeud.
Note: Si le numéro d’identificateur existe déjà, cette fonction ne sera
pas complétée.

90

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Programmation du système
Menu reseau sans-fil

Menu Hiberner
Le menu Hiberner permet de mettre (le réseau) en hibernation, c’est à
dire de mettre les appareils sur le réseau hors tension. Ceci permet de
faire de l’entretien sans risque d’endommager les appareils.

Reseau sans-fi
4. Nouveau noeud
5. Hiberner
6. RAZ reseau

Hiberner
Enter pour confirmer
Esc pour annuler

Menu RAZ reseau
Cette fonction, qui devraient seulement être utilisé par des
techniciens autorisés et qualifiés, réinitialise les paramètres de
réseau sans-fil à zéro, permettant aux noeuds de rechercher une
centrale en mode Association.
Reseau sans-fi
4. Nouveau noeud
5. Hiberner
6. RAZ reseau

ATTENTION

M-510324
7/10

RAZ reseau
Enter pour confirmer
Esc pour annuler

Cette fonction réinitialise les noeuds; lorsque réinitialisés, les
identificateurs des noeuds peuvent changer, ce qui rend les
Événements et les Groupes de la centrale inopérants et
invalides.

Manuel de l’utilisateur 301C
Honeywell

91

Programmation du système
Menu reseau sans-fil

Menu Log Statut
Ce menu permet de générer un fichier log qui sera enregistré sur la
carte mémoire de la centrale (nommé waammjjq.log). Le registre
contient 27 colonnes d’informations, correspondantes aux 27 premiers
champs du menu noeuds.
Reseau sans fil
5. Hiberner
6. RAZ reseau
7. Log Statut
NoLog

Log Statut
Log

Log Statut
Enter pour confirmer
Esc pour annuler

Le fichier générer peut ensuite être consulté sur un ordinateur ou
imprimé, selon les besoins.

Menu Consolider Acces
Quoique les noeuds recherchent toujours le meilleur chemin de
communication avec la centrale, cette fonction active immediatement la
recherche. Les noeuds rechercheront donc le meilleur chemin, avec le
moins de sauts vers la centrale en utilisant un parent alternatif.

Reseau sans fil
6. RAZ reseau
7. Log Statut
NoLog
8. Consolider acces

92

Consolider acces
VAL : 00060
MAX : 65535
MIN : 00000

Manuel de l’utilisateur 301C
Honeywell

Consolider acces
Enter pour confirmer
Esc pour annuler

M-510324
7/10

Programmation du système
Menu reseau sans-fil

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

93

MODULE BACNET/IP
(option -BIP)

Spécifications
Port Ethernet :
Indicateurs :

10/100-compatible avec 10Base-T interface, RJ-45
DEL vert
LINK
DEL jaune ACT

Configuration de réseau
Voir section du menu VA301C BACnet.

Protocole BACnet/IP
Port UDP/IP: 47808, non modifiable depuis la centrale VA301C.
Le module est développé selon la norme 135-2001 ANSI/ASHRAE :
« BACnet®— A Data Communication Protocol for Building Automation
and Control Networks ». L'option de couche liaison de données (Data
Link Layer) est selon le BACnet/IP (Annexe J).

http://www.ashrae.org/

M-510324
7/10

Manuel d’utilisateur 301C
Honeywell

95

Objets BACNet

Objets BACNet
Les objets BACnet représentent toutes les informations disponibles par
le sous-réseau du VA301C. Chacune des valeurs disponibles est
représentée par un objet de type précis. Il y a actuellement six types
d'objets supportés :
Entrée analogique
Valeur analogique
Entrée binaire

représenté par ‘AI’
représenté par ‘AV’
représenté par ‘BI’

Sortie binaire

représenté par ‘BO’

Valeur binaire

représenté par ‘BV’
représenté par
‘DEV’

Dispositif

(Analog Input)
(Analog Value)
(Binary Input)
(Binary
Output)
(Binary Value)
(Device)

Entrée analogique
Le type d'objet Entrée analogique définit un objet normalisé dont les
propriétés représentent des caractères externes visibles d'une entrée
analogique, tel un détecteur de gaz.
Les propriétés supportés pour un objet d'entrée analogique sont :
Object_Identifier, Object_Name, Object_Type, Status_Flags,
Event_State, Reliability, Out of Service et Present_Value and Units.
Valeur analogique
Le type d'objet Valeur analogique définit un objet normalisé dont les
propriétés représentent des caractères externes visibles d'une valeur
analogique. Une valeur analogique est un paramètre de système de
contrôle dans la mémoire du dispositif BACNet, tel un niveau de gaz.
Les propriétés supportés pour un objet valeur analogique sont :
Object_Identifier, Object_Name, Object_Type, Status_Flags,
Event_State, Reliability, Present_Value, Out_of_Service et Units.

96

Manuel d’utilisateur 301C
Honeywell

M-510324
7/10

Objets BACNet

Entrée binaire
Le type d'objet Entrée binaire définit un objet normalisé dont les
propriétés représentent des caractères externes visibles d'une entrée
binaire. Une entrée binaire est un appareil ou un matériel physique qui
peut être seulement en un de deux états possibles, tels les entrées
numériques du VA301ADI.
Les propriétés supportés pour un objet entrée binaire sont :
Object_Identifier, Object_Name, Object_Type, Status_Flags,
Event_State, Reliability, Present_Value, Polarity, Inactive_Text,
Out_of_Service et Active_Text.
Sortie binaire
Le type d'objet Sortie binaire définit un objet normalisé dont les
propriétés représentent des caractères externes visibles d'une sortie
binaire. Une sortie binaire est un appareil ou un matériel physique qui
peut être seulement en un de deux états possibles, tels les relais ou les
puissances de sorties commutables.
Les propriétés supportés pour un objet entrée binaire sont :
Object_Identifier, Object_Name, Object_Type, Status_Flags,
Event_State, Reliability, Present_Value, Polarity, Inactive_Text,
Active_Text, Priority_Array, Out_of_Service et Relinquish_Default.
Valeur binaire
Le type d'objet Valeur binaire définit un objet normalisé dont les
propriétés représentent des caractères externes visibles d'une valeur
binaire. Une valeur analogique est un paramètre de système de
contrôle dans la mémoire du dispositif BACNet.
Les propriétés supportés pour un objet entrée binaire sont :
Object_Identifier, Object_Name, Object_Type, Status_Flags,
Event_State, Reliability, Present_Value, Inactive_Text, Active_Text,
Priority_Array, Out_of_Service et Relinquish_Default.

M-510324
7/10

Manuel d’utilisateur 301C
Honeywell

97

Objets BACNet

Dispositif
Le type d'objet Dispositif définit un objet normalisé dont les propriétés
représentent des caractères externes visibles d'un dispositif BACNet. Il
y a seulement un objet Dispositif pour représenter le module BACNet.
Les propriétés supportés pour un objet dispositif sont :
Object_Identifier, Object_Name, Object_Type, System_Status,
Vendor_Name, Vendor_Identifier, Model_Name, Firmware_Revision,
Application_Software_Version, Protocol_Version, Protocol_Revision,
Protocol_Services_Supported, Protocol_Object_Types_Supported,
Object_List, Max_APDU_Length_Accepted, Segmentation_Supported,
APDU_Timeout, Number_Of_APDU_Retries,
Device_Address_Binding, Database_Revision, Local_Time,
Local_Date, UTC_Offset and Daylight_Savings_Status.

Produits Vulcain et objets BACnet
Nom d'objets
Les noms d'objets sont composés en deux parties, ainsi :
La première partie est composée du label d'affichage (nom du produit)
du dispositif de réseau où réside l'objet. La deuxième partie est son
étiquette repère unique parmi tous les objets du même dispositif.
Ex : “301D2 CO2 AD:14.CO2” où ‘301D2 CO2 AD:14’ est le label
d'affichage du dispositif et ‘CO2’ est le label repère unique qui identifie
l'objet comme une sonde CO2.

98

Manuel d’utilisateur 301C
Honeywell

M-510324
7/10

Objets BACNet

Labels repères d'objets Vulcain
Labels repères
.‘Gas label’
.Alrm
.Amin / .Amax
.Bmin / .Bmax
.Cmin / .Cmax
.relx
.buzz
.outx
.AIx
.BIx
.RH
.Temp

M-510324
7/10

Description
Capteur de gaz
Niveau d'alarme simple
Niveau d'alarme A et
hystérésis
Niveau d'alarme B et
hystérésis
Niveau d'alarme C et
hystéerésis
Sortie relais X (1 à 8)
Sortie alarme sonore
Output X (1 to 3)
Analog input X (1 to 16)
Binary Input X (1 to 12)
Relative Humidity sensor
Temperature sensor

Manuel d’utilisateur 301C
Honeywell

Type d'objet
AI
AV
AV
AV
AV
BO
BO
BO ou BV
AI
BI
AI
AI

99

Objets BACNet

Objets pour les dispositifs de réseau Honeywell
Objets pour les dispositifs de réseau Honeywell
Dispositif GP2

301IRF

301EM

201T2/vulbus 90DM3R

.GAZ

.GAZ

.GAZ

.GAZ

.GAZ

.Amin

.Amin

.Amin

.Amin

.Alrm

.Amax

.Amax

.Amax

.Amax

.Bmin

.Bmin

.Bmin

.Bmin

.Bmax

.Bmax

.Bmax

.Bmax

.Cmin

.Cmin

.Cmin

.Cmin

.Cmax

.Cmax

.Cmax

.Cmax

.rel1

.rel1

.rel1 (snsr1) .rel1

.rel2

.rel2

.rel2 (snsr1)

.rel3

.rel3 (snsr1)
.rel4 (snsr1)
.out1
(snsr1)

Objets

.out2
(snsr1)

M-510324
7/10

.out3
(snsr1)

Manuel d’utilisateur 301C
Honeywell

100

Objets BACNet

Objets pour les dispositifs de réseau Honeywell
Objets pour les dispositifs de réseau Honeywell
Dispositif

301AP

301C

301R

301ADI

901T

.rel1

.rel1

.rel1

.AI1 to .AI16 .GAZ

.rel2

.rel2

.rel2

.BI1 to .BI12 .Amin

.rel3

.rel3

.rel3

.Amax

.buzz

.rel4

.rel4

.Bmin

.buzz

.rel5

.Bmax

.rel6

.Cmin

.rel7

.Cmax

Objets

.rel8

M-510324
7/10

Manuel d’utilisateur 301C
Honeywell

101

Objets pour les dispositifs de réseau Honeywell
Objets pour les dispositifs de réseau Honeywell
Dispositif

ECF9

S301RLC

301W

301RW

Std.Device*

.GAZ

.GAZ

.GAZ

.rel1

.GAZ

.Amin

.Amin

.Amin

.rel2

.Amin

.Amax

.Amax

.Amax

.rel3

.Amax

.Bmin

.Bmin

.Bmin

.rel4

.Bmin

.Bmax

.Bmax

.Bmax

.rel5

.Bmax

.Cmin

.Cmin

.Cmin

.rel6

.Cmin**

.Cmax

.Cmax

.Cmax

.rel7

.Cmax**

Objets

.rel8

* Std.Device comprend les produits suivants : S301M, 420MDBS and
90DM4
** Les valeurs .Cmin et .Cmax s’appliquent uniquement au 90DM4.

Objets BACNet

Exemples d'objet
Exemple 1
Voici une représentation de l'entrée de sonde d'un dispositif de réseau
VA301D2 de Vulcain.
Name : “301D2 CO2 AD:14.CO2”
Value : 600
Units : PPM
Object : 1.AI2*
Description : Analog Input
* 1 est l'instance de dispositif unique du 301C, AI est le type d'objet et 2
est l'instance unique de l'objet dans ce dispositif. Cet objet est identifié
« Entrée analogique 2 du dispositif BACNet 1 ».
Exemple 2
Voic une représentation du statut de sortie du relais 2 du même
dispositif de réseau de Vulcain avec un label d'affichage de dispositif
différent.
Name : “Floor 01 Sensor 02 .rel2”
Value : OFF
Units :
Object : 1.BO4*
Description : Binary Output
*Cet objet est identifié « Sortie binaire 4 du dispositif BACNet1 ».
Exemple 3
Voici une représentation du premier statut de sortie 24V d'un dispositif
de réseau de Vulcain 301EM.
Name : “301EM CO AD:25.out1”
Value : OFF
Units :
Object : 1.BV1
Description : Binary Value*
*Cet objet est identifié « Valeur binaire 1 du dispositif BACNet 1 ».
M-510324
7/10

Manuel d’utilisateur 301C
Honeywell

103

Énoncé de conformité d'implémentation de protocole

Énoncé de conformité d'implémentation
de protocole
(NORMATIF)
Énoncé de conformité d'implémentation de protocole BACnet
Date : août 1 2005
Nom du vendeur : Honeywell Analytics
Nom du produit : 301C -BIP
Numéro de modèle du produit : N/A
Version de logiciel d'application : 1.0
Révision de micro logiciel : 1.0
Révision de protocole BACnet : 1.0

Description du produit :
Le 301C -BIP comporte un module utilisant la communication BACnet.
Comme tel, les composantes d'un réseau Vulcain peuvent être
connectées sur le réseau BACnet par la centrales 301C.

Profil de dispositif normalisé BACnet
(Standardized Device Profile) :
 BACnet Operator Workstation (B-OWS)
 BACnet Building Controller (B-BC)
 BACnet Advanced Application Controller (B-AAC)
 BACnet Application Specific Controller (B-ASC)
 BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

105

Énoncé de conformité d'implémentation de protocole

Liste de toutes les unités de structure d'interopérabilité BACnet
supportées (Annexe K) :
Partage de données

 Data Sharing-ReadProperty-A (DS-RP-A)
 Data Sharing-ReadProperty-B (DS-RP-B)
 Data Sharing-ReadPropertyMultiple-A (DS-RPM-A)
 Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)
 Data Sharing-ReadPropertyConditional-A (DS-RPC-A)
 Data Sharing-ReadPropertyConditional-B (DS-RPC-B)
 Data Sharing-WriteProperty-A (DS-WP-A)
 Data Sharing-WriteProperty-B (DS-WP-B)
 Data Sharing-WritePropertyMultiple-A (DS-WPM-A)
 Data Sharing-WritePropertyMultiple-B (DS-WPM-B)
 Data Sharing-COV-A (DS-COV-A)
 Data Sharing-COV-B (DS-COV-B)
 Data Sharing-COVP-A (DS-COVP-A)
 Data Sharing-COVP-B (DS-COVP-B)
 Data Sharing-COV-Unsolicited-A (DS-COVU-A)
 Data Sharing-COV-Unsolicited-B (DS-COVU-B)
Planification

 Scheduling-A (SCHED-A)
 Scheduling-Internal-B (SCHED-I-B)
 Scheduling-External-A (SCHED-E-B)
Tendances

 Viewing and Modifying Trends-A (T-VMT-A)
 Trending-Viewing and Modifying Trends-Internal-B (T-VMT-I-B)
 Trending-Viewing and Modifying Trends-External-B (T-VMT-E-B) 
Trending-Automated Trend Retrieval-A (T-ATR-A)
 Trending-Automated Trend Retrieval-B (T-ATR-B)

106

Manuel de l’utilisateur 301C
Honeywell

M-510324
7/10

Énoncé de conformité d'implémentation de protocole

Gestion de réseau

 Network Management-Connection Establishment-A (NM-CE-A)
 Network Management-Connection Establishment-B (NM-CE-B)
 Network Management-Router Configuration-A (NM-RC-A)
 Network Management-Router Configuration-B (NM-RC-B)
Gestion d'alarme et d'événement

 Alarm and Event-Notification-A (AE-N-A)
 Alarm and Event-Notification Internal-B (AE-N-I-B)
 Alarm and Event-Notification External-A (AE-N-E-B)
 Alarm and Event-ACK-A (AE-ACK-A)
 Alarm and Event-ACK-B (AE-ACK-B)
 Alarm and Event-Alarm Summary-A (AE-ASUM-A)
 Alarm and Event-Alarm Summary-B (AE-ASUM-B)
 Alarm and Event-Enrollment Summary-A (AE-ESUM-A)
 Alarm and Event-Enrollment Summary-B (AE-ESUM-B)
 Alarm and Event-Information-A (AE-INFO-A)
 Alarm and Event-Information-B (AE-INFO-B)
 Alarm and Event-LifeSafety-A (AE-LS-A)
 Alarm and Event-LifeSafety-B (AE-LS-B)
Gestion de dispositif

 Device Management-Dynamic Device Binding-A (DM-DDB-A)
 Device Management-Dynamic Device Binding-B (DM-DDB-B)
 Device Management-Dynamic Object Binding-A (DM-DOB-A)
 Device Management-Dynamic Object Binding-B (DM-DOB-B)
 Device Management-DeviceCommunicationControl-A (DM-DCC-A)
 Device Management-DeviceCommunicationControl-B (DM-DCC-B)
 Device Management-Private Transfer-A (DM-PT-A)
 Device Management-Private Transfer-B (DM-PT-B)
 Device Management-Text Message-A (DM-TM-A)
 Device Management-Text Message-B (DM-TM-B)
 Device Management-TimeSynchronization-A (DM-TS-A)
 Device Management-TimeSynchronization-B (DM-TS-B)
 Device Management-UTCTimeSynchronization-A (DM-UTC-A)
 Device Management-UTCTimeSynchronization-B (DM-UTC-B)
 Device Management-ReinitializeDevice-A (DM-RD-A)
 Device Management-ReinitializeDevice-B (DM-RD-B)
 Device Management-Backup and Restore-A (DM-BR-A)
 Device Management-Backup and Restore-B (DM-BR-B)
M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

107

Énoncé de conformité d'implémentation de protocole

 Device Management-List Manipulation-A (DM-LM-A)
 Device Management-List Manipulation-B (DM-LM-B)
 Device Management-Object Creation and Deletion-A (DM-OCD-A)
 Device Management-Object Creation and Deletion-B (DM-OCD-B)
 Device Management-Virtual Terminal-A (DM-VT-A)
 Device Management-Virtual Terminal-B (DM-VT-B)
Capacité de segmentation :

 Segmented requests supported window Size
 Segmented responses supported window Size : Take maximum
Windows size supported by the other device
Types d'objets normalisés supportés :
Entrée
analogique
Sortie
analogique
Valeur
analogique
Entrée binaire

Pour tout objet:
1) ne peut être créé dynamiquement
avec le service « CreateObject »
2) ne peut être supprimer
dynamiquement avec le service
« DeleteObject »
3) aucunes autres propriétés
inscriptibles n'existent

Sortie binaire

4) aucune propriété propriétaire existe

Valeur binaire
Dispositif

5) aucune restriction de plage

108

Manuel de l’utilisateur 301C
Honeywell

Analog
Input
Analog
Output
Analog
Value
Binary Input
Binary
Output
Binary Value
Device

M-510324
7/10

Énoncé de conformité d'implémentation de protocole

Options Couche liaison de données
(Data Link Layer) :
 BACnet IP, (Annex J)
 BACnet IP, (Annex J), Foreign Device
 ISO 8802-3, Ethernet (Clause 7)
 ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
 ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)
 MS/TP master (Clause 9), baud rate(s):
 MS/TP slave (Clause 9), baud rate(s):
 Point-To-Point, EIA 232 (Clause 10), baud rate(s):
 Point-To-Point, modem, (Clause 10), baud rate(s):
 LonTalk, (Clause 11), medium:
 Other:
Association d'adresse de dispositif :
L'association de dispositif statique est supporté? (En ce moment, ceci
est nécessaire pour la communication bidirectionnelle avec les
esclaves MS/TP et certains autres dispositifs.) Yes No
Options de réseautage:
 Router, BACnet / Modbus.
 Annex H, BACnet Tunneling Router over IP
 BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? Yes No
Jeux de caractères supportés :
L'indication du support de multiples jeux de caractères ne signifie pas
qu'ils peuvent tous être supportés simultanément.
 ANSI X3.4 IBM/Microsoft DBCS ISO 8859-1
 ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226
Si ce produit est un point d'accés de communication, décrire les types
d'équipements ou réseaux non-BACnet supportés par le point d'accès :

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

109

Spécifications

Spécifications
Alimentation 301C

17-27 Vca, 50/60 Hz, 8.64 VA
18-36 Vcc, 350mA@24 Vcc, 8.4 VA

Plage de température de
fonctionnement
Plage d’humidité relative
de fonctionnement
Altitude de fonctionnement
Capacité mise en réseau

Communication
(longueur de lignes)
Portée communication
sans fil
Interface utilisateur
Indicateurs visuels

Sorties
Alarme sonore
Délais
Pile
Boîtier
Dimensions (h, l, p)
Poids
Certifications

M-510324
8/10

-20°C à 50°C (-4°F to 122°F)
0 à 95% RH (sans-condensation)
Jusqu’à 3,000 m (9843 pi)
Jusqu’à 96 transmetteurs, 32 par port
Ports 1, 2 = Modbus et Vulbus
Port 3 = Modbus seulement
Port 4 = Communication esclave (c-à-d. pour
option BACNet)
Jusqu’à 609 m (2,000 feet) par port
Dérivation maximum = 20 m (65pi) par
dérivation, 40 m au total (130 pi)
30 m (98.5 pi)
Affichage graphique à matrice 122 x 32 points
à rétroéclairage, clavier convivial
Alimentation DEL vert
Alarme A, B, C DEL rouge
Faute
DEL jaune
Tx
DEL jaune
Rx
DEL vert
4 relais DPDT
5A, 30Vcc ou 250 Vca (charge résistive)
65dBA à 1 m (3 pi)
Délais configurables Avant/Après
Pile au lithium 3 V
NEMA 4X, ABS-polycarbonate - intérieure
28 x 20.3 x 7cm (7.99” x 11.02” x 2.76”)
1.1 Kg (2.4 lbs)
conforme à ANSI/UL 61010-1
CAN/CSA C22.2 No. 61010-1
ETL 116662

Manuel de l’utilisateur 301CW
Honeywell

111

Garantie limitée

Garantie limitée
Garantie limitée
Honeywell Analytics, Inc. garantie à l’Acheteur d’origine et/ou au client
final (« Acheteur ») de produits Vulcain (« Produit ») que si une pièce
quelconque du produit s’avère défectueuse , soit en matériel ou en
main d’oeuvre, dans douze (12) mois, cette pièce sera réparée ou
remplacer, sans frais, à la discrétion d’Honeywell Analytics si expédié,
port payé, à Honeywell Analytics at 4005 Matte Blvd., Unit G, Brossard,
Quebec, J4Y 2P4, dans l’emballage d’origine ou l’équivalent. Le Produit
sera retourné au client port payé si Honeywell Analytics détermine que
la pièce est défectueuse en raison de défaut matériel ou de main
d’oeuvre. La réparation ou le remplacement d’une telle pièce
défectueuse représente la seule et exclusive responsabilité
d’Honeywell Analytics sous cette garantie limitée.
Politique de Retour
Les frais suivants seront applicables lors de retour de produit pour
crédit :
•

Des frais de retour de 15% seront appliqués lorsque le produit est
retourné dans le 1er mois suivant la date d’expédition

•

Des frais de retour de 30% seront appliqués lorsque le produit est
retourné dans les 3 mois suivant la date d’expédition

Un crédit total (moins les frais de retour) sera uniquement appliqué si le
produit est en parfait état de fonctionnement. Si des réparations sont
nécessaires sur le produit retourné, les frais de cette réparation seront
déduit du crédit.
Auncuns crédits ne seront appliqués pour les retours après les 3 mois
suivant la date d’expédition.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

113

Garantie limitée

Exclusions
A. Si des capteurs de gaz font partie du Produit, le capteur est
couvert par une garantie limitée de douze (12) mois du fabricant.
B. Si les capteurs de gaz sont couverts par cette garantie limitée,
le capteur sera assujeti à l’inspection par Honeywell Analytics pour
l’exposition prolongée à des concentrations de gaz élevées si
l’Acheteur fait une réclamation sous cette garantie limitée. SI
l’inspection indique que la cause de la défectuosité est l’épuisement du
capteur plutôt qu’un défaut, cette garantie ne s’appliquera pas au
Produit.
C. Cette garantie limitée ne s’applique pas au produits
consommables, tels les piles, ou les articles sujets à l’usure ou au
remplacement régulier, incluant les lampes, les fusibles, les valves, les
aubes, les élements de sonde, les cartouches ou les éléments de
filtres.
Limitation et exclusion de la garantie
Honeywell Analytics n’aura aucun autre responsabilité sous cette
garantie limitée. Toutes responsabilités de garantie d’Honeywell
Analytics sont annulées si le Produit a subi des abus, de la
négligeance, un accident ou si l’Acheteur est en défaut de ses
obligations tels que décrit dans cette garantie ou si le Produit n’a pas
été utilisé selon les instructions ou si le numéro de série du Produit été
enlevé ou modifié.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

114

Garantie limitée

Dénégation de responsabilité d’autres garanties
La garantie ci-haut est la seule garantie applicable à cet achat. Toutes
autres garanties, soit implicites ou exprès, incluant mais pas limité à,
les garanties tacites de qualité marchande ou de l’aptitude à un emploi
particulier sont dénéguées par le présent document.
Limitation de responsabilité
Il est entendu que la responsabilité d’Honeywell Analytics, soit en
contrat, en délit civil, sous n’importe quelle garantie de responsabilité,
en négligence ou autrement n’excédera pas le prix d’achat payé par
l’Acheteur pour le produit. Honeywell Analytics ne sera pas
responsable, sous aucune circonstance, pour des dommages spéciaux
ou indirectes. Le prix déclaré pour le produit est une considération
limitant la responsabilité d’Honeywell Analytics. Aucune action, en
quelle forme que soit, survenant des transactions sous cette garantie
peuvent être entreprises par l’Acheteur plus d’un an après l’occurence
de la cause de ces actions.

M-510324
7/10

Manuel de l’utilisateur 301C
Honeywell

115



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Author                          : e487851
Create Date                     : 2006:08:21 11:54:58Z
Modify Date                     : 2010:08:12 12:55:20-05:00
Has XFA                         : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Creator Tool                    : FrameMaker 9.0
Metadata Date                   : 2010:08:12 12:55:20-05:00
Producer                        : Acrobat Distiller 9.3.3 (Windows)
Format                          : application/pdf
Title                           : Bilingual_Cover Page.fm
Creator                         : e487851
Document ID                     : uuid:1cf43216-17cc-4980-be37-48514beb1590
Instance ID                     : uuid:c5f41b8c-2e01-4499-8c63-b4cf45e2dc5a
Page Mode                       : UseOutlines
Page Count                      : 228
EXIF Metadata provided by EXIF.tools

Navigation menu