MS4120F; MS4620F,S;
MS8120F,S; S2024-F; S20230-F
Fast-Acting, Two-Position Actuators
PRODUCT DATA

FEATURES
• 175 lb-in. (20 N•m) minimum driving torque at 350°F
(176°C).
• Reversible mounting facilitates use in either clockwise
(cw) or counterclockwise (ccw) spring rotation.
• Integral spring return ensures level of return torque.
• Stainless steel internal spring.
• Fifteen-second spring return timing.
• No special cycling required during long-term holding.
(See Operation section.)
• No audible noise during holding.
• Patent pending design eliminates need for limit
switches to reduce power consumption.
• Models available for 24, 120, and 230 Vac applications.
• Ninety-five degree angle of rotation.
• Actuator holds rated torque at reduced power level.
• Die-cast aluminum housing.

APPLICATION

• Housing design allows flush mounting to damper.
• Self-centering shaft adapter (SCSA), patent pending.

The MS4120F, MS4620F, MS8120F, S2024-F, and S20230-F
Fast-Acting, Two-Position Actuators are spring return direct
coupled actuators (DCA) for on/off damper control. The
actuator accepts an on/off signal from a single-pole, singlethrow (spst) controller. Reversible mounting allows actuator to
be used for either clockwise (cw) or counterclockwise (ccw)
spring rotation.
Designed to operate reliably in smoke control systems
requiring Underwriter’s Laboratories Inc. UL555S ratings up to
350°F.

MS4120F, MS4620F, MS8120F

• High temperature Teflon® lead wires.
• Models available with integral high temperature (350°F)
SPST position-indicating switches (7°, 85° stroke).

S2024-F, S20230-F, MS4620S, MS8120S

APPLICABLE LITERATURE
— Specification Data Sheet
— Motor/Actuator Selection Guide
for Damper Applications
— Engineering Manual of Automatic Control
(also called The Gray Manual)
— Direct Coupled Actuator
Quick Selection Guide
— Damper Torque Calculator

• Designed to operate reliably in smoke control systems
requiring Underwriter’s Laboratories Inc. UL555S
ratings up to 350°F.

• Double-insulation rating.
63-2592
63-8419

• High-temperature, halogen-free, silicone-free
leadwires.
• Models available with integral high temperature (350°F)
SPDT position-indicating switches (7°, 85° stroke).

77-1100
63-8553
63-8437

63-2584—7

MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

SPECIFICATIONS

Timing (At Rated Torque and Voltage):
Drive Open: 15 seconds typical.
Spring Close: 15 seconds typical.

Models: See Tables 1, 2, and 3.
Table 1. Models.
Model

Voltage Internal Auxiliary
in Vac
Switches

MS4120F1006

120

None

MS4120F1204

120

2 SPSTa

MS4620F1005

230

None

MS4620F1203

230

2 SPSTa

MS8120F1002

24

None

MS8120F1200

24

2 SPSTa

S2024-F (MS8120S1006)

24

None

S20230-F (MS4620S1009)

230

S2024-F-SW2 (MS8120S1204)

24

Auxiliary Switches:
Ratings (maximum load): 250 Vac, 5A resistive, 3A inductive.
Settings (fixed): 7° nominal stroke, 85° nominal stroke.
Torque Rating (at Rated Voltage):
Typical Holding (minimum at 350°F): 175 lb-in. (20 N•m).
Spring Return (minimum at 350°F): 175 lb-in. (20 N•m).
Stall Maximum (fully open at 75°F): 425 lb-in. (48.0 N•m).
350°F Minimum Driving: 175 lb-in. (20 N•m).
Design Life (at Rated Voltage): 30,000 full stroke cycles.
Minimum Damper Shaft Length:
1 in. (25 mm); 3-1/4 (83 mm) recommended.
Cycling Requirements:
Prolonged holding-period (1 year) testing of these actuators
has been performed with no spring return failures. The
actuator and the internal spring are designed to require no
special cycling during long-term holding.
Honeywell recommends following all local, state and national
codes for periodic testing of the entire smoke control
system. Refer to National Fire Protection Association
(NFPA) National Fire Codes®: NFPA90A, NFPA92A and
NFPA92B for your application.
NFPA recommends periodic examination of each fire/smoke
damper (semi-annually or annually) to ensure proper
performance.

2 SPDTa

S20230-F-SW2 (MS4620S1207) 230
a Internal

switches are designed to pass UL555S
requirements (at 350°F).

Dimensions: See Fig. 1.
Device Weight: 7 lb (3.2 kg).
Stroke: 95° ± 3°, mechanically limited.
Electrical Ratings:
Power Input:
MS4120F: 120 Vac ±10%, 60 Hz.
MS4620F,S; S20230-F: 230 Vac ±10%, 50/60 Hz.
MS8120F,S; S2024-F: 24 Vac +20%, -10%, 50/60 Hz
(Class 2).
Power Consumption:
MS4120F: Driving: 0.35A, 35W. Holding: 0.15A, 10W.
MS4620F,S; S20230-F:
Driving: 0.20A, 35W. Holding: 0.14A, 10W.
MS8120F,S; S2024-F: Driving: 45 VA. Holding: 10 VA.

Mounting: Self-centering shaft adapter.
Round Damper Shafts: 0.5 to 1.06 in.
Square Damper Shafts: 1/2 to 3/4 in.
Actuator can be mounted with shaft in any position.
IMPORTANT
• Honeywell does not recommend using linkages with
these actuators because side-loading of the output
hub reduces actuator life.
• 3/4 in. or greater shaft diameter recommended.
Noise Rating at 1m (Maximum):
Driving or Spring Return: 70 dBA.
Holding: 20 dBA (no audible noise).

Electrical Connections:
Lead Wires:
MS4120F, MS4620F, MS8120F: 1m Teflon wire.
MS4620S, MS8120S, S2024-F, S20230-F: 1m halogenfree, silicone-free wire.
Two integral 3/8 in. flexible conduit connections.

ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2584—7

2

MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

Temperature Ratings:
Ambient: -40°F to 130°F (-40°C to 55°C).
Shipping and Storage: -40°F to 140°F (-40°C to 60°C).

Table 3. Actuator Selection (S20 Series).
S Fail Safe Function (Spring Return)
20 20 N•m (175 lb-in.)

IMPORTANT
The actuator is designed to meet UL555S standards
at 350°F (176°C). The actuator must be tested with
the damper to achieve this rating.

24 24 Vac 2-position Control; Reversible Mount Spring Return
230 Vac 2-position Control; Reversible Mount Spring
230 Return

NOTE: The actuator is designed to operate for 30 minutes
during a one-time excursion to 350°F (176°C).

F Fire and Smoke Actuator
No Auxiliary Switches
-SW2

Humidity Ratings: 5% to 95% RH noncondensing.
Environmental Protection Ratings:
NEMA2 and IP54 when mounted on a horizontal shaft.

S 20 24 - F

Two Auxiliary Switches

-SW2

Accessories:
205649 Mounting Bracket (not supplied with actuator).

Table 4. Approvals.
S20230-F,
S2024-F,
MS4620F, MS4620S,
MS4120F MS8120F MS8120S

Approvals: See Table 4.
Controller Type:
MS4120F: Line voltage (120 Vac), 2-position, spst (Series 40).
MS4620F,S; S20230-F: Line voltage (230 Vac), 2-position, spst
(Series 40).
MS8120F,S; S2024-F: Low voltage (24 Vac), 2-position, spst
(Series 80).
Table 2. Actuator Selection (MS Series).
M Electrical Motor

UL/cUL

X

X

UL873 Plenum Rating,
File No. E4436;
Guide No. XAPX.a

X

X

CE

X

X

C-TICK

X

X

a Plenum

S Fail Safe Function (Spring Return)
41 120 Vac 2-position Control; Reversible Mount Spring Return

applications require that conductors be enclosed in
conduit (see Wiring section for conduit details).

46 230 Vac 2-position Control; Reversible Mount Spring Return

3-15/16 (100)
2 (50)

81 24 Vac 2-position Control; Reversible Mount Spring Return
20 175 lb-in. (20 N•m)

1-9/16
(40)

F Fire and Smoke (US)
S Fire and Smoke (EU)
1 No Feedback
0 No Auxiliary Switches
2 Two Auxiliary Switches
XX System Controlled Numbers
M S 41

10-11/16
(271)

20 F 1 2 XX
8-5/8
(220)

M20051

1/4 (6)

2-15/16 (75)

Fig. 1. Dimensional drawing of actuator in inches (mm).

3

63-2584—7

MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

INSTALLATION

Determine Appropriate Mounting Orientation

When Installing this Product...

NOTES:
—
—

1.
2.
3.
4.

See Fig. 2 for mounting orientation.

Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
Installer must be a trained, experienced service
technician.
After installation is complete, check out product
operation as provided in these instructions.

—

Actuators are shipped in the fully closed position.
An arrow molded into the hub points to tick marks
on the label to indicate the hub rotary position.
See Fig. 3 for proper mounting to a square damper
shaft.

CCW TO CLOSE
(FAIL-SAFE
POSITION)

CW TO CLOSE
(FAIL-SAFE
POSITION)

CW TO OPEN

CCW TO OPEN

WARNING

Electrical Power Hazard.
Line voltage can cause death or serious injury
and short equipment circuitry.
Disconnect power supply before installation.

CAUTION

M20052

Electrical Shock or Equipment Damage Hazard.
Low voltage can shock individuals or short
equipment circuitry.
Disconnect power supply before installation.

Fig. 2. Spring Return DCA mounting orientation.

IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.

Location
The actuators are designed to open a damper by driving the
damper shaft in either a clockwise
or counterclockwise
direction. The actuator housing has two slots on the
bottom, either of which, with a 205649 Mounting Bracket,
secures it flush to a damper box (see Fig. 2).
NOTE: When mounted correctly, these slots allow the
actuator to float without rotating relative to the damper
shaft.

CAUTION

Equipment Damage Hazard.
Tightly securing actuator to damper housing can
damage actuator.
Mount actuator to allow it to float along its vertical axis.

Preparation
Before mounting the actuator onto the damper shaft, determine
the:
— Damper/valve opening direction for correct spring return
rotation. The actuator can be mounted to provide clockwise
or counterclockwise spring return.
— Damper shaft size (see Specifications section).

63-2584—7

4

M21007

DAMPER SHAFT

Fig. 3. Proper mounting to square damper shaft.

Measure Damper/Valve Shaft Length
If the shaft is less than three inches in length, the shaft
coupling must be located between the damper/valve and
actuator housing. If the shaft length is more than three inches,
the shaft coupling may be located on either side of the actuator
housing.
If the coupling must be moved from one side of the actuator to
the reverse, follow these instructions (see Fig. 4):
1. Remove the retainer clip from the shaft coupling and set
it aside for later use.
2. Remove shaft coupling from one side of the actuator.
3. Replace the shaft coupling on the opposite side of the
actuator aligning it based on the stroke labelling.
4. Replace the retainer clip on the shaft coupling using the
groove of the coupling.

MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

5.
6.
7.

Turn damper blades to desired normal (closed) position.
Place actuator and mounting bracket back into position
and secure bracket to damper box with sheet metal
screws.
Using 10 mm wrench, tighten shaft coupling securely
onto damper shaft using minimum 120 lb-in., maximum
180 lb-in. torque.

M20054

Fig. 4. Mounting shaft coupling to actuator opposite side.

Mounting

CAUTION

1

Device Malfunction Hazard.
Improper shaft coupling tightening causes device
malfunction.
Tighten shaft coupling with proper torque to prevent
damper shaft slippage.

CAUTION

Actuator Damage Hazard.
Using actuator as shaft bearing causes device
damage.
Use actuator only to supply rotational torque. Avoid any
side loads to actuator output coupling bearings.

To mount actuator, proceed as follows:
1. Place actuator over damper shaft; and hold mounting
bracket in place. See Fig. 5.
2. Mark screw holes on damper housing.
3. Remove actuator and mounting bracket.
4. Drill or center-punch holes for mounting screws (or use
no.10 self-tapping sheet metal screws).

2

1

ENSURE THAT MOUNTING ASSEMBLY PREVENTS ACTUATOR
ROTATION AND ALLOWS ACTUATOR TO FLOAT ALONG
INDICATED AXIS. WHEN TOO TIGHT, THE RESULTING BINDING
CAN DAMAGE THE ACTUATOR OR REDUCE TORQUE OUTPUT.

2

ACCESSORY MOUNTING BRACKET IS NOT SUPPLIED WITH
M20055
THE ACTUATOR.

Fig. 5. Mounting actuator to damper housing.

NOTE: If necessary, use a field-fabricated steel base plate
secured with sheet metal screws.

5

63-2584—7

MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

WIRING
See Fig. 6 through 10 for typical wiring diagrams.
MS4620F

WARNING

L2 ( )

Electrical Power Hazard.
Line voltage can cause death or serious injury and
short equipment circuitry.
Disconnect power supply before installation.

BLUE

230 VAC
L1 ( )

GREEN

7° AUXILIARY
SWITCH

CAUTION

Electrical Shock or Equipment Damage Hazard.
Disconnect all power supplies before installation.
Motors with auxiliary switches can have more than one
disconnect.

IMPORTANT
1. All wiring must comply with local electrical codes,
ordinances and regulations.
2. Voltage and frequency of transformer used with
MS8120F,S and S2024-F must correspond with the
characteristics of power supply and actuator.

85° AUXILIARY
SWITCH

BLUE
BLUE
YELLOW
YELLOW

M20057A

Fig. 8. Typical 230 Vac wiring (MS Series).
S2024-F-SW2, MS8120S

L2 ( )

BLUE

230 VAC

BROWN

L1 ( )

NOTE: The conduit fittings are designed for use with 3/8 in.
reduced-wall steel or aluminum flexible conduit.

GRAY/BLUE
85° AUXILIARY
SWITCH

MS8120F

GRAY/RED
GRAY/YELLOW
BLACK/BLUE

L2 ( )

7° AUXILIARY
SWITCH

BLACK
24 VAC

BROWN

BLACK/RED
BLACK/YELLOW

RED
M20678A

L1 ( )

Fig. 9. Typical 24 Vac wiring (S20 Series).
GREEN
7° AUXILIARY
SWITCH

S20230-F-SW2, MS4620S

BLUE
BLUE
YELLOW

85° AUXILIARY
SWITCH

L2 ( )

YELLOW

230 VAC
L1 ( )

M20053A

Fig. 6. Typical 24 Vac wiring (MS Series).

BLUE
BROWN

GRAY/BLUE
85° AUXILIARY
SWITCH

MS4120F

GRAY/RED
GRAY/YELLOW
BLACK/BLUE

L2 ( )
120 VAC
L1 ( )

7° AUXILIARY
SWITCH

WHITE

BLACK/RED
BLACK/YELLOW

BLACK
M20680A

GREEN

Fig. 10. Typical 230 Vac wiring (S20 Series).
7° AUXILIARY
SWITCH

BLUE
BLUE
YELLOW

85° AUXILIARY
SWITCH

YELLOW

M20056A

Fig. 7. Typical 120 Vac wiring (MS Series).

63-2584—7

6

MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

OPERATION

SPST Switches (Table 5)
See Fig. 6 through 8 for SPST auxiliary switch wiring.

The actuators are designed for use in Smoke Control Systems.
If power fails, the actuator spring returns to the 0° position. The
actuator mounts flush with the damper box. The actuator drives
from 0° to 95° and spring returns back to 0°.
The actuators are operated by an spst two-position controller.
When using an spst two-position controller, the actuator drives
to the damper fully open position when controller contact
makes and spring returns to the damper fully closed position
when controller contact breaks. The actuator drops to holding
power level on detection of stall, independent of hub position.

Table 5. SPST Auxiliary Switch Operation.
Makes

Wire
Color

Switch

Breaks

(degrees from fully closed position)

7°

blue

less than 7

greater than 7

85°

yellow

greater than 85

less than 85

NOTE: Both sets of contacts are open when the actuator is
between 7° and 85°.

SPDT Switches (Fig. 11)

Cycling
The actuator and the internal spring are designed so that no
special cycling during long-term holding is required. Honeywell
recommends following all local, state, and national codes for
periodic testing of the entire smoke control system. Refer to
National Fire Protection Association (NFPA) National Fire
Codes®: NFPA90A, NFPA92A, and NFPA92B for your
application.

See Fig. 9 through 11 for SPDT auxiliary switch wiring.

7° SWITCH
LESS 7°

85° SWITCH
MORE 7°

LESS 85°

MORE 85°

BLACK/BLUE

BLACK/BLUE

GRAY/BLUE

GRAY/BLUE

BLACK/RED

BLACK/RED

GRAY/RED

GRAY/RED

BLACK/YELLOW

BLACK/YELLOW

GRAY/YELLOW

GRAY/YELLOW
M20679B

Auxiliary Switches

Fig. 11. SPDT auxiliary switch operation.

Some models include auxiliary switches (see Table 1).

7

63-2584—7

MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

CHECKOUT

3.
4.

MS4120F (120 Vac model)
1.
2.
3.
4.
5.
6.

Check damper position.
Connect 120 Vac to the black and white leadwires to
drive the damper to the open position. The actuator
should drive the damper.
If the actuator does not run, remove power for at least
two seconds.
If the actuator spring returns, allow it to close entirely,
then return to step 2.
If the actuator does not spring return, verify that the actuator is properly installed. See Installation section.
If the actuator is correctly installed but neither runs nor
spring returns, replace the actuator.

5.
6.

MS8120F,S; S2024-F (24 Vac models)
1.
2.
3.
4.

MS4620F,S; S20230-F (230 Vac models)
1.
2.

5.

Check damper position.
Connect 230 Vac to the blue and brown leadwires to
drive the damper to the open position. The actuator
should drive the damper.

63-2584—7

6.

8

If the actuator does not run, remove power for at least
two seconds.
If the actuator spring returns, allow it to close entirely,
then return to step 2.
If the actuator does not spring return, verify that the actuator is properly installed. See Installation section.
If the actuator is correctly installed but neither runs nor
spring returns, replace the actuator.

Check damper position.
Connect 24 Vac to the red and black leadwires to drive
the damper to the open position. The actuator should
drive the damper.
If the actuator does not run, remove power for at least
two seconds.
If the actuator spring returns, allow it to close entirely,
then return to step 2.
If the actuator does not spring return, verify that the actuator is properly installed. See Installation section.
If the actuator is correctly installed but neither runs nor
spring returns, replace the actuator.

MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

D Montageanweisung

NL Installatievoorschrift

F Instructions d’Installation

DK Installasjonsinstruks

I Istruzioni per I’Installazione

A

S Installations Instrukioner

N Installationsinstrukioner

!

D
F
I
NL
DK
N
FIN
S
E

SF Asennusohje
E Instrucciones de montage

A1,
A4

24 VAC
120 VAC
230 VAC

a

ASSEMBLY
EINBAU
MONTAGE
MONTAGGIO
MONTAGE
MONTERE
MONTERING
ASENTAMINEN
MONTERA
MONTAJE

b
M20726

M20727

A2

A3
d

a
b
c

b

M12030

M20728

A5

A6

10 mm

b
a

b
a

M20730A

M20729

9

63-2584—7

MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

B

B2

B1
!

24 VAC
120 VAC
230 VAC

a
D
F
I
NL
DK
N
FIN
S
E

DISASSEMBLY
AUSBAU
DÉMONTAGE
SMONTAGGIO
DEMONTAGE
AFMONTERE
DEMONTERE
PURKAMINEN
NEDMONTERA
DESMONTAJE

b
M20732

M20733A

M20731A

B3

B4
a

M20734

63-2584—7

10

M20735A

MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

11

63-2584—7

MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

Teflon® is a registered trademark of the E.I. du Pont de Nemours and Company.
National Fire Codes® is a registered trademark of the National Fire Protection Association (NFPA).

Automation and Control Solutions
Honeywell International Inc.

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN 55422

Scarborough, Ontario M1V 4Z9

customer.honeywell.com
® U.S. Registered Trademark
© 2006 Honeywell International Inc.
63-2584—7 C.H. Rev. 03-06



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Encryption                      : Standard V1.2 (40-bit)
User Access                     : Print, Copy, Fill forms, Extract, Assemble, Print high-res
Page Count                      : 12
Page Mode                       : UseOutlines
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:76ae3cfe-0dec-40ce-b249-48a431bcfe3a
Producer                        : Acrobat Distiller 6.0.1 (Windows)
Creator Tool                    : FrameMaker 7.0
Modify Date                     : 2006:03:14 10:50:16-06:00
Create Date                     : 2005:07:01 11:41:56Z
Metadata Date                   : 2006:03:14 10:50:16-06:00
Document ID                     : uuid:58ba8745-4e33-4bbf-95d9-a07fa2159a87
Format                          : application/pdf
Title                           : 63-2584-7 - MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F Fast-Acting, Two-Position Actuators
Creator                         : Honeywell ECC Technical Communications
Description                     : Product Data
Author                          : Honeywell ECC Technical Communications
Subject                         : Product Data
EXIF Metadata provided by EXIF.tools

Navigation menu