Honeywell Notifier Ifs 2600 Users Manual Install V3_01
IFS-2600 to the manual 1e530b99-d5ae-4bcc-97f7-4c9b2f2572bf
2015-01-23
: Honeywell Honeywell-Notifier-Ifs-2600-Users-Manual-261874 honeywell-notifier-ifs-2600-users-manual-261874 honeywell pdf
Open the PDF directly: View PDF
.
Page Count: 80
| Download | |
| Open PDF In Browser | View PDF |
IFS-2600
Fire Indicator Panel
TECHNICAL, PROGRAMMING
& INSTALLATION MANUAL
8/05/08
P/N 10069
Rev:
3.01
ECN08-0066
Installation Precautions
Adherence to the following will aid in
problem-free installation with long-term
reliability:
WARNING - Several different sources of power
can be connected to the fire alarm control
panel. Disconnect all sources of power before
servicing. Control unit and associated equipment
may be damaged by removing and/or inserting
cards, modules, or interconnecting cables while the
unit is energized. Do not attempt to install, service,
or operate this unit until manuals are read and
understood.
Verify that wire sizes are adequate for all
initiating and indicating device loops. Most devices
cannot tolerate more than a 10% I.R. drop from the
specified device voltage.
Like all solid state electronic devices, this
system may operate erratically or can be damaged
when subjected to lightning induced transients.
Although no system is completely immune from
lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or
outside aerial wiring is not recommended, due to
an increased susceptibility to nearby lightning
strikes. Consult with the Technical Services
Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to
removing or inserting circuit boards. Failure to do
so can damage circuits.
Remove all electronic assemblies prior to any
drilling, filing, reaming, or punching of the
enclosure. When possible, make all cable entries
from the sides or rear. Before making
modifications, verify that they will not interfere with
battery, transformer, or printed circuit board
location.
Do not over tighten screw terminals. Over
tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty
with screw terminal removal.
This system contains static-sensitive
components. Always ground yourself with a
proper wrist strap before handling any circuits so
that static charges are removed from the body.
Use static suppressive packaging to protect
electronic assemblies removed from the unit.
Follow the instructions in the installation,
operating, and programming manuals. These
instructions must be followed to avoid damage to
the control panel and associated equipment.
FACP operation and reliability depend upon proper
installation.
This equipment must be correctly programmed
and installed to suit the specific application.
Please ensure correct operational parameters are
set prior to commissioning. If further details on
programming options are required, please consult
the programming manual or contact our helpful
technical support personnel.
EMC WARNING:
This equipment may radiate radio frequency energy. It may also be affected by radio frequency energy and, if
not installed and operated in accordance with the manufacturers instructions, may cause interference to radio
communications. It has been tested and found to comply with the Class A radiated and conducted EMI
requirements of AS/NZ 3548:1995 (including Amendments 1 & 2) as well as the EMI susceptibility
requirements of Clause C3.5 in AS4428.0:1997.
Radio communication devices should not be used in the vicinity of fire panels or associated ancillary devices
and systems.
Documentation Feedback
Your feedback helps us keep our documentation up to date and accurate. If you have any comments or suggestions about
our printed manuals you can email us.
Please include the following information:
Product name and version number (if applicable)
Manual part number and revision (found on the front cover)
Page number
Brief description of the content you think should be improved or corrected
Your suggestion for how to correct/improve documentation
Send email messages to:
techpubs@notifier.com.au
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
you nearest branch for technical support.
IFS-2600 Installation & Programming Manual
Page 1
TABLE OF CONTENTS
COMPATIBLE DETECTORS................................................................................................5
OVERVIEW...........................................................................................................................6
CAUTION ........................................................................................................................................................................... 6
SPECIFICATION...................................................................................................................7
APPROVALS...................................................................................................................................................................... 7
ENVIRONMENTAL LIMITS........................................................................................................................................... 7
POWER SUPPLY RATINGS AND SETTINGS ............................................................................................................. 9
INTERNAL 24 VDC (nom) 3.0A MAIN POWER SUPPLY .......................................................................................... 9
INTERNAL 27.3V DC 1.5A BATTERY CHARGER ..................................................................................................... 9
Internal 5VDC 2A Power Supply ..................................................................................................................................... 9
EXTERNAL 27VDC POWER SUPPLY ....................................................................................................................... 10
BATTERY TYPE AND CAPACITIES .......................................................................................................................... 10
TECHNICAL DESCRIPTION ..............................................................................................11
GENERAL ........................................................................................................................................................................ 11
TRANSIENT SUPPRESSION......................................................................................................................................... 11
CURRENT CONSUMPTION ......................................................................................................................................... 11
AZF DESCRIPTION........................................................................................................................................................ 12
AZF SUPERVISORY CURRENT .................................................................................................................................. 12
OVERLOAD PROTECTION.......................................................................................................................................... 12
ZONE OVERLOAD SELF RESET ................................................................................................................................ 12
PRINTER OUTPUT......................................................................................................................................................... 13
CABLE CONNECTION .................................................................................................................................................. 13
PROGRAMMING BY COMPUTER ............................................................................................................................. 13
ALIGNMENT AND ADJUSTMENT .....................................................................................14
PCB2006 POWER SUPPLY BOARD ............................................................................................................................ 14
INTERNAL 24VDC (nom) POWER SUPPLY.............................................................................................................. 14
INTERNAL 27.3 VDC BATTERY CHARGER............................................................................................................ 14
EXTERNAL 24VDC (nom) POWER SUPPLY (if fitted) ............................................................................................. 14
P/N 10069 ECN08-0066
Page 2
IFS-2600 Installation & Programming Manual
PCB2005 TERMINATION BOARD............................................................................................................................... 14
INTERNAL 5VDC POWER SUPPLY TP8................................................................................................................... 14
POWER SUPPLY COMPARATOR REFERENCE VOLTAGE TP10 ......................................................................... 14
NON ADJUSTABLE TEST POINTS.............................................................................................................................. 14
ALARM THRESHOLD COMPARATOR TP7............................................................................................................. 15
FAULT THRESHOLD COMPARATOR TP6 .............................................................................................................. 15
CONFIGURATION JUMPERS ...................................................................................................................................... 16
IFS2004 - JP3 DEFAULT ............................................................................................................................................. 16
IFS2004 - JP4 PROGRAM DISABLE .......................................................................................................................... 16
IFS2004 - JP5 CPU RESET........................................................................................................................................... 16
IFS2005 – JP2 DOOR HOLDER BYPASS................................................................................................................... 16
IFS2006 – JP1 EXTERNAL PS MONITORING .......................................................................................................... 16
IFS804 - JP1-7 ZONE BOARD ADDRESSING........................................................................................................... 16
PLACING INTO OPERATION ............................................................................................ 17
EQUIPMENT AS FITTED .............................................................................................................................................. 17
INITIAL CHECKLIST .................................................................................................................................................... 17
POWER UP CHECKLIST............................................................................................................................................... 18
FUNCTIONAL TESTING ............................................................................................................................................... 18
FAULT RECORD............................................................................................................................................................. 19
INSTRUCTIONS TO OPERATORS.................................................................................... 20
INDICATORS ................................................................................................................................................................... 20
SUGGESTED ALARM PROCEDURE .......................................................................................................................... 21
OPERATOR INSTRUCTIONS....................................................................................................................................... 21
FIREFIGHTER FUNCTIONS........................................................................................................................................ 21
GLOBAL FUNCTIONS ................................................................................................................................................. 22
ZONE FUNCTIONS....................................................................................................................................................... 24
PROGRAMMING ................................................................................................................ 27
GLOBAL OPTIONS......................................................................................................................................................... 27
ZONE OPTIONS .............................................................................................................................................................. 27
OUTPUT RELAY OPTIONS .......................................................................................................................................... 28
DEFAULT SETTINGS..................................................................................................................................................... 28
PROGRAM MODE.......................................................................................................................................................... 29
PROGRAMMING MODE.............................................................................................................................................. 29
PROGRAMMING HIERARCHY .................................................................................................................................. 29
ZONES............................................................................................................................................................................ 29
RELAYS ......................................................................................................................................................................... 30
GLOBAL ........................................................................................................................................................................ 30
PRINT............................................................................................................................................................................. 30
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 3
MAIN MENU.................................................................................................................................................................... 30
EXIT PROGRAMMING MODE ................................................................................................................................... 31
ZONE PROGRAMMING................................................................................................................................................ 31
SELECT ZONE # ........................................................................................................................................................... 31
ZONE SELECTED......................................................................................................................................................... 31
ZONE TYPE .................................................................................................................................................................. 31
ZONE OUTPUT CONFIGURATION ........................................................................................................................... 32
RELAY PROGRAMMING MODE................................................................................................................................ 32
SELECT RELAY # ........................................................................................................................................................ 32
RELAY SELECTED ...................................................................................................................................................... 32
RELAY TYPE ................................................................................................................................................................ 33
RELAY MAPPING ........................................................................................................................................................ 33
GLOBAL PROGRAMMING.......................................................................................................................................... 33
ACF OUTPUT................................................................................................................................................................ 34
AVF ................................................................................................................................................................................ 34
RELAY (GLOBAL RELAY UNITY MAP) .................................................................................................................. 34
PRINT PROGRAMMING DATA .................................................................................................................................. 35
TIME (DATE & TIME) ................................................................................................................................................... 35
APPENDIX A ......................................................................................................................36
DESCRIPTION OF ALARM ZONE TYPES ................................................................................................................ 36
LATCHING TYPE......................................................................................................................................................... 36
NON LATCHING TYPE ............................................................................................................................................... 36
TIME DELAY AZF........................................................................................................................................................ 37
APPENDIX B ......................................................................................................................38
ZONE OUTPUT CONFIGURATIONS.......................................................................................................................... 38
APPENDIX C ......................................................................................................................39
ALARM VERIFICATION FACILITY (AVF) .............................................................................................................. 39
GLOBAL PROGRAMMABLE OPTIONS.................................................................................................................... 39
APPENDIX D ......................................................................................................................40
ANCILLARY TRIP (ACF).............................................................................................................................................. 40
GLOBAL PROGRAMMABLE OPTIONS.................................................................................................................... 40
APPENDIX E.......................................................................................................................41
RELAY OUTPUT MAPPING......................................................................................................................................... 41
AND MAPPING ............................................................................................................................................................... 41
OR MAPPING .................................................................................................................................................................. 41
FAULT MAPPING........................................................................................................................................................... 41
FAULT/ISOLATE MAPPING ........................................................................................................................................ 42
ISOLATE MAPPING ...................................................................................................................................................... 42
P/N 10069 ECN08-0066
Page 4
IFS-2600 Installation & Programming Manual
APPENDIX F ...................................................................................................................... 43
GLOSSARY OF TERMS................................................................................................................................................. 43
APPENDIX G...................................................................................................................... 44
SUMMARY OF TERMINATIONS AND CAUTIONS................................................................................................. 44
MCP LOOP..................................................................................................................................................................... 44
DETECTION ZONES .................................................................................................................................................... 44
RELAY OUTPUTS ........................................................................................................................................................ 44
BELL OUTPUTS ........................................................................................................................................................... 44
ACF OUTPUTS.............................................................................................................................................................. 44
WARNING SYSTEM..................................................................................................................................................... 44
DOOR HOLDER OUTPUTS ......................................................................................................................................... 44
AUXILIARY POWER & MIMIC POWER ................................................................................................................... 44
MAF ISOL & TRANSPONDER 0V .............................................................................................................................. 44
MIMIC DATA & CLOCK.............................................................................................................................................. 44
AC INPUT ...................................................................................................................................................................... 44
BATTERY ...................................................................................................................................................................... 45
DOOR HOLDER AC INPUT ......................................................................................................................................... 45
OUTPUT RELAYS ........................................................................................................................................................ 45
APPENDIX H ...................................................................................................................... 46
IFS-2600 PROGRAMMED OPTIONS........................................................................................................................... 46
APPENDIX I........................................................................................................................ 53
TECHNICAL DRAWINGS ............................................................................................................................................. 53
MAIN KEYPAD AND DISPLAY.................................................................................................................................. 53
EXPANSION DISPLAY ................................................................................................................................................ 53
Block Connection Diagram............................................................................................................................................. 54
System Sensor Conventional Detector Connection Diagram .......................................................................................... 54
System Sensor Conventional Detector Connection Diagram .......................................................................................... 55
Hochiki Conventional Detector Connection Diagram..................................................................................................... 55
Hochiki Conventional Detector Connection Diagram..................................................................................................... 56
Ancillary Connection Diagram........................................................................................................................................ 57
ASE Connection Diagram............................................................................................................................................... 58
Auto Changeover Dual Sounder Connection Diagram.................................................................................................... 59
Auto Change Over Dual Sounder Connection Diagram.................................................................................................. 60
MIMIC Connection Diagram .......................................................................................................................................... 61
Single Fan Connection Diagram ..................................................................................................................................... 62
Dual Fan Connection Diagram........................................................................................................................................ 63
Exhaust Fan Connection Diagram................................................................................................................................... 64
Supply Fan Connection Diagram .................................................................................................................................... 65
Smoke Spill Fan Connection Diagram ............................................................................................................................ 66
10W EVAC Connection Diagram................................................................................................................................... 67
10W EVAC Slave Connection Diagram ......................................................................................................................... 68
30W EVAC Connection Diagram................................................................................................................................... 69
30W EVAC Slave Connection Diagram ......................................................................................................................... 70
50W EVAC Connection Diagram................................................................................................................................... 71
50W EVAC Slave Connection Diagram ......................................................................................................................... 72
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 5
COMPATIBLE DETECTORS
Make
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
Model
Thermal
Thermal
Thermal
Thermal
Thermal
Thermal
Thermal
Smoke
Smoke
Smoke
Thermal
Smoke
Smoke
Type
Type A
Type A
Type B
Type B
Type B Sealed
Type C
Type D
Photo-Optical
Photo-Optical
Ionisation
Type D
Beam
Duct
Model Number
5451 AUS
51A51
4451 AUS
51B51
51B51S
51C51
51D51
2151 AUS
2151B AUS
1151 AUS
51D51
BEAM1224
DHP-100
Apollo
Apollo
Apollo
Apollo
Apollo
Apollo
Thermal
Thermal
Thermal
Thermal
Smoke
Smoke
Type A
Type B
Type C
Type D
Ionisation
Photo Optical
Series 60
Series 60
Series 60
Series 60
Series 60
Series 60
Hochiki
Hochiki
Hochiki
Hochiki
Hochiki
Hochiki
Hochiki
Hochiki
Hochiki
Hochiki
Hochiki
Hochiki
Hochiki
Hochiki
Hochiki
Thermal
Thermal
Thermal
Thermal
Thermal
Thermal
Thermal
Thermal
Thermal
Thermal
Thermal Cool Room
Smoke
Smoke
Smoke
Smoke
Type A
Type A
Type A
Type B
Type B
Type C
Type C
Type C
Type D
Type D
Type B sealed
Ionisation
Ionisation
Photo Optical
Photo Optical
DCA-B-60R MkV
DCC-A
DCD-A
DFE-60B
DFJ-60B
DCA-B-90R Mk1
DCC-C
DCD-C
DFE-90D
FDJ-90D
DFG-60BLKJ
SIH-AM
SIJ-ASN
SLK-A
SLR-AS
Olsen
Olsen
Olsen
Olsen
Olsen
Olsen
Thermal
Thermal
Thermal
Thermal
Smoke
Smoke
Type A
Type B
Type C
Type D
Ionisation
Photo Optical
T56B-T6A
T56B-T6B
T56B-T6C
T56B-T6D
C24B
P24B
Panelect
Panelect
Panelect
Panelect
Panelect
Panelect
Panelect
Panelect
Thermal
Thermal
Thermal
Thermal
Smoke
Smoke
Smoke
Smoke
Type A
Type B
Type C
Type D
Ionisation
Ionisation
Photo Optical
Photo Optical
PFS-A
PFS-B
PFS-C
PFS-D
PFS-I
PFS-I , MkII
PFS-P
PFS-P, MkII
IEI
VESDA E700, E70D
CONTACT DEVICE
Please contact NOTIFIER INERTIA for any additional detectors.
P/N 10069 ECN08-0066
Page 6
IFS-2600 Installation & Programming Manual
OVERVIEW
IFS-2600 Fire Indicator Panel (FIP) is designed to provide simplicity to the end user. The FIP uses both a liquid crystal
display and conventional LED displays for fast and accurate display of system status and changing events.
A custom designed membrane keypad is used together with the liquid crystal display and LED indicators to provide fast,
efficient and simple modes of operation. The keypad also provides the required flexibility for the programming of the
many user configurable options of this FIP. The FIP can be configured on-site without the need of expensive
programmers or components.
A serial printer can also be connected if required. The printer can be used to output programming information for ease of
modification, for safekeeping and to assist in the commissioning of the installation.
IFS-2600 uses serial chain mimic outputs which significantly saves time and costs of cabling to mimic panels.
A door holder power supply (using optional transformer) is incorporated into the system for the release of smoke and fire
doors on alarm.
IFS-2600 is available in a standard 8-zone configuration and can be expandable to its fully expanded state as required.
The IFS-2600 in its fully expanded state can;
•
•
•
•
•
•
Monitor 64 detection zones
Control 64 optional "mapped" relay outputs
Output to a serial printer
Output serially to a mimic panel
Control to door holders
Interface as required to any Australian Fire Brigade
IFS-2600 has been designed to be functional, flexible and reliable whilst maintaining a user-friendly interface.
CAUTION
IFS-2600 FIP has been tested and approved to AS4428.1 and meets the requirements of AS1670 and AS1668 Parts 1 &
2.
However, the equipment must be correctly programmed and installed to suit the specific application. Please ensure
correct operational parameters are set prior to commissioning. If further details on programming options are required,
please consult the programming manual or contact our helpful technical support personnel.
WARNING:
This equipment may radiate radio frequency energy. It may also be affected by radio frequency energy and, if
not installed and operated in accordance with the manufacturers instructions, may cause interference to radio
communications. It has been tested and found to comply with the Class A radiated and conducted EMI
requirements of AS/NZ 3548:1995 (including Amendments 1 & 2) as well as the EMI susceptibility
requirements of Clause C3.5 in AS4428.0:1997
CAUTION: Radio communication devices should not be used in the vicinity of fire panels or associated
ancillary devices and systems
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 7
SPECIFICATION
Cabinet
Zinc Sealed Steel 1.6mm
Powder Coated
Hinged Inner Door
Hinged Outer Door
Outside Dimensions
2608 (8 zones)
2624 (24 zones)
2600 (32 to 64 zones)
Battery Box
394mm H x 390mm W x 180mm D*
750mm H x 390mm W x 180mm D*
18U, 28U & 40U Cabinets
*Note: the depth quoted is including the door and break glass.
The internal cabinet depth not including he door and break glass
is 140mm.
AC Operational Voltage
240 VAC 50Hz
+ 10%
Internal Power Supplies
Battery Charger
27.3 VDC
Panel Supply
24 VDC (nom) 3.0AMP
Logic Supply
5 VDC
1.5AMP
2.0AMP
Microprocessor
80C52
Memory Type
Non-volatile E ROM
Liquid Crystal Display
2 Lines x 16 Characters LED Backlit
Fuses
F1: Panel Supply
M205 5A
F2: Battery Charger
F3: Battery Protection
F4: External Supply
F5: Door Holder
F6: Aux Power Output
F7: Bell
F8: Warning System
F9: ACF
M205 3A
Polyfuse 3A
M205 7A
M205 3A
M205 1A Slow Blow
M205 1A
M205 1A
M205 1A
E.O.L Resistor On AZFs, monitored
outputs, Bells, Warning system, ACF
APPROVALS
Australian Standard AS4428.1 1998
SSL Approval No AFP-1553
C-Tick Approval No. N1336
ENVIRONMENTAL LIMITS
-10 Deg. C to +55 Deg. C Dry heat.
+40 Deg. C @ 93% Relative Humidity.
P/N 10069 ECN08-0066
2
4K7 Ohms
Page 8
IFS-2600 Installation & Programming Manual
SYSTEM EXPANSION
Zones
8
16
24
32
40
48
56
64
Qty
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
3
2
1
1
1
4
2
1
1
1
5
3
1
1
1
6
3
1
1
1
7
4
Hardware Required
Main Control Board
Main Termination board
Power Supply board
Main Control board
Main Termination board
Power Supply board
8 Zone Expansion board
16 Zone Indicator board
Main Control board
Main Termination board
Power Supply board
8 Zone Expansion board
16 Zone Indicator board
Main Control board
Main Termination board
Power Supply board
8 Zone Expansion board
16 Zone Indicator board
Main Control board
Main Termination board
Power Supply board
8 Zone Expansion board
16 Zone Indicator board
Main Control board
Main Termination board
Power Supply board
8 Zone Expansion board
16 Zone Indicator board
Main Control board
Main Termination board
Power Supply board
8 Zone Expansion board
16 Zone Indicator board
Main Control board
Main Termination board
Power Supply board
8 Zone Expansion board
16 Zone Indicator board
Product Code
PCB-2004
PCB-2005
PCB-2006
PCB-2004
PCB-2005
PCB-2006
PCB-804G3
PCB-816
PCB-2004
PCB-2005
PCB-2006
PCB-804G3
PCB-816
PCB-2004
PCB-2005
PCB-2006
PCB-804G3
PCB-816
PCB-2004
PCB-2005
PCB-2006
PCB-804G3
PCB-816
PCB-2004
PCB-2005
PCB-2006
PCB-804G3
PCB-816
PCB-2004
PCB-2005
PCB-2006
PCB-804G3
PCB-816
PCB-2004
PCB-2005
PCB-2006
PCB-804G3
PCB-816
Additional relay outputs:
Relays
8
16
24
32
40
48
56
64
Qty
1
2
3
4
5
6
7
8
Hardware Required
Relay board containing 8 relays 24VDC 1A
Relay board containing 8 relays 24VDC 1A
Relay board containing 8 relays 24VDC 1A
Relay board containing 8 relays 24VDC 1A
Relay board containing 8 relays 24VDC 1A
Relay board containing 8 relays 24VDC 1A
Relay board containing 8 relays 24VDC 1A
Relay board containing 8 relays 24VDC 1A
P/N 10069 ECN08-0066
Product Code
IFS-717
IFS-717
IFS-717
IFS-717
IFS-717
IFS-717
IFS-717
IFS-717
IFS-2600 Installation & Programming Manual
Page 9
POWER SUPPLY RATINGS AND SETTINGS
INTERNAL 24 VDC (nom) 3.0A MAIN POWER SUPPLY
This supply's primary function is to power panel logic and all external operations of the FIP, i.e.: detection
circuits, ancillary circuits, etc. This supply meets the requirements of AS4428.5.
AC Input
Output Current
Output Voltage
Current Limit
Output Ripple
30 VAC +10% - 15%
3.0 AMPS
26.5 VDC
3.0 AMPS
50 mV
INTERNAL 27.3V DC 1.5A BATTERY CHARGER
Its primary function is to charge the batteries. This supply meets the requirements of AS4428.5.
AC Input
Output Current
Output Voltage
Current Limit
Output Ripple
30 VAC +10% -15%
1.5 AMPS
27.3 VDC
1.5 AMPS
200 mV
Important Note:
After a power failure, the battery will only reconnect to the charger if the battery voltage is above approximately
20V +/- 2V.
A battery fault will be generated in the event that the battery does not automatically reconnect. This is to ensure
that a faulty or dead flat battery (due to an extended power failure) does not bring the entire system down.
In order to reconnect a flat battery, it is necessary to disconnect the battery from the panel and charge it
externally. The battery should be thoroughly tested before returning it to service.
In the event that an external charger is not available, the battery may be trickle charged above 22V via a 30
ohm, 5W resistor connected between the 24v Aux Output and the battery positive terminal. A 1N4004 Diode
(Notifier part number #286) or similar should also be fitted in series with the resistor to stop the battery from
pulling down the main panel voltage. Trickle charging the battery by this method may take several hours to
bring it up to the minimum level.
The battery can then be reconnected to the panel for charging via the internal battery charger. It is important
that the voltage on the battery be monitored to ensure that it is charging. The battery should then be left for 24
hours and then fully tested to ensure that no damage has occurred due to the deep discharge.
Internal 5VDC 2A Power Supply
This supply's primary function is to power all internal operations of the FIP, i.e.: Microprocessor, liquid crystal
display, LED's keypad etc.
AC Input
Output Current
Output Voltage
Current Limit
Output Ripple
P/N 10069 ECN08-0066
30 VAC +15% or 27.6VDC+15%
2.0 AMPS
5.0 VDC
2.0 AMPS
150 mV
Page 10
IFS-2600 Installation & Programming Manual
EXTERNAL 27VDC POWER SUPPLY
This supply is used in addition to the internal power supply for large systems. Its primary function is to power
any additional ancillary loads of the FIP up to 7 amps. This supply meets the requirements of AS4428.5
Important Notes:
When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU monitoring.
If this supply is used to power a NI-2008 gas module, the following additional components are required to
ensure a break free change over from the mains supply to the panel battery in case of mains fail condition.
1. A 6A4 or P600G rectifier diode (Notifier part number #266) is to be installed in series with the
external +27V output of the IFS-2600 termination board.
2. A 3300µF 50V Electrolytic Capacitor (Notifier part number #1248) should be installed across the
+27V and 0V of the ancillary device.
IFS-2600 TERMINATION BOARD
AC
REMOTE REMOTE BATT
INPUT OUTPUT INPUT INPUT
24V 0V 24V 0V +
6A4
POWER IN
+
OUTPUT
EXTERNAL
POWER
SUPPLY
3300uF
24V
0V
NI-2008 GAS
SUPPRESSION
MODULE
0V
24V
BATTERY TYPE AND CAPACITIES
In general, any Sealed Lead Acid Battery, or Wet Lead Acid Battery designed for stationary use is compatible
with the IFS-2600 Fire Indicator Panel. Automotive batteries must not be used. The use of Nickel Cadmium
batteries is not recommended.
Manufacturer
Type
Number
Voltage
Capacity (Ah)
Qty Required
Best and Best
Sealed LA
BP17-12
12
17
2
Best and Best
Sealed LA
BP24-12
12
24
2
Best and Best
Sealed LA
BP40-12
12
40
2
Olympic Batteries
Sealed LA
CJ12-7
12
7
2
Olympic Batteries
Sealed LA
CJ12-12
12
12
2
Olympic Batteries
Sealed LA
CJ12-18
12
18
2
Olympic Batteries
Sealed LA
CJ12-26
12
26
2
Olympic Batteries
Sealed LA
CJ12-33
12
33
2
Olympic Batteries
Sealed LA
CJ12-40
12
40
2
Olympic Batteries
Sealed LA
CJ12-88
12
88
2
Olympic Batteries
Sealed LA
CJ12-100
12
100
2
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 11
TECHNICAL DESCRIPTION
GENERAL
The IFS-2600 in its most basic form comprises of three boards, the main control board, the main termination
board and the power supply board.
2
The main control board contains the Microprocessor, EPROM, RAM and E ROM. The main control board also
has the liquid crystal display and keypad attached. All of the "delicate" electronics have been placed on this
board. The main control board complete with the inner door is easily removed during installation to avoid
damage and allow greater access to the field terminals.
The main termination board contains the one power supply for 5V logic, and connectors for a Power Supply
and Battery Charger daughter board, the first eight zones, all common outputs and the printer interface. All
charger settings, fuses etc are located on this board. The Power Supply and Battery Charger board contains
two switch mode regulators, 26.5V for the panel power, 27.3V for the battery charger.
Up to seven (7) zone expansion boards can be added to the system to increase its detection capability. These
boards contain the same electronics as on the main termination board for zone scanning. Addressing is by a
jumper that selects which group of eight zones the board refers to.
Up to four (4) zone indicator boards can also be added. These boards will display the status of the zone
expansion boards fitted.
Up to eight (8) relay boards can be added. These boards contain 8 change-over relay contacts, each rated at
1 amp. These boards require no addressing, as they work on a serial data chain. Output 1 is the closest
output to the main board.
NOTE This product utilises state of the art components and materials and therefore boards must be returned
to our factory for proper troubleshooting, repair and retesting. Field component level repairs are not
recommended and would void all warranties on the product.
TRANSIENT SUPPRESSION
The IFS-2600's superior transient protection comprises of Dual Transorb input traps, inductive paths on
incoming PCB tracks, circuit board planes and metal oxide varistors on outputs. These devices are all selfresetting.
CURRENT CONSUMPTION
Zones Fitted
8
16
24
32
40
48
56
64
Quiescent Current
150 mA
250 mA
350 mA
450 mA
550 mA
650 mA
750 mA
850 mA
Quiescent + 2 AZF'S in alarm +1A of Bell +1 Amp ACF
2.23 AMPS
2.33 AMPS
2.43 AMPS
2.53 AMPS
2.63 AMPS
2.73 AMPS
2.83 AMPS
2.93 AMPS
Note:
1:
Each installation would require individual battery calculations to be performed for load capacity and
power supply capacity.
2:
Each IFS-717 relay board, can add 370 mA (in alarm and quiescent) current per board.
P/N 10069 ECN08-0066
Page 12
IFS-2600 Installation & Programming Manual
AZF DESCRIPTION
The AZF's on the IFS-2600 are monitored and scanned by custom thick film hybrids. These hybrid IC's
significantly reduce the possibility of false alarms and improve product efficiency and reliability.
The total Alarm Zone loop resistance is the sum of the end of line resistor (EOLR 4K7) plus all the parallel
connected detector loads.
AZF SUPERVISORY CURRENT
The supervisory current flows through the external terminal AZF+, through the field cable and to the end of line
resistor (EOLR), returning to the panel at AZF- terminal. Parallel connected, across the 2-wire pair field cable,
are a number of the previously listed detectors. During the quiescent state there is essentially an open circuit
across the + and - terminals of the detector base. The maximum number of detectors that can be installed on
each AZF is dependant on the type of detector and is listed in the IFS-2600 ActivFire® listing.
In an alarm state, a 560-ohm resistor is connected across the detector base causing additional loop current to
flow. This is sensed by the AZF to produce an alarm output. Removal of the E.O.L. resistor (in a non alarm
state) or the interruption of the supervisory current will produce a fault signal in the AZF.
As described above, the level of current is used to define the status of the alarm zone: I = 3.5 mA and below
I = 4.0 - 5.0mA at 24V
I = 16 mA to 40 mA (current limited)
FAULT
QUIESCENT
ALARM
The zone current is used by the hybrid IC to determine the condition of the zone as above. This information is
then transferred to the microprocessor for processing.
OVERLOAD PROTECTION
Panel Supply
Battery Charger
Battery Protection
External Supply
Door Holder
Aux Power Output
Bell
Warning System
ACF
AZF Circuits
Fuse F1
Fuse F2
Fuse F3
Fuse F4
Fuse F5
Fuse F6
Fuse F7
Fuse F8
Fuse F9
Current Limited
M205 5A
M205 3A
Polyfuse 3A
M205 7A
M205 3A
M205 1A Slow Blow
M205 1A
M205 1A
M205 1A
40mA
ZONE OVERLOAD SELF RESET
If a zone is overloaded by an accidental short to earth on an AZF circuit, the zone will automatically shut down
and produce a fault. Once this happens the panel will automatically recheck the zone every 60 seconds and
once the overload is removed, restore power and the fault will clear.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 13
PRINTER OUTPUT
The printer port is designed to be used during testing and commissioning of the panel. The serial printer will
report alarms and faults together with the date and time of the event. The printer can also be used during
“walk test” mode to produce a history of the test and can also be used to print current programming
configuration.
A DB9 plug male is provided at the top of the main termination board. This communication port will
communicate with an IBM compatible serial printer (ASCII printer) with the following settings.
Baud Rate
Data Bits
Stop Bits
Parity
Handshaking
1200 bps
8
1
None
DTR
CABLE CONNECTION
Cabling to the printer requires a 4-core telephone style cable with a maximum length of 10 metres. A DB9
socket is required at the panel end. The printer end is dependent on the type of printer used but is usually a
male DB25. Connection is as follows. A 5-core cable can be used for both comms and printer functions
IFS-2600 END
DB9 FEMALE
2
RX (only for programming)
3
TX
5
GND
7
RTS ( do not use)
8
CTS ( only for printer)
PRINTER END
DB25 MALE
DB9 MALE
2
3
3
2
7
5
(5)
(8)
4
7
PROGRAMMING BY COMPUTER
Programming of the zones, relays, global functions and time can by set with the DOS based program
“2600/SW” using the printer port. (Cannot be used with Windows XP)
After the cable is installed, the program can be run and the menu will prompt for the available functions.
2600
P/N 10069 ECN08-0066
Page 14
IFS-2600 Installation & Programming Manual
ALIGNMENT AND ADJUSTMENT
PCB2006 POWER SUPPLY BOARD
INTERNAL 24VDC (nom) POWER SUPPLY
With batteries disconnected and no alarms present, measure voltage across the 0V and MAIN test
points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer VR2 until
voltage is 26.5V 0.05V (26.45V – 26.55V).
Current limiting is fixed and field adjustment is not possible.
INTERNAL 27.3 VDC BATTERY CHARGER
With batteries disconnected and no alarms present, measure voltage across the 0V and CHARG test
points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer VR1 until
voltage is 27.3V 0.05V (27.25V – 27.35V).
Current limiting is factory preset and field adjustment is not required.
EXTERNAL 24VDC (nom) POWER SUPPLY (if fitted)
With batteries disconnected and no alarms present, measure voltage across Remote Input terminals
on PCB2005 and adjust the voltage on the external power supply until the voltage is 26.5V 0.5V
(26.0V – 27.0V). Note: This voltage is not critical for the operation of the IFS-2600 panel, but the
voltage must not go outside the limits as specified for the field ancillaries that it powers.
PCB2005 TERMINATION BOARD
INTERNAL 5VDC POWER SUPPLY TP8
All parameters are fixed and field adjustment is not possible.
POWER SUPPLY COMPARATOR REFERENCE VOLTAGE TP10
With the panel in the quiescent mode, measure voltage between system 0V and TP10. Adjust multiturn potentiometer VR3 until voltage is 7.0V 1% (6.93V – 7.07V)
NON ADJUSTABLE TEST POINTS
TP8 = 5.0 VDC 5%
TP5 = 12.0 VDC 5%
5VDC POWER SUPPLY
12VDC POWER SUPPLY
(If these test point voltages are not correct, please return the main termination board to the factory for
repair.)
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 15
ALARM THRESHOLD COMPARATOR TP7
With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER
SUPPLY as above.
Measure voltage between system 0V and TP7. Adjust multi-turn potentiometer VR4, and adjust until
the voltage is as per the following table.
Rail Voltage
20.6
21.0
21.5
22.0
22.5
23.0
23.5
24.0
24.5
25.0
25.5
26.0
26.5
27.0
27.5
27.6
28.0
3.3V Setting
2.833
2.888
2.956
3.025
3.094
3.163
3.231
3.300
3.369
3.438
3.506
3.575
3.644
3.713
3.781
3.795
3.850
Range
2.80 to 2.86
2.86 to 2.92
2.93 to 2.99
2.99 to 3.06
3.06 to 3.12
3.13 to 3.19
3.20 to 3.26
3.27 to 3.33
3.34 to 3.40
3.40 to 3.47
3.47 to 3.54
3.54 to 3.61
3.61 to 3.68
3.68 to 3.75
3.74 to 3.82
3.76 to 3.83
3.81 to 3.89
FAULT THRESHOLD COMPARATOR TP6
With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER
SUPPLY as above.
Measure the voltage between system 0V and TP6. Adjust multi-turn potentiometer VR1, and adjust
until the voltage is as per the following table.
Rail Voltage
20.6
21.0
21.5
22.0
22.5
23.0
23.5
24.0
24.5
25.0
25.5
26.0
26.5
27.0
27.5
27.6
28.0
P/N 10069 ECN08-0066
0.6V Setting
0.600
0.612
0.626
0.641
0.655
0.670
0.684
0.699
0.714
0.728
0.743
0.757
0.772
0.786
0.801
0.804
0.816
Range
0.59 to 0.61
0.61 to 0.62
0.62 to 0.63
0.63 to 0.65
0.65 to 0.66
0.66 to 0.68
0.68 to 0.69
0.69 to 0.71
0.71 to 0.72
0.72 to 0.74
0.74 to 0.75
0.75 to 0.76
0.76 to 0.78
0.78 to 0.79
0.79 to 0.81
0.80 to 0.81
0.81 to 0.82
Page 16
IFS-2600 Installation & Programming Manual
CONFIGURATION JUMPERS
IFS2004 - JP3 DEFAULT
Holding a short across these pins for 5 seconds during start-up causes the panel to reset to standard
factory defaults. The panel will give 4 beeps after reset, to acknowledge default on start-up.
IFS2004 - JP4 PROGRAM DISABLE
When fitted, jumper between these pins to inhibit program changes.
IFS2004 - JP5 CPU RESET
With panel operating, a momentary short across these pins will cause a CPU restart.
IFS2005 – JP2 DOOR HOLDER BYPASS
If zoned door holder outputs are required and is to be done external to the main termination board,
then the main door holder release needs to be disabled. Fitting a link across JP2 on IFS2005 PCB
does this.
Note: Door holder output is only enabled if optional door holder transformer is fitted. SW1 must be
linked on PCB2004 CPU board prior to Version 6 Firmware.
IFS2006 – JP1 EXTERNAL PS MONITORING
When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU
monitoring.
IFS804 - JP1-7 ZONE BOARD ADDRESSING
Jumper JP1 to JP7 on zone expansion board IFS-804 selects the addressing for the zones.
Place jumper in link position for the appropriate 8 zones to which the expansion board applies.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 17
PLACING INTO OPERATION
Suitably qualified technicians must install the panel. The following check procedures are recommended after
every installation and prior to initial power-up.
A thorough visual inspection should be made to every aspect of the fire panel. This includes loose wire, metal
filings, loose circuit boards, loose cabling, damage in transit etc.
All problems must be rectified immediately as they could cause incorrect operation or permanent damage to
the equipment.
EQUIPMENT AS FITTED
QTY
Description
Code
1
MAIN CONTROL BOARD
IFS -2004
1
MAIN TERMINATION BOARD
IFS -2005
1
MAIN POWER SUPPLY
IFS -2006
8 ZONE EXPANSION BOARD
IFS -804
16 ZONE INDICATOR BOARD
IFS -816
ADD ON, 8 WAY RELAY BOARD
IFS-717
EXTERNAL POWER SUPPLY BOOSTER
PS244, PS249, NPS-3,
NPS-5, NPS-11
3A DOOR HOLDER P/SUPPLY TRANSFORMER
2600/DHTX
INITIAL CHECKLIST
System general appearance good
Cabinet colour and condition good
Cabinet keyed 003
All circuit boards firmly fastened
Manual call point fitted & functional
Viewing window clear and firmly secured
Cable entries adequately sealed
240VAC mains cabling is correctly terminated
All earthing secured
Transformer securely mounted
Transformer correctly wired
All ribbon cables firmly secured
All operational zones adequately identified
All fuses correct value and fitted properly
All other modules securely fitted
Manufacturing label affixed
You are now ready to power up the IFS-2600 Fire Indicator Panel.
P/N 10069 ECN08-0066
Page 18
IFS-2600 Installation & Programming Manual
POWER UP CHECKLIST
Ensure batteries are disconnected.
Turn mains switch to "on"
The "mains on" led should light.
Allow 15 seconds for the panel to perform its start up tests.
Connect batteries
FUNCTIONAL TESTING
Primary ac supply voltage: 200 or 220 or 240vac +10% as required
Charger output voltage without batteries: 27.3v dc
Keypad functional
Perform auto test
Led’s all functional
LCD backlighting functional
Liquid crystal display functional
Zone fault detection
Zone alarm detection
Internal sounder operating
MCP loop wired to zone number ______ (if applicable)
Test auxiliary power output
Test bell output
Test warning system output
Test ACF output
Test door holder output (optional)
Test bell output supervision
Test warning system output supervision
Test ACF output supervision
Test brigade alarm relay #1
Test brigade alarm relay #2
Test standby relay (normally energised)
Test fault relay (normally energised)
Test mains fail relay
Test isolate relay
Test general alarm relays (2)
Test relay boards (if fitted)
Test open collector output boards (if fitted)
Press "battery test" once
If batteries are flat, allow 24hrs to charge and then re-test.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 19
FAULT RECORD
FAULT
CORRECTION
DATE
TESTS SATISFACTORILY COMPLETED.
TESTED BY _______________________________
SIGNATURE _______________________________
DATE OF TEST ____________________________
If all faults have been rectified and all tests are completed satisfactorily, the 2600 fire indicator panel is now
ready for operation.
P/N 10069 ECN08-0066
Page 20
IFS-2600 Installation & Programming Manual
INSTRUCTIONS TO OPERATORS
INDICATORS
Qty
Descriptor
Colour
Function
Illuminates when there is 200/220/240 VAC supply to
the panel.
Illuminates if the battery fails a battery test.
Illuminates if batteries are disconnected >30
seconds.
Illuminates if batteries are short circuit >30 seconds.
Illuminates if the power supply is outside the
manufacturers range.
Illuminates if the battery charger is outside the
recommended float charge voltage.
Illuminates if;
Any un-isolated zone goes into fault.
ACF output is open or short circuit
Bell output is open or short circuit
Warning System output is open or short circuit
Battery Fault
Charger Fault
Power Supply Fault
MAF Isolate Input is Open Circuit
Configuration Fault
Illuminates if the ACF output has been activated.
Illuminates if the ancillary circuit is open or short
circuit. The LED will extinguish when the load is
restored.
Illuminates if the ancillary output has been manually
isolated.
Illuminates when the bell output has been energised.
Illuminates if the bell circuit is open or short circuit.
The LED will extinguish when the load is restored.
Illuminates if the bell output has been manually
isolated.
Illuminates if the Warning System output has been
energised.
Illuminates if the Warning System circuit is open or
short circuit. The LED will extinguish if the load is
restored.
Illuminates if the Warning System has been manually
isolated.
This LED will flash if it's corresponding zone goes
into alarm. It will remain flashing until it is
Acknowledged at which time it will go steady and
remain on until the alarm is reset. If the zone is
programmed as a time delay type, a steady LED
indicates the “pre-alarm” condition. If the zone is
isolated and in alarm it will also be steady.
This LED illuminates if it's corresponding zone goes
into fault. It will remain on until the fault is removed.
This LED illuminates if its corresponding zone is
isolated. It will remain on until the zone is deisolated.
1
MAINS ON
Green
1
BATTERY
FAULT
Yellow
1
PSU FAULT
Yellow
1
CHARGER
LOW
COMMON
FAULT
Yellow
1
1
ACF ACT
ACF FLT
Red
Yellow
1
ACF ISO
Yellow
1
1
Bell ACT
Bell FLT
Red
Yellow
1
Bell ISO
Yellow
1
Warning
System ACT
Warning
System FLT
1
1
1
Yellow
Red
Yellow
Yellow
8
Warning
System ISO
ALARM LEDS
8
FAULT LEDS
Yellow
8
ISOLATE LEDS
Yellow
P/N 10069 ECN08-0066
Red
Buzzer
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
IFS-2600 Installation & Programming Manual
Page 21
SUGGESTED ALARM PROCEDURE
The following is a suggested alarm procedure for use by building fire officers or duty wardens. The fire
indicator panel is designed for use by qualified fire fighters and it is strongly recommended that the fire panel
not be operated in an emergency situation by anyone other than suitably qualified fire fighters.
Do not open fire indicator panel door or press any buttons until fire officers arrives.
Determine location of the fire by inspecting the label beside any lit red zone alarm LEDs on the panel.
Visually inspect area at a safe distance for actual fire or false alarm.
Notify fire-monitoring station of either result.
Perform evacuation and extinguishing operations as required.
IF a FIRE, direct fire fighters to the fire indicator panel and cause of alarm as they arrive.
IF a FALSE ALARM, advise maintenance technicians to determine and rectify cause.
Record all events in logbook.
NOTE A suitably qualified fire officer should perform the above procedure. These are suggested procedures
only, and if specific fire procedures are available or issued, they MUST prevail.
OPERATOR INSTRUCTIONS
The functions of the IFS-2600 are divided into three (3) categories
Fire Fighter Functions
Global Functions
Zone Functions
FIREFIGHTER FUNCTIONS
Fire Fighter Functions are those specifically used by the Fire Brigade on attendance. Following is an
explanation of their operation and the keystrokes required to perform the function required. These keys are
located at the top of the keypad marked FIREFIGHTER’S FACILITY and bordered in red.
ACKNOWLEDGE
ACK
The purpose of the internal buzzer is to alert persons of a new event on the panel, and a new potential fire
danger. Once the fire's location has been determined, the fire-fighter may wish to silence the internal buzzer
without having to totally reset the alarm.
When the buzzer is operating, pressing the "ACK" key once will silence it, however the External Alarm Bell will
continue to sound. If a subsequent alarm arises, the buzzer will be reactivated and a second ACK operation
will be required to silence it.
When an alarm is acknowledged, the Alarm LED will stop flashing and light continuously.
RESET
RESET
The reset function momentarily disconnects power, and resets all alarm parameters for the zone(s) that have
been acknowledged. This returns the zone back to its "normal" state. The reset key only operates on zones
with acknowledged alarms.
ISOLATE
ISOLATE
The isolate function prevents the transmission of alarms or faults from the zones to the master alarm facility.
The isolate key only operates on zones with acknowledged alarms.
P/N 10069 ECN08-0066
Page 22
IFS-2600 Installation & Programming Manual
EXT BELL
BELL ISOLATE
ISOL
Depressing the "EXT BELL ISOLATE" key will isolate the bells. The "Ext Bells Isolate" LED will illuminate and
the bells will not sound until the bells are de-isolated. Pressing "EXT BELL ISOLATE" a second time will deisolate the bell.
WARN SYS ISOLATE
WARN SYS
ISOL
Depressing the "WARN SYS ISOLATE" key will isolate the warning system. The "Warn Sys Isolate" LED will
illuminate and the warning system will not operate in the event of an alarm. Pressing "WARN SYS ISOLATE"
a second time will de-isolate the warning system.
GLOBAL FUNCTIONS
Global functions are those relating to the overall system and are not specific to particular zones. Following is
an explanation of their operation and the keystrokes required to perform the function.
BATTERY TEST
BATT
TEST
This function tests the performance of the batteries fitted to the system. Pressing this button will initiate a
battery test as specified in AS4428. The test will temporarily disconnect the batteries from the panel and apply
load on the batteries for 15 seconds.
The result of the test will be displayed on the LED's. If the "Battery Fault" LED is on, only a successful battery
test will turn the LED off. The pressing of any key during the test period will abort the battery test and return
the system back to normal mode.
Battery test function is disabled when the panel is in alarm condition.
AUTO TEST MODE
AUTO
TEST
This function will perform a fixed automatic test procedure to the panel. This mode cannot be selected if any
zone(s) is in alarm. Auto test will perform the following test functions;
Turn on ALL LEDs for 0.5 seconds
Test LCD backlighting
Test panel memory (E2ROM & RAM)
Test LCD
Isolate all alarm zones
Fault test all alarm zones
Alarm test all alarm zones
Test buzzer
The pressing of any key during "AUTO TEST" will abort the tests and return the system back to normal mode
once the current test is complete.
Note
During "AUTO TEST", all zones are treated as zone type #1 (standard latching type with 2 second
delay). Once AUTO TEST has finished, all zones will be reset and returned back to their previously
configured types.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
WALK TEST MODE
Page 23
WALK
TEST
This function will place the panel into "walk test" mode. Walk test mode is used for the on-site testing of
detector zones. This mode cannot be selected if any zone(s) is in alarm. Entry to walk test mode will be
acknowledged by three beeps and the LCD will display "WALK TEST MODE".
For the duration of walk test mode, all zones are changed to output configuration #2 (indicate and ring bells
only) and all zones are set to type #1 (standard latching, 2 second).
If the bells are not required to ring during walk test, simply press the "EXT BELL ISOLATE" key once. The EXT
BELL ISOLATE LED will illuminate to verify that the bells have been isolated.
Any alarm signal from detectors etc. will be received by the panel on its appropriate zone. The panel will beep
to acknowledge receipt of the alarm and indicate the alarm by illuminating the appropriate alarm LED for 4
seconds (the bells will also ring for a 3 second period unless previously isolated).
The zone and detector will then be automatically reset for 15 seconds
If the optional printer is connected, the alarm will be printed out as it is received. This can eliminate the need
for a second serviceman to record zone numbers during walk test and the printout can be retained for
verification at a later date.
Pressing any key will terminate the walk test mode and return the panel back to normal operation, restoring all
zone types and output configurations also ensuring that bell and ancillary outputs are de-isolated. The bells will
give three pulses of 1 second each to warn any testers still in the building that walk test mode has been
terminated.
Failure to receive any alarms or keystrokes within a 15 minutes period will result in the panel automatically
exiting walk test mode and returning back to normal as follows:
Bell outputs to be de-isolated.
Ancillary outputs to be de-isolated.
Bell will sound 3 times, each of 1-second duration.
Exit from walk test mode.
Zone types and output configurations restored
ACF ISOLATE
ACF
ISOL
Depressing the "ACF ISOLATE" key will isolate the ACF (Ancillary output) and the Door Holder Output. The
ACF isolated LED will illuminate and the output will not operate until de-isolated. Pressing "ACF ISOLATE" for
a second time will de-isolate the output.
If the ancillary output has already been tripped and is programmed as latching, isolating the ACF will not affect
the existing ancillary output. If the ACF is isolated prior to the alarm, it will prevent the ancillary output from
tripping. This does not apply to the Door Holder output.
ACF RESET
ACF
RESET
Resetting of the ancillary output (ACF) is only required if the ancillary output was programmed as latching.
The ancillary alarm will remain latched until manually reset. Pressing the "ACF RESET" button will extinguish
the 'ACF Activated' LED and de-energise the ancillary output. Pressing "ACF RESET" when the ACF is not
tripped will have no effect.
P/N 10069 ECN08-0066
Page 24
IFS-2600 Installation & Programming Manual
ZONE FUNCTIONS
Zone functions are those relating specifically to the detection zones. Following is an explanation of their
operation and the keystrokes required to perform the function required.
ALARM TEST
ALARM TEST
#
ENT
The alarm test function momentarily disconnects the detector lines of the zone(s) under test and simulates a
detector going into alarm, therefore testing the zone(s) alarm detection capability.
A resistive load equal to worst case alarm condition is placed on the zone for a period of 120 seconds and
then removed, if the zone being tested is not a latching type, the alarm will reset automatically once the load is
removed. Acknowledging and resetting the alarm will terminate an alarm test.
Once the zone has alarmed, all outputs are initiated (as programmed) similar to a real alarm.
The zone may be isolated prior to an alarm test if desired; this will prevent any outputs from operating.
‘#’ in the above key sequence is the zone number.
If only one zone is to be tested, use the appropriate number. Alternatively the "ALL" button can be used to
simultaneously test all zones.
To perform an alarm test:
1. Press the "ALARM TEST" button once; the buzzer will give 2 short beeps to indicate that alarm test mode
has been entered.
2. The LCD display will read "ALARM TEST MODE, ENTER ZONE No.".
3. Now enter the zone number ("#") 1-64 or “all”
4. Press "ENT"
If a correct entry is made, alarm testing on the zone commences immediately. However remember there is a 2
second transient delay on all zones. It will therefore take approximately 2 seconds before the zone registers an
alarm (this could be longer, depending on zone type).
A long beep will signify an incorrect entry and will revert back to normal operating mode. The "ALARM TEST"
button will need to be depressed again to re-enter alarm test mode.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
FAULT TEST
Page 25
FAULT TEST
#
ENTER
The fault test function momentarily disconnects the detection zone(s) under test and simulates the worst-case
condition for fault.
A resistor load equal to worst case fault is placed on the zone continuously for 5 seconds then the zone is
returned back to its normal condition.
If several zones are being tested consecutively and are being entered at a rate faster than the 5-second fault
timer, the fault timeout will occur 5 seconds after the last entry was completed.
Once the zone has registered a fault, all outputs relating to that zone are initiated similar to a real fault.
The zone may be isolated prior to a fault test if desired. This will prevent any outputs from operating.
‘#’ in the above key sequence is the zone number.
If only one zone is to be tested, use the appropriate zone number. Alternatively the "ALL" button can be used
to simultaneously test all zones.
To perform a fault test on a particular zone or on all zones:
1.
Press the "FAULT TEST" button once.
The buzzer will give 2 short beeps to indicate that fault test mode has been entered.
2.
The LCD display will read "FAULT TEST MODE, ENTER ZONE No.".
3.
Enter the zone number ("#") 1-64 or “all”.
4.
Press "ENTER".
A long beep will signify an incorrect entry and the panel will revert back to normal operating mode. The
"FAULT TEST" button will need to be pressed again to re-enter fault test mode.
If a correct entry is made, fault testing on the zone commences and the fault LED will illuminate.
P/N 10069 ECN08-0066
Page 26
IFS-2600 Installation & Programming Manual
ISOLATE
ISOLATE
#
ENTER
The isolate function prevents the transmission of alarms or faults from the zones, to the master alarm facility.
‘#’ in the above key sequence is the zone number.
If only one zone is to be isolated, use the appropriate zone number. Alternatively the "ALL" button can be used
to simultaneously isolate all zones.
To isolate a particular zone or all zones:
1.
Press the "ISOLATE" button.
The buzzer will give 2 short beeps to indicate that isolate mode has been entered.
2.
The LCD display will read "ALARM ISOL. MODE, ENTER ZONE No.".
3.
Enter the zone number ("#")1-64 or “all”.
4.
Press "ENTER".
A long beep will signify an incorrect entry and will revert back to normal operating mode. The "ISOLATE"
button will need to be depressed again to re-enter isolate mode.
If a correct entry is made, the zone is immediately isolated. If the zone is already in alarm, all of its alarm
outputs are isolated and indicators remain visible.
If the "ALL" function is performed, all zones will be isolated, regardless of their previous state. Performing the
"ALL" function for a second time will de-isolate all zones.
RESET
RESET
#
ENTER
The reset function momentarily disconnects power, and resets all alarm parameters for the zone(s) being
reset. This returns the zone back to its "normal" state.
‘#’ in the above key sequence is the zone number.
If only one zone is to be reset, type in the zone number. Alternatively the "ALL" button can be used to
simultaneously reset all zones.
To perform a reset on a particular zone or on all zones:
1.
Press the "RESET" button.
The buzzer will give 2 short beeps to indicate that reset mode has been entered.
2.
The LCD display will read "ALARM RESET MODE, ENTER ZONE NO".
3.
Enter the zone number ("#") 1-64 or “all”.
4.
Press "ENTER".
A long beep will signify an incorrect entry and will revert back to normal operating mode. The "RESET" button
will need to be depressed again to re-enter reset mode.
If a correct entry is made, resetting of the zone begins immediately. Any alarm indication will be removed
immediately; also resetting the zone(s) programmed outputs.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 27
PROGRAMMING
GLOBAL OPTIONS
ANCILLARY TRIP
1
2
3
4
LATCHING
NON-LATCHING
LATCHING
NON-LATCHING
NORMALLY DE-ENERGISED
NORMALLY DE-ENERGISED
NORMALLY ENERGISED
NORMALLY ENERGISED
ALARM VERIFICATION
1
2
3
4
5
DISABLED
2 MINUTES
3 MINUTES
4 MINUTES
5 MINUTES
TIME
(DD) / (MM) / (YY)
(HH) : (MM)
ZONE OPTIONS
1
2
3
4
5
6
7
8
9
10
DESCRIPTION
INPUT DELAY
Standard Latching
Standard Latching
Non Latching
Non Latching
Time Delay
Time Delay
Time Delay
Time Delay
Time Delay
Time Delay
2 seconds
2 seconds with AVF
2 seconds
20 seconds
10 seconds
20 seconds
30 seconds
40 seconds
50 seconds
60 seconds
Type
Output Description
1
2
3
4
5
6
7
Indicate Only
Indicate, Bell
Indicate, Bell, General Alarm
Indicate, Bell, General Alarm, Ancillary
Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1
Indicate, Bell, General Alarm, Ancillary Brigade Relay #2
Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1, & Brigade Relay #2
P/N 10069 ECN08-0066
Page 28
IFS-2600 Installation & Programming Manual
OUTPUT RELAY OPTIONS
Optional Relays can be programmed to simulate: -
Isolate Relay
ACF Output
Brigade Relay #1
Brigade Relay #2
Fault Relay
Mains Fail Relay
General Alarm Relay
Bell Output
Door Holder Relay
Door Switch
Reset
Or Can Be Used To:
"MAP AND"
"MAP OR"
“MAP FAULT”
“MAP ISOLATE”
“MAP ISO/FAULT”
Up to 5 Zones in Alarm
Up to 5 Zones in Alarm
Up to 5 Zones in Fault
Up to 5 Zones in Isolate
Up to 5 Zones in Isolate/Fault
DEFAULT SETTINGS
ACF OUTPUT
ALARM VERIFICATION (AVF)
TIME
ZONE TYPES
ZONE OUTPUT CONFIG
RELAY MAPPING
NON-LATCHING, NORMALLY DE-ENERGISED
3 MINUTES
1/1/11 11:11
STANDARD LATCH 2S
I-B-G-A-BR1 & BR2
MAP -OR-, MAPPING = 1 TO 1
IE: RELAY 1 = ZONE 1, RELAY 2 = ZONE 2.............
The 2600 PANEL is self-configuring on power-up therefore it is not necessary to program the number
of relay boards.
Zone expansion boards fitted must have the correct jumper selected.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 29
PROGRAM MODE
Press the following buttons in order shown to enter programming mode.
PREVIOUS
→
NEXT
→
→
SELECT
EXIT
→
ENTER
PROGRAMMING MODE
The liquid crystal display will display all messages and prompts required to program the 2600.
ONLY the "PREVIOUS","NEXT","SELECT","EXIT" AND "ENTER" keys are used in programming mode. All
other keys will give an error beep and are ignored.
Alarm detection is not affected during the programming function but you must exit programming mode if any
other panel functions are to be performed including acknowledge and reset of alarms.
Note:
Refer to appendices for detailed explanation of functions
PROGRAMMING HIERARCHY
EXIT
SAVE CHANGES
YES
NO
ZONES
GLOBAL
RELAY
PRINT
ZONES
TYPE
STD LATCHING
STANDARD LATCHING AVF
NON LATCH
NON LATCH 20S
TIME DELAY 10S
TIME DELAY 20S
TIME DELAY 30S
TIME DELAY 40S
TIME DELAY 50S
TIME DELAY 60S
P/N 10069 ECN08-0066
OUTPUT
INDICATE
I BELL
IB GENERAL
IBG ACF OUT
IBGA BRIGADE 1
IBGA BRIGADE 2
IBGA BRIGADE 1 & 2
Page 30
IFS-2600 Installation & Programming Manual
RELAYS
TYPE
ISOLATE RELAY
ANCILLARY OUTPUT (ACF)
BRIGADE RELAY #1
BRIGADE RELAY #2
FAULT RELAY
MAINS FAIL RELAY
GENERAL ALARM RELAY
BELL OUTPUT
DOOR HOLDER RELAY
MAP - AND
MAP - OR
MAP - FAULT
MAP – ISOLATE
MAP – ISOLATE / FAULT
DOOR SWITCH
RESET
MAPPING
(00)(00)(00)(00)(00)
(00)(00)(00)(00)(00)
(00)(00)(00)(00)(00)
(00)(00)(00)(00)(00)
(00)(00)(00)(00)(00)
GLOBAL
ACF
NON-LATCHING ND
LATCHING ND
NON-LATCHING NE
LATCHING NE
AVF
DISABLED
2 MINUTES
3 MINUTES
4 MINUTES
5 MINUTES
RELAY
MAP RELAY (XX) >>>
FROM ZONE XX
TIME
(DD) / (MM) / (YY)
(HH) : (MM)
ND: = NORMALLY DE-ENERGISED
NE: = NORMALLY ENERGISED
PRINT
PRINT
PRINTS OUT CURRENT CONFIGURATION
MAIN MENU
(ZONES)
GLOBAL
RELAYS
PRINT
Use the "NEXT" & "PREVIOUS" keys to scroll through "ZONES" "RELAYS" "GLOBAL" "PRINT" and wrap
around. Once the desired option has been highlighted, pressing the "SELECT" button will select it.
Pressing "EXIT" at this stage will exit programming mode.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 31
EXIT PROGRAMMING MODE
SAVE
YES
CHANGES
(NO)
Use the "NEXT" & "PREVIOUS" keys to scroll through "YES" & "NO". Once the desired option has been
highlighted, pressing the "SELECT" button will select it.
2
Highlighting "YES" and pressing "SELECT" will write all changes made to the system memory (E ROM) and
the panel will then restart.
WARNING!! The above action cause the panel to drop any door holders / air-conditioning if connected.
Highlighting "NO" and pressing "SELECT" will ignore any changes made to the programming and exit back to
normal panel operation without restarting.
Note: This does not apply to saving changes to the time. Changes to time are saved immediately the
select key is pressed when in the time adjustment menu.
ZONE PROGRAMMING
SELECT ZONE #
SELECT ZONE #
(ALL)
Use the "NEXT" & "PREVIOUS" keys to scroll through "ALL" "1" "2" "3"
Up to the maximum number of zones fitted and then wrap around. Once the desired zone number has been
highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return to main menu.
ZONE SELECTED
ZONE # ALL
(TYPE) OUTPUT
Use the "NEXT" & "PREVIOUS" keys to scroll through "TYPE" & "OUTPUT". Once the desired option has
been highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return
"SELECT ZONE #".
ZONE TYPE
ZONE # ALL TYPE
STD LATCHING
Use the "NEXT" & "PREVIOUS" keys to scroll through
STD LATCHING
STD LATCHING AVF
NON LATCH
NON LATCH 20S
TIME DELAY 10S
TIME DELAY 20S
TIME DELAY 30S
TIME DELAY 40S
TIME DELAY 50S
TIME DELAY 60S
P/N 10069 ECN08-0066
Page 32
IFS-2600 Installation & Programming Manual
Once the desired option has been highlighted, pressing the "SELECT" button will select it. Making a selection
or pressing "EXIT" will return to zone selected.
Note: The option previously set is displayed in brackets and is the first to be displayed. Previously
set options will not be displayed if "ALL" is selected.
A function of “BELL” also operates the WARNING SYSTEM.
ZONE OUTPUT CONFIGURATION
ZONE #ALL OUTPUT
IBGA BRIG 1&2
Use the "NEXT" & "PREVIOUS" keys to scroll through:
INDICATE
I BELL
IB GENERAL
IBG ACF OUT
IBGA BRIGADE 1
IBGA BRIGADE 2
IBGA BRIG 1&2
Once the desired option has been highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at
this stage will return to "Zone Selected".
Note: The option previously set is displayed in brackets and is the first to be displayed. Previously
set options will not be displayed if "ALL" is selected.
A function of “BELL” also operates the WARNING SYSTEM.
RELAY PROGRAMMING MODE
SELECT RELAY #
SELECT
RELAY#
(ALL)
Use the "NEXT" & "PREVIOUS" keys to scroll through "ALL" "1" "2" "3". Up to 64 and then wrap around.
Once the desired relay number has been selected, pressing the "SELECT" button will select it. Pressing
"EXIT" at this stage will return to main menu.
RELAY SELECTED
RELAY #ALL
(TYPE) MAPPING
Use the "NEXT" & "PREVIOUS" keys to scroll through "TYPE" & "MAPPING". Once the desired option has
been highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return to
"Select Relay #".
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 33
RELAY TYPE
RELAY #ALL TYPE
(GENERAL)
Use the "NEXT" & "PREVIOUS" keys to scroll through:
ISOLATE
ANCILLARY
BRIGADE 1
BRIGADE 2
FAULT
MAINS FAIL
GENERAL
BELL
DOOR HOLDER
MAP -ANDMAP -ORMAP –FAULTMAP –ISOLATEMAP -ISOLATE/FLTDOOR SWITCH
RESET
Once the desired option has been highlighted, pressing the "SELECT" button will select it. Making a selection
or pressing "EXIT" will return to "Relay Selected".
Note:
The option previously set is displayed in brackets and is the first to be displayed. Previously
set options will not be displayed if "ALL" is selected.
RELAY MAPPING
(00)
RELAY #1 MAP
00 00 00
00
** Relay mapping can only be selected if the relay is set as a MAP type.
These 5 entry fields represent the zone numbers that the relay is to be mapped to and will be activated from.
Use the "NEXT" and "PREVIOUS" keys to increment/decrement the zone number within the brackets.
Use the "ENTER" key to move to the next field. Fields may be changed as required and set by pressing
"SELECT".
Any fields left as (00) will be ignored.
Pressing "EXIT" at this stage will return to "RELAY # ".
Note: The option previously set is displayed in brackets and is the first to be displayed. Previously
set options will not be displayed if "ALL" is selected.
GLOBAL PROGRAMMING
(ACF)
RELAY
Use the "NEXT","PREVIOUS" & "SELECT" keys to select.
Pressing "EXIT" will return to "Main Menu".
P/N 10069 ECN08-0066
AVF
TIME
Page 34
IFS-2600 Installation & Programming Manual
ACF OUTPUT
ACF OUTPUT
(NON-LATCH ND)
Use the "NEXT" & "PREVIOUS" keys to scroll through:
LATCHING ND
NON-LATCH NE
LATCHING NE
Note:
The option previously set is displayed in brackets and is the first to be displayed.
ND = Normally De-energised i.e.: Output is not energised until an alarm occurs.
NE = Normally energised i.e.: Output is energised and then is de-energised once an alarm occurs.
AVF
AVF TIMEOUT
(3 MINUTES)
Use the "NEXT" & "PREVIOUS" keys to scroll through:
DISABLED
2 MINUTES
3 MINUTES
4 MINUTES
5 MINUTES
Note:
The option previously set is displayed in brackets and
is the first to be displayed.
RELAY (GLOBAL RELAY UNITY MAP)
MAP RELAY (XX) >>
FROM ZONE (XX)
Use the "NEXT" & "PREVIOUS" keys to change the first relay to start from, together with the matching zone.
Use the “ENTER” key to toggle between the two and press “SELECT” once finalised. “Exit” will abort unity
map.
This function will start programming relays starting from the relay number specified in a 1 to 1 configuration
with zones starting from the first zone number specified.
Example 1: if the above table was to look like this:
MAP RELAY (10) >>
FROM ZONE (01)
Then relay #10 would be set as MAP OR with its mapping as (01) 00 00 00 00, relay #11 would be set as MAP
OR with it’s mapping set as (02) 00 00 00 00 and so on all the way up to relay #64. Relays number 1-through
9 remains unaffected by this function.
Example 2: if the above table was to look like this:
MAP RELAY (01) >>
FROM ZONE (09)
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 35
Then relay #1 would be set as MAP OR with its mapping as (09) 00 00 00 00, relay #2 would be set as MAP
OR with it’s mapping set as (10) 00 00 00 00 and so on all the way up to relay #64.
Note:
In example 2, zone number 64 is reached and there are still more relays to go. (I.e. we are only at
relay #56) the programming stops at this point and any relays not yet programmed will be left in their
previous programmed mode and are unaffected by this function.
PRINT PROGRAMMING DATA
Prints the programming data currently stored in RAM, including all changes made (they may have not yet been
written to the E2ROM).
Output is printed directly onto the serial printer if fitted.
TIME (DATE & TIME)
The current DATE & TIME will be displayed as DD/MM/YY (in 24h format)
Use the PREVIOUS” & NEXT” keys to increment or decrement the number highlighted by brackets.
The ENTER key will move to the next field.
When finished, the SELECT key must be pushed to store the date/time.
Note:
The Date/Time data is saved when the Select key is pushed.
DO NOT select “Save Changes “Y” as this will restart (and drop any door holders / airconditioning if connected).
P/N 10069 ECN08-0066
Page 36
IFS-2600 Installation & Programming Manual
APPENDIX A
DESCRIPTION OF ALARM ZONE TYPES
Different zone types can be selected using the programming mode. Each zone can be selected as any one of
the following:
Type
1
2
3
4
5
6
7
8
9
10
Description
Standard Latching
Standard Latching
Non Latching
Non Latching
Time Delay
Time Delay
Time Delay
Time Delay
Time Delay
Time Delay
Input Delay
2 seconds
2 seconds with AVF
2 seconds
20 seconds
10 seconds
20 seconds
30 seconds
40 seconds
50 seconds
60 seconds
LATCHING TYPE
Once an alarm condition is received from the detector, the alarm zone will start a timer, if after 2 seconds the
detector is still activated the alarm zone will register an alarm condition. Indicators will illuminate and alarm
functions are initiated immediately, unless zone is set as AVF - refer Appendix C. The alarm zone will remain
in alarm until manually reset.
A reset is performed by interrupting the power to the detector for 0.5 seconds and returning the alarm zone
back to its quiescent state. If an alarm is still present in the detector area, the detector will re-activate and the
2-second timer will be re-initiated.
NON LATCHING TYPE
A temporary actuation device (e.g. Flow Switch) is usually connected to this type of alarm zone. Once a
signal has been received CONTINUOUSLY for 2 seconds or 20 seconds (dependant on programming) an
alarm will be registered causing the alarm LED to flash and alarm functions will be performed as programmed.
The alarm group will remain in alarm until the actuating device no longer reports a signal. When actuating
device signal is clear, the alarm is cleared, causing the zone to power down for 0.5 seconds and return back to
normal state.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 37
TIME DELAY AZF
The time delay AZF zone can be preset to any one of 6 time delays in the initial setup. This type of zone is
used for AS1668 smoke detection zones. Zone timing etc is as per AS1668-1991.
Example:
Timer #1 = 60 seconds
Once the first alarm is received, the alarm LED is turned on steady; this indicates "PARTIAL ALARM"
condition.
The detector is then reset (by removing its power for 0.5 seconds) and a timer is also started for 60 seconds
(TIMER#1). Another timer of 10 seconds (TIMER#2) is also started. The zone must respond again within this
10 seconds (TIMER#2) to register another alarm.
Failure to receive another alarm within this 10-second period will return the zone back to its normal state
immediately and extinguish the alarm LED.
If an alarm is received, the detector is reset again and TIMER#2 is also reset.
This monitoring continues until the 60-second timer (TIMER#1) has elapsed and then the NEXT alarm signal
will trip the zone into "FULL ALARM". This is the stage at which all mapped relays, bells etc. will operate.
When "FULL ALARM" condition is reached, a third timer (TIMER#3) of 70 seconds is started. This timer is
used to prevent "hunting" of air conditioning fans as specified in AS1668
TIMER#2 is kept operating and alarm signals are still to be received as per previous. Alarm signals are
required continually to keep the zone in "FULL ALARM". Each time another alarm is received Timer#3 is
restarted (i.e. 70 seconds)
Failure to comply with TIMER#2 will result in the zone being returned back to its NORMAL state once
TIMER#3 has elapsed.
P/N 10069 ECN08-0066
Page 38
IFS-2600 Installation & Programming Manual
APPENDIX B
ZONE OUTPUT CONFIGURATIONS
Once a zone has alarmed, its output functions as programmed to one of the following output types.
Type
1
2
3
4
5
6
7
Output Description
Indicate Only
Indicate, Bell
Indicate, Bell, General Alarm
Indicate, Bell, General Alarm, Ancillary
Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1
Indicate, Bell, General Alarm, Ancillary, Brigade Relay #2
Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1, & Brigade Relay #2
NOTE: A function of “BELL” also operated the WARNING SYSTEM.
Refer to technical specification for descriptions of output types.
The zone can also be programmed to operate one (1) or more relay contacts through the use of the relay
mapping output feature.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 39
APPENDIX C
ALARM VERIFICATION FACILITY (AVF)
Alarm verification (AVF) is a facility used to minimise false alarms.
AVF only applies to the zones programmed for the AVF function.
GLOBAL PROGRAMMABLE OPTIONS
AVF TIMEOUT
Disabled
2 Minutes
3 Minutes
4 Minutes
5 Minutes
Operation is as follows:
If a zone is programmed as AVF and it registers an alarm, no alarm functions are performed, if it is the first
AVF zone in alarm.
This zone and all other zones programmed as AVF zones are reset by shutting down power to their detectors
for 12 seconds, the power is then restored and the zones are re- enabled.
The alarm verification zones are now in "alert" mode. Any AVF zone going into alarm within the pre-selected
timeout period (2,3,4,5 minutes) will then cause an immediate alarm condition with all the programmed output
functions being initiated.
If no alarm is received within this period, the AVF zones are removed from the "alert" mode and returned to
normal. A further alarm will re-initiate the reset sequence etc.
Other zones are unaffected by the actions of AVF zones. They will all function as normal, regardless of AVF
zone status.
If the timeout period is disabled, the alarm will transmit instantly thus making the AVF non-functional.
P/N 10069 ECN08-0066
Page 40
IFS-2600 Installation & Programming Manual
APPENDIX D
ANCILLARY TRIP (ACF)
The ancillary trip is used for the shutting down of air conditioning systems etc. in the event of a fire.
GLOBAL PROGRAMMABLE OPTIONS
ANCILLARY TRIP (ACF)
NON-LATCHING ND
LATCHING
ND
NON-LATCHING
NE
LATCHING
NE
The ancillary trip can be programmed as latching or non- latching depending on the application.
It call also be programmed as normally energised or normally de-energised.
If a zone is programmed to operate the ancillary trip, an alarm condition will energise the ancillary trip until the
alarm is removed (if non-latching), or until the alarm is removed and the ACF is manually reset via the keypad
(latching).
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 41
APPENDIX E
RELAY OUTPUT MAPPING
A total of 64 expansion relays can be fitted to the IFS-2600. Each relay can be individually programmed to
mimic any of the following;
STANDARD OUTPUTS WHICH MAY BE MIMICED
ANCILLARY OUTPUT (ACF)
BRIGADE ALARM RELAY #1
BRIGADE ALARM RELAY #2
* FAULT RELAY (NORMALLY ENERGISED)
* MAINS FAIL RELAY (NV) (NORMALLY ENERGISED)
ISOLATE RELAY
GENERAL ALARM RELAYS
BELL OUTPUT
DOOR SWITCH
RESET
DOOR HOLDER RELAY
FAULT/ISOLATE
When mapping to a normally energised relay, take care to ensure that connections take into account the
normally energised state of the relay.
Alternatively, the expansion relay(s) can be mapped to provide customised
logic to suit specific installations:
AND MAPPING
AND MAPPING allows the relay output to be programmed for a combination of up to 5 zones, and only
after they all go into alarm, will the relay operate.
AND MAPPING is useful for applications which have special shutdowns, multiple risk Gas Facilities
etc.
OR MAPPING
OR MAPPING works similarly. This function will cause the relay to operate if any one of up to five (5)
zones go into alarm, the relay will operate.
If the relay map options are set as "01" "02" "03" "00" "00", zones 1 or 2 or 3 in alarm will cause the
relay to operate.
OR MAPPING is useful for applications which have special shutdowns, zoned mimic outputs etc.
FAULT MAPPING
FAULT MAPPING works the same as OR mapping of alarm except it relates to the fault flag on each
zone instead of the alarm flag. This function will cause the relay to operate if any one of up to five (5)
zones go into fault.
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3 going into fault, will
cause the relay to operate.
P/N 10069 ECN08-0066
Page 42
IFS-2600 Installation & Programming Manual
FAULT/ISOLATE MAPPING
FAULT/ISOLATE MAPPING works the same as OR mapping of alarm except it relates to the
fault/isolate flag on each zone instead of the alarm flag. This function will cause the relay to operate if
any one of up to five (5) zones go into fault/put in isolate.
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3 going into fault/(or
are manually put in isolate) will cause the relay to operate.
ISOLATE MAPPING
ISOLATE MAPPING works the same as or mapping of alarm except it relates to the isolate flag on
each zone instead of the alarm flag. This function will cause the relay to operate if any one of up to
five zones is put in isolate.
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3, if put in isolate will
cause the relay to operate.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 43
APPENDIX F
GLOSSARY OF TERMS
AS-4428.1
Australian standard for; Automatic Fire Detection and Alarm Systems Control and Indicating Equipment.
AS-4428.1
Australian standard for; Automatic Fire Detection and Alarm Systems Power Supply Units.
AS-1670
Australian standard for; Automatic Fire Detection and Alarm Systems System Design Installation and Commissioning.
AS-1668.1
Australian standard for; SAA Mechanical Ventilation and Air Conditioning Fire Precautions in Buildings with Airhandling Systems.
AZF
MAF
ACF
AVF
ISOL
FLT
ZONE
DET
LED
LCD
A/C
AC
DC
V
A
FIP
N/L
TD
STD
SBY
BR1
BR2
NV
IS
GEN
D/H
RLY
Alarm Zone Facility (zone)
Master Alarm Facility
Ancillary Control Facility
Alarm Verification Facility
Isolate
Fault
Alarm Zone Facility
Detector
Light Emitting Diode
Liquid Crystal Display
Air Conditioning
Alternating Current
Direct Current
Voltage
Amps
Fire Indicator Panel
Non Latching
Time Delay
Standard
Standby
Brigade Relay 1
Brigade Relay 2
AC Fail Relay
Isolate
General Alarm Contacts
Door Holder
Relay
P/N 10069 ECN08-0066
Page 44
IFS-2600 Installation & Programming Manual
APPENDIX G
SUMMARY OF TERMINATIONS AND CAUTIONS
MCP LOOP
Used for the looping of the manual call point to a particular zone chosen for indication. This is achieved by
wiring from the zone, to the MCP, to the MCP loop then out to the field with the EOL across the last detector.
The MCP is the first device on the circuit and both fault and alarm conditions will be indicated.
DETECTION ZONES
Refer to list of compatible actuation devices for detectors which may be used. Any other hard contact device
may be used on these detection zones. An end of line resistor (E.O.L) of 4K7 ohms is required.
RELAY OUTPUTS
Relay outputs are voltage free change over contacts rated at 24VDC 1Amp (resistive). DO NOT attempt to
switch 240VAC with these relay contacts.
Note:
Relay Contacts Shown At Terminals (NC, C, NO) Are For The Relay In a De-energised State.
BELL OUTPUTS
This output is fused at 1 Amp and can drive up to 10 NIFS bells as specified. Output is also monitored and if
no bells are connected an EOL resistor (4K7 ohms) is required across the output terminals.
ACF OUTPUTS
This output is fused at 1 Amp. Output is also monitored and if no ancillary devices are connected, an EOL
resistor (4K7 ohms) is required across the output terminals.
WARNING SYSTEM
Connection for warning systems such as Occupant Warning System or electronic sounders.
DOOR HOLDER OUTPUTS
When a door holder transformer is fitted to the panel, this output becomes functional. Output is rated at 3
Amps maximum and can power up to 30 NIFS style door holders continuously. (Nom. 80mA each). Output is
separately fused at 3A (FS-1). Jumper JP3 if fitted will disable this output, i.e. 24V DC output all the time. The
Door Holder Output can be isolated using the ACF Isolate function.
AUXILIARY POWER & MIMIC POWER
A total auxiliary power draw of 500mA is available from the auxiliary power and mimic power terminals. This
output is fused at 1 Amp (FS-3) and is battery backed.
MAF ISOL & TRANSPONDER 0V
A 0V signal is switched back from the transponder test switch and is used for indication purposes at the FIP.
This will indicate as MAF ISOLATED and initiate a common fault. It can also used for an external device to
indicate a fault.
MIMIC DATA & CLOCK
These outputs together with the mimic power terminals are used to serially communicate with the mimic
panels when fitted. EOL resistor is not required on these lines.
NOTE: Firmware must be Version 6 or above for mimic operation
AC INPUT
Mains step down transformer output (30VAC) is connected at these terminals. DO NOT connect 240VAC to
these terminals.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual
Page 45
BATTERY
The 24V batteries are connected at these terminals.
damage to the equipment.
Reverse polarity will cause serious and permanent
DOOR HOLDER AC INPUT
Terminate the door holder AC transformer at these terminals. 24 VAC is the only acceptable power source at
this point. DO NOT connect 240VAC at this point.
OUTPUT RELAYS
STANDBY (N) Normally energised, drops out when power supply (or battery supply) is below specified
voltage.
BRIGADE1
Brigade 1, defaults as energising on any alarm zone, programmable.
BRIGADE2
Brigade 2, defaults as energising on any alarm zone, programmable.
FAULT (N)
Normally energised, drops out on any fault unless that function is isolated.
AC-FAIL (N)
Normally energised, drops out if the mains power is lost.
ISOLATE
Energised if any zone is isolated.
GENERAL1
Energised if any zone goes into alarm
GENERAL2
Energised if any zone goes into alarm
P/N 10069 ECN08-0066
Page 46
IFS-2600 Installation & Programming Manual
APPENDIX H
IFS-2600 PROGRAMMED OPTIONS
Global System Parameters
Latch ND
Date:
Non-Latch ND
/
/
Latch NE
Non-Latch NE
ACF Output
Disabled
2 min
3 min
4 min
Alarm Verification
(AVF)
Notes:
Programmed by
Place an "X" in the appropriate box
P/N 10069 ECN08-0066
= Default
5 min
IFS-2600 Installation & Programming Manual
Page 47
ZONE TYPE PROGRAMMING
1
2
3
AZF No. STD STD N/L
2S AVF 2S
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
4
N/L
20S
Date:
5
T/D
10S
Place an "X" in the appropriate box
P/N 10069 ECN08-0066
6
T/D
20S
/
/
7
T/D
30S
8
T/D
40S
= Default
9
T/D
50S
10
T/D
60S
Page 48
1
2
3
AZF No. STD STD N/L
2S AVF 2S
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
IFS-2600 Installation & Programming Manual
4
N/L
20S
5
T/D
10S
Place an "X" in the appropriate box
P/N 10069 ECN08-0066
6
T/D
20S
7
T/D
30S
8
T/D
40S
= Default
9
T/D
50S
10
T/D
60S
IFS-2600 Installation & Programming Manual
ZONE OUTPUT PROGRAMMING
AZF No.
INDICATE
IBELL
IBGENERAL
Page 49
Date:
IBGACF
/
IBGABR1
/
IBGA- BR2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Place an "X" in the appropriate box
P/N 10069 ECN08-0066
= Default
IBGABR1&BR2
Page 50
AZF No.
IFS-2600 Installation & Programming Manual
INDICATE
IBELL
IBGENERAL
IBGACF
IBGABR1
IBGABR2
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
Place an "X" in the appropriate box
P/N 10069 ECN08-0066
= Default
IBGABR1&BR2
IFS-2600 Installation & Programming Manual
Page 51
RELAY OUTPUT MAPPING
Date:
/
/
MAPPING
RLY
ISO
ACF
BR1
BR2
FLT
MAINS
FAIL
GEN
BELL
D/H
AND
OR
FLT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Place an "X" in the appropriate box
P/N 10069 ECN08-0066
= Default
ISO
ISO/
FLT
DOOR
RESET
Page 52
IFS-2600 Installation & Programming Manual
MAPPING
RLY
ISO
ACF
BR1
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
P/N 10069 ECN08-0066
BR2
FLT
MAINS
FAIL
GEN
BELL
D/H
AND
OR
FLT
ISO
ISO/
FLT
DOOR
RESET
IFS-2600 Installation & Programming Manual
Page 53
APPENDIX I
TECHNICAL DRAWINGS
MAIN KEYPAD AND DISPLAY
EXPANSION DISPLAY
P/N 10069 ECN08-0066
Page 54
IFS-2600 Installation & Programming Manual
Block Connection Diagram
1
2
3
4
4 CORE CABLE
TX, CTS, GND
DB-9 FEMALE
SERIAL PRINTER
A
A
OUTPUTS
PCB1125
MAIN TERMINATION BOARD
MAIN PROCESSOR BOARD
IFS PCB2005
CABLE C32
IFS PCB2004
ZONE DISPLAYS 1-8
BELL/ACF
POWER
SUPPLY
BOARD
PCB2006
ZONE
INPUTS
1-8
MAX 120M
CABLE C3
CABLE C5
LAPTOP
3 CORE CABLE
RX, TX, GND
OUT
CABLE C1
P/N 130
16 ZONE
DISP
PCB816
ZONE
INPUTS
9-16
B
ZONE
IN
OUT
RELAY
EXP
PCB804
BOARD
IFS803
4 CORE CABLE
8 RELAY
B
OUTPUTS
1-8
MIMIC PANEL
CABLE C8
ZONE
INPUTS
32-40
MAINS SUPPLY
240 V AC
8 ZONE
DISP
PCB816
ZONE
IFS 811B IND BRD
IN
OUT
RELAY
BOARD
240V
ISOL
S/W
IFS803
LAST DISPLAY CAN BE 8/16
OTHERS MUST BE 16 ZONE
C
IFS 810 MIMIC DRV
CABLE C3
EXP
PCB804
IFS 812 DISPLAY BRD
(1 FOR EACH 8 ZONES)
8 RELAY
OUTPUTS
9-16
CABLE C3
240V/30V AC
100 VA
TRANSFORMER
PANEL
2600/DHTX
100 VA
TRANSFORMER
D/HOLDER
C
POWER
POWER
IN
OUT
RELAY
8 RELAY
BOARD
OUTPUTS
IFS803
32-40
OPTION
+
-
CABLE C9
-
+
MAX 8 PCB803
12V BATTERY
D
12V BATTERY
Copyright
D
C
B
No.
Removed Part Numbers
Revised Printer Connection
REVISED PART NUMBERS
IP
IP
IP
IP
G.W. G.W.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
This document is & shall
remain the property of
Notifier Inertia Fire Systems
21/12/05Unauthorised use of this
18/8/05 document in any way is
9/3/04 prohibited.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/
Engineer
Baulkham Hills NSW 2153
I.P.
Traced 14/08/03 Design
AUSTRALIA
Tel 61 2 9894 1444
Approved
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
D
IFS2600
BLOCK CONNECTION DIAGRAM
Drg.
A4 No.
3
Rev
L2600-1
4
D
IFS-2600 Installation & Programming Manual
Page 55
System Sensor Conventional Detector Connection Diagram
1
2
3
DET A
A
DET B
DET B
+
3
4
5
+R
+D
-D
1
TO PANEL
A
4
RIP
4
5
4
RIP
5
1
+R
+D
-D
1
3
3
4K7
EOL
2
-
2
BASE B401
2
BASE B401
CONVENTIONAL DETECTOR CONNECTION DIAGRAM
B
BASE A
PROBE A
+
PROBE B
4
5
4
5
SEALED
PROBE
1
TO PANEL
B
BASE B
3
SEALED
PROBE
1
3
4K7
EOL
2
-
2
BASE B401R
BASE B401R
SEALED DETECTOR CONNECTION DIAGRAM
( NORMAL HEAD NOT CONNECTED )
C
C
+R
Current limited 10 mA
470R
+R
+D
Not current limited (3-24 V)
+D
-D
Common Return
-D
REMOTE INDICATOR
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/
Baulkham Hills NSW 2153
I PERRY Engineer I PERRY
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved I PERRY
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
SYSTEM SENSOR
CONVENTIONAL DETECTOR
CONNECTION DIAGRAM
A4
3
Drg. SS-DET
No.
4
Rev
A
D
Page 56
IFS-2600 Installation & Programming Manual
Hochiki Conventional Detector Connection Diagram
1
2
DET A
A
DET B
3
+
1
+R
+D
-D
5
7
3
3
2
4
6
4
DET C
RIP
2
TO PANEL
3
1
4
1
5
7
RIP
2
4
6
+R
+D
-D
5
7
6
A
4K7
EOL
CONNECTION FOR STANDARD DETECTORS AND BASES
B
B
DET A
DET B
DET C
+
RIP
BLUE
L
TO PANEL
RED
S
RIP
+R
+D
-D
C
WHITE
-
L
S
C
L
S
+R
+D
-D
C
4K7
EOL
CONNECTION FOR DFG-60BLKJ SEALED DETECTOR
C
C
+R
Current limited 10 mA
470R
+R
+D
Not current limited (3-24 V)
+D
-D
Common Return
-D
REMOTE INDICATOR
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/ I PERRY Engineer I PERRY
Baulkham Hills NSW 2153
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved I PERRY
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
HOCHIKI
CONVENTIONAL DETECTOR
CONNECTION DIAGRAM
Drg. HOC-DET
A4 No.
3
4
Rev
A
D
IFS-2600 Installation & Programming Manual
Page 57
Ancillary Connection Diagram
1
2
3
4
1
2
3
4
NOTE:
PCB1125 may be omitted if the
ancillary device is high
impedance or contains an inbuilt
reverse protection diode.
A
+
+
IN -
LOAD
+
D2
D1
R1
-
OUT
-
In this case a 4K7 EOL must be
fitted to the last device on the
circuit.
N/C
+
IN -
LOAD
N/O
+
+24
OUT
D2
D1
R1
+24
-
-
0V
1
2
3
4
+
WARN
COM
BELL
GEN2
1ST SOUNDER
A
PCB1125C
REMOVE RESISTOR R1
EXCEPT ON LAST PCB
IFS2600
TERMINATION
PCB2004
2220
SOUNDER
2220
SOUNDER
LAST SOUNDER
PCB1125C
1.5 OHM 5W
R1 TO BE FITTED ON
LAST PCB ONLY
0V
AUX
+24
+
IN -
LOAD
+24
+
D2
D1
R1
FITTED WHEN
STROBE USED
0V
-
PCB1125C
MIMIC
HOLD
REMOVE RESISTOR R1
EXCEPT ON LAST PCB
CLK
DATA
+
+
IN -
LOAD
+
+
D2
D1
R1
-
OUT
-
INPUT
HOLD
24VDC
BELL
-
OUT
MAF ISO
DOOR DOOR
+
0V
TP 0V
C
B
+
ACF
B
STROBE
C
PCB1125C
R1 TO BE FITTED ON
LAST PCB ONLY
2600/DHTX
DOOR HOLDER TRANSFORMER
+
A
240 V AC
DOOR HOLDERS
+
D2
D1
R1
-
240V/24V
TRANSFORMER
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
-
+
RELAY
FAN
PCB1125C
E
No.
LOAD
OUT
N
+
IN -
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/
Engineer
Baulkham Hills NSW 2153
23/8/05
I PERRY
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved I PERRY
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
D
IFS2600 TYPICAL
ANCILLARY CONNECTION
A4
3
Drg. 26-ANC-CON
No.
4
Rev
A
Page 58
IFS-2600 Installation & Programming Manual
ASE Connection Diagram
1
2
3
4
A
N
IFS2600
B
N
FAULT BRIGADE 2 BRIGADE 1 STANDBY
A
N/O
N/C
COM
AUX
ISOLATE
N
AC-FAIL
PCB2004
C
N/O
N/C
COM
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
AC FAIL
N
N/O
N/C
COM
FAULT
N
B
ASE
BRACKET
N/C
COM
ISOLATE
CODE RED #10115
N/O
ROMTEK 10117
N/C
COM
TYCO #10116
POWER
N/O
+24
0V
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
ASE
BR1
N/O
TERMINATION
D
N/C
COM
C
O
Drawing File No.
=DocumentFullPathAndName
2
C
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/ 22/8/05
Engineer I.P.
Baulkham Hills NSW 2153
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
D
2600
ASE CONNECTION
A4
3
Drg.
No.
26-ASE
4
Rev
A
IFS-2600 Installation & Programming Manual
Page 59
Auto Changeover Dual Sounder Connection Diagram
1
2
3
4
A
A
NOTE:
NOTE:
Maximum capacity is 10 sounders
or 4 strobes
INSTALL LINK JP1 FOR AUTO
CHANGEOVER FROM ALERT TO EVAC
TERM B
TERM A
+24
0V
AL
EVAC
FAULT N/O
NC
COM
NO
NC
COM
NO
0V
IFS958 RELAY BOARD
+24V
IFS2600
TERMINATION
PCB2004
B
FAULT COM
MONITORED DRIVER BOARD
IFS 993
B
ALERT STROBE
(AMBER)
EVAC STROBE
(RED)
WARN
+24
ACF
+24
BELL
N/O
AUX
C
0V
+24V
RED
0V
BLACK
+24V
RED
0V
BLACK
0V
WARN SYS EOL
4K7
+24
1K8
EOL
0V
+24
C
4 3 2 1
0V
4 3 2 1
DUAL TONE AS2220
SOUNDER
D
Copyright
B
No.
ADDED RELAY
G.W. G.W.23/1/04
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
C
O
Drawing File No.
=DocumentFullPathAndName
2
DUAL TONE AS2220
SOUNDER
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/ 23/8/05 Engineer I PERRY
Baulkham Hills NSW 2153
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved I PERRY
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
A4
3
D
IFS2600 MONITORED
DUAL SOUNDER
AUTO CHANGEOVER
Drg.
No.
2600-DUAL
AUTO-SNDR
4
Rev
A
Page 60
IFS-2600 Installation & Programming Manual
Auto Change Over Dual Sounder Connection Diagram
1
2
3
4
A
A
NOTE:
NOTE:
Maximum capacity is 10 sounders
or 4 strobes
REMOVE LINK JP1 FOR MANUAL
CHANGEOVER FROM ALERT TO EVAC
IFS2600
TERMINATION
PCB2004
TERM B
TERM A
+24
0V
AL
EVAC
NC
COM
NO
NC
COM
0V
NO
+24V
WARN
BELL
AUX
ACF
+24
0V
IFS958 RELAY BOARD
ALERT ACTIVATION
+24
FAULT N/O
N/O
B
FAULT COM
MONITORED DRIVER BOARD
IFS 993
B
ALERT STROBE
(AMBER)
EVAC STROBE
(RED)
0V
+24
0V
+24V
RED
0V
BLACK
+24V
RED
0V
BLACK
+24
WARN SYS EOL
4K7
0V
1K8
EOL
C
C
4 3 2 1
4 3 2 1
NC
IFS803
RELAY
BOARD
COM
NO
EVAC ACTIVATION
DUAL TONE AS2220
SOUNDER
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
DUAL TONE AS2220
SOUNDER
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/
Baulkham Hills NSW 2153
23/8/05 Engineer I PERRY
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved I PERRY
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
A4
3
D
IFS2600 MONITORED
DUAL SOUNDER
MANUAL CHANGEOVER
Drg.
No.
2600-DUAL
MANUAL-SNDR
4
Rev
A
IFS-2600 Installation & Programming Manual
Page 61
MIMIC Connection Diagram
1
2
3
PCB812
4
PCB812
PCB812
A
A
ZONES 1-8
IFS2600
TERMINATION
BOARD
ZONES 9-16
ZONES 17-24
PCB810
FITTED WITH
IFS2600 MIMIC
DRIVER
WARN
+24
+24
0V
B
33-40
1-8
41-48
9-16
49-56
17-24
57-64
25-32
0V
0V
DATA
+24
CLK
0V
+24
+24
0V
AUX
ACF
B
BELL
N/O
TP 0V
Max 120 Meters
4/0.75mm cable
MAF ISO
CLK
POWER AND SIGNAL RETURN
MIMIC
C
C
SERIAL BUS
MIM/EXT/26
+
MIM/EXT/26
DOOR
HOLD
INPUT
DOOR
HOLD
DATA
FOR EXTRA ZONES
STANDARD SIZES 8, 24 AND 64 ZONES
MIM/26/KIT
FOR 8 ZONES
PCB811
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/
Engineer
Baulkham Hills NSW 2153
G.W.
Traced 2/2/04 Design
AUSTRALIA
Tel 61 2 9894 1444
Approved
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
A4
3
D
MIM/26/KIT
Drg.
No.
26-MIM-CON
4
Rev
A
Page 62
IFS-2600 Installation & Programming Manual
Single Fan Connection Diagram
1
2
3
4
FIRE PANEL
FIELD WIRING
A
A
FAN TERMINATION BOARD
AUX POWER
AUX +24
+24
AUX 0V
0V
+24
COMMON +VE
START
STOP
START
CONTROL
FAN START RELAY
START1
STOP
STOP1
RUN
FAN RUNNING
STOP
INDICATION
FAN STOPPED AND POWER AVAILABLE
B
B
FLT
FAN FAULT OR NO POWER AVAILABLE
FAN STOP RELAY
RIBBON CABLE
PCB1128
C
FAN 1
C
RUN
STOP
FAULT
* NOTE
AUTO
OFF
ON
THE MECHANICAL SERVICES BOARD
MUST BE CONFIGURED TO HAVE
THE STOP RELAY TO TAKE
PRECEDENCE OVER THE START RELAY
FRONT PANEL CONTROL
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/
Baulkham Hills NSW 2153
19/8/05 Engineer I PERRY
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
D
SINGLE FAN (GENERAL)
CONTROL
Drg.
A4 No.
3
Rev
2600-DUAL FAN
4
A
IFS-2600 Installation & Programming Manual
Page 63
Dual Fan Connection Diagram
1
2
3
4
FIRE PANEL
FIELD WIRING
A
A
FAN TERMINATION BOARD
AUX POWER
AUX +24
+24
AUX 0V
0V
+24
COMMON +VE
START
STOP
START
CONTROL
FAN 1 START RELAY
START1
STOP
STOP1
RUN
START2
STOP
FAN 1
FAN RUNNING
INDICATION
FAN STOPPED AND POWER AVAILABLE
B
B
STOP2
FLT
FAN FAULT OR NO POWER AVAILABLE
FAN 1 STOP RELAY
+24
COMMON +VE
START
START
STOP
CONTROL
FAN 2 START RELAY
STOP
FAN 2
PCB1102
RUN
FAN RUNNING
STOP
INDICATION
FAN STOPPED AND POWER AVAILABLE
FAN 2 STOP RELAY
RIBBON CABLE
FLT
C
FAN FAULT OR NO POWER AVAILABLE
FAN 1
FAN 2
C
RUN
RUN
STOP
STOP
FAULT
FAULT
AUTO
OFF
* NOTE
AUTO
ON
OFF
ON
THE MECHANICAL SERVICES BOARD
MUST BE CONFIGURED TO HAVE
THE STOP RELAY TO TAKE
PRECEDENCE OVER THE START RELAY
*NOTE
FOR SINGLE CONTROL
REMOVE SW2
LINK SW1 A & B TO SW2 A, B
FRONT PANEL CONTROL
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/
Engineer
Baulkham Hills NSW 2153
19/8/05
I PERRY
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
A4
3
D
DUAL FAN (GENERAL)
CONTROL
Drg.
No. 2600-DUAL FAN
4
Rev
A
Page 64
IFS-2600 Installation & Programming Manual
Exhaust Fan Connection Diagram
1
2
3
4
FIRE PANEL
FIELD WIRING
FAN TERMINATION BOARD
A
A
AUX POWER
AUX +24
+24
AUX 0V
0V
+24
COMMON +VE
START
STOP
START
CONTROL
START1
FAN STOP RELAY
(MAPPED TO ACF FOR
GENERAL OR ZONED)
STOP1
STOP
RUN
FAN RUNNING
STOP
INDICATION
FAN STOPPED AND POWER AVAILABLE
FLT
FAN FAULT OR NO POWER AVAILABLE
B
B
PCB1128
* NOTE
RIBBON CABLE
EITHER THE MAPPING ABOVE MAY
BE USED TO STOP THE EXHAUST FAN
OR THE GENERAL ACF TRIP BELOW,
BUT NOT BOTH.
USE OF THE FIRE TRIP RELAY BELOW
REQUIRES THAT THE MSSB
STOPS THE FAN.
* NOTE
FAN 1
THE MECHANICAL SERVICES BOARD
MUST BE CONFIGURED TO HAVE
THE STOP RELAY TO TAKE
PRECEDENCE OVER THE START RELAY
RUN
STOP
FAULT
C
C
AUTO
OFF
FRONT PANEL CONTROL
FROM FIP
ACF
ON
+
+24
0v
PCB1125
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
+
IN -
LOAD
+
D1
R1
OUT
-
-
FIRE TRIP
RELAY
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/ 19/8/05 Engineer I PERRY
Baulkham Hills NSW 2153
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
D
EXHAUST FAN (TYPICAL)
CONTROL
Drg.
A4 No.
3
2600-EXH
4
Rev
A
IFS-2600 Installation & Programming Manual
Page 65
Supply Fan Connection Diagram
1
2
3
4
FIRE PANEL
FIELD WIRING
FAN TERMINATION BOARD
A
A
AUX POWER
AUX +24
+24
AUX 0V
0V
+24
COMMON +VE
START
STOP
START
CONTROL
START1
FAN START RELAY
(MAPPED TO ACF FOR
GENERAL OR ZONED)
STOP1
STOP
RUN
FAN RUNNING
STOP
INDICATION
FAN STOPPED AND POWER AVAILABLE
FLT
FAN FAULT OR NO POWER AVAILABLE
FAN STOP RELAY
(MAPPED TO AIR INTAKE
SMOKE DETECTOR)
B
B
PCB1128
* NOTE
RIBBON CABLE
EITHER THE MAPPING ABOVE MAY
BE USED TO START THE SAF
OR THE GENERAL ACF TRIP BELOW,
BUT NOT BOTH.
USE OF THE FIRE TRIP RELAY BELOW
REQUIRES THAT THE MSSB
STARTS THE FAN.
* NOTE
FAN 1
THE MECHANICAL SERVICES BOARD
MUST BE CONFIGURED TO HAVE
THE STOP RELAY TO TAKE
PRECEDENCE OVER THE START RELAY
RUN
STOP
FAULT
C
C
AUTO
OFF
FRONT PANEL CONTROL
FROM FIP
ACF
ON
+
+24
0v
PCB1125
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
+
IN -
LOAD
+
D1
R1
OUT
-
-
FIRE TRIP
RELAY
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/
Baulkham Hills NSW 2153
19/8/05 Engineer I PERRY
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
D
SUPPLY AIR FAN (TYPICAL)
CONTROL
A4
3
Drg.
No.
2600-SAF
4
Rev
A
Page 66
IFS-2600 Installation & Programming Manual
Smoke Spill Fan Connection Diagram
1
2
3
4
FIRE PANEL
FIELD WIRING
FAN TERMINATION BOARD
A
A
AUX POWER
AUX +24
+24
AUX 0V
0V
+24
COMMON +VE
START
STOP
START
CONTROL
START1
FAN START RELAY
(MAPPED TO ACF FOR
GENERAL OR ZONED)
STOP1
STOP
RUN
FAN RUNNING
STOP
INDICATION
FAN STOPPED AND POWER AVAILABLE
FLT
B
FAN FAULT OR NO POWER AVAILABLE
B
* NOTE
EITHER THE MAPPING ABOVE MAY
BE USED TO START THE SSF
OR THE GENERAL ACF TRIP BELOW,
BUT NOT BOTH.
RIBBON CABLE
PCB1128
USE OF THE FIRE TRIP RELAY BELOW
REQUIRES THAT THE MSSB
STARTS THE FAN.
* NOTE
FAN 1
THE MECHANICAL SERVICES BOARD
MUST BE CONFIGURED TO HAVE
THE STOP RELAY TO TAKE
PRECEDENCE OVER THE START RELAY
RUN
STOP
FAULT
C
C
AUTO
OFF
FRONT PANEL CONTROL
FROM FIP
ACF
ON
+
+24
0v
PCB1125
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
+
IN -
LOAD
+
D1
R1
OUT
-
-
FIRE TRIP
RELAY
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/ 19/8/05 Engineer I PERRY
Baulkham Hills NSW 2153
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
D
SMOKE SPILL FAN (TYPICAL)
CONTROL
A4
3
Drg.
No.
2600-SSF
4
Rev
A
IFS-2600 Installation & Programming Manual
Page 67
10W EVAC Connection Diagram
2
3
4
VOL
1
A
COM
LINE +
+24
GND
SOUND
JP1 JP2
BGM +
BGM -
PA -
0V
PA+
PTT
ALERT IN
BGM EN
EVAC IN
ALARM
EVAC OUT
FAULT
+24
0V
ALERT OUT
+24
+24V COM
WARN
IFS2600
TERMINATION
BOARD
AUX
A
10W EVAC
PCB 908
PA
FRONT
PANEL
EVAC
CONTROL
0V
EXTERNAL
POWER
MONITOR
JP1
B
4K7 5%
EOL
SPEAKERS WITH
47K 5%
100V LINE TRANSFORMERS
AND ISOLATION CAPACITORS
LINK JP1
WHITE
RED
0V
+24V
BATT
REMOTE
INPUT
0V
+24V
REMOTE
OUTPUT
0V
+24V
AC INPUT
B
BLACK/SHIELD
BLUE
MICROPHONE
WITH PTT
SHIELDED
NOTE:
C
C
TO SLAVE TWO AMPLIFIERS
TOGETHER, REMOVE THE IFS903
BOARD FROM THE SLAVE
AMPLIFIER AND CONNECT JP1
ON THE MASTER TO JP2 ON THE
SLAVE.
BGM ENABLE
( ENABLED ON
CLOSURE )
THE MICROPHONE AND BGM
MUST ONLY BE CONNECTED TO
THE MASTER AMPLIFIER.
SHIELDED
CONNECT PIN 4, P12 ON MASTER
TO PIN4 P12 ON SLAVE.
BGM INPUT
1V P-P
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/ I PERRY Engineer I PERRY
Baulkham Hills NSW 2153
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved I PERRY
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
D
IFS-2600
10 WATT
CONNECTION DIAGRAM
A4
3
Drg.
No.
Rev
2600-10W
4
A
Page 68
IFS-2600 Installation & Programming Manual
10W EVAC Slave Connection Diagram
2
3
4
VOL
1
A
COM
LINE +
+24
GND
SOUND
JP1 JP2
BGM +
BGM -
PA -
0V
PA+
PTT
ALERT IN
BGM EN
EVAC IN
ALARM
EVAC OUT
FAULT
+24
0V
ALERT OUT
+24
+24V COM
WARN
IFS2600
TERMINATION
BOARD
AUX
A
10W EVAC
PCB 908
PA
FRONT
PANEL
EVAC
CONTROL
0V
EXTERNAL
POWER
MONITOR
JP1
B
4K7 5%
EOL
SPEAKERS WITH
47K 5%
100V LINE TRANSFORMERS
AND ISOLATION CAPACITORS
LINK JP1
CONNECT TO
FAULT OUT
FROM SLAVE
0V
+24V
BATT
REMOTE
INPUT
0V
+24V
REMOTE
OUTPUT
0V
+24V
AC INPUT
B
WHITE
RED
BLACK/SHIELD
BLUE
MICROPHONE
WITH PTT
SHIELDED
NOTE:
TO SLAVE TWO AMPLIFIERS
TOGETHER, REMOVE THE IFS903
BOARD FROM THE SLAVE
AMPLIFIER AND CONNECT JP1
ON THE MASTER TO JP2 ON THE
SLAVE.
THE MICROPHONE AND BGM
MUST ONLY BE CONNECTED TO
THE MASTER AMPLIFIER.
C
BGM ENABLE
( ENABLED ON
CLOSURE )
CONNECT FAULT OUTPUTS
TOGETHER AND MOVE THE
LAST WRE ON I/O PCB TO THE
FAULT TERMINAL ON THE
MASTER AMPLIFIER.
SHIELDED
BGM INPUT
1V P-P
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
CONNECT PIN 4, P12 ON MASTER
TO PIN4 P12 ON SLAVE.
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/ I PERRY Engineer I PERRY
Baulkham Hills NSW 2153
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved I PERRY
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
D
IFS-2600
10 WATT SLAVE
CONNECTION DIAGRAM
A4
3
C
Drg.
No.
Rev
2600-10W SLAVE
4
A
IFS-2600 Installation & Programming Manual
Page 69
30W EVAC Connection Diagram
2
3
4
VOL
1
A
COM
LINE +
+24
GND
SOUND
JP1 JP2
BGM +
BGM -
PA -
0V
PA+
PTT
ALERT IN
BGM EN
EVAC IN
ALARM
EVAC OUT
0V
FAULT
+24
+24V COM
WARN
+24
AUX
IFS2600
TERMINATION
BOARD
ALERT OUT
A
30W EVAC
PCB 908
PA
FRONT
PANEL
EVAC
CONTROL
0V
EXTERNAL
POWER
MONITOR
JP1
B
4K7 5%
EOL
SPEAKERS WITH
47K 5%
100V LINE TRANSFORMERS
AND ISOLATION CAPACITORS
LINK JP1
WHITE
RED
0V
+24V
BATT
REMOTE
INPUT
0V
+24V
REMOTE
OUTPUT
0V
+24V
AC INPUT
B
BLACK/SHIELD
BLUE
MICROPHONE
WITH PTT
SHIELDED
NOTE:
C
AC1
A
+24V
IFS1100
0V
POWER SUPPLY
BGM ENABLE
( ENABLED ON
CLOSURE )
AC2
N
240V/20V
TRANSFORMER
THE MICROPHONE AND BGM
MUST ONLY BE CONNECTED TO
THE MASTER AMPLIFIER.
SHIELDED
E
CONNECT PIN 4, P12 ON MASTER
TO PIN4 P12 ON SLAVE.
BGM INPUT
1V P-P
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
TO SLAVE TWO AMPLIFIERS
TOGETHER, REMOVE THE IFS903
BOARD FROM THE SLAVE
AMPLIFIER AND CONNECT JP1
ON THE MASTER TO JP2 ON THE
SLAVE.
C
O
Drawing File No.
=DocumentFullPathAndName
2
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/ 25/8/05
Engineer I PERRY
Baulkham Hills NSW 2153
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved I PERRY
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
D
IFS-2600
30 WATT
CONNECTION DIAGRAM
A4
3
Drg.
No.
Rev
2600-30W
4
A
Page 70
IFS-2600 Installation & Programming Manual
30W EVAC Slave Connection Diagram
2
3
4
VOL
1
COM
LINE +
GND
SOUND
JP1 JP2
BGM +
BGM -
PA -
0V
PA+
PTT
ALERT IN
BGM EN
EVAC IN
ALARM
EVAC OUT
FAULT
0V
ALERT OUT
+24
+24V COM
WARN
+24
AUX
IFS2600
TERMINATION
BOARD
A
+24
A
30W EVAC
PCB 908
PA
FRONT
PANEL
EVAC
CONTROL
0V
EXTERNAL
POWER
MONITOR
JP1
B
4K7 5%
EOL
SPEAKERS WITH
47K 5%
100V LINE TRANSFORMERS
AND ISOLATION CAPACITORS
LINK JP1
CONNECT TO
FAULT OUT
FROM SLAVE
0V
+24V
BATT
REMOTE
INPUT
0V
+24V
REMOTE
OUTPUT
0V
+24V
AC INPUT
B
WHITE
RED
NOTE:
BLACK/SHIELD
BLUE
MICROPHONE
WITH PTT
TO SLAVE TWO AMPLIFIERS
TOGETHER, REMOVE THE IFS903
BOARD FROM THE SLAVE
AMPLIFIER AND CONNECT JP1
ON THE MASTER TO JP2 ON THE
SLAVE.
THE MICROPHONE AND BGM
MUST ONLY BE CONNECTED TO
THE MASTER AMPLIFIER.
SHIELDED
C
AC1
A
CONNECT FAULT OUTPUTS
TOGETHER AND MOVE THE
LAST WRE ON I/O PCB TO THE
FAULT TERMINAL ON THE
MASTER AMPLIFIER.
+24V
IFS1100
0V
POWER SUPPLY
BGM ENABLE
( ENABLED ON
CLOSURE )
AC2
N
C
240V/20V
TRANSFORMER
SHIELDED
CONNECT PIN 4, P12 ON MASTER
TO PIN4 P12 ON SLAVE.
E
BGM INPUT
1V P-P
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/
Engineer
25/8/05
I PERRY
Baulkham Hills NSW 2153
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved I PERRY
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
D
IFS-2600
30 WATT SLAVE
CONNECTION DIAGRAM
A4
3
Drg.
No.
Rev
2600-30W-SLAVE
4
A
IFS-2600 Installation & Programming Manual
Page 71
50W EVAC Connection Diagram
1
2
AUDIO TRANSFORMER
A
3
0
60
2
30
4
20
6
10
8
0
4
A
PA GAIN
BAT OV
JP1 JP2
+24 BAT
BGM -
BGM +
PA -
PA+
GND
PTT
ALERT
EVAC
BGM EN
ALARM
EVAC OUT
ALERT OUT
FAULT
+24 COM
EXTERNAL
POWER
MONITOR
JP1
0V
+24V
BATT
REMOTE
INPUT
0V
+24V
REMOTE
OUTPUT
0V
+24V
AC INPUT
LINK JP1
TO SLAVE TWO AMPLIFIERS
TOGETHER, REMOVE THE IFS903
BOARD FROM THE SLAVE
AMPLIFIER AND CONNECT JP1
ON THE MASTER TO JP2 ON THE
SLAVE.
THE MICROPHONE AND BGM
MUST ONLY BE CONNECTED TO
THE MASTER AMPLIFIER.
SOUND MAIN
AUX
+24
0V
B
NOTE:
24V AC
LINE -
24V AC
LINE +
SEC
LINE -
0V
OUT
LINE +
+24
WARN
IFS2600
TERMINATION
BOARD
FAN
50W EVAC
PCB 905E
GND
SPEAKERS WITH
100V LINE TRANSFORMERS
AND ISOLATION CAPACITORS
JP3 JP4
AMP
PRI
EOL
47K 5%
B
CONNECT JP3 MASTER TO JP4
SLAVE FOR FAN CONTROL
CONNECT PIN 4, P12 ON MASTER
TO PIN4 P12 ON SLAVE.
FRONT
PANEL
EVAC
CONTROL
4K7 5%
C
BAT CHG
0V
BLACK/SHIELD
BLUE
MAINS_ON
PCB 974
MF_N/C
N
MF_N/O
MICROPHONE
WITH PTT
SHIELDED
240V/30V
A
MF_COM
LOW_N/C
N
LOW_N/O
N
LOW_COM
TRANSFORMER
E
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
C
WHITE
RED
+24V
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
BGM ENABLE
( ENABLED ON
CLOSURE )
SHIELDED
BGM INPUT
1V P-P
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/ 25/8/05
Engineer I PERRY
Baulkham Hills NSW 2153
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved I PERRY
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
D
IFS-2600
50 WATT
CONNECTION DIAGRAM
Drg.
Rev
A4 No.
3
2600-50W
4
A
Page 72
IFS-2600 Installation & Programming Manual
50W EVAC Slave Connection Diagram
1
2
AUDIO TRANSFORMER
A
3
0
60
2
30
4
20
6
10
8
0
4
A
PA GAIN
SOUND MAIN
AUX
+24
BAT OV
JP1 JP2
+24 BAT
BGM -
BGM +
PA -
PA+
GND
PTT
ALERT
EVAC
BGM EN
ALARM
EVAC OUT
ALERT OUT
+24 COM
EXTERNAL
POWER
MONITOR
JP1
0V
+24V
BATT
REMOTE
INPUT
0V
+24V
REMOTE
OUTPUT
0V
+24V
AC INPUT
LINK JP1
FAULT
0V
B
TO SLAVE TWO AMPLIFIERS
TOGETHER, REMOVE THE IFS903
BOARD FROM THE SLAVE
AMPLIFIER AND CONNECT JP1
ON THE MASTER TO JP2 ON THE
SLAVE.
THE MICROPHONE AND BGM
SHOULD ONLY BE CONNECTED
TO THE MASTER AMPLIFIER.
B
CONNECT JP3 MASTER TO JP4
SLAVE FOR FAN CONTROL
24V AC
LINE -
NOTE:
24V AC
LINE +
SEC
LINE -
0V
OUT
WARN
IFS2600
TERMINATION
BOARD
LINE +
FAN
50W EVAC
PCB 905E
GND
+24
SPEAKERS WITH
100V LINE TRANSFORMERS
AND ISOLATION CAPACITORS
JP3 JP4
AMP
PRI
EOL
47K 5%
CONNECT FAULT OUTPUTS
TOGETHER AND MOVE THE
LAST WRE ON I/O PCB TO THE
FAULT TERMINAL ON THE
MASTER AMPLIFIER.
FRONT
PANEL
EVAC
CONTROL
CONNECT PIN 4, P12 ON MASTER
TO PIN4 P12 ON SLAVE.
4K7 5%
C
0V
CONNECT TO
FAULT OUT
FROM SLAVE
MAINS_ON
PCB 974
MF_N/C
N
BLACK/SHIELD
BLUE
MICROPHONE
WITH PTT
SHIELDED
240V/30V
MF_N/O
A
MF_COM
LOW_N/C
N
LOW_N/O
N
LOW_COM
TRANSFORMER
E
D
Copyright
This document is & shall
remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.
No.
C
WHITE
RED
+24V
BAT CHG
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
App.
Date
C
O
Drawing File No.
=DocumentFullPathAndName
2
BGM ENABLE
( ENABLED ON
CLOSURE )
SHIELDED
BGM INPUT
1V P-P
Title
7 Columbia Court,
Sheet: 1 Of: 1
Norwest Business Park
Drawn/ 25/8/05
Engineer I PERRY
Baulkham Hills NSW 2153
Traced
Design
AUSTRALIA
Tel 61 2 9894 1444
Approved I PERRY
Size
Fax 61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au unless signed as approved
D
IFS-2600
50 WATT SLAVE
CONNECTION DIAGRAM
Drg.
Rev
A4 No.
3
2600-50W-SLAVE
4
A
Notes
Notes
New South Wales
(Head Office)
7 Columbia Court
Baulkham Hills NSW 2153
Queensland
24 Potts Street
East Brisbane, QLD 4169
Victoria
32 Lambert Street
Richmond, VIC 3121
ph +61 (02 9899-4155
fax +61 (0)2 9899-4156
ph +61 (0)7 3391 5777
fax +61 (0)7 3391 5800
ph +61 (0)3 9421 5552
fax +61 (0)3 9421 5553
Western Australia
Unit 4, 283 Camboon Road
Malaga WA 6090
New Zealand
264 Mt Eden Road
Auckland
ph +61 (0)8 9270 6555
fax +61 (0)8 9270 6556
ph +64 (0)9 623 5275
fax +64 (0)9 623 5060
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No Creator : Microsoft Word - IFS-2600 Install Manual V3_01.doc Producer : ScanSoft PDF Create! 4 Create Date : 2008:05:08 16:28:18+10:00 Modify Date : 2008:05:08 16:28:18+10:00 Author : E208382 Title : Microsoft Word - IFS-2600 Install Manual V3_01.doc Page Count : 80 Page Mode : UseNoneEXIF Metadata provided by EXIF.tools