1 60-2241—8
T4039 Thermostats Control Line Voltage Valves of
a fan coil unit in cooling, manual changeover heat-
ing-cooling, or automatic changeover heating-cool-
ing systems. One or two valves may be controlled
directly by the thermostat. The fan switch (where
applicable) controls air circulation.
T4039A,B,D-M,S,V
Line Voltage Cooling and
Heating-Cooling Thermostats
J. H. • Rev. 10-92 • ©Honeywell Inc. 1992 • Form Number 60-2241—8
■Color-coded leadwires.
■All models can be mounted on standard vertical
outlet boxes. Models with manual switching can be
mounted on 4 in. square junction boxes or 2-
ganged outlet boxes.
■Adjustable range stops limit temperature adjust-
ment or lock at selected setpoint.
■Models available with separate power source for
fan and thermostat.
■1-, 2-, or 3-speed manual fan control available.
■Positive deadspot separates heating-cooling circuits
in automatic models. Remote changeover switch is
required to separate circuits in manual changeover
heating-cooling models.
■Scale range is approximately 55° F to 95° F [13° to
35° C] in 10° F [6° C] increments from 75° F [24°
C] midpoint. Scale is marked COOL-WARM.
■Cooling circuit breaks in FAN-OFF position to re-
duce condensation problems in the fan coil unit.
CONTENTS
Specifications ................................................. 2
Ordering Information ..................................... 2
Installation ..................................................... 5
Operation ....................................................... 8
Checkout......................................................... 8
2
T4039A,B,D-M,S,V
SPECIFICATIONS • ORDERING INFORMATION
Specifications
MODELS:
Manual
System SwitchingaModel
Cooling Only Off-OnbT4039A
Cooling Only Hi-Med-Lo T4039B
Off-Onb
Heating-Coolingc— T4039D
Off-Ond
Heating CoolingcOff-Hi-LobT4039E
—
Heating-CoolingcHi-Med-Lo T4039F
Off-Onb
Automatic Heating-Cooling None T4039G
Automatic Heating-Cooling — T4039H
Off-Ond
Automatic Heating-Cooling Off-Hi-LobT4039J
Automatic Heating-Cooling Off-Hi-LodT4039K
—
Automatic Heating-Cooling Hi-Med-LobT4039L
Off-On
Autoamtic Heating-Cooling Hi-Med-Lo T4039M
Off-Ond
Automatic Heating-Cooling Hi-Med-Lo T4039S
Heat-Off-Coold
Automatic Heating-Cooling Hi-Lo T4039V
Off-Ond
aSee Fig. 4 for arrangements of switches.
bOFF breaks cooling circuit and fan circuit.
cRemote changeover switch required.
dOFF breaks both heating and cooling circuits and
fan circuit.
ELECTRICAL RATINGS:
A. Thermostat (valve load).
Normal (A) Inrush (B)
120 Vac 0.32 1.00
240 Vac 0.16 0.50
277 Vac 0.14 0.43
B. Fan Switch
Full Load (A) Locked Rotor (A)
120 Vac 5.5 33.0
240 Vac 2.75 16.5
277 Vac 2.4 14.4
10A Resistive at 125 Vac
5A Resistive at 240 Vac
4.2A Resistive at 277 Vac
TEMPERATURE SETTING RANGE: Approximately
55° F to 95° F [13° C to 35° C]; marked COOL-
WARM in 10° F [6° C] increments from 75° F [24° C]
midpoint.
DIFFERENTIAL: Approximately 2° F [1° C] at mid-
scale. On automatic heating-cooling models, the
differential from make of one contact to make of
the opposite contact is 7° F [4° C] maximum with a
positive deadspot.
DIMENSIONS: See Figs. 1 and 2.
Ordering Information
When purchasing replacement and modernization products from your TRADELINE® wholesaler or your distributor, refer to the
TRADELINE Catalog or price sheets for complete ordering number, or specify—
1. Model number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directly).
2. Home and Building Control Customer Satisfaction
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9. International Sales and
Service offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico,
Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
3 60-2241—8
T4039A,B,D-M,S,V
SPECIFICATIONS
FINISH: Silver bronze. T4039M is available in white.
MOUNTING: Models without manual switching mount
on standard vertical outlet boxes. Models with manual
switching mount on 4-in. square junction boxes or
2-ganged outlet boxes. Manual switching models may
Fig. 1—Mounting dimensions in in. [mm] of
T4039 models with manual switching. Fig. 2—Mounting dimensions in in. [mm] of
T4039 models without manual switching.
also mount on a standard vertical outlet box if local
codes permit. See Fig. 3.
UNDERWRITERS LABORATORIES, INC. LISTED: File
No. E4436, Vol. 2, dated 3-19-73; Guide No. XAPX.
4
T4039A,B,D-M,S,V
SPECIFICATIONS
Fig. 3—Mounting T4039.
5 60-2241—8
T4039A,B,D-M,S,V
INSTALLATION
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After the installation is complete, check out product
operation as provided in these instructions.
CAUTION
Disconnect power supply to prevent electrical shock
or equipment damage.
Before mounting, be sure to remove cardboard shipping
inserts that protect the contacts.
1. Remove T4039 cover by loosening the cover screw
with Allen wrench.
2. Open the cardboard inside cover by pressing inward on
the left side to release latch. Do not remove this cover.
3. Carefully remove the shipping inserts from around the
snap contacts.
4. Check contact operation before mounting device.
MOUNTING
Models without manual switching mount on standard
vertical outlet boxes. Models with manual switching
mount on 4-in. square junction boxes or 2-ganged outlet
boxes. Manual switching models can also mount on stan-
dard vertical outlet boxes if local electrical codes permit.
Mount thermostat on side wall about 5 ft. [1.5 m] above
the floor. Do not mount where thermostat can be affected by
drafts, radiant heat from the sun or other sources of heat.
Use Allen wrench to open cover and mount according
to Fig. 3. Two mounting screws are provided.
WIRING
Disconnect power supply before beginning installa-
tion to avoid electrical shock or equipment damage. All
wiring must comply with local codes and ordinances.
Internal schematic and external connections for the
T4039 are shown in Fig. 4. Use solderless connectors or
other approved methods to wire thermostat into the sys-
tem. Six-inch color-coded leadwires are provided.
SETTING
The T4039 temperature scale is marked COOL-WARM
with approximate scale divisions of 10° F from 75° F
[24° C] midpoint. The range is approximately 55° F to 95°
F [13° C to 35° C]. Set lever at desired temperature.
To adjust the temperature setpoint range stops, Fig. 3,
locate stops at the desired temperature range setpoint
and insert.
6
T4039A,B,D-M,S,V
INSTALLATION
Fig. 4—Internal schmeatics and external connections for T4039 Thermostats.
M5353
OFF BREAKS COOLING AND FAN CIRCUITS.
OFF BREAKS HEATING, COOLING AND FAN CIRCUITS.
SEPARATE POWER SOURCE FOR THERMOSTAT AND
FAN. CONNECT ORANGE AND YELLOW FOR
SINGLE POWER SOURCE IF NEEDED.
1
2
3
T4039G
BROWN
RED TO COOLING
CONTROL
ORANGE L1 (HOT)
RISE
TO HEATING
CONTROL
TO FAN
SPEED CONTROL
YELLOW
TAN
T4039B
HI
LO
MED
OFF
ON
RISE
BLUE
RED TO COOLING
CONTROL
ORANGE
1
L1 (HOT)
OFF
ON
RISE
TO FAN
BLUE
RED TO COOLING
CONTROL
YELLOW
ORANGE
1
3
L1 (HOT)
L1 (HOT)
T4039A
T4039F
TO FAN
SPEED CONTROL
YELLOW
TAN
HI
LO
MED
OFF
ON
BLUE
1
TO COOLING
CONTROL
BROWN TO HEATING
CONTROL
RED
ORANGE L1 (HOT)
RISE
RISE
HI
LO
MED
T4039H
TO HEATING
CONTROL
BROWN
2
OFF
ON
TO FAN
BLUE
RED TO COOLING CONTROL
YELLOW
ORANGE 3
L1 (HOT)
RISE
L1 (HOT)
TO COOLING CONTROL
YELLOW
BROWN TO HEATING
CONTROL
T4039E
TO FAN
SPEED CONTROL
HI
LO
OFF
BLUE
RED
ORANGE
1
L1 (HOT)
RISE
RISE
LO
HI
TO HEATING
CONTROL
BROWN
2
T4039D
OFF
ON
TO FAN
BLUE
RED TO COOLING CONTROL
YELLOW
ORANGE 3
L1 (HOT)
RISE
RISE
L1 (HOT)
7 60-2241—8
T4039A,B,D-M,S,V
INSTALLATION
Fig. 4—Internal schmeatics and external connections for T4039 Thermostats
(Continued).
M5352
OFF BREAKS COOLING AND FAN CIRCUITS.
OFF BREAKS HEATING, COOLING AND FAN CIRCUITS.
SEPARATE POWER SOURCE FOR THERMOSTAT AND
FAN. CONNECT ORANGE AND YELLOW FOR SINGLE
POWER SOURCE IF NEEDED.
1
2
3
THE WIRE COLORS OF THE T4039K1024 MODEL DIFFER
FROM THE TYPICAL T4039K MODELS AS FOLLOWS:
4
TYPICAL
T4039K YELLOW RED
BLUE BROWN ORANGE
T4039K1024 BROWN RED BLUE YELLOW BLACK
T4039J
TO COOLING
CONTROL
YELLOW
BROWN TO HEATING
CONTROL
TO FAN
SPEED CONTROL
HI
LO
OFF
BLUE
RED
ORANGE
1
L1 (HOT)
RISE
LO
HI
T4039M
TO COOLING
CONTROL
RED
YELLOW
BLACK
HI
LO
MED
OFF
ON
BLUE
2
BROWN TO HEATING
CONTROL
ORANGE L1 (HOT)
RISE
HI
LO
MED
TO FAN
SPEED CONTROL
BLACK L1 (HOT)
T4039V
YELLOW
TO COOLING
CONTROL
RED
HI
LO
OFF
ON
BLUE
BROWN
TO HEATING
CONTROL
RISE
HI
LO TO FAN
SPEED CONTROL
2
T4039S
YELLOW
TAN
HI
LO
MED
OFF
COOL
BLUE
TO COOLING
CONTROL
BROWN TO HEATING
CONTROL
RED
ORANGE L1 (HOT)
RISE
HI
LO
MED
TO FAN
SPEED CONTROL
HEAT
2
TYPICAL T4039K 4
2
TO COOLING
CONTROL
YELLOW
BROWN TO HEATING
CONTROL
TO FAN
SPEED CONTROL
HI
LO
OFF
BLUE
RED
ORANGE
L1 (HOT)
RISE
LO
HI
T4039L
TO FAN
SPEED CONTROL
YELLOW
TAN
HI
LO
MED
OFF
ON
BLUE
TO COOLING
CONTROL
BROWN TO HEATING
CONTROL
RED
ORANGE L1 (HOT)
RISE
HI
LO
MED
1
8
Operation
In heating applications, as the temperature drops, the
thermostat heating contacts make to open a valve that
allows hot water to flow through the coil. On select models,
the speed at which the heat is circulated is controlled
manually by the fan switch.
In cooling applications, as the temperature rises, the
thermostat cooling contacts close to open a valve that
allows cold water to flow through the coil. Cooling mecha-
nism will not operate if manual switch is in the OFF
position. Models T4039D,H,K,M,S,V will also turn off
the heating valve when the manual switch is in OFF.
In manual changeover heating-cooling models, the
thermostat must be used with a remote changeover switch
or control to select the proper heating or cooling cycle
for the thermostat.
CALIBRATION
The T4039 is accurately calibrated at the factory under
controlled conditions. Do not attempt to field calibrate
this device.
Checkout
Home and Building Control Home and Building Control
Honeywell International, Inc. Honeywell Limited—Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario
M1V 4Z9
Check the T4039 before leaving the installation. Raise
the temperature setting to start the heating cycle or lower the setting to start the cooling cycle. Check both cycles
on heating-cooling models.