Honeywell T8400C Users Manual 69 1480 And T8401C Electronic Thermostats

2015-01-23

: Honeywell Honeywell-T8400C-Users-Manual-262480 honeywell-t8400c-users-manual-262480 honeywell pdf

Open the PDF directly: View PDF PDF.
Page Count: 6

DownloadHoneywell Honeywell-T8400C-Users-Manual- 69-1480 - T8400C And T8401C Electronic Thermostats  Honeywell-t8400c-users-manual
Open PDF In BrowserView PDF
T8400C and T8401C
Electronic Thermostats
INSTALLATION INSTRUCTIONS
The T8400C and T8401C Thermostats provide singlestage, non-programmable temperature control for 24V
heating-cooling systems with manual changeover from
heat to cool. Heating cycle rate is selectable at 1, 3, 4, 5,
6, or 9 cph. Cooling cycle rate is fixed at 3 cph.
Temperature indication can be set for °F or °C.
The T8400C Thermostat is powered through the heating/
cooling system controls. The T8401C Thermostat is
powered directly from the system transformer. Batteries
are not required because setpoints are held permanently
by non-volatile memory for all models.
All TRADELINE® models include a thermostat, wallplate
(for wiring and mounting thermostat) and owner’s guide.
The T8400C SUPER TRADELINE® model also includes
two decorator cover plates for covering wallmarks.

MERCURY NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of an old control containing
mercury in a sealed tube.

INSTALLATION
When Installing this Product…
1.
2.
3.
4.

Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
Installer must be a trained, experienced service
technician.
After installation is complete, check out product
operation as provided in these instructions.

CAUTION

Electrical Shock or Equipment Damage
Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.

Location
Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1. Do not install the thermostat where it can be
affected by:
— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from the sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
This thermostat is a precision instrument and was
carefully adjusted at the factory. Handle it carefully.

® U.S. Registered Trademark
Copyright © 2002 Honeywell •

• All Rights Reserved

69-1480-1

T8400C AND T8401C ELECTRONIC THERMOSTATS

YES
NO

NO
5 FEET
[1.5 METERS]
NO

M10308

Fig. 1. Typical location of thermostat.

Mounting Decorator Cover Plate and
Wallplate to Wall

The shape of the terminals permits insertion of straight or
wraparound wiring connections; either method is
acceptable. See Fig. 4.

IMPORTANT
Level only for appearance. The thermostat functions normally even when not level.

The T8400C Thermostat is powered through the heating/
cooling system controls and is adaptable to most 4-wire,
18 to 30 Vac heating-cooling systems.

NOTE: Only SUPER TRADELINE® models have the
cover plate.

The T8401C Thermostat is powered directly from the
system transformer and is adaptable to most 5-wire, 18
to 30 Vac heating-cooling systems. Refer to Fig. 5 and 6
for typical wiring hookups.

Mount decorator cover plate (SUPER TRADELINE®
model only), wallplate, T8400C or T8401C, and the
screws provided (see Fig. 2) as follows:
1. Place the desired decorator cover plate and the
wallplate at the desired location on the wall.
2. Pull the thermostat wire through the entrance hole
on the decorator cover plate, then through the wallplate entrance hole.
3. Select the two mounting holes that best fit the
application.
4. Fasten the decorator cover plate and the wallplate
to the wall using the anchors and screws provided.
5. After wiring the wallplate, plug the hole to prevent
drafts from affecting the thermostat; see Wiring
section.

5-3/4 IN. x 5-3/4 IN.
DECORATOR
COVER PLATE
WALL

1
2

WALL
ANCHORS (2)

Wiring
IMPORTANT
Use an 18-gauge maximum wire for wiring the
T8400C and T8401C Thermostats.
All wiring must comply with local electrical codes and
ordinances. Disconnect the power supply to prevent
electrical shock or equipment damage.
NOTE: To ensure proper mounting of thermostat,
restrict all wiring to the shaded area on the left
side of the terminals. See Fig. 3.

69-1480-1

1

3-7/8 IN. x 3-7/8 IN. DECORATOR COVER PLATE (SELECT MODELS).

2

DRILL 3/16 INCH HOLES (IF DRYWALL) OR 7/32 (PLASTER OR WOOD)
WHEN USING WALL ANCHORS.
M11041C

Fig. 2. Mounting decorator cover plate
and wallplate to wall.

2

T8400C AND T8401C ELECTRONIC THERMOSTATS

KEEP WIRING IN
SHADED AREA

T8400C, T8401C

ALTERNATE MOUNTING
SCREW HOLE

W
COOLING
CONTACTOR

Y
G
R

W

FAN
RELAY

C

2

1

Y

MOUNTING
SCREW
HOLE

G
R

L1
(HOT)

1
L1
(HOT)

L2

24V

T

T

OIL PRIMARY
CONTROL

L2

C

ALTERNATE
MOUNTING
SCREW HOLE

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.

2

IN T8401C INSTALLATIONS, CONNECT C TERMINAL.

M11022B

Fig. 6. T8400C/T8401C heat-cool wiring
diagram in oil heating/electric cooling system.
Oil primary has its own transformer.

WIRING ENTRANCE HOLE
MOUNTING
SCREW HOLE

1

M11023

Mounting Thermostat to Wallplate

Fig. 3. Restrict wiring to shaded area.

1.
2.

W

Engage the tabs at the top of the thermostat and
wallplate.
Swing down the thermostat and press the lower
edge of the thermostat onto the wallplate to latch.
See Fig. 7.
DASHED LINES INDICATE TABS
ON BACK OF THERMOSTAT

Y

G
FOR WRAPAROUND
STRIP 7/16 IN. (11 MM)

Set
Set

Room

Room

R
FOR STRAIGHT INSERTION
STRIP 5/16 IN. (8 MM)

FAN
Auto On

FAN
Auto

SYSTEM
Cool Off Heat

SYSTEM
Cool Off Heat

C

A

M11232

TERMINAL SCREW

Fig. 4. Wiring connections.

COOLING
CONTACTOR

Y
G
R

L1
(HOT)

PRESS LOWER EDGE OF
CASE TO LATCH.

Fig. 7. Mounting thermostat wallplate.

W

C
HEATING
PRIMARY
CONTROL

1

B

M18416

T8400C, T8401C

2

ENGAGE TABS AT TOP
OF THERMOSTAT WITH
SLOTS ON WALLPLATE.

OPERATION
Setting FAN and SYSTEM Switches

FAN
RELAY

Fan and system settings are controlled manually by
using the switches located at the bottom of the
thermostat case. See Fig. 8.

24V

L2
1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.

2

IN T8401C INSTALLATIONS, CONNECT C TERMINAL.

FAN Switch
M11021B

Fig. 5. T8400C/T8401C heat-cool wiring diagram in
single transformer system with gas heat/electric
cooling.

Fan switch settings are:
On: The fan runs continuously. Use for improved air
circulation and air quality.
Auto: Normal setting for most homes. In cooling, the
fan starts and stops with the cooling equipment. In
heating, the fan is controlled directly by the heating
equipment and may start a few minutes after the
heating equipment turns on (on most systems).
When using an electric heat thermostat, the fan
starts and stops with the heating equipment.
3

69-1480-1

T8400C AND T8401C ELECTRONIC THERMOSTATS
Slide the FAN switch in the bottom left corner of the
thermostat to select the desired fan setting.

3.

To increase the temperature setpoint press the s
key. Each press changes the setpoint one degree;
press and hold to change the setpoint several
degrees.

4.

To decrease the temperature setpoint press the t
key. Each press changes the setpoint one degree;
press and hold to change the setpoint several
degrees.

SYSTEM Switch
System switch settings control thermostat operation as
follows:
Cool: The thermostat controls the cooling system.
Off: Both heating and cooling are off.
Heat: The thermostat controls the heating system.

M14681

Slide the SYSTEM switch in the bottom right corner of
the thermostat to select the desired system setting.
TEMPERATURE DISPLAY

M14682

INCREASE
SETTING

Set

NOTE: To save changes to the °F/°C indication and the
heat cycle rate, all seven steps must be completed.

Room

FAN
Auto On

Setting °F/°C Indication and Heat Cycle Rate

DECREASE
SETTING

SYSTEM
Cool Off Heat

FAN SWITCH

SYSTEM SWITCH

To set the °F/°C indication and heat cycle rate:
1. If the temperature is displayed in °F, set the temperature setpoint to 52°F. If the room temperature
is displayed in °C, set the temperature setpoint to
11°C.

M18417

Fig. 8. Digital display and system
switches (FAN and SYSTEM).

Set Temperature Setpoint
NOTE: Temperature setpoint range is 40° to 99°F (5° to
37°C).

M14683

OPTIONAL SYSTEM CHECKOUT
When in steps 2 and 3 only, the t key can be used to turn
heat or cool outputs on and off. Change the SYSTEM
switch setting to test heat or cool outputs. No action
takes place If the system switch is in the Off position.
Examples: System setting at HEAT: If heat is on, the t
key turns it off; if heat is off, t turns it on.

The temperature setpoint and the room temperature are
shown separately on the digital display. The t indicator
points to Set when the temperature setpoint is displayed
and to Room when the room temperature is displayed
.

M14684

System setting at COOL: If cool is on, t key
turns it off; if cool is off, t turns it on.

INDICATOR
Set

Room

ROOM TEMPERATURE

SETPOINT TEMPERATURE
M14679
M14685

To set temperature setpoint:
1. Select Heat or Cool by sliding the SYSTEM switch
in the lower right corner of the thermostat to the
desired mode. See Fig. 8.
2. To display the temperature setpoint on the digital
display, press either the s or t key once. The temperature setpoint is displayed for approxi-mately
five seconds as the indicator points to Set and
flashes.

M14680

69-1480-1

2.

Press the st keys simultaneously for more than one
second to light all segments on display and to enter
installer setup mode. When the keys are released,
a two-digit software revision code is displayed.

M14686

NOTE: In installer setup mode only, each press of the s
key momentarily displays 01. Each press of the
t key momentarily displays 02. When the keys
are released, these two-digit codes are no
longer displayed.

4

T8400C AND T8401C ELECTRONIC THERMOSTATS
3.

Press the s key. Factory information is displayed. A
typical example is shown, but information displayed varies by model. This information is for factory use only.

Press the s key to save all changes, exit installer
setup mode and return to normal operation.

NOTE: After exiting installer setup mode, change the
setpoint to the desired room temperature.

CHECKOUT

M14687

4.

10.

Press the s key again to display °C or °F.

Heating
1.
2.

M14688

5.

Press the t key to change the °C or °F indication.

6.

Press the s key to display the heat cycle rate of 1, 3,
4, 5, 6, 9, or 12. If the desired cycle is displayed,
press the s key to exit the installer setup mode. To
change the heat cycle rate, press the t key to scroll
between 1, 3, 4, 5, 6, or 9. Stop scrolling when the
desired rate is displayed. See Table 1 for the cycle
rate options and the corresponding system equipment.

M14689

3.

Slide the SYSTEM switch to Heat and the FAN
switch to Auto, if available.
Press and hold the s key to raise the temperature
setting several degrees above the room temperature. After approximately ten seconds, the heating
equipment should start. In conventional systems,
the system turns on the fan through the use of a
time delay relay or through a limit control. When
using an electric heat thermostat, the fan starts
immediately.
Press the t key to lower the temperature setting
below the room temperature. Heating equipment
should stop.

Cooling

CAUTION

Low Temperature Hazard.
Operating at too low of an outdoor
temperature may cause compressor damage.
Do not operate cooling if outdoor temperature is
below 50°F (10°C). Refer to manufacturer’s
recommendations.

M14690

Table 1. Heating Cycle Rates.
System

Cycles Per Hour

Steam, radiant floor heat, gravity

1

Hydronic heat, condensing gas
furnacea

3

Gas or oil forced air

6

Electric heat

1.
2.

9
4, 5, 12

Special applicationsb

3.

aHigh

efficiency furnace.
bRefer to equipment manufacturer’s instructions.
NOTE: Steps 7 and 8 are available on select models.
7.

Press the s key to display cooling algorithm configuration default.

NOTE: To bypass the 5 minute delay, see the Optional
System Checkout section.

Fan
1.
2.

M18419A

8.

9.

Press the s key again to change cooling algorithm
to C1 or C3.
C1 = Standard cooling algorithm.
C3 = Aggressive cooling algorithm (can cause
overshooting).
Press the s key again. Current configuration (CC) is
displayed. A typical example is shown, but CC varies
by model. (This information is for factory use only.)

Slide the SYSTEM switch to Cool and the FAN
switch to Auto.
Press the t key to lower the temperature setting
several degrees below the room temperature. After
approximately five minutes, the cooling equipment
should start. The fan starts and stops with the cooling equipment.
Press the s key to raise the temperature setting
above the room temperature. Cooling system
should shut down.

Slide the SYSTEM switch to Off and the FAN
switch to On. The fan should run continuously.
Slide the FAN switch to Auto. In heating, the fan is
controlled directly by the heating equipment and
may start a few minutes after the heating equipment
turns on (on most systems). When using an electric
heat thermostat, the fan starts and stops with the
heating equipment. In cooling, the fan starts and
stops with the cooling equipment.

Make certain all equipment responds properly to the
thermostat.

M18420

5

69-1480-1

Automation and Control Solutions
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422

69-1480-1

G.H. Rev. 2-02

Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario
M1V 4Z9

www.honeywell.com/yourhome



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Encryption                      : Standard V1.2 (40-bit)
User Access                     : Print, Copy, Fill forms, Extract, Assemble, Print high-res
Page Mode                       : UseOutlines
XMP Toolkit                     : 3.1-701
Producer                        : Acrobat Distiller 7.0 (Windows)
Creator Tool                    : FrameMaker 7.0
Modify Date                     : 2006:06:16 13:12:21-05:00
Create Date                     : 1999:07:07 12:30:47Z
Metadata Date                   : 2006:06:16 13:12:21-05:00
Format                          : application/pdf
Title                           : 69-1480 - T8400C and T8401C Electronic Thermostats
Creator                         : Honeywell ECC Technical Communications
Description                     : Installation Instructions
Document ID                     : uuid:dbe761d1-3f94-4028-9544-16740a44f323
Instance ID                     : uuid:ae66e038-e0b8-4809-b563-a32b6c27c81e
Page Count                      : 6
Subject                         : Installation Instructions
Author                          : Honeywell ECC Technical Communications
EXIF Metadata provided by EXIF.tools

Navigation menu