TRADELINE ® R182J, R482J, R845A, R847A, RA89A, RA832A Switching Relays Application These relays can be used for a variety of switching applications. Typically they provide control of line- or low-voltage devices by a low voltage controller. See Table 1. TABLE 1—SWITCHING RELAY SPECIFICATIONS. Models R182J R482J a Application For 24V thermostat control of line voltage devices. Controlled by a line voltage controller R845A For hot water zone control systems or spst control of two separate loads. R847A Provides switching for high-current loads such as cooling compressors. RA89A For switching one line voltage load. RA832A For switching two line voltage loads with a common power source. Voltage (50/60 Hz) Switch Action Control Circuit Coil Voltage (Vac at 50/60 Hz) 120 Dpdt 3-wire 24 Relay Coil Current (A) 0.40 a Contact Ratings (A) AFL ALR 240 120 2-wire 7.4 44.4 3.7 22.2 120 0.08 7.4 44.4 208/240 0.04 3.7 22.2 24 0.40 7.4 44.4 120 22 100 240 10 50 10.2 61.2 208/240 120 Dpst 120 Spst 120 Dpst 240 IMPORTANT: The transformer on the R182 can overheat when used with a series 20 thermostat if the total resistance of the thermostat circuit exceeds 2.5 ohms. If the measured resistance of the thermostat (including thermostat wire and thermostat contact resistance) exceeds 2.5 ohms, add a 100 ohm, 10 watt resistor between the W and R terminals. Table 2 gives maximum thermostat wire runs; if longer runs are necessary, measure the resistance or add a 100 ohm, 10 watt resistor across terminals W and R. 7.4 44.4 3.7 22.2 TABLE 2—LENGTH OF WIRE. Length of Run to Thermostat (Wires) AWG Wire Size (Number) Feet Meters Feet 22 120 38.0 60 18.0 20 200 61.0 100 30.5 18 300 91.5 150 45.5 16 500 152.5 250 76.0 14 800 244.0 400 122.0 Total Wire Length Meters J.H. • Rev. 10-94 1 • ©Honeywell Inc. 1994 • Form Number 69-0791—3 Installation Fig. 1—Approximate mounting dimensions in in. [mm]. WHEN INSTALLING THIS PRODUCT… 1. Read these instructions carefully. Failure to follow instructions can damage product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. Make sure installer is a trained, experienced service technician. 4. After completing installation, use these instructions to check out product operation. 4 5 1 [29] 32 1 [108] 4 7 8 [48] 1 7 [22] DIAMETER 8 3 [2] DIAMETER 32 1 [13] DIAMETER 2 WARNING KEYHOLE TYPE MOUNTING HOLE ELECTROCUTION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH. Transformer core not bonded. 1 2 [114] 4 Disconnect power supply before wiring to prevent electrical shock or equipment damage. 1 4 [133] 5 MOUNTING For replacement, mount the relay in the same location as the old relay. If this is a new installation, locate the relay vertically on a solid wall or partition as close as possible to the device to be controlled. Select a location that is easily accessible for installation and service. 3 [10] 8 1 3 [89] 2 7 [6] DIAMETER MOUNTING HOLE 32 NOTE: To reduce the possible transformer hum and relay noise that is sometimes amplified by mounting surfaces such as sheetmetal, plasterboard, and similar materials, place rubber or felt washers between the case and the mounting surface. 15 2 16 [75] 7 8 [48] 1 1. Position the relay and mark the mounting holes. See Fig. 1. 2. Start a screw for the keyhole type mounting hole in the upper right corner. Screw it down within about 1/8 in. [3 mm] of the surface. 3. Hang the relay on the screw, position the case, and start the bottom screw. 4. Tighten both screws. 25 [20] 32 1 KNOCKOUT FOR 1/2 (13) CONDUIT (3) 3 [35] 8 M3823 Fig. 2—Internal schematic and typical hookup for RA89A. LOW VOLTAGE (CLASS 2) 2-WIRE THERMOSTAT WIRING All wiring must comply with all applicable electrical codes, ordinances, and regulations. Follow any instructions furnished with the controlled equipment. T T RA89A (SPST) RA89A 2 JUMPER REMOVED 2 IMPORTANT: The switching relay terminals are approved for use with copper wires only. 1 3 4 JUMPER 2 See Figs. 2 through 9 for hookup diagrams for these relays. When two or more devices are to be controlled in parallel, the total current must not exceed the relay load rating. Fig. 11 is an internal view of the RA832A showing terminal locations and barriers. Never connect load terminals to a load that takes more current than the amount listed in the electrical ratings on the relay. 69-0791—3 3 [10] 8 1 3 4 L2 1 CONTROLLER (IF USED) L2 2 1 L1 HOT TO LOAD L1 HOT 1 TO LOAD 1 POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED. 2 COMPLETE WIRING AS SHOWN ABOVE. M3819 Fig. 3—Internal schematic and typical hookup for RA832A. LOW VOLTAGE (CLASS 2) 2-WIRE THERMOSTAT Fig. 6—Internal schematics and typical hookup for R482J. R482J AUXILIARY TO LOW OR MILLIVOLTAGE (POWERPILE) LOAD RA832A T T 2 1 X X 3 3 1 CONTROLLER L2 1 LOAD 1 L1 HOT 1 LOAD 2 (OPTIONAL) R 3 OHMS 6 7 8 N.O. N.C. COM. TO LOAD TO LOAD POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED. 2 CONTROLLER (IF USED) MUST BE SNAP ACTION OR MERCURY SWITCH TYPE. 3 N.O. CONTACTS MAKE BEFORE N.C CONTACTS BREAK, AND N.C. CONTACTS MAKE BEFORE N.O. CONTACTS BREAK. M8234 K1 K1 Fig. 7—Schematic diagram showing R845A in multizone, forced hydronic heating system. This arrangement is suitable for any number of additional zones. L2 2 K2 K1 4 3 HYDRONIC HEATING CONTROL TERMINALS 6 7 T LOAD L1 L2 (HOT) 3 B K2 L1 5 1 R182J X 4 N.O. N.C. COM. L2 Fig. 4—Internal schematic and typical hookup for R182J. 2 2 L1 (HOT) 1 POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED. M3821 W 3 4 1 N.O. N.C. N.O. RA845A RELAY THERM. THERMOSTAT ZONE 1 T LOAD N.C. TO ADDITIONAL R845A RELAYS FOR OTHER ZONES 2 1 POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED. 2 N.O. CONTACTS MAKE BEFORE N.C CONTACTS BREAK, AND N.C. CONTACTS MAKE BEFORE N.O. CONTACTS BREAK. THERMOSTAT ZONE 2 1 ZC 4 ZP 3 B1 BURNER BURNER CONTROL B2 M8232 5 6 C1 Fig. 5—Thermostat connections for R182J. CIRC. CIRCULATOR ZONE 1 CIRCULATOR ZONE 2 C2 THREE-WIRE LOW VOLTAGE (SERIES 10) THERMOSTAT 1 W R THREE-WIRE LOW VOLTAGE (SERIES 20) 2 THERMOSTAT B B W TWO-WIRE LOW VOLTAGE (SERIES 80) THERMOSTAT 1 LINE 2 1 L1 HOT L2 2 3 R 1 POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED. W X R B W X R B W X R 2 IF CONTROLLING TWO LOADS, USE: 3 AND 4 FOR LINE VOLTAGE LOAD 5 AND 6 FOR LINE OR LOW VOLTAGE LOAD B 3 IF USING LOW VOLTAGE, USE A SEPARATE TRANSFORMER. R182J R182J M3822 R182J JUMPER 1 MAKES CONTACT ON TEMPERATURE FALL ONLY. 2 MAKES CONTACT ON BOTH A TEMPERATURE RISE AND FALL. M8233A 3 69-0791—3 Fig. 8—R845A hookup for controlling two loads. Fig. 10—Internal view of RA832A Switching Relay. LOW VOLTAGE (CLASS 2) 2-WIRE THERMOSTAT T X T X R845A T T 2 1 4 3 5 RELAY 6 24V TRANSFORMER 3 1 2 1 L1 HOT L2 TO POWER 1 TO POWER LOAD 1 LOAD 2 1 POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED. 2 WHEN CONTROLLING TWO LOADS, USE 3 AND 4 FOR LINE VOLTAGE LOAD AND 5 AND 6 FOR LINE OR LOW VOLTAGE LOAD. 3 IF USING LOW VOLTAGE, USE A SEPARATE TRANSFORMER. 2 1 M3820 3 4 M3824 Fig. 9—Internal schematics and hookup for R847A. LOW VOLTAGE (CLASS 2) 2-WIRE THERMOSTAT Service and Checkout R847A T T L2 L1 4 3 7 4 1. Never use oil on any part of the relay coil or contacts. 2. Keep the cover on the relay during normal operation and remove only for service and checkout. 3. Relay contacts require no cleaning; they are arranged so they close with a wiping action and are self-cleaning. The contacts may turn black after being in service for some time; this discoloration does not prevent proper operation. 4. After installation is complete, operate system through at least one cycle from the controller to make certain the relay controls the equipment as intended. 6 4 3 1 L2 2 1 TO L1 POWER (HOT) LOAD 1 1 TO POWER LOAD 2 1 POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED. 2 WHEN CONTROLLING TWO LOADS, USE 3 AND 4 FOR LINE VOLTAGE LOAD AND 5 AND 6 FOR LINE OR LOW VOLTAGE LOAD. 3 IF USING LOW VOLTAGE, USE A SEPARATE TRANSFORMER. 4 10 AMP CONTACT RATING OR 20 AMP WHEN POLES ARE CONNECTED IN PARALLEL. M8231B Home and Building Control Honeywell Inc. 1985 Douglas Drive North Golden Valley, MN 55422 69-0791—3 Printed in U.S.A. Home and Building Control Honeywell Limited—Honeywell Limitée 740 Ellesmere Road Scarborough, Ontario M1P 2V9 4 Helping You Control Your World QUALITY IS KEY
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : Yes Encryption : Standard V4.4 (128-bit) User Access : Print, Copy, Extract, Assemble, Print high-res XMP Toolkit : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39 Create Date : 2001:05:16 12:35:05Z Creator Tool : Adobe PageMaker 6.5 Modify Date : 2007:05:07 15:46:32-05:00 Metadata Date : 2007:05:07 15:46:32-05:00 Format : application/pdf Description : Installation Instructions Creator : HBC Technical Communications Title : 69-0791 - R182J, R482J, R845A, R847A, RA89A, RA832A Switching Relays Keywords : Producer : Acrobat Distiller 4.05 for Macintosh Document ID : uuid:8fe93f05-ca25-4991-a04a-3501ca815fd5 Instance ID : uuid:5c040633-3ae0-460b-933b-39c87a6e3771 Page Count : 4 Subject : Installation Instructions Author : HBC Technical CommunicationsEXIF Metadata provided by EXIF.tools