Honeywell WFSLCDUI Wireless Display Driver User Manual SLC Gateway Firelite

Honeywell International Inc. Wireless Display Driver SLC Gateway Firelite

Exhibit D Users Manual per 2 1033 b3

FLP/N LS10036-000FL-E:FLRev ECN FLECNDocument LS10036-000FL-E10/10/FLite                          Firelite Wireless Sensor NetworkLS10036-000FL-EUser ManualPRELIMINARY
2 PRELIMINARY:  Firelite Wireless Sensor Network — P/N LS10036-000FL-E:N0  10/10/2013Fire Alarm & Emergency Communication System LimitationsWhile a life safety system may lower insurance rates, it is not a substitute for life and property insurance!An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notifi-cation capability—can provide early warning of a developing fire.  Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.  An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice commu-nication, and other various interoperable communication meth-ods—can broadcast a mass notification message.  Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.  The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers.  This document can be found at http://www.systemsensor.com/appguides/.  A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires.  While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire.  A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors.  Smoke detectors also may not sense a fire on another level or floor of a building.  A second-floor detector, for example, may not sense a first-floor or basement fire.  Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:• Barriers such as closed or partially closed doors, walls, chim-neys, even wet or humid areas may inhibit particle or smoke flow.  • Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.  • Smoke particles may be blown away from detectors by air outlets, such as air conditioning vents. • Smoke particles may be drawn into air returns before reach-ing the detector.  The amount of “smoke” present may be insufficient to alarm smoke detectors.  Smoke detectors are designed to alarm at var-ious levels of smoke density.  If such density levels are not cre-ated by a developing fire at the location of detectors, the detectors will not go into alarm.  Smoke detectors, even when working properly, have sensing limitations.  Detectors that have photoelectronic sensing cham-bers tend to detect smoldering fires better than flaming fires, which have little visible smoke.  Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires.  Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.  Smoke detectors cannot be expected to provide adequate warn-ing of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materi-als, etc.).  Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level.  Rate-of-rise heat detec-tors may be subject to reduced sensitivity over time.  For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist.  Heat detectors are designed to protect property, not life.  IMPORTANT!  Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power.  If detectors are not so located, a devel-oping fire may damage the alarm system, compromising its abil-ity to report a fire.  Audible warning devices such as bells, horns, strobes, speakers and displays may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building.  Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol, or medication.  Please note that:• An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.• Voice messaging systems must be designed to meet intelligi-bility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).• Language and instructional requirements must be clearly dis-seminated on any local displays.• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.  • Studies have shown that certain people, even when they hear a fire alarm signal, do not respond to or comprehend the meaning of the signal.  Audible devices, such as horns and bells, can have different tonal patterns and frequencies.  It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm sig-nals.  • In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.  A life safety system will not operate without any electrical power.  If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.  Equipment used in the system may not be technically compat-ible with the control panel.  It is essential to use only equipment listed for service with your control panel.  Telephone lines needed to transmit alarm signals from a prem-ises to a central monitoring station may be out of service or tem-porarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.  The most common cause of life safety system malfunction is inadequate maintenance.  To keep the entire life safety system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan-dards.  At a minimum, the requirements of NFPA 72 shall be fol-lowed.  Environments with large amounts of dust, dirt, or high air velocity require more frequent maintenance.  A maintenance agreement should be arranged through the local manufacturer's representative.  Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be per-formed by authorized professional life saftety system installers only.  Adequate written records of all inspections should be kept.  Limit-D-1-2013
PRELIMINARY:  Firelite Wireless Sensor Network — P/N LS10036-000FL-E:N0  10/10/2013 3Installation PrecautionsAdherence to the following will aid in problem-free installation with long-term reliability:WARNING - Several different sources of power can be connected to the fire alarm control panel.  Disconnect all sources of power before servicing.  Control unit and associ-ated equipment may be damaged by removing and/or insert-ing cards, modules, or interconnecting cables while the unit is energized.  Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any pro-gramming operation or change in site-specific software.  Re-acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo-nents, circuits, system operations, or software functions known to be affected by a change must be 100% tested.  In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.  This system meets NFPA requirements for operation at 0-49º C/32-120º F  and at a relative humidity  93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F).   However, the useful life of the system's standby batteries and the electronic com-ponents may be adversely affected by extreme temperature ranges and humidity.  Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F. Verify that wire sizes are adequate for all initiating and indi-cating device loops.  Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light-ning induced transients.  Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.  Consult with the Technical Ser-vices Department if any problems are anticipated or encoun-tered. Disconnect AC power and batteries prior to removing or inserting circuit boards.  Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear.  Before making modifi-cations, verify that they will not interfere with battery, trans-former, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs.  Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. This system contains static-sensitive components.  Always ground yourself with a proper wrist strap before han-dling any circuits so that static charges are removed from the body.  Use static suppressive packaging to protect electronic assemblies removed from the unit.Follow the instructions in the installation, operating, and pro-gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.Precau-D1-9-2005HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®,VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.HARSH™ is a trademark; and Acclimate®, FlashScan®, NION®, andVIEW® are all registered trademarks of Honeywell International Inc. MULTI-NET™,  Multi-Net Manager™,  Unimode Network™,  Unimode NetworkManager™, and Uni-Tility™ are trademarks of Tyco Integrated Security.  Echelon® is a registered trademark and LonWorks™ is a trademark of EchelonCorporation.  ARCNET® is a registered trademark of Datapoint Corporation.  Microsoft® and Windows®  are registered trademarks of the MicrosoftCorporation.  ©2013 by Honeywell International Inc.  All rights reserved. Unauthorized use of this document is strictly prohibited.
4 PRELIMINARY:  Firelite Wireless Sensor Network — P/N LS10036-000FL-E:N0  10/10/2013Software DownloadsIn order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products.  To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system.  Contact Technical Support with any questions about software and the appropriate version for a specific application. Documentation FeedbackYour feedback helps us keep our documentation up-to-date and accurate.  If you have any comments or suggestions about our online Help or printed manuals, you can email us.Please include the following information:•Product name and version number (if applicable)•Printed manual or online Help•Topic Title (for online Help)•Page number (for printed manual)•Brief description of content you think should be improved or corrected•Your suggestion for how to correct/improve documentationSend email messages to:FireSystems.TechPubs@honeywell.comPlease note this email address is for documentation feedback only.  If you have any technical issues, please contact Technical Services.
PRELIMINARY:  Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013   5Table of ContentsSection 1: About This Guide..................................................................................................101.1: Purpose ........................................................................................................................................................101.2: Assumed Knowledge...................................................................................................................................101.2.1: Additional References .......................................................................................................................101.3: Site Survey...................................................................................................................................................101.4: Abbreviations and Meanings.......................................................................................................................11Section 2: W-GATE .................................................................................................................122.1: Description...................................................................................................................................................122.2: Agency Approvals .......................................................................................................................................122.2.1: FCC....................................................................................................................................................122.3: Specifications...............................................................................................................................................132.3.1: Environmental Specification .............................................................................................................132.4: Installing W-GATE ......................................................................................................................................132.4.1: Before Installing ................................................................................................................................132.5: Mounting & Wiring .....................................................................................................................................142.5.1: Mounting ...........................................................................................................................................142.5.2: Wiring................................................................................................................................................162.5.3: W-GATE Powered from SLC ...........................................................................................................172.5.4: W-GATE Powered from an External +24VDC source .....................................................................182.6: Configuration and Programming.................................................................................................................192.6.1: Without a PC-based Configuration Tool...........................................................................................19Create a New Profile ............................................................................................................................19Assign a Previously Created Profile Using a Distributor.....................................................................20Removing a Profile...............................................................................................................................20Create Mesh Network...........................................................................................................................202.6.2: With a PC-based Configuration Tool................................................................................................21Assign Profile with PC Tools...............................................................................................................21Removing Profile with PC Tools .........................................................................................................22Mesh Formation with PC Tools ...........................................................................................................232.6.3: Profile Distribution............................................................................................................................232.6.4: SLC Configuration ............................................................................................................................242.7: Operations....................................................................................................................................................252.7.1: W-GATE Modes of Operation ..........................................................................................................25Start Up.................................................................................................................................................25Factory Default.....................................................................................................................................25Profile Configured................................................................................................................................25Mesh Formation....................................................................................................................................26Initial Mesh Optimization.....................................................................................................................26Normal Mode........................................................................................................................................26Rescue Mode ........................................................................................................................................26Mesh Optimization...............................................................................................................................27Bootloader ............................................................................................................................................272.7.2: Magnet Sensor Activations................................................................................................................27Profile Magnetic Sensor .......................................................................................................................27Mesh Formation Magnetic Sensor........................................................................................................272.7.3: LED Indications.................................................................................................................................272.7.4: Lock/Unlock W-GATE .....................................................................................................................31Lock/Unlock W-GATE through PC tools............................................................................................31Password Reset.....................................................................................................................................312.7.5: Weak Link Trouble Reporting...........................................................................................................32Disabling Trouble Reporting at the W-GATE Using PC Tools...........................................................322.7.6: Collapse Network Command.............................................................................................................33Collapsing Mesh Network Using PC Tools .........................................................................................33
Table of Contents6 PRELIMINARY:  Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013 2.7.7: Silence Network Command...............................................................................................................34Silencing Mesh Network Using PC Tools............................................................................................342.7.8: Multiple Wireless Sensor Network Installation Restrictions.............................................................352.7.9: Avoiding RF Interference..................................................................................................................35Section 3: Wireless Display Driver (W-DIS-D)......................................................................363.1: Description...................................................................................................................................................363.2:  Agency Approvals ......................................................................................................................................373.2.1: FCC....................................................................................................................................................373.3: Specifications...............................................................................................................................................37W-DIS-D...............................................................................................................................................37ANN-80 ................................................................................................................................................383.3.1: Environmental Specification .............................................................................................................383.4: Features........................................................................................................................................................38W-DIS-D...............................................................................................................................................38Listed to UL standard ANSI/UL 864 edition. ......................................................................................38ANN-80 ................................................................................................................................................383.5: Mounting & Wiring......................................................................................................................................393.5.1: Mounting W-DIS-D...........................................................................................................................393.5.2: Wiring................................................................................................................................................413.5.3: ANN-80 .............................................................................................................................................41Mounting ..............................................................................................................................................41Wiring ..................................................................................................................................................413.6: W-DIS-D Configuration...............................................................................................................................423.6.1: Assigning Profiles..............................................................................................................................42Assign Profile with PC Tools ...............................................................................................................42Assigning a Profile to a W-DIS-D with W-GATE or Distributor........................................................433.6.2: Mesh Formation.................................................................................................................................433.6.3: Removing Profiles .............................................................................................................................44Restoring a W-DIS-D to Factory Default Without Using the PC-based Configuration Tool..............44Restoring a W-DIS-D to Factory Default with the PC-based Configuration Tool...............................443.7: ANN-80 Configuration................................................................................................................................453.8: W-DIS-D Operations ...................................................................................................................................463.8.1: W-DIS-D Operations.........................................................................................................................46Modes of Operation Not in a Mesh Network .......................................................................................46Modes of Operation as a Mesh Participant...........................................................................................47SLC Operation......................................................................................................................................473.8.2: W-DIS-D LED Indications................................................................................................................473.8.3: Switches.............................................................................................................................................513.9: ANN-80 Operations.....................................................................................................................................523.9.1: Buttons and Switches.........................................................................................................................523.9.2: Visual Indicators................................................................................................................................533.9.3: Audible Indicators .............................................................................................................................543.9.4: Event Messaging................................................................................................................................54LCD UI Not in Network.......................................................................................................................54Mesh Formation In Progress.................................................................................................................54Low Battery Event................................................................................................................................55Trouble Jamming Event........................................................................................................................55Duplicate Address.................................................................................................................................55Degraded Connection ...........................................................................................................................56System Initialization.............................................................................................................................56System Normal .....................................................................................................................................56Tamper Event........................................................................................................................................56Weak Link ............................................................................................................................................57Key Bus Trouble...................................................................................................................................57Capacity Exceeded................................................................................................................................57Maximum Gateways.............................................................................................................................57
Table of ContentsPRELIMINARY:  Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013   73.9.5: Clearing messages .............................................................................................................................573.9.6: LED Indications.................................................................................................................................58Section 4: Devices..................................................................................................................604.1: Description...................................................................................................................................................60Subsystem Overview............................................................................................................................604.2:  Agency Approvals ......................................................................................................................................604.2.1: FCC....................................................................................................................................................604.3: Specifications...............................................................................................................................................614.4: Installing Devices ........................................................................................................................................614.5: Mounting & Wiring .....................................................................................................................................614.6: Configuration and Programming.................................................................................................................614.6.1: Assigning Profiles .............................................................................................................................62Assigning Profile Using PC Tools .......................................................................................................62Assigning a Profile to a Detector with a W-GATE or Distributor.......................................................634.6.2: Distributor Mode ...............................................................................................................................64Converting a Device into a Distributor ................................................................................................64Converting a Distributor Back into a Device .......................................................................................654.6.3: Mesh Formation.................................................................................................................................654.6.4: Restoring a Device to Factory Default..............................................................................................65Removing Profiles Without PC-based Configuration Tool..................................................................65Removing a Profile with PC Tools.......................................................................................................664.7: Device Operations .......................................................................................................................................664.7.1: Modes of Operation...........................................................................................................................66Factory Default.....................................................................................................................................66Profile Assigned ...................................................................................................................................66Bootloader ............................................................................................................................................67Distributor.............................................................................................................................................67Mesh Participant...................................................................................................................................674.7.2: LED Indications.................................................................................................................................67Section 5: USB Adapter..........................................................................................................725.1: Introduction..................................................................................................................................................725.2:  Agency Approvals ......................................................................................................................................725.2.1: FCC....................................................................................................................................................725.3: Specifications...............................................................................................................................................735.3.1:  Electrical Specifications...................................................................................................................735.3.2:  Serial Communication Specification................................................................................................735.3.3:  Mechanical Specifications................................................................................................................735.3.4: Environmental Specifications............................................................................................................735.4: Driver Installation........................................................................................................................................74Appendix A: Site Survey ........................................................................................................78A.1: Description..................................................................................................................................................78A.1.1: Conducting Site Survey at the Job Site ............................................................................................78Link Quality Test..................................................................................................................................78Results of Link Test..............................................................................................................................79Link Quality Test and RF Scan Test ....................................................................................................80Conduct a Link Test .............................................................................................................................80Results of Link Test..............................................................................................................................81Results of RF Scan Test .......................................................................................................................81Appendix B: PC tools .............................................................................................................82B.1: Description..................................................................................................................................................82B.1.1: Launching PC Tools .........................................................................................................................82B.1.2: Creating Jobsite.................................................................................................................................83B.1.3: Opening Jobsite.................................................................................................................................84
Table of Contents8 PRELIMINARY:  Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013 Appendix C: Troubleshooting and Testing..........................................................................86C.1: Troubleshooting...........................................................................................................................................86C.2: Testing W-GATE and Devices ....................................................................................................................86C.2.1: Testing LED Indications...................................................................................................................86C.3: Testing Wireless Network ...........................................................................................................................86C.3.1: Network Topology............................................................................................................................87Parent-Child Devices............................................................................................................................87Orphan Devices ....................................................................................................................................87Class A Compliance .............................................................................................................................87C.3.2: History Events...................................................................................................................................88C.3.3: Network Snapshots ...........................................................................................................................88C.3.4: Network Statistics .............................................................................................................................88C.3.5: Device Attributes ..............................................................................................................................88Index ........................................................................................................................................ 90
Table of ContentsPRELIMINARY:  Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013   9
10 PRELIMINARY: Firelite Wireless Sensor Network — P/N LS10036-000FL-E:N0  10/09/2013About This Guide PurposeSection 1: About This Guide1.1  PurposeThe Firelite Wireless Sensor Network user’s manual provides an overview of the following:• Wireless fire alarm system• Instructions for installing and configuring the wireless devices• Information on monitoring the status of the wireless devices• Removal and replacement procedures of the W-GATE and W-DIS-D• Testing, maintenance and firmware upgrade information of the W-GATE and W-DIS-D.1.2  Assumed KnowledgeThe document is created with the assumption that all users are familiar with working on a PC andlaptop for configuration purposes. Installers should be familiar with the Fire Alarm and RelatedService Standards.    The terminology and level of details of this document reflect this assumption.1.2.1  Additional References1.3  Site SurveyA site survey is recommended to assess and qualify the site prior to installing the Wireless Fire Alarm system. The site survey utility allows you to perform the Link quality test and radio fre-quency (RF) assessment of the site. This information is used for site qualification, maximum device spacing identification, and configuring the network. This helps to optimize the reliability and per-formance of the wireless network in the wireless fire alarm system. Conduct a site survey, and ensure there are no obstructions for using RF communications. For more information on a site sur-vey, refer to Appendix A:, "Site Survey".Model Description ManualW-SD355 Wireless LiteSpeed Detector, PhotoW-SD355 and W-SD355T Intelligent Wireless Photoelectric Smoke Sensors. Manual part number for the above devices- I56-4081-000W-SD355T Wireless LiteSpeed Detector, Photo/HeatW-H355R Wireless LiteSpeed Heat sensorHeat, Rate Of Rise 135 W-H355R and W-H355 and Intelligent Wireless Temperature Sensors. Manual part number for the above devices- I56-4082-000  W-H355 Wireless LiteSpeed Heat sensor Heat, Fixed Temp135W-MMF Monitor Module W-MMF Wireless Monitor Module.  Manual Part number - I56-4083-000
PRELIMINARY: Firelite Wireless Sensor Network — P/N LS10036-000FL-E:N0 10/09/2013   11Abbreviations and Meanings About This Guide1.4  Abbreviations and MeaningsThe following table lists the abbreviations and their definitions used in this manual.Abbreviation DefinitionAHJ Authority Having JurisdictionANSI American National Standards InstitutedBm Milli DecibelFACP Fire Alarm control PanelFCC Federal Communications CommissionISM Industrial, Scientific and Medical RadioBands.LCD Liquid Crystal DisplayLED Light Emitting DiodemA MilliampereMHz MegahertzNFPA National Fire Protection AssociationPC Personal ComputerRF Radio FrequencySLC Signaling Line CircuitUI User InterfaceUL Underwriters LabaratoriesW-DIS-D Wireless Display DriverW-GATE Wireless Gateway
12 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013W-GATE DescriptionSection 2: W-GATE2.1  DescriptionThe W-GATE is a device in a wireless fire system that acts as a bridge between fire alarm controlpanels and wireless fire devices. All wireless fire devices communicate with the W-GATE over thewireless network formed by the devices and the W-GATE. The Wireless Sensor Network includes a W-DIS-D (Wireless Display Driver). The W-DIS-D andANN-80 are required for the display of wireless specific events. W-DIS-D and ANN-80 areexplained in detail in Chapter 3.The W-GATE is powered by either the SLC loop or from any external 24VDC UL listed powersupply. The W-GATE uses LiteSpeed protocol on the SLC to communicate with the panel and aproprietary wireless protocol to communicate with wireless fire devices. The following graphic isan illustration of the components of the Firelite Wireless Sensor Network.Figure 2.1   Firelite Wireless Sensor Network 2.2  Agency Approvals2.2.1  FCCThis device complies with part 15 of the FCC Rules. Operation is subject to the following two con-ditions: 1. This device may not cause harmful interference, and 2. This device must accept any interference received, including interference that may cause undesired operation.FCC ID PV3WFSGWWARNING: CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY THE MANUFACTURER COULD VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   13Specifications W-GATE2.3  SpecificationsFollowing are the specifications of the W-GATE.NOTE: Devices that do not meet the minimum signal strength or have an ambient noise level that exceeds the limit are not allowed to join the mesh network.2.3.1  Environmental Specification2.4  Installing W-GATE2.4.1  Before InstallingChoose a location for the W-GATE that is clean, dry, and vibration-free. The area should be readily accessible with sufficient room to easily install and maintain the W-GATE. Metal obstructions impede the radio frequency communication and should be avoided. Carefully unpack the system and inspect for shipping damage if any. All wiring must comply with the national and local codes for fire alarm systems. Specifications DataExternal Supply Electrical Ratings 18V-30VSLC Electrical Ratings 15V-30VMaximum current when using the external supply 40mAMaximum current when using the SLC power supply 24mAMaximum SLC Resistance 50 OhmsMinimum signal strength level needed at the receiver for a primary path with weak link trouble reporting enabled.-50dBmMinimum signal strength level needed at the receiver for a secondary path or primary path with weak link trouble reporting disabled.Must be 15 dBm higher than the noise floor down to a minimum of -87dBm*Maximum ambient noise level -90dBm*Maximum RF Power Output +17dBm (Tx power level without antenna)Radio Frequency Lower ISM Band (915MHz).System Operating Temperature Storage Temperature HumidityW-GATE 0°C-49°C / 32°F-120°F -10°C- 60°C / 14°F-140°F 10 to 93% RH Non- condensing
14 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013W-GATE Mounting & Wiring2.5  Mounting & Wiring2.5.1  MountingThe W-GATE has two major pieces, the cover and the mounting plate. The mounting plate is mounted to the wall or ceiling, and field wiring is connected to it. The cover contains the PC board and is fastened to the mounting plate once the wiring is connected. Mount the mounting plate directly to an electrical box on the ceiling or wall. The plate mounts directly to 4˝ square (with and without plaster ring), 4˝ octagon, 3 1/2˝octagon, single gang or dou-ble gang junction boxes. If an electrical box is not available, the mounting plate can be mounted to any flat surface and the wiring can be connected via the knockout points in the mounting plate. To mount the W-GATE, do the following:1. Pull the wiring through the opening in the mounting plate.2. Mount the mounting plate to the junction box or ceiling. See figure 2.2.3. Connect field wiring to the terminals, as described in section 2.5.2, "Wiring".4. Connect necessary jumpers where applicable, as described in section 2.5.3, "W-GATE Powered from SLC".5. To mount the cover, align the locating pins on the cover to the corresponding slots in the mounting plate. See Figure 2.3, "Cover Attaching to Mounting Plate".6. Secure the cover by tightening the mounting screws. Figure 2.2  Mounting Plate
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   15Mounting & Wiring W-GATEFigure 2.3  Cover Attaching to Mounting Plate
16 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013W-GATE Mounting & Wiring2.5.2  Wiring• All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction.• 12-18 AWG is recommended. Figure 2.4  (Wiring diagram with terminal descriptions)For wiring connections, follow this procedure:• Strip about 3/8” of insulation from the end of the wire.• Then, to make the wire connection, slide the bare end of the wire under the appropriate clamping plate, and tighten the clamping plate screw. NOTE: Do not loop the wire under the clamping plate.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   17Mounting & Wiring W-GATE2.5.3  W-GATE Powered from SLCTo power the W-GATE using the signal line circuit, connect it as described in table 2.1 below:Figure 2.5  Wiring Connections (W-GATE powered from SLC)NOTE: It is recommended to use the same wire gauge if there are multiple connections to the same terminal.The W-GATE provides isolation of short circuits on the SLC in class A installations, that use the A6 and A7 connections as an in and out connection. A5 is common for SLC wiring that enters and leaves. Class B wiring that terminates at the W-GATE can use either the A6 or A7 connection for the SLC positive. SLC connections are power limited by the panel. An interruption in the SLC that causes a loss of power at the W-GATE for more than 100ms may result in a trouble condition and loss of fire protection provided by the wireless devices for up to 15 minutes. Using an external 24V power source (not SLC power) is recommended for installations that require fire protection in the presence of short circuits, including class A applications and applications that utilize isolator mod-ules.Terminal Pins Description A5 & A7 SLC Common & SLC Output/InputA5& A6 SLC Common & SLC Input/OutputA4 & A5 Jumper selection to enable power from the SLC supply (Insert Jumper when using SLC power)A3 UnusedA1 & A2 Jumper selection to disable power from the external supply. (Insert Jumper when using SLC power) Table 2.1
18 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013W-GATE Mounting & Wiring2.5.4  W-GATE Powered from an External +24VDC sourceTo power the W-GATE using a +24VDC source, connect the W-GATE as described in table 2.2 below.Figure 2.6  Wiring Connections -W-GATE Powered from an External +24VDC sourceNOTE: Terminal A5 is referenced more than once in the above connections. It is recommended to use wire of the same gauge for all connections to A5 and use the same wire gauge if there are multiple connections to the same terminal.The W-GATE provides isolation of short circuits of the SLC in class A installations that use the A6 and A7 as an in and out connection. A5 is common for in and out SLC wiring. Class B SLC wiring that terminates at the W-GATE can use either the A6 or A7 connection for the SLC positive. SLC connections are power limited by the panel.  24VDC must be power limited by the source.Terminal Pins Devices PoweredA5 & A7 SLC Input/outputA5 & A6 SLC Input/outputA4 UnusedA2 & A3 +24VDC input. Voltage range from 18VDC to 30VDC. Use only power limited device circuits.A1 UnusedTable 2.2
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   19Configuration and Programming W-GATE2.6  Configuration and ProgrammingThe goal of configuring and/or programming the W-GATE is to:1. Create a profile - A profile is a set of parameters that binds together a W-GATE and the devices in a mesh network. 2. Distribute the profile to every device that will be a part of the mesh.3. Form the mesh - The mesh cannot be formed until the profile is assigned to the W-GATE. The profile contains a mesh ID and, if required, a password, that are used when forming the associations. Creating and distributing the profile will enable all the devices that have that profile to form associative links when the mesh is formed. All devices, including the W-GATE, require a common profile.This section shows how to configure/program an W-GATE with a profile, how to distribute that profile to other devices, and how to form all these devices into a mesh. These processes may be per-formed with or without using PC-based configuration tool.2.6.1  Without a PC-based Configuration ToolThis section shows the configuration of the W-GATE using only a magnet and a screw driver. For configuration instructions using the PC-based configuration tool, refer to 2.6.2, "With a PC-based Configuration Tool". There are two ways to provide a W-GATE with a profile without using a configuration tool.• Create a new profile using the W-GATE• Assign a previously created profile to the W-GATE using a distributor.Create a New ProfileTo create a unique profile in the W-GATE without using the PC-based configuration tool, perform the following steps.1. Start with the device powered off.  The process is performed during the start-up. 2. Power on the W-GATE using SLC power or external +24V.  This can be done either by attaching the W-GATE to its mounting plate with the terminals already energized, or by connecting the SLC or external source wiring to a W-GATE that is already installed in its mounting plate.3. Verify if the W-GATE is in the factory default state; if it is in the factory default state, both the LEDs on the W-GATE flash red (double blink) every second for ten seconds.  If the LEDs are yellow, refer to section below on removing a profile.Figure 2.7  W-GATE with LEDs and Magnetic sensors
20 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013W-GATE Configuration and Programming4. Activate either magnetic sensor with a magnet within  ten secoands of starting up the W-GATE while the double red blink is active in the W-GATE.  (If you miss this ten-second window, power down the W-GATE and repeat step 1). The LED next to the magnetic sensor emits a red light for one second when it is activated.When the profile is successfully created, the LEDs on the W-GATE emit green light for five sec-onds (Refer to 2.7.2, "Magnet Sensor Activations" for further information on activating magnetic sensors).  A default profile has been created, containing a mesh ID, and a password. The default password is ‘12345’ and is needed if the W-GATE is locked by the FACP and later accessed by the PC-based configuration tool.  Assign a Previously Created Profile Using a DistributorTo assign an existing profile to the W-GATE (as you would do during a replacement), use the W-GATE that has the profile, or a device in the mesh that contains the profile, to distribute that profile to the W-GATE that requires it. Perform the following steps:1. Ensure that the W-GATE or other mesh device with the profile is set for distribution (Refer to 2.6.3, "Profile Distribution"" or 4.6.2, "Distributor Mode").2. Start with the device powered off.  The process is performed during the start-up. 3. Power on the W-GATE and ensure it is in the factory default state (Refer to steps 1 and 2 in the above topic, "Create a New Profile").4. Bring the profile distributor within 20 feet of the W-GATE.  5. Wait until the W-GATE blinks only a single red blink (ten seconds after startup).  6. Use a magnet to activate either of the magnetic sensors.  The LED blinks a single red every half-second indicating that it is searching for a profile.When the profile is successfully received from the distributor, the LEDs on the W-GATE emit  green light for five seconds. If the profile is rejected, the W-GATE LEDs emit red light for five sec-onds.Removing a ProfileTo remove the profile from a W-GATE, perform the following steps:1. Start with the device powered off. The process is performed during the start-up.2. Power on the W-GATE using SLC power or external +24V.  This can be done either by attaching the W-GATE to its mounting plate with the terminals already energized, or by connecting the SLC or external source wiring to a W-GATE that is already installed in its mounting plate.3. Verify the W-GATE is in the profile modification state; if it is in the profile modification state, both the LEDs on the W-GATE flash yellow (double blink) every second for ten seconds.4. Activate both the magnetic sensors within ten seconds of starting up the W-GATE (while the double yellow blink is active on the W-GATE) or repeat step 1 (If you miss the ten second window, power down the W-GATE and repeat steps 1 and 2).The W-GATE LEDs blink green every second for five seconds indicating that the profile is removed.Create Mesh NetworkMesh formation forms a wireless communication mesh around the W-GATE.  The W-GATE com-municates with all devices in range that have a common profile and establishes communication links with all the devices. Once a device joins the mesh, it acts as a repeater for devices out of the range of the W-GATE.  All devices must be in their final mounting locations prior to initiating the mesh formation.  The mesh formation is initiated and terminated by the W-GATE.To form a mesh network, ensure that the W-GATE is powered on and contains a profile.  (Refer to 2.7.3, "LED Indications" for information on how the W-GATE indicates its status).  Activate the “Mesh Formation” magnet switch on the W-GATE with a magnet.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   21Configuration and Programming W-GATEFigure 2.8  Mesh Formation Magnetic Sensor on a W-GATEThe W-GATE transitions to the mesh for-mation mode and establishes communica-tion with all the devices containing a common profile.  The blink pattern in W-GATE indicates that it is in mesh forma-tion mode. •At this stage, both the LEDs on the W-   GATE blinks twice every 3.4 seconds. •The first blink is green and the second  blink is red when the W-GATE is acting  as a profile distributor and forming the mesh. • The first blink is green and the second blink is yellow when the W-GATE is only forming the mesh. Mesh formation typically takes one minute for each device in the mesh. Mesh formation automati-cally terminates 10 minutes after the last device joins the mesh.  The mesh formation can be termi-nated manually by the user by activating the mesh formation magnetic sensor again. Once the mesh formation is complete, the network transitions to optimize the mesh. For further operating instructions, refer to 2.7, "Operations".2.6.2  With a PC-based Configuration ToolAssign Profile with PC ToolsTo assign a profile to the W-GATE using the PC Tools application, do the following:1. Connect the W-USB dongle device to your computer.  For more information on USB dongle, refer to Section 5:, "USB Adapter".2. Launch the PC Tools application.  Refer to Appendix B:, "PC tools" to know about launching the PC Tools application.3. Go to the Create Mesh Network step.4. Create a new profile or import an existing profile as required.5. Select and open the profile to be assigned to the W-GATE from the Name drop-down list in the left panel.6. Power on the W-GATE in range of the PC Tools.
22 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013W-GATE Configuration and Programming7. Select the W-GATE from the Communicator panel.8. Click Assign.The W-GATE is now included in the list of devices with a profile assigned.Removing Profile with PC ToolsTo remove a profile in a W-GATE using the PC Tools application, do the following:1. Connect the W-USB dongle device to your computer.  For more information on USB dongle, refer to Section 5:, "USB Adapter".2. Launch the PC Tools application.  Refer to Appendix B:, "PC tools" to know about launching the PC Tools application.3. Go to Site Survey, Create Mesh Network, or Diagnostics step.4. Click Extras and select Reset Devices. The Reset Devices screen appears, displaying the W-GATE and other devices that have a profile assigned.5. Click to select the W-GATE and click Reset Device to remove the profile.The profile is removed and the W-GATE is reset to factory default state.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   23Configuration and Programming W-GATEMesh Formation with PC ToolsTo create a mesh network using the PC Tools, perform the following steps.1. Connect the W-USB dongle device to your computer. For more information on USB dongle, refer to Section 5:, "USB Adapter".2. Launch the PC tools application.  Refer to Appendix B:, "PC tools" to know about launching the PC tools application.3. Go to Create Mesh Network step.4. Navigate to the second step of Create Mesh Network by clicking    on top of the screen.5. Click to select the W-GATE displayed in the Gateways in Range table, and click 'Start Mesh Formation'.When the mesh is formed, the tool helps you to track the number of devices that have joined the mesh, and view the progress. The mesh formation terminates 10 minutes after the last device joins the mesh.  In addition, it can be terminated by the user by clicking Stop Mesh Formation.Once mesh formation is complete, the network transitions to optimize the mesh. For further operat-ing instructions, refer to 2.7, "Operations".2.6.3  Profile DistributionThere are two ways to initiate profile distribution from the W-GATE.  • Automatically after creating a profile, • Activating the profile creating magnetic sensor when it has a profile.  After Creating a Profile  Profile distribution is automatically enabled from the W-GATE after creating a profile.  The profile distribution automatically terminates after 10 minutes. Activating the Profile Magnetic Sensor When it has a Profile  Activating the profile magnetic sensor while it has profile will put the W-GATE in a mode of distributing the profile to any device that requests a profile. The W-GATE’s LED pattern will be altered when it is distributing a profile for easy identification.  Profile distribution will automatically terminate after 10 minutes. For more information on W-GATE LED patterns, refer to the table in 2.7.3, "LED Indications". Figure 2.9   Profile MagneticSensor on a W-GATE
24 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013W-GATE Configuration and Programming2.6.4  SLC ConfigurationThe W-GATE,• Communicates with the control panel via the SLC circuit. • Is a LiteSpeed only device. • CLIP mode is not supported.  • FACPs have limited support for displaying all troubles from the wireless device, and requires the use of an ANN-80 for event details.  Refer to the appropriate section below for configuration steps.Three consecutive SLC addresses are used for a W-GATE.  Set the base address using the rotary dials on the W-GATE prior to installation. Ensure the address and the next two addresses on the SLC loop are available.The base address uses the following configuration parameters:• Module Type: Monitor• Type Code Label: MonitorThe W-GATE does not cause any alarms at this address, but the point is used for supervision of the W-GATE.  The base address +1 uses the following configuration parameters:• Module Type: Monitor• Type Code Label: TamperThis address is a latching supervisory condition that goes active whenever a wireless detector in the mesh is removed from its base or a module has its cover plate removed (tamper). This point does not show the address of the tampered device. The ANN-80 displays the device address information.The base address +2 uses the following configuration parameters:• Module Type: Monitor• Type Code Label: Trouble MonThis address is a tracking trouble condition that goes active whenever a wireless device in the mesh is in a trouble condition. Refer to 3.9.4, "Event Messaging"for the message displayed at the ANN-80 for the trouble event.The specific address and trouble condition is displayed on the ANN-80.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   25Operations W-GATE2.7  Operations2.7.1  W-GATE Modes of OperationFigure 2.10  W-GATE Modes Of OperationStart UpStartup is a temporary mode of operation. It is during the startup mode, that a profile can be created or removed. The startup period lasts for 10 seconds. If a particular unit contains a profile, the LEDs blink yellow twice every second. If the unit does not contain a profile, the LEDs blink red twice every second.  During startup, the W-GATE does not provide fire protection. After startup, the W-GATE  proceeds to the factory default state if a profile was removed or miss-ing.  In the presence of a profile, the W-GATE will proceed to mesh formation if it was previously part of a mesh network or normal mode if it was not previously part of a mesh network. The W-GATE does not respond to the panel during startup.   All the three SLC addresses will be an INVALID REPLY.Factory DefaultFactory default is the initial state of the W-GATE. The W-GATE and peripheral devices do not pro-vide any fire protection when they are in factory default mode. The W-GATE does not communi-cate with wireless devices. The only wireless communication is with the configuration tool. The configuration tool needs to be within 20 feet of the W-GATE for communication. The W-GATE needs to be assigned a profile before continuing the installation.The W-GATE reports “Factory Default” to the communicator display of the PC Tools application.The W-GATE’s base address will be normal and the supervisory point (base address + 1) will also be normal.  The trouble point (base address + 2) will indicate open circuit.Profile ConfiguredThe W-GATE enters the profile configured mode after getting assigned a profile from the tool or a distributor or creating a profile.  Profile configured is a temporary mode before the W-GATE transi-tions to mesh formation or normal mode.  The W-GATE does not provide fire protection in the profile configured mode.  The W-GATE reports “Profile Assigned” to the communicator display of the PC Tools application.The W-GATE’s base address will be normal and the supervisory point (base address + 1) will also be normal.  The trouble point (base address + 2) will indicate open circuit.
26 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013W-GATE OperationsMesh FormationThe W-GATE must have a profile before entering mesh formation. The W-GATE and the peripheral devices do not provide any fire protection in mesh formation. The W-GATE automatically enters mesh formation in the following ways:• After creating a profile using the mesh formation sensor.• After activating the mesh formation sensor with a magnet when the W-GATE contains a profile.• Automatically after startup when the W-GATE previously was part of a mesh• By command from the PC Tools application A W-GATE in mesh formation mode instructs all devices in the mesh to also transition to mesh for-mation. The W-GATE and all communicating devices search for new or lost devices with the same profile to join the network.If the W-GATE automatically entered mesh formation after startup, then mesh formation terminates after all existing devices are recovered.  If new devices are found or if mesh formation was initiated by the user, then mesh formation terminates after a period of 10 minutes without any new devices joining the mesh. At any point Mesh formation can be terminated by user interaction by activating the magnet sensor again, or by using the PC Tools application.The W-GATE reports “Mesh Formation” to the communicator display of the PC Tools application.The W-GATE’s base address will be normal and the supervisory point (base address + 1) will also be normal.  The trouble point (base address + 2) will indicate open circuit.Initial Mesh OptimizationThe initial mesh optimization mode automatically runs after each mesh formation. The W-GATE and peripheral devices do not provide fire protection during the initial mesh optimization.  Mesh optimization analyzes the signal strengths between devices.  The W-GATE designates the primary and secondary communication paths between devices that provide a redundant path for all trans-missions. Mesh Optimization terminates automatically once all devices have a redundant commu-nication path and signal strengths that meet the requirements of primary and secondary transmission paths.  Any device that does not have a redundant path or meet the requirements for signal strength will report a fault.The W-GATE reports “Optimization” to the communicator display of the PC tools application.The W-GATE’s base address will be normal and the supervisory point (base address + 1) will also be normal.  The trouble point (base address + 2) will indicate open circuit.Normal ModeNormal mode can be described as a standard operating state. The mesh network is formed, provid-ing fire protection.  The mesh network continuously searches for additional devices with a match-ing profile to join the mesh.  To avoid interference, the mesh network periodically checks for adjacent mesh networks created by Honeywell.  The W-GATE reports “Normal” to the communica-tor display of the PC Tools application.Rescue ModeDuring normal mode, when a device loses communication to the network, the W-GATE triggers rescue mode in all communicating devices. All devices in communication continue to provide fire protection during rescue mode, but also searches for a lost or added device. The rescue mode termi-nates automatically 6 minutes after the last device is rescued and returns to the normal mode.  The W-GATE reports “Rescue” to the communicator display of the PC Tools application.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   27Operations W-GATEMesh OptimizationIn addition to the initial mesh optimization, the routine executes after any restoration of communi-cation to a device or to recover from a link failure (class A fault).  Mesh optimization that occurs during the normal mode does not generate a trouble and provides fire protection from all devices that are participating in the mesh communication. The W-GATE reports “Optimization” to the com-municator display of the PC Tools application.BootloaderThe W-GATE enters the bootloader mode when it is being updated using the PC Tools application.  The W-GATE does not communicate with the FACP during bootloader mode.  The W-GATE reports “Bootloader” to the communicator display of the PC Tools application.2.7.2  Magnet Sensor ActivationsProfile Magnetic SensorThe profile magnetic sensor (Figure 2.9, "Profile Magnetic Sensor on a W-GATE") is used to create a unique profile on startup.  It can also be used to start profile distribution for a W-GATE that con-tains a profile.  The LED next to the profile magnet sensor emits solid red light for ½ a second when the sensor is activated.Mesh Formation Magnetic SensorThe mesh formation magnetic sensor (Figure 2.8, "Mesh Formation Magnetic Sensor on a W-GATE") toggles the W-GATE, in and out of mesh formation mode. The initial activation of the sen-sor puts the W-GATE in mesh formation mode (as long as it contains a profile). A subsequent acti-vation of the magnetic sensor toggles the W-GATE out of mesh formation and into the initial mesh optimization and normal mode. The W-GATE can be placed back into mesh formation by activat-ing the magnet sensor once again.  The Mesh formation magnetic sensor can also be used to create a profile on startup for a W-GATE that does not already contain a profile.The LED next to the mesh formation magnetic sensor emits solid red light for ½ a second when the sensor is activated. 2.7.3  LED IndicationsThe two LEDs on the W-GATE blink in the same pattern to allow the LED to be viewed from any angle.  The LED indications are provided in the table below.
28 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013W-GATE OperationsDuration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M30Condition Action RequiredDevice is ready to updateLED PatternProle removed Gateway has returned to the factory default stateMesh formation Gateway is forming the mesh & looking for devices that are not in the meshWait until all devices join the mesh, and then terminate mesh forma-tionUse PC based congura-tion tool to initiate the downloadMesh formation with prole distributionGateway is forming the mesh & looking for devices that are not in the mesh.  The gateway is also distributing a prole to any device that requests a proleWait until all devices join the mesh, and then terminate mesh forma-tionApp eraseApp loadingNew application code is being downloaded77251414Normal Mode / Background mesh optimiza-tionNormal operation of the gatewayNormal Mode/Back-ground mesh optimization with prole distributionNormal operation of the gateway.  The gateway is also distributing a prole to any device that requests a proleProle accepted Gateway is now prole assigned5Rescue Mode Gateway and the mesh network are searching for any device that is not in the mesh network with the same prole76MBootloader5
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   29Operations W-GATEDuration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M307Rescue Mode with prole distributionGateway and the mesh network are searching for any device that is not in the mesh network with the same prole.  The gateway is also distributing a prole to any device that requests a proleProle assigned; pending hall sensor activationsstarting up with a prole Activate both hall sensors simultaneously within 10 seconds to remove a prole1st mesh optimizationMesh is formed and initializingEnsure all devices in the mesh have a valid address.710 16M15MCondition Action RequiredLED Pattern741414Refer to the panel to identify the trouble and possible resolution1st mesh optimization with prole distribu-tionMesh is formed and initializing.  The gateway is also distributing a prole to any device that requests a proleGeneric Trouble The gateway has a trouble condition.Refer to the panel to identify the trouble and possible resolutionGeneric Trouble with prole distributionThe gateway has a trouble condition. The gateway is also distribut-ing a prole to any device that requests a prole.Ensure all devices in the mesh have a valid address.Address Trouble The gateway is in a dual address condition with another wireless module in the mesh or there is a device in the mesh set to address 0.15MDuration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M307Rescue Mode with prole distributionGateway and the mesh network are searching for any device that is not in the mesh network with the same prole.  The gateway is also distributing a prole to any device that requests a proleProle assigned; pending hall sensor activationsstarting up with a prole Activate both hall sensors simultaneously within 10 seconds to remove a prole1st mesh optimizationMesh is formed and initializingEnsure all devices in the mesh have a valid address.710 16M15MCondition Action RequiredLED Pattern741414Refer to the panel to identify the trouble and possible resolution1st mesh optimization with prole distribu-tionMesh is formed and initializing.  The gateway is also distributing a prole to any device that requests a proleGeneric Trouble The gateway has a trouble condition.Refer to the panel to identify the trouble and possible resolutionGeneric Trouble with prole distributionThe gateway has a trouble condition. The gateway is also distribut-ing a prole to any device that requests a prole.Ensure all devices in the mesh have a valid address.Address Trouble The gateway is in a dual address condition with another wireless module in the mesh or there is a device in the mesh set to address 0.15M
30 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013W-GATE OperationsDuration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M304Ensure all devices in the mesh have a valid address.Address Trouble with prole distributionThe gateway is in a dual address condition with another wireless module in the mesh or there is a device in the mesh set to address 0.  The gateway is also distributing a prole to any device that requests a prole.Condition Action RequiredLED PatternFactory default; pending hall sensor activationStarting up without a proleActivate either hall sensors within 10 seconds to create a default prole Waiting for proleGateway is factory default Use PC tool to assign prole or activate switch to search for proleSearching for proleGateway is factory default and requesting a prole from a distributor or another gatewayProle rejected; incompatible deviceThere is a mismatch between the prole and the gateway.  Recreate the prole or update the gatewayCreate prole Gateway is creating a default prole15110100.51MDuration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M304Ensure all devices in the mesh have a valid address.Address Trouble with prole distributionThe gateway is in a dual address condition with another wireless module in the mesh or there is a device in the mesh set to address 0.  The gateway is also distributing a prole to any device that requests a prole.Condition Action RequiredLED PatternFactory default; pending hall sensor activationStarting up without a proleActivate either hall sensors within 10 seconds to create a default prole Waiting for proleGateway is factory default Use PC tool to assign prole or activate switch to search for proleSearching for proleGateway is factory default and requesting a prole from a distributor or another gatewayProle rejected; incompatible deviceThere is a mismatch between the prole and the gateway.  Recreate the prole or update the gatewayCreate prole Gateway is creating a default prole15110100.51M
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   31Operations W-GATE2.7.4  Lock/Unlock W-GATEThe W-GATE can be locked to prevent access to the magnetic sensors and to password-protect all wireless interactions.  The lock function can be performed by the PC tool.  When the PC tool is used to lock the W-GATE, a password must be provided for all future interactions, including unlocking the W-GATE. If the W-GATE was previously locked with a password from the PC tools, the previous password will be applied. Use this password for all future interactions from the PC Tools application. Lock/Unlock W-GATE through PC toolsTo lock/unlock the W-GATE, perform the following steps.1. Connect the W-USB dongle device to your computer. For more information on USB dongle, refer to Section 5:, "USB Adapter".2. Launch the PC tools application.  Refer to Appendix B:, "PC tools" to know about launching the PC tools application.3. Go to Site Survey, Create Mesh Network, or Diagnostics step.4. Click Extras. The following screen is displayed. 5. Select Lock/Unlock Gateway.6. To lock or unlock the gateway, click Lock or Unlock as required.•Lock - The Lock Gateway screen is displayed.  Create a password and click Lock.  The gateway is locked.•Unlock - The Enter password for Gateway screen is displayed.  Enter the password and click Unlock.  The W-GATE is unlocked.Password Reset To reset the password, contact technical support.
32 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013W-GATE Operations2.7.5  Weak Link Trouble ReportingThe Firelite Wireless Sensor Network uses two paths of communication for each device.  To estab-lish the link between devices as a viable communication path, the signal strengths must meet the limits provided in 2.3, "Specifications".  The Wireless Sensor Network implements a higher thresh-old for primary connections to provide an extra layer of robustness and immunity from interfer-ence.  A weak link trouble condition is initiated for any device that does not have at least one connection at the primary threshold.  This is an optional setting that can be disabled to ignore the weak link trouble condition.  The trouble can be disabled at the W-GATE.Disabling Trouble Reporting at the W-GATE Using PC ToolsTo disable trouble reporting at the W-GATE through PC tools, perform the following steps:1. Connect the W-USB dongle device to your computer. For more information on USB dongle, refer to Section 5:, "USB Adapter".2. Launch the PC tools application.  Refer to Appendix B:, "PC tools" to know about launching the PC tools application.3. Go to Diagnostics step.4. Choose the W-GATE from the communicator pane.5. Click View Mesh.6. Click Advanced Functions.  A drop-down list is displayed.7. Click Weak links troubles (On).  The Report weak links troubles screen is displayed.8. Click Turn off reporting.  The trouble reporting is disabled.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   33Operations W-GATE2.7.6  Collapse Network CommandThe collapse command is a diagnostic function to break the mesh network. All devices will retain the profile information but will be removed from the mesh. The mesh can be immediately reformed by activating mesh formation.CAUTION: FIRE PROTECTION FROM WIRELESS DEVICES WILL BE LOST WHEN A COLLAPSE COMMAND IS ISSUED.The mesh network can be collapsed using the PC-based configuration tool.Collapsing Mesh Network Using PC ToolsTo collapse the mesh network using the PC based configuration tool, perform the following steps:1. Connect the W-USB dongle device to your computer. For more information on USB dongle, refer to Section 5:, "USB Adapter".2. Launch the PC tools application.  Refer to Appendix B:, "PC tools" to know about launching the PC tools application.3. Go to Diagnostics step.4. Select a Gateway from the communicator pane.5. Click View Mesh. The mesh is displayed.6. Click Advanced Functions   on top of the mesh display.  A drop down list is displayed.7. Click Collapse Mesh. The Collapse mesh network screen is displayed.8. Click Yes.  The network is collapsed and a confirmation is displayed as shown below.
34 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013W-GATE Operations2.7.7  Silence Network CommandThe silence network command is a diagnostic function to turn off all radio communication from the wireless devices for the set amount of time. All devices will retain the profile information but will be removed from the mesh. The devices will not send or receive any wireless communication until the set time expires or the device is rebooted. The mesh network can be reformed at the end of the silence period or after the device is restarted. CAUTION: FIRE PROTECTION FROM WIRELESS DEVICES WILL BE LOST WHEN A SILENCE COMMAND IS ISSUEDThe mesh network can be silenced using the PC-based configuration tool.Silencing Mesh Network Using PC ToolsTo silence the mesh network using the PC based configuration tool, perform the following steps:1. Connect the W-USB dongle device to your computer. For more information on USB dongle, refer to Section 5:, "USB Adapter".2. Launch the PC tools application.  Refer to Appendix B:, "PC tools" to know about launching the PC tools application.3. Go to Diagnostics step.4. Select a Gateway from the communicator pane.5. Click View Mesh.  The mesh is displayed.6. Click Advanced Functions  on top of the mesh display. A dropdown list is displayed.7. Click Silence Devices. The Silence mesh network screen is displayed.8. Select the time interval to silence the wireless devices from the dropdown list and click Yes.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   35Operations W-GATE9. Enter the Verification Password in the Gateway Password screen. The network is silenced and confirmation is displayed as shown below.2.7.8  Multiple Wireless Sensor Network Installation RestrictionsFirelite’s Wireless Sensor Network technology shares the RF spectrum with other Honeywell Wire-less Sensor Network systems.  Honeywell has established a limit of 4 overlapping networks to avoid congestion in the RF spectrum.  If the limit of overlapping systems is exceeded, a system trouble will be generated for the system that detects 4 or more adjacent networks.  To resolve this situation, the instances of overlap need to be removed.  Refer to Appendix C:, "Troubleshooting and Testing"for suggestions on removing overlap between wireless networks.  The trouble will be self restoring up to 36 hours after the condition is resolved.  To expedite the trouble resolution, tog-gle the network that is reporting the trouble in and out of mesh formation mode. 2.7.9  Avoiding RF InterferenceThe Firelite wireless mesh network uses radio frequency hopping spread spectrum technology to communicate in the 900 MHz ISM band (902MHz to 928MHz). Other commercial and industrial products also operate in this band. If two-way radios or other wireless communication devices are used during the installation process it is recommended that they be kept at least 4 feet away fromthe Firelite wireless devices or that they operate on a different frequency band to ensure rapid mesh formation. A properly installed Firelite wireless mesh network with primary link reporting enabled will be highly immune to RF interference from other wireless products even when they are nearby. The use of the primary link reporting feature is highly recommended. If the system is installed in a controlled environment where other 900 MHz ISM band devices will not be present, the primary link reporting feature may be disabled to permit greater distances between installed devices if required. The Firelite wireless mesh network will be able to automatically detect and avoid certain types of in-band channel interference (often caused by two-way radios) by using an alternate chan-nel set.  The system will log detection and avoidance of this kind interference in the W-GATE his-tory as "Walkie Talkie Mode" Entry or Exit and in the NFS2-3030 history as Alternate Channel Set or Normal Channel Set.
36 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Wireless Display Driver (W-DIS-D) DescriptionSection 3: Wireless Display Driver (W-DIS-D)This section describes the wireless user interface display driver and how it is connected to the ANN-80. In addition, this section provides information on how to install, configure and monitor the messages on the ANN-80.3.1  DescriptionThe W-DIS-D and ANN-80 are required for the display of wireless specific events.Figure 3.1  The W-DIS-D is a part of the wireless network and has a specific SLC module address. The W-DIS-D and ANN-80 display the wireless specific events that cannot be displayed on the FACP.These wireless events are related to the trouble and supervisory conditions that are specific to theW-GATE and devices. The wireless events are indicated at the FACP as a generic trouble or asupervisory event via the W-GATE utilizing the base address +1 and the base address +2 for super-visory and trouble events respectively. The specific event details are sent to the ANN-80 via anEIA-485 communication line from the W-DIS-D. The following conditions lead to the trouble andsupervisory events.Trouble Events• Jamming (device communication loss due to RF interference)• Duplicate address•Battery low• Class A missing second link• Weak link low signal strength• Mesh Optimization• Wireless mesh formation in progress• RF comm loss• Illegal address
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   37Agency Approvals Wireless Display Driver (W-DIS-D)• Maximum Gateway• Maximum devicesSupervisory Event• Tamper3.2   Agency Approvals3.2.1  FCCThis device complies with part 15 of the FCC Rules. Operation is subject to the following two con-ditions: 1. This device may not cause harmful interference, and 2. This device must accept any interference received, including interference that may cause undesired operation.FCC ID PV3WFSLCDUIWARNING: CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY THE MANUFACTURER COULD VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.3.3  SpecificationsW-DIS-DThe following are the specifications for the W-DIS-D device.NOTE: All connections are power limited and supervised.Specification DataOperating Voltage Range 18VDC to 30VDCMaximum current draw 30 mAANN-BUS Driver: 1.5V - 3.4V and 60 mA max.Receiver: 0.2V - 6VRadio Frequency Lower ISM band (915 MHz)Maximum power output +17 dBmMinimum signal strength level needed at the receiver for a primary path with weak link reporting enabled-63 dBmMinimum signal strength level needed at the receiver for a secondary path (minimum signal to noise point) or a primary path with weak link trouble reporting disabledMust be 15 dBm higher than the noise floor down to -87dBmTable 3.1  W-DIS-D specifications
38 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Wireless Display Driver (W-DIS-D) FeaturesANN-80Table 3.2  ANN-80 SpecificationsNOTE: All connections are power limited and supervised.3.3.1  Environmental Specification3.4  FeaturesW-DIS-DThe W-DIS-D has the following features.Listed to UL standard ANSI/UL 864 edition.ANN-80The ANN-80 has the following features.• Listed to UL standard ANSI/UL 864 edition. • Control switch ACK for acknowledging the piezo.• Scrolling keys to scroll up or down when there are multiple events.• Enclosure supervised for tamper.• LEDs  for trouble and supervisory events.• Surface mount directly to wall or single, double or 4” square junction box. Specification DataOperating Voltage Range(TB1 Terminals 1 & 2)18VDC to 28VDCMaximum current drawn Normal / Standby (no activity): 37.0 mAtrouble condition: 39.0 mATBI Terminals 3 & 4 ANN-BUS Driver: 1.5V - 5.5V and 60 mA max.Receiver: 0.2V - 6VDimensions 6 7/8”Wx 5 3/8”H x 1 3/8”DSystem Operating Temperature Storage Temperature HumidityW-DIS-D 0°C-50°C -10°C-50°C 10 to 93% RH Non condensing
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   39Mounting & Wiring Wireless Display Driver (W-DIS-D)3.5  Mounting & Wiring3.5.1  Mounting W-DIS-DWARNING:  ENSURE THAT THE FORMEX SHEET INSIDE THE W-GATE IS NOT REMOVED OR TAMPERED WHILE INSTALLING OR CLEANING.The W-DIS-D has two major pieces, the cover and the mounting plate. The mounting plate is mounted to the wall or ceiling and field wiring is connected to it. The cover contains the PC board and is fastened to the mounting plate once the wiring is connected. Mount the mounting plate directly to an electrical box on the ceiling or wall. The plate mounts directly to 4˝ square (with and without plaster ring), 4˝ octagon, 3 1/2˝octagon, single gang or dou-ble gang junction boxes. If an electrical box is not available, the mounting plate can be mounted to any flat surface and the wiring can be connected via the knockout points in the mounting plate. To mount the W-DIS-D, do the following:1. Pull the wiring through the opening in the mounting plate.2. Mount the mounting plate to the junction box or ceiling. See figure 3.2.3. Connect field wiring to the terminals, as described in 3.5.2, "Wiring".4. Connect necessary jumpers where applicable. Refer to section 2.5.3, "W-GATE Powered from SLC".5. To mount the cover, align the locating pins on the cover to the corresponding slots in the mounting plate. See Figure 3.3, “Cover Attaching to Mounting Plate” .Secure the cover by tightening the mounting screws.Figure 3.2  Mounting Plate
40 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Wireless Display Driver (W-DIS-D) Mounting & WiringFigure 3.3  Cover Attaching to Mounting Plate
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   41Mounting & Wiring Wireless Display Driver (W-DIS-D)3.5.2  Wiring• All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction.• 12-18 AWG is recommended. Figure 3.4  Wiring Diagram with Terminal DescriptionsFor wiring connections, follow this procedure:• Strip about 3/8” of insulation from the end of the wire. • Then, to make the wire connection, slide the bare end of the wire under the appropriate clamping plate, and tighten the clamping plate screw. 3.5.3  ANN-80MountingThe ANN-80 has to be mounted next to the Fire Alarm Control Panel. For further instructions on mounting and wiring of ANN-80, refer to ANN-80-series product installation document.Wiring Table 3.3  ANN-80 series to power sourceANN-80 Series Terminals (TB1) ANN-BUS TerminalsTerminal 1 (-) External power groundTerminal 2 (+) External power 24VDCTerminal 3 (A) A (ANN-BUS)Terminal 4 (B) B (ANN-BUS)
42 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Wireless Display Driver (W-DIS-D) W-DIS-D ConfigurationNotes•12-18 AWG wire for must be used for the 24VDC circuit.•The maximum wiring distance is 6000 ft.The ANN-80 and ANN-BUS requires 24VDC power supply; powered by 24VDC from the host FACP or by remote power supply. NOTE: Installation and wiring must be done in accordance with the NFPA 72 and local ordinances.3.6  W-DIS-D ConfigurationThe configuration of a W-DIS-D starts with assigning a profile. There are two ways to assign a pro-file.• Assign profiles using PC Tools.• Assign profile to a W-DIS-D with W-GATE or Distributor.NOTE: To assign a profile, the W-DIS-D must be in a factory default state. This is confirmed by a single red light that flashes on the LED. To restore the W-DIS-D to factory default state, refer to section 3.3.33.6.1  Assigning Profiles Assign Profile with PC ToolsTo assign a profile to the W-DIS-D using the PC Tools application, do the following:1. Connect the W-USB dongle device to your computer.  For more information on USB dongle, refer to Section 5:, "USB Adapter".2. Launch the PC Tools application.  Refer to Appendix B:, "PC tools" to know about launching the PC Tools application.3. Go to the Create Mesh Network step.4. Create a new profile or import an existing profile as required. 5. Select and open the profile to be assigned to the W-DIS-D from the Name drop-down list in the left panel.6. Switch on the W-DIS-D in range of the USB adapter, which is connected to the laptop or PC where PC tool is installed.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   43W-DIS-D Configuration Wireless Display Driver (W-DIS-D)7. Select the W-DIS-D from the Communicator panel.  The W-DIS-D is listed by its generic name, “LCD UI”.8. Click Assign.The W-DIS-D is now included in the list of devices with a profile assigned. When the profile is assigned, the LED emits a solid green light for 10 seconds.Assigning a Profile to a W-DIS-D with W-GATE or DistributorA W-GATE that has a profile can be used to distribute the profile to a W-DIS-D. The W-GATE must be in a state where it can distribute a profile.  For further information on profile distribution from a W-GATE, refer to 2.6.3, "Profile Distribution".  A device that has a profile can be used to distribute the profile by using distributor mode.  For more information on distributor mode of a device refer to 4.6.2, "Distributor Mode".To transfer profile from W-GATE/distributor to W-DIS-D, do the following:1. Bring the W-DIS-D within the range of the W-GATE or the distributor device.2. Power on the W-DIS-D. Ensure the W-DIS-D is in the factory default state. A single or double red light flashes on the LED confirming that the W-DIS-D is in the default state. 3. Activate either magnet sensors to make the W-DIS-D request the profile. Once a magnet sensor is activated, the LED flashes red light every half second indicating that it is requesting a profile. If the profile is successfully received, the LED emits a solid green light for 10 seconds. If the profile is not received within a minute, the LED flashes a red light every ten seconds indicating that it has stopped requesting for a profile. 3.6.2  Mesh FormationTo add a W-DIS-D to a mesh, refer to , "Mesh Formation with PC Tools" or “, "Mesh Formation".
44 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Wireless Display Driver (W-DIS-D) W-DIS-D Configuration3.6.3  Removing ProfilesRestoring a W-DIS-D to Factory Default Without Using the PC-based Configuration ToolTo remove a profile from a W-DIS-D without using the PC-based configuration tool, perform the following steps:1. Start with the device powered off. The process is performed during the start-up2. Power on the W-DIS-D using external +24V.  This can be done either by attaching the W-DIS-D to its mounting plate with the terminals already energized, or by connecting the external source wiring to a W-DIS-D that is already installed in its mounting plate.3. Verify the W-DIS-D is in the profile modification state; if it is in the profile modification state, both the LEDs on the W-DIS-D flash yellow (double blink) every second for ten seconds.4. Activate both the magnetic sensors within ten seconds of starting up the W-DIS-D (while the double yellow blink is active in the W-DIS-D) or repeat step 1.5. The W-DIS-D LEDs blink green every second for five seconds indicating that the profile is removed.NOTE: After following the above steps, the profile is erased and the device returns to factory default state. This is indicated by five green blinks every 0.5 seconds.Restoring a W-DIS-D to Factory Default with the PC-based Configuration ToolTo restore a W-DIS-D to factory default state with the PC-based configuration tool, perform the fol-lowing steps:1. To remove a profile in a device using the PC Tools application, do the following:2. Connect the W-USB dongle device to your computer.  For more information on USB dongle, refer to Section 5:, "USB Adapter".3. Launch the PC Tools application.  Refer to Appendix B:, "PC tools" to know about launching the PC Tools application.4. Go to Site Survey, Create Mesh Network or Diagnostics step.5. Click Extras and select Reset Devices. The Reset Devices screen appears, displaying the W-DIS-D and other devices that have the profile assigned.6. Click to select the required device and click Reset Device to remove the profile.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   45ANN-80 Configuration Wireless Display Driver (W-DIS-D)The profile is removed and the device is reset to factory default state.3.7  ANN-80 ConfigurationTo configure the ANN-80, set the serial address of ANN-80 to 1 when it is connected to W-DIS-D. To set the serial address of the ANN-80, refer to the ANN-80 series product installation document.
46 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Wireless Display Driver (W-DIS-D) W-DIS-D Operations3.8  W-DIS-D OperationsTable 3.4 outlines the wireless related events and the location of display.Table 3.4  Event Display Location TableNOTE: One W-DIS-D is required for one W-GATE. Multiple W-GATE installations require a W-DIS-D for each W-GATE.3.8.1  W-DIS-D OperationsModes of Operation Not in a Mesh NetworkBootloaderIn this mode, the W-DIS-D cannot participate in a mesh and cannot provide fire protection. The W-DIS-D will be available in the communicator window of the PC Tool with a status “Bootloader”.  To get a device out of bootloader, refer to the troubleshooting section.Factory DefaultIn this mode, the W-DIS-D is  not associated with the W-GATE. For further information on assign-ing a profile, refer to section 3.6.1.  In this mode, the W-DIS-D will be viewable in the communica-tor window of the PC tool with a state of “Factory Default”.  The ANN-80 will display RF COMM LOSS when the W-DIS-D is at Factory Default state. Events FACP AnnunciatorAlarm (Detector or Module activations)YES (Address specific to the initiating device)NO (No Display)Tamper YES (Generic Supervisory at GW +1 address)YES (Detailed display with SLC address)RF related trouble conditions -  Jamming, Battery Low, Duplicate address, Class-A missing second link, Weak link low signal strength. YES (Generic Trouble GW +2 address)YES (Detailed display with SLC address)Wireless Device Missing from networkYES (No Answer/Invalid response for the specific SLC Address)NOW-GATE initializing, wireless mesh formation in progress. YES (Generic Trouble GW +2 address)YES (no address specified)Illegal address YES (Generic Trouble GW +2 address)YES (address zero)Mesh capacity exceeded YES (Generic Trouble GW +2 address)YES (W-GATE base address)RF comm loss YES (No Answer/Invalid response for the W-DIS-D SLC Address)YESNormal None  Mesh ID number
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   47W-DIS-D Operations Wireless Display Driver (W-DIS-D)Profile ConfiguredIn this mode, the W-DIS-D is associated with the W-GATE but is not an active participant in the mesh network. For further information on mesh formation, refer to, “4.6.3, "Mesh Formation".  To remove a profile from a W-DIS-D, refer to section, “3.6.3, "Removing Profiles".In this mode, the W-DIS-D will be viewable in the communicator window of the PC tool  with a state of profile configured.  The ANN-80 will display RF COMM LOSS when the W-DIS-D is at factory default state.Modes of Operation as a Mesh ParticipantMesh Formation ModeIn this mode, the W-DIS-D is an active participant in a mesh that is forming. The LED flashes in the following pattern: First blink green, second blink yellow for every 6.8 seconds.  For further information on mesh formation mode, refer to, “4.6.3, "Mesh Formation".  The W-DIS-D will not communicate directly with the tool for display in the communicator.  The status of the W-DIS-D must be obtained via the W-GATE.  The ANN-80 will display ‘Mesh Formation in Progress’ during mesh formation mode.Initial Mesh Optimization ModeIn this mode, the mesh network is formed and is in the process of establishing stronger communica-tion paths. The LED pattern flashes in the following pattern: A single yellow blink every 6.8 sec-onds.  For further information on initial mesh optimization mode, refer to the topic, "Initial Mesh Optimization".   The W-DIS-D will not communicate directly with the tool for display in the com-municator.  The status of the W-DIS-D must be obtained via the W-GATE.  The ANN-80 will dis-play Gateway Initializing during the initial mesh optimization mode. Normal ModeIn this mode, the mesh network formation is complete. The LED flashes in the following pattern: A single green blink every 13.6 seconds. The LED flash can be disabled by panel configuration. If a device is in trouble, it will be displayed at the ANN-80 or the FACP.  For information, refer to 3.9.4, "Event Messaging".  The W-DIS-D will not communicate directly with the tool for display in the communicator.  The status of the W-DIS-D must be obtained via the W-GATE.  The ANN-80 will display the mesh ID when the system is normal, or will display a wireless event as specified in 3.9.4, "Event Messaging".Rescue ModeIn this mode, devices that are active participants in the mesh search and retrieve the devices that have lost the communication link. The rescue mode is indicated by the following LED pattern: One green blink every 6.8 seconds. For more information on rescue mode refer to “2.7.1, "W-GATE Modes of Operation"  The W-DIS-D will not communicate directly with the tool for display in the communicator.  The status of the W-DIS-D must be obtained via the W-GATE.  The ANN-80 will display the mesh ID when the system is normal, or will display a wireless event as specified in 3.9.4, "Event Messaging". SLC OperationProgram the point as a monitor point.  When the communication to the ANN-80 is missing or dis-rupted, the point will indicate open circuit.  The monitor point will not initiate an alarm condition.3.8.2  W-DIS-D LED IndicationsThe two LEDs on the devices blink in the same pattern to allow the LED to be viewed from any angle.  The LED indications are provided in the table below.
48 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Wireless Display Driver (W-DIS-D) W-DIS-D OperationsDuration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M30Condition Action RequiredDevice is ready to updateBootloaderLED Pattern5Device not permitted into the meshConrm device count and software versionDevice is in the mesh & looking for devices that are not in the mesh7Slot request rejectedMesh FormingApp eraseApp loading2New application code is being downloaded730MDevice has returned to factory default stateDevice is now prole assigned.Minimum of 2.5 years battery life remainingDevice is distributing  its prole to other devices which requested proleProle removed15Prolereceived10SolidBattery Check - All batteries are freshSolid2.5Distributor mode0.5Device is functioning as normal and searching for lost devicesDevice is functioning as normal and optimizing parent-child connectivityDevice is functioning as normalRescue modeM76Background mesh optimization5M14Normal mode14Use PC based congura-tion tool to initiate the downloadDuration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M30Condition Action RequiredDevice is ready to updateBootloaderLED Pattern5Device not permitted into the meshConrm device count and software versionDevice is in the mesh & looking for devices that are not in the mesh7Slot request rejectedMesh FormingApp eraseApp loading2New application code is being downloaded730MDevice has returned to factory default stateDevice is now prole assigned.Minimum of 2.5 years battery life remainingDevice is distributing  its prole to other devices which requested proleProle removed15Prolereceived10SolidBattery Check - All batteries are freshSolid2.5Distributor mode0.5Device is functioning as normal and searching for lost devicesDevice is functioning as normal and optimizing parent-child connectivityDevice is functioning as normalRescue modeM76Background mesh optimization5M14Normal mode14Use PC based congura-tion tool to initiate the download
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   49W-DIS-D Operations Wireless Display Driver (W-DIS-D)Duration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M30Condition Action RequiredLED PatternDevice is factory default Use PC tool to assign prole or activate switch to search for proleDevice is factory default and requesting a prole from a distributor or gatewayClear the tamper condition within 1 minute to enter site surveyDevice is factory default and is ready to enter site surveyPending site survey51MWaiting for prole10Searching for prole0.51MDevice has failed internal self diagnosticsSelf test failDevice is in a congura-tion state.Restart the device. If problem persists. Contact customer supportRestart the device. If problem persists. Contact customer supportDevice has a prole and can be set as distributor or have prole removedSet code wheel pattern to enter the desired modeMinimum of 6 months battery life remainingProle is assigned and device is searching for the meshEnsure the mesh is in rescue mode or wait for timeout to search mesh in formation modeSolidFactory Command1Prole modication51Battery Check - All batteries are presentSolid2.5Searching for mesh (in rescue mode)90 3Ensure the mesh is in formation modeProle is assigned and device is searching for the meshMesh is formed and initializingSearching for mesh (in formation mode)201st Mesh optimization2.5 7Duration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M30Condition Action RequiredLED PatternDevice is factory default Use PC tool to assign prole or activate switch to search for proleDevice is factory default and requesting a prole from a distributor or gatewayClear the tamper condition within 1 minute to enter site surveyDevice is factory default and is ready to enter site surveyPending site survey51MWaiting for prole10Searching for prole0.51MDevice has failed internal self diagnosticsSelf test failDevice is in a congura-tion state.Restart the device. If problem persists. Contact customer supportRestart the device. If problem persists. Contact customer supportDevice has a prole and can be set as distributor or have prole removedSet code wheel pattern to enter the desired modeMinimum of 6 months battery life remainingProle is assigned and device is searching for the meshEnsure the mesh is in rescue mode or wait for timeout to search mesh in formation modeSolidFactory Command1Prole modication51Battery Check - All batteries are presentSolid2.5Searching for mesh (in rescue mode)90 3Ensure the mesh is in formation modeProle is assigned and device is searching for the meshMesh is formed and initializingSearching for mesh (in formation mode)201st Mesh optimization2.5 7
50 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Wireless Display Driver (W-DIS-D) W-DIS-D OperationsDuration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M30Condition Action RequiredLED PatternDevice is in the mesh and in trouble condition. Device is in the mesh but has a incorrect SLC addressRefer to the panel to identify the trouble and possible resolutionVerify the address is non duplicate and non zeroDevice has just been tamperedEnsure detector is in the base and module has the face-plate onEnsure detector is in the base and module has the face-plate onDevice is tamperedDevice generic trouble (Eg: Low battery, Partial link condition)14Device address trouble (Eg: Dual address, Zero address)3Battery Check - WeakLess than 6 months or not all 4 batteries presentSolid2.5Device is functioning as normal and has been activatedAlarm state3Sustained tamper12Tamper entrySolid4Ensure all 4 batteries are present or replace the batteries.Duration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M30Condition Action RequiredLED PatternDevice is in the mesh and in trouble condition. Device is in the mesh but has a incorrect SLC addressRefer to the panel to identify the trouble and possible resolutionVerify the address is non duplicate and non zeroDevice has just been tamperedEnsure detector is in the base and module has the face-plate onEnsure detector is in the base and module has the face-plate onDevice is tamperedDevice generic trouble (Eg: Low battery, Partial link condition)14Device address trouble (Eg: Dual address, Zero address)3Battery Check - WeakLess than 6 months or not all 4 batteries presentSolid2.5Device is functioning as normal and has been activatedAlarm state3Sustained tamper12Tamper entrySolid4Ensure all 4 batteries are present or replace the batteries.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   51W-DIS-D Operations Wireless Display Driver (W-DIS-D)3.8.3  SwitchesThe W-DIS-D has two magnetic sensor switches.  The switches are used to remove a profile as described in 3.6.3, "Removing Profiles" or to request a profile as described in 3.6.1, "Assigning Profiles". Figure 3.5  W-DIS-D
52 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Wireless Display Driver (W-DIS-D) ANN-80 Operations3.9  ANN-80 OperationsThe ANN-80 displays wireless specific events for the associated mesh network.  Alarm conditions and trouble events that are displayed by the FACP are not displayed at the ANN-80.  The ANN-80 incorporates an automatic resound of the piezo and trouble indicator every 4 hours for active events.3.9.1  Buttons and SwitchesThe buttons and switches in the ANN-80 are displayed below in the image and are explained in the Table 3.5 .Figure 3.6  Buttons in ANN-80Table 3.5  Button ActionDrill button Not UsedUp Arrow Press the UP Arrow to scroll up through the messagesAck button Press the ACK button to acknowledge the messagesDown Arrow Press the Down Arrow to scroll down through the messagesSilence button Not UsedReset button Press the Reset buttonto clear latching wireless eventsKey switch Use the Key switch to switch on and switch off, to enable the Reset button
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   53ANN-80 Operations Wireless Display Driver (W-DIS-D)3.9.2  Visual IndicatorsThe visual indicators in the ANN-80 are displayed in the below image and are explained in the Table 3.6.Figure 3.7  Visual Indicators in ANN-80Table 3.6  Indicator buttons ActionAlarm Not UsedTrouble The trouble LED blinks yellow for any unacknowledged trouble event, and it glows steady for acknowledged trouble eventsSupervisory The Supervisory LED blinks yellow for any unacknowledged tamper event, and it glows steady for acknowledged tamper eventsAlarm Silenced  Not UsedAC Power Not used
54 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Wireless Display Driver (W-DIS-D) ANN-80 Operations3.9.3  Audible IndicatorsThe wireless events are sent to the FACP as generic trouble or supervisory events by the W-GATE and the details of the specific events are sent to the ANN-80 by the W-DIS-D. The FACP piezo activates for the first trouble event and the first supervisory event.  The FACP piezo will not acti-vate for additional trouble events or supervisory events when the initial event is still active. The ANN-80 piezo will not activate for the first event but will sound for each event after the initial event.Use the ACK button to acknowledge the piezo.  The reset function can be enabled in the ANN-80 using the key switch.  To enable the reset button,  insert the key into the key switch and turn the key switch counter clockwise to the ON position. To silence the buzzer, press the ACK key on the ANN-80 (Figure 3.6).3.9.4  Event MessagingThe wireless specific events are related to the wireless W-GATE and devices. These events are dis-played and notified on the FACP and N-ANN 80 in the form of messages. These messages are dis-played based on their occurrences. You can scroll through the messages using the up arrow and down arrow buttons. LCD UI Not in NetworkThe message, ‘RF COMM LOSS’ is displayed when the W-DIS-D is not in the network.  The mes-sage displayed is if the W-DIS-D is in Bootloader, factory default, or profile assigned state but not a part of a mesh network.  RF COMM LOSS is a tracking event that will clear once the W-DIS-D joins a mesh network.Mesh Formation In ProgressThe message, ‘MESH FORMATION IN PROGRESS’ is displayed when the network is in mesh formation mode.   Mesh Formation in Progress is a tracking trouble that will clear once the W-GATE exits mesh formation mode.NOTE: The ANN-80 must join the network to show this message. If it is not present in the network, ‘RF Comm Loss’ message is displayed.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   55ANN-80 Operations Wireless Display Driver (W-DIS-D)Low Battery EventThe low battery event denotes that:• The device has less than one month power left to perform the required operations.Or• Presence of less than four viable batteries.The low battery event is a latching condition. To clear the low battery event, tamper the device and replace all the four batteries. When a device is tampered, it drops out of the mesh network and attempts to rejoin as soon as the batteries are replaced and the tamper event is cleared.  The low bat-tery levels on the wireless devices are displayed as a trouble in the ANN-80 and generic trouble on the FACP.  Initiate a RESET at the ANN-80 to clear the low battery event.It is displayed as the following ASCII text on the ANN-80.Trouble Jamming EventJamming occurs when a device is overloaded with an interfering RF signal; but is able to send the messages out.  A jamming event is detected after 20 seconds of exposure to the jamming signal.The jamming event is displayed as a trouble event in the ANN-80 and generic trouble event on the FACP.   Jamming is a tracking trouble.  To clear the jamming trouble, remove any interference sources near the point that is reporting the trouble. Duplicate AddressTwo wireless devices on the same mesh network that are set to the same address reports a duplicate address trouble.  Duplicate address is a tracking trouble that will self restore once the conflict has been resolved.The following graphic illustrates the duplicate address trouble.
56 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Wireless Display Driver (W-DIS-D) ANN-80 OperationsDegraded ConnectionThe class A fault denotes a single connection path from the device. The wireless system is a class A system requiring two communication paths for normal operations. To remedy the class A fault, ensure adequate device spacing or the use of a repeater may be required. The wireless mesh is a self healing network. If the trouble is not cleared within 5 minutes, additional actions may be required.  Refer to the troubleshooting section for tips on resolving class A fault conditions.The following graphic illustrates the Class A trouble.System InitializationANN-80 displays the below displayed message when it initializes.  Gateway initializing is a track-ing trouble that is active during the first mesh optimization. Once the first mesh optimization rou-tine executes, the trouble will clear.System NormalANN-80 displays the below displayed message when the system is functioning normally and there are no wireless troubles in the system.Tamper EventA tamper trouble indicates that a detector is not firmly attached to the base or, cover plate is not properly attached in a module.  The Tamper events are displayed as supervisory events in the ANN-80 and generic supervisory events on the FACP.   Tamper is a latching condition that requires a reset at the ANN-80 to clear.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   57ANN-80 Operations Wireless Display Driver (W-DIS-D)Weak LinkA weak link trouble indicates that the connection of a device with its parent device is weak, since the signal strength fails to meet the minimum RSSI threshold.  The threshold is -50 dB during com-missioning mode and -58 dB during normal mode.  The trouble will be cleared only if the parent- child signal strength goes above the required RSSI threshold, or if a mesh optimization is triggered.Key Bus TroubleA Key bus trouble indicates that the ANN-80 has lost connection with W-DIS-D.Capacity ExceededA device count trouble indicates that there are fifty devices that are already present in the mesh and one more device is trying to join the network.  Maximum GatewaysGateways Exceeded trouble indicates that the number of overlapping gateways exceeds the limit of 4 gateways.  The trouble will be cleared only when the number of overlapping gateways is reduced to 4.3.9.5  Clearing messagesThe events that are tracking will clear once the event returns to the normal state. Events that are latching require a reset at the ANN-80. To reset messages, press the Reset button in the ANN-80 Refer Figure 3.5.  To reset messages in the panel, initiate a system reset in the FACP.
58 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Wireless Display Driver (W-DIS-D) ANN-80 Operations3.9.6  LED IndicationsThe LED Indications in the ANN-80 are provided below.DEVICE/MODULES LED COLOR FUNCTIONAnnunciator  Yellow The trouble button blinks yellow until it is acknowledged, to indicate trouble state.Yellow The supervisory button blinks yellow until it is acknowledged, to indicate supervisory state.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   59ANN-80 Operations Wireless Display Driver (W-DIS-D)
60 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Devices DescriptionSection 4: Devices4.1  DescriptionSubsystem OverviewThe Wireless Sensor Network consists of the following devices:W-SD355 - Wireless Photoelectric Smoke Detector - FCC ID AUBWFSSDThe wireless photoelectric smoke detector is powered by four CR123A batteries.  It has a sensor head to detect smoke and LEDs to indicate the activation & trouble status. For further details, refer to the table in 4.7.2, "LED Indications".W-SD355T- Wireless Photo/Heat Detector - FCC ID AUBWFSSDThe wireless Photo/Heat detector is powered by four CR123A batteries.  It has a sensor head to detect heat and LEDs to indicate activation & trouble status.  For further details,  refer to the table in 4.7.2, "LED Indications".W-H355R- Wireless Rate of Rise Heat Detector - FCC ID AUBWFSSDThe Rate of Rise heat detectors are powered by four CR123A batteries. The detectors have LEDs, to indicate the activation & trouble status. For further details,  refer to the table in 4.7.2, "LED Indi-cations".W-H355- FIX135 Wireless Fixed Heat Detector - FCC ID AUBWFSSDThe Fixed heat detectors are powered by four CR123A batteries. The detectors have LEDs, to indi-cate the activation & trouble status. For further details, refer to the table in 4.7.2, "LED Indica-tions".W-MMF- Wireless Monitor Module - FCC ID AUBWFSMMThe wireless monitor module is powered by four CR123A batteries. It can be connected to a switch within three feet of its location or wired directly to the pull station. The module has LEDs, to indi-cate the activation & trouble status. For further details,  refer to the table in 4.7.2, "LED Indica-tions".4.2   Agency Approvals4.2.1  FCCThis device complies with part 15 of the FCC Rules. Operation is subject to the following two con-ditions: 1. This device may not cause harmful interference, and 2. This device must accept any interference received, including interference that may cause undesired operation.WARNING: CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY THE MANUFACTURER COULD VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   61Specifications Devices4.3  SpecificationsThe following are the specifications for the devices.Table 4.1  Device SpecificationsThe below table provides details on the device references.4.4  Installing DevicesFor information on installing the devices, refer to the manuals mentioned in the above table.4.5  Mounting & WiringFor information on mounting and wiring, refer to the manuals mentioned in the table 4.2.4.6  Configuration and ProgrammingThe configuration of a device starts with assigning a profile.  Refer to the instructions below for assigning a profile. • Assiging profiles using PC Tools.• Assigning profile to a detector with a W-GATE or distributor.• Assigning profile to a module with a W-GATE or distributor.Specification DataRadio Frequency Lower ISM Band (915 MHz)Maximum power output +17dBmMinimum signal strength level needed at the receiver for a primary path with weak link trouble reporting enabled.-50dBmMinimum signal strength level needed at the receiver for a secondary path or primary path with weak link trouble reporting disabled.Must be 15 dBm higher than the noise floor down to -87dBmMaximum ambient noise level -90dBmMinimum battery life 1 yearModel Description ManualW-SD355 Wireless LiteSpeed Detector, Photo W-SD355 and W-SD355T Intelligent Wireless Photoelectric Smoke Sensors.Manual part number for the above devices- I56-4081-000W-SD355T Wireless LiteSpeed Detector, Photo/HeatW-H355R Wireless LiteSpeed Heat sensorHeat, Rate Of Rise 135 W-H355R and W-H355 and Intelligent Wireless Temperature Sensors.Manual part number for the above devices- I56-4082-000 W-H355 Wireless LiteSpeed Heat sensor Heat, Fixed Temp135W-MMF Monitor Module W-MMF Wireless Monitor ModuleManual part number - I56-4083-000Table 4.2  Device References
62 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Devices Configuration and Programming4.6.1  Assigning Profiles NOTE: To assign a profile, the device must be in a factory default state. A single red light flashes on the LED confirming that the device is in the default state. To restore the device to factory default state, refer to 4.6.4, "Restoring a Device to Factory Default".Assigning Profile Using PC ToolsTo assign a profile to the device using the PC Tools application, do the following:1. Connect the W-USB dongle device to your computer. For more information on USB dongle, refer to Section 5:, "USB Adapter".2. Launch the PC tools application.  Refer to Appendix B:, "PC tools" to know about launching the PC tools application.3. Go to the Create Mesh Network step.4. Create a new profile or import an existing profile as required. 5. Select and open the profile to be assigned to the device from the Name drop down list in the left panel.6. Switch on the device in range of the USB adapter, which is connected to the laptop or PC where PC tool is installed.7. Select the device from the Communicator panel.8. Click Assign.The device is now included in the list of devices with a profile assigned.  When the profile is assigned, the LEDs emit a solid green light for 10 seconds.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   63Configuration and Programming DevicesAssigning a Profile to a Detector with a W-GATE or DistributorA W-GATE that has a profile can be used to distribute the profile to other devices. The W-GATE must be in a state where it can distribute a profile. For more information on converting a W-GATE to a distributor, refer to 2.6.3, "Profile Distribution".  A device with a profile can be used to distrib-ute the profile. To put  a device into distributor mode, refer to topic, “Converting a Device into a Distributor”.Transfer Profile from W-GATE/Distributor to DetectorTo transfer profile from W-GATE/distributor to the detector, do the following:1. Bring the detector within the range of the W-GATE/distributor.2. Power on the detector. Ensure the detector is in factory default state. A single or double red light flashes on the detector confirming that the detector is in the default state. 3. To make the detector request the profile, activate the magnetic test switch shown in the below figure.Figure 4.1  Magnet in a detectorOnce the magnet test switch is activated, the LED flashes red light every half second indicating that it is requesting a profile. If the profile is successfully received, the LED emits a solid green light for 10 seconds. If the profile is not received within a minute, the LED flashes a red light every ten sec-onds indicating that it has stopped requesting for a profile. Transfer Profile from W-GATE/Distributor to ModuleTo assign a profile to a module, perform the following steps:1. Bring the module in range of the W-GATE or the distributor.2. Power on the module. Ensure the module is in factory default state. If the module is in factory default state, the LED blinks red once.3. To make the module request the profile, toggle the state of the tamper condition. To toggle the  tamper condition state, start with the faceplate removed.
64 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Devices Configuration and Programming4. Place the faceplate over the module temporarily, and remove the faceplate again in less than 1 second.  Do not attach the mounting screws for the faceplate during this step.  The LED flashes red light every half a second indicating that it is requesting a profile.  The LEDs blink solid green for ten seconds indicating that the profile is assigned. Figure 4.2  Magnetic sensor in a module4.6.2  Distributor ModeConverting a Device into a DistributorNOTE: Only a device with a profile can be made as a distributor.To turn a device into a distributor, do the following: 1. Power up the device with one battery. NOTE: Ensure that the device is in the profile modification mode. This is indicated by a single yellow blink every 5 seconds. The profile modification mode times out if it has not received a command in one minute.2. Toggle the SLC code wheel address to pattern of 0-1-0-1. To toggle the SLC code wheel address,• Set the address to 0.• Change the address to 1.• Change the address back to 0.• Change the address back to 1.NOTE: The LED flashes a single green every half a second when the device is functioning as a distributor.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   65Configuration and Programming DevicesConverting a Distributor Back into a DeviceTo turn a distributor device back to a network device, replace the battery and provide a proper code wheel address. A normal device requires four batteries for trouble-free operation. It is recom-mended to use fresh batteries after the distributor mode. 4.6.3  Mesh FormationTo add a device to a mesh, refer to the topic, "Mesh Formation with PC Tools" or, to form a mesh network, ensure that the W-GATE is powered on and contains a profile.  Activate the mesh forma-tion” (Figure 2.8, “Mesh Formation Magnetic Sensor on a W-GATE”) magnet sensor on the W-GATE.RepeaterThe Firelite Wireless Sensor Network does not require the use of a dedicated repeater; all wireless devices act as repeaters. When the repeater function is needed in a location where there is no spe-cific fire function is required, a wireless monitor module or another device can be installed to fulfill the function as a repeater.4.6.4  Restoring a Device to Factory DefaultRemoving Profiles Without PC-based Configuration ToolA device can be restored to factory default state by following the below steps.1. Start with the device powered off. The process is performed during the start-up.2. Power on the device by inserting a single battery into any slot in the device. The LEDs blink yellow twice every five seconds for one minute continuously after inserting the battery.3. Toggle the code wheel address pattern to 0-159-0.  To toggle the SLC code wheel address,• Set the address to 0.• Change the address to 159.• Change the address back to 0.NOTE: The above illustration depicts the rotary switches being set at address 35 (rotary switch on 'TENS' set at 3 and rotary switch on 'ONES’ set at 5. Ensure that the code wheel address pattern is toggled within 1 minute of inserting the battery. After the code wheel pattern is set, the LEDs in the device blink green five times followed by a sin-gle or double red blink confirming that the device has been reverted back to factory default condi-tion.
66 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Devices Device OperationsRemoving a Profile with PC ToolsTo remove a profile in a device using the PC Tools application, do the following:1. Connect the W-USB dongle device to your computer. For more information on USB dongle, refer to Section 5:, "USB Adapter".2. Launch the PC tools application.  Refer to Appendix B:, "PC tools" to know about launching the PC tools application.3. Go to Site Survey, Create Mesh Network or Diagnostics step.4. Click Extras and select Reset Devices. The Reset Devices screen appears, displaying the W-GATE and other devices that have the profile assigned.5. Click to select the required device and click Reset Device to remove the profile.The profile is removed and the device is reset to factory default state.4.7  Device Operations4.7.1  Modes of OperationFactory DefaultIn this mode, the devices are not associated with the W-GATE. A profile must be assigned to asso-ciate the device with the W-GATE. For further information on assigning a profile,  refer to, "Assigning a Profile to a Detector with a W-GATE or Distributor". A device in factory default can be used for site survey.  Refer to Appendix A:, "Site Survey". The device cannot perform any fire protection in the factory default state.  In this mode, the devices will be viewable in the communicator window of the PC tool with the state displayed as “Factory Default”.Profile AssignedIn this mode, the devices are associated with the W-GATE but are not an active participant in the mesh network. A device that is not in the tampered state can join the mesh network in formation or in the rescue mode. For further information on mesh formation, refer to “Mesh Formation Mode” and for further information on rescue mode, refer to “Rescue Mode”.  A device in the profile con-
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   67Device Operations Devicesfigured state can also be used to distribute profiles. For further information on distributing a profile, refer to “4.6.2, "Distributor Mode"”.  To remove a profile from a device, refer to the topic , "Removing Profiles Without PC-based Configuration Tool".A device cannot perform any fire protection until it becomes a part of the mesh network. The device will be an invalid reply or no answer at the FACP.In this mode, the devices will be viewable in the communicator window of the PC tool and indi-cates a status of “Profile Assigned”.BootloaderIn this mode, the device cannot participate in a mesh and cannot provide fire protection.  The device will be viewable in the communicator window of the PC Tool with a status “Bootloader”.  To get a device out of bootloader, refer to Appendix C:, "Troubleshooting and Testing".DistributorIn this mode the device is functioning as a profile distributor. The device cannot participate in a mesh and cannot provide fire protection. It can be used to share the profile with any device that requests a profile. The device will be viewable in the communicator window of the PC Tool with a status “Distributor”.Mesh ParticipantDevices that are in the mesh network, no longer communicates directly with the PC Tools applica-tion.  The PC Tools application must communicate with the W-GATE for status information from the device.  The W-GATE will respond to the FACP for the device at the address set with the code wheels.  The following states are applicable for a device in a mesh network.Mesh Formation ModeIn this mode, the devices are active participants in a mesh that is forming. The LED flashes in the following pattern. First blink green, second blink yellow every 6.8 seconds. The device cannot per-form any fire protection in this state.For further information on this state (mesh formation), refer to the topic “Mesh Formation”.Initial Mesh Optimization ModeIn this mode, the mesh network is formed and is in the process of establishing stronger communica-tion paths. The LED pattern flashes in the following pattern. Single yellow blink every 6.8 seconds. The device cannot perform any fire protection in this state.  For further information on initial mesh optimization mode, refer to the topic, “Initial Mesh Optimi-zation Mode”.Normal ModeIn the normal mode, the mesh network is formed and provides fire protection. The LED pattern is single green blink every 13.6 seconds. The LED flash can be disabled by panel configuration. If a device is in trouble, it is indicated by the trouble states. Rescue ModeIn the rescue mode, devices that are active participant in the mesh search and retrieve the devices that have lost the communication link. The rescue mode is indicated by the LED pattern of 1 green blink every 6.8 seconds. For more information on rescue mode, refer to the topic, “Rescue Mode”.4.7.2  LED IndicationsThe two LEDs on the devices blink in the same pattern to allow the LED to be viewed from any angle.  The LED indications are provided in the table below.
68 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Devices Device OperationsDuration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M30Condition Action RequiredLED PatternDevice is factory default Use PC tool to assign prole or activate switch to search for proleDevice is factory default and requesting a prole from a distributor or gatewayClear the tamper condition within 1 minute to enter site surveyDevice is factory default and is ready to enter site surveyPending site survey51MWaiting for prole10Searching for prole0.51MDevice has failed internal self diagnosticsSelf test failDevice is in a congura-tion state.Restart the device. If problem persists. Contact customer supportRestart the device. If problem persists. Contact customer supportDevice has a prole and can be set as distributor or have prole removedSet code wheel pattern to enter the desired modeMinimum of 6 months battery life remainingProle is assigned and device is searching for the meshEnsure the mesh is in rescue mode or wait for timeout to search mesh in formation modeSolidFactory Command1Prole modication51Battery Check - All batteries are presentSolid2.5Searching for mesh (in rescue mode)90 3Ensure the mesh is in formation modeProle is assigned and device is searching for the meshMesh is formed and initializingSearching for mesh (in formation mode)201st Mesh optimization2.5 7Duration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M30Condition Action RequiredDevice is ready to updateBootloaderLED Pattern5Device not permitted into the meshConrm device count and software versionDevice is in the mesh & looking for devices that are not in the mesh7Slot request rejectedMesh FormingApp eraseApp loading2New application code is being downloaded730MDevice has returned to factory default stateDevice is now prole assigned.Minimum of 2.5 years battery life remainingDevice is distributing  its prole to other devices which requested proleProle removed15Prolereceived10SolidBattery Check - All batteries are freshSolid2.5Distributor mode0.5Device is functioning as normal and searching for lost devicesDevice is functioning as normal and optimizing parent-child connectivityDevice is functioning as normalRescue modeM76Background mesh optimization5M14Normal mode14Use PC based congura-tion tool to initiate the download
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   69Device Operations DevicesDuration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M30Condition Action RequiredDevice is ready to updateBootloaderLED Pattern5Device not permitted into the meshConrm device count and software versionDevice is in the mesh & looking for devices that are not in the mesh7Slot request rejectedMesh FormingApp eraseApp loading2New application code is being downloaded730MDevice has returned to factory default stateDevice is now prole assigned.Minimum of 2.5 years battery life remainingDevice is distributing  its prole to other devices which requested proleProle removed15Prolereceived10SolidBattery Check - All batteries are freshSolid2.5Distributor mode0.5Device is functioning as normal and searching for lost devicesDevice is functioning as normal and optimizing parent-child connectivityDevice is functioning as normalRescue modeM76Background mesh optimization5M14Normal mode14Use PC based congura-tion tool to initiate the downloadDuration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M30Condition Action RequiredLED PatternDevice is factory default Use PC tool to assign prole or activate switch to search for proleDevice is factory default and requesting a prole from a distributor or gatewayClear the tamper condition within 1 minute to enter site surveyDevice is factory default and is ready to enter site surveyPending site survey51MWaiting for prole10Searching for prole0.51MDevice has failed internal self diagnosticsSelf test failDevice is in a congura-tion state.Restart the device. If problem persists. Contact customer supportRestart the device. If problem persists. Contact customer supportDevice has a prole and can be set as distributor or have prole removedSet code wheel pattern to enter the desired modeMinimum of 6 months battery life remainingProle is assigned and device is searching for the meshEnsure the mesh is in rescue mode or wait for timeout to search mesh in formation modeSolidFactory Command1Prole modication51Battery Check - All batteries are presentSolid2.5Searching for mesh (in rescue mode)90 3Ensure the mesh is in formation modeProle is assigned and device is searching for the meshMesh is formed and initializingSearching for mesh (in formation mode)201st Mesh optimization2.5 7
70 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Devices Device OperationsDuration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M30Condition Action RequiredLED PatternDevice is in the mesh and in trouble condition. Device is in the mesh but has a incorrect SLC addressRefer to the panel to identify the trouble and possible resolutionVerify the address is non duplicate and non zeroDevice has just been tamperedEnsure detector is in the base and module has the face-plate onEnsure detector is in the base and module has the face-plate onDevice is tamperedDevice generic trouble (Eg: Low battery, Partial link condition)14Device address trouble (Eg: Dual address, Zero address)3Battery Check - WeakLess than 6 months or not all 4 batteries presentSolid2.5Device is functioning as normal and has been activatedAlarm state3Sustained tamper12Tamper entrySolid4Ensure all 4 batteries are present or replace the batteries.Duration of LED stateAll units are in seconds. Minute is indicated by M.Example:LegendLED colorNo. of blinksInterval between blink patternsApproximate durationWill transition to next state after 30 min (approx)First blink is green. Second is yellowTwo blinks in this pattern7 sec between blink patterns7M30Condition Action RequiredLED PatternDevice is in the mesh and in trouble condition. Device is in the mesh but has a incorrect SLC addressRefer to the panel to identify the trouble and possible resolutionVerify the address is non duplicate and non zeroDevice has just been tamperedEnsure detector is in the base and module has the face-plate onEnsure detector is in the base and module has the face-plate onDevice is tamperedDevice generic trouble (Eg: Low battery, Partial link condition)14Device address trouble (Eg: Dual address, Zero address)3Battery Check - WeakLess than 6 months or not all 4 batteries presentSolid2.5Device is functioning as normal and has been activatedAlarm state3Sustained tamper12Tamper entrySolid4Ensure all 4 batteries are present or replace the batteries.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   71Device Operations Devices
72 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013USB Adapter IntroductionSection 5: USB Adapter5.1  IntroductionThe W-USB is an interface that can be connected to a PC through USB.  It communicates with the RF devices using the same frequencies as the mesh protocol.  This device is powered directly by the USB port.The LED gives an indication of power and initialization status.The W-USB has an adjustable USB connector to facilitate the connection by reducing the size when connected to a laptop/tablet. Figure 5.1  USB Adapter5.2   Agency Approvals5.2.1  FCCThis device complies with part 15 of the FCC Rules. Operation is subject to the following two con-ditions: 1. This device may not cause harmful interference, and 2. This device must accept any interference received, including interference that may cause undesired operation.FCC ID PV3WFSADPTWARNING: CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY THE MANUFACTURER COULD VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   73Specifications USB Adapter5.3  Specifications5.3.1   Electrical Specifications5.3.2   Serial Communication Specification5.3.3   Mechanical Specifications5.3.4  Environmental SpecificationsITEM TYP MIN MAX UNITS CommentsOperating Voltage 5 4.3 5.5 VDCSupply Current 33 25 85 mAITEM CommentsUSB Standard USB 2.0 full speedITEM TYP UNITS CommentsUSB connector type ALength 76.2 mm Connector closedLength 96.2 mm Connector openThickness 13 mm Connector sideThickness 8.4 mm Antenna sideWidth 31.2 mmWeight 19.5 gSpecification MIN MAX UNITS CommentsHumidity 10 93 %RH Non CondensingTemperature 0°C/32°F 49°C/120°FMaximum operating temperature rangeStorage Temperature -10°C 60°C
74 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013USB Adapter Driver Installation5.4  Driver InstallationNOTE: Install PC Tools application before attempting to install the driver.To install a driver, perform the following steps:1. Insert the adapter into the PC. The adapter is detected and is displayed in the Computer Management screen as a Wireless Fire System Dongle.2. Right click on Wireless Fire System Dongle and select Update Driver Software.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   75Driver Installation USB Adapter3. Select Browse my computer for driver software option.4. Browse to the location of the driver software by clicking Browse. Select the file and click Next.  To locate the driver software,  go to c:\Program Files\Honeywell\Device Driver.   The file resides inside the Device Driver folder.
76 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013USB Adapter Driver Installation5. The confirmation message is displayed that the driver software is updated.6. The device is displayed under ports. The driver is installed.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   77Driver Installation USB Adapter
78 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Site Survey DescriptionAppendix A: Site SurveyA.1  DescriptionThe site survey allows you to assess and qualify the site for installing the wireless fire alarm sys-tem. The site survey view in the PC tool allows you to view the Radio Frequency (RF) assessment of the site. The tool reports the suggested device spacing based on the data collected during the site survey. This helps to optimize the reliability and performance of the wireless network in the wire-less fire alarm system.A.1.1  Conducting Site Survey at the Job Site The site survey includes two tests:• Link quality test• RF Scan TestThe link test can be conducted individually or it can be done followed by the RF Scan test. This section explains the steps for a link quality test and a link quality test followed by RF Scan test.Link Quality TestA link quality test is a quick and repeatable test that provides immediate feedback on the device connectivity.  It is conducted primarily to check if there is an event of pocket loss during data trans-mission between devices.  In a link test, the device addresses are set in the range of 001 to 100. Basic RequirementsTo conduct a link test, ensure that• You possess two or more devices.• The devices are in factory default condition.NOTE: The LEDs in the device blink red (single or double blink) upon starting the device if it is in a factory default condition.  Refer to 4.6.4, "Restoring a Device to Factory Default" for more information on setting the device to factory default state.Conduct a Link Test NOTE: The below procedure lists the steps for conducting only a link test. Hence, examples on the setting the address on devices is explained considering only link test.To conduct a link test, perform the following steps.1. Remove the batteries if any present, from the devices and set the address of the first device as 001.NOTE: For each subsequent device, use the next highest SLC address.  For example, set the first device address as 001, second device as 002 and third device as 003.  The upper address limit for a device address is 100 while doing a link test.2. Bring the first device to the required location to conduct the test.3. Insert one battery in to the factory fresh device.   After inserting the battery, the LEDs in the device blink red twice every five seconds, if the device is ready for site survey.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   79Description Site SurveyNOTE: You could insert the battery into any available slot. Inserting more than one battery deters the device from entering the site survey mode.4. Clear the tamper condition within one minute of the device startup, to enter the site survey mode. To clear the tamper condition, position the decorative ring around the base of the detector and rotate it in either direction until the ring snaps to its place (Refer to the below image).  When you clear the tamper, the device starts the transmission that is denoted by LEDs.  Refer to the Table A.1, "Link Test Results-LED Pattern"NOTE: Due to the absence of the second device that is yet to be introduced, the transmission fails. Hence, the LEDs in the first device emits solid red.5. Bring the second device to the required location and repeat the steps 3 and 4. The LEDs in the second device emit yellow light while the test is being conducted.Results of Link TestOnce you have introduced the two devices, the devices start communicating and the link quality test is started. The blinking pattern of the LEDs in the device 002 communicates the results of the link test.   To repeat the test, follow the steps 1 to 4 listed under “Conduct a Link Test”The following table explains the LED patterns during a link test.Table A.1  Link Test Results-LED PatternState Pattern LED Results & DescriptionLInk Test in progress Single blink every 0.5 seconds. Yellow Transmission of data packets to another device.Solid Red Failure - No Packets receivedSingle blink every 5 seconds. Red Poor -Received only half of the total transmission of data packets or poor signal strength2 blinks every 5 seconds. Red Marginal - Packets partially received or marginal signal strength.3 blinks every 5 seconds. Green Good - All packets received and good signal strength4 blinks every 5 seconds. Green Excellent - All packets received and excellent signal strength
80 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Site Survey DescriptionTasks After Link test• Reboot the devices of the link test. To do this, remove and insert the batteries. • After rebooting, do not push the detector back in the base. • The devices can be moved around different locations in the site to optimize the results.• The results of the link quality test (or) the LED indications will exist until the battery lasts in the devices.• Upon completion of the link test using the devices numbered 001 and 002, you can test the link quality using different set of devices in other required locations.  To do so, follow the steps 1 to 5 listed under “Conduct a Link Test”• Retrieve the site survey results. To retrieve the site survey results, refer to the topic “Retrieving Site Survey Results”at the end of this section.Link Quality Test and RF Scan TestAn RF Scan test can be conducted following a link test. A Radio Frequency scan test is conducted to assess and measure the background noise and interference, from other wireless systems if any, in the site. The RF Scan test is conducted following the link test. While doing a RF Scan test, the device addresses are set starting from 100 till 159.   The below procedure lists the steps for conducting a link test followed by a RF Scan test. Hence, examples on the setting the address on devices is explained considering both the tests.Conduct a Link Test To understand the basic requirements of a link test, refer to the section A.1.1.To conduct a link test, perform the following steps.1. Remove the batteries if any present, from the devices and set the address of the first device as 101.  For each subsequent device, use the next highest SLC address. For example, set the first device address as 101, second device as 102 and third device as 103. The upper address limit for a device address is 100 while doing a link test.2. Bring the first device to the required location to conduct the test.3. Insert one battery in to the factory fresh device in any available slot. Inserting more than one battery deters the device from entering the site survey mode.  If the device is ready for site survey, after inserting the battery, the LEDs in the device blink red twice every five seconds. 4. Clear the tamper condition within one minute of the device startup to enter the site survey mode. To clear the tamper condition, position the decorative ring around the base of the detector and rotate it in either direction until the ring snaps to its place. Refer to the below image. At this stage, the device starts the transmission.  Due to the absence of the second device that is yet to be introduced, the transmission fails. Hence, the LEDs in the first device emits solid red.  For more information,  Refer to table A.2.5. Bring the second device to the required location and repeat the steps 3 and 4. The LEDs in the second device emit yellow light while the test is being conducted.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   81Description Site SurveyResults of Link TestOnce you have introduced the two devices, the devices start communicating and the link quality test is started. The blinking pattern of the LEDs in the device 102 communicates the results of the link test.   To repeat the test, follow the steps 1 to 4. The link test results stay for 5 minutes and then the RF test begins. You can repeat the test any number of times; the only condition being that the next test should be conducted within five minutes of the last concluded test. Refer to Table A.1, "Link Test Results-LED Pattern" for LED patterns that convey the link quality results. This concludes the link test and the RF Scan test starts. The devices addressed 101 or higher, transition to RF Scan test. On devices addressed below 100, the link test results stay until the bat-tery last. If you are conducting the link test with several devices started in various time frames, it is possible that the devices that start and complete the link test first can transition to RF Scan test, when the devices that began later are still in the link test mode. The RF Scan test may take up to 70 minutes and you have to check the LED patterns for results. The LED patterns are given below.Results of RF Scan TestTable A.2  RF Scan Test Results - LED Pattern  Retrieving Site Survey Results To retrieve the site survey results, do the following:1. Reboot the devices by removing and inserting the battery back in to the device.2. Plug in the USB adapter in to the laptop/PC where you have installed the PC tool.3. Bring the devices within a range of 20ft from the USB adapter. 4. Launch PC tools application and retrieve the data.State Pattern LED ResultIn Progress- 70 minutes remaining 7 short blinks (Solid) every 30 secondsRed BadIn Progress- 70 minutes remaining7 short blinks (Solid) every 30 secondsYellow MarginalIn progress- 70 minutes remaining7 short blinks (Solid) every 30 secondGreen Good
82 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013PC tools DescriptionAppendix B: PC toolsB.1  DescriptionThe PC Tool is a standalone desktop windows application. It is a configuration and maintenance tool for the W-GATE and devices of the Wireless Sensor Network. It allows you to survey the site, configure the devices and diagnose the wireless network of the Wireless Sensor Network. This tool can be installed on a PC or a laptop. The tool communicates with the W-GATE and wireless devices through USB based user interface.  You have to connect the USB adapter to the computer to invoke the PC tools application. At any point of time, only one instance of PC Tool can run on a laptop or PC.The tool has the following utilities.• Site Survey view• Creating Mesh Network• Diagnostic viewNOTE: At any point of time, only one instance of PC Tool can run on a laptop or PC.The PC tool works in a wireless environment with the W-GATE and devices within the range of 25 feet.  B.1.1  Launching PC ToolsTo Launch PC Tools application,1. Click Start, point to All Programs, click Wireless Tool, and then Wireless Tool. The following screen is displayed.  Alternatively, you can double click the Wireless Tool shortcut in your desktop.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   83Description PC tools2. Click Start Using. The PC Tools screen is displayed.B.1.2  Creating JobsiteYou can create a new jobsite or open an existing one.To create a new jobsite,1. Perform the steps listed to launch the PC Tools application.2. Click Create from PC Tools screen.3. Enter the name of the new jobsite in the Jobsite Name field.4. Enter the Location/Description if any, and click Create.5. The Create Project window opens and displays the name of the jobsite that you created.6. Click Save.The jobsite is created, and the following screen is displayed. You can go to the required function that you want to perform by clicking the Start button in the respective function.
84 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013PC tools DescriptionB.1.3  Opening JobsiteIf you have a jobsite already created, you can open the existing jobsite. To open an existing jobsite,1. Perform the steps listed to launch the PC Tools application.2. Click Open from the PC tools screen.3. Choose the required file from your local drive and click Open against Open Existing Jobsite option. Enter the name of the new jobsite in the Jobsite Name field.The following screen is displayed. You can go to the required function that you want to perform byclicking the Start button in the respective function.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   85Description PC tools
86 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Troubleshooting and Testing TroubleshootingAppendix C: Troubleshooting and TestingC.1  TroubleshootingC.2  Testing W-GATE and DevicesThe W-GATE must be tested after installation and as an integral part of a periodic maintenance pro-gram. The testing methods must satisfy the Authority Having Jurisdiction (AHJ). The W-GATE provides optimum performance when tested and maintained in compliance with NFPA 72 ordi-nances.NOTE: The W-GATE used with this base must be tested and maintained regularly following the NFPA 72 ordinances. The W-GATE should be cleaned at least once a year.C.2.1  Testing LED IndicationsFor more information on LED indications, refer to the respective chapters and the attachments pro-vided for LED indications.C.3  Testing Wireless NetworkThe PC Tools application allows you to,• Diagnose and troubleshoot the wireless network and connectivity of the devices. • Monitor the wireless network topology, quality of the communication links between the devices, live and historical event reports for the troubleshooting purpose. • View the parent-child relationship and the signal strength between the two devices, and identifies the device that has lost the communication link with the wireless network.Trouble Type Trouble Description ActionWeak link condition The weak link trouble denotes a connection of insufficient primary signal strength.Ensure spacing between devices, or use repeaters.Class A fault condition Device loses the connection with any of the parent devices.Ensure spacing between devices, or use repeaters.Jamming Jamming occurs when a device is overloaded with an interfering RF signal; but is able to send the messages out.If any jammers are installed in the vicinity of the devices, remove them.Low battery The low battery event denotes that the device has less than one month power left to perform the required operations.Or presence of less than four viable batteries.To clear the low battery event, tamper the device and replace all the four batteries. When a device is tampered, it drops out of the mesh network and attempts to rejoin as soon as the batteries are replaced and the tamper event is cleared.Duplicate address Two wireless devices on the same mesh network that are set to the same address reports a duplicate address trouble.  Change the address of a device to avoid duplication.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   87Testing Wireless Network Troubleshooting and TestingIn addition to the above,  the PC tools application• Communicates with the W-GATE to retrieve the live information about the connectivity and status of the devices.• Stores the wireless network data such as network map, parent-child information, device information, history events, and network statistics.The PC Tools application allows you to retrieve the following information for diagnosing and trou-bleshooting purpose.• Network Topology • History Events• Network Snapshots• Network Statistics• Device AttributesC.3.1  Network TopologyParent-Child DevicesThe parent child relationship between the devices in the wireless network is displayed using the directional arrows.Orphan DevicesThe device that is not linked with any other device in the wireless topology is an orphan device. The device is represented as an orphan device due to one of the following reasons:• The device was originally a part of the wireless network and due to a 'Device Connected' live event, the device sets out of wireless network range.• The device was system configured with the same network ID and hence it was a part of the same wireless network. When the network topology was retrieved, the device detail was not retrieved.• The network connections are saturated and hence parent-child connection with the device is not established.Class A ComplianceEach device must comply with Class A guidelines. The guidelines provide instructions on the required number of parent device for each device to be compliant with the guideline. Following are the compliance requirements.• Class A guideline requirement:Every device must have two parent devices.NOTE:  The device image is changed to depict that it does not meet the required guidelines. NOTE: The Class A guidelines are not applicable for the W-GATE. Selecting a device from the graphical representation and clicking either left or right allows you to view the following details. The Network Topology window allows you to click either left or right on any connected or orphan device.
88 PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Troubleshooting and Testing Testing Wireless NetworkC.3.2  History EventsThe PC Tools application allows you to retrieve and view the history events of the wireless network for troubleshooting purpose. This report provides information on when the device gets connected with the wireless network, mode change, and the slot change details.C.3.3  Network SnapshotsThe PC Tools application allows you to retrieve and view the network snapshot for troubleshooting purpose. The network snapshot helps you to analyze on how the wireless network is functioning over a period of time.C.3.4  Network StatisticsThe PC Tools application allows you to retrieve and view the network statistics for troubleshooting purpose. The network statistics provides information on the attributes and RSSI of a device. The attributes provide information on the retransmission count and device re-join events. The retrans-mission count is a value equal to the number of times a device retransmits the wireless signal. The device re-join events is a value equal to the number of times the devices gets disconnected from the wireless network and gets connected with the wireless network. The RSSI of a device displays the parent-child relationship between the devices.C.3.5  Device AttributesThe PC Tools application allows you to retrieve and view the attributes of a device for trouble-shooting purpose. The attributes of a device such as low indication, removal indication, level, tam-per fault and others are retrieved.
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013   89Testing Wireless Network Troubleshooting and Testing
90 PRELIMINARY:  Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Index AAbbreviations 11Abbreviations and Meanings 13Activations 27Additional References 10adjacent 26ambient 13Assign a profile to the Gateway 19Assumed Knowledge 10Bbackground 80basic 80Bootloader 27CClass 17Class A 86Clearing 57code 64Collapse 33Configuration 19configuration 33CR123A 60Creating Jobsite 83Dddress 24Device Attributes 87device spacing 10Devices 60Configuration and Programming 61dongle 42Driver 36Duplicate 36EExcellent 79Ffaceplate 63Factory 65FCC 60First blink 67future 31GGateway 12, 23, 31Description 12Installing Gateway 13Specification Sheet 13gateway 31Gateway Powered from SLC 17green 20green light 20IInitialization 56initiate 57installing 78Installing Devices 61isolator 17JJamming 36, 46, 55Jobsite 83jumper 14KKey Bus Trouble 57Llatching 24LCD UI 36Features 38LED indications 27Link 32LiteSpeed 61Lock 31Mmagnet 21Magnet switch activations 27magnetic 20, 23mesh 24, 25Mesh Formation 20mesh formation 25Mesh Optimization 27Mounting 14NNormal Mode 26PPurpose 10
PRELIMINARY:  Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013 91Index R–YRRecommended Installation and Best Practices 10Rescue Mode 26SSLC Configuration 23, 24slot 14spectrum 35TTamper 24tamper 24toggles 27transmission 26Trouble 32trouble 27, 32trouble-free 65Uunique 19USB Adapter 72USB adapter 42, 62WWalkie Talkie 35weak 13Weak Link 57Weak link 32Wiring 16with 14, 19Without 19Yyellow 19
92 PRELIMINARY:  Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013Y–Y Index
PRELIMINARY:  Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013 93Changes & Comments  LS10036-000FL-E:N0                                                                Revise to: UL change? Brief description:
Changes & Comments LS10036-000FL-E:N094 PRELIMINARY:  Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013
Manufacturer Warranties and Limitation of LiabilityManufacturer Warranties.  Subject to the limitations set forth herein,Manufacturer warrants that the Products manufactured by it in itsNorthford, Connecticut facility and sold by it to its authorizedDistributors shall be free, under normal use and service, from defectsin material and workmanship for a period of thirty six months (36)months from the date of manufacture (effective Jan. 1, 2009).  TheProducts manufactured and sold by Manufacturer are date stamped atthe time of production. Manufacturer does not warrant Products thatare not manufactured by it in its Northford, Connecticut facility butassigns to its Distributor, to the extent possible, any warranty offeredby the manufacturer of such product.  This warranty shall be void if aProduct is altered, serviced or repaired by anyone other thanManufacturer or its authorized Distributors.  This warranty shall alsobe void if there is a failure to maintain the Products and the systems inwhich they operate in proper working conditions.MANUFACTURER MAKES NO FURTHER WARRANTIES, ANDDISCLAIMS ANY AND ALL OTHER WARRANTIES, EITHEREXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS,TRADEMARKS, PROGRAMS AND SERVICES RENDERED BYMANUFACTURER INCLUDING WITHOUT LIMITATION,INFRINGEMENT, TITLE, MERCHANTABILITY, OR   FITNESS FORANY PARTICULAR PURPOSE.  MANUFACTURER SHALL NOT BELIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAYARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL,COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.This document constitutes the only warranty made by Manufacturerwith respect to its products and replaces all previous warranties and isthe only warranty made by Manufacturer.  No increase or alteration,written or verbal, of the obligation of this warranty is authorized.Manufacturer does not represent that its products will prevent any lossby fire or otherwise.Warranty Claims.  Manufacturer shall replace or repair, atManufacturer's discretion, each part returned by its authorizedDistributor and acknowledged by Manufacturer to be defective,provided that such part shall have been returned to Manufacturer withall charges prepaid and the authorized Distributor has completedManufacturer's Return Material Authorization form.  The replacementpart shall come from Manufacturer's stock and may be new orrefurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE ANDEXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM.  Warn-HL-08-2009.fmPRELIMINARY:  Firelite Wireless Sensor Network — P/N LS10036-000FL-E:N0  10/09/2013 95
World Headquarters1 Firelite PlaceNorthford, CT 06472-1653 USA203-484-7161fax 203-484-7118www.firelite.com