Ref. Service/self service/prep case

/CHINO

Installation
& Operation
Manual

R3, R3P

R3, R3P

Refrigerated Service and/or Prep
with refrigerated
self service front

P/N IGFP-R3, R3P-0608

INSTALLATION & OPERATION GUIDE

IGFP-R3, R3P-0608

General Instructions
Table of Contents

This Booklet Contains Information on:
R3: Refrigerated Service Top/Self-Service Front Case
R3P: Service Prep Top/Refrigerated Self-Service Front
Case
R3TO: Service Top only for in-counter installation
Shipping Damage
All equipment should be thoroughly examined for shipping
damage before and during unloading.
This equipment has been carefully inspected at our factory
and the carrier has assumed responsibility for safe arrival.
If damaged, either apparent or concealed, claim must be
made to the carrier.
Apparent Loss or Damage
If there is an obvious loss or damage, it must be noted on
the freight bill or express receipt and signed by the carrier’s
agent; otherwise, carrier may refuse claim. The carrier will
supply necessary claim forms.
Concealed Loss or Damage
When loss or damage is not apparent until after equipment
is uncrated, a claim for concealed damage is made. Make
request in writing to carrier for inspection within 15 days,
and retain all packaging. The carrier will supply inspection
report and required claim forms.
Shortages
Check your shipment for any possible shortages of
material. If a shortage should exist and is found to be the
responsibility of Hussmann Chino, notify Hussmann Chino.
If such a shortage involves the carrier, notify the carrier
immediately, and request an inspection. Hussmann Chino
will acknowledge shortages within ten days from receipt
of equipment.
Hussmann Chino Product Control
The serial number and shipping date of all equipment
has been recorded in Hussmann’s files for warranty and
replacement part purposes. All correspondence pertaining
to warranty or parts ordering must include the serial number
of each piece of equipment involved, in order to provide
the customer with the correct parts.

General Instructions...............................................................2
Cut and Plan Views.................................................................3
Installation................................................................................4

Location................................................................................................... 4
Uncrating the Stand................................................................................ 4
Exterior Loading...................................................................................... 4
Glass Adjustment.................................................................................... 4
Setting and Joining.................................................................................. 4
Leveling................................................................................................... 4
Corner Wedges....................................................................................... 5
Joint Trim................................................................................................. 5
Scale Stand Installation Instructions....................................................... 5
Wrapping Boards Installation Instructions............................................... 6
Bumper Installation Instructions.............................................................. 8

Plumbing................................................................................12

Waste Outlet and P-TRAP.................................................................... 12
Installing Condensate Drain.................................................................. 12

Refrigeration..........................................................................12

Refrigerant Type.................................................................................... 12
Piping.................................................................................................... 12
Refrigeration Lines................................................................................ 12
Control Settings..................................................................................... 12
Access to TX Valves and Drain Lines................................................... 12
Electronic Expansion Valve (Optional).................................................. 13
Thermostatic Expansion Valve Location............................................... 13
Expansion Valve Adjustment................................................................. 13
Measuring the Operating Superheat..................................................... 13
Evaporator Pressure Regulator............................................................. 13
Service Case Temperature Control....................................................... 13
T-STAT Location.................................................................................... 13

Electrical................................................................................13

Wiring Color Code................................................................................. 13
Electrical Circuit Identification............................................................... 13
Electrical Service Receptacles (When Applicable)................................ 13
Field Wiring and Serial Plate Amperage............................................... 14
Ballast Location..................................................................................... 14

User Information....................................................................14

Stocking................................................................................................ 14
Cleaning Glass and Mirrors................................................................... 14
Replacing Fluorescent Lamps............................................................... 14
Non-glare Glass.................................................................................... 15
Plexiglass and Acrylic Care................................................................... 15
Cleaning................................................................................................ 15
Antistatic Coatings................................................................................ 15
Evaporator Fans.................................................................................... 15
Copper Coils......................................................................................... 15
Tips and Troubleshooting...................................................................... 15

Electrical Wiring Diagrams...................................................16
Wiring Diagrams....................................................................17
Appendices............................................................................30

Appendix A. - Temperature Guidelines.................................................. 30
Appendix B. - Application Recommendations....................................... 30
Appendix C. - Field Recommendations................................................. 30
Appendix D. - Recommendations to User............................................. 31

Keep this booklet with the case at all times for future reference.

/CHINO

This equipment is to be installed
to comply with the applicable
NEC, Federal, State , and Local
Plumbing and Construction
Code ha ving jurisdiction.

A publication of HUSSMANN® Chino
13770 Ramona Avenue • Chino, California 91710
(909) 628-8942 FAX
(909) 590-4910
(800) 395-9229



Rev. 0608	

Cut and Plan Views
11 1/4"
14
5 /8"

"

23 3/4"
18

18

Optional
Shelf

"

10"

20 5/8"

19 3/8"
12 3/8"
6"

20 5/8"

13 1/2"

36 3/8"

10"

13 1/2"

R3

50 3/8"

Ref. Service/Self-Service

R3P

Scale = 1/2"

Service Prep / Self Service Case
Scale = 1/2"

11 1/4"

26 1/8"

5 /8 "
14

36"

9 1 /2 "

24 3/4"

Your Counter

36"

R3TO

Regrigerated
Service /Self Service / Prep Case
Scale = 1/2"

10 5/8"

Prep Top Area

7

/8"

8"

8"

20

8"
40 1/2"
50 1/4"

12"

20 5/8"
19 3/8"
12"

REF.
STUB UP
18" X 18"

48"

DRAIN &
ELEC.
STUB UP
18" X 18"

6"

CASE FRONT

13 1/2"

8-2"

50 3/8"
52 1/8"

(Variable Lengths)

R3

R3 Options

Plan View = 1/4”

Sushi Service Top and Prep Areas With
Two Shelf Self Service Options
Self Contained
Scale = 1/2"



IGFP-R3, R3P-0608

Installation
Location
The refrigerated merchandisers have been designed for
use only in air conditioned stores where temperature and
humidity are maintained at or below 75°F and 55% relative
humidity. DO NOT allow air conditioning, electric fans, ovens,
open doors or windows (etc.) to create air currents around
the merchandiser, as this will impair its correct operation.
Product temperature should always be maintained at a
constant and proper temperature. This means that from the
time the product is received, through storage, preparation
and display, the temperature of the product must be
controlled to maximize life of the product.

Leveling
IMPORTANT! IT IS IMPERATIVE THAT CASES BE
LEVELED FROM FRONT TO BACK AND SIDE TO SIDE
PRIOR TO JOINING. A LEVEL CASE IS NECESSARY
TO INSURE PROPER OPERATION, WATER DRAINAGE,
PLEXIGLASS ALIGNMENT.
NOTE: 	 A. To avoid removing concrete flooring, begin lineup 		
leveling from the highest point of the store floor.
	

B. When wedges are involved in a lineup, set them first.

All cases were leveled and joined prior to shipment to
insure the closest possible fit when cases are joined in
the field. When joining, use a carpenters level and shim
legs accordingly. Case must be raised correctly, under legs
where support is best, to prevent damage to case.
1. 	 Check level of floor where cases are to be set.
Determine the highest point of the floor; cases will
be set off this point.
2. 	 Set first case, and adjust legs over the highest part
of the floor so that case is level. Prevent
damage - case must be raised under leg or by use
of 2x6 or 2x4 leg brace. Remove side and back leg
braces after case is set.
3. 	 Set second case as close as possible to the first
case and level case to the first using the instructions
in step one.
4. 	 Apply masking tape 1/8” in from end of case on
inside and outside rear mullion on both cases to be
joined.
5. 	 Apply liberal bead of case joint sealant (butyl) to
(dotted area shown in figure) first case. Apply heavy
amount to cover entire shaded area.
DO NOT USE PERMAGUM!

Uncrating the Stand
Place the fixture as close to its permanent position as
possible. Remove the top of the crate. Detach the walls
from each other and remove from the skid. Unbolt the case
from the skid. The fixture can now be lifted off the crate
skid. Lift only at base of stand!
Exterior Loading
These models have not been structurally designed to
support excessive external loading. Do not walk on their
tops; This could cause serious personal injury and damage
to the fixture.

GLASS BREAKAGE MAY OCCUR!
Retighten glass along clamshell after
leveling and first time case is brought
to full operating temperature!
Glass Adjustment
During shipment, the lubricant inside the cylinders may
have settled. This settling may cause excessive or uneven
tension on the glass - to the point of breakage. To avoid
any damage, please follow these three easy steps:
1. 	 Slowly raise and lower each glass section 6 times to
a height of 6 inches.
2. 	 Increase the height to 12 inches, and raise and
lower the glass 6 more times.
3. 	 Finally raise the glass to its full extension, and lower.
These steps should release any settled lubricant within the
cylinders and prevent any stress on the front glass.

It is the contractor’s responsibility to install
case(s) according to local construction and
health codes.
6. 	 Slide second case up to first case snugly. Then level
second case to the first case so glass front, bumper
and top are flush.
7. 	 To compress silicone at joint, use two Jurgenson wood
clamps. Make sure case is level from front to back and
side to side on inside bulkheads at joint.
8. 	 Attach sections together via a 2 bolts located in the
base of the case. Secure the overhead structure by
bolting the bracket, located inside behind lights.
9. 	 Apply bead of silicone to top of bulkheads and slip
on stainless steel bulkhead cap. Also apply silicone
to seam between overhead light tubes.

Setting and Joining
The sectional construction of these models enable them to
be joined in line to give the effect of one continuous display.
A joint trim kit is supplied with each joint.



Rev. 0608	

Installation (Cont'd)
Joint Trim
After cases have been leveled and joined, and refrigeration,
electrical, and wasted piping work completed, install the
splashguards. Fasten along the top edge, or center, with
#10 X 3/3” sheet metal screws.
DO NOT SEAL JOINT TRIM TO FLOOR!

10.	Use finger to smooth silicone as thin as possible at
masking tape on inside and outside of rear mullion
(apply additional silicone if necessary). Remove
tape applied on line #3.
Corner Wedges
Corner wedges are attached via front and rear camlocks.
Use a 7mm allen wrench to turn the locks. Do not
overtighten! Join the top by using a joint bracket (included
in joint kit) with 3/8” bolts.
Scale Stand Installation Instructions

1.- Set Scale Stand to desire location

2.- Drill holes and screw in place
(with screws provided – Hex Tek S/S
10-16 X ½”)

Note: Use hole pattern



IGFP-R3, R3P-0608

Installation (Cont'd)
Wrapping Boards Installation Instructions

Step 2: Measure 10 inches from top of the case.

Step 1: Measure 6 inches from wrapping board end.
					

Note: Line up 6 inch mark with 10 inch mark.

Step 3: Use bracket center hole to align with cross mark.
Note: Use pencil/marker to mark hole pattern.

HOLE PATTERN
		

Step 4: Drill holes (7/32”)

Screws # 14 X 1”
				

Step 5: Install bracket with screws (provided)

Note: Repeat Steps 1 Thru 5 for Second Bracket Installation.



Rev. 0608	

Installation (Cont'd)

Step 6: Install upper
support bracket

Step 7: Mount wrap board on top of bracket using a ¼”
spacer to have a gap between rear wall and board.

	
	

Step 8: screw bracket into wrap board
(screws provided -#8 X 1 ¼”)

Installation Complete



IGFP-R3, R3P-0608

Installation (Cont'd)
Bumper Installation Instructions

Step 2:	 Use silicone lubricant to help the 			
	
bumper	slide into the channel.

Step 1: 	Make sure the aluminum channel and end caps 		
	
are installed.

Step 3:	 Starting on one end: while inserting the bumper, 		
	
push it up against the end cap to prevent 		
	
the bumper from shrinking after installation 		
	
(when it gets cold).

Step 4:	 As you insert the bumper into the channel with 		
	
one hand, pull the bumper toward you with 		
	
the other to open the inside lips. Slowly 			
	
apply pressure by rolling the bumper into 		
	
the track.



Rev. 0608	

Installation (Cont'd)
Boston Series 2000
NOTE: 	 Flexible top: Over cut vinyl 1/8" for every 4' section for the flexible top to ensure a proper fit.
NOTE: 	 Rigid Top: Do not over cut.

1. 	 Attach the base and end/corner cap to the desired surface by inserting #8 pan head screws through the pre-slotted
holes in both the end cap and the base. Insert screws through the two holes of end cap and tighten.

2a. 	Flexible Top: Butt end of the vinyl top against end/corner cap. While applying pressure, bend back vinyl top so that
vinyl legs are positioned within the base grooves. Roll vinyl top over full length of base, then tap with rubber mallet
to ensure vinyl is securely locked into the base.
2b. 	Rigid Top: Snap the Rigid Top over the Rigid Base.

3. If necessary wipe clean with any household cleaning product.
Helpful Hints:
● 	 For best results, before cutting, install a scrap piece of base into vinyl top to achieve a clean cut.
● 	 Set the uncoiled flexible vinyl at room temperature 24 hours prior to installation.
● 	 Lubricate the inside of the vinyl with soapy water or silicone before installing.
● 	 Over cut the flexible vinyl and compression fit. Adding the additional materials will compensate for stretching which
occurs during installation.



IGFP-R3, R3P-0608

Installation (Cont'd)
Boston 2000 Eco Series

1. 	 Attach the base and end/corner cap to the desired surface by inserting #8 pan head screws through the pre-slotted
holes in both the end cap and the base. Insert screws through the two holes of end cap and tighten.

2a. 	Flexible Top: Butt end of the vinyl top against end/corner cap. While applying pressure, bend back vinyl top so that
vinyl legs are positioned within the base grooves. Roll vinyl top over full length of base, then tap with rubber mallet
to ensure vinyl is securely locked into the base.
2b. 	Rigid Top: Snap the Rigid Top over the Rigid Base.

3. 	 If necessary wipe clean with any household cleaning product.
Helpful Hints:
● 	 For best results, before cutting, install a scrap piece of base into vinyl top to achieve a clean cut.
● 	 Set the uncoiled flexible vinyl at room temperature 24 hours prior to installation.
● 	 Lubricate the inside of the vinyl with soapy water or silicone before installing.
● 	 Over cut the flexible vinyl and compression fit. Adding the additional materials will compensate for stretching which
occurs during installation.

10

Rev. 0608	

Installation (Cont'd)
Boston 1000 Series
NOTE: 	 Flexible top: Over cut vinyl 1/8" for every 4' section for the flexible top to ensure a proper fit.
NOTE: 	 Rigid Top: Do not over cut.

Installation

1. 	 Attach the base and end/corner cap to the desired surface by inserting #8 pan head screws through the pre-slotted
holes in both the end cap and the base. Insert screws through the two holes of end cap and tighten.

2a. 	Flexible Top: Butt end of the vinyl top against end/corner cap. While applying pressure, bend back vinyl top so that
vinyl legs are positioned within the base grooves. Roll vinyl top over full length of base, then tap with rubber mallet
to ensure vinyl is securely locked into the base.
2b. 	Rigid Top: Snap the Rigid Top over the Rigid Base.

3. 	 If necessary wipe clean with any household cleaning product.
Helpful Hints:
● 	 For best results, before cutting, install a scrap piece of base into vinyl top to achieve a clean cut.
● 	 Set the uncoiled flexible vinyl at room temperature 24 hours prior to installation.
● 	 Lubricate the inside of the vinyl with soapy water or silicone before installing.
● 	 Over cut the flexible vinyl and compression fit. Adding the additional materials will compensate for stretching which
occurs during installation.

11

IGFP-R3, R3P-0608

Plumbing
Waste Outlet and P-TRAP
The waste outlet is located off the center of the case on
one side allowing drip piping to be run lengthwise under
the fixture. There are 3 drains in each fixture that can be
easily located.
1-1/2", 1" and 3/4" P-TRAPS and threaded adapters
are supplied with each fixture. The 3 P-TRAPS must be
installed to prevent air leakage and insect entrance into
the fixture.

3. 	 Always provide as much down hill slope ("fall") as
possible; 1/8" per foot is the preferred minimum.
PVC pipe, when used, must be supported to
maintain the 1/8" pitch and to prevent warping.
4. 	 Avoid long runs of condensate drains. Long runs
make it impossible to provide the "fall" necessary for
good drainage.
5. 	 Provide a suitable air break between the flood rim of
the floor drain and outlet of condensate drain. 1" is
ideal.
6. 	 Prevent condensate drains from freezing:
a. Do not install condensate drains in contact with
non-insulated suction lines. Suction lines should
be insulated with a non - absorbent insulation
material such as Armstrong's Armaflex.
b. Where condensate drains are located in dead
air spaces (between refrigerators or between a
refrigerator and a wall), provide means to prevent
freezing. The water seal should be insulated to
prevent condensation.

NOTE: 	 PVC-DWV solvent cement is recommended. Follow the
manufacturer’s instructions.

Installing Condensate Drain
Poorly or improperly installed condensate drains can
seriously interfere with the operation of this refrigerator, and
result in costly maintenance and product losses. Please
follow the recommendations listed below when installing
condensate drains to insure a proper installation:
1. 	 Never use pipe for condensate drains smaller
than the nominal diameter of the pipe or P-TRAP
supplied with the case.
2. 	 When connecting condensate drains, the P-TRAP
must be used as part of the condensate drain
to prevent air leakage or insect entrance. Store
plumbing system floor drains should be at least 14"
off the center of the case to allow use of the P-TRAP
pipe section. Never use two water seals in series in
any one line. Double P-TRAPS in series will cause a
lock and prevent draining.

Refrigeration

Refrigerant Type
The standard refrigerant will be R-22 unless otherwise
specified on the customer order. Check the serial plate on
the case for information.

Control Settings
See R3, R3P technical data sheet for the appropriate
settings for your merchandiser. Maintain these parameters
to achieve near constant product temperatures. Product
temperature should be measured first thing in the morning,
after having been refrigerated overnight. Defrost times
should be as follows: OFF CYCLE - Defrost times should
be as directed in the R3, R3P technical data sheet. The
number of defrosts per day and the duration of the defrost
cycle may be adjusted to meet conditions present at your
location.

Piping
The refrigerant line outlets are located under the case.
Locate first the electrical box, the outlets are then on the
same side of the case but at the opposite end. Insulate
suction lines to prevent condensation drippage.
Refrigeration Lines

Liquid
3/8” O.D.

Suction
5/8” O.D.

Access to TX Valves and Drain Lines
Mechanical - Remove product from end of case. Remove
product racks. Remove refrigeration and drain access
panels (labeled). TX valve (mechanical only) and drain are
located under each access panel at end of the case.
Electronic - The Electronic Expansion valve master and
slave cylinder(s) are located within the electrical access
panel(s).

NOTE: 	The standard coil is piped at 5/8” (suction); however,
the store tie-in may vary depending on the number of
coils and the draw the case has. Depending on the case
setup, the connecting point in the store may be 5/8”, 7/8”,
or 11/8”. Refer to the particular case you are hooking up.

Refrigerant lines should be sized as shown on the
refrigeration legend furnished by the store.
Install P-TRAPS (oil traps) at the base of all suction line
vertical risers.
Pressure drop can rob the system of capacity. To keep the
pressure drop to a minimum, keep refrigerant line run as
short as possible, using the minimum number of elbows.
Where elbows are required, use long radius elbows only.

12

Rev. 0608	

Refrigeration (Cont'd)
Electronic Expansion Valve (Optional)
A wide variety of electronic expansion valves and case
controllers can be utilized. Please refer to EEV and
controller manufacturers information sheet. Sensors for
electronic expansion valves will be installed on the coil inlet,
coil outlet, and in the discharge air. (Some supermarkets
require a 4th sensor in the return air). Case controllers will
be located in the electrical raceway or under the case. The
front Self Service Evaporator has an EPR valve installed to
maintain a constant discharge temperature. It is located in
the front at the right side of the case under the fan plenum
near the TX valve.

4. 	 Subtract the saturation temperature obtained in step
No. 2 from the temperature measured in step No. 3.
The difference is superheat.
5. 	 Set the superheat for 5°F - 7°F.
Evaporator Pressure Regulator
An Evaporator Pressure Regulator is installed in the front
of the self service section to maintain a constant discharge
temperature. It is located at the front right side of the case,
under the fan plenum near the TX Valve.
Service Case Temperature Control
Temperature control in the upper section of the R3 with
the Service Option is done by means of a thermostat and
suction solenoid valve. This controls both temperature
and humidity.

Thermostatic Expansion Valve Location
This device is located on the same side as the refrigeration
stub. A Sporlan balanced port expansion valve model
is furnished as standard equipment, unless otherwise
specified by customer.

T-STAT Location
T-STATS are located within the electrical raceway. Refer
to diagram below.

Expansion Valve Adjustment
Expansion valves must be adjusted to fully feed the
evaporator. Before attempting any adjustments, make
sure the evaporator is either clear or very lightly covered
with frost, and that the fixture is within 10°F of its expected
operating temperature.

Rear Storage
T-Stat and
Solenoid inside
Storage Area
T-Stat &
Ballast

Measuring the Operating Superheat
1. 	 Determine the suction pressure with an accurate
pressure gauge at the evaporator outlet.
2. 	 From a refrigerant pressure temperature chart,
determine the saturation temperature at the
observed suction pressure.
3. 	 Measure the temperature of the suction gas at the
thermostatic remote bulb location.

(Located in the
same place for
hot and cold)

Front Coils
controlled by
EPR Valve
under Deck Pan

(Right side)

Electrical
Wiring Color Code

Electrical Circuit Identification
Standard lighting for all refrigerated models will be full
length fluorescent lamps located within the case at the
top.
The switch controlling the lights, the plug provided for
digital scale, and the thermometer are located at the rear
of the case mullion.
The receptacle that is provided on the exterior back of these
models is intended for computerized scales with a five amp
maximum load, not for large motors or other high wattage
appliances. It should be wired to a dedicated circuit.
Electrical Service Receptacles (When Applicable)
The receptacles located on the exterior of the merchandiser
are intended for scales and lighted displays. They are not
intended nor suitable for large motors or other external
appliances.

CASE MUST BE GROUNDED
NOTE: 	 Refer to label affixed to case to determine the actual
configuration as checked in the “TYPE INSTALLED”
boxes.

13

IGFP-R3, R3P-0608

Electrical (Cont'd)
Field Wiring and Serial Plate Amperage
Field Wiring must be sized for component amperes printed
on the serial plate. Actual ampere draw may be less than
specified. Field wiring from the refrigeration control panel to
the merchandisers is required for refrigeration thermostats.
Most component amperes are listed in the “Case Specs”
section, but always check the serial plate.

BEFORE SERVICING
ALWAYS DISCONNECT ELECTRICAL
POWER AT THE MAIN DISCONNECT
WHEN SERVICING OR REPLACING ANY
ELECTRICAL COMPONENT.
This includes (but not limited to) Fans, Heaters
Thermostats, and Lights.

Ballast Location
Ballasts are located within the access panel that runs the
length of the rear of the case.

User Information

Stocking
Improper temperature and lighting will cause serious
product loss. Discoloration, dehydration and spoilage
can be controlled with proper use of the equipment and
handling of product. Product temperature should always
be maintained at a constant and proper temperature.
This means that from the time the product is received,
through storage, preparation and display, the temperature
of the product must be controlled to maximize life of the
product. Hussmann cases were not designed to “heat up”
or “cool down” product - but rather to maintain an item’s
proper temperature for maximum shelf life. To achieve the
protection required always:
1. 	 Minimize processing time to avoid damaging
temperature rise to the product. Product should be
at proper temperature.
2. 	 Keep the air in and around the case area free
of foreign gasses and fumes or food will rapidly
deteriorate.
3. 	 Maintain the display merchandisers temperature
controls as outlined in the refrigerator section of this
manual.
4. 	 Do not place any product into these refrigerators
until all controls have been adjusted and they
are operating at the proper temperature. Allow
merchandiser to operate a minimum of 6 hours
before stocking with any product.
5. 	 When stocking, never allow the product to extend
beyond the recommended load limit. Air discharge
and return air flow must be unobstructed at all
times to provide proper refrigeration.
6.	 Keep the service doors closed (when applicable).
Refrigeration performance will be seriously affected
if left open for a prolonged period of time.
7. 	 Avoid the use of supplemental flood or spot lighting.
Display light intensity has been designed for
maximum visibility and product life at the factory.
The use of higher output fluorescent lamps (H.O.
and V.H.O.), will shorten the shelf life of the product.

FOR PROMPT SERVICE
When Contacting the Factory regarding problems.
Be sure to have the Case MODEL and
SERIAL NUMBER Handy. This Information
is on a plate located on the case itself.

Cleaning Glass and Mirrors
Only use a soft cloth and mild glass cleaning for cleaning
any glass or mirrored components. Be sure to rinse and/or
dry completely.
Never use hot water on cold glass surfaces! It may
shatter and cause serious injury! Allow glass surfaces
to warm first.
Replacing Fluorescent Lamps
Fluorescent lamps are furnished with a shatterproof
protective coating. The same type of lamp with protective
coating must be used if replaced.

RU
R

ENCAPSULITE
SHATTERPROOF COATING - SA 10645
Complies with FDA USDA

& OSHA Regulations
for replacement call:
1-800-395-9229

Turn switch off then on after replacing bulb

14

NSF

Rev. 0608	

User Information (Cont'd)
Non-glare Glass
Windex® or Glass Plus® are the only solutions recommended
to be used to clean the non-glare glass. The damage to the
glass from improper, caustic solutions is irreparable.
In addition to cleaning the glass with the recommended
product, there are precautions that should be taken when
working and cleaning the inside of the case.
• 	 When cleaning the inside of the cases, we
recommend that the glass be fully opened and
covered to prevent to prevent solutions from
splashing onto the glass and ruining the coating on
the inside.
Plexiglass and Acrylic Care
Improper cleaning not only accelerates the cleaning cycle
but also degrades the quality of this surface. Normal daily
buffing motions can generated static cling attracting dust
to the surface. Incorrect cleaning agents or cleaning cloths
can cause micro scratching of the surface, causing the
plastic to haze over time.

CLEANING PRECAUTIONS

When cleaning:

• Do not use high pressure water hoses
• Do not introduce water faster than waste outlet can drain
• NEVER ON A SELF CONTAINED UNIT WITH AN EVAPORATOR FAN
• NEVER USE A CLEANING OR SANITIZING SOLUTION THAT HAS AN OIL
BASE (these will dissolve the butyl sealants) or an AMMONIA BASE
(this will corrode the copper componets of the case)

TO PRESERVE THE ATTRACTIVE FINISH:

• DO USE WATER AND A MILD DETERGENT FOR THE EXTERIOR ONLY
• DO NOT USE ABRASIVES OR STEEL WOOL SCOURING PADS
(these will mar the finish)
Evaporator Fans
The evaporator fans are located at the center front of these
merchandisers directly beneath the display pans. Should
fans or blades need servicing, always replace fan blades
with the raised embossed side of the blade TOWARD THE
MOTOR.

Cleaning
Hussmann recommends using a clean damp chamois, or a
paper towel marketed as dust and abrasive free with 210®
Plastic Cleaner and Polish available by calling Sumner
Labs at 1-800-542-8656. Hard, rough cloths or paper towels
will scratch the acrylic and should not be used.

Copper Coils
The copper coils used in Hussmann merchandisers may
be repaired in the field. Materials are available from local
refrigeration wholesalers.
Hussmann recommends using #15 Sil-Fos for repairs.

Antistatic Coatings
The 210® has proven to be very effective in not only
cleaning and polishing the Plexiglass surface, but also
providing antistatic and anti-fog capabilities. This product
also seals pores and provides a protective coating.

Tips and Troubleshooting
Before calling for service, check the following:
1. 	 Check electrical power supply to the equipment for
connection.
2. 	 Check fixture loading. Overstocking case will affect
its proper operation.
3. 	 If frost is collecting on fixture and/or product,
check that no outside doors or windows are
open - allowing moisture to enter store. These
merchandisers were designed for use in stores were
temperature & humidity does not exceed 75° F and
55% H.

15

IGFP-R3, R3P-0608

Electrical Wiring Diagrams
R3 Prep

4'

W0180047

6'

W0180048

8'

W0180049

12'

W0180051

R3-P-8-REM

8'

W1800167

R3-P-4-REM WALMART

4'

W1800172

R3-P-6-REM WALMART

6'

W1800173

R3 Top Only - Cold

4'

W0180101

6'

W0180102

8'

W0180103

12'

W0180105

4'

W1800122

R3TO 2000 S/C

TOP ONLY BLOWER

16

Hussmann Corporation, Int'l.
13770 Ramona Avenue
Chino, CA. 91710
(909)-590-4910 Lic.#: 644406

?

LIGHT SWITCH
TIPPETTE
125-01-0311

DATE:
8/29/07

REVISIONS:
#: DESCRIPTION:

A

Updated dwg; revised load ratings; removed fuse

L

LIGHT
CIRCUIT
TAG ORANGE

M

L1 N
~120 VAC - 60 Hz.
MCA= .65A
MOP= 15A

M

R3 & CR3 - 4 PREP CASES

R3 & CR3 CASES

FAN CIRCUIT
TAG BROWN

EVAP FAN MOTORS
(2) 4W .29A @ 120VAC
0392457

LIGHT CIRCUIT= .26A, 28W

DRAWN BY:
D.QUAN
PROJECT TITLE:
DATE: 03/17/06
BY: CHECKED BY:
PRODUCTION ORDER #:
DRAWING TITLE:
JR
FILE LOCATION:

N
L1
~120 VAC - 60 Hz.
MCA= .33A
MOP= 15A

BLACK # 14

NOTE: CASE MUST
BE GROUNDED

F28T5-48"
125-03-1131
WHITE # 14

CAP OFF
WIRE
BALLAST 125-01-3266
FULHAM LH3-120-L

LOADING
120 V
L1 1.5

BLACK # 14

17
WHITE # 14

CIRCUIT #1 36W

DRAWING #:

PAGE 1 OF 1

W0180047

Rev. 0608	

Wiring Diagrams

Hussmann Corporation, Int'l.
13770 Ramona Avenue
Chino, CA. 91710
(909)-590-4910 Lic.#: 644406

?

LIGHT SWITCH
TIPPETTE
125-01-0311

FP21/830 T5-36"
125-03-1131
L

8/29/07

A

Updated dwg; revised load ratings; removed fuse

DATE:

REVISIONS:
#: DESCRIPTION:

M

FAN MOTOR
CIRCUIT
TAG BROWN

M

M

R3 & CR3 CASES
R3 & CR3 - 6 PREP CASES

DRAWN BY:
D.QUAN
PROJECT TITLE:
DATE: 03/17/06
BY: CHECKED BY:
PRODUCTION
ORDER
#:
DRAWING
TITLE:
JR
FILE LOCATION:

L1 N
~120 VAC - 60 Hz.
MCA= 1.2A
MOP= 15A

M

EVAP FAN MOTORS
(4) 4W .29A @ 120VAC
0392457

LIGHT CIRCUIT= .39A, 42W

LIGHT CIRCUIT
TAG ORANGE

FP21/830 T5-36"
125-03-1131

BALLAST 125-01-3266
FULHAM LH3-120-L

N
L1
~120 VAC - 60 Hz.
MCA= .49A
MOP= 15A

BLACK # 14

NOTE: CASE MUST
BE GROUNDED

BLACK # 14

LOADING
120 V
L1 1.6

WHITE # 14

18
WHITE # 14

CIRCUIT #1 58W

DRAWING #:

PAGE 1 OF 1

W0180048

IGFP-R3, R3P-0608

Wiring Diagrams (Cont'd)

Hussmann Corporation, Int'l.
13770 Ramona Avenue
Chino, CA. 91710
(909)-590-4910 Lic.#: 644406

?

LIGHT SWITCH
TIPPETTE
125-01-0311

DATE:
8/29/07

A

Updated dwg; revised load ratings; removed fuse

L

LIGHT CIRCUIT
TAG ORANGE

M

L1 N
~120 VAC - 60 Hz.
MCA= 1.2A
MOP= 15A

M

M

R3 & CR3 - 8 PREP CASES

R3 & CR3 CASES

FAN CIRCUIT
TAG "BOTTOM"
BROWN

M

EVAP FAN MOTORS
(4) 4W .29A @ 120VAC
0392457

LIGHT CIRCUIT= .52A, 56W

DRAWN BY:
D.QUAN
PROJECT TITLE:
DATE: 03/17/06
BY: CHECKED BY:
PRODUCTION ORDER #:
DRAWING TITLE:
JR
FILE LOCATION:

N
L1
~120 VAC - 60 Hz.
MCA= .65A
MOP= 15A

REVISIONS:
#: DESCRIPTION:

NOTE: CASE MUST
BE GROUNDED

BLACK # 14

F28T5-48"
125-03-1131

BALLAST 125-01-3266
FULHAM LH3-120-L

LOADING
120 V
L1 1.7

BLACK # 14

F28T5-48"
125-03-1131
WHITE # 14

19
WHITE # 14

CIRCUIT #1 72W

DRAWING #:

PAGE 1 OF 1

W0180049

Rev. 0608	

Wiring Diagrams (Cont'd)

Hussmann Corporation, Int'l.
13770 Ramona Avenue
Chino, CA. 91710
(909)-590-4910 Lic.#: 644406

?

LIGHT SWITCH
TIPPETTE
125-01-0311

F28T5-48"
125-03-1131
L

8/29/07

A

Updated dwg; revised load ratings; removed fuse

DATE:

REVISIONS:
#: DESCRIPTION:

M

FAN MOTOR
TAG BROWN

M

M

EVAP FAN MOTORS
(6) 4W .29A @ 120VAC
0392457

M

R3 & CR3 CASES

M

R3 & CR3 - 12 PREP CASES

DRAWN BY:
D.QUAN
PROJECT TITLE:
DATE: 03/17/06
BY: CHECKED BY:
PRODUCTION
ORDER
#:
DRAWING
TITLE:
JR
FILE LOCATION:

L1 N
~120 VAC - 60 Hz.
MCA= 1.8A
MOP= 15A

M

LIGHT CIRCUIT= .52A, 56W

LIGHT CIRCUIT
TAG ORANGE

F28T5-48"
125-03-1131

BALLAST 125-01-3266
FULHAM LH3-120-L

N
L1
~120 VAC - 60 Hz.
MCA= .65A
MOP= 15A

BLACK # 14

20
WHITE # 14

NOTE: CASE MUST
BE GROUNDED

BLACK # 14

LOADING
120 V
L1 2.3

WHITE # 14

CIRCUIT #1 80W

DRAWING #:

PAGE 1 OF 1

W0180051

IGFP-R3, R3P-0608

Wiring Diagrams (Cont'd)

21

BLACK #14

WHITE #14

Hussmann Corporation, Int'l.
13770 Ramona Avenue
Chino, CA. 91710
(909)-590-4910 Lic.#: 644406

MCA= .59A
MOP= 15A

L1 N
~120 VAC - 60 Hz

?

BUNDLE
BROWN
LABELED
FAN CIRCUIT

M

REVISIONS:
#: DESCRIPTION:

MCA= 1.23A
MOP= 15A

L1 N
~120 VAC - 1Ø - 60 Hz

BUNDLE
ORANGE
LABELED
LIGHT CIRCUIT

WHITE #14

F28T5-48"
125-03-1131

L

M
M

M

N

MCA= 2.0A
MOP= 15A

DATE:

G

BK

CIRCUIT #2

BLK # 14
RED # 14

CONTACTOR
SQUARE -D
8910DPA43V02
125-01-1001

BUNDLE
YELLOW
LABELED
RECEPTACLE
CIRCUIT

MCA= 3.58A
MOP= 15A

~208 / ~240 VAC - 50/60 HZ

GRN # 14

L

SWITCH
TIPPETTE
125-01-0311

BOHN COIL ASSY
(1) VA-08 120V 0.8A
225-02-0513

W

DUPLEX
125-01-3178
CIRCUIT # 3

7

PACKTRONICS
CONTROLLER
225-01-3229

R3-P-8-REM

1 2 3 4 5 6

P1

TEMP. CONTROL

L

BUNDLE
PURPLE
LABELED
HEATER
CIRCUIT

WARMER
125-01-0767
TYCO
THERMAL
CONTROLS
10BTV1-CR
80 WATTS
0.67AMP@120V

DRAWING #:

MCA= .84A
MOP= 15A

LI N
~120 VAC - 1Ø - 50/60 Hz.

PILOT LIGHT
175-01-1102C

GRIDDLE HEATER - THERMOFLEX™
(2) 342 W, 1.43A @ 240 VAC
225-01-6787T

DRAWN BY:
JESSE RIOS
PROJECT TITLE:
DATE: 5/14/07
BY: CHECKED BY:
PRODUCTION ORDER #: 914276
DRAWING TITLE:
FILE LOCATION:

N
G

BUNDLE
WHITE/BLACK
LABELED
THERMOSTAT
CIRCUIT
L1
L2

T-STAT
(1) 225-01-0710

~120 VAC - 60 Hz

L1

BLACK #14

F28T5-48"
125-03-1131

BALLAST 125-01-3266
FULHAM LH3-120-L

FAN MOTOR
0.29 AMP @ 120VAC
(4) 0392457

BLACK #14

SUCTION SOLENOID
(1) 225-01-3206

WHITE #14

SENSOR
COMTROL
90TB002G01
225-01-2028

BLACK #14

RJ-45 NETWORK JACK
125-01-0202

WHT # 14

SENSOR
225-01-3228

LIGHT CIRCUIT= .47A

PAGE 1 OF 2

W1800167

Rev. 0608	

Wiring Diagrams (Cont'd)

22

Hussmann Corporation, Int'l.
13770 Ramona Avenue
Chino, CA. 91710
(909)-590-4910 Lic.#: 644406

?

REVISIONS:
#: DESCRIPTION:

NOTE: CASE MUST
BE GROUNDED

LOADING
120 V
L1 15.0
L2
L3

CIRCUIT #3

NOTE: CASE MUST
BE GROUNDED

LOADING
208 V 240V
5.7
L1 5.0
5.7
L2 5.0
L3

CIRCUIT #2

NOTE: CASE MUST
BE GROUNDED

LOADING
120 V
L1 3.9
L2
L3

CIRCUIT #1

DATE:

R3-P-8REM

DRAWN BY:
JESSE RIOS
PROJECT TITLE:
DATE: 4/12/07
BY: CHECKED BY:
PRODUCTION ORDER #: 914276
DRAWING TITLE:
FILE LOCATION:

DRAWING #:

PAGE 2 OF 2

W1800167

IGFP-R3, R3P-0608

Wiring Diagrams (Cont'd)

Hussmann Corporation, Int'l.
13770 Ramona Avenue
Chino, CA. 91710
(909)-590-4910 Lic.#: 644406

LIGHT SWITCH
TIPPETTE
125-01-0311

NOTE: CASE MUST
BE GROUNDED

?

REVISIONS:
#: DESCRIPTION:

MCA= .59A
MOP= 15A

SENSOR
225-01-3072

M

BUNDLE
BROWN
LABELED
FAN CIRCUIT

M

FAN MOTOR
0.29 AMP @ 120VAC
(2) 0392457

BLACK #14

WHITE #14

MCA= 0.65A
MOP= 15A

L1 N
~120 VAC - 1Ø - 60 Hz

BUNDLE
ORANGE
LABELED
LIGHT CIRCUIT

L

F28T5-48"
125-03-1131

BALLAST 125-01-3266
FULHAM LH3-120-L

L1 N
~120 VAC - 60 Hz

WHITE #14

23

BLACK #14

F28T5-48"
125-03-1131

LIGHT CIRCUIT= .47A

L1

DATE:

BOHN COIL ASSY
(1) VA-08 120V 0.8A
225-02-0513

BUNDLE
YELLOW
LABELED
RECEPTACLE
CIRCUIT

LOADING
120 V
L1 15.0
L2
L3

R3-P-4-REM

R3

MCA= .41A
MOP= 15A

LI N
~120 VAC - 1Ø - 50/60 Hz.

BUNDLE
PURPLE
LABELED
HEATER
CIRCUIT

WARMER (4ft)
125-01-0767
TYCO
THERMAL
CONTROLS
10BTV1-CR
40 WATTS
0.33AMP@120V

ALL SINGLE
RECEPTACLES TO BE
TIED TO DUPLEX
GFCI RECEPTACLE

GFCI
DUPLEX
125-01-3178

DRAWING #:

LOAD SIDE POWER
~120 VAC -60 Hz
125-01-0443

NOTE FOR GFCI PROTECTION: IF MORE THAN ONE
SINGLE RECEPTACLE IS USED IN CONJUNCTION WITH
A GFCI DUPLEX RECEPTACLE "DOWNSTREAM" ON
THE LOAD SIDE, THE SUM OF ALL RECEPTACLES
SHOULD NOT BE MORE THAN 15A

INCOMING POWER
~120 VAC -60 Hz

WHT # 14

CIRCUIT # 2 (optional)

GRN # 14

DRAWN BY:
JESSE RIOS
PROJECT TITLE:
DATE: 6/27/07
BY: CHECKED BY:
PRODUCTION ORDER #: 914520
DRAWING TITLE:
FILE LOCATION:

MCA= 1.0A
MOP= 15A

~120 VAC - 60 Hz

N

BUNDLE
WHITE/BLACK
LABELED
THERMOSTAT
CIRCUIT

T-STAT
(1) 225-01-0710

SUCTION SOLENOID
(1) 225-01-3206

RJ-45 NETWORK JACK
125-01-0202

WHITE #14

LOADING
120 V
L1 2.2
L2
L3

BLACK #14

BLK # 14

CIRCUIT #1

PAGE 1 OF 1

W1800172

Rev. 0608	

Wiring Diagrams (Cont'd)

Hussmann Corporation, Int'l.
13770 Ramona Avenue
Chino, CA. 91710
(909)-590-4910 Lic.#: 644406

F21T5-36"
125-03-1128

?

F21T5-36"
125-03-1128

REVISIONS:
#: DESCRIPTION:

MCA= .88A
MOP= 15A

F21T5-36"
125-03-1128

BALLAST 125-01-3266
FULHAM LH3-120-L

BUNDLE
ORANGE
LABELED
LIGHT CIRCUIT

L

F21T5-36"
125-03-1128

BALLAST 125-01-3266
FULHAM LH3-120-L

L1 N
~120 VAC - 60 Hz

WHITE #14

24

BLACK #14

LIGHT SWITCH
TIPPETTE
125-01-0311

NOTE: CASE MUST
BE GROUNDED

M

WHITE #14

MCA= 0.65A
MOP= 15A

L1 N
~120 VAC - 1Ø - 60 Hz

BUNDLE
BROWN
LABELED
FAN CIRCUIT

M

DATE:

SENSOR
225-01-3072

FAN MOTOR
0.29 AMP @ 120VAC
(2) 0392457

BLACK #14

LIGHT CIRCUIT= 0.7A

L1

R3

MCA= .63A
MOP= 15A

LI N
~120 VAC - 1Ø - 50/60 Hz.

BUNDLE
PURPLE
LABELED
HEATER
CIRCUIT

WARMER (6ft)
125-01-0767
TYCO
THERMAL
CONTROLS
10BTV1-CR
60 WATTS
0.5AMP@120V

DRAWING #:

PAGE 1 OF 1

W1800173

LOAD SIDE POWER
~120 VAC -60 Hz
125-01-0443

ALL SINGLE
RECEPTACLES TO BE
TIED TO DUPLEX
GFCI RECEPTACLE

GFCI
DUPLEX
125-01-3178

INCOMING POWER
~120 VAC -60 Hz

R3-P-6-REM

BOHN COIL ASSY
(1) VA-012 120V 1.6A
225-02-133

BUNDLE
YELLOW
LABELED
RECEPTACLE
CIRCUIT

LOADING
120 V
L1 15.0
L2
L3

NOTE FOR GFCI PROTECTION: IF MORE THAN ONE
SINGLE RECEPTACLE IS USED IN CONJUNCTION WITH
A GFCI DUPLEX RECEPTACLE "DOWNSTREAM" ON
THE LOAD SIDE, THE SUM OF ALL RECEPTACLES
SHOULD NOT BE MORE THAN 15A

GRN # 14

CIRCUIT # 2 (optional)

WHT # 14

DRAWN BY:
JESSE RIOS
PROJECT TITLE:
DATE: 6/27/07
BY: CHECKED BY:
PRODUCTION ORDER #: 914522
DRAWING TITLE:
FILE LOCATION:

MCA= 2.0A
MOP= 15A

~120 VAC - 60 Hz

N

BUNDLE
WHITE/BLACK
LABELED
THERMOSTAT
CIRCUIT

T-STAT
(1) 225-01-0710

SUCTION SOLENOID
(1) 225-01-3206

RJ-45 NETWORK JACK
125-01-0202

WHITE #14

LOADING
120 V
L1 3.4
L2
L3

BLACK #14

BLK # 14

CIRCUIT #1

IGFP-R3, R3P-0608

Wiring Diagrams (Cont'd)

Hussmann Corporation, Int'l.
13770 Ramona Avenue
Chino, CA. 91710
(909)-590-4910 Lic.#: 644406

?

REVISIONS:
#: DESCRIPTION:
A Updated dwg; revised load ratings

LIGHT SWITCH
TIPPETTE
125-01-0311
L

N

BUNDLE
ORANGE

DATE:
9/4/07

N

WHITE # 14

L1

M

R3 & CR3 CASES

~120 VAC - 60 Hz.
MCA= .36A
MOP= 15A

L1 N

M

DRAWING #:

AXIAL EVAP FANS
0.16 AMP 11W@ 120VAC
(2) 125-01-2011

R3 & CR3 - 4 TOP ONLY COLD CASES

DRAWN BY:
D.QUAN
PROJECT TITLE:
DATE: 03/17/06
BY: CHECKED BY:
PRODUCTION ORDER #:
DRAWING TITLE:
JR
FILE LOCATION:

BUNDLE
BROWN

T-STAT
(1) 225-01-0707

SUCTION SOLENOID
(1) 225-01-3202

~120 VAC - 60 Hz.

BUNDLE
BLACK/WHITE

LIGHT CIRCUIT= .26A 28W

CAP OFF
WIRE
BALLAST 125-01-3266
FULHAM LH3-120-L

~120 VAC - 60 Hz.
MCA= .33A
MOP= 15A

L1

BLACK # 14

25
WHITE # 14

NOTE: CASE MUST
BE GROUNDED

BLACK # 14

F28T5-48"
125-03-1131

BLACK # 14

LOADING
120 V
L1 0.6

WHITE # 14

CIRCUIT #1 50W

PAGE 1 OF 1

W0180101

Rev. 0608	

Wiring Diagrams (Cont'd)

Hussmann Corporation, Int'l.
13770 Ramona Avenue
Chino, CA. 91710
(909)-590-4910 Lic.#: 644406

?

LIGHT SWITCH
TIPPETTE
125-01-0311

N

~120 VAC - 60 Hz.
MCA= .49A
MOP= 15A

L1

BUNDLE
ORANGE

L

REVISIONS:
#: DESCRIPTION:
A Updated dwg; revised load ratings; removed fuse

NOTE: CASE MUST
BE GROUNDED

BLACK # 14

BALLAST 125-01-3266
FULHAM LH3-120-L

DATE:
9/5/07

N

WHITE # 14

T-STAT
(1) 225-01-0707

SUCTION SOLENOID
(1) 225-01-3202

L1

M

BUNDLE
BROWN

M

DRAWING #:

M

R3 & CR3 - 6 TOP ONLY COLD CASES

R3 & CR3 CASES

M

AXIAL EVAP FANS
0.16 AMP 11W@ 120VAC
(4) 125-01-2011

L1 N
~120 VAC - 60 Hz.
MCA= .68A
MOP= 15A

BLACK # 14

DRAWN BY:
D.QUAN
PROJECT TITLE:
DATE: 03/17/06
BY: CHECKED BY:
PRODUCTION
ORDER
#:
DRAWING
TITLE:
JR
FILE LOCATION:

~120 VAC - 60 Hz.

BUNDLE
WHITE/BLACK

LIGHT CIRCUIT= .39A 42W

FP21/830 T5-36"
(2)125-03-1131

BLACK # 14

LOADING
120 V
L1 1.0

WHITE # 14

26

WHITE # 14

CIRCUIT #1 86W

PAGE 1 OF 1

W0180102

IGFP-R3, R3P-0608

Wiring Diagrams (Cont'd)

Hussmann Corporation, Int'l.
13770 Ramona Avenue
Chino, CA. 91710
(909)-590-4910 Lic.#: 644406

?

L

N

REVISIONS:
#: DESCRIPTION:
A Updated dwg; revised load ratings; removed fuse

BUNDLE
WHITE/BLACK

LIGHT CIRCUIT= .52A 56W

DATE:
9/5/07

BUNDLE
ORANGE

BALLAST 125-01-3266
FULHAM LH3-120-L

~120 VAC - 60 Hz.
MCA= .65A
MOP= 15A

L1

BLACK # 14

LIGHT SWITCH
TIPPETTE
125-01-0311

WHITE # 14

NOTE: CASE MUST
BE GROUNDED

N

L1

L1 N

M

M

M

DRAWING #:

R3 & CR3 - 8 TOP ONLY COLD CASES

R3 & CR3 CASES

M

AXIAL EVAP FANS
0.16 AMP 11W@ 120VAC
(4) 125-01-2011

~120 VAC - 60 Hz.
MCA= .68A
MOP= 15A

DRAWN BY:
D.QUAN
PROJECT TITLE:
DATE: 03/17/06
BY: CHECKED BY:
PRODUCTION ORDER #:
DRAWING TITLE:
JR
FILE LOCATION:

~120 VAC - 60 Hz.

BUNDLE
BROWN

T-STAT
(1) 225-01-0707

SUCTION SOLENOID
(1) 225-01-3202

BLACK # 14

F28T5-48"
(2)125-03-1131

WHITE # 14

27

BLACK # 14

LOADING
120 V
L1 1.2

WHITE # 14

CIRCUIT #1 100W

PAGE 1 OF 1

W0180103

Rev. 0608	

Wiring Diagrams (Cont'd)

Hussmann Corporation, Int'l.
13770 Ramona Avenue
Chino, CA. 91710
(909)-590-4910 Lic.#: 644406

?

LIGHT SWITCH
TIPPETTE
125-01-0311

LIGHT CIRCUIT= .52A 56W

L1

BUNDLE
ORANGE

L

N

DATE:
9/5/07

BUNDLE
WHITE/BLACK

L1
~120 VAC - 60 Hz.

N

T-STAT
(1) 225-01-0707

BUNDLE
BROWN

M

MCA= 1.0A
MOP= 15A

M

M

AXIAL EVAP FANS
0.16 AMP 11W@ 120VAC
(6) 125-01-2011

M

DRAWING #:

M

R3 & CR3 - 12 TOP ONLY COLD CASES

R3 & CR3 CASES

L1 N
~120 VAC - 60 Hz.

M

WHITE # 14
DRAWN BY:
D.QUAN
PROJECT TITLE:
DATE: 03/17/06
BY: CHECKED BY:
PRODUCTION
ORDER
#:
DRAWING
TITLE:
JR
FILE LOCATION:

F28T5-48"
125-03-1131

BALLAST 125-01-3266
FULHAM LH3-120-L

~120 VAC - 60 Hz.
MCA= .65A
MOP= 15A

REVISIONS:
#: DESCRIPTION:
A Updated dwg; revised load ratings; removed fuse

NOTE: CASE MUST
BE GROUNDED

BLACK # 14

F28T5-48"
125-03-1131
WHITE # 14

SUCTION SOLENOID
(1) 225-01-3202

BLACK # 14

LOADING
120 V
L1 1.5

WHITE # 14

28
BLACK # 14

CIRCUIT #1 122W

PAGE 1 OF 1

W0180105

IGFP-R3, R3P-0608

Wiring Diagrams (Cont'd)

Hussmann Corporation, Int'l.
13770 Ramona Avenue
Chino, CA. 91710
(909)-590-4910 Lic.#: 644406

?

L

TOP LIGHTING SECTION
(1) FP28/835 125-03-1131

BUNDLE
ORANGE

REVISIONS:
#: DESCRIPTION:
A Updated dwg; revised load ratings

L1 N
~120 VAC - 60 Hz.
MCA= .65A
MOP= 15A

LIGHT SWITCH
TIPPETTE
125-01-0311

MCA= 15.6A
MOP= 20A

BUNDLE
BROWN

M

DATE:
9/4/07

MCA= .36A
MOP= 15A

L1 N
~120 VAC - 60 Hz.

N

L1

3

X
4

MCA= 8.3A
MOP= 15A

~120 VAC - 60 Hz.

BUNDLE BLUE

PRESSURE
SAFETY

L1
CONDENSING UNIT

R3TO-2000-4-S/C

DRAWING #:

CONDENSING UNIT
COPELAND MCFH-0027-IAA-201
RLA= 6.65A 1300W
LRA= 29.0
MCC= 9.6A
225-03-0111A

L2

R3TO-2000-4-S/C

CONDENSER FAN

T-STAT

POWER SWITCH

T

M

SAFETY
SWITCH

FLOAT SWITCH

FISHER™ EVAPOWAY™
DM15WW1D
1500W @ ~ 120 VAC
12.5A
125-01-0765

DRAWN BY:
M. KIMURA
PROJECT TITLE:
DATE: 03/23/04
BY: CHECKED BY:
PRODUCTION ORDER #:
JR
DRAWING TITLE:
FILE LOCATION:

M

2

1

N

DEFROST TIMER
PARAGON 8045-00
~115 V - 60 Hz.
125-01-0710

BUNDLE
YELLOW

PLUG NEMA 5-15P

L1
~120 VAC - 60 Hz.

N

WHITE # 14

DUPLEX
125-01-3049

GRN # 14

AXIAL EVAP FANS COMAIR™
(2) 3" SU2B7-E1 125-01-2011
.16A 11W @120VAC

LIGHT CIRCUIT= .52A 56W

SHELF LIGHT
(1) FP28/835 125-03-1131
OPTIONAL

BALLAST 125-01-3266
FULHAM LH3-120-L
BLACK # 14

CIRCUIT #2 1500W
LOADING
120 V
L1 20.0

BLACK # 14

BLACK # 14

NOTE: CASE MUST BE GROUNDED

WHITE # 14

29
WHITE # 14

CIRCUIT #2

WHITE # 14

LOADING
120 V
L1 7.5

BLACK # 14

CIRCUIT #1 1378W

PAGE 1 OF 1

W1800122

Rev. 0608	

Wiring Diagrams (Cont'd)

IGFP-R3, R3P-0608

Appendices
1.3	 A clogged waste outlet blocks refrigeration. The
installer is responsible for the proper installation
of the system which dispenses condensate waste
through an air gap into the building indirect waste
system.
1.4	 The installer should perform a complete start-up
evaluation prior to the loading of food into the
refrigerator, which includes such items as:
a) 	Initial temperature performance, Coils should
be properly fed with a refrigerant according to
manufacturer’s recommendations.
b) 	Observation of outside influences such
as drafts, radiant heating from the ceiling
and from lamps. Such influence should be
properly corrected or compensated for.
c) 	 At the same time, checks should be made of
the store dry-bulb and wet-bulb temperatures
to ascertain that they are within the limits
prescribed by Hussmann.
d) 	Complete start-up procedures should include
checking through a defrost to make certain
of its adequate frequency and length without
substantially exceeding the actual needs.
This should include checking the electrical
or refrigerant circuits to make sure that
defrosts are correctly programmed for all the
refrigerators connected to each refrigeration
system.
e) 	Recording instruments should be used to
check performance.
Appendix C. - Field Recommendations
Recommendations for field evaluating the
performance of retail food refrigerators and hot
cases
1.0	 The most consistent indicator of display
refrigerator performance is temperature of the air
entering the product zone (see Appendix A). In
practical use, the precise determination of return
air temperature is extremely difficult. Readings of
return air temperatures will be variable and results
will be inconsistent. The product temperature
alone is not an indicator of refrigerator
performance.

Appendix A. - Temperature Guidelines
The refrigerators should be operated according to the
manufacturer’s published engineering specifications for
entering air temperatures for specific equipment applications.
Table 1 shows the typical temperature of the air entering the
food zone one hour before the start of defrost and one hour
after defrost for various categories of refrigerators. Refer to
Appendix C for Field Evaluation Guidelines.

Table 1
Type of Refrigerator
I.	 OPEN DISPLAY
	 A. 	Non frozen:
		 1) 	Meat
		2) 	Dairy/Deli
		 3) 	Produce
			 a. Processed
			 b. Unprocessed
	 B.	 Frozen
	 C.	 Ice Cream
II.	CLOSED DISPLAY
	 A.	 Non frozen:
		 1) 	Meat
		2) 	Dairy/Deli
		 3) 	Produce
			 a. Processed
			 b. Unprocessed
	 B. 	Frozen
	 C.	 Ice Cream

Single Deck

Typical Entering
Air Temperature

Multi Deck

I. Open Display Styles

28°F
32°F
36°F
45°F
0°F
-5°F
34°F
34°F
36°F
45°F
0°F
-5°F

Service Case	

Reach-In

II. Closed Display Styles

Appendix B. - Application Recommendations

1.0	 Temperature performance is critical for controlling
bacteria growth. Therefore, the following
recommendations are included in the standard.
They are based on confirmed field experience
over many years.
1.1	 The installer is responsible for following the
installation instructions and recommendations
provided by Hussmann for the installation
	
of each individual type refrigerator.
1.2	 Refrigeration piping should be sized according to
the equipment manufacturer’s recommendations
and installed in accordance with normal
refrigeration practices. Refrigeration piping
should be insulated according to Hussmann’s
recommendations.

NOTE:	

30

Public Health will use the temperature of the product in
determining if the refrigerator will be allowed to display
potentially hazardous food. For the purpose of this
evaluation, product temperature above the FDA Food
Code 1993 temperature for potentially hazardous food
will be the first indication that an evaluation should
be performed. It is expected that all refrigerators will
keep food at the FDA Food Code 1993 temperature for
potentially hazardous food.

Rev. 0608	

Appendices (Cont'd)
1.1	 The following recommendations are made
for the purpose of arriving at easily taken and
understood data which, coupled with other
observations, may be used to determine whether
a display refrigerator is working as intended:
a) 	INSTRUMENT - A stainless steel stem-type
thermometer is recommended and it should
have a dial a minimum of 1 inch internal
diameter. A test thermometer scaled only
in Celsius or dually scaled in Celsius and
Fahrenheit shall be accurate to 1°C (1.8°F).
Temperature measuring devices that are
scaled only in Fahrenheit shall be accurate to
2°F. The thermometer should be checked for
proper calibration. (It should read 32°F when
the stem is immersed in an ice water bath).
b) 	LOCATION - The probe or sensing element
of the thermometer should be located in
the airstream where the air first enters the
display or storage area, and not more than
1 inch away from the surface and in the
center of the discharge opening.
c) 	 READING - It should first be determined
that the refrigerator is refrigerating and has
operated at least one hour since the end
of the last defrost period. The thermometer
reading should be made only after it has
been allowed to stabilize, i.e., maintain a
constant reading.
d) 	OTHER OBSERVATIONS - Other
observations should be made which may
indicate operating problems, such as
unsatisfactory product, feel/appearance.
e) 	CONCLUSIONS - In the absence of any
apparent undesirable conditions, the
refrigerator should be judged to be operating
properly. If it is determined that such
condition is undesirable, i.e., the product is
above proper temperature, checks should be
made for the following:
1. 	 Has the refrigerator been loaded with warm
product?
2. 	 Is the product loaded beyond the “Safe Load
Line” markers?
3. 	 Are the return air ducts blocked?
4. 	 Are the entering air ducts blocked?
5. 	 Is a dumped display causing turbulent air flow and
mixing with room air?
6. 	 Are spotlights or other high intensity lighting
directed onto the product?
7. 	 Are there unusual draft conditions (from heating/
air-conditioning ducts, open doors, etc.)?

8. 	 Is there exposure to direct sunlight?
9. 	 Are display signs blocking or diverting airflow?
10. 	Are the coils of the refrigerator iced up?
11.	 Is the store ambient over 75°F, 55% RH as set
forth in ASHRAE Standard 72 and ASHRAE
Standard 117?
12.	 Are the shelf positions, number, and size other
than recommended by Hussmann?
13.	 Is there an improper application or control
system?
14.	 Is the evaporator fan motor/blade inoperative?
15.	 Is the defrost time excessive?
16.	 Is the defrost termination, thermostat (if used) set
too high?
17.	 Are the refrigerant controls incorrectly adjusted?
18.	 Is the air entering the condenser above design
conditions? Are the condenser fins clear of dirt,
dust, etc.?
19.	 Is there a shortage of refrigerant?
20. 	Has the equipment been modified to use
replacements for CFC-12, CFC-502 or other
refrigerant? If so, have the modifications been
made in accordance with the recommendations of
the equipment manufacturer? Is the refrigerator
charged with the proper refrigerant and lubricant?
Does the system use the recommended
compressor?
Appendix D. - Recommendations to User
1.0	 Hussmann Corporation provides instructions
and recommendations for proper periodic
cleaning. The user will be responsible for
such cleaning, including the cleaning of low
temperature equipment within the compartment
and the cooling coil area(s). Cleaning practices,
particularly with respect to proper refrigerator
unloading and warm-up, must be in accordance
with applicable recommendations.

31

IGFP-R3, R3P-0608

Appendices (Cont'd)
d)	 Care must be taken when cross
merchandising products to ensure that
potentially hazardous vegetable products are
not placed in non refrigerated areas.
e)	 Display and storage equipment doors should
be kept closed during periods of inactivity.
f)	 Minimize the transfer time of perishables
from storage to display.
g)	 Keep meat under refrigeration in meat cutting
and processing area except for the few
moments it is being handled in processing.
When a cut or tray of meat is not to be
worked on immediately, the procedure should
call for returning it to refrigeration.
h)	 Keep tools clean and sanitized. Since
mechanical equipment is used for fresh
meat processing, all such equipment should
be cleaned at least daily and each time
a different kind of meat product comes in
contact with the tool or equipment.
i)	 Make sure that all refrigeration equipment is
installed and adjusted in strict accordance
with the manufacturer’s recommendations.
j)	 See that all storage and refrigeration
equipment is kept in proper working order by
routine maintenance.

1.1	 Cleaning of non frozen food equipment
should include a weekly cleaning of the food
compartment as a minimum to prevent bacteria
growth from accumulating. Actual use and
products may dictate more frequent cleaning.
Circumstances of use and equipment design
must also dictate the frequency of cleaning the
display areas. Weekly washing down of the
storage compartment is also recommended,
especially for equipment subject to drippage
of milk or other liquids, or the collection of
vegetable, meat, crumbs, etc. or other debris
or litter. Daily cleaning of the external areas
surrounding the storage or display compartments
with detergent and water will keep the equipment
presentable and prevent grime buildup.
1.2	 Load levels as defined by the manufacturer must
be observed.
1.3	 The best preservation is achieved by following
these rules:
a) 	Buy quality products.
b) 	Receive perishables from transit equipment
at the ideal temperature for the particular
product.
c) 	 Expedite perishables to the store’s storage
equipment to avoid unnecessary warm-up
and prolonged temperature recovery. Food
store refrigerators are not food chillers nor
can they reclaim quality lost through previous
mishandling.

For further technical information, please log on to http://www.hussmann.com/products/R3P.htm
or http://www.hussmann.com/products/R3TO.htm

32

IGFP-R3, R3P-0608

Service Record
Last service date:	

By:

_______________ 	

___________________________________________________________________________________________________

_______________ 	

___________________________________________________________________________________________________

_______________ 	

___________________________________________________________________________________________________

_______________ 	

___________________________________________________________________________________________________

_______________ 	

___________________________________________________________________________________________________

_______________ 	

___________________________________________________________________________________________________

_______________ 	

___________________________________________________________________________________________________

/Chino

Additional copies of this publication may be obtained by contacting:
Hussmann® Chino
13770 Ramona Avenue • Chino, California 91710
(909) 628-8942 FAX
(909) 590-4910
(800) 395-9229

The MODEL NAME and SERIAL NUMBER is required in order to provide
you with the correct parts and information for your particular unit.
They can be found on a small metal plate on the unit.
Please note them below for future reference.

MODEL:
SERIAL NUMBER:



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Tagged PDF                      : Yes
XMP Toolkit                     : 3.1-701
Instance ID                     : uuid:cdfe5ad3-904d-4e07-a9e8-62a0da21a997
Document ID                     : adobe:docid:indd:4dbfc918-2246-11dd-ab95-f4fbf44b2905
Rendition Class                 : proof:pdf
Derived From Instance ID        : 3dee7ed2-2231-11dd-ab95-f4fbf44b2905
Derived From Document ID        : adobe:docid:indd:caaff867-222a-11dd-ab95-f4fbf44b2905
Manifest Link Form              : ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 600.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00
Manifest Placed Y Resolution    : 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 600.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00
Manifest Placed Resolution Unit : Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches
Manifest Reference Instance ID  : uuid:72BAD47EE826DD1191DAAE426C5B7223, uuid:E3A513B75197DC11A9FCBA9F7BA3C3D9, uuid:74BAD47EE826DD1191DAAE426C5B7223, uuid:8C265F23EF26DD1191DAAE426C5B7223, uuid:4F3191671626DD11B4D1E545F6BAB7BE, uuid:247292576B21DD11827DDD63B823D713, uuid:287292576B21DD11827DDD63B823D713, uuid:2A7292576B21DD11827DDD63B823D713, uuid:BF2F6CE86C21DD11827DDD63B823D713, uuid:2E7292576B21DD11827DDD63B823D713, uuid:C02F6CE86C21DD11827DDD63B823D713, uuid:E6B93C577021DD11827DDD63B823D713, uuid:C62F6CE86C21DD11827DDD63B823D713, uuid:C82F6CE86C21DD11827DDD63B823D713, uuid:E3B93C577021DD11827DDD63B823D713, uuid:E5B93C577021DD11827DDD63B823D713, uuid:90265F23EF26DD1191DAAE426C5B7223, uuid:94265F23EF26DD1191DAAE426C5B7223, uuid:92265F23EF26DD1191DAAE426C5B7223, uuid:8E265F23EF26DD1191DAAE426C5B7223, uuid:2D53FF687F33DD11BD1A97587787E5B8, uuid:C6E756208133DD11BD1A97587787E5B8, uuid:C995C0158233DD11BD1A97587787E5B8, uuid:2D53FF687F33DD11BD1A97587787E5B8, uuid:C6E756208133DD11BD1A97587787E5B8, uuid:C995C0158233DD11BD1A97587787E5B8, uuid:BE345DCB8433DD11BD1A97587787E5B8, uuid:C6345DCB8433DD11BD1A97587787E5B8, uuid:53E20C158533DD11BD1A97587787E5B8, uuid:03E8E2DD140ADD11A6D58C2655C59A35, uuid:0CE0F86CFA26DD1191DAAE426C5B7223, uuid:A59104B02938DD11AE4384C7B8B6896A, uuid:0DE0F86CFA26DD1191DAAE426C5B7223, uuid:802D6C9D731DDD11A667FD3A8A6ABB60, uuid:909C3AA39720DD11A895E5A3EF2D7F2A, uuid:5087EA76EB26DD1191DAAE426C5B7223, uuid:7ABAD47EE826DD1191DAAE426C5B7223, uuid:78BAD47EE826DD1191DAAE426C5B7223, uuid:76BAD47EE826DD1191DAAE426C5B7223, uuid:5B58C33AEE26DD1191DAAE426C5B7223, uuid:6358C33AEE26DD1191DAAE426C5B7223, uuid:6158C33AEE26DD1191DAAE426C5B7223, uuid:5F58C33AEE26DD1191DAAE426C5B7223, uuid:5887EA76EB26DD1191DAAE426C5B7223, uuid:5687EA76EB26DD1191DAAE426C5B7223, uuid:5487EA76EB26DD1191DAAE426C5B7223, uuid:5287EA76EB26DD1191DAAE426C5B7223, uuid:5D58C33AEE26DD1191DAAE426C5B7223
Manifest Reference Document ID  : uuid:71BAD47EE826DD1191DAAE426C5B7223, uuid:E2A513B75197DC11A9FCBA9F7BA3C3D9, uuid:73BAD47EE826DD1191DAAE426C5B7223, uuid:6458C33AEE26DD1191DAAE426C5B7223, uuid:6A75B9A80B20DD119DCAE0128B407795, uuid:01C741616121DD11827DDD63B823D713, uuid:257292576B21DD11827DDD63B823D713, uuid:297292576B21DD11827DDD63B823D713, uuid:BE2F6CE86C21DD11827DDD63B823D713, uuid:2D7292576B21DD11827DDD63B823D713, uuid:2B7292576B21DD11827DDD63B823D713, uuid:C12F6CE86C21DD11827DDD63B823D713, uuid:C52F6CE86C21DD11827DDD63B823D713, uuid:C72F6CE86C21DD11827DDD63B823D713, uuid:E2B93C577021DD11827DDD63B823D713, uuid:E4B93C577021DD11827DDD63B823D713, uuid:8F265F23EF26DD1191DAAE426C5B7223, uuid:93265F23EF26DD1191DAAE426C5B7223, uuid:91265F23EF26DD1191DAAE426C5B7223, uuid:8D265F23EF26DD1191DAAE426C5B7223, uuid:2C53FF687F33DD11BD1A97587787E5B8, uuid:C5E756208133DD11BD1A97587787E5B8, uuid:C895C0158233DD11BD1A97587787E5B8, uuid:2C53FF687F33DD11BD1A97587787E5B8, uuid:C5E756208133DD11BD1A97587787E5B8, uuid:C895C0158233DD11BD1A97587787E5B8, uuid:BD345DCB8433DD11BD1A97587787E5B8, uuid:C5345DCB8433DD11BD1A97587787E5B8, uuid:52E20C158533DD11BD1A97587787E5B8, uuid:02E8E2DD140ADD11A6D58C2655C59A35, uuid:95265F23EF26DD1191DAAE426C5B7223, uuid:A39104B02938DD11AE4384C7B8B6896A, uuid:2CDF2DFB6722DD11B4D18F29D6574095, uuid:7F2D6C9D731DDD11A667FD3A8A6ABB60, uuid:8F9C3AA39720DD11A895E5A3EF2D7F2A, uuid:4F87EA76EB26DD1191DAAE426C5B7223, uuid:79BAD47EE826DD1191DAAE426C5B7223, uuid:77BAD47EE826DD1191DAAE426C5B7223, uuid:75BAD47EE826DD1191DAAE426C5B7223, uuid:5987EA76EB26DD1191DAAE426C5B7223, uuid:6258C33AEE26DD1191DAAE426C5B7223, uuid:6058C33AEE26DD1191DAAE426C5B7223, uuid:5E58C33AEE26DD1191DAAE426C5B7223, uuid:5787EA76EB26DD1191DAAE426C5B7223, uuid:5587EA76EB26DD1191DAAE426C5B7223, uuid:5387EA76EB26DD1191DAAE426C5B7223, uuid:5187EA76EB26DD1191DAAE426C5B7223, uuid:5C58C33AEE26DD1191DAAE426C5B7223
Create Date                     : 2008:06:12 09:47:23+05:30
Modify Date                     : 2008:06:16 16:33:20-07:00
Metadata Date                   : 2008:06:16 16:33:20-07:00
Creator Tool                    : Adobe InDesign CS2 (4.0)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 6521 bytes, use -b option to extract)
Format                          : application/pdf
Producer                        : Adobe PDF Library 7.0
Trapped                         : False
Page Count                      : 33
Creator                         : Adobe InDesign CS2 (4.0)
EXIF Metadata provided by EXIF.tools

Navigation menu