ICP C8DNL050B12B1 User Manual 80+ SINGLE STAGE GAS FURNACE Manuals And Guides L0601261
ICP Furnace/Heater, Gas Manual L0601261 ICP Furnace/Heater, Gas Owner's Manual, ICP Furnace/Heater, Gas installation guides
User Manual: ICP C8DNL050B12B1 C8DNL050B12B1 ICP 80+ SINGLE STAGE GAS FURNACE - Manuals and Guides View the owners manual for your ICP 80+ SINGLE STAGE GAS FURNACE #C8DNL050B12B1. Home:Heating & Cooling Parts:Icp Parts:Icp 80+ SINGLE STAGE GAS FURNACE Manual
Open the PDF directly: View PDF .
Page Count: 38
Download | |
Open PDF In Browser | View PDF |
80+Single Stage DedicatedDownflow *8DNL Category I Furnace See section 4 for Category safety to the potential Understand words hazards, those CAUTIONis highlight Installing install, Untrained to or shipped Follow all safety safety glasses These instructions tions exceed require these unsafe practices in enhanced personnel. In the United gloves. Lewisburg, These injury that may words or death. result installation, in minor reliability, can be hazardous on the furnace and in instruction manuals be alert are used with the safety-alert symbol. DANGER identifies the WARNINGsignifiesahazardthatcouldresultinpersonalinjuryor personal injury or product and property damage. NOTE is used to or operation. due to gas and electrical basic maintenance When States, on heating safety precautions follow Standard requirements functions working and other all safety of Canada especially such components. as cleaning equipment, that codes observe Only trained and qualified personnel should to existing the National Gas and Propane during and replacing precautions air filters. All other in the literature, operations on tags, must be and on labels at- may apply. including Natural available and conform and ordinances, as a minimum International personal Have fire extinguisher minimum local codes instructions you see this symbol equipment. refer to the National cover When or CAUTION. in severe with the furnace and work certain WARNING, can perform service codes. In Canada, REQUIREMENTS symbolZl._. result equipment heating personnel by trained tached 54-2002. heating or service service performed DANGER, that will that will result and servicing repair, This is the safety-alert used to identify suggestions (C, H, T) injury. the signal most serious death. information. for personal Brands I definition. SAFETY Recognize * Denotes start-up national Fuel Gas Code Installation and adjustment standards Code (NFGC) procedures and safety those that may not have kept up with changing ANSI (NSCNGPIC) codes. and service In some residential Z223.1-2002/NFPA CSA B149.1-05. Wear calls. instances, construction these instruc- practices. We for a safe installation. Comfort Products, LLC TN 37097 INSTALLER: or adjacent Affix these instructions on to the furnace. CONSUMER: Retain these instructions for future reference. Table of Contents 1. Safe Installation Requirements ................ 2. Installation ............................... 3 4 3. Combustion 6 & Ventilation Air 4. Gas Vent Installation ................. ........................ 9 5. Horizontal Venting ......................... 11 6. Masonry Chimney Venting ................... 13 7. Gas Supply and Piping ....................... 8. Electrical Wiring ........................... 9. Ductwork and Filter ......................... 10.Checks and Adjustments..................... 11.Furnace Maintenance........................ 12.Sequence of Operation & Diagnostics ........... TechSupport and Parts ......................... 16 18 19 23 27 28 31 CARBON MONOXIDE POISONING AND FIRE HAZARD. Failure to follow safety warnings exactly could result in serious injury, death, and/or property damage. This furnace is not designed for use in mobile homes, trailers or recreational vehicles. Portions of the textand tablesare reprinted from NFPA 54 / ANSI Z223,1-2002©, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washington, DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI, on the referenced subject, which is represented only by the standard in its entirety. Printedin U.S.A. 11/10/2005 441 01 2314 (02) START-UP (Keep Recommended, Dealer but not this page CHECK for future SHEET reference) required, Name: Address: City, Business Card Here Zip or Postal Code: State(Province), Phone: Owner Name: Manual Gas Shut-Off Upstream Address: City, State(Province), Zip or Postal Code: of Furnace/Drip- Leg? YES_I NO_I Drip-Leg Upstream of Gas Valve? YES_I NO_I Blower Speed Checked? NO [_I YES _1 Model Number: YEs_I All Electrical Connections Tight? Serial Number: Gas Valve turned ON? YES _1 NO[_I Blower Motor H. P,: Measured When Firing Unit: Supply Voltage: Calculated Checks and Type of Gas: Natural: Limit Opens at...(°F) _1 LP: _1 Line Pressure Firing Rate:(See Adjustments Section). or(°C). Limit Closes at,,,(°F)___or(°C) Measured Manifold Pressure: Which blower speed tap is used? Thermostat OK? YES _1 NOE_ Subbase Level? YES _1 NOE_I Anticipator Set? YES _1 NO E_ Set At?: (Heating) NO[31 (Cooling). Temperature of Supply Air: (°F)___or(°C) Temperature of Return Air: (°F) Rise (Supply Temp.-Return Temp.): (°F) or(°C)__ or(°C)__ Breaker On? YES _1 NoE_I Filter Type and Size: Fan "Time ON" Setting:. Fan "Time OFF" Setting: Date of Installation: Date of Start-Up: Dealer Comments: 441 01 2314 02 1. Safe Installation Requirements FIRE, EXPLOSION, AND ASPHIXIATION HAZARD Improper adjustment, alteration, service, maintanence or installation could cause death, personal injury, and/or property damage. Installation or repairs made by unqualified persons could result in hazards to you and others. Installation MUST conform with local codes or, in the absence of local codes, with codes of all governmental authorities havingjurisdiction. The information contained in this manual is intended for use by a qualified service agency that is experienced in such work, is familiar with all precautions and safety procedures required in such work, and is equipped with the proper tools and test instruments. • This furnace is NOT approved homes, trailers or recreation for installation vehicles. • Seal around air ducts. • Install • Unit MUST be installed so electrical components tected from direct contact with water. abuse create A, Always install furnace to operate within the furnace's intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in" Technical Support Manual"of these instructions. See furnace rating plate. When a furnace is installed so culated by the furnace to areas the furnace, the return air shall sealed to the furnace casing space containing the furnace. A gas-fired furnace must be installed structions. • that supply ducts carry air ciroutside the space containing also be handled by a duct(s) and terminating outside the for installation as specified in a residential in "2. Installation"of 441 01 2314 02 injury and/or and odorless or when the dential Carbon Alarming Devices installed and maintained in the building or dwelling concurrently with the gas- fired furnace installation (see Note below). The alarm should be installed as recommended by the alarm manufacturer's installation instructions. B, There can be numerous sources of fire or smoke in a building or dwelling. Fire or smoke can cause serious bodily injury, death, and/or property damage. Therefore, in order to alert people of potentially dangerous fire or smoke, you should have fire extinguisher and smoke alarms listed by Underwriters Laboratories installed and maintained in the building or dwelling (see Note below). Note: The manufacturer of your furnace does not test any alarms and makes no representations regarding any brand or type of alarms. C. To ensure safe and efficient do the following: 1. Thoroughly read this manual and labels on the unit. This will help you understand how your unit operates and the hazards involved with gas and electricity. operation of your unit, you should Do not use this unit if any part has been under water. Immediately call a qualified service agency to inspect the unit and to replace any part of the control system and any gas control which has been under water. garage these in- This furnace is not to be used for temporary heating of buildings or structures under construction. See "2, Installation, item 10 " The U.S. Consumer Product Safety Commission encourages installation of carbon monoxide alarms. There can be various sources of carbon monoxide in a building or dwelling. The sources could be gas-fired clothes dryers, gas cooking stoves, water heaters, furnaces, gas-fired fireplaces, wood fireplaces. Therefore, to help alert people of potentially dangerous ca rbon monoxide levels, you should have a commercially available carbon monoxide alarm that is listed by a nationally recognized testing agency in accordance with Underwriters Laboratories Inc. Standard for Single and Multiple Station Carbon Monoxide Alarms, ANSI/UL 2034 or the CSA 6.19-01 Resi- Use a commer- cially available soap solution made specifically for the detection of leaks to check all connections, as specified in "7. Gas Supply and Piping, Final Check"of these instructions. are pro- the life of the unit and gas produced when fuel is not burned completely flame does not receive sufficient oxygen. combustion and ventilation air to the furin "3. Combustion and Ventilation Air" of Never test for gas leaks with an open flame. and/or improper use can shorten hazards for you, the owner. Carbon monoxide can cause serious bodily death. Carbon monoxide or "CO" is a colorless as speci- Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in "4. Gas Vent Installation, 5, Horizontal Venting and 6. Masonry Chimney Venting"of these instructions. filter type and size. Your unit is built to provide many years of safe and dependable service providing it is properly installed and maintained. However, Use onlythe Type of gas approved for this furnace (see Rating Plate on unit). Overfiring will result in failure of heat exchanger and cause dangerous operation. (Furnaces can be converted to L.P. gas with approved kit.) Provide adequate nace as specified these instructions. and return Safety Rules NOTE: This furnace is design-certified by CSA International (formerly AGA and CGA) for installation in the United States and Candada. Refer to the appropriate codes, along with this manual, for proper installation. Install this furnace only in a location and position fied in "2. Installation"of these instructions. correct supply in mobile 3. Never obstruct the vent grilles, or any ducts that provide air to the unit. Air must be provided for proper combustion and ventilation of flue gases. Frozen Water Pipe Hazard .your furnace home to provide cold weather you should and drain the water lines if possible and add an antifreeze for potable water to drain traps and toilet tanks. Open faucets in appropriate areas. Do not leave your home unattended for long periods during freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes and resultant damage. solely during Turn off the water supply to the structure Failure to protect against the risk of freezing could result in property damage. is designed remains off for an extended time, the pipes in your freeze and burst, resulting in serious water damage. If the structure will be unattended take these precautions. WATER DAMAGE TO PROPERTY HAZARD Your furnace could -or- Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing. Instruct them on a service agency to call to provide service, if required. a safe and comfortable living environment. The furnace is NOT designed to ensure that water pipes will not freeze. It is equipped with several safety devices that are designed to turn the furnace off and prevent it from restarting in the event of various potentially unsafe conditions. -or- 3. Install a reliable remote sensing device that will notify somebody of freezing conditions within the home. 2. Installation Do NOT install furnace directly on carpeting, tile or other combustible material. See 9, Ductwork and Filter Sub-base for Combustible Floors. CARBON MONOXIDE POISONING HAZARD. Failure to properly vent this furnace or other appliances could result in death or personal injury. If this furnace is replacing a previously commonvented furnace, it may be necessary to resize the existing vent system to prevent oversizing problems for the other remaining appliances(s). See Venting and Combustion Air Check in the 4. Gas Vent Installation section of this instruction. Location and Clearances 6. Maintain clearance for fire safety and servicing. A front clearance of 24" is minimum for access to the burner, controls and filter. See clearance requirements in Figure 1. 7. Use a raised 8. Residential mensions based (Figure clearance and furnace • Furnace possible di- 10. This furnace • CARBON MONOXIDE POISONING HAZARD. exactly could Do NOT operate furnace in a corrosive atmosphere containing chlorine, fluorine or any other damaging chemicals, which could shorten furnace life. • and remedy. Install furnace level. • 2. This furnace is NOT to be used for temporary heat of buildings or structures under construction. 3. Install furnace as centralized heat distribution system. 4. Install the vent pipes as short as practical. Installation section). as practical at least must be located or physically damage by a vehicle. protected 18" (457 from may be used for construction heat provided that: The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure. Clean outside air is provided for combustion. minimize the corrosive effects of adhesives, This is to sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components. Installation Requirements 1, installed The furnace is controlled by a thermostat. It may not be "hot wired" to provide heat continuously to the structure without thermostatic control. Refer to 3. Combustion & Ventilation Air section, Contaminated Combustion Air for combustion air evaluation or wet at times. require: If the furnace is to be suspended from the floorjoists in a basement or a crawl space or the rafters in an attic, it is necessary to use steel pipe straps or an angle iron frame to attach the furnace. These straps should be attached to the furnace bottom side with sheet metal screws and to the rafters or joists with bolts. The preferred method is to use an angle iron frame bolted to the rafters or joists. 1). Failure to follow safety warnings result in death or personal injury. installations Burners and ignition sources mm) above the floor. 9. upon the minimum if the floor is damp • If furnace is a replacement, it is usually best to install the furnace where the old one was. Choose the location or evaluate the existing location base garage with respect 4. Gas to the Vent of the return air to the furnace is main55 ° F (13 ° C) and 80 ° F (27 ° C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent • (See The temperature tained between operation The air temperature per our installation rise is within instructions. the rated rise range on the furnace rating plate, and the firing rate has been set to the rating plate value. 441 01 2314 02 The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy. The furnace, ductwork and filters are cleaned Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these installation instructions. as neces- sary to remove drywall dust and construction debris from all HVAC system components after construction is completed. Dimensions and Clearances (*8DNL) MINIMUM 281/2 CLEARANCES MATERIALS 0 FRONT (combustion air openings in furnace and structure) 3" Required For Service 0" 313116 FURNACES REAR _E _-J TO COMBUSTIBLE FOR ALL *24" ALL SIDES Of SUPPLY PLENUM 1" SIDES 0 VENT Single-Wall 11/16 fl°'T i _ 213/16 LEFT SIDE Vent 6" Type B-1 Double-Wall TOP OF FURNACE 11/16 Vent 1" 1" "30" clearancerecommendedfor casing removal. FRONT See Section9.DuctworkandFiiter, Sub-basesfor CombustibleFloorsFurnace ONLYand DownflowCoil AdapterBox sectionsof this manual for installationon combustibleconstruction. -- 2415/16 181/2 RIGHTSIDE Drawing is representative, but some models may vary 40 24 3/16 165/8 nil 6 DIMENSIONAL Unit INFORMATION Top Bottom Capacity A B C D *8DNL050B12 *8DNL075B12 151/2 14 5 5/16 141/8 191/8 175/8 73/4 1711116 Furnace is designed for top return ONLY. *8DNLO75F16 *8DNL1OOF14 Return air through back of furnace is NOT allowed. 8DNL1OOL20 *8DNL125L20 241/2 23 107116 231/8 NOTE: Evaporator "A" coil drain pan dimensions may vary from furnace duct opening size. Always consult evaporator specifications for duct size requirements. Cabinet 121/16 _3 3/4 DIMENSIONS IN INCHES Dentoes Brand Downflow Furnace Installation Inspect the rating plate to be certain the model number begins "*8DNL". This identifies the furnace as a dedicated downflow with fur- nace that is permitted Figure 2). * Denotes Brand (see 441 O1 231402 to be Installed in a Downflow position. FIRE HAZARD. Failure to install furnace on noncombustible subbase could result in death, personal injury and/or property damage. Place furnace on noncombustible subbase on downflow applications, unless installing on noncombustible flooring. [_ The minimum clearances maintained between shown in Figure 1. to combustion the furnace In addition to clearances must be considered. in Figure A su bbase for combustible is installed on combustible construction and adjacent MUST construction, 1, clearance be Typical Downflow as Installation for the vent pipe RETURN AIR floors MUST be used when the furnace material. See "9. DuctworkandFilter't GAS SUPPLY SUPPLY AIR 25-24-38 3. Combustion & Ventilation Air evaluated carefully as it may be necessary to provide outdoor air for combustion. CARBON MONOXIDE POISONING HAZARD. Failure to provide ventilation air could injury. adequate result in Use methods described combustion and ventilation combustion and death or personal here air. to provide Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases. All duct or openings for supplying combustion and ventilation air must comply with the gas codes, or in the absence of local codes, the applicable national codes. Combustion and ventilation with one of the following: 1. 2. 3. air must be supplied in accordance Section 8.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, (NFGC), ANSI Z223.1-2002/NFPA 54-2002 in the U.S., • Commercial • Buildings with indoor buildings. • Furnaces installed in laundry • Furnaces installed in hobby • • Furnaces installed near chemical storage Permanent wave solutions for hair. • Chlorinated • Chlorine • Water • • De-icing salts or chemicals. Carbon tetrachloride. • Halogen • Cleaning • Printing • • Hydrochloric acid. Sulfuric Acid. waxes based rooms. or craft rooms. areas. and cleaners. swimming softening type pools. pool chemicals. chemicals. refrigerants. solvents (such as perchloroethylene). inks, paint removers, • Solvent • Antistatic cements fabric • Masonry acid washing varnishes, etc. and glues. softeners for clothes dryers. materials. Sections 7.2, 7.3, 7.5, 7.6, 7.7, and 7.8 of National Standard of Canada, Natural Gas and Propane Installation Code (NSCNGPIC), CSA B149.1-05 in Canada, Outdoor Combustion Applicable A space having less than 50 cubic feet per 1,000 BTUH input rating for all gas appliances installed in the space requires outdoor air for combustion and ventilation. provisions When the installation of the local building is complete, check code. that all appliances have adequate combustion air and are venting properly. See Venting And Combustion Air Check in "4. Gas Vent Installation "Section in Air Openings and Connecting Combustion Air Installations in certain areas or types of structures could cause excessive exposure to contaminated air having chemicals or halogens that will result in safety and performance related problems Ducts 1. Total input rating for all gas appliances in the space MUST considered when determining free area of openings. 2. Connect 3. When MUST 4. The minimum this manual. Contaminated Air Method ducts or openings screens are used be no smaller than dimension directly to the outdoors. to cover openings, 1/4" mesh. of air ducts be MUST the openings NOT be less than 3 _ . and may harm the furnace. door air for combustion. These instances The following areas or types of structures posure to the substances listed below. must use only out- may contain or have exThe installation must be When sizing a grille, louver, or screen use the free area of opening. If free area is NOT stamped or marked on grill or louver, assume a 20% free area for wood and 60% for metal. Screens shall have a mesh size not smaller than 1/4". 441 01 2314 02 air when two permanent used. Requirements 1. Provide the space with sufficient air for proper combustion and ventilation of flue gases using horizontal or vertical ducts or openings. 2. Figure 3 illustrates how to provide Outside combustion Air (This and ventilation is ONLY a guide. Subject openings, a. One opening MUST the second opening ceiling. b. Size openings to codes commence within 12" of the floor and MUST commence within 12" of the and ducts of country one inlet and one outlet, are per Table having 1. jurisdiction.) ThisinstallationNOTapprovedin Canada / • GableVent) GasVent Gas Vent .,1' j_Gable Vent Ventilated Attic'S. SoffitVent J_utlet II I Air (1) II Outle_ Air(1) [_ " _G% _ F...... _' Air(1) _. _ --- SoffitVent Inlet Air (2) ;pace Inlet Air(1) -, i I I,n,e ` _ '_ _ _ Air (2) MinimumOne Inlet and OneOutlet Air Supply is Required May be in andCombination Shown Inlet Air Opening Must beWithin12"(300mm)of floor Outlet Air OpeningMust be Within12"(300mm)of ceiling (1) 1 Square Inch (6cm2) per 4000 BTUH (2) 1 Square Inch (6cmz) per 2000 BTUH c. d. 3. Horizontal duct openings require I square inch of free area per 2,000 BTUH (1,100 mmZ/kW) of combined input for all gas appliances in the space (see Table 1). nicate with the outdoors horizontal duct to the outdoors or spaces communicate with the outdoors. (crawl or attic) that freely Vertical duct openings or openings directlycommunicating with the outdoors require 1 square inch of free area per 4,000 BTUH (550 mm2/kW) for combined input of all gas appliances in the space (see Table 1). 4. Air shall have: When one permanent requires: a. 1 sq. in of free area combined input Table 1) and b. outdoor opening per 3,000 is used, the opening BTUH of all gas appliances not less than the sum of the areas (700 mm2/kW) in the space for Combination Indoor openings that comply with the Indoor tion Air Method below and b. Outdoor openings located as required Combustion Air Method above and C. Outdoor openings sized as follows. in the CombusOutdoor in 2) Outdoor opening size reduction Factor is 1 minus the Ratio in 1) above. 3) Minimum size of Outdoor openings shall be the size required in Outdoor Combustion Air Method above multiplied by reduction Factor. commu- Area BTUH Input Rating TwoHorizontalDucts (sq. in./2,000BTUH) MinimumFree Area Requiredfor EachOpeningor Ductto Outdoors TwoVertical Ductsor SingleOpening Openings (sq. in./3,000BTUH) (sq.in./4,000 BTUH) Round Duct (sq. in./4,000 BTUH) 50,000 25 sq. in. 16.7 sq. in, 12.5 sq. in, 4" 75,000 37,5 sq. in. 25 sq. in. 1825 sq. in. 5" 100,000 50 sq, in. 33.3 sq. in, 25 sq. in. 6" 125,000 62.50sq. in. 41.7 sq. in. 31.25 sq. in. 7" 150,000 75 sq. in. 50 sq. in. 37.5 sq. in. 7" EXAMPLE: Determining Furnace 100,000 + Furnace 100,000 441 01 231402 + or 1) Calculate the Ratio of all Indoor Space volume divided by required volume for Indoor Combustion Air Method. The opening shall commence within 12" of the top of the enclosure. Appliances shall have clearances of at least I "from the sides shall directly and Outdoor a vertical (see of all vent connectors The opening of Indoor through a. the space. and back and 6" from the front. or shall communicate Free Area Water Heater Total Input 30,000 (130,000 + 4,000) Water Heater Total Input 30,000 (130,000 + 2,000) 32.5 Sq. In. Vertical 65 Sq. In. Horizontal Indoor Combustion Air Standard and Known-Air-Infiltration © NFPA& AGA Rate Methods Indoor air is permitted for combustion and ventilation, if the Standard or Known-Air-Infiltration Rate Method is used. CARBON MONOXIDE POISONING HAZARD. The Standard Failure to supply adequate combustion result in death or personal injury. ume than 50 cubic feet per 1,000 BTUH input rating for all gas appliances installed in the space. The standard method permits indoor air to be used for combustion and ventilation air. air could Most homes will require additional air from outdoors for combustion and ventilation. A space with at least 50 cubic feet per 1,000 BTUH input rating or homes with tight construction may need outdoor air, supplied through ducts, to supplement air infiltration for proper combustion and ventilation of flue gases. The Known Method Air may be used, if the space Infiltration shall be used if the in- greater than 0.60 ACH shall not be used. The volume of the space varies with the number of determined per Table 2 or Equations 1 and minimum required volume for each appliance iiiiiiiiiiiiiiiiiiiii_i;_;:_i:_i:_i:_i:_i:_i:_i:_i:_i:_i:_i:_i:_i:_i:_:i_!!!!_ii!#_;i!_#_;i!i!;i_iiiii_ii_iiiiiiiiiii;i#;ii;ii;ii;ii;ii;i MINIMUM SPACE VOLUME FOR 100% COMBUSTION AND VENTILATION minimum required ACH and shall be 2. Determine the in the space, and to get the total minimum AIR FROM INDOORS required vol- (ft 3) Fan- assistedTotal (1,000'sBtuh) Total (1,OOO'sBtuh) 30 Method filtration rate is known to be less than 0.40 air changes per hour (ACH) and equal to or greater than 0.10 ACH. Infiltration rates add the volumes together ume for the space. Other Than Fan-Assisted Rate has no less vol- 40 50 50 75 100 0.60 1,050 1,400 1,750 1250 1,875 2,500 3,125 3,750 0.50 1,260 1,680 2,100 1,500 2,250 3,000 3,750 4,500 0.40 1,575 2,100 2,625 1,875 2,813 3,750 4,688 5,625 0.30 2,100 2,800 3,500 2,500 3,750 5,000 6250 7,500 0.20 3,150 4200 5,250 3,750 5,625 7,500 9,375 11,250 0.10 6,300 8,400 10,500 7,500 11,250 15,000 18,750 22,500 0.00 NP NP NP NP NP NP NP NP ACH 125 150 NP = Not Permitted Table 2 Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI Z223.1/NFPA 54-2002, 8.3.3.2: 1. For other hood-equipped than fan-assisted water heater, Volume - 2. other 21 ft 3 ACH For fan-assisted Volume fan = ( appliances 15ft3 ACH ( appliances ! other 1000 Btu / hr such An attic or crawl space may be considered a space that freely communicates with the outdoors provided there are adequate ventilation openings directly to outdoors. Openings MUST remain open and NOT have any means of being closed off. Ventilation openings to outdoors MUST be at least I square inch of free area per 4,000 BTUH of total input rating for all gas appliances in the space. as a draft ) In spaces that use the Indoor Combustion Air Method, infiltration should be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings with unusually tight construction, additional air MUST be provided using the methods described in section titled Outdoor Combustion Air Method: such as this furnace, Iran 1000 Btu ! hr ) Unusually • If: [ other = input of all fan-assisted appliances = air changes per hour The following requirements the Known Air Infiltration (ACH shall apply to the Standard Rate Method. Method 0.60.) and to • Adjoining rooms can be considered part of a space, are no closable doors between rooms. • Combining spaces on the same floor level. Each opening shall have a free area of at least 1 square inch/1,000 BTUH (2,000 mm2/kW) of the total input rating of all gas appliances in the space, but not less than 100 square inch (0.06 m2). Once opening shall commence within 12" (300 mm) of the ceiling and the second opening shall commence within 12" (300 mm) of the floor. The minimum ings shall be at least 3 in. (80 mm). dimension if there of air open- with: 2, Doors in Btu/hr not exceed as Construction Walls and ceilings exposed to the outdoors have a continuous, sealed vapor barrier. Openings are gasketed or sealed and 3. ACH is defined 1. combined input of all other than fan-assisted appliances in Btu/hr [ ran = combined tight construction and openable windows are weather stripped and Other openings are caulked or sealed. These include joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc. Ventilation Air Some provincial codes and local municipalities or make-up air be brought into the conditioned require ventilation space as replace- ment air. Whichever method is used, the mixed return air temperature across the heat exchanger MUST not fall below 60 ° continuously, or 55 ° on an intermittent basis so that flue gases will not condense excessively in the heat exchanger. Excessive condensation will shorten the life of the heat exchanger and possibly void your warranty. 441 O1 2314 02 4. Gas Vent Installation • CARBON MONOXIDE POISONING, to death, Read properly FIRE AND Push personal and follow vent injury all this furnace and/or instructions could property of Canada Natural Gas and result in section. Install the vent in compliance with codes of the country havingjurisdiction, local codes or ordinances and these instructions. This Category ] furnace is fan-assisted. A fan assisted appliance is an appliance equipped with an integral mechanical means to either draw or force products of combustion through the heat exchanger. Category ] furnace definition: A central furnace which operates with a non-positive vent static pressure and with a flue loss not less than 17 percent. These furnaces are approved for commonventing and multi-story venting with other fan-assisted or draft hood-equipped appliances in accordance with the NFGC or NSCNGPIC. the vent connector onto the furnace Pro- B149.1-05 in Canada. flue collar of the venter assembly until it touches the bead (at least 5/8" overlap) and fasten with at least two field-supplied, corrosion-resistant, sheet metal screws located at least 140 ° apart. damage. in this Standard pane Installation Code (NSCNGPIC) CSA section 7 and appendix C venting requirements EXPLOSION HAZARD. Failure the National 5. Keep vertical Category [ vent pipe or vent connector short and direct as possible. runs as 6, Vertical outdoor runs of Type-B or ANY single wall vent pipe below the roof line are NOT permitted. 7. Slope all horizontal runs up from furnace to the vent terminal a minimum of 1/4" per foot (21 ram/m). 8. Rigidly support all horizontal portions of the venting system every 6' or less using proper clamps and metal straps to prevent sagging and ensure there is no movement after installation. 9. Check existing gas vent or chimney to ensure they meet clearances and local codes. See Figure 1 10. The furnace Category [ Safe Venting Requirements Category [ furnace vent installations shall be in accordance Parts 10 and 13 of the National Fuel Gas Code (NFGC), Z223.1-2002/N FPA 54-2002; the CSA B149.1-05, National and Propane Installation and vent manufacturer's and/or Section 7 and Appendix Standard of Canada, Natural Code; the local building instructions. codes; with ANSI C of Gas furnace NOTE: The following instructions comply with the ANSI Z223.1/NFPA 54 National Fuel Gas Code and CSA B149.1 Natural Gas and Propane Installation code, based on the input rate on the furnace rating plate. If a Category ] vent passes through an attic, any concealed space or floor, use ONLY Type B or Type L double wall vent pipe. If vent pipe passes through interior wall, use Type B vent pipe with ventilated thimble ONLY. 1, 2, Do NOT vent furnace into any chimney serving an open fireplace or solid fuel burning appliance. 3. Use the same mitted by: • diameter Category ] connector or pipe as per- the National Fuel Gas Code Code (NFGC) ANSI Z223.1-2002 / N FPA 54-2002 sections 10 and 13 venting requirements in the United States or 441 01 2314 02 MUST be connected to a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction. Venting into an unlined masonry chimney or concrete chimney is prohibited. See the 6. Masonry Chimney Venting section in these instructions. 11. Fan-assisted not be vented combustion system Category into single-wall metal vents. [ furnaces shall 12. Category [ furnaces must be vented vertically or nearly cally, unless equipped with a listed mechanical venter. verti- 13. Vent connectors serving Category I furnaces shall not be connected into any portion of mechanical draft systems operating under positive pressure. A 4-to-3 inch reducer is permitted at the flue collar when installing a 50,000 Btuh gas input furnace, if the installation meets all the following requirements for sizing the vent connectors and vents: 1. The National Fuel Gas Code, ANSI Z223.1/NFPA-54-2002, sections 10.5.3.1(1), 10.6.3.1(2), 10.10.3.1, 13.1.2, 13.1.10, and 13.2.21(1) through (3) in the U.S. or 2. The Natural Gas and Propane Installation Code CSA B149.1-05, sections 7.13.1 (b), 7.13.2(b), 7.18.5(b), and Appendix C-GVR no. 2. in Canada. [_ Venting and Combustion Air Check NOTE: placed, When an existing the original venting erly vent adequate LOWING the attached combustion CHECK. Vent Check Category I furnace is removed or resystem may no longer be sized to prop- appliances, and to make sure there is air for all appliances, MAKE THE FOL- VentPipe _1 I A/ Draft Hood Typical Gas Water Heater ! CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation, could poisoning or death: result in The following steps shall be followed connected to the venting system operation, while all other appliances venting 1 .Seal system are not any unused carbon for each appliance being placed into connected to the in the venting system. is no blockage or restriction, leakage, corrosion and deficiencies which could cause an unsafe condition. 3.As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. 4.Close fireplace dampers. 5.Turn on clothes dryers and any appliance not connected the venting system. Turn on any exhaust fans, such to as range hoods and bathroom exhausts, sothey are operating at maximum speed. Do not operate a summer exhaust fan. 6.Follow the lighting instructions. Place the appliance inspected into operation. Adjust the thermostat appliance is operating continuously. being so 7.Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle. (Figure 4) 8.If improper venting is observed, during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or Code. CSA B149, 1, Natural Gas and Propane draft hoo_, this indicates Venting to Existing Masonry Chimney Dedicated venting of one fan assisted sonry chimney is restricted. A chimney 2.Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223. 1/NFPA 54 or CSA B 149. 1, Natural Gas a nd Propane Installation Code and these instructions. Determine that there other NOTE: If Elaine p_ulls towards sufficient infiltration air. monoxide in operation: openings ! Installation furnace into any mamust first be lined with either Type B vent sized in accordance with NFGC tables 13.1 or 13.2 or a listed metal lining system, sized in accordance with the NFGC section 13.1.7 for a single appliance or 13.2.19 for multiple appliances, or NSCNGPIC Appendix C, section 10. (See Section 6 Masonry Chimney Venting of these instructions.) Listed, corrugated metallic chimney liner systems in masonry chimneys shall be sized in the U.S. by using NFGC tables per 13.1.7 for dedicated venting and per 13.2.19 for common venting with the maximum capacity reduced by 20% (0.80 X maximum capacity) and the minimum capacity as shown in the applicable table. Corrugated metal vent systems installed with bends or offsets require additional reduction of 5% of the vent capacity for each bend up to 45 ° and 10% of the vent capacity for each bend from 45 ° up to 90 °. In Canada, use the NSCNGPIC. NOTE: Two(2) 45 ° elbows are equivalent to one (1) 90 ° elbow. Combined Venting into a Masonry Chimney Venting into a masonry or concrete chimney is only permitted as outlined in the NFGC or NSCNGPIC venting tables. Follow all safe venting requirements. Note: See section "6. Masonry Chimney Venting'. 9.After it has been determined that each a pplia nce connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use. _] 441 01 2314 02 5. Horizontal Venting Vent Termination Category I Furnaces With External Power Venters In order to maintain a Category naces when vented horizontally venter is REQUIRED ] classification with sidewall to maintain a negative Venting Through a Non-Combustible Combustible Wall of fan-assisted furtermination, a power pressure in the vent- ing system. In the U.S.: Per the NFGC, a listed power venter may be used, when approved by the authority having jurisdiction. In Canada: manufacturer Only power venters approved by the appliance and where allowed by the authority having jurisdic- tion may be used. Consult consult for power the Fields venters 441 01 2314 02 certified Controls Co. or Tjernlund for use with this furnaces. Products, Inc. Power Venter manufacturer instructions. Select the power venter to match the Btuh input of the furnace being vented. Follow all of the power venter manufacturer's installation requirements included with the power venter for: • venting • vent terminal • preventing • protecting • see Figure NOTE: Please External and installation, location, blockage building by snow, materials 5 for required It is the responsibility from degradation by flue gases, vent termination. of the installer to properly terminate the vent and provide adequate shielding. This is essential in order to avoid water/ice damage to building, shrubs and walkways. [_ iiiiiiiiiiiiiiiiii;ii_;;_i:_i:_i;!;!:;!_i_ii!_!ii_i:_:i::_;_i_!_!_i!ii!ii!ii!ii!ii!ii!ii!ii!ii!ii!ii!_i!;iiiiiiiii_iiiiiiiiiiiiiiiiiiiiiii_!!!;!_i ¸ii;ilililiiiiiiiiiiiiiiiiiiiiiiii_i_i_ii!!!iiiii Other than Direct Vent Termination Clearance r_ A (_ AIR SUPPLYINLET VENT TERMINAL Item AREA WHERE TERMINAL IS NOT PERMITED Canadian Installation(1) Clearance Descriptions Clearance above grade, veranda, porch, deck, balcony, or U.S. Installation 12" (30cm)# 12" (30 cm) 6" (lfi cm) for appliances_<10,000 BTUH (3kW), 12" (30 cm) for appliances> 10,000 Btub (3 kW) and _<100,000Btub (30 kW), 36" (01 cm) for appliances> 100,000Btuh (30kW) above lhe opening. (2) anticipated snow level B Clearance to a window or door that may be opened C Clearance to a permanently D Vertical clearance to a ventilated soffit located above the 4' (1.2 m) below or to the side of the opening. 1' (30 cm) closed window terminal within a horizontal distance of 2' (61cm) from the centedine of the terminal E Clearance to an unventilated F Clearance to an outside corner G Clearance to an inside corner H Clearance to each side of the centefline extended above 3' (91 cm) within 15' (4.5 m) above the meter/regulator 3' (91 cm) electrical meter or gas service regulator assembly assembly assembly I Clearance to service regulator vent outlet 3' (01 cm) J Clearance to non-mechanical 6" (15cm)forappliances_10,000 Btuh (3 kW) and _<100,000 Btuh the combustion soffit air supply inlet to building or air inlet to any other appliance (30 kW), 36" K Clearanceto a mechanicalair supplyinlet 6' (1.83 m) L Clearanceunder a veranda, porch,deck, or balcony 12" (30 cm) + M Clearance to each side of the centefline extended above or (01 cm) for appliances 4' (1.2 within m) below 15' (4.5 m) above or to the side if within 10' the meter/regulator of opening: 1' (30 cm) above opening. > 100,000 Btuh (30 kW) 3' (91 cm) above (3m) horizontally below vent terminal of the furnace to a dryer or water heater vent, or other appliance's direct vent intake or exhaust. N Clearance from a plumbing vent stack 3' (01cm) 3' (01cm) 0 Clearanceabove a paved sidewalkor paved drivewaylocated on publicproperty. 7' (2.13m) 7' (2.13m) (1.) In accordance with the current CSA B149.1, Natural Gas and Propane (2,) In accordance with the currem ANSI Z223.1/NFPA Installation Code # 18" (46 cm) above roof surface + Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. fi4, National Fuel Gas Code For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B140.1, clearances shall be in accordance installation instructions. with local installation codes and the requiremenls of the gas supplier and the manufacture's A vent shall nol terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. Notes: 1, 2. The vent for this appliance shall not terminate a. Over public walkways; or b. Near soffit vents or crawl space vents or other areas where condensate c. Where condensate When locating vent terminations, Recirculafion or vapor could create a nusiance or hazard or property damage; or vapor could cause damage or could be detrimental to the operafion of regulators, consideration can cause poor combustion, relief valves, or other equipment. must be given to prevailing winds, location, and other conditions which may cause recirculation inlet condensate problems, and accelerated of the combusfiob products of adjacent vents. corrosion of the heat exchangers. 441 01 2314 02 6. Masonry Chimney Venting Chimney Inspection All masonry chimney construction must conform to Standard ANSI/NFPA 211-2003 and to any state or local codes applicable. The chimney must be in good condition and a complete chimney inspection must be conducted prior to furnace installation. If the inspection reveals damage or abnormal conditions, make necessary repairs or seek expert help. See "The Chimney Inspection Chart" Figure 6. Measure inside area of tile-liner and exact height of chimney from the top of the chimney to the highest appliance flue collar or drafthood outlet. Connector Type To reduce lems, flue gas heat loss and the chance the vent connector of condensate must be double-wall Type masonry to the outdoors Chimneys shall below the roof line, relining might be required. conform to the Standard for Chimneys, Fire- chimney places, Vents, and Solid Fuel 211-2003 in the United States Building Code Code in Canada of Canada) is being used and it is exposed Burning Appliances and to a Provincial (in its absence, and must be in good the ANSI/NFPA or Territorial National Building condition. U.S.A.- Refer to Sections 13.1.9 or 13.2.20 of the N FGC or the authority having jurisdiction to determine whether relining is required. If relining is required, use a properly sized listed metal liner, Type-B vent, or a listed alternative venting design. prob- B vent. This model (*8DNL) kits. A multi-position Venting Restrictions for Chimney Types Interior Chimney - has no sides exposed to the outdoors below the roofline. All installations can be single furnace or common vented with another draft hood equipped Category ] appliance. Exterior Chimney - has one or more sides exposed to the outdoors below the roof line. All installations with a 99% Winter Design Temperature* below 17°F must be common a draft hood equipped Category I appliance. Ifa claytile-lined vented only with The 99%Winter DesignDry- Bulb(db)temperatures arefoundinthe1993ASHRAE FundamentalsHandbook,Chapter24, Table1 (UnitedStates) and 2 (Canada),or usethe 99.6%heatingdbtemperaturesfound inthe1997or 2001ASHRAEFundamentalsHandbook,ClimaticDesign Informationchapter,Table1A (UnitedStates) and 2A (Canada). for use with NAHAOO2DH is NOT listed for use with Chimney Adapter furnace in the downflow position that is listed one of the Chimney Adapter may be used with a masonry Kits NAHAOOIDH chimney. or Canada (and U.S.A.)-This furnace is permitted to be vented into a clay tile-lined masonry chimney that is exposed to the outdoors below the roof line, provided: 1. Vent connector is Type-B double-wall, 2. This furnace is common vented with at least 1 draft hoodequipped appliance, and and The combined appliance input rating is less than the maximum capacity given in Table A, and CARBON MONOXIDE POISONING, EXPLOSION HAZARD. FIRE AND The input rating of each space-heating appliance is greater than the minimum input rating given in Table B for Masonry Chimneys for the local 99% Winter Design Temperature. Chimneys having internal areas greater than 38 square inches require furnace input ratings greater than the input ratings of these furnaces. See footnote at bottom of Table B, and Failure to properly vent this furnace could result in death, personal injury and/or property damage. These furnaces are CSA (formerly AGA and CGA design-certified for venting into exterior clm tile-lined masonry chimneys with a factory accesso ry Chimney Adapter Kit. Refer to the furnace rating 31atefor correct kit usage. The Chimney Adapter Kits are for use with ONLY furnaces having a Chimne_ Adapter Kit number marked on the furnace ratin i plate. 441 01 2314 02 5. The authority having jurisdiction If all of these conditions sign shall be used, Type-B vent. cannot approves. be met, an alternative such as a listed chimney-lining venting system, [_ deor a Exterior Masonry FAN+NAT Type-B Installations Double-Wall Inspections Chimney, Vent with Connectors © NFPA& AGA If the inspection INTERNAL AREA OF CHIMNEY (SQ IN.) (FT) 12 19 28 38 6 74 119 178 257 8 80 130 193 279 10 84 138 207 299 15 NR 152 233 334 20 NR NR 250 368 30 NR NR NR 404 Table BMinimum Allowable Input Rating of Space-Heating Appliance in Thousands of Btu per Hr VENT HEIGHT (FT) INTERNAL 12 28 Local 99% Winter Design Temperature: o used tile-lined chimney: b. Indicates the chimney exceeds the maximum permissible size in the tables, the chimney should be rebuilt or relined to conform to the requirements of the equipment being installed and the authority having jurisdiction. A chimney without a clay tile liner, which is otherwise in good condition, shall be rebuilt to conform to AN SI/N FPA 211 or be lined with a UL listed (ULC listed in Canada) vent. Relining with a listed metal ered to be a vent-in-a-chase. metal liner or UL listed Type-B liner or Type-B vent is consid- If a metal liner or Type-B vent is used to line a chimney, no other appliance shall be vented into the annular space between the and the metal liner. APPLIANCE APPLICATION REQUIREMENTS Appliance operation has a significant impact on the performance of the venting system. If the appliances are sized, installed, adjusted, and operated properly, the venting system and/or the appliances should not suffer from condensation and corrosion. The 38 venting system with applicable and all appliances shall be installed listings, standards, and codes. in accordance 17 to 26 ° F* The furnace should be sized to provide 100 percent of the design heating load requirement plus any margin that occurs because of furnace model size capacity increments. Heating load estimates 0 55 99 141 8 52 74 111 154 10 NR 90 125 169 NR NR 167 212 2O NR NR 212 258 30 NR NR NR 362 approved engineering methods. Excessive oversizing of the furnace could cause the furnace and/or vent to fail prematurely. When a metal vent or metal liner is used, the vent or liner must be in Temperature: 5 to 16° F* NR 78 Design 121 166 NR 94 135 182 10 NR 111 149 198 15 NR NR 193 247 20 NR NR NR 293 30 NR NR NR 377 0 ,_ of a previously 6 Local 99% Winter _" will deter- Shows signs of vent gas condensation, the chimney should be relined in accordance with local codes and the authority having jurisdiction. The chimney should be relined with a listed metal liner or Type-B vent to reduce condensation. If a condensate drain is required by local code, refer to the NEGC, Section 10.9 for additional information on condensate drains. chimney AREA OF CHIMNEY (SQ IN.) 19 the sale a nd at the time of installation a. Table ACombined Appliance Maximum Input Rating in Thousands of Btu per Hr VENT HEIGHT before mine the acceptability of the chimney or the need for repair and/or (re)lining. Refer to the Chimney Inspection Chart to perform a chimney inspection. Local 99% Winter Design Temperature: can be made using approved methods available from Air Conditioning Contractors of America (Manual J); American Society of Heating, Refrigerating, and Air-Conditioning Engineers; or other good condition manufacturer's NR NR 145 196 8 NR NR 159 213 o 10 NR NR 175 231 o is NR NR NR 283 2O NR NR NR 333 30 NR NR NR NR in accordance To prevent condensation in the furnace lowing precautions must be observed: 1. -10 to 4° F* 6 and be installed instructions. with the vent or liner and vent system, the fol- The return-air temperature must be at least 60°F db except for brief periods of time during warm-up from setback at no lower than 55°F db or during initial start-up from a standby condition. Adjust the gas input rate per the Low gas input rate causes low vent ing condensation and corrosion in ing system. Derating is permitted 2000'. installation instructions. gas temperatures, ca usthe furnace and/or ventonly for altitudes above i -11 ° F or lower Local 99% Winter Design Temperature: lower* Not recommended 3. Adjust the air temperature rise to the midpoint of the rise range or slightly a hove. Low air temperature rise ca n ca use low vent gas temperature and potential for condensation problems. 4. Set the thermostat short cycling. -11 ° F or for any vent configuration The 99% Winter Design Dry-Bulb (db) temperatures are found in the 1993 ASHRAE Fundamentals Handbook, Chapter 24, Table 1 (United States) and 2 (Canada), or use the 99.6% beating db temperatures found in the 1997 or 2001 ASHRAE Fundamentals Handbook, Climatic Design Information chapter, Table 1A (United States) and 2A (Canada). heat anticipator or cycle rate to reduce Air for combustion must not be contaminated by halogen compounds which include chlorides, fluorides, bromides, and iodides. These compounds are found in many common home products such as detergent, paint, glue, aerosol spray, bleach, cleaning solvent, salt, and air freshener, and can cause corrosion of furnaces and vents. Avoid using such products in the combustion-air sup- 441 01 2314 02 ply. Furnace the furnace ture failure use during construction to be exposed of the furnace Vent dampers of the building could cause can cause to halogen compounds, causing premaor venting system due to corrosion. on any appliance connected to the common condensation not use vent dampers Race. and corrosion on appliances in the venting common vented system. vent CHIMNEY INSPECTION CHART Foradditionalrequirementsreferto the NationalFuelGas CodeNFPA54/ANSIZ223.1-2002 andANSIINFPA211-2003Chimneys,Fireplaces, Vents,and Solid Fuel BurningAppliancesin the U.S.A. or to the Canadian InstallationCode CSAB149.1-05 in Canada. condition: Rebuild Missing mortar crown or brick? I ,_ withclay tile No Yes Reline lineror top seal orreline chimnei'as _ liner and top seal in good IRepair metalvent, fuel oil residue? Mortar or Remove mortar file debris? and tile debris? Remove metal vent or liner. _,,_stile n_isalignrnent, Yes p- ing sections, No No adapter venting - / Condensate drainage atbottom _ _ \ /,sObi e, _ < _:_r ofchimney? _ Chimney . / , be,owroof,ine? Yes [ _ / / 441 01 2314 02 _ _ U_nUalUe'_u;nace./ \ /_ , IsChimnevto _. Suitable vo_[ _ '_[ InstallchimneyI I adaprerper I II _ _ _.3,_ i, " tab,iy ._ / / application/ _'-]Vl TvDe-Bven_/ "' / _. / T.T v^_ No Not Suitable instructions for ' _ j_rT-"_, [ S_le adapter venting _ I instal]ation instructions. / Consul__ /PartCofchimney_ t,,_J_ _2_uT Linechim !ywitbpropedy sized,listedflexiblemetal linerorType-BventperNFGCor NSCNGPIC VentSizingTables andlinerorventmanufacturer's Not Suitable \ ,nstructionsfor apl_!ica! i°n / _,uitability/ Do with this fur- | _' I installchimney [_ 7. Gas Supply and Piping Typical Gas Piping ('8DNL) CARBON MONOXIDE EXPLOSION HAZARD. POISONING, FIRE AND Failure to follow safety warnings exactly could result in death, personal injury and/or property damage. Models designated for Natural Gas are to be used with Natural Gas ONLY, unless properly converted to use with LP gas. Listed Flexible Gas Appliance Connector if 11o4 IO] Se_c% Gas Supply Requirements union • Use only the Type of gas approved plate for approved gas type. for this furnace. See rating • Gas input must not exceed the rated input shown on the rating plate. Overfiring will result in failure of heat exchanger and cause dangerous operation. Drip leg & pipe cap _. \ Gas control valve Do not allow minimum supply pressure to vary downward. Doing so will decrease input to furnace. Refer to Table 3 for gas supply. Refer to Table 5 or Table 6 for manifold pressures. i I Elbows & short nipples Pressures 25-25-17 3. Use black iron or steel pipe and fittings by local code. 4. Use pipe thread gases. 5. Use ground joint unions and install a drip leg no less than 3" long to trap dirt and moisture before it can enter gas control valve inside furnace. NOTE: The gas supply line must be installed bya qualified service technician in accordance with all building codes. 6. Provide a 118" NPT plugged tapping for test gauge immediately up stream of gas supply connection NOTE: 7. Use two pipe wrenches gas valve from turning. Gas Type Supply Pressure Recommended Natural Propane 7" 11" Max. Min, 14" 4,5" 14" 11" Gas Piping Requirements 1, 2. In the state of Massachusetts. a. Gas supply connections MUST be performed censed plumber or gas fitter). by a li- b. When flexible connectors are used, the maximum shall not exceed 36" (915 ram). length c. When lever handle type manual equipment are used, they shall be T-handle valves. valves d. The use of copper tubing for gas piping is NOT approved. shutoff Install gas piping in accordance with local codes, or in the absence of local codes, the applicable national codes. It is recommended that a manual equipment shutoff valve be installed in the gas supply line outside the furnace. Locate valve as close to the furnace as possible where it is readily accessible. Refer to Figure 7. compound which when or other is resistant making pipe approved to natural and LP connection to furnace. connections to prevent NOTE: If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously served another gas appliance. 8. Flexible corrugated metal gas connector may NOT be used inside the furnace or be secured or supported by the furnace or ductwork. 9. Properly size gas pipe to handle combined appliance load or run gas pipe directly from gas meter or LP gas regulator. 10. Install correct pipe size for run length 11. Measure pipe length from gas meter lator to determine gas pipe size. and furnace or LP second rating. stage regu- Left Side Gas Supply Piping Gas line can be installed provided in the left side directly to the gas valve through of the cabinet. See Figure 7 the hole Right Side Gas Supply Piping FIRE HAZARD Failure to follow safety warnings exactly could result in death, personal injury and/or property damage. Use wrench to hold furnace gas control valve when turning elbows and gas line to prevent damage to the gas control valve and furnace. Two(2) 90 ° street two(2) close Figure 7. nipples or two(2) are required 90 ° standard for right elbows and side gas supply. See Piping with Street Elbows 1. Assemble the elbows so that the outlet of one(l) elbow is 90 ° from the inlet of the other. The elbows should be tight enough to be leak proof. An additional 1/4 turn will be required at the end of step _] elbows 2, see Figure 8. 441 01 2314 02 2. Screw elbow assembly into gas valve far enough to be leak proof. Position el bow assembly so that the inlet of the el bow is at the bottom of the gas valve. An additional 1/2 turn will be required in step 3. Turn open end of inlet elbow to face the right side of the furnace (1/4 turn), see Figure 9. 3. Turn assembly an additional 1/2 turn to position top of the gas valve and in line with gas opening furnace, see Figure 7 and Figure 10. iiiiiiiiiiiiiiiiiiiiiiii i:iiiiiii;;;i _i¸!!iii!ilil !!!!!!!i !!!iiiii¸;I i!iliiii¸i¸Ii;¸ FIRE OR EXPLOSION HAZARD. Failure to properly install metal gas connector could result in death, personal injury and/or property damage. inlet near the on right side of A flexible corrugated metal gas connector must be properly installed, shall not extend through the side of the furnace, and shall not be used inside the furnace. E,bows *aDNL Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2" outside furnace. Additional LP Piping Requirements • Have a licensed tank and check • If copper tubing is used, it MUST comply with limitation set in Local Codes, or in the absence of local codes, the gas codes of the country having jurisdiction. • Two-stage 25-23-23c Gas Valve with Elbows LP gas dealer make all connections at storage all connections from tank to furnace. regulation of LP gas is recommended. (*8DNL) FIRE OR EXPLOSION HAZARD. A natural gas or LP gas leak ignited by an open flame or spark could result in death, personal injury and/or property damage. Natural gas is lighter than air and will rise. Liquefied petroleum (LP) gas is heavier than air and will settle and remain in low areas and open depressions. Thoroughly ventilate area and dissipate gas. Do NOT use a match or open flame to test for leaks, or attempt to start up furnace before thoroughly ventilating area. 25-25-03 Gas Valve with Elbows (*aDNL) Final Check • Test all pipes • If orifices leaks. • During for leaks. were pressure changed, testing make sure of gas supply they piping are checked for system: a. If test pressure does not exceed 1/2 psi, isolate the furnace from the gas supply piping system by closing the equipment shutoff valve. 25-25-12 4. Gas supply line then can be run directly into opening b. If test of elbow. Assemble in Figure 2. Follow elbows 8. steps 441 01 2314 02 and nipples 2 through similar 4 Piping with to street elbows Street Elbows. shown exceeds 1/2 psi, the valve must system. furnace To check for leaks each joint. Bubbles apply soap suds or a liquid forming indicate a leak. • Do not use an open flame to test for gas leaks. sion could occur. • Correct even the smallest and its be disconnected • Piping with Close Nipples and Standard Elbows 1. pressure manual equipment shutoff from the gas supply piping detergent to Fire or explo- leak at once. [_ 8. Electrical Wiring 7. ELECTRICALSHOCK HAZARD. Failure to follow safety warnings result in death or personal injury. exactly could Turn OFF electrical power at fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage. Power Supply Wiring The furnace MUST be electrically wired and grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code (NEC), ANSI/NFPA 70-2002 or the Canadian Electrical Code (CEC), CSA C22.1 in the U.S., in Canada. The power supply to the furnace connections must be between 104 VAC and 127 VAC during furnace operation for acceptable performance. Field wiring connections must be made inside the furnace connection box. A suitable strain relief should be used at the point the wires exit the furnace casing. Copper conductors shall be used. Line voltage wires should conform to temperature limitation of 63 ° F (35 ° C) rise. Wire and circuit breaker sizing shall be based on the ampacity of the furnace electrical components plus the amps for all installed accessories (1.0 amps toni for EAC and HUM). Ampacity can be determined by using the NEC or CEC. NOTE: Furnace will not have normal operation is line polarity is reversed. Check ALL field and control connections prior to operation. Furnace must be installed so the electrical components are protected from water and connected to its own separate circuit. J- Box Relocation The J-box is installed on left side of casing. location on right side can be used. An alternate J-box 1. Remove bag containing two hole plugs and two self-tapping screws from loose parts bag in blower compartment. 2. Remove 3. Move 4. Move J-box to alternate location tapping screws from bag. 5. A wire tie may need 6. Apply and discard two screws holding J-box Position all wires away from sharp edges Do not pinch J-box or other wires when compartment door. Thermostat Thermostat location has an important effect on the operation of the furnace. Follow instructions included with thermostat for correct mounting and wiring. Low voltage connections to furnace must be made on terminal board of furnace control. (See Figure 11) If cooling is used, the Y from the thermostat must be connected the control board Y to energize cooling blower speed. Set thermostat Support heat anticipator Heat anticipator fier is installed. mostat. furnace _] two hole plugs right to left J-box and attach to be cut for additional from bag at left J-box with the Technical setting will need to be measured if 24VAC humidiMeasure currentin series from R to W at thether- Be sure 24VAC humidifier is wired up to control. Allow to operate for 2 minutes before recording the AC amper- age reading. Set anticipator on thermostat to recorded value. Optional Equipment All wiring from furnace to optional equipment MUST conform cal codes or, in the absence of local codes, the applicable codes. Install wiring in accordance with manufacturer's tions. Humidifier/Electronic to lo- national instruc- Air Cleaner The furnace is wired for humidifier connection. and/or electronic air cleaner REDUCED FURNACE LIFEHAZARD Failure to follow reduced furnace caution life. Do NOT exceed 115V/1.0 load for both the EAC terminal combined. instructions may result in amp. maximum current terminal and the HUM to casing. location. using wire in accordance to Manual. HUMIDIFIER large hole plug from and moving parts. reinstalling blower two self- length. location. pressure gized - switch when The HUM closes the inducer (115VAC) is energized on a call for heat. when The HUM the is ener- is energized. ELECTRONIC AIR CLEANER - EAC is energized when there is a blower speed call, except is NOT energized when blower operates in the hard-wired continuous fan mode. 441 01 2314 02 Electrical Control Connections Connections % llSV. 60Hz. DiagnosticLight 24 VAC HUM_4 -- BOX P Jumper i Ground HUM _tat Therm°_ i @ t i i i 1 , 'I' I,I t i FUSE i i 25-24-98 Low Voltage Terminal Board Furnace Control Fuse The 24V circuit contains a 5-amp, automotive-type fuse located on furnace control. (See Figure 12) Any electrical shorts of 24V wiring during installation, service, or maintenance may cause fuse O NOTE: 115 VAC/6OHz/single-phase Operating voltage range*: 127 VAC max, 104 VAC min. * Permissible 25-25-13 to blow. If fuse replacement size (5 amp.). is required, use only a fuse of identical limits of voltage at which unit will operate satisfactorily Furnace Control The furnace control is preset at the factory with ON delay of 30 seconds in the heating mode. The blower OFF timing is preset at 140 seconds. If desired, the fan OFF delay can be reset to obtain the longest delay times while still maintaining comfort levels. See "Furnace Wiring Diagram". 9. Ductwork and Filter nace is NOT permitted. Supply ONLY the bottom of the furnace. CARBON MONOXIDE POISONING HAZARD. Failure to properly personal injury. seal duct could result in death or Do NOT draw return air from inside a closet or utility room where furnace is located. Return air duct MUST be sealed to furnace casing. Failure to install furnace on noncombustible subbase could result in death, personal injury and/or property damage. Place furnace on noncombustible subbase on downflow applications, unless installing on non-combustible flooring. is permitted to Duct Design Design and install the air distribution Conditioning Contractors of America methods that conform to local codes system to comply with Air manuals or other approved and good trade practices. When the furnace is located in an area near or adjacent to the living area, the system should be carefully designed with returns to minimize noise transmission FIRE HAZARD. duct connection through Any blower moving which could be objectionable the supply a high volume when the unit is located a living area. It is often advisable der the floor and return air ducts Refer to furnace Technical airflow information. and return of air will produce to route the supply through the attic. Support Manual air grilles. audible noise very close to air ducts un- (BlowerData) for Size ductwork to handle airflow for heating and air conditioning if used. Duct Installation Requirements Duct Connections This furnace may be installed in only a top return-air application. Return air duct connection through the side(s) or back of the fur441 01 231402 When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. Eil • Ductwork installed in attic, or exposed requires a minimum of 2" of insulation barrier. • Ductwork installed in an indoor unconditioned space requires a minimum of 1" of insulation with indoor type vapor barrier. CARBON MONOXIDE POISONING HAZARD. Failure to follow safety warning result in death or personal injury. exactly could Install cooling coil on furnace discharge. Cool air passing over heat exchanger could cause condensate to form resulting in heat exchanger failure. to outside temperatures with outdoor type vapor Inspection Panel on Some Models For a furnace not equipped with a cooling be provided with a removable accessible when the furnace coil, the outlet duct shall access panel. This opening shall be is installed and shall be of such a size that the heat excha nger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. This access cover shall be attached in such a manner as When the furnace is used with a cooling unit, the furnace shall be installed parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering the furnace. Chilled air going through the furnace could cause condensation and shorten furnace life. Dampers (purchased locally) can be either automatic or manual. Manually or automatically operated dampers MUST be equipped with a means to prevent furnace or air conditioning operation, unless damper is in the full heat or cool position Installation branches, flexible and supply duct connectors connections 4 Sub-bases sub-base for Combustible Floors Part Number Furnace The N _ Subbase NOTE: for Combustible Floors - Furnace Only Floors Supply opening is 37/8" MUST 1. Cut the opening in the floor be used when the rear of the from a wall behind according Table 4 because the base is equipped center the base over the opening. furnace. the fur- to the dimensions with locating The opening in the base is 11/4" shorter and 11/8" narrower than the minimum required size of the opening in the floor. This is done to maintain a 1" clearance between the floor and the plenum. 2. Fabricate the plenum that the dimensions to the dimensions given are outside given in Table 4. Note dimensions. Floors Dimensions for Combustible Dimensions Opening In Floor Opening In Base For Plenum J* K** L M N P R Typical Plenum Dimensions NAHHOOISB 1511/16 283/4 149/16 16 16114 14518 15 131/2 15 131/2 NAHHOO2SB 195/16 283/4 183/16 16 16114 18114 15 171/8 15 171/8 221/2 24J/4 28J/4 239/16 16 16]/4 235/8 15 221/2 15 NAHHOO4SB 1511/16 209/16 149/16 16 161/4 145/8 15 131/2 15 131/2 NAHHOOSSB 195/16 209/16 183/16 16 161/4 181/4 15 171/8 15 171/8 NAHHOO9SB 24]]/16 209/16 239/16 16 16]/4 235/8 15 221/2 15 221/2 Subbase for Coil Box Outside Dimension _ Base Spacer Side To Side 3. Set the base over the opening in the floor, centering the opening in the base over the opening in the floor. Fasten the base to the floor with screws or nails. See Figure 13 and Figure 14. 4, Drop the plenum through the opening in the base. of the plenum should rest on top of the combustible _] in tabs that Only NAHHOIOSB a floor, even when the fur- from Therefore maintain a 37/8 ', clearance nace (where applicable). are recommended for Combustible sub-base Floor for Combustible downflow furnace is set on a combustible nace is installed on a coil box. to furnace. If air return grille is located close to the fan inlet, install at least one, 90 ° air turn between fan and inlet grille to reduce noise. Table air leaks. Sub-Bases of locking-type dampers is recommended in all or in individual ducts to balance system's air flows. Non-combustible, for return to prevent The flange floor base. 441 01 2314 02 Exploded Furnace View ONLY of Sub-Base for Exploded Downflow View of Base for Cased Coil Plenum Plenum S H J Combustible Floor Base Combustible Floor Base 25-21-46b 25-21-46b Consideration must be given to the height of the base to allow for easy installation of the condensate drain. See Figure 17. This Setting subbase for combustible floors has been designed so that the height of the subbase ra ises the downflow coil off the floor to allow easy installation of the condensate drain the Base Setting the Base Subbase Insulation co, Subbase Insulation / Wood Floor Plenum 25-20-46A Wood Screw Sub-base for Combustible Floors- Downflow Coil _ _ Condensate _ Plenum Line Raised 25-20-46A by Base Adapter Box The subbase for combustible floors is required when a downflow furnace, used with a downflowcoilbox, is set on combustible flooring. 7 NOTE: Supply opening is 3 /8' from the rear of the furnace. Therefore maintain a 37/8 " clearance from wall (where applicable). 25-20-52 Cut the opening in the floor according Table 4 because the base is equipped center the base over the opening. 1, to the dimensions in with locating tabs that Non-Combustible Floor: The opening in the base is 11/4" shorter and 11/8" narrower than the minimum required size of the opening in the floor. This is done to maintain a 1" clearance between the floor and the Set the furnace over the opening in the floor. If necessary, grout around the base to seal air leaks between the base and the floor. plenum. Filters: be used. Fabricate the plenum to the dimensions in Table the dimensions given are outside dimensions. 3. Set the base over the opening in the floor, centering the opening in the base over the opening in the floor. Fasten the base to the floor with screws or nails. See Figure 15 and Figure 16. furnace may be installed in the return air plenum above the furnace. A filter rack is supplied with each furnace. See Figure 18. 4. Drop the plenum through the opening in the base. of the plenum should rest on top of the combustible • 441 01 231402 4. Note that A filter MUST 2, The 181/4" X 1 53/4" framed The flange floor base. Use either high-velocity filters supplied with the filter type: Washable, flow rating high-velocity of 600 FPM. filters are based on a maximum air Disposable, lowvelocity filtersarebasedona maximum air flowof300FPMwhenusedwithexternal filtergrille. i • See page 33, Circulation mation. Air Blower Data for additional infor- If there is insufficient plenum height for this type of installation, fil- ters may be installed in any accessible location in the return air system. In such a case, the filters should be of equivalent size and style as originally supplied with the furnace. Filter Installation REDUCED FURNACE LIFE HAZARD Failure to follow caution reduced furnace life. instructions Version may result in Use of excessively dirty and/or restrictive air filters may increase furnace operating temperatures and shorten the life of the furnace. ,,A,, l "A'" 14" (350mm) Filters supplied with the furnace are rated at a maximum of 600 fpm air velocity and sized for the furnace's airflow rate. Replacement filters must be of equivalent type, size, and rating except as described below. Disposable, low-velocity filters may be used to replace washable, high-velocity filters, providing they are sized for 300 FPM or less. 25-25-14 OR Filter Rack Installation Version "B" 16" Version "A" factory-attached top of the blower (400mm) to the housing 25-25-14a OR Version factory-supplied installed "B" but field The redesigned filter bracket needs to be centered on top of the flanges spanning the depth of the flange opening. Position it sothe "V" portion is between the inner sides of the flanges with the flat tabs are resting on top of the flange edges. The tabs can then be bent over the flanges on both ends by hand or by tapping lightly with a hammer to secure the bracket to the top of the furnace. (see Figure 18) NOTE: The return air plenum MUST extend a sufficient above the furnace (dimension "A" in Figure 19) to provide attachment of a return air duct or grille above height for the No further attachment is necessary. Once the plenum is attached to the top of the furnace the bracket will not move. The bracket will look like Figure 18 after being formed onto the flanges. the filters. NOTE: Plenum must be fitted as close to the return air flange of the furnace as possible to eliminate any air bypassing the filters. Filter Removal 1. Remove the right hand side of the fur- 2. nace blower opening. Slide filter into furnace until it is in position to be pushed up and over into place on the left hand side of furnace. See Figure 19. Reach up above right side of blower rack at top of furnace. 3. Straighten up filters and pull straight Pull out through right door opening. Slide remaining filter into furnace 4. Vacuum side of furnace. See Figure Filters _] can only be installed through 19. and up into place on right hand blower compartment door. and lift dirty filters down out of at side of blower. clean or wash with warm water and dry thoroughly fore replacing. 441 O1 2314 02 be- NOTE: If filters are only suitable vise homeowner that filter conditioning is added. application, ad- size may need to be increased for heating if air Addition Of Air Conditioning must be consulted for proper coil location and installation proce- dures. With a parallel flow arrangement, dampers must be installed to prevent chilled air from entering the furnace. If ma nually operated dampers are used, they must be equipped with a means to prevent operation of either unit unless the damper is in full heat or full cool position. When a refrigeration coil is used in conjunction with this furnace, it must be installed on the discharge side of the furnace to avoid condensation on the heat exchanger. The coil installation instructions 10. Checks Copper or plastic tubing may be used for the condensate drain line. and AdJustments iiiiiiiil!!!!! ii¸¸Iiiiiii_ ¸¸I Startup !!i!!iiil;;i;;iiiiiiiiiiiiiiii;iiiiiii Typical NOTE: Manual. Refer to startup procedures in the Users Gas RegulatorAdjustment Under Ca ELECTRICAL Control Valve Information SHOCK, FIRE, OR EXPLOSION HAZRD. HONEYWELL Outlet Pressure ©o Tap 1/8NPT / Failure to follow safety warnings exactly could result in death, personal injury, and/or property damage. If any sparks, odors or unusual noises occur, immediately shut OFF gas and power to furnace. Check for wiring errors or obstruction to blower. OUTLET Inlet Pressure Tap 1/8NPT 25-24-98a Gas SupplyPressure 4. Set manifold 5. When the manifold ment screw cover Gas supply pressure should be within minimum and maximum values listed on rating plate. Pressures are usually set by gas suppliers. 6. (See L.P. Gas Conversion Kit instruction manual for furnaces converted to L.P. gas) 7. to manifold pressure with burners oper- FIRE OR EXPLOSION HAZARD. Failure to turn OFF gas at shut off before connecting manometer could result in death, personal injury and/or property damage. Turn OFF manometer. 1. gas at shut off before 3. Check Check for leaks 5 or Table 6. the adjust- at plug. can be used to measure with gas supplier for actual input to furnace. BTU content. 1. Turn OFF gas supply to all appliances other start furnace. Use jumper wire on R to W. 2. Time how many seconds it takes the smallest meter to make one complete revolution. Note: two. If meter content than furnace uses a 2 cubic foot dial, divide results Refer to Example. of 1,000 The Example BTU's per cubic is based and dial on the gas (seconds) on a natural by gas BTU foot. Example Natural Gas BTU Content With gas OFF, connect manometer to manifold pressure tap on outlet of gas control valve. See Figure 20. Use a manometer with a 0" to 12" water column range. Remove manifold pressure adjustment screw cover on furnace gas control valve. Turn screw counterclockwise to decrease manifold pressure and clockwise to increase pressure. See Figure 20. NOTE: Adjustment screw cover MUST be replaced on gas control valve before reading manifold pressure and operating furnace. 441 01 231402 in Table set, replace connecting Turn gas ON. Operate the furnace by using a jumper wire on the R to W thermostat connections on the control. 2. shown Remove jumper wire from thermostat connection on control. Remove manometer connection from manifold pressure tap, and replace plug in gas valve. The gas meter Make adjustment to value pressure is properly on the gas valve. Natural Gas Input Rating Check Manifold Gas Pressure Adjustment NOTE: ating. pressure No. of Seconds Per Hour Time Per Cubic Foot in per cu, foot BTU Per Hour Seconds 1,000 3,600 48 75,000 1,000 x 3,600 + 48 = 75,000 BTUH Refer to Example. The Example is based content of 1,000 BTU's per cubic foot. 3. Remove 4. Relight jumper on a natural gas BTU wire from R to W. all appliances and ensure all pilots are operating. Orifice Sizing NOTE: Factory sized the furnace Technical orifices for natural Support Manual. and LP gas are listed in Ensure furnace isequipped withthe Refer to Table correct main burner orifices. 6 for correct orifice size and manifold 5 or Table pressure for a given heating and propane gas. Operation value and specific gravity To use the natural for natural section Above 2000' Altitude FIRE, EXPLOSION, POISONING HAZARD. high-altitude qualified CARBON service and NamElevationeplate local agency codes, in instructions requirements, the of the altitude MONOXIDE gas-conversion Manufacturer's or applicable shall be done accordance with and in your local gas utility for and heating value provides not only the manifold pressure but also the orifice size. In the natural gas tables, the factoy-shipped orifice size is in bold (42). Other sizes must be obtained from service parts. Failure to follow safety warnings exactly could result in death, personal injury and/or property damage. This gas table, first consult the heating value of the gas supply. Select the heating value in the first column and follow across the table until the appropriate elevation for the installation is reached. The value in the box at the inter- all applicable the absence national High Altitude Sea Level Input Input High Elevation by a Natural Rate Rate Altitude = x (Multiplier)[USA] Multiplier Gas LP Gas 2001'-3000' 0.95 0.90 3001'-4000' 0.93 0.86 4001'-5000' 0.91 0.82 codes 5001'-6000' 0.89 0.78 of 6001'-7000' 0.87 0.74 7001'-8000' 0.85 0.70 the codes. These furnace may be used at full input rating when installed at altitudes up to 2000'. When installed above 2000', the input must be decreased 2% (natural gas) or 4% (LP gas) for each 1000' above * Based on mid-range of elevation. sea level in the USA. In Canada, the input rating must be derated o 5% (natural) or 10 _ (LP) for each 1000' above sea level. This may be accomplished by a simple adjustment of manifold pressure or an orifice change, or a combination of a pressure adjustment and an orifice change. The changes required depend on the installation altitude and the heating value of the fuel. Table 5 & Table 6 show the proper furnace manifold pressure and gas orifice size to achieve proper performance based on elevation above sea level for both natural gas and propane gas. MANIFOLD PRESSUREAND ORIFICE SIZE FOR HIGH ALTITUDEAPPLICATIONS NATURAL GAS MANIFOLD PRESSURE (" w.c.) MEAN ELEVATION 0 to 2000 HEATING VALUE at ALTITUDE BTU/CU. FT. Orifice No. 2001 to 3000 Manifold Pressure Orifice No. Manifold Pressure 3001 to 4000 Orifice No. Manifold Pressure FEET ABOVE SEA LEVEL 4001 to 5000 Orifice No. Manifold Pressure 5001 to 6000 Orifice No. Manifold Pressure 6001 to 7000 Orifice No. Manifold Pressure 725 41 3.7 75O 41 7001 to 8000 Orifice No. Manifold Pressure 41 3.7 41 3.4 3.5 42 3,6 7OO 775 41 3.6 42 3.6 42 3,3 8OO 42 3.7 42 3.4 42 3.1 825 41 3.7 41 3.6 42 3,5 42 3.2 42 2,9 85O 41 3.5 41 3.4 42 3.3 42 3.0 42 2.8 875 41 3.6 42 3.6 42 3.4 42 3.1 42 2.8 42 2.6 9OO 42 3,7 42 3,4 42 3.2 42 2,9 42 2.7 42 2,5 925 41 3.7 42 3.5 42 3.3 42 3.0 42 2,8 42 2.5 44 3.3 95O 41 3.5 42 3,3 42 3,1 42 2.9 42 2.6 42 2.4 44 3.1 975 42 3.7 42 3.2 42 2.9 42 2.7 42 2.5 44 3.2 45 3.6 1000 42 3,5 42 3,0 42 2.8 42 2.6 42 2.4 45 3.7 45 3.4 1050 42 3,2 42 2,7 42 2,5 44 3.3 45 3.6 1100 43 3.6 42 2.5 44 3.2 45 3.6 NOTE: Natural gas data is based on 0.60 specific gravity. For fuels with different specific gravity consult the National Fuel Gas Code ANSI Z223.1-2002/NFPA 54-2002 or National Standard of Canada, Natural Gas And Propane Installation Code CSA B149.1-05. _] 441 01 2314 02 LPG or PROPANE GAS MANIFOLD HEATING VALUE NOTE: MEAN ELEVATION at ALTITUDE BTU/CU, FT. 0 to 2000 2001 to 3000 2500 10.0 Orifice Size #54 The derating PRESSURE (" w.c.) 10.0 9.0 10.0 #54 #54 #55 5001 to 6000 6001 to 7000 7001 to 8000 9.4 8.5 10.0 #55 #55 #56 at 2% (Natural Gas) and 4% (Propane Gas) has been tested Gas) and 10% (Propane Gas) for altitudes NOTE: Gas) and 4% (Propane Gas) has been tested of these furnaces 4001 to 5000 In Canada, the input rating must be derated 5% (Natural the 2001 to 3000 column in Table 5 and Table 6. The derating of these FEET ABOVE SEA LEVEL 3001 to 4000 furnaces at 2% (Natural The burner orifice part nos. are as follows: Orifice #41 1096942 Orifice #42 Orifice #43 1011377 Orifice #44 Orifice #45 1011353 Orifice #54 Orifice #55 1011354 Orifice #56 1011351 1011352 1011376 1011355 Altitude The factory-installed Air Pressure pressure switch by CSA. and design-certified by CSA. Clearances Measure ( I back High and design-certified of 2,000 to 4,500 above sea level. Use from face of orifice to the side of the manifold, Switch need NOT be changed any furnace installations from sea level up to and including altitude. See service parts for use above 8,000' altitude. for 8,000' Changing Orifices 1. After disconnecting move the burner compartment. power and gas supply to the furnace, recompartment door, exposing the burner 2. Disconnect removed. gas line from gas control 3. Disconnect wiring at gas control valve. Be sure to note the proper location of all electrical wiring before being disconnected. 4. Remove the four (4) screws holding the manifold and gas control valve to the manifold supports. Do not discard any screws. See Figure 21. 5. Carefully remove the manifold valve so manifold 8. Reassemble all parts in reverse order as removed. Be sure to engage the main burner orifices in the proper openings in the burners. 9. After reassembling, leaks using a soapy diately. can be assembly. Manifold turn gas on and check all joints for gas solution. All leaks must be repaired imme- LP Conversion the furnace rating plate for the LP conversion accessory kit part An accessory kit shall be used to convert to propane gas use, see number. CARBON Failure death, injury. MONOXIDE to follow property HAZARD. this warning can result damage and/or personal Nox inserts for use with ONLY. If LP Gas is required, removed. O FIRE, EXPLOSION, 25-25-15 Failure death, injury. to follow property in Natural Gas units NOx inserts must be UNIT DAMAGE HAZARD. this warning can result damage and/or personal in An LP conversion accessory kit is required when operating the furnace with LP gas. Remove the orifices from the manifold proper sized orifices. See Figure 22. 6. and replace them with For LP conversion discard 7. Tighten orifices Figure 22. 441 01 231402 so they are seated and gas-tight. remove screws insert. See Reinstall screws. See Figure 23 that secure the NOx insert and NOTE: It is very important to reinstall the NOx insert mounting screws. Air Temperature Rise Check iiiiiiiiiiiiiiiiiiiiiiiiiiiii_i_i!:!!!!i_!ill ¸II ¸II¸I ¸;i;_i!i_i_i_i_ii!i!i!!!!!!i!_;_;_;_;_;_;_;_;_;_i_i!iiiiiiiiiiiiiii_iii!!_iiiiiiiii_i;;i_i_i!i!_!;;!iiiiii!_ Removing NOx inserts REDUCED FURNACE LIFE HAZARD Failure to properly set the air temperature result in reduced furnace life. rise may Use ONLY the blower motor speed taps marked "Y" for YES for setting air temperature rise. Blower Motor Speed Taps for "8DNL ModelSizes LO RED M LO BLUE M HI ORN HI BLK 050B12 N Y Y N 075B12 N Y Y Y 075F16 N N Y Y 100F14 N N Y Y 100J20 N Y Y Y 100L20 Y Y Y Y 125L20 Y Y Y Y ModelSizes Main Burner Flame Check Allow the furnace to run approximately 10 minutes. the main burner and pilot flames. See Figure 24. Check for the following (Figure Then inspect 24): • Stable and blue flames. Dust may cause orange tips or wisps of yellow, but flames MUST NOT have solid, yellow tips. • Flames extending • Flames do NOT touch directly from sides burner To check MUST temperature be set to give the correct air temperature as marked on the rating plate. Temperabetween supply and return air tempera- rise, use the following procedure: 1. Place thermometers in supply and return air registers as close to furnace as possible, avoiding direct radiant heat from heat exchangers. 2. Operate furnace for 10 minutes with all the registers and duct dampers open by using a jumper wire on R to W thermostat connections on the fan board. 3. Take readings plate. 4. If the air temperature rise is not in the correct range, the blower speed must be changed. A higher blower speed will lower the temperature rise. A lower blower speed will increase the are noted, it may be necor check for drafts. Main Burner speed rise through the furnace ture rise is the difference tures. into heat exchanger. of heat exchanger If any problems with main burner flames essary to adjust manifold gas pressure, The blower temperature 5. Remove and compare with range specified on rating rise. the jumper wire after the adjustments are complete. Changing Blower Speed ELECTRICAL Failure NOTE: For Ignitor location see Figure 25. or to disconnect personal Turn OFF SHOCK HAZARD. power could result in death injury. power to furnace before changing speed taps. Ignitor Location NOTE: 21/16 The speed taps that the manufacturer sets at the factory for this furnace are based on a nominal 400 CFM per ton cooling and the basic mid range on the temperature rise for heating. Since the manufacturer cannot predict the static pressure that will be applied to the furnace, it is the responsibility of the installer dealer/contractor to select the proper speed tap leads 25-25-08 NOTE: Flame sensor has a different orientation in all 050 models. for the application If it is necessary 1. to change when the furnace speeds, is installed. refer to steps Refer to Furnace Hhking Diagram for location and cooling speed taps located on the furnace below. of the heating control as well 441 01 2314 02 aslocation of unused blowermotorspeedleads.Usethe the thermostat chart (Table FAN switch is turned from auto to ON the fan will operate continuously at "HEAT" speed. EAC will be energized in this mode. 7) to determine the blower motor speed settin( s. to the G terminal on the furnace control. When the Blower Speed Chart NOTE: Wire Motor Speed Color Black Med- Red 3, speed may not be provided on all models. blower motor speed by removing the the "Heat" or "Cool" terminal and remotor speed lead from the "MI" or the wire previously removed from the to the vacated "M1" or "M2" termi- Note: When using the same speed on motors with (4) speed leads, it will be necessary to tape off the terminal of the motor speed lead removed from the "Heat" or "Cool" terminal with electrical tape since an open terminal will not be available at the "MI" or "M2" location. check the system of the circulating after modification air blower to ensure in all modes the of opera- Continuous-Fan Operation using "G" Energizing the"G" uous fan operation. terminal on the furnace This is done 11. Furnace control by connecting Failure to have the maintained could result and/or property damage. provides contin- the G terminal furnace in death, MONOXIDE inspected personal and injury It is recommended that the furnace be inspected and serviced on an annual basis (before the heating season) by a qualified service agency. and Information Operation of and has a lower contact rating (8 amps) than the heat and cool taps. When the low speed blower lead is connected to this terminal, this will provide low speed blower operation er two speeds (Heat or Cool) are not energized. in this mode. whenever the othEAC not powered Thoroughly check the system after modification to ensure the proper operation of the circulating air blower in all modes of operation. Separate speed selections Continuous-Fan Connect terminal should for Heat, Cool, and low speed lead from circulating air motor at the furnace control. The appropriate already be connected to the "Heat" Heating and Continuous-Fan to the "Cont" motor leads and "Cool" terminals. Speed the Same If it is necessary to operate the heating speed and continuous -fan speed using the same blower speed, connect a jumper between the "Heat" and "Cont" terminals on the furnace control. Note: There should be only ONE motor and "Cont" terminals. Manual". ELECTRICAL HAZARD SHOCK, lead going to the "Heat" FIRE OR EXPLOSION Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous operation, death, personal injury or property damage. • Before servicing, disconnect all electrical power to furnace. • When servicing disconnecting. controls, label all wires prior to Reconnect wires correctly. • Verify proper operation 441 01 2314 02 ignition Maintenance FIRE, EXPLOSION, OR CARBON POISONING HAZARDS See "User's furnace speed. A terminal is provided on the furnace control located in the circulating air blower compartment for operation of the continuous-fan option. This connection is intended for the low speed motor tap, If the same speed must be used for both heating and cooling, remove the undesired motor speed lead from the "Heat" or "Cool" terminal and connect that lead to the open terminal at "M1" or "M2" location or tape off. Attach a jumper between the "Heat" and "Cool" terminals and the remaining motor speed lead. proper operation tion. at heating Low Low Change the heat or cool motor speed lead from place it with the desired "M2" location. Connect "Heat" or "Cool" terminal nal. Thoroughly the fan will turn off during Hard Wired Continuous-Fan Med-High Blue 2, In heating, up then restart High Orange* * Med-High warm after servicing. [_ 12. Sequence The following of Operation is the normal operating & Diagnostics sequence. Cooling (Y) Request: 24VAC • signals applied Cool motor speed Y & G signals removed • speed Cool motor Continuous to Y & G terminals is energized from Circulating is applied • speed Heat motor G signal • removed Heat motor from NOTE 1) Furnace unless a blower NOTE 2) Heating de-energizes • blower requests NOTE 3) time. delay. delay. to the Cont received or Cooling terminal during warm-up a Fan request The fan returns period on a call for Heating on the FCB, in which cause to continuous case during a G request 2). to change to the appropriate the fan speed circulating that occurs see NOTE speed after the selected heat or cool Fan Off Delay time ex pires request. Fan Hard-Wired (Cont) Request: motor is energized demands Fan Off Delay the fan during the heat exchanger or Cooling low speed Low speed Cool after 5 second lead is connected Circulating Field selected time. FCB. loss of the Heating Continuous board) of the FCB. without speed after the Fan on Delay time expires. following control Fan On Delay Fan (G) Request: is de-energized motor Cool after 90 second to G terminal is energized speed FCB (furnace FCB is de-energized 24 VAC signal of after 5 second tap installed when from furnace EAC is NOT active power on "CONT" applied control. Fan demands for hard-wired terminal. to furnace. mode Operates from furnace but IS active at this speed control continuously while there for heat, cool or "G" will override for fan demands from furnace control are no other hard-wired for heat, speed tap. cool and "G". Heating (W) Request: Heating (W) Request: • 24 VAC signal applied • Inducer turns • Following • The gas valve • The igniter • FCB will delay W signal motor to W terminal on and the pressure a 15 second prepurge is energized, is de-energized removed blower from delay The gas valve de-energizes The inducer after the main • The fan stays at Heat speed. • The fan de-energizes burners and the main after the selected FIE R - The 24V HUM is energized the inducer burners postpurge Heat _] 4) If a new Heating Fan Off Delay then closes, the igniter begins a 17 second warm-up. is sensed. ignite. timed from the opening of the gas valve. go out. period. Heat Fan Off Delay when the pressure time expires, switch closes timed from the gas valve on a call for heat. de-energizing. The 115V HUM (called HUM on Control) is energized. ELECTRONIC AIR CLEAN E R - EAC is energized hard-wired continuous fan mode. NOTE switches light and flame for the 30 seconds runs for a 15 second when close(s). FCB. • is energized switch(es) after the pressure the main burners operation • HUMIDI of FCB. request arrives while start a new heating when there the control cycle is a blower is waiting speed call. It is NOT energized when blower operates in the in the Heat Fan Off Delay time, the FCB will wait for the selected as long as the heat call remains. 441 01 2314 02 Heating Request with Gas Shut Off: 24 VAC signal applied to W terminal of FCB. The FCB will attempt 4 cycles for ignition Power reset will clear lockout. • Inducer • Following • The igniter glows red-hot • The igniter stays off for 17 seconds, • The igniter glows red hot for 22 seconds • The igniter stays off for 17 seconds, • The igniter glows red hot for 22 seconds • The igniter stays off for 17 seconds, • The igniter glows red hot for 22 seconds flashing • motor turns then go to soft lockout The inducer again as long as the heat call remains. on a 15 second error for 3 hours then try for ignition prepurge delay, the igniter for 22 seconds, begins then turns then begins begins to warm up again. off. begins flashes error code The FCB continues to warm then turns then up. The FCB then turns then warm off. off. flashing error code 6. flashing error code 6. up again. The FCB continues to warm 6. up again. then turns off. The FCB proceeds to soft lockout and stops flashing error code 6 and begins code 6 + 1. motor de-energizes after a 15 second post purge. Control Board Diagnostic Codes (See Figure 26) OFF = 24VAC Heartbeat ON SOLID = Normal operation or no previous Diagnostic Code = Soft Lockout - Furnace Control Error (1 hr delay) or 115VAC 1 Flash If code repeats = Not used 2 Flashes = Pressure switch(es) 3 Flashes = Pressure switch 4 Flashes = Limit or roll-out 5 Flashes = Flame 6 Flashes 6 + 1 Flashes = Failure to ignite or flame sense lost while running = Soft Lockout - Max trials for ignition reached (3hr delay) 7 Flashes = Soft Lockout sensed (roll-out 8 Flashes 10 Flashes is off, fuse is open immediately closed open when switch open following when power should should reset then replace control be open be closed out of sequence - Limit or roll-out switch requires manual switch open longer than 2 minutes (1 hr delay) reset) = Permanent Lockout - Gas valve relay contact stuck = Line voltage (115VAC) polarity reversed. If twinned, closed or miswired gas valve (power refer to twinning kit instructions reset only) * If status code recall is needed, briefly (2-3 seconds) remove then reconnect one limit switch wire (main or rollout) to display last stored status code. Do not remove power or blower door before initiating status code recall or code will be lost. Code is automatically cleared after 72 hours or upon power reset. * Proper flame sense microamps: Control 441 01 2314 02 0.7 microamps D.C. minimum 2.0 - 4.0 microamps nominal Board [_ _] 441 012314 02 Save This Manual For Future Reference Models +8DNL050B12B1 +8DNL075B12B1 +8DNL075F16B1 +8DNL100F14B1 +8DNL100L20B1 +8DNL125L20B1 + Denotes Brand International Comfort Lewisburg, TN 37097 Fast Parts Division (866) 380-3278 441 01 2314 02 Products, LLC / [_ Model Specifications Manufacturers Number (Mfr No-See RatingPlate) ALL Models Specifications *8DNLO5OB12 *8DNLO75B12 *8DNLO75F16 *8DNLIOOF14 *8DNLIOOL20 *8DNL125L20 General Input(8tuh) Output(Btuh) Temp. Rise (F) 50,000 40,000 35-65 75,000 61,000 35-65 75,000 61,000 35-65 100,000 81,000 35-65 100,000 81,000 30-60 125,000 101,000 35-65 Electrical(Volts/Hz) 115/60 115/60 115/60 115/60 115/60 115/60 Rating PlateAmps 9.2 9.0 12.0 9.2 13.5 13.2 Gas Type NatI,P NatI LP NatI'P Transformer Size (VA) T'stat Heat Anticipator Gas & Ignition Std.Main Orifices(No/Size) NatI'P Nat Nat 40 .50 2I#42 2t#54 3I#42 3/#54 3/#42 3/#54 GasValve Honeywell RegulationType) ManifoldPress.(Inch'sWC) 4/#42 4/#54 4/#42 4/#54 5/#42 5/#54 VR 8205S SNAP 3.5 110.0 3.5 110.0 3.5 110.0 IgnitionTypelSeries Combustion FlueOutlet Size (Inches) Std.OutletTemp (F) Limits & Controls Thermal Sensor (F) LimitControl 3.5 110.0 3.5 110.0 3.5 110.0 Hot Surface 4 <480 4 <480 4 <480 4 <480 4 <480 4 <480 300 See PartsList 300 See PartsList 300 See PartsList 300 See PartsList 300 See PartsList 300 See PartsList 11-10 11.91900 PSC/314 40/370 Washable 16x18xl (2) 3 5 11-10 11.91900 PSC/3/4 40/370 Washable 16x18x1(2) 3 5 Std.PressureSw. (Part No) Press (Close) Press (Open) 1013529 -0.69 -0.59 HighPressureSw. (Part No) 1014051 FurnaceControl(Type) FurnaceControl On (Timed-secs) Off Integrated 30 60,100,140,180 Blower Data Type & Size MotorAmps/Rpm MotorTypelH.p. Cap.Mfd/Volts FilterType(600 FPM) FilterSize (") Min. CoolCap. (Tons) Max. CoolCap. (Tons) 11-8 8/1050 PSC/II2 7.51370 Washable 16x18xl (2) 1.5 3 11-8 811050 PSC/II3 5.01370 Washable 16x18xl (2) 1.5 3 11-10 10/1050 PSC/I/2 10/370 Washable 16x18x1(2) 3 4 11-10 8/900 PSC/II2 7.51370 Washable 16x18xl(2) 2 3.5 Gas Conversion Kits Natto LP NAHA001LP(1172958*) LPtoNat NAHA001NG(1172960*) * Must be ordered from ServiceParts THIS DATA IS SUBJECT TO CHANGE WITHOUT NOTICE 44101231402 Circulation Air Blower Data (CFM #) *8DNLO50B12 *8DNLIOOF14 Air Delivery in Cubic Feet per Minute (C.F.M.) (Furnace Rated @0.5" WC in Cubic Feet per Minute (C.F.M.) (Furnace TAP LOW MED L MED H HIGH _-_5, .10 702 963 1260 1537 ,£ Rated @0.5" WC ESP) TAP LOW MED L MED H HIGH _-_5, .10 756 1012 1372 1881 ,£ ,30 624 845 1183 1416 ,30 585 888 1273 1724 _ .60 510 760 1088 1308 _ .50 491 780 1176 1606 =u ,70 412 617 917 1111 =u ,70 387 697 1035 1481 .90 310 468 664 948 .90 255 561 873 1281 1,00 249 436 529 808 1.0 210 444 767 1132 No •_ uJ *8DNLO75B12 Rated @0.5" WC MED L MED H HIGH •_O' ,10 634 728 975 1353 '£ .30 533 653 936 1307 _ ,50 454 559 861 1225 =u .70 373 473 737 1087 ,90 255 392 605 884 1,00 232 294 529 764 *8DNL075F16 @0.5" WC ESP) LOW MED L MED H HIGH •_ O' ,10 1798 2024 2212 2375 '-£ To .30 1709 1896 2081 2205 _ ,50 1614 1774 1922 2026 =u .70 1470 1614 1752 1860 ,90 1282 1428 1548 1645 1.00 1065 1263 1407 1508 x uJ in Cubic Feet per Minute (C.F.M.) (Furnace Rated @0.5" WC Air Delivery ESP) in Cubic Feet per Minute (C.F.M.) (Furnace TAP LOW MED L MED H HIGH .10 648 900 1285 1789 ,30 628 916 1328 1747 _ .50 611 889 1309 1680 =u ,70 557 843 1240 1588 .90 485 748 1122 1452 1,00 441 680 1041 1374 ,£ Rated TAP *8DNL125L20 Air Delivery 5 in Cubic Feet per Minute (C.F.M,) (Furnace LOW = Air Delivery ESP) TAP "_ ua x uJ in Cubic Feet per Minute (C.F.M,) (Furnace _o No *8DNL100L20 Air Delivery x _J Air Delivery ESP) = @0.5" WC ESP) LOW MED L MED H HIGH .10 1936 2165 2319 --- ,30 1845 2028 2246 2334 _ .50 1728 1902 2061 2172 =u ,70 1536 1695 1856 1952 .90 1331 1490 1800 1687 1.00 1215 1352 1424 1537 5 ,£ x _J Rated TAP • Denotes Brand I #Filter CFMrequired - Cubic for feeteach per minute return-airairflow. inlet. Airflow performance 44101231402 includes 1" washable (600 FPM max) filter media. THIS DATA IS SUBJECT TO CHANGE WITHOUT NOTICE [_ f CONNECTION WARNING: ELECTRICAL DISCONNECT BEFORE DIAGRAM LADDER SHOCK HAZARD SERVICING ROLLOUT SWITCH1TO2 TO LP PRESSURE CAPACITOR 'NSE_hSM_D'NG M_NL'M'T _VSsS E _.,,T&. E --I--(_)--_.R7 _o--_-(_--..(:_-, _ (WHEN USED) (WHEN USED) (SOME COPPER | I TO 21N SERIES DEPENDINGON MODEL MOTOR .OTE._ _:= 100 18( _1_1_- x_'_' _i _ I IND -- I _1__U BK RELAY I Z _ _ _ _ I IGNI,T_ ON I I_ I JUNCTION , _I_-- ,'_"-_ _ _ o_:<" _ /'_ 8 o m_rn © _ _ om o ... z_ C) MHI (O) MLO (BL) _> RELAY _EAC _< _ SEC 9_ IN • COM .q ,o_t, CONT 60 PSC _LOWER O J1 U= _ NL FAN _ _mZ ,oo,_o ___ _ XF "m,',,",,ROLLOUT IN SWITCH _ 100SEC Ill 1 TO3 SE RIES DEPENDING ON MODEL P1 6 FUSE TRANSFOR -- 5A MER - LIMIT NOTE #6 24VAC COM J 1 _O R BL" w 1. If any of the original equipment wire is replaced use wire rated 105° C. 2. Use only copper wire between the disconnect switch and the furnace junction box. 3. This wire must be connected to furnace sheet metal for contlol to prove flame. 4. Symbols are electdcat representation only. 5. Solid lines inside circuit board are printed circuit board tlaces and are not depicted as shown in the legend. 6. Replace only with a 5 amp fuse. 7. Blower motor speed selections are for average conditions, see installation taatrdctions for details on optimum speed selection. 8. Factory connected when LP Pressure Switch and BVSS (Chimney Adapter Accessory Kit) are not installed. 9. Btawer off-delay, gas heating selections are (60, 100,146, and 180) seconds, cooling or heat pump 90 seconds. 10. Ignition lockout will occur after four consecutive unsuccessful tdals for ignition. Control will auto-reset after three hours. 11. Blower motor and inducer motor contain internal auto-reset thermal overload switches. 12. Flame sensor: 0.7 pA D.C. minimum, 2.0 - 4.0 pA nominal. 13. Depending on model, P4 inducer motor leads may be in a single connector o :<>_< m_ _ M1 MAIN 4_ Zr_ B O HEAT _OO: "'--WW ]- .....'-*' I 2 mr_m_mr_ Oo TR_R _ MOTOR _:CO:E P3 1 HEAT ., _ NOTT#13 RELAY -- _--, _ Zmz _ I I._. 2 P4 _ :: " ©+_ (SOME MODELS :ZoJ_ I _ fT_NDU_ER_ I_1 CAPACITOR _(>X)_w_ _7.g GROUND P2 _INDUCER]_.- ° 2 "" wr:-r2 • =11 EQUIPMENT 7 ]- •n I" I ,..-t ×. | ''_l I_;]_P4 I I nN_ JUUL %-_ --W_SENSOR J.NEUTRAL _ #2 =oo moo >00 m > I %" I " IGNITER _ /_ NOTE DIAGRAM DISCONNECT CONDUCTORS H -_'_¢JSTET_'U_E--S;_--.---_NDU(ER % GRN/Y y FIELD O.LY OT HOT NEUTRAL G,D L1_-"V/'sNwT,_T_C'H °oK MODELS) NOTE #g I 115VAC SPEEDTAP CODE BLACK ORANGE BLUE HI MHI MLO RED LO COLOR LOW VOLTAGE i i . CODE BLACK BLUE BROWN GREEN/YELLOW ORANGE RED WHITE YELLOW FIE LD LINE VOLTAGE LINE VOLTAGE FACTORY FIELD ON CONTROL JUNCTION O I I P .... _,4 -4_1/ I P1 8 CPU SS SWITCH ,TO_INSERIE_ _J_l-a (LPMODELS ONLY) NOTE#8 ,_ VALVE RELAY GAS .... ___! BVSS , O _q J1 m_ FACTORY LOW VOLTAGE CONDUCTOR BK BL BR GRN/Y O R W Y UNMARKED TERMINAL CONTROL TERMINAL _C _zO_Z_ --_ i m_m_ [ CONTROL _OARD _--_ NOTE (FIELDINSTALLED #3 I1___1_'-- _)P13 ._=_>_] SENSOR _" _ _ _ 100 180 Parts for *8DNL II 19 6 A \ KK JJ CC BB 18 \ O BB AA DD \ 16 25-25-11-1 441 01 231402 [_ I Replacement Models - *8DNLO50B12B1, Replacement Key No, *SDNLO75B12B1, part supplied will be current Functional Parts Description 3 4 5 6 active part. Part Number - *8DNL *8DNL100F14B1, 050B12B1 075B12B1 Switch, Pressure 1013529 1 1 Wheel, Blower 1013011 1011420 1 1 Motor Motor, BIr Capacitor 1/115 1/115 1/115 1/115 100F14B1 100L20B1 125L20B1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1171728 1171727 1171729 1171982 7.SuF 5uF 10uF 40 uF 075F16B1 1 1172487 1172493 1172488 1172489 1/2 COW 1/3 COW 1/2 COW 3/4 CCW place of purchase. 1 1014824 1014825 1014823 kit* *SDNL125L20B1 *8DNL 1 Mount, I (Natural Gas) *SDNLIOOL2OB1, For parts not listed, consult 1014316 1014317 1014318 1014319 1014320 1014321 Heat Exchanger 2 Parts *SDNLO75F16B1, 1 1 1 1 7 Transformer 1172810 1 1 1 1 1 1 8 Control 1172550 1 1 1 1 1 1 9 Switch, Interlock 1171981 1 1 1 1 1 1 10 Burner Assembly 1172884 1172965 1172966 1179667 1 1 1 1 11 Flame Sensor 1172827 1 1 1 1 1 1 12 Igniter 1172533 1 1 1 1 1 1 14 Orifice, Burner # 42 1011351 2 3 3 4 4 5 15 Valve, Gas 1172821 1 1 1 1 1 1 16 Switch, Limit (Rollout) 1013102 2 2 2 2 2 2 17 Switch, Limit (Main) 34335001 1009169 1008417 1065294 1320362 1 1 1 1 1 1 18 Blower, Combustion 1014433 1013517 1 1 1 1 1 19 Filter, Air 1009750 2 2 2 2 2 *See Table below for bell, band location 1 2 on motor Bellyband Location on Motor Model *8DNL A(in.) O50B12B1 1.38" 075B12B1 1.65" 075F16B1 1.81" 100F14B1 1.38" 100L20B1 1.65" 125L20B1 1.65" 441 01 231402 I Replacement Models - "8DNL050B12B1, Replacement *8DNL075B12B1, part supplied Key No, *8DNL075F16B1, will be current active part. Non-Functional Description Panel, Parts Top Part Number - *8DNL "8DNL100F14B1, I (Natural Gas) *8DNL100L20B1, For parts not listed, consult *8DNL125J20B1 place of purchase. *8DNL 050B12B1 1013593 1013594 1014410 1 078B12B1 078F16B1 100F14B1 100L20B1 125L20B1 1 1 1 1 1 B Box, Junction 1172860 1 1 1 1 1 1 C Cover, Junction box 1012350 1 1 1 1 1 1 D Partition, Blower 1013571 1013572 1014416 1 1 1 1 1 1 Housing, Blower 1172885 1172969 1 1 Hanger, Blower 1012328 2 2 721020013 721020008 1 1 E F 1 1 1 1 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 G Panel, Blower Cutoff 1 1 H Clamp, Capacitor 1170643 1014315 1 1 1 1 J Bracket, Control Mounting 1172846 1 1 1 1 Door, Blower 1173028 1173029 1173030 1173025 1173026 1173027 1173031 1173032 1173033 1 1 1 1 1 1 1 1 1 1 1 1 L (Hell Only) (Hell Only) (Hell Only) (Comfortmaker Only) (Comfortmaker Only) (Comfortmaker Only) (Tempstar Only) (Tempstar Only) (Tempstar Only) 1172267 1172268 1172269 Bracket, Door Door, Louver Manifold, (Hell Only) (Hell Only) (Hell Only) (Comfortmaker Only) (Comfortmaker Only) (Comfortmaker Only) (Tempstar Only) (Tempstar Only) (Tempstar Only) Gas 1173020 1173021 1173022 1173017 1173018 1173019 1173023 1173024 1014435 1 1013478 1013479 1013480 1013481 1 1 1 1 1 1 1 1 1012377 2 2 2 T Top, Burner Box 1013705 1013015 1013016 1 1 1 Bracket, Burner Box Sides 1012532 2 2 2 V Baffle, Burner Box 1012338 1012339 1012340 1 1 1 Z 1172847 1172848 1172849 1172850 Box Gasket, Combustion 441 01 231402 Blower 2 2 1 1 2 2 2 1 1 2 1 1 1014033 1013483 1013484 1013485 1013540 1 1 U Collector 1 1 Bracket, Manifold Support Bottom, Burner Box 1 1 S W 1 1 1 1 1 1 1 1 1 1 1 1 I Replacement Models - "8DNLO50B12B1, Replacement part Key No, AA I Partition, Front Heat Exchanger Gaskets, CC Tubing, Silicone Heat Exchanger be current Parts 'SDNLO75F16B1, active Part Number 1013543 1013521 1013545 1013548 1013547 1013548 )art. - "8DNL For parts not I (Natural Gas) "8DNL100F14B1, '8DNLIOOL2OB1, listed, consult 'SDNL125J20B1 place of purchase. "SDNL 080B12B1 075B12B1 075F16B1 100F14B1 100L20B1 125L20B1 1 1 1 1 1 1 1013991 1013992 1013993 1013994 1172190 1172191 Baffle, Nox 1014019 2 3 3 4 4 5 JJ Shield, Flue Pipe 1013975 1 1 1 1 1 1 KK Pipe, Flue 1014031 1 1 1 1 1 1 LL Rack, Filter (Version A) 1014020 1 1 1 1 1 1 Rack, Filter (Version B) 1173903 1 1 1 1 1 1 Sightglass 1172768 1 1 1 1 1 1 Fuse, 5 Amp 1083348 1 1 1 Harness, Wire 1172819 1172820 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 L2 MM )( )( )( )( _] will Non-Functional Description BB DD supplied 'SDNLO75B12B1, PART NOT ILLUSTRATED Manual, Installation 441 01 2314 02 Manual, Users 441 02 2011 01 441 01 231402
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 38 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 13:49:05 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools