ICP Furnace/Heater, Gas Manual L0502491

User Manual: ICP ICP Furnace/Heater, Gas Manual ICP Furnace/Heater, Gas Owner's Manual, ICP Furnace/Heater, Gas installation guides

Open the PDF directly: View PDF PDF.
Page Count: 42

DownloadICP  Furnace/Heater, Gas Manual L0502491
Open PDF In BrowserView PDF
NTV6NNE

80+ 2-Stage &

NTP6/TNE

VariableSpeedNDP6/TDE
SAFETY
Recognize

safety information.

be alert to the potential
Understand

the signal

lies the most serious
personal

injury

This is the safety-

for personal

alert symbolZ_.

When

you see this symbol

on the furnace

and in instructions

manuals

injury.

words

DANGER,

hazards,

those

or death.

REQUIREMENTS

WARNING,

that will

or CA UTION.

result

in severe

These

personal

words

injury

are used with the safety-alert

or death.

symbol.

DANGERidenti-

WARNINGsignifiesahazardthatcouldresu]tin

CAUT__Nisusedt_identifyunsafe_racticesthatc_u_dresu_tinmin_r_ers_na_injury_r_r_ductand_r__erty

damage.
Installing

and servicing

should

install,

Untrained

repair,

service

be performed

heating

equipment

or service

heating

personnel

by trained

can perform

service

labels

attached

to or shipped

Follow

all safety

codes.

No. 541ANSIZ223.1.
Gasand

When

In the United

States,

instructions

instructions
practices.

exceed

procedures
cover
certain

We require

follow

all safety
edition

Only trained

and qualified

personnel

codes

air filters.

precautions

All other

operations

in the literature,

must

on tags, and on

that may apply.

including

of the National
glasses

and replacing

observe

the current
Standard

edition

Canada

and work gloves.

National

Fuel Gas Code

CANICGA-B149.1

(NFGC)

NFPA

- and .2-M91

Natural

Havefireextinguisheravailableduringstart-

calls.

requirements

instructions

equipment,

precautions

Wear safety

and service

and conform

local codes and ordinances,

these

components.

such as cleaning

on heating

safety

refer to the current

minimum

functions

working

with the unit and other

In Canada,

due to gas and electrical

basic maintenance

personnel.

PropanelnstallationCodes(NSCNGPIC).

up and adjustment
These

can be hazardous
equipment.

as a minimum

to existing

especially

those

national

standards

and safety

codes.

that may not have kept up with changing

In some

instances,

residential

these

construction

for a safe installation.

f

Manufactured

by:

International
Lewisburg,

Comfort
TN USA

Products

Corporation

(USA)

37097

Table of Contents
I. SafeInstallation Requirements................
2. Installation ...............................
3. Combustion & VentilationAir .................

2
4
7

4.Vent and Combustion Air Piping ..............
5. Horizontal Venting .........................

9
10

6. Gas Supply and Piping ......................

10

Printed in U.S.A.

7. Electrical Wiring ..........................
8. Ductworkand Filter(Upflow) ................
9. Ductworkand Filter(Downflow) ..............
10. Checksand Adjustments ..................
11.FurnaceMaintenance......................
12.Sequence of Operation& Diagnostic .........
13.TenchSupport and Parts ...................

LP1

10/1/2002

14
16
17
19
21
21
26

441 01 2016 02

1. Safe Installation

Requirements
There

B,

can be numerous

ing or dwelling.
Installation

or repairs

made

by

unqualified

ry, death,

persons

alert

can result
in hazards
to you and others.
Installation
MUST conform
with local codes or, in the absence
of
local codes, with codes
having jurisdiction.
The information
for use by
experienced
precautions
work, and is
instruments.

of all governmental
in this

manual

authorities

a qualified
service
technician
in such work,
who is familiar
and safety procedures
required
equipped
with the proper
tools

injury

who
is
with
all
in such
and test

Note:

property

or dwelling

brand

damage.

1.

the United States and Canada.
Refer to the appropriate
along with this manual, for proper installation.

•

Do NOT use this furnace
a building

•

that is under

for installation
vehicles.

as a construction

codes,

safe

Thoroughly

Do not

2,

and

read

this

heater

or to heat

Never
vide

for this furnace

(see Rat-

ing Plate on unit). Overfiring
will result in failure of heat exchanger and cause dangerous
operation.
(Furnace can be
converted
to L.E gas with approved
kit.)
Do NOT use open

•

Ensure adequate
to the furnace.

•

Seal supply

•

The vent system MUST be checked
the correct type and size.

•

Install

correct

flame

and ventilation

air is provided

to determine

the
unit.

and ventilation

Carbon

monoxide

Freeze

labels

on the unit.
and

part has been
service

under

technician

any part of the control
has been under

vent

grilles,

water.

to inspect
system

and

water.

or any ducts

Air must be provided

that

pro-

for proper

com-

of flue gases.

or "CO" is a colorless
fuel is not burned

does not receive

sufficient

and odorless

completely

or when

gas
the

oxygen.

bon monoxide
in a building or dwelling. The sources could
be gas-fired
clothes
dryers,
gas cooking
stoves,
water
heaters,
furnaces,
gas-fired
fireplaces,
wood fireplaces,
and several other items. Carbon monoxide
can cause serious bodily injury and/or death.
people of potentially
dangerous

(see Note below).

system.

If your unit remains
shut off during
cold weather
the
water pipes could freeze and burst, resulting
in serious
water damage.

Your unit is equipped
erating if sensors
haust flues.

If the structure
take these

1.

2,

with safety

detect abnormal

will be unattended

devices

that may keep it from op-

conditions

during

such as clogged

cold weather

ex-

you should

precautions.

Turn off main supply
water

Therefore,
to help alert
carbon monoxide
levels,

you should have carbon monoxide
detectors listed by a nationally recognized
agency (e.g. Underwriters
Laboratories
or International
Approval
Services)
installed
and mainor dwelling

warning.

off water

are pro-

for you, the owner.

in the building

when

and

how your unit operates

Freezing Temperatures and Your Structure

filter type and size.

The U.S. Consumer
Product Safety Commission
recommends that users of gas-burning
appliances
install carbon
monoxide
detectors.
There can be various sources of car-

tained

unit, you

that it is

Your unit is built to provide many years of safe and dependable
service providing it is properly installed and maintained.
However,
abuse and/or improper
use can shorten the life of the unit and

A.

of your

air ducts.

Unit MUST be installed so electrical
components
tected from direct contact with water.

hazards

if any

which

obstruct

produced

Safety Rules

create

unit

bustion

Turn
•

any

to test for gas leak.

combustion

and return

operation

manual

call a qualified

air to the

flame
•

use this

any gas control
3.

regarding

with gas and electricity.

the unit and to replace

in mobile

does not test any

no representations

efficient

involved

Immediately

construction.

Use only the Type of gas approved

to
you

do the the following:

the hazards

NOTE: This furnace
is design certified
by the American
Gas
Association
and the Canadian
Gas Association
for installation
in

This furnace
is NOT approved
homes,
trailers
or recreation

in order

fire or smoke,

or type of detector.

To ensure
should

of your furnace

and makes

This will help you understand

•

Therefore,

dangerous

(see Note below).

The manufacturer
detectors

C.

and/or

damage.

of potentially

in a buildbodily inju-

is intended

Failure to carefully
read and follow all instructions
in
this manual
can result in furnace
malfunction,
death,
personal

property

of fire or smoke

can ca use serious

should have fire extinguisher
and smoke detectors listed by
Underwriters
Laboratories
installed and maintained
in the
building

contained

and/or

people

sources

Fire or smoke

lines if possible.

water

into the structure

Open faucets

and drain the

in appropriate

areas.

Have someone
check the structure frequently
during cold
weather to make sure it is warm enough to prevent pipes
from freezing.

Suggest

they call a qualified

service

agency,

if required.

441 01 2016 02

START-UP
(Keep
Dealer

this

page

CHECK
for future

SHEET
reference)

Name:

Address:

Business Card Here

City, State(Province),

Zip or Postal Code:

Phone:
Owner

Name:

Manual Gas Shut-Off Upstream

Address:
City,

State(Province),

Zip or Postal

Code:

of Furnace/Drip-Leg?

YES

NOE_

Drip-Leg Upstream of Gas Valve?

YES

NoE I

Blower Speed Checked?

YES _

Model Number:

All Electrical Connections Tight?

Serial Number:

Electrical Polarity Checked?

Type of Gas:

Natural: _

Gas Valve Status Light OK?

Blower Motor H.P.:

Gas Valve Turned ON?

YES _I

YES _I

NO _I

YES _I

YES _

NO _I
NO _I

YES _I

Furnace Properly Grounded?

LP:

NO

NO _I
NO

Supply Voltage:
Measured Line Pressure When Firing Unit:
Which blower (DIP switch) setting is used?
Heating

Cooling

Temperature of Supply Air: High Fire (°F)__
Low Fire
Temperature of Return Air:

(°F)__or

(°F)__

Lo Fire (Supply - Return ): (°F)

Adjustments Section).
or (°C).__

Measured Manifold Pressure: Hi Fire

(°C)__

Thermostat OK?

or (°C)__

Temp. Rise Hi Fire (Supply - Return ): (°F)or

Filter Type and Size:

Calculated Firing Rate: (High & Low Fire) (See Checks and

Continuous

(°C',__
or (°C)__

YES _

NO

Thermostat: Single Stage

Two Stage

Subbase Level?

YES _

NO

Anticipator Set?

YES _

NO _

Breaker On?

YES _

Fan "Time ON" Setting:

Date of Installation:

Fan "Time OFF" Setting:

Date of Start-Up:

Lo Fire

Set At?:

NO

Dealer Comments:

441 01 2016 02

[_

2. Installation
Location and Clearances
Poison

carbon

monoxide

gas hazard.

If this furnace
is replacing
a previously
common-vented
furnace,
it may be necessary
to resize the existing
vent
line and chimney
to prevent
oversizing
problems
for the
other remaining
appliances(s).
See applicable
codes
and Venting
and Combustion
Air Check in Gas Vent
Installation
section.

and Clearances

ing location
mensions

based

upon the minimum

(Figure

1, Figure

clearance

2 or Figure

and furnace

di-

3).

CAUTION
Do NOT operate furnace
in a corrosive
atmosphere
containing chlorine,
fluorine
or any other damaging
chemicals.
Refer
to Combustion
& Ventilation
Air section,
Contaminated
Combustion
Air.

Failure to properly
vent this furnace
or other appliances
can result
in death,
personal
injury
and/or
property
damage.

Dimensions

If furnace is a replacement,
it is usually best to install the furnace
where the old one was. Choose the location or evaluate the exist-

(NTV6NNE)

MINIMUM CLEARANCES TO
COMBUSTIBLE
MATERIALS FOR ALL UNITS
REAR

0

FRONT

3"

Recommended

For Service

30"

ALL SIDES Of SUPPLY PLENUM

1"

SIDES

0

VENT
Single Wall Vent

6"

Type B-1 Double Wall Vent
TOP OF FURNACE

1"
1"

NOTE: Evaporator
"A" coil drain pan dimensions
ma
vary from furnace duct opening
size. Always consul
evaporator
specifications
for duct size requirements
Unit

@

is designed

Return

for bottom

air through

back

return

of unit

or side return.

is NOT

allowed.

30" rain.
25-22-28

DIMENSIONAL

INFORMATION
Electrical

ReturnAir

Connections

Cabinet

Supply Air
Top

Unit Capacity

A

B

C

D

E

Left/Right Side
D
E

Low Volt
R
P

O

N

F

G

Gas Connections
Side

J

H

Right Side
M
K

LeftSide
L
K

050FBI050BI2

40

15112

28112

1112 11/2

11/2

1112

41/2

175116 18112

23118 12518 22112 12114 237/8 28114 26

281I

075GF/075F14

40

19118

28112

11/2

11/2

11/2

11/2

41/2

175116 181/2 175/8 231/8 143/4 22112 14112 23718 28114 26

281/

100KJ & 125KJ
100J20 & 125J20

40

223/4

28112

1112 11/2

11/2

1112

41/2

175116 18112 21114 23118 18314 22112 14112 23718 281/4

281I

14

ALL DIMENSIONS

_]

Bottom

26

IN INCHES

441 O1 201602

Dimensions

and Clearances

(NTP6/TNE)

MINIMUM CLEARANCES TO
COMBUSTIBLE
MATERIALS FOR ALL UNITS
REAR

0

FRONT

3"

Recommended

for Service

30"

ALL SIDES Of SUPPLY PLENUM

1"

SIDES

0

VENT
Single Wall Vent

6"

Type B-1 Double Wall Vent
TOP OF FURNACE

1"
1"

NOTE:
Evaporator
"A" coil drain pan dimensions
may vary from furnace duct opening size, Always
consult evaporator
specifications
for duct size requirements.

@

Unit

is designed

Return

for bottom

air through

back

return

of unit

or side return.

is NOT

allowed.

Illllllll
0

30" rain.
25-22-28

DIMENSIONAL

INFORMATION
ElectricalConnections

ReturnAir

Cabinet

Top

Unit Capacity

Left/Right Side

Low Volt
P

Supply Air
O

Bottom

C

D

E

D

E

R

NTP6050FB
TNE050BI2

40

15112

28112

11/2

11/2

11/2

11/2

41/2

178116 18112

23118 12818 22112 12114 23718 28114 26

281/

NTP6075GF
TNEO75FI4
NTP6100GF
TNE100F14

40

19118 28112 11/2

11/2

11/2

11/2

41/2

178116 18112 17518 23118 14314 22112 14112 23718 28114 26

281/

NTP6100HKJ
TNE100J20
NTP6125KJ
TNE125J20

40

223/4 28112 11/2

11/2

11/2

11/2

41/2

178116 181/2 211/4 231/8 183/4 22112 14112 237/8 281/4

281/

ALL DIMENSIONS

441 O1 2016 02

J

H

Left Side
L
K

B

14

G

Right Side
M
K

A

N

F

Gas Connections
Side

26

IN INCHES

[_

Dimensions

and Clearances

(NDP6/TDE)

MINIMUM CLEARANCES TO
COMBUSTIBLE
MATERIALS FOR ALL UNITS
REAR

0

FRONT

3"

Recommended

For Service

30"

ALL SIDES Of SUPPLY PLENUM

1"

SIDES

0

VENT

....
c_

Single Wall Vent

6"

Type B-1 Double Wall Vent

1"

TOP OF FURNACE

B_"

1"

37/8

30" rain.
25-21-47b

DIMENSIONAL

INFORMATION
Electrical
Cabinet

A

B

C

D

E

D

E

NDP6050/O75FB
TDEOSO/O75B12

40

151/2

28112

11/2

11/2

15/8

NDP61OOHF
TDE1OOF16

40

19116

281/2

11/2

1112

NDP6125KJ
TDE125J20

40

22314

28112

1112

11/2

Gas Connections

Unit Dimensions

J

K

M

14

165/6

313116

25314

17518

165/6

313/16

25314

211i4

16516

board

or sheet

315116

253/4

313116

1518

11/2

315/16

175/6

15/8

1112

315116

211/4

Flue

N

P

R

18112

37/8

51/4

14

NDP610OHF
TDE1OOF16

9112

261116

237/8

175i6

181i2

55116

51/4

NDP6125KJ
TDE125J20

91/2

261116

237/8

211i4

181/2

71/2

5114

3.

24314

11/2

23718

2.

I

(G)

261116

Install

H

(F)

91/2

1.

Left

Right
(G)

NDP6050/O75FB
TDEO5O/O75B12

Installation

Supply

Low Voltage

(F)

Return
L

Connections

Left Side

Top

Unit
Dimensions

ALL DIMENSIONS

IN INCHES

Requirements

furnace

level.

Install furnace as centralized
heat distribution
system.

Fire Hazard.
as practical

with respect

Install the vent pipes as short as practical.
Installation
section).

(See

Gas

to the

Vent

4.

Do NOT install furnace directly on carpeting,
tile or other
combustible
material other than wood flooring.

5.

Maintain
clearance
for fire
clearance
of 30" is minimum
trols and filter.

safety and servicing.
A front
for access to the burner, con-

Place

furnace

metal

on downflow

Failure
sheet
and/or

6.

on noncombustible

to install

unit on noncombustible

metal can result
in death
property
damage.

Use a raised

cement

applications.

base if the floor

and/or

is damp

cement
personal

board

or

injury

or wet at times.
441 O1 201602

7. Residential
garage
installations
require:
•

Burners and ignition
above the floor.

sources

installed

•

Furnace must be located or physically
sible damage by a vehicle.

at least 18" (457mm)

protected

If you purchased
a horizontally
mountable
furnace,
installed horizontally
in an attic, basement, crawl space,

it can be
alcove, or

suspended
from a ceiling in a basement
right or left airflow position. See Figure

in either

The following
minimum
clearances
to combustibles
MUST
maintained
between
the furnace and adjacent
construction,

be
as

shown in Figure 4. ONLY the corner of the cabinet is allowed to
contact the rafters. All other clearances
should be observed
as
shown

Horizontal

a

from pos-

Horizontal Furnace Installation
Typical

or utility room
4.

in Figure

1, Figure

2, or Figure

3.

Installation
If the furnace

is to be suspended

from the floor joists

in a crawl

space or the rafters in an attic, it is necessary
to use steel pipe
straps or an angle iron frame to attach the furnace. These straps
should be attached to the furnace with sheet metal screws and to
the rafters or joists with bolts. The preferred
method
angle iron frame bolted to the rafters or joists.

is to use an

Thirty inches (30") is recommended
between the front of the furnace and adjacent
construction
or other appliances.
This should
be maintained
for service clearance.
Keep all insulating materials
clear from Iouvered
materials
may be combustible.
It is recommended
for further fire protection
sheet metal is placed between
the furnace

IMPORTANT
NOTE: Inspect unit rating plate to be certain model number
with "NTV6",
"NTP6",
"VNE"
or "TNE".
This identifies
horizontally

mountable.

you may NOT mount
may not be mounted

If unit does

Poison

carbon

NOT bear this designation,

this unit horizontally.
on its back.

3. Combustion

Horizontal

& Ventilation

furnace

•

Chlorinated

here to provide

•

Chlorine

•

Water

•
•

De-icing
salts or chemicals.
Carbon tetrachloride.

•

Halogen

•

Cleaning

•

Printing

•
•

Hydrochloric
acid.
Sulfuric Acid.

•

Solvent

•

Antistatic

fabric

•

Masonry

acid washing

combustion

and

and ventilation
injury.

of local codes,

the applicable

na-

When the installation
is complete,
check that all appliances
have
adequate
combustion
air and are venting properly. See Venting
And Combustion
Air Check in Section 4 of this manual.

Combustion

Air

Installations
in certain areas or types of structures will increase the
exposure
to chemicals
or halogens
that may harm the furnace.
These

instances

This furnace MUST NOT be installed directly on carpeting or tile
or other combustible material other than wood flooring or supports.

gas hazard.

or in the absence

Contaminated

the front of the furonly, not a require-

Air

Furnaces
require ventilation
openings to provide sufficient air for
proper combustion
and ventilation of flue gases. All duct or openings for su pplying combustion
and ventilation air must comply with
the gas codes,
tional codes.

wood floor and extend 12" (300mm) beyond
nace louver door. (This is a recommendation
ment).

Furnaces installed near chemical storage
Permanent
wave solutions
for hair.

Failure to provide
adequate
combustion
air can result
in death and/or
personal

must use only outside

Insulating

that cement board or
and the combustible

•
•
monoxide

Use methods
described
ventilation
air.

begins
unit as

door.

waxes

and cleaners.

based swimming

softening

areas.

pool chemicals.

chemicals.

type refrigerants.
solvents
inks,

(such

as perchloroethylene).

paint removers,

cements

varnishes,

etc..

and glues.
softeners

for clothes

dryers.

materials.

Confined Space Installation
NOTE: A confined
space is defined as an area with less than 50
cubic feet(1.4m 3) per 1,000 BTUH input rating for all gas appliances installed in the area.

air for combustion.

The following areas or types of structures may contain or have exposure to the substances
listed below. The installation
must be
evaluated
carefully as it may be necessary
to provide outside air
for combustion.

•
Commercial buildings.
•
Buildings with indoor pools.
•
Furnaces installed in laundry rooms.
•
Furnaces installed in hobby or craft rooms.
441 01 2016 02

Air Openings and Connecting
1.

Ducts

Total input rating for all gas appliances
MUST
ered when determining
free area of openings.
ducts

or openings

directly

be consid-

2.

Connect

3.

When screens are used to cover openings,
the openings
MUST be no smaller than 1/4" (6ram) mesh.

to outside.

4.

The minimum
dimension
of rectangular
NOT be less than 3" (75ram).

air ducts

MUST

5. When
sizinggrilleorlouver,
usethefreeareaofopening.
If
freeareaisNOTstamped
ormarked
ongrillorlouver,
assumea20%freeareaforwoodand60%formetal.
Requirements
1.

Figure

2.

and one outlet,

3.

Provide confined
space with sufficient air for proper combustion and ventilation of flue gases using horizontal or vertical ducts or openings.
Outside

Air

(This

is ONLY

a guide.

Subject

5 illustrates

how to provide

tion air. A minimum

4.

combustion

of two permanent

and ventila-

openings,

one inlet

are required.

One opening MUST be within 12" of the floor and the second opening within 12" of the ceiling.
Size openings

to codes

and ducts

of country

per Table

having

1.

jurisdiction.)

ThisinstallationNOTapprovedin Canada
, GableVent

GasVent

(1)

/

.d

SoffitVent

Soffit Vent

letAir (1) HI
Inlet
Air (1

Outlet
Air (1)

[[_J

Outlet
Air (2)

Inlet
Air (2)

Furnace

Inlet
Air (1)

MinimumOne Inlet and One Outlet Air Supplyis Required
May be in andCombination Shown

G_

E_:_,_r._

T

Inlet
Air (2)

Inlet Air OpeningMust be Within12"(300ram)of floor
Outlet Air OpeningMust be Within12"(300mm)of ceiling
(1) 1 Square Inch (6cmz) per 4000 BTUH
(2) 1 Square Inch (6cmz) per 2000 BTUH

5.

Horizontal duct openings require I square inch of free area
per 2,000 BTU H of combined input for all gas appliances in
area (see Table 1).

6.

Vertical

duct openings

or openings

directly

to outside

re-

quire 1 square inch of free area per 4,000 BTUH for combined input of all gas appliances
in area (see Table 1).
One permanent

opening,

enclosure,
shall
ances of at least

commencing

within

shall directly communicate
through a vertical or hori-

zontal duct to the outdoors
or spaces (crawl or attic) that freely
communicate
with the outdoors,
and shall have a minimum
free
area of:
•

1 sq. in per 3000
equipment

•

Btu per hr of the total

located

in the enclosure,

Not less than the sum of the areas
the confined

MinimumFree Area Requiredfor EachOpening
BTUH
Input

HorizontalDuct

Rating

(sq.in,i2,000BTUH)

input rating

of all

of all vent connectors

space.

50,000

25 sq. in,

12.5sq, in.

4"

75,000

37.5 sq, in,

18.75sq. in,

5"

100,000

50 sq, in.

25 sq. in.

6"

125,000

62,5 sq. in.

31.25 sq. in,

7"

EXAMPLE:
Furnace

Determining

Water Heater

carbon
homes

monoxide
will

require

gas hazard.
additional

air.

An unconfined
space or homes with tight construction
may
not have
adequate
air infiltration
for proper
combustion
and ventilation
of flue gases.
Failure
grilles
injury.

to supply
additional
air by means of ventilation
or ducts could
result in death and/or personal

Free Area

Total Input

100,000 + 30,000 = (130,000 + 4,000) = 32.5 Sq. In. Vertical

in

An unconfined

space

is defined

ume of 50 cubic feet per 1,000
appliances
in area.

as an area having

a minimum

BTUH total input rating

Adjoining
rooms can be considered
there are no doors between
rooms.
An attic or crawl space

Poison

Rd
Duct
(sq,in.
/4,000
BTUH)

Furnace Water Heater Total Input
100,000 + 30,000 = (130,000 + 2,000) = 65 Sq. In. Horizontal

and

Unconfined Space Installation

Most

VerticalDuct or openings
to outside
(sq.in./4,000BTUH)

12" of the top of the

be permitted
where the equipment
has clear1" from the sides and back and 6" (16 cm.) from

the front of the appliance.
The opening
with the outdoors or shall communicate

Free
Area

part of an unconfined

may be considered

vol-

for all gas

an unconfined

area if

space

provided there are adequate ventilation
openings directly to outdoors. Openings MUST remain open and NOT have any means of
being closed off. Ventilation
openings
to outdoors
MUST be at
least I square inch of free area per 4,000 BTU H oftotal
for all gas appliances
in area.

input rating

In unconfined
spaces, infiltration
should be adequate
to provide
air for combustion,
ventilation and dilution of flue gases. However,
in buildings with unusually tight construction,
be provided using the methods
described
fined Space Installation:

additional
air MUST
in section titled Con441 01 201602

Unusually
tightconstruction
isdefined
as:Construction
with
Ventilation Air
1 Wallsandceilings
exposed
totheoutside
haveacontinuous,sealed
vaporbarrier.
Openings
aregasketed
orsealed Some provincial codes and local municipalities require ventilation
or make-up
air be brought into the conditioned
space as replaceand
ment air. Whichever
method is used, the mixed return air tempera2 Doorsandopenable
windows
areweather
stripped
and
across the heat exchanger
MUST not fall below 60°F or flue
3. Other
openings
arecaulked
orsealed.
These
include
joints ture
gases will condense
in the heat exchanger.
This will shorten the
around
window
anddoorframes,
between
soleplates
and life of the heat exchanger and possibly void your warranty.
floors,between
wall-ceiling
joints,between
wallpanels,
at
penetrations
forplumbing,
electrical
andgaslines,etc.

4. Gas Vent Installation

Poison
hazard.
Read

carbon

monoxide

and follow

gas,

all instructions

fire

and

explosion

Poison

in death,

Install the vent in compliance
with codes of the country having jurisdiction,
local codes or ordinances
and these instructions.
These fan assisted

combustion

Category [ appliances
which
a negative
vent pressure.

furnaces
means

have been classified

that they MUST

operate

as
with

The following

National
furnace

instructions

Fuel Gas Code.
rating plate.

comply

Based

with the United

on the highest

States

input rate on the

If a Category [ vent passes through an attic, any concealed
space or floor, use ONLY Type B or Type L double wall vent
pipe. If vent pipe passes through interior wall, use type B
vent pipe with ventilated thimble ONLY.
2.

Do NOT vent furnace into any chimney serving an open
fireplace or solid fuel burning appliance.

3.

Use the same diameter
permitted
by the United
venting tables.

4.

Keep vertical Category [vent pipe or vent connector runs as
short and direct as possible.

5.

Vertical outdoor runs of type B or ANY single wall vent pipe
below the roof line are NOT permitted.

6.

Slope all horizontal
of 1/4" per foot.

Category
[ connector
States National
Fuel

Failure to properly
vent this furnace
or other appliances
can result
in death,
personal
injury
and/or
property
damage.

Venting and Combustion
NOTE:

If this installation

from a vent-

openings

in the venting

Visuallyinspect
the venting system for proper size and horizontal pitch to ensure there is no blockage
or restriction,
leakage, corrosion
or other
an unsafe condition.

3.

deficiencies

which

could

Insofar as is practical, close all doors and windows
doors between the space in which the appliance(s)
ing connected
to the venting
spaces of the building.

4.

system.

system

are located

cause

and all
remain-

and other

Turn on clothes dryers and any appliance not connected
the venting system. Turn on any exhaust
fans, such

to
as

range hoods and bathroom exhausts, so they will operate at
maximum
speed. Do not operate a summer exhaust fan.
Close fireplace
dampers.
Follow the lighting
spected.
Adjust
continuously.
6.

instructions
thermostat

for each appliance
so appliance(s)

will

being inoperate

Allow 5 minutes of main burner operation,
then check for
spillage at the draft hood relief opening of each appliance.
of a match

or candle

(Figure

6).

Vent Check

8.

Check existing gas vent or chimney
clearances
and local codes.

to ensure

they

Chimney

Vent Pipe

meet

Draft Hood

Typical Gas
Match

The furnace MUST be connected
to a factory built chimney
or vent complying with a recognized
standard. Venting into
a masonry
or concrete
chimney
is only permitted
as
outlined
in the United States National
Fuel Gas Code

441 01 2016 02

furnace

a minimum

Support all horizontal vent pipe every 6' using proper
clamps and metal straps.

or Masonry

an existing

Seal any unused

or pipe as
Gas Code

7.

venting
tables
instructions.

removes

2.

Use the flame
from furnace

Air Check

1,

5.

runs up away

gas hazard.

ing system serving one or more other appliances,
and to make
sure there is adequate
combustion
air for all appliances,
MAKE
THE FOLLOWING
CHECK.

Category I Safe Venting Requirements
NOTE:

monoxide

If this furnace
is replacing
a previously
common-vented
furnace,
it may be necessary
to resize
the existing
chimney
liner or vent to prevent
over sizing problems
for
the other remaining
appliances(s).
See codes of country
having jurisdiction.

in this section.

Failure to properly
vent this furnace
can result
personal
injury and/or property
damage.

carbon

section

in these

Water Heater

7.

[

1

I

_--

After it has been determined
that each appliance
vents
properly,
return doors, windows,
appliances
etc. to their
normal condition.

8.

If improper venting is observed, the cause MUST be corrected.

NOTE: If flame
infiltration
air.

pulls towards

draft hood,

this indicates

sufficient

Venting to Existing Masonry Chimney
NOTE:

The tables and notes

most

recent

printing

Code

venting

of the

referred
United

to below
States

are found

National

in the

Fuel

Gas Code tables for dedicated
venting and United
States National Fuel Gas Code tables for common venting with the maximum capacity reduced by 20% (0.80 X maximum
capacity)
and
the minimum
capacity
as shown in the applicable
table. Corrugated metal vent systems installed with bends or offsets require
additional
reduction
of 10% of the vent capacity for each 90 ° elbow.

Gas

NOTE: Two(2) 45 ° elbows are equivalent to one (1) 90 ° elbow.

tables.

Use the United States
size the chimney

Listed, corrugated
metallic
chimney
liner systems
in masonry
chimneys
shall be sized by using United States National
Fuel

National

Fuel Gas Code or N FGC Tables to

or vent. Dedicated

venting

of one fan assisted

furnace
into any masonry
chimney
is restricted.
The chimney
must first be lined with either type B vent sized in accordance
with
tables 1 or 2 or a listed single wall, metal lining system, sized in
accordance
with the vent tables.

5. Horizontal

Combined Venting into a Masonry Chimney
Venting
into a masonry
or concrete
chimney
is only
mitted as outlined
in the United States
National
Fuel
Code

venting

tables.

Follow

all safe venting

perGas

requirements.

Venting
CAUTION

Category ] Furnaces With External Power
Venters
In order to maintain a Category
] classification
of fan assisted furnaces when vented horizontally
with sidewall termination,
a power
venter is REQUIRED
to maintain a negative pressure in the vent-

It is the responsibility
of the installer
nate the vent and provide
adequate
essential
in order to avoid water/ice
ing, shrubs and walk-ways.

to properly
termishielding.
This is
damage to build-

ing system.
Please consult the Fields Controls Co. or Tjernlund
Products,
Inc. for power Venters certified for use with our furRaces.

Vent Termination
Venting Through a Non-Combustible
Combustible Wall
Consult

External

Power

Venter

6. Gas Supply

manufacturer

instructions.

and Piping

Poison

carbon

Models
Natural

designated
for Natural Gas are to be used with
Gas ONLY, unless
properly
converted
to use

with

monoxide

and

gas hazard.

LP gas.

Failure
personal

to follow
injury

these
and/or

instructions
property

can result

Gas Pressures
•____________________________________________________________________________
Gas
Manifold
Supply Pressure
Pressure
Type
RecomMax.
Min.
mended
High
Low
Natural

7"
(1.7 kPa)

14"
(3.5 kPa)

4.5"
(1.1 kPa)

3.5"
(0.9
kPa)

1.7"
(0.42
kPa)

Propane

11"
(2.7 kPa)

14"
(3.5 kPa)

11"
(2.7 kPa)

10"

4.3"

(2.5
kPa)

(1.07
kPa)

in death,

damage.

Gas Supply Requirements
•

Use only the Type of gas approved
ing plate for approved
gas type.

•

Gas input must not exceed the rated input shown on the rating plate. Overfiring
will result in failure of heat exchanger
and cause

•

Do not allow

dangerous
minimum

for this furnace.

See rat-

Fire)

operation.
supply

pressure

Doing so will decrease input to furnace.
Gas supply and manifold
pressures.

Manifold Gas Pressure Adjustments (Hi& Lo

to vary downward.
Refer to Table

2 for

NOTE: Gas supply
mum values listed
gas suppliers.

pressure MUST
on rating plate.

Make adjustment
to manifold pressure
combustion
air box cover removed.
combustion

with burners

operating

and

1.

Remove

2.

Connect manometer
to the tapped opening on the outlet
side of gas valve or on the manifold pipe. Use a manometer
with a 0 to 12" minimum water column range.

3.

Turn gas ON. Operate

air box cover.

the

jumper wire on the R to Wl
on the fan board.

_]

be within minimum and maxiPressures
are usually set by

furnace

on high fire by using

& W2 thermostat

connections

441 01 2016 02

a

4. Remove
theadjustment
coveronthegasvalve.Turnadjustingscrewcounterclockwise
todecrease
themanifold
pressure
andclockwise
toincrease.
SeeFigure29.
5. Setthe manifold pressure to value shown in Table 2,
Table

3 or Table

4.

Ensure furnace is equipped with the correct
Refer to Table 3 & Table 4 for correct orifice
ing value

and specific

gravity

for natural

main burner orifices.
size for a given heat-

and propane

gas.

Operation Above 2000' Altitude

6.

Operate the furnace on low fire by using a jumper wire on
the R to Wl thermostat connections on the fan board.
Note: The fourth (4th) DIP switch should be in the on position to set the low fire manifold pressure. (See wiring diagram)

7.

Repeat steps 4 and 5 for low fire operation.

8.

When the manifold pressures are properly set, replace the
adjustment screw covers on the gas valve.

9.

Removethejumper wires from the thermostat connections
on the fan board. Remove manometer and replace plug in
manifold.

Fire,

Explosion,

Poison

carbon

monoxide

gas

hazard.

This conversion
shall
be done by a qualified
service
agency
in
accordance
with
the
Manufacturer's
instructions
and all applicable
codes
and requirements, or in the absence
of local codes, the applicable
national
codes.
Failure

to follow

these

death,

personal

injury

instructions
and/or

exactly

property

can result

in

damage.

10. Replace combustion air box cover.
11. Return fourth (4th) DIP switch to previous setting.
These units may be used at full input rating when installed at altitudes up to 2000'. When installed above 2000', the high fire input
must be decreased
2% (natural) or 4% (LP) for each 1000' above

Natural Gas Input Rating Check
NOTE: The gas meter can be used to measure
input to furnace.
Rating is based on a natural gas BTU content of 1,000 BTU's per
cubic

meter.

Check

with gas supplier

for actual

BTU

content.

1.

Make sure combustion
air box cover is in place and closed
before performing
the following
steps.

2.

Turn OFF

gas supply

Use jumper
3.

Time

gas meter
ample.
4.

wire

how many

to all appliances

and start

to make

it takes

one complete

the smallest

dial on the

revolution.

Refer to Ex-

Repeat steps 2 and 3 with jumper wire on R to Wl for low
fire. NOTE: Fourth (4th) DIP switch must be in on position.
(See furnace
wiring diagram).
Return
switch to previous
setting after check.

fourth

(4th)

DIP

No. of Seconds

BTUContent
1,000

Per
Hour
3,600

TimePer Cubic

the intersection
of the heating value and elevation will be the manifold pressure required. If a gas orifice change is also required, the
box is shaded.
the table.

|

Foot in48
Seconds ]

The required

High

Altitude

Hour
75,000
Elevation

5.

If meter

Relight

uses a 2 cubic foot dial, divide results

all appliances

and ensure

(seconds)

by

all pilots are operating.

Orifice Sizing
NOTE: Factory sized
the furnace Technical

441 01 2016 02

orifices for natural
Support manual.

and LP gas are listed

orifice

size is shown

at the bottom

Sea Level

BTU Per

1,000 x 3,600 + 48 = 75,000 BTUH
NOTE:
two.

performance
based on elevation
gas and propane.

To use the natural gas table, first consult your local gas utility for
the heating value of the gas supply. Select the heating value on the
vertical border and follow across the table until the appropriate
elevation for the installation
is reached. The first value in the box at

Example
NaturaIGas

by a simple adjustment
of
or a combination
of a pres-

sure adjustment
and an orifice change. The changes required depend on the installation
altitude and the heating value of the fuel.
Table 3 & Table 4 showthe
proper furnace manifold pressure and
gas orifice size to achieve proper
above sea level for both natural

furnace.

on R to W1 and W2 for Hi fire.
seconds

sea level. This may be accomplished
manifold pressure or an orifice change,

in

Input

Rate = Nameplate
Input Rate
High Altitude
Natural

x (Multiplier)

Multiplier
LP Gas

2000'-2999'

0.96

0.92

3000'-3999'

0.94

0.88

4000'-4999'

0.92

0.84

5000'-5999'

0.90

0.80

6000'-6999'

0.88

0.76

7000'-7999'

0.86

0.72

[_

of

MANIFOLDPRESSUREAND ORIFICE SIZE FOR HIGH ALTITUDEAPPLICATIONS
Table3

NATURAL GAS
MEAN ELEVATION

HEATING VALUE

0 to 1999

BTU/CU. FT,

("wc)

2000 to
2999("wc)

FEET ABOVE SEA LEVEL

3000 to

4000 to

5000 to

6000 to

7000 to

3999 (" wc)

4999 (" wc)

5999 (" wc)

6999 (" wc)

8000 (" wc)

Hi

Lo

Hi

Lo

Hi

Lo

Hi

Lo

Hi

Lo

Hi

Lo

Hi

Lo

800

3.5

1.7

3.5

1.7

3.5

1.7

3.5

1.7

3.5

1.7

3.5

1.7

3.5

1.7

850

3.5

1.7

3.5

1.7

3.5

1.7

3.5

1.7

3.5

1.7

3.5

1.7

3.5

1.7

900

3.5

1.7

3.5

1.7

3.5

1.7

3.5

1.7

3.5

1.7

3.5

1.7

3.4

1.7

950

3.5

1.7

3.5

1.7

3.5

1.7

3.5

1.7

3.3

1.6

3.2

1.6

3.1

1.5

1000

3.5

1.7

3.4

1.7

3.3

1.6

3.2

1.5

3.0

1.5

2.9

1.4

2.8

1.4

1050

3.2

1.6

3.1

1.5

3.0

1.5

2.9

1.4

2.7

1.3

2.6

1.3

2.5

1.2

1100

2.9

1.4

2.8

1.4

2.7

1.3

2.6

1.3

2.5

1.2

2.4

1.2

2.3

Orifice Size

Table

#42

#42

#42

#42

#42

#42

1.1
#42

LPG or PROPANE

4

MEAN ELEVATION
HEATING VALUE
BTU/CU, FT.

2500

2000 to

3000 to

4000 to

5000 to

6000 to

7000 to

(" wc)

2999 (" wc)

3999 (" wc)

4999 (" wc)

5999 (" wc)

6999 (" wc)

8000 ("wc)

#55

#55

#55

#55

10.0
Hi

Orifice Size

FEET ABOVE SEA LEVEL

0 to 1999

I

4.9
Lo

10.0
Hi

#54

I

4.9
Lo

9.4
Hi

#54

I

Lo
4.6

#54

NOTE:
NATURAL GAS DATA BASED ON 0.60 SPECIFIC GRAVITY. PROPANE DATA BASED ON 1.53 SPECIFIC GRAVITY. FOR
FUELS WITH DIFFERENT SPECIFIC GRAVITY CONSULT THE LATEST EDITION OF THE NATIONAL FUEL GAS CODE ANSI
Z223.1 and CAN B149.

Changing Orifices
1.

After

disconnecting

remove
ment.

the access

power

and gas supply

door,

exposing

the

Manifold

to the furnace,
burner

(Downflow)

compart-

a. Remove the five (5) screws holding the burner box cover
to expose the manifold and burners. (Figure
7 or Figure 8)
2.

Disconnect
gas line and pilot tubing
ifold can be removed.

3.

Disconnect
wiring at gas valve.
location of any and all electrical

4.

Remove

the four (4) screws

valve to the manifold supports.
See (Figure
7 or Figure 8).

from gas valve so man-

Be sure to note the proper
wiring disconnected.

holding

the manifold

Do not discard

and gas

any screws.

Manifold (Upflow/Horizontal)
25-22-38

5.
6.

Carefully

remove

Remove

the orifices

with proper
7.

Tighten
Figure

sized

orifices
9.

the manifold

assembly.

from the manifold

orifices.
so they

See Figure
are

seated

and replace

them

9.
and

gas

tight.

See

25-22-32

_]

441 O1 2016 02

8.

Changing

--( -{,

Orifices

j

Flexible corrugated
inside the furnace
nace or ductwork.

Measure from face of orifice
to the back side of the

9.

mani fold.

10.

Install

11.

Measure

_,,,",,,,_

Properly

metal gas connector may NOT be used
or be secured or supported
by the fur-

size gas pipe to handle

or run gas pipe directly
correct

combined

from gas meter

pipe size for run length

pipe length

from gas meter

appliance

load

or LP gas regulator.
and furnace

rating.

or LP second

stage

regulator.

Fire or explosion

8.

Reassemble
all parts in reverse order as removed. Be sure
to engage the main burner orifices in the proper opening in
the burners.

9.

After reassembling,

turn gas on and check all joints

leaks using a soapy
mediately.

solution.

for gas

All leaks must be repaired

hazard.

Gas connector
must be properly
through
the side of the furnace,
inside
the furnace.
Failure
death,

to properly
bodily
injury

install
and/or

installed,
cannot
go
and can not be used

gas connector
can
property
damage.

result

in

im-

Additional LP Piping Requirements

Gas Piping Requirements

•

1.

Install gas piping in accordance
with local codes, or in the
absence
of local codes, the applicable
national codes.

2.

It is recommended

that a manual

shutoff

•

valve be installed

in the gas supply line outside the unit. Locate valve as close
to the furnace as possible where it is readily accessible.
Refer to Figure
10.

Have a licensed

LP gas dealer

age tank and check
If copper

tubing

make all connections

all connections

is used,

it MUST

at stor-

from tank to furnace.

comply

with limitation

set

in Local Codes, or in the absence of local codes, the gas
codes of the country having jurisdiction.
See Appendix.
•

Two-stage

regulation

of LP gas is recommended.

Typical Gas Piping
Fire or explosion

hazard.

Liquid
settle

(LP) gas is heavier
than air and will
in low areas and open depressions.

petroleum
and remain

Thoroughly
ventilate
area and dissipate
gas. Do NOT
use a match or open fla me to test for lea ks, or attempt to
start up furnace
before thoroughly
ventilating
area.
An open flame or spark can result
injury and/or property
damage.

in death,

personal

Final Check
•

Test all pipe for leaks.

•

If orifices
leaks.

•

During pressure
following:

25-22-31

3.

Use black
proved

iron or steel

pipe and fittings

Use pipe thread
LP gases.

5.

Install a dripleg no less than 3" long totrap
before it can enter gas valve.

7.

compound

which

is resistant

to natural

Use two pipe wrenches
vent gas valve

441 01 2016 02

when

from turning.

making

supply

dirt and moisture

connections

testing

make

sure they are checked

of gas piping system,

for

observe

the

does not exceed 1/2" PSIG, isolate
its individual
manual shutoff valve.

the

b. If test pressure exceeds 1/2" PSIG, the furnace and its individual shutoff valve must be disconnected
from the gas

and

•

Provide a 118" inch plug for test gauge connection
immediately up stream of gas supply connection
to furnace.

changed,

a. If test pressure
furnace
by closing

pipe ap-

by local code.

4.

6.

or other

where

system.

To check

for leaks apply

each joint.

Bubbles

soap suds or a liquid detergent

forming

indicate

•

Do not use an open flame totest
sion could occur.

•

Correct

to pre-

even the smallest

to

a leak.

for gas leaks. Fire or explo-

leak at once.

[_

7. Electrical

Wiring
Humidifier/Electronic
The furnace

Electrical

shock

hazard.

cleaner

Turn OFF electrical
power at fuse box or service
panel
before making
any electrical
connections
and ensure
a
proper
ground
connection
is made before
connecting
line voltage.
Failure
and/or

to do so can result
property
damage.

in death,

personal

Do NOT exceed 115V/0.8 amp. maximum
for

electronic

air

both

the

EAC

terminal

and

the

HUM

current

load

terminal

com-

the furnace

is fired

bined.

injury

NOTE:

and grounded
of local codes,

in accorthe appli-

Field wiring connections
must be made inside the furnace connection box. A suitable strain relief should be used at the point the
wires exit the furnace casing.
shall

and/or

The humidifier

will be powered

when

and the circulating air blower comes on. The electronic
air cleaner
will be powered anytime the thermostat
calls for air movement.

The furnace MUST be electrically
wired
dance with local codes, or in the absence
cable national codes.

conductors

for 115 VAC humidifier

connection.

CAUTION

Power Supply Wiring

Copper

is wired

Air Cleaner

be used.

Line voltage

sized for the input amps stated on the rating
be connected
to its own separate
circuit.

wires

should

plate. Furnace

be

must

However, the electronic
air cleaner is NOT energized
during continuous fan operation
controlled
by the electronic
fan control.

Dehumidification

(NTV6NNE)

The fan control is wired for 24 VAC normally open (N/O) dehumidistat connection.
Connect dehumidistat
to the R terminal and the
1/4" male quick connect
Figure 14 and "Furnace
cooling
ergized

Y2 terminal
on the fan control
(See
Wiring Diagram3
A 20% reduction
of

airflow will occur when the Y2 dehumidistat
terminal
during a call for cooling from the thermostat.

is en-

I

Figure 11

Thermostat
The 2-stage
furnace control will operate with either a single stage
or a two stage heating thermostat
and will provide 2-stage
heating

I Electrical Connections
I (NTV6/VNE)

NOTE: Control is ground sensitive.
NOTE: Junction Box can be mounted to either the left or right side.

operation.
For single stage thermostat
installations,
the R and W
wires from the thermostat
connect to the R and Wl connections
on the furnace

control.

Note:

The fourth

(4th) DIP switch

should

115V=

60Hz.

be in the off position for the furnace to operate properly with a
single stage thermostat.
Failure to change DIP switch with single
stage thermostat
will result in Low Fire operation
ONLY. (See wiring diagram) During operation,
the furnace will operate on low fire
for 12 minutes. If the heat request exists for more than 12 minutes,
the furnace will automatically
shift to the high fire mode for the re-

Ground

maining duration
of the heating cycle. For 2-stage
thermostat
installations,
the R, Wl and W2 wires from the thermostat
connect

_Lo*Vo_go

to the R, Wl

and W2 connections

on the furnace

control.

During
i Terminal Board _

operation,
the furnace will shift from low fire to high fire as requested by the thermostat.
The thermostat
heat anticipator
should
be adjusted
to a .10 setting for both types of thermostats.
Thermostat
location has an important
effect on the operation
of
the unit. Follow instructions
included with thermostat
for correct
mounting

2
_

"rh_no_tat

and wiring.

Low voltage connections
board to fan control.

to furnace

must

be made

on terminal

Optional Equipment
All wiring from furnace to optional equipment
MUST conform to local codes or, in the absence of local codes, the applicable
national
codes. Install wiring in accordance
with manufacturer's
instructions.

_]

(_'_,F,_ TwoStage'
_Thermostat

1

Motor
Control

Variable
Motor

Speed

25-23-11

441 01 2016 02

Figure 12

Electrical Connections
(Upflow/Horizontal)

NTP6/TNE

Fan Control
The fan control

NOTE: Control is ground sensitive.
NOTE: Junction Box can be mounted to either the left or right side.

is preset

at the factory

with an adjustable

blower

ON delay of 30 seconds in the heating mode. The blower OFF timing is preset at 140 seconds. If desired, the fan ON delay and OFF
delay can be reset to obtain the longest delay times while still
maintaining

comfort

levels.

See "Furnace

Wiring

Diagram".

NOTE: It is recommended
to achieve maximum
efficiency that the
fan control be set to turn on at 30 seconds after the burners light.
NOTE: For single stage thermostat
operation
switch must be in the off position. (See furnace
Figure 14). Failure to change
will result in Lo fire operation
Fan

_L
I

switch with single stage thermostat
ONLY.
Timer

I _/

_
_

the fourth (4th) DIP
wiring diagram and

,¢-k..-./_
_,
_

Connections

/
_

_

Dip

_

Switch
_See"Wiring
for switch

Figure 13

Electrical Connections
(Downflow)

NDP6/TDE

//_

_

._ _ ,_,

_ _L_.L_

settings

FUSE

116V._=.

iv
25-22-60

441 01 2016 02

[_

8. Ductwork

and Filter (NTV6/VNE

& NTP6/TNE)
When

a refrigeration

coil is used in conjunction

with

this

Poison carbon monoxide gas hazard.

unit, it must be installed on the discharge
side of the unit to
avoid condensation
on the heat exchanger.

Do NOT draw return air from inside a closet or utility
room where furnace is located. Return air duct MUST be
sealed to furnace casing.

sealing
through

If separate

evaporator

and blower

unit is used, install

good

dampers
for air flow control.
Chilled
air going
the furnace could cause condensation
and shorten

furnace life. Dampers (purchased
locally) can be either automatic or manual. Manually operated
dampers MUST be
equipped with a means to prevent furnace or air condition-

Failure to properly seal duct can result in death and/or
personal injury.

ing operation
tion.

Duct Connections

unless

damper

is in the full heat or cool posi-

This furnace may be installed in only a bottom or side return application. Return air through the back of the unit is NOT allowed.

Side connections can be made by cutting out the embossed area
shown in Figure 15.

Cutting

Poison

This

Side Return Air Opening

carbon

Cool
air
condensate

•

monoxide

could

result

Installation

Starting
Hole

•

•

Duct Design (NTV6NNE & NTP6/TTNE)
Design

and install

air distribution

system

to comply

tioning Contractors
of America manuals or other
ods that conform to local codes and good trade

meth-

When the furnace is located in an area near or adjacent to the living area, the system should be carefully designed with returns to
minimize
noise transmission
through
the return air grille. Any
blower moving a high volume of air will produce
audible noise
which could be objectionable
when the unit is located very close to
a living area. It is often advisable to routethe return air ducts under
the floor or through the attic.
•

•

Refer to furnace Technical
for air flow information.
Size ductwork
tioning.

Duct Installation
•

Manual

(Blower

furnace

Data)

air flow for heating

ducts

flexible

and supply

for return

duct

injury.

are recommended
to balance

connectors

connections

in

system's

are

air

recom-

to furnace.

If air return grille is located close to the fan inlet, install at
least one, 90 ° air turn between fan and inlet grille to reduce
noise.
Ductwork

installed

require

in attic, or exposed

2" of insulation

to outside

with outdoor

tempera-

type vapor

Ductwork
installed
in an indoor unconditioned
quires a minimum of 1" of insulation with indoor
barrier.

barri-

space retype vapor

Panel on some models

A removal access panel should be provided
in the outlet duct
when the furnace is installed without a cooling coil. This will allow
smoke or reflected light to be observable
inside the casing to indicate the presence of leaks in the heat exchanger.
This access cover shall be attached in such a manner as to prevent air leaks.

Filters
A filter MUST be used. Filters may not be supplied
but can be purchased
from your dealer.

with all models,

The furnaces, with 1600 or less CFM rating, are supplied with a
16" x 25" high velocity filter and rack. On these models, the supinternally

for bottom

return

or ex-

and air condiThe furnaces with greater than 1600 CFM requires that both left
and right side returns are used in side return applications.
Two 16"
x 25" high velocity filters and racks are provided with furnace. Fil-

Requirements

space.

dampers

or in individual

plied filter rack may be mounted
ternally for side return.

When furnace supply ducts carry air outside furnace
seal return air duct to furnace casing and terminate
outside

_]

to handle

Support

personal

mended

Inspection

with Air Condiapproved
practices.

•

and/or

Non-combustible,

tures
er.
Bottom returns can be made by removing
the knockout
panel in
the furnace base. Do NOT remove knock-out
except for a bottom
return.

in death

of locking-type

all branches,
flow.
•

gas hazard.

passing
over
heat
exchanger
can
cause
to form resulting
in heat exchanger
failure.

area,
duct

ter racks must be mounted externally.
If return air must be on one
side only, an optional 20"x 25" filter standoff rack kits can be used.
(See Figure 16) For bottom return, an optional 20" x 25" filter rack
kit can be mounted

internally.

441 01 2016 02

iiiiiiiiiiiiiiiiiiiiiiiill
!!!!!!!iilli! iili!i

iil¸i!!!
i iiiiiiiiii!i

ii!!

Optional

Filters Installed

Duct Standoff

on Two Sides

20 x 25 Optional
Filter Rack

Filter

Filter

Filters Rack Installation
Bottom

Side Return
Center

the filter rack on the side panel, flush with the bottom

edge

of the furnace. Mark the fastening
holes. Drill the fastening holes in
the side panel and fasten the filter rack in place with sheet metal
screws.

See Figure

17 & Figure

18.

CAUTION

When installing a bottom mounted filter rack, slide the two side filter clips to the back of the furnace BEFORE installing.
This will allow the rack to clear the front raised edge of the furnace.
Insert
rack into side clips first and push rack back until it is fully engaged
into back clip. When rack is in place, slide clips back into place
midway

If filters
are only suitable
homeowner
that filter size
conditioning
is added.

Return

on rack as shown

in Figure

Bottom

Side

19.

for heating
application,
advise
may need to be increased
if air

Return

Filter

Mounted

Filter

Rack

Rack

AW3192

Slide filter clips

towards

back

before

removing

Filter

=

Ductwork

Sub-Bases
The

for Combustible

Subbase

downflow
furnace

and Filter (Downflow/Horizontal)

for Combustible

furnace
is installed

The opening

Floors - Furnace Only
Floors

MUST

is set on combustible

material

on a coil box (cased

be used

when

a

even when the

1.

in the base is 11/4"(32mm)

narrower
than the minimum
floor. This is done to maintain

shorter

and 11/8"(29mm)

required size of the opening
in the
a 1" clearance
between the floor and

the plenum.

coil).

NOTE:
Supply
opening
is 37/8" from the rear of the furnace.
Therefore
maintain a 37/8" clearance
from a wall behind the furnace (where

on NDP6/TDE

2.

Fabricate

the

plenum

to the dimensions

Note that the dimensions

given

are outside

given

in Table

dimensions.

applicable).

Cut the opening in the floor according
the floor must be cut to the dimensions
the base is equipped

with locating

to Table 5. The hole in
listed in Table 5 since

tabs that center

the base

over the opening.

441 01 2016 02

[_

5.

Table 5

Sub-bases

for Combustible

sub-base
Floor

sub-base for Combustible Floors
Part Number

for Combustible
Dimensions

N _

J*

K**

NAHH001SB

1511116

283/4

149/16

NAHH002SB

1 95/16

283/4

183/16

NAHH003SB

2215116

283/4

NAHH004SB

1511/16

NAHH005SB

1 95/16

NAHH006SB

2215/16

(Furnace

Floors Dimensions
Opening

Opening In
Base For Plenum

In Floor

Typical Plenum
Dimensions

M

N

P

R

S

16

16114

14518

15

13112

15

13112

16

16114

18114

15

17118

15

17118

2113/16

16

16114

21 t/8

15

193/4

15

193/4

209/16

149/16

16

161/4

145/8

15

131/2

15

13112

209/16

183/16

16

161/4

181/4

15

171/8

15

17118

209/16

2113/16

16

161/4

21 t/8

15

193/4

15

193/4

Only)

sub=base for
Cased Coil

Outside Dimension
_
3.

Base Spacer Side To Side
Set the base over the opening

in the floor, centering

ing in the base over the opening
to the floor with screws
or
Figure 22.

Figure 20

4,

the open-

3.

in the floor. Fasten the base
nails.
See
Figure 20 and

Exploded View of Sub-Base
for Furnace ONLY

Figure

Drop the plenum through the opening in the base. The flange
of the plenum should rest on top of the combustible
floor
base.

Sub-base for Combustible

Set the base over the opening

Floors- Downflow Coil

in the floor, centering

ing in the base over the opening
to the floor with
screws
or
Figure 22.

21

[

the open-

in the floor. Fasten
nails.
See Figure

the base
21 and

Exploded View of Base for
Downflow Cased Coil

25-21-46b

4,

Drop the plenum through the opening in the base. The flange
of the plenum should rest on top of the combustible
floor
base.

Box
The

Subbase

downflow
bustible

for Combustible

furnace,

used

Floors

MUST

with a downflowcoilbox,

when

Setting

a
Furnace

Cut the opening in the floor according
the floor must be cut to the dimensions
the base is equipped
over the opening.

the Base

is set on com-

flooring.

NOTE:
Supply
opening
is 37/8" from the
Therefore
maintain
a 37/8 ', clearance
from
ble).
1.

be used

with locating

rear
wall

of the
(where

furnace.
applica-

Subbase
Insulation

to Table 6. The hole in
listed in Table 6 since

tabs that center

the base

Wood Floor

The opening in the base is 11/4"(32mm)
shorter and 1 1/8" (29mm)
narrower than the recommended
size of the opening in the floor.
This is done to provide
plenum.
2.

a 1" clearance

between

the floor and the

Fabricate
the plenum to the dimensions
given in Table
Note that the dimensions
given are outside dimensions.

6.

This subbase for combustible
floors has been designed so that the
height of the sub-base
raises the downflow
coil off the floor to allow easy installation
of the condensate
drain. See Figure 23.
441 01 201602

Figure 23

Condensate

Line Raised

by Base

Figure 24

Filter Rack Installation

25-20-52

25-21-05c

Non-Combustible

Floor:

NOTE: Plenum must be fitted as close to the return air flange of the
unit as possible to eliminate any air bypassing
the filters.

Set the furnace over the opening in the floor. If necessary,
grout
around the base to seal air leaks between the base and the floor.

3.

4.

Filters:

The filters

supplied

air plenum

above

furnace.

NOTE:

with the furnace
the furnace.

See Figure

air plenum
"A" (Figure

a return

air duct or grille

NOTE:

The furnace

MUST

extend

25) to provide

above

is provided

handle the airflow
the furnace.

required

if central

Insert end of filter rack with

a sufficient

height

for the attachment

with high velocity

and type of filter supplied

of

Slide remaining filter into unit and up into place
side of unit. See Figure 25.

Figure 25

[

Filter

3

air conditioning

Installation

/4' (19ram)

flange

into slot in the

insert front end with 1/4" (6mm)

and

back,
push

into front slot.

14"
(350mm)

will

With filter rack pushed
into position

T

is used with

24.

with filter rack
25-21-05d

pushed as far forward as it will go, bend 1/4" (6mm) flange and
3/4"(19mm)
flange up 90 degrees.
See Figure 24.

10. Checks

and Adjustments
CAUTION

Startup
NOTE:
Refer
ManuaL
441 01 2016 02

on left hand

type filter(s).

with the furnace

back of the unit. See Figure

flange

the right hand side of the

with each

the filters.

The size, quantity,

2,

in the return

through

24.

The return

above dimension

may be installed

A filter rack is supplied

Filters can only be installed

unit blower opening. Slide filter into unit until it is in position to
be pushed up and over into place on the left hand side of unit.
See Figure 25.

to startup

procedures

in the

Users

Information

If any sparks,
odors or unusual
noises
shut OFF power to furnace.
Check for
struction
to blower.

occur,
wiring

immediately
errors
or ob-

Gas Supply Pressure
Gas supply

pressure

values listed on rating
pliers.

should

be within

plate. Pressures

(See L.P. Kit instruction

manual

Place thermometers
in supply and return air registers as
close to furnace as possible, avoiding
direct radiant heat

1,

minimum

and

are usually

for furnaces

maximum

from heat exchangers.

set by gas sup-

converted

Operate furnace on high fire for 10 minutes with all the registers and duct dampers open by using a jumper wire on R
to Wl and W2 thermostat
connections
on the fan board.

2,

to L.R gas)

Note: The fourth (4th) DIP Switch should
tion. (See furnace wiring diagram)

Adjust Pilot Burner
3.

The furnace has a pilot flame to light the main burner. The flame
should surround 3/8" to 1/2" of the flame rod. See Figure 26. To adjust, remove cap from pilot adjusting
screw on gas valve. Turn
screw counterclockwise
to increase
or clockwise
to decrease
flame as required.

Replace

cap after adjusting

Take readings

with range

4.

on rating

If the temperature
rise is not in the correct range, the blower
speed must be changed. A higher blower speed will lower

screw.

the temperature
rise. A lower blower
temperature
rise.

speed will increase

the

5.

Repeat steps 2 thru 4 with the furnace operating on low fire
for 10 minutes by using a jumper wire on the R to W1 thermostat connections
on the fan board.

6,

Remove the jumper
plete. Return fourth

Flame Rod

Hot Surface
Igniter

specified

plate.

Pilot Burner

/

and compare

be in the on posi-

wire after the adjustments
(4th) to previous setting.

are com-

Changing Blower Speedon NTP6/TNE&
NDP6/TDE

10-11-65

Main Burner Flame Check
Allow

the furnace

the main burner
Check

to run approximately
and pilot flames.

for the following

(Figure

10 minutes

See Figure

then

inspect

27.

27):

Since the manufacturer
cannot establish
that will be applied
to the unit, it is the
installer
dealer/contractor
to select
speeds

•

Stable and blue flames. Dust may cause orange tips or
wisps of yellow, but flames MUST NOT have solid, yellow tips.
Flames
extending
changer.

•

Flames

directly

do NOT touch

from

burner

into

heat

application

If it is necessary
1.

•

for the

ex-

sides of heat exchanger

to change

when
speeds,

the

the static pressure
responsibility
of the
the
proper
blower

unit

is installed.

refer to steps

below.

Refer to Furnace Wiring Diagram for location of
and cooling speed taps located on the electronic
as well as location of unused blower motor speed
the chart (Table 6) to determine
the blower motor

the heating
fan control
leads. Use
speed set-

tings.
If any problems with main burner flames are noted, it may be necessary to adjust gas pressures,
or check for drafts.

Table 6

Blower

Speed

i iiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
i! i !! ! !! i! !!i!ii!!i!i i i!ii!ii!ii!ii!ii!ii!i !i !! !! !!i
Main Burner
Wire Color

iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii

Chart

Motor Speed

Black

High

Orange*
Blue

Med-High
Medium

Red
* Med-High
2,

Temperature Rise Check
3,

speed MUST

rise through the furnace
ture rise is the difference
tures.
To check

IN

temperature

be set to give the correct

air temperature

as marked on the rating plate. Temperabetween supply and return air tempera-

rise,use

the following

procedure:

may not be provided

on all models.

Change the heat or cool blower motor speed by removing the
motor lead from the "Heat" or "Cool" terminal and replace it
with the desired motor speed lead from the "Unused
Motor
Lead" location.
Connect
the wire previously
removed
from
the "Heat" or "Cool" terminal to the vacated "Unused
Motor
Lead" terminal.

10-10-78

The blower

speed

Low

If the same speed must be used for both heating and cooling,
remove the undesired
motor speed lead from the "Heat" or
"Cool" terminal and connect that lead to the open terminal at
"Unused
Motor Lead" location or tape off. Attach a jumper
between the "Heat" and "Cool" terminals
and the remaining
motor speed lead.
441 01 201602

Note:Whenusingthesamespeed
onmotors
with(4)speed
leads,
itwillbenecessary
totapeofftheterminal
ofthemotor
speedleadremoved
fromthe"Heat"
or"ooor'terminal
with
electrical
tapesinceanopenterminal
willnotbeavailable
at
the"UnusedMotorLead"location.
is provided

on the electronic

fan control

located

in the

circulating
blower compartment
for operation
of the continuous
fan option. This connection
is intended for the low speed motor
tap, and has a lower contact rating (8 amps) than the heat and cool
taps. When

the low speed

blower

lead is connected

Heating and Continuous

Note:

The blower

speeds

tory for this product

Turn OFF
Failure

power

hazard.

Since

to furnace

that

to do so can result

before

changing

in death

and/or

speed

personal

taps.

be applied

installer

injury.

speeds

that the manufacturer

cannot
to the

unit,

dealer/contractor
for the

application

sets from the fac-

400 C FM per ton cool-

on the temperature

the manufacturer
will

lead going to the "Heat"

a re based on a nominal

ing and the mid range

shock

Blower Speed the Same

Note: There should be only ONE motor
and "Cont" terminals.

to this termi-

Changing BlowerSpeed on NTV6/VNE

Electrical

the oth-

If it is necessary
to operate the heating speed and continuous
blower speed using the same blower speed, connect a jumper between the "Heat" and "Cont" terminals
on the electronic
fan control.

Continuous Fan Operation
A terminal

nal, this will provide low speed blower operation whenever
er two speeds (Heat or Cool) are not energized.

rise for heating.

establish

the static

it is the

responsibility

to

select

when

the

the
unit

proper

pressure
of the
blower

is installed.

Blower Motor Control

CF"
s%%cC%U",
010
*EXAMPLE
ON
;

1

l

0

INPUT
SIGNALOR
THERMOSTAT
CONNECTIONS

1_8;

OFF
DIP
SWITCHES

Cooling
6,7&8:

Airflows

000
001
010
011

Ton
Ton
Ton
Ton

3,5
3,0
2,5
2,0

Switches

*See "Technical
Support
Manual" for correct airflow
rates.
25-23-10

If it is necessary
1.

to change

speeds,

refer to steps

below.

The heating, cooling and continuous
blower speeds can be
adjusted by changing the switch settings that are located on
the motor control (see Figure 28). Switches #1 and #2 adjust the continuous
blower speeds. Switches #3, #4 and #5

2,

The 115 VAC power supply to the furnace must be turned
OFF before making adjustments
to the motor.

adjust the heating speeds. Switches #6, #7 and #8 adjust
the cooling speed. See the" Technical Support Manual"for
the switch settings for the desired airflow rates for the installation.

11. Furnace

Maintenance
CAUTION

It is recommended
iced on an annual
qualified

service

that the furnace
be inspected
and
basis
(before
the heating
season)

"User's

Information

of Operation

is the normal

servby a

operating

sequence

& Diagnostics
for the 2-stage

control

for NTV6/VNE

system.

Cooling (Y) Request:
24 VAC signals
•

Cool motor

441 01 2016 02

Manual".

technician.

12. Sequence
The following

See

applied
speed

to Y & G terminals
energized

of EFT (electronic

after 5 second

fan timer)

Cool Fan On Delay

time.

control.

Y & G signals removed from EFT.
• Cool motor speed de-energized
Cooling

(Y) and dehumidification

(Y2) requests:

•

24 VAC signals

applied

•

Same operation

as the cooling

during

cooling

Circulating

(Variable

to Y, Y2 & G terminals

operation.

(Y) request,

The cooling

speed

Speed

ONLY)

of EFT (electronic

except

the cooling

returns

to the normal

fan timer)

control.

speed is reduced
setting

20% to compensate

after the Y2 signal

for high humidity

Low motor

applied
speed

to G terminals

energized

of EFT control.

without

G signal removed from EFT.
• Low motor speed de-energized

delay.

without delay.

NOTE1)

Furnaces with DC blower motors run a low circulating fan speed in response to G request.

NOTE2)

Furnaces

call for Heating
NOTE3)

with PSC blower

that occurs

Heating

during

or Cooling

speed after the selected
following

conditions

is removed.

Fan (G) Request:

24 VAC signals
•

after 60 second Cool Fan Off Delay time.

motors

de-energize

requests

received

during

Fan On Delay time expires.

loss of the Heating

the Low Heat fan speed

during

the heat exchanger

warm-up

period

on a

a G request.

or Cooling

a Fan request

The fan returns

cause

the fan speed to change

to circulating

to the appropriate

speed after the selected

heat or cool

Fan Off Delay time expires

request.

Heating (W1) Request (single stage thermostat operation, 4th DIP switch on fan timer, must be in off position)
(see furnace wiring diagram):
24 VAC signals

applied

Inducer

•

The high fire solenoid

•

Following

•

After the pilot lights,

•

Timed

from the opening

inducer

to low speed,

•

Timed

motor

to Wl

•

turns

from initial

Wl

signal

prepurge

delay,

energize

application

from

request,

begins

will delay

the selected

Heat

and the fan switches

if the Wl

to warm up.

now at high fire rate).

request

is still present

the high fire solenoid

Fan On Delay

time before

switching

the

to Low Heat speed.

energizes

after the Low

Fire Delay

and the fan switches

time expires

to High Heat speed.

EFT.

The gas valve

de-energizes

•

The inducer

and the main

•

The fan switches

•

Timed from the gas valve de-energizing,

runs at its present
to (or stays

If a new Heating

Heat until the Heat

the control

to high speed,

and the ignitor

(burners

the high fire solenoid

of the Heating

switches

opens

and light

of the main gas valve,
de-energizing

•

NOTE4)

the pilot valve

the main burners

the inducer

removed

of EFT control.

energizes.

a 3 second

(12 minutes),

terminal

on at high speed.

speed

burners

go out.

for a 5 second

postpurge

period.

at) Low Heat speed.

request

arrives

Fan Off Delay

expires

the Low Heat fan speed
while the control
or the Heat

de-energizes

is waiting

after the selected

Heat Fan Delay time expires.

in the Heat Fan Off Delay time, the fan speed switches

Fan On Delay

expires

for the new Heating

to High

request.

Heating Request (two stage thermostat operation, 4th DIP switch must be in on position) (see furnace wiring
diagram):
24 VAC signals
•

applied

Same

response

speed

unless

24 VAC signals
•

a W2 signal
applied

Same light-off
Delay,

NOTE5)

to Wl

as single

to Wl

routine

the inducer

remains

of EFT control.
operation

described

above

except

the control

will not go to high fire, High Heat fan

is applied.
and W2 terminals

as described

The EFT control

high fire and High

terminal

stage thermostat

of EFT control.

for the signal stage thermostat

on high fire, the high fire solenoid

responds

Heat fan speed.

without
Wl

delay

to the presence

only results

operation

remains

except

energized

that at the end of the selected

and the High Heat fan speed

or loss of W2 (with Wl constant).

in low inducer,

low fire and Low Heat

Wl & W2 results

Heat Fan On
energizes.
in high inducer,

fan speed.

Heating Request with Gas Supply Line Shut Off:
24 VAC signals

The high fire solenoid

energizes.

•

Following

prepurge

to warm

glows

of EFT control.

on at high speed.

a 3 second

begins

The igniter

turns

terminal

•

•

motor

to Wl

Inducer

igniter

_]

applied

•

delay,

the pilot valve

opens

and the

up.

red-hot

for 30 seconds,

then

turns off.
441 01 201602

•
•
•
•
•
•

Theigniterstaysofffor25seconds,
thenbegins
towarm-up
again.
Theigniterglowsred-hotfor30seconds,
thenturnsoff.
Thepilotvalvecloses
3seconds
aftertheigniterde-energizes.
Theinducer
de-energizes
5 seconds
afterthepilotvalvecloses.
TheSmartValve
proceeds
tosoftlockout
andflashes
errorcode6.
Thecontrol
exitssoftlockout
after5 minutes
andbeginsanother
ignition
sequence.

Gas Valve Diagnostic Codes (See Figure 29)
Steady Flash
2 Flashes

=
=

Normal Operation
Low Pressure Switch

3 Flashes

=

Low Pressure Switch Stuck Open or
Manual ON/OFF Switch in OFF Position
(Aux.

4 Flashes

=

Limit Switch

Limit Switch
Downflow

Open

Stuck

Closed

Open

- Upflow

(Aux.

Limit Switch

Open

-

ON LY)

5 Flashes

=

Flame

6 Flashes

=

Control

8 Flashes

=

High Pressure

Switch

Stuck

Closed

9 Flashes

=

High Pressure

Switch

Stuck

Open

Retry

or

ONLY)

Sensed

Out of Sequence

in Soft Lockout

(Automatic

Restart

or

Delay)

Typical

Gas

Valve

Honeywell

Diagnostic Light
(€
models)
_

LO Manifold Pressure
adjustments
HI

On/Off
Switch
OUTLET
INLET

OUTLET
Pilot
Adjustment

25-22-25a

_

INLET

25-22-49a

11. Sequence
The following

of Operation & Diagnostics

is the normal

operating

sequence

for the 2-stage

control

for NTP6/TNE & TDP6/TDE

system.

Cooling (Y) Request:
24 VAC signals
•

Cool motor

applied
speed

to Y & G terminals
energized

Y & G signals removed from EFT.
• Cool motor speed de-energized
Cooling

(Y) and dehumidification

•

24 VAC signals

applied

•

Same operation

as the cooling

during

cooling

441 01 2016 02

operation.

of EFT (electronic

after 5 second

control.

time.

after 60 second Cool Fan Off Delay time.

(Y2) requests:

to Y, Y2 & G terminals
(Y) request,

The cooling

fan timer)

Cool Fan On Delay

speed

(Variable

Speed

ONLY)

of EFT (electronic

except

the cooling

returns

to the normal

fan timer)

control.

speed is reduced
setting

20% to compensate

after the Y2 signal

for high humidity

is removed.

conditions

Circulating Fan (G) Request:
24 VAC signals
•

Low motor

applied
speed

to G terminals

energized

of EFT control.

without

G signal removed from EFT.
• Low motor speed de-energized

delay.

without delay.

NOTE1)

Furnaces with DC blower motors run a low circulating fan speed in response to G request.

NOTE2)

Furnaces

call for Heating
NOTE3)

with PSC blower

that occurs

Heating

during

or Cooling

motors

de-energize

the Low Heat fan speed

during

the heat exchanger

warm-up

period

on a

a G request.

requests

received

during

speed after the selected Fan On Delay time expires.
following
loss of the Heating or Cooling request.

a Fan request

The fan returns

cause

the fan speed to change

to circulating

to the appropriate

speed after the selected

heat or cool

Fan Off Delay time expires

Heating (W1) Request (single stage thermostat operation, 4th DIP switch on fan timer, must be
in off position) (see furnace wiring diagram):
24 VAC signals

applied

•

The high fire solenoid

energizes.

•

Following

prepurge

•

After the pilot lights,

•

Timed

from the opening

inducer

to low speed,

Timed

turns

terminal

Inducer

•

motor

to Wl

•

a 3 second

from initial

(12 minutes),
Wl

signal

delay,

the main burners

energize

de-energizing

application

from

of the Heating

switches

and light

and the ignitor

(burners

the control

request,

to high speed,

begins

now at high fire rate).

will delay

the selected

Heat

and the fan switches

if the Wl

to warm up.

request

is still present

the high fire solenoid

Fan On Delay

time before

switching

the

to Low Heat speed.

energizes

after the Low

Fire Delay

and the fan switches

time expires

to High Heat speed.

EFT.

The gas valve

de-energizes

•

The inducer

and the main

•

The fan switches

•

Timed from the gas valve de-energizing,

runs at its present
to (or stays

If a new Heating

Heat until the Heat

opens

the high fire solenoid

•

NOTE4)

the pilot valve

of the main gas valve,

the inducer

removed

of EFT control.

on at high speed.

speed

burners

go out.

for a 5 second

postpurge

period.

at) Low Heat speed.

request

arrives

Fan Off Delay

expires

the Low Heat fan speed
while the control
or the Heat

is waiting

Fan On Delay

de-energizes

after the selected

Heat Fan Delay time expires.

in the Heat Fan Off Delay time, the fan speed switches
expires

for the new Heating

to High

request.

Heating Request (two stage thermostat operation, 4th DIP switch must be in on position) (see
furnace wiring diagram):
24 VAC signals
•

applied

Same

response

speed

unless

24 VAC signals
•

a W2 signal
applied

Same light-off
Delay,

to Wl

as single

of EFT control.
operation

described

above

except

the control

will not go to high fire, High Heat fan

is applied.

to Wl

routine

the inducer

terminal

stage thermostat

and W2 terminals

as described

remains

of EFT control.

for the signal stage thermostat

on high fire, the high fire solenoid

operation

remains

except

energized

that at the end of the selected

and the High Heat fan speed

Heat Fan On
energizes.

NOTE5) The EFT control responds without delay to the presence or loss of W2 (with Wl constant). Wl & W2 results in high inducer,
high fire and High Heat fan speed. W1 only results in low inducer, low fire and Low Heat fan speed.

Heating Request with Gas Supply Line Shut Off:
24 VAC signals

applied

motor

turns

to Wl

terminal

•

Inducer

•

The high fire solenoid

energizes.

•

Following

prepurge

•

The igniter

glows

red-hot

•

The igniter

stays

off for 25 seconds,

•

The igniter

glows

red-hot

•

The pilot valve

•

The inducer

•

The SmartValve

•

The control

a 3 second

closes

delay,

proceeds

the pilot valve

for 30 seconds,

then

after the igniter

5 seconds

opens

begins

to warm up.

to warm-up

again.

turns off.
de-energizes.

and flashes

after 5 minutes

and the igniter

turns off.

after the pilot valve

to soft lockout

soft lockout

then

then begins

for 30 seconds,

3 seconds

de-energizes

exits

of EFT control.

on at high speed.

closes.

error code 6.

and begins

another

ignition

sequence.
441 01 2016 02

Gas Valve Diagnostic Codes (See Figure 30)
Steady Flash
2 Flashes
3 Flashes

=
=
=

Normal Operation
Low Pressure Switch

Stuck

Closed

Low Pressure

Stuck

Open or Manual

(Aux.

Switch

Limit Switch

Open

- Upflow

(Aux.

Limit Switch

4 Flashes

=

Limit Switch

5 Flashes

=

Flame

6 Flashes

=

Control

8 Flashes

=

High Pressure

Switch

Stuck

Closed

9 Flashes

=

High Pressure

Switch

Stuck

Open

Open

Sensed

ON/OFF

Switch

in OFF

Position

or

ONLY)
Open

- Downflow

ONLY)

Out of Sequence

in Soft Lockout

Typical

(Automatic

Gas Valve

Restart

or Retry

Delay)

Honeywell

Diagnostic Light
(€
models)
_

_

LO Manifold Pressure
adjustments
HI

OnlOff
Switch
OUTLET
INLET

OUTLET

Pilot
Adjustment

25-22-25a

25-22-49a

441 01 2016 02

[_1

Upflow

25-20-24

Models

NTV6050FBG1
NTV6075GFG1
NTV6100KJG1
NTV6125KJG1

VNEO50B12G1
VNEO75F14G1
VNE10OJ20G1
VNE125J20G1

NTP6050FBG1
NTP6075GFG1
NTP6100GFG1
NTP6100KJG1
NTP6125KJG1

TNE050B12G1
TNE075F14G1
TNE100F14G1
TNEIOOJ2OG1
TNE125J20G1

Downflow
NDP6050FBG1
NDP6075FBG1
NDP6100HFG1
NDP6125KJG1

Models
TDE050B12G1
TDE075B12G1
TDElOOF16G1
TDE125J20G1

25-21-47

%_'_
_'_,

}
,_

Manufactured

International
Comfort
Products
Lewisburg, TN USA 37091

Save This

_]

by:

Manual

Corporation

For Future

(USA)

_'
'_....

Reference

441 01 201602

Manufacturers
ALL Models

Number

(Mfr

No-See

Rating Plate)

Specifications
General
Gas Type
Transformer

Size

(VA)

T'stat Heat Anticipator
Gas & Ignition
Gas Valve
Regulation Type
Manifold Press. Hi Fire (" WC)
Lo Fire (" WC)
Pilot Orifice Size
Ignition Type/Series

Nat

LP

40
.30

40
.30

HW SV 9540
SNAP
3.5
1.7

HW SV 9540
SNAP
10.0
4.9

.018

.011

HW HSP

HW HSP

3
<480

3
<480

Combustion
Flue Outlet Size (Inches)
Std. Outlet Temp (F)
Limits & Controls
Fan Control (Type)
Fan Control
(Timed-secs)

On
Off

HWST9162A
30160
60,100,140,180

HWST9162A
30160
60,100,140,180

Gas Conversion
Kits
Nat to LP
*1011789
LP to Nat
*1011787
*Must be ordered from Service Parts

Specifications
NTV6050FB/
VNE050B12

NTV6075GF/
VNE075F14

NTV6100KJ/
VNE100J20

NTV6125KJ/
VNE125J20

50,000
35,000
40,000
28,000
35-65
35-65

75,000
52,500
60,000
42,000
35-65
35-65

100,000
70,000
79,000
56,000
45-75
45-75

125,000
87,000
89,000
72,000
40-70
40-70

115/60/5.3

115/60/9.2

115160112

115160112

General
Input (Btuh) Std/AIt.

Hi Fire
Lo Fire

Output (Btuh) Std/AIt.

Hi Fire
Lo Fire

Temp. Rise (F)

Hi Fire
Lo Fire

Electrical (Volts/Hz/FLA)
Gas & Ignition
Gas Type
Std. Main Orifices (No/Size)
Limits & Controls
Thermal Sensor (F)
Limit Control Setting (F)
Auxiliary Limit (F)

Nat
2/#42

LP
2/#54

Nat
3/#42

LP
3/#54

Nat
4/#42

LP
4/#54

Nat
5/#42

LP
5/#54

30O
See Limitin Parts List
130

30O
See Limit in Parts List
130

30O
See Limit in Parts List
130

3OO
See Limit in Parts List
130

Std. Pressure Sw. Hi Fire (Part No)
Press (Close)
Press (Open)

1010945
-0.95
-0.80

1010945
-0.95
-0.80

1010945
-0.95
-0.80

1010945
-0.95
-0.80

Std. Pressure Sw. Lo Fire (Part No)
Press (Close)
Press (Open)

1011739
-0.53
-0.35

1011739
-0.53
-0.35

1011739
-0.53
-0.35

1011739
-0.53
-0.35

10-8
4.611050
DC/1/2
Washable

10-10
6.811050
DC/1/2
Washable

11-10
9.81900
DC/1
Washable

11-10
9.8/900
DC/1
Washable

14x25x1/2
1.5
3

16x25x1/2
1.5
3.5

Blower

Data

Type & Size
Motor Amps/Rpm
Motor Type/H.p.
Filter Type
Filter Size (")
Min. Cool Cap. (Tons)
Max. Cool Cap. (Tons)

44101201602

16x25x1/2 (2)
3
5

THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE

16x25x1/2 (2)
3
5

I_

Circulation

Air Blower

Heating,
Continuous
Switch

Blower

Furnace

#2

& Continuous

Airflow

(CFM) @ 0,10" Static

Settings

#1

Cooling

50K

I

Data - NTV6/VNE
Settings

Cooling (CFM) @ 0,50" Static
(See Figure 1 - 3 for complete Airflow

Range)

Model

75K

Switch

100/125K

0*

0*

600

540

1000

0

1

730

660

1260

1

0

870

780

1500

1

1

1000

900

1725

Settings

Furnace

Model

#6

#7

#8

50K

75K

100/125K

O*

0*

0*

1200

1350

2100

0

0

1

1100

1200

2000

0

1

0

1000

1100

1800

0

1

1

900

1000

1600

1

0

0

800

900

1400

1

0

1

700

800

1200

1

1

0

650

600

1000

1

1

1

550

550

800

*Factory Setting
Heating
Switch

Air Temperature

Adjustment

Settings

(° F)*

Furnace

Model

#3

#4

#5

50K

75K

100/125K

0"*

0"*

0"*

0

0

0

0

0

1

2

3

3

0

1

0

4

7

7

0

1

1

6

12

11

1

0

0

9

14

14

1

0

1

-4

-4

-5

1

1

0

-7

-9

-8

1

1

1

-6

-13

-13

*Factory setting

*Approximate air temperature change from factory setting @ 0.20" static
on high heat )low heat speed changes with change of high heat speed on
most settings)
**Factory setting

Blower

Motor

Settings

010

DDDDD

678)

1_

8

000
001
010
011

INPUT

SIGNALOR
DIP

CONNECTIONS

OFF SWITCHES

0

*EXAMPLE
Cooling Airflows
6,7&8:

THERMOSTAT

3,5
3,0
2,5
2,0

Switches

Ton
Ton
Ton
Ton

*See "Technical Support
Manual" for correct
airflow
rates.

W
25-23-I0

i_

THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE

44101201602

Air Blower

Data - NTV6/VNE

I
n

Circulation
Heating,

Cooling

& Continuous

Airflow

Settings

Figure 1

NTV6/VNE050

(CFM VS. EXTERNAL

STATIC PRESSURE

)

1350
1250

SWITCH
SETTINGS
(#6,#7,#8)

1150

_ooo
--_--001

1050

_010
---)_--011

950 I
u.

o
_0

--I-850

.

._.... _

100

_101

k

_110

750

_111
650
550
450
0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

0.55

0.6

0.65

0.7

ESP

Figure 2

NTV6/VNE075

(CFM VS. EXTERNAL

STATIC PRESSURE)

1500
1400
SWITCH

1300

SETTINGS
1200

(#6,#7,#8)
_ooo

1100

_OOl
_010

1000 I

_011
I.L

•--I--

O

900

100

_101

800

+110

"-'-

,---,.,.,.,.,.,..

+111
700
6OO

_

k..

""_

_

...._. m

5OO
4OO
011

0.I5

0.2

0.25

0.3

0.35

0.4

0.45

0.5

0.55

0.6

0.65

0.7

ESP

44101201602

THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE

I_

Circulation
Heating,
Figure

Air Blower
Cooling

Data - NTV6/VNE

& Continuous

Airflow

I

Settings

3

NTV6NNE100/125

PRESSURE

(CFM VS.

EXTERNAL

STATIC PRESSURE)

22OO

SWITCH
SETTINGS
(#6,#7,#8)

, ,-----.-........_
2000

n

•_

1800

ooo
OOl

--_--010

1600 1

•--)_
_

1400'

011

•--)K_ 100
---e_

i

1200

101

+110
_e_111

1000
80O
6OO
0.1

0.2

0.3

0.4

0.5

0.6

0.7

ESP

_]

THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE

44101201602

LADDER

ONJ-_

DIAG_M
m >
_o
©

oo
CO
CO
r_r CO
mz
m_
_m
mr

+N
©

g_

+N

_=
g

$

o

9

8
z
%
o

r

C

_c
oC
r
©
z0

M
g<

,,o

_
>
:_
>

©

o
0

z
m

_
m
>

e

©

m
1-H E RM OSTAT
SEE MANUALS

E

FOR ADJUSTING

SWITCHES

FOR PROPER HEATING,

COOLING & CIRCULATING

SPEEDS

t012522+B

+

I

i,,',!

P,:

I

•

I I i

-

I

__

I

-t-

-

_ Jr

....

(#'_0]

,,iiJ

Y

_1

I

H

"

I

THERMOSTAT

I
I

_
--STAGE

THERMOSTAT
SEE MANUALS

I

3

-G"

_ _
i_
i_

_

,

I

IBK

I

I

I

h

¢
SWITCHES

Ii....
I # ]#_'

I

I

i

r-r-

_

CO

_==4

_

HUM

m

;

O

i'
: i_

oz

_

>

HUMO=
....

O
_H

_TRANSFORMER

--

1 --

_

MAIN
LIMIT

IGNITER

- zmh

CONTROL
_
F_5 T_

...........

T

-

___5

---

LINE VOLTAGE
LOWVOLTAGE
LOWVOLTAGE

I_

_--

INTERNAL

ROLLOUT SWITCH I TO 2
MODELIN
SERIES DEPENDING ON

....

CO[]

_

CO

FOR PROPER HEATING,

COOLING

--R

m

_ p'

_ _

O

_

40

/
_SOMEMODELS
_ ;o l/Im
O
_

i_

_

___

i

_a

[li

_

[

i

II

F _
GAS

IpRESSURE

I

I___

____

BOARD WIRING

L _1

q{_iq

PR_SSUREs,,,,ITOH
L .............

....

CONTROL

!:_

--,_

i

--

"r-_T]

--

II }'z'l'
--

-- _ --

ii

o
_

Jj

-<

m_I_l

_Jnc:X

-_ 4_-\MOTOR,
-'@ "_BLO'_VER

RED
WHITE
YELLOW

R
W
Y

I" i---------_'-=-i-----_THEU APPLIANCE MUST BE
IF ANY OF THE ORIGINAL
WIRE AS SUPPLIED WITH

PURPLE

p

REPLACED.

SPEEDS.

_Lr

F

I

AUX LIMITUPTO 2 --i
.................

I1!I;<--_
L--.--_

THERMOSTAT

<,->
s

(_
H_H
G

.... VALV_F:_4_II I

P2 :_FI,I_

GREEN
G
ORANGE
0

Ls M_L

I

2 STAGE

cO_ORCOD['
_,oooool I'J '1_"::
BLUE
BL
_ _l
II'lL==,::::t

FIELD
FACTORY
FIELD

& CIRCULATING

III

O

____LWI,I'_
2ba:E'l' IE ............ r-_-_
_<_

m

CIRCUIT

CAPACITOR

--- 5iG_UI_,

_-_=_=_=_=_=_=_=__.
|-LINE VOLTAGE FACTORY

I_

Ii_

i

__y_-TT __y_ DE__
_

I,rrZZ
i2
7! I I
U,

-7

_ _

T

-.-._ |

g

O

_
_

,

= 

ii

===@O

B,RI

$_

iRi

....

" ::<:'.....

I---

O803
_

_

i

_.

[l '_

_

_

7tt

_

I

I
J

--

--

o

"-1__

IW IG _

y
/
G
G f

FOR ADJUSTING

_

J

Y

i_ i_ w_\i.
--1 L.
W1
\

___
--

_

' IIII

_7\

--y.

--

-

_

'1 I ll_.qi n _

II

(OPTIONAL)

L
I':":'/
_

_

L

_=

BRIBKI BLI_

HUMIDISTAT

2-STAGE

,

_
©

!!

I

'"

i

_

=

I I_1

\MOTOR/

_GF

I

I

I i

_ _

/

:::l

. AUX LIMITUP TO 2 IN SERIES
DEPENDINGON MODEl

_

_b o
<:

j

ii I A=__

_isi_U

I

o

------

......

I

F--

.ll!_!_

I

I--_-_YI_I

SINGLE

_

¢W2

RI',

BL

w

w

4 _4

DC _'_

i Z

tom

_c

1111_41

e

_

--

............

-/7"

BL[I

Wr

.,,==,_

_1i_
3 8

_

II_CIRCUITBOARD

, i l___--_

.......

_

,i

SWITCH

U

-,

.....
....

i lt 

DIAGRAM

115V-60HZ

_INTERLOCK

I

IZl

_

i

'_

_

,_
_1
_w_-STAGEI

_J]

I FF_

I

I

CONDUCTORS

I

I SENSOR_

oou

_Li

^,

'

---BL--

HOT

--"
./_

R-CEPE_iDk_G_ CNiMOicELJ

_

I

I

I

FIELD) _

COPPER

_1

Vl

_
ROIIOUTSEV_TCH_TO2

.......

_iGAiSVALVE
8 4-

-.....

_1

BL

(HIVOLT

_11

....

L=.._
\'l_

IGNITER

J

_

_

_iBK_
GND

_

/

I

_q

MAINUMtT

i

I

SWITCH

iR

_

_

INTERLOCK

J
I

LADDER

SERVICING

i_

CONNECTION
BOX

115V

BEFORE

HAZARD

_

DISCONNECT
FIELD

SHOCK

_

ELECTRICAL

j

DANGER:

DIAGRAM

....

CONNECTION

_

s
2

_

_m_ _m

rn

_ o_
"' _

-- _
=
_ 4_

r_

,44
_]

_m_

m

IT MUST BE REPLACED WITH TYPE AWM-105°C WIRE OR EQUtV
I012673-B

I

!

NTV6/VNE

_SS

D

E

21

18 T_T__

_30

18

25-23-07

441 01 2016

02

I

Replacement

Models

- NTV605OFBG1,
VNEO50B12G1,

Replacement
Key
No.
1

2

NTV6075GFG1,
VNEO75F14G1,

part supplied
Functonal
Description

Heat Exchanger

BlowerWheel

3
4

Switch,AuxiliaryLimit
BlowerMotor

5

Motor Mount Kit

6
7
9

ControI,FanTimer
Transformer,40VA
Switch Door

10

Burner Assembly

will be current
Part
Number
1011544
1011363
1012407
1012408

Parts

NTV6100KJG1,
VNEIOOJ2OG1

050

active part. For parts not listed, consult
NTV6/VNE
075
100

125

1
1
1

1013105

2

2

1012478
1012479
1066700
522020024
1012084

1

1

1

1

1

1012722
1010886

1
1

1008723
1008724
1008725
1008726

1

1

1

1

1

1
3

1
4

1
5

1

1

1

1

2

2

1010901
1011450

1
2

741010042
741010039
741020004
741020001
1010364
1010365
2791042
2791043

1

Manifold Supt Bracket

1
1

1
1

1
1

P

Filter Rack Wrapper

Q

Filter

R

Filter

S

Filter Cover Plastic

T
U

Clip, Filter
Fan Timer Bracket

1008482
1012462

3
1

Blower Housing

1013131
1013132
1013128

1

Rack

Front

1

1011698
1011699
1011700
1011701

1

Valve,Natural& LP
Switch,Limit 260°F
180°F
230° F
190°F

1012188

1

1320366
1008417
1320361
1008445

1

18
19
20

Tubing,Silicone
CombustionBlowerAssembly
Relloot Switch,Limit

2071255

1

1

1

1

1011632
1005549

1
2

1
2

1
2

1
2

21

Switch,Pressure(HI)(Upper)

1

1

Heat ExchangerGaskets

1
2

1

22

1010945
2480904
2480905
2480906
2480907
1008068
1008071
1012410
1012411

1

1009524

1

1

1011739
1012472
1012473
1012475

1
1

1

W

14" x 25"

x

16"

x

x 25"

1/2"
1/2"

1
1

X

Blower

Cutoff

1
1
1

1

1

1
1

Y
BB

Blower Hanger
Rail, Blower Slide

EE
NN

Baffle, NOx
Partition, Blower

1
OO

PP

Baffle, Burner Box

Top, Burner Box

2
2
2

QQ

Cover, Burner Box

1

1

1

1

1

1

O

1

1

1

1
2

1
2

1
2

1

2

2

1

2

2

1

2

2

1

2

2

3
1

3
1

3
1

1
1
1

1
1

1

1

1

1

1
2

2

2

2

57059
1009876

2
2

2
3

2
4

2
5

1013456
1013457
1013461

1
1

1

1011454
1011455
1011456

1

1011768
1011769
1011770

1

1011469
1011470
1011471

1

721020008
721020013
1010690

1
1
1
1
1
1
1
1
1
I

1

RR
SS

Sight Glass
Bracket,PressureSwitch

1011781
1011611

1
1

1
1

1
1

I
I

1

1

TT

PressureTapTee

1011750

1

1

1

I

1

1

)(
)(
)(

PARTNOTILLUSTRATED
Wire Harness
Harness, HiVolt Motor
LoVolt Motor

1011858
1012521
1012520

1
1
1

1
1
1

1
1
1

1
1
1

)(
)(

Fuse,SAmp
Manual,Homeowners

1083348
44102200105

1
1

1
1

1
1

1
1

)(

Manual,Installation& Tech

)(

GasConve. Kit (Nat. to LP.)
(LP.to Nat.)

44101201601
1011789
1011787

1
1
1

1
1
1

1
1
1

1
1
1

1

1
1

1

Functonal
Non- Description
Top

1

1
1

1

1

1

1013303
1013304
1013305

1

Bracket, Pilot

1

1013295
1013296
1013298

1
1

125

1

M

1011943
1011944
1011946

A

Door, Blower

1011379
1013331
1013332
1013333

NTV6NNE
075
100
1

1
1

Tube, Pilot

IgnitorlSensorwith clip
Switch,Pressure (LO)(Lower)
Motor Control

Door, Louvered

1

1
1

14

28
30
33

H

1085400
1011048
1011672
1011738

1

1
2

Heat ExchangerFrt Partition

Gasket, Comb. Blower

050

1

503211
1011351

23

F

J

Pilot/Igniter
Pilot Orifice,
NAT(.018)
Orifice,
#42 NAT

16
17

Collector

1

601210
600587
1011420

place of purchase.
Pan
Number

Functonal
Non-Description

1

11
12
13

Manifold

Key
No.
E

1

1008731

15

I

- NTV6/VN E (Natural
Gas)

NTV6125KJG1:
& VNE125J20G1

1
1

1

B

Field Connect Box

1011941

1

1

1

1

C

Cover, Field Connect

1
1

1

Gasket, Collector

1
1

1

D

1010360
1093661
1093662
1093663

1

441 01 2016 02

Manufacturers
ALL Models

Number

(Mfr

No-See

Rating Plate)

Specifications
General
Gas Type

Nat

LP

Transformer
Size (VA)
T'stat Heat Anticipator

4O
.30

4O
.30

HW SV 9540
SNAP
3.5
1.7

HW SV 9540
SNAP
10.0
4.9

.018

.011

HW HSP

HW HSP

3
<480

3
<480

Gas & Ignition
Gas Valve
Regulation Type
Manifold Press.

Hi Fire C WC)
Lo Fire (" WC)

Pilot Orifice Size
Ignition Type/Series
Combustion
Flue Outlet Size (Inches)
Std. Outlet Temp (F)
Limits & Controls
Fan Control (Type)
Fan Control
(Timed-secs)

HW ST9162A
30/60
60,100,140,180

On
Off

HWST9162A
30/60
60,100,140,180

Gas Conversion
Kits
Nat to LP
*1011789
LP to Nat
*1011787
*Must be ordered from Service Parts

Specifications
NTP605OFB/
TNEO50B12

NTP6075GF/
TNEO75F14

NTP6100GF/
TNE100F14

NTP6100KJ/
TNEIOOJ20

NTP6125KJ/
TNE125J20

50,000
35,000
40,000
28,000
35-65
35-65

75,000
52,500
60,000
42,000
25-55
25-55

100,000
70,000
80,000
56,000
45-75
45-75

100,000
70,000
79,000
56,000
35-65
35-65

125,000
87,500
99,000
72,000
40-70
40-70

11516019.2

115160112

General
Input(Btuh) Std/AIt.

HiFire
Lo Fire

Output(Btuh) StdIAlt.

HiFire
Lo Fire

Temp. Rise (F)

Hi Fire
Lo Fire

Electrical(VoltslHzlFLA)
Gas & Ignition
GasType
Std.Main Orifices(NolSize)
Limits & Controls
Thermal Sensor (_F)
LimitControlSetting ('F)
AuxiliaryLimit (F)

11516015.3
Nat
2t#42

LP
2/#54

11516019.2
Nat
31#42

LP
3/#54

Nat
41#42

LP
41#54

300
SeeLimit inPartsList
130

Nat
4/#42

LP
4I#54

115160112
Nat
5/#42

LP
5/#54

300
See Limitin PartsList
130

300
See Limitin PartsList
130

Std.PressureSw. Hi Fire (Part No)
Press (Close)
Press (Open)

1010945
-0.95
-0.80

1010945
-0.95
-0.80

Std.PressureSw. Lo Fire (Part No)
Press (Close)
Press (Open)

1011739
-0.53
-0.35

1011739
-0.53
-0.35

1011739
-0.53
-0.35

1011739
-0.53
-0.35

1011739
-0.53
-0.35

10-8
6.511050

10-10
6.511050

10-10
6.511050

11-10
11.01900

11-10
11.91900

PSC/I/3
51370
Washable
14x25x1
1.5
3

PSCII/2
7.51370
Washable
16x25x1
1.5
3.5

PSCIII2
7.51370
Washable
16x25x1
1.5
3.5

PSC/3/4
101370
Washable

PSCI3/4
10/370
Washable

16x25x1(2)
3
5

16x25x1(2)
3
5

1010945
-0.95
-0.80

300
SeeLimitin PartsLi_
130

300
SeeLimitin PartsList
130

1010945
-0.95
-0.80

1010945
-0.95
-0.80

Blower Data
Type & Size
MotorAmpslRpm
MotorTypetH.p.
Cap.MfdlVolts
FilterType
FilterSize (")
Min. CoolCap. (Tons)
Max. CoolCap. (Tons)

44101201602

THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE

[_

Specifications
NDP6050FB/TDE050B12

NDP6075FB/TDE075B12

NDP6100HF/TDE100F16

NTP6125JB/TDE125J20

General
Input(Btuh) StdlAlt.

HiFire
Lo Fire

Output(Btuh) StdlAlt.

HiFire
Lo Fire

Temp. Rise (F)

Hi Fire
Lo Fire

50,000
35,000
40,000
28,000
30-60
30-60

75,000
52,500
60,000
42,000
40-70
40-70

11516015.3

Electrical(Volts/Hz/FLA)
Gas & Ignition
GasType
Std.Main Orifices(No/Size)

Nat.
2/#42

Limits& Controls
Thermal Sensor (_F)
LimitControlSetting (F)
AuxiliaryLimit (F)

11516019.2

LP
2/#54

Nat.
31#42

LP
4/#54

100,000
70,000
80,000
56,000
35-65
35-65

125,000
87,500
89,000
72,000
45-75
45-75

115/60/12

115160112

Nat.
4/#42

LP
4/#54

Nat.
5/#42

LP
5/#54

300
See Limitin PartsList
110

300
See Limitin Parts List
II0

300
See Limitin PartsList
110

300
See Limitin Parts Li_
110

Std.PressureSw. Hi Fire (Part No)
Press (Close)
Press (Open)

1010945
-0.95
-0.80

1010945
-0.95
-0.80

1010945
-0.95
-0.80

1010945
-0.95
-0.80

Std.PressureSw. Lo Fire (Part No)
Press (Close)
Press (Open)

1011739
-0.53
-0.35

1011739
-0.53
-0.35

1011739
-0.53
-0.35

1011739
-0.53
-0.35

10-8
6.5/1050

10-12
6.511050

10-10
8.5/1050

11-10
11.9/900

PSC/I/3
5/370
Washable

PSC/I/3
5/370
Washable

PSC/I/2
10/370
Washable

PSC/3/4
10/370
Washable

16x18xl (2)
1.5
3

16x18x1(2)
1.5
3

16x18xl (2)
2
4

16x18x1(2)
3
5

Blower Data
Type & Size
MotorAmpslRpm
MotorTypelH.p.
Cap.Mfd/Volts
FilterType
FilterSize (")
Min. CoolCap. (Tons)
Max. CoolCap. (Tons)

CIRCULATION AIR BLOWER DATA
NTP605OFB/TNE050B12,
Air

Delivery

NDP6050FB/TNE050B12

& NDP6075FB/TNE075B12
Air Delivery in Liters Per Second (L/S)
(Furnace Rated Co)0.5"WC ESP)

in Cubic
Feet per Minute (C.F.M.)
(Furnace Rated @0.5" WC ESP)

TAP

LOW

MED L

MED

MED H

HIGH

TAP

LOW

MED L

MED

MED H

HIGH

,10

675

859

--

1015

1394

,10

318

405

--

479

658

q
.95

.20

662

846

--

999

1342

_- o."

.20

312

399

--

472

633

_

.30
.40

651
636

819
795

---

977
952

1289
1227

1__
_,

.30
.40

307
300

387
375

---

461
449

608
579

,50
,60

608
564

765
735

---

914
870

1163
1086

"_

,50
,60

287
266

361
347

---

431
411

549
513

,70

514

685

--

818

1002

,70

243

323

--

386

473

_
w

NTP6075GF/TNEO75F14
Air

Delivery

uJ

& NTP6100GF/TNE100F14
Air Delivery in Liters Per Second (L/S)
(Furnace Rated @0.5" WC ESP)

in Cubic
Feet per Minute (C.F.M.)
(Furnace Rated @0.5" WC ESP)

TAP

LOW

MED L

MED

MED H

HIGH

o

TAP

LOW

MED L

MED

MED H

HIGH

,10

815

1043

--

1324

1649

_,

_
.95

,20

783

1030

--

1302

1616

o."

,10
.20

385
370

492
486

---

625
615

778
763

_

.30
.40

755
735

1021
989

---

1280
1255

1592
1546

"_ "6

.30

356

482

--

604

751

_

.40

347

467

--

592

730

E_

.50

704

988

--

1218

1502

E_

,50

332

457

--

575

709

,60

668

941

--

1171

1426

!_

,60

315

444

--

553

673

,70

646

881

--

1100

1353

,70

305

415

--

519

639

W

_]

_

ILl

THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE

44101201602

NTP6100KJ/TNE100J20
Air Delivery in Cubic Feet per Minute (C.F.M)
(Furnace Rated @0.5" WC ESP)

_
,9 _

Air Delivery in Liters Per Second (L/S)
(Furnace Rated @0.5" WC ESP)

TAP
.10

LOW
1210

MED L
1441

MED
--

MED H
1773

HIGH
2104

.20
,30

1201
1197

1430
1453

---

1740
1740

2078
2061

_- o."
,9 _

TAP
.10

LOW
571

MED L
680

MED
--

MED H
837

HIGH
993

,20
,30

567
565

675
686

---

821
821

981
973

,40

1191

1441

--

1718

2020

e

,40

562

680

--

811

953

-8

,50

1167

1425

--

1707

2005

-8

.50

552

673

--

806

946

-

.60

1160

1390

--

1676

1953

_ --_

.60

548

656

--

791

922

.70

1130

1365

--

1654

1917

w

.70

533

644

--

781

905

w

NTP6125KJ/TNE125J20
Air Delivery in Cubic Feet per Minute (C.F.M)
(Furnace Rated @0.5" WC ESP)

Air Delivery in Liters Per Second (L/S)
(Furnace Rated @0.5" WC ESP)

,_

TAP
.10

LOW
1264

MED L
1520

MED

MED H
1841

HIGH
2161

0. o."
-9 _

.20
.30

1251
1249

1506
1486

---

1803
1772

2132
2079

,40

1219

1456

--

1736

2042

,50

1168

1427

--

1702

1991

,60
.70

1178
1143

1415
1358

---

1672
1614

1914
1838

-8
E_=
UJ

TAP
.10

LOW
597

MED L
717

MED
--

MED H
869

HIGH
1020

,20
,30

590
590

711
701

---

851
836

1006
981

_

,40

575

687

--

819

964

"8
E_=

.50

551

674

--

803

940

.60

556

668

--

789

903

.70

540

641

--

762

868

_" o."
-9 _

UJ

NDP6100HF/TDE100F16
Air Delivery in Cubic Feet per Minute (C.F.M.)
(Furnace Rated @0.5" WC ESP)

Air Delivery in Liters Per Second (L/S)
(Furnace Rated @0.5" WC ESP)

TAP

LOW

MED L

MED

MED H

HIGH

TAP

LOW

MED L

MED

MED H

HIGH

,10

954

1312

--

1698

1925

,10

450

619

--

801

908

_

.20

950

1292

--

1645

1853

_

.20

448

610

--

776

874

.30
,40

946
915

1265
1231

---

1596
1530

1780
1708

_

.30

446

597

--

753

840

®

,40

432

581

--

722

806

E_

.50

878

1175

--

1455

1638

E_

.50

414

555

--

687

773

w

,60

830

1118

--

1362

1546

w

,60

392

528

--

643

730

.70

778

1020

--

1241

1435

.70

367

481

--

586

677

_

NDP6125KJ/TDE125J20
Air Delivery

in Cubic

(Furnace

Rated

Feet per Minute (C.F.M.)
@0.5"

WC

Air Delivery

ESP)

TAP

LOW

MED L

MED

MED H

HIGH

_
.9 _

.10
.20

1333
1294

1573
1544

---

1840
1816

2148
2093

_

w

in Liters Per Second

(Furnace

A- o."
,9 _

Rated

Co)0.5" WC

(L/S)

ESP)

TAP

LOW

MED L

MED

MED H

HIGH

.10
,20

629
611

742
729

---

868
857

1014
988

,30

1266

1500

--

1776

2041

_

,30

598

708

--

838

963

-8

,40

1240

1467

--

1726

1981

-

,50

1175

1419

--

1665

1906

"_ -8
-_

,40
.50

585
555

692
670

---

815
786

935
900

.60

1141

1357

--

1607

1828

w

.60

539

641

--

759

863

.70

1054

1308

--

1538

1751

.70

497

617

--

726

826

44101201602

THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE

[_

I
OANOER:

CONNECTION

DIAGRAM

_ID_,L_CT!ON

[MZ_jTY_#'N

BOX

TNT_R_nr

H_OT.

K

L_

NOT ON ALL

___

HAZAR0

LADDER

SERVICING

ROLLOUT

SWITCH

I_./_1

,

I ,-

,

_

t _dNTERLOCK

_

,,__1

Do

PRESSURE

Q

_EUTRAL
/

(3-11,

I_WI[CH

I

u')-_

llSV-68HZ

i TO 2 'N

GND.

L]
68HZ

DIAGRAM

--I('I
-{--I

SERIES DEPENDING ON MO_

/7,,
....VALVE
GAS

--_

SHOCK

BEFORE

_----

&
,x::_ pooELs
oW_Tc,.
----R--

=

ELECTRICAL

DISCONNECT

_

t(_COOL

F] (BK)

N

•
_i--_

_

HEAT

MLO

(BL,'>"-._W

II
FR

_TOR,_
._

L

(

,

L ' I_"__
-

W

ONLY

'

_

L

I _

1

_

_

- -- _

I

.

I

W_

III

_K
I

_

----

'

_

I--

W --

I

j

I

I

SWI'-TCH

I(Lp MODELS ONLY)I

I 14__>._

I

,

;

0

P

L.

__ ._2¢:_/___.
_,,.B.L

TZ

_°'__
_

__

DOP_E_TO_
,,

L 4J;B
lit c_-

I :;:V _'qMI/"¥
I

_

n

n

I

I

__ I_ I

iF ®_--4--

I

.....

_---°cI

4

__°°_

II

m

,@

I

_

L

I

c)

J

W

AUX. LIMIT

_ _

fIN SERIES

UP

TO2

DEPENDNG

=00

HUM

HU;_

II
. XFMR ..5V
_TRANSFORHER

I

--w--

---- w2

_

-

FrTr-_

RI/
r-----¢
Y
I BL / i,---_@ s
-

I

_
_

---

IGNITER

ON

ALL

MODELS

r

-_

_

ROLLOU

SWitCH

I 02

IN SEBES

3[

_

_ ................

I--I "" %1

o

.
_0
_,_,s_

CAiAP

=_
N
_

NOT

r-

z

I

-- --_

s_
Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 42
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Fri Apr 20 16:21:13 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu