ICP Furnace/Heater, Gas Manual L0502491
User Manual: ICP ICP Furnace/Heater, Gas Manual ICP Furnace/Heater, Gas Owner's Manual, ICP Furnace/Heater, Gas installation guides
Open the PDF directly: View PDF .
Page Count: 42
NTV6NNE
80+ 2-Stage & NTP6/TNE
VariableSpeedNDP6/TDE
SAFETY REQUIREMENTS
Recognize safety information. This is the safety- alert symbolZ_. When you see this symbol on the furnace and in instructions manuals
be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, or CA UTION. These words are used with the safety-alert symbol. DANGERidenti-
lies the most serious hazards, those that will result in severe personal injury or death. WARNINGsignifiesahazardthatcouldresu]tin
personal injury or death. CAUT__Nisusedt_identifyunsafe_racticesthatc_u_dresu_tinmin_r_ers_na_injury_r_r_ductand_r__erty
damage.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel
should install, repair, or service heating equipment.
Untrained service personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must
be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on
labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes including the current edition National Fuel Gas Code (NFGC) NFPA
No. 541ANSIZ223.1. In Canada, refer to the current edition of the National Standard Canada CANICGA-B149.1 - and .2-M91 Natural
Gasand PropanelnstallationCodes(NSCNGPIC). Wear safety glasses and work gloves. Havefireextinguisheravailableduringstart-
up and adjustment procedures and service calls.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these
instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction
practices. We require these instructions as a minimum for a safe installation.
f
Manufactured by:
International Comfort Products Corporation (USA)
Lewisburg, TN USA 37097
Table of Contents
I. SafeInstallation Requirements................ 2
2. Installation ............................... 4
3. Combustion & VentilationAir ................. 7
4.Vent and Combustion Air Piping .............. 9
5. Horizontal Venting ......................... 10
6. GasSupply and Piping ...................... 10
7. Electrical Wiring .......................... 14
8. DuctworkandFilter(Upflow) ................ 16
9. DuctworkandFilter(Downflow) .............. 17
10. ChecksandAdjustments .................. 19
11.FurnaceMaintenance...................... 21
12.Sequence of Operation&Diagnostic ......... 21
13.TenchSupport andParts ................... 26
Printed in U.S.A. LP1 10/1/2002 441 01 2016 02
1. Safe Installation Requirements
Installation or repairs made by unqualified persons
can result in hazards to you and others. Installation
MUST conform with local codes or, in the absence of
local codes, with codes of all governmental authorities
having jurisdiction.
The information contained in this manual is intended
for use by a qualified service technician who is
experienced in such work, who is familiar with all
precautions and safety procedures required in such
work, and is equipped with the proper tools and test
instruments.
Failure to carefully read and follow all instructions in
this manual can result in furnace malfunction, death,
personal injury and/or property damage.
NOTE: This furnace is design certified by the American Gas
Association and the Canadian Gas Association for installation in
the United States and Canada. Refer to the appropriate codes,
along with this manual, for proper installation.
• This furnace is NOT approved for installation in mobile
homes, trailers or recreation vehicles.
• Do NOT use this furnace as a construction heater or to heat
a building that is under construction.
• Use only the Type of gas approved for this furnace (see Rat-
ing Plate on unit). Overfiring will result in failure of heat ex-
changer and cause dangerous operation. (Furnace can be
converted to L.E gas with approved kit.)
• Do NOT use open flame to test for gas leak.
• Ensure adequate combustion and ventilation air is provided
to the furnace.
• Seal supply and return air ducts.
• The vent system MUST be checked to determine that it is
the correct type and size.
• Install correct filter type and size.
• Unit MUST be installed so electrical components are pro-
tected from direct contact with water.
Safety Rules
Your unit is built to provide many years of safe and dependable
service providing it is properly installed and maintained. However,
abuse and/or improper use can shorten the life of the unit and
create hazards for you, the owner.
A. The U.S. Consumer Product Safety Commission recom-
mends that users of gas-burning appliances install carbon
monoxide detectors. There can be various sources of car-
bon monoxide in a building or dwelling. The sources could
be gas-fired clothes dryers, gas cooking stoves, water
heaters, furnaces, gas-fired fireplaces, wood fireplaces,
and several other items. Carbon monoxide can cause seri-
ous bodily injury and/or death. Therefore, to help alert
people of potentially dangerous carbon monoxide levels,
you should have carbon monoxide detectors listed by a na-
tionally recognized agency (e.g. Underwriters Laboratories
or International Approval Services) installed and main-
tained in the building or dwelling (see Note below).
B, There can be numerous sources of fire or smoke in a build-
ing or dwelling. Fire or smoke can ca use serious bodily inju-
ry, death, and/or property damage. Therefore, in order to
alert people of potentially dangerous fire or smoke, you
should have fire extinguisher and smoke detectors listed by
Underwriters Laboratories installed and maintained in the
building or dwelling (see Note below).
Note: The manufacturer of your furnace does not test any
detectors and makes no representations regarding any
brand or type of detector.
C. To ensure safe and efficient operation of your unit, you
should do the the following:
1. Thoroughly read this manual and labels on the unit.
This will help you understand how your unit operates and
the hazards involved with gas and electricity.
2, Do not use this unit if any part has been under water.
Immediately call a qualified service technician to inspect
the unit and to replace any part of the control system and
any gas control which has been under water.
3. Never obstruct the vent grilles, or any ducts that pro-
vide air to the unit. Air must be provided for proper com-
bustion and ventilation of flue gases.
Carbon monoxide or "CO" is a colorless and odorless gas
produced when fuel is not burned completely or when the
flame does not receive sufficient oxygen.
Freezing Temperatures and Your Structure
Freeze warning.
Turn off water system.
If your unit remains shut off during cold weather the
water pipes could freeze and burst, resulting in serious
water damage.
Your unit is equipped with safety devices that may keep it from op-
erating if sensors detect abnormal conditions such as clogged ex-
haust flues.
If the structure will be unattended during cold weather you should
take these precautions.
1. Turn off main supply water into the structure and drain the
water lines if possible. Open faucets in appropriate areas.
2, Have someone check the structure frequently during cold
weather to make sure it is warm enough to prevent pipes
from freezing. Suggest they call a qualified service agency,
if required.
441 01 2016 02
START-UP CHECK SHEET
(Keep this page for future reference)
Dealer Name:
Address:
City, State(Province), Zip or Postal Code:
Business Card Here
Phone:
Owner Name:
Address:
City, State(Province), Zip or Postal Code:
Model Number:
Serial Number:
Type of Gas: Natural: _ LP:
Blower Motor H.P.:
Supply Voltage:
Which blower (DIP switch) setting is used?
Heating Cooling Continuous
Temperature of Supply Air: High Fire (°F)__ or (°C).__
Low Fire (°F)__or (°C)__
Temperature of Return Air: (°F)__ or (°C)__
Temp. Rise Hi Fire (Supply - Return ): (°F)or (°C',__
Lo Fire (Supply - Return ): (°F) or (°C)__
Filter Type and Size:
Fan "Time ON" Setting:
Fan "Time OFF" Setting:
Dealer Comments:
Manual Gas Shut-Off Upstream
of Furnace/Drip-Leg? YES
Drip-Leg Upstream of Gas Valve? YES
Blower Speed Checked? YES _ NO
All Electrical Connections Tight?
Electrical Polarity Checked?
Furnace Properly Grounded?
Gas Valve Status Light OK?
NOE_
NoE I
YES _I NO _I
YES _I NO _I
YES _I NO _I
YES _I NO _I
Gas Valve Turned ON? YES _ NO
Measured Line Pressure When Firing Unit:
Calculated Firing Rate: (High & Low Fire) (See Checks and
Adjustments Section).
Measured Manifold Pressure: Hi Fire Lo Fire
Thermostat OK? YES _ NO
Thermostat: Single Stage Two Stage
Subbase Level? YES _ NO
Anticipator Set? YES _ NO _ Set At?:
Breaker On? YES _ NO
Date of Installation:
Date of Start-Up:
441 01 2016 02 [_
2. Installation
Poison carbon monoxide gas hazard.
If this furnace is replacing a previously common-vented
furnace, it may be necessary to resize the existing vent
line and chimney to prevent oversizing problems for the
other remaining appliances(s). See applicable codes
and Venting and Combustion Air Check in Gas Vent
Installation section.
Failure to properly vent this furnace or other appliances
can result in death, personal injury and/or property
damage.
Location and Clearances
If furnace is a replacement, it is usually best to install the furnace
where the old one was. Choose the location or evaluate the exist-
ing location based upon the minimum clearance and furnace di-
mensions (Figure 1, Figure 2 or Figure 3).
CAUTION
Do NOT operate furnace in a corrosive atmosphere contain-
ing chlorine, fluorine or any other damaging chemicals. Refer
to Combustion & Ventilation Air section, Contaminated Com-
bustion Air.
Dimensions and Clearances (NTV6NNE)
@
30" rain.
25-22-28
MINIMUM CLEARANCES TO
COMBUSTIBLE MATERIALS FOR ALL UNITS
REAR 0
FRONT 3"
Recommended For Service 30"
ALL SIDES Of SUPPLY PLENUM 1"
SIDES 0
VENT
Single Wall Vent 6"
Type B-1 Double Wall Vent 1"
TOP OF FURNACE 1"
NOTE: Evaporator "A" coil drain pan dimensions ma
vary from furnace duct opening size. Always consul
evaporator specifications for duct size requirements
Unit is designed for bottom return or side return.
Return air through back of unit is NOT allowed.
DIMENSIONAL INFORMATION
Unit Capacity
Electrical Connections
Cabinet
BC
15112 28112
19118 28112
223/4 28112
A
050FBI050BI2 40
075GF/075F14 40
100KJ & 125KJ 40
100J20& 125J20
ALL DIMENSIONS IN INCHES
Top Left/Right Side Low Volt
DEDERP
1112 11/2 11/2 1112 41/2 175116
11/2 11/2 11/2 11/2 41/2 175116
1112 11/2 11/2 1112 41/2 175116
Supply Air
O N
18112 14
181/2 175/8
18112 21114
ReturnAir
Bottom Side
F G J H
23118 12518 22112 12114
231/8 143/4 22112 14112
23118 18314 22112 14112
GasConnections
RightSide LeftSide
M K LK
237/8 28114 26 281I
23718 28114 26 281/
23718 281/4 26 281I
_] 441 O1 201602
Dimensions and Clearances (NTP6/TNE)
@
Illllllll0
30" rain.
25-22-28
MINIMUM CLEARANCES TO
COMBUSTIBLE MATERIALS FOR ALL UNITS
REAR 0
FRONT 3"
Recommended for Service 30"
ALL SIDES Of SUPPLY PLENUM 1"
SIDES 0
VENT
Single Wall Vent 6"
Type B-1 Double Wall Vent 1"
TOP OF FURNACE 1"
NOTE: Evaporator "A" coil drain pan dimensions
may vary from furnace duct opening size, Always
consult evaporator specifications for duct size re-
quirements.
Unit is designed for bottom return or side return.
Return air through back of unit is NOT allowed.
DIMENSIONAL INFORMATION
Unit Capacity Cabinet
ABC
40 15112 28112
ElectricalConnections
Top Left/Right Side Low Volt
D E D E R P
11/2 11/2 11/2 11/2 41/2 178116
Supply Air
ON
18112 14
ReturnAir
Bottom Side
F G JH
23118 12818 22112 12114
Gas Connections
RightSide Left Side
M K L K
23718 28114 26 281/
NTP6050FB
TNE050BI2
NTP6075GF
TNEO75FI4 40 19118 28112 11/2 11/2 11/2 11/2 41/2 178116 18112 17518 23118 14314 22112 14112 23718 28114 26 281/
NTP6100GF
TNE100F14
NTP6100HKJ
TNE100J20 40 223/4 28112 11/2 11/2 11/2 11/2 41/2 178116 181/2 211/4 231/8 183/4 22112 14112 237/8 281/4 26 281/
NTP6125KJ
TNE125J20
ALL DIMENSIONS IN INCHES
441 O1 2016 02 [_
Dimensions and Clearances (NDP6/TDE)
....
c_ B_" 37/8
30" rain.
MINIMUM CLEARANCES TO
COMBUSTIBLE MATERIALS FOR ALL UNITS
REAR 0
FRONT 3"
Recommended For Service 30"
ALL SIDES Of SUPPLY PLENUM 1"
SIDES 0
VENT
Single Wall Vent 6"
Type B-1 Double Wall Vent 1"
TOP OF FURNACE 1"
25-21-47b
DIMENSIONAL INFORMATION
Unit
Dimensions
Cabinet
A
40
40
40
Electrical Connections
B C
151/2 28112
19116 281/2
22314 28112
Top
DE
11/2 11/2
11/2 1112
1112 11/2
Left Side
DERight
(F)
Low Voltage
(G) (F)
NDP6050/O75FB 15/8 11/2 315116 253/4 313116
TDEOSO/O75B12
NDP61OOHF 1518 11/2 315/16 175/6 313116
TDE1OOF16
NDP6125KJ 15/8 1112 315116 211/4 313/16
TDE125J20
Left
(G)
24314
25314
25314
GasConnections Return Flue
Unit Dimensions J K LMNP R
NDP6050/O75FB 91/2 261116 23718 14 18112 37/8 51/4
TDEO5O/O75B12
NDP610OHF 9112 261116 237/8 175i6 181i2 55116 51/4
TDE1OOF16
NDP6125KJ 91/2 261116 237/8 211i4 181/2 71/2 5114
TDE125J20
ALL DIMENSIONS IN INCHES
Supply
H I
14 165/6
17518 165/6
211i4 16516
Installation Requirements
1. Install furnace level.
2. Install furnace as centralized as practical with respect to the
heat distribution system.
3. Install the vent pipes as short as practical. (See Gas Vent
Installation section).
4. Do NOT install furnace directly on carpeting, tile or other
combustible material other than wood flooring.
5. Maintain clearance for fire safety and servicing. A front
clearance of 30" is minimum for access to the burner, con-
trols and filter.
Fire Hazard.
Place furnace on noncombustible cement board or sheet
metal on downflow applications.
Failure to install unit on noncombustible cement board or
sheet metal can result in death and/or personal injury
and/or property damage.
6. Use a raised base if the floor is damp or wet at times.
441 O1 201602
7. Residentialgarageinstallationsrequire:
•Burners and ignition sources installed at least 18" (457mm)
above the floor.
• Furnace must be located or physically protected from pos-
sible damage by a vehicle.
Horizontal Furnace Installation
Typical Horizontal Installation
IMPORTANT
NOTE: Inspect unit rating plate to be certain model number begins
with "NTV6", "NTP6", "VNE" or "TNE". This identifies unit as
horizontally mountable. If unit does NOT bear this designation,
you may NOT mount this unit horizontally. Horizontal furnace
may not be mounted on its back.
If you purchased a horizontally mountable furnace, it can be
installed horizontally in an attic, basement, crawl space, alcove, or
suspended from a ceiling in a basement or utility room in either a
right or left airflow position. See Figure 4.
The following minimum clearances to combustibles MUST be
maintained between the furnace and adjacent construction, as
shown in Figure 4. ONLY the corner of the cabinet is allowed to
contact the rafters. All other clearances should be observed as
shown in Figure 1, Figure 2, or Figure 3.
If the furnace is to be suspended from the floor joists in a crawl
space or the rafters in an attic, it is necessary to use steel pipe
straps or an angle iron frame to attach the furnace. These straps
should be attached to the furnace with sheet metal screws and to
the rafters or joists with bolts. The preferred method is to use an
angle iron frame bolted to the rafters or joists.
Thirty inches (30") is recommended between the front of the fur-
nace and adjacent construction or other appliances. This should
be maintained for service clearance.
Keep all insulating materials clear from Iouvered door. Insulating
materials may be combustible.
It is recommended for further fire protection that cement board or
sheet metal is placed between the furnace and the combustible
wood floor and extend 12" (300mm) beyond the front of the fur-
nace louver door. (This is a recommendation only, not a require-
ment).
This furnace MUST NOT be installed directly on carpeting or tile
or other combustible material other than wood flooring or sup-
ports.
3. Combustion & Ventilation Air
Poison carbon monoxide gas hazard.
Use methods described here to provide combustion and
ventilation air.
Failure to provide adequate combustion and ventilation
air can result in death and/or personal injury.
Furnaces require ventilation openings to provide sufficient air for
proper combustion and ventilation of flue gases. All duct or open-
ings for su pplying combustion and ventilation air must comply with
the gas codes, or in the absence of local codes, the applicable na-
tional codes.
When the installation is complete, check that all appliances have
adequate combustion air and are venting properly. See Venting
And Combustion Air Check in Section 4 of this manual.
• Furnaces installed near chemical storage areas.
• Permanent wave solutions for hair.
• Chlorinated waxes and cleaners.
• Chlorine based swimming pool chemicals.
• Water softening chemicals.
• De-icing salts or chemicals.
• Carbon tetrachloride.
• Halogen type refrigerants.
• Cleaning solvents (such as perchloroethylene).
• Printing inks, paint removers, varnishes, etc..
• Hydrochloric acid.
• Sulfuric Acid.
• Solvent cements and glues.
• Antistatic fabric softeners for clothes dryers.
• Masonry acid washing materials.
Contaminated Combustion Air
Installations in certain areas or types of structures will increase the
exposure to chemicals or halogens that may harm the furnace.
These instances must use only outside air for combustion.
The following areas or types of structures may contain or have ex-
posure to the substances listed below. The installation must be
evaluated carefully as it may be necessary to provide outside air
for combustion.
• Commercial buildings.
• Buildings with indoor pools.
• Furnaces installed in laundry rooms.
• Furnaces installed in hobby or craft rooms.
441 01 2016 02
Confined Space Installation
NOTE: A confined space is defined as an area with less than 50
cubic feet(1.4m 3) per 1,000 BTUH input rating for all gas ap-
pliances installed in the area.
Air Openings and Connecting Ducts
1. Total input rating for all gas appliances MUST be consid-
ered when determining free area of openings.
2. Connect ducts or openings directly to outside.
3. When screens are used to cover openings, the openings
MUST be no smaller than 1/4" (6ram) mesh.
4. The minimum dimension of rectangular air ducts MUST
NOT be less than 3" (75ram).
5. Whensizinggrilleorlouver,usethefreeareaofopening.If
freeareaisNOTstampedormarkedongrillorlouver,as-
sumea20%freeareaforwoodand60%formetal.
2. Figure 5 illustrates how to provide combustion and ventila-
tion air. A minimum of two permanent openings, one inlet
and one outlet, are required.
Requirements 3.
1. Provide confined space with sufficient air for proper com-
bustion and ventilation of flue gases using horizontal or ver-
tical ducts or openings. 4. Size openings and ducts per Table 1.
Outside Air (This is ONLY a guide. Subject to codes of country having jurisdiction.)
One opening MUST be within 12" of the floor and the se-
cond opening within 12" of the ceiling.
ThisinstallationNOTapprovedin Canada
,GableVent
GasVent
(1) .d
SoffitVent
Inlet
Air (1
MinimumOne Inlet and OneOutlet Air Supplyis Required
May be in andCombination Shown
InletAir OpeningMust be Within12"(300ram)of floor
OutletAir OpeningMust be Within12"(300mm)of ceiling
(1) 1SquareInch(6cmz) per 4000BTUH
(2) 1SquareInch(6cmz) per 2000BTUH
/
letAir (1) HI
Soffit Vent
Outlet
Air (1)
Inlet
Air (2)
Inlet
Air (1)
Furnace G_
[[_J Outlet
Air (2)
E_:_,_r._ TInlet
Air (2)
5. Horizontal duct openings require I square inch of free area
per 2,000 BTU H of combined input for all gas appliances in
area (see Table 1).
6. Vertical duct openings or openings directly to outside re-
quire 1 square inch of free area per 4,000 BTUH for com-
bined input of all gas appliances in area (see Table 1).
One permanent opening, commencing within 12" of the top of the
enclosure, shall be permitted where the equipment has clear-
ances of at least 1" from the sides and back and 6" (16 cm.) from
the front of the appliance. The opening shall directly communicate
with the outdoors or shall communicate through a vertical or hori-
zontal duct to the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors, and shall have a minimum free
area of:
• 1 sq. in per 3000 Btu per hr of the total input rating of all
equipment located in the enclosure, and
• Not less than the sum of the areas of all vent connectors in
the confined space.
Unconfined Space Installation
FreeArea
MinimumFree Area Requiredfor EachOpening
BTUH Rd
Input HorizontalDuct VerticalDuct or openings Duct
to outside (sq,in.
Rating (sq.in,i2,000BTUH) (sq.in./4,000BTUH) /4,000
BTUH)
50,000 25 sq. in, 12.5sq, in. 4"
75,000 37.5 sq, in, 18.75sq. in, 5"
100,000 50 sq, in. 25 sq. in. 6"
125,000 62,5 sq. in. 31.25 sq. in, 7"
EXAMPLE: Determining Free Area
Furnace Water Heater Total Input
100,000 + 30,000 = (130,000 + 4,000) = 32.5 Sq. In. Vertical
Furnace Water Heater Total Input
100,000 + 30,000 = (130,000 + 2,000) = 65 Sq. In. Horizontal
An unconfined space is defined as an area having a minimum vol-
ume of 50 cubic feet per 1,000 BTUH total input rating for all gas
appliances in area.
Adjoining rooms can be considered part of an unconfined area if
there are no doors between rooms.
Poison carbon monoxide gas hazard.
Most homes will require additional air.
An unconfined space or homes with tight construction
may not have adequate air infiltration for proper
combustion and ventilation of flue gases.
Failure to supply additional air by means of ventilation
grilles or ducts could result in death and/or personal
injury.
An attic or crawl space may be considered an unconfined space
provided there are adequate ventilation openings directly to out-
doors. Openings MUST remain open and NOT have any means of
being closed off. Ventilation openings to outdoors MUST be at
least I square inch of free area per 4,000 BTU H oftotal input rating
for all gas appliances in area.
In unconfined spaces, infiltration should be adequate to provide
air for combustion, ventilation and dilution of flue gases. However,
in buildings with unusually tight construction, additional air MUST
be provided using the methods described in section titled Con-
fined Space Installation:
441 01 201602
Unusuallytightconstructionisdefinedas:Constructionwith
1 Wallsandceilingsexposedtotheoutsidehaveacontinu-
ous,sealedvaporbarrier.Openingsaregasketedorsealed
and
2 Doorsandopenablewindowsareweatherstrippedand
3. Otheropeningsarecaulkedorsealed.Theseincludejoints
aroundwindowanddoorframes,betweensoleplatesand
floors,betweenwall-ceilingjoints,betweenwallpanels,at
penetrationsforplumbing,electricalandgaslines,etc.
4. Gas Vent Installation
Poison carbon monoxide gas, fire and explosion
hazard.
Ventilation Air
Some provincial codes and local municipalities require ventilation
or make-up air be brought into the conditioned space as replace-
ment air. Whichever method is used, the mixed return air tempera-
ture across the heat exchanger MUST not fall below 60°F or flue
gases will condense in the heat exchanger. This will shorten the
life of the heat exchanger and possibly void your warranty.
Read and follow all instructions in this section.
Failure to properly vent this furnace can result in death,
personal injury and/or property damage.
Install the vent in compliance with codes of the country having ju-
risdiction, local codes or ordinances and these instructions.
Poison carbon monoxide gas hazard.
If this furnace is replacing a previously common-vented
furnace, it may be necessary to resize the existing
chimney liner or vent to prevent over sizing problems for
the other remaining appliances(s). See codes of country
having jurisdiction.
Failure to properly vent this furnace or other appliances
can result in death, personal injury and/or property
damage.
These fan assisted combustion furnaces have been classified as
Category [ appliances which means that they MUST operate with
a negative vent pressure.
Category I Safe Venting Requirements
NOTE: The following instructions comply with the United States
National Fuel Gas Code. Based on the highest input rate on the
furnace rating plate.
If a Category [vent passes through an attic, any concealed
space or floor, use ONLY Type B or Type L double wall vent
pipe. If vent pipe passes through interior wall, use type B
vent pipe with ventilated thimble ONLY.
2. Do NOT vent furnace into any chimney serving an open
fireplace or solid fuel burning appliance.
3. Use the same diameter Category [connector or pipe as
permitted by the United States National Fuel Gas Code
venting tables.
4. Keep vertical Category [vent pipe or vent connector runs as
short and direct as possible.
5. Vertical outdoor runs of type B or ANY single wall vent pipe
below the roof line are NOT permitted.
6. Slope all horizontal runs up away from furnace a minimum
of 1/4" per foot.
7. Support all horizontal vent pipe every 6' using proper
clamps and metal straps.
8. Check existing gas vent or chimney to ensure they meet
clearances and local codes.
The furnace MUST be connected to a factory built chimney
or vent complying with a recognized standard. Venting into
a masonry or concrete chimney is only permitted as
outlined in the United States National Fuel Gas Code
venting tables or Masonry Chimney section in these
instructions.
441 01 2016 02
Venting and Combustion Air Check
NOTE: If this installation removes an existing furnace from a vent-
ing system serving one or more other appliances, and to make
sure there is adequate combustion air for all appliances, MAKE
THE FOLLOWING CHECK.
1,
2.
Seal any unused openings in the venting system.
Visuallyinspect the venting system for proper size and hori-
zontal pitch to ensure there is no blockage or restriction,
leakage, corrosion or other deficiencies which could cause
an unsafe condition.
3. Insofar as is practical, close all doors and windows and all
doors between the space in which the appliance(s) remain-
ing connected to the venting system are located and other
spaces of the building.
4. Turn on clothes dryers and any appliance not connected to
the venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will operate at
maximum speed. Do not operate a summer exhaust fan.
Close fireplace dampers.
5. Follow the lighting instructions for each appliance being in-
spected. Adjust thermostat so appliance(s) will operate
continuously.
6. Allow 5 minutes of main burner operation, then check for
spillage at the draft hood relief opening of each appliance.
Use the flame of a match or candle (Figure 6).
Vent Check
Vent Pipe Draft Hood
Typical Gas
Water Heater [1 I _--
Match
7. After it has been determined that each appliance vents
properly, return doors, windows, appliances etc. to their
normal condition.
8. If improper venting is observed, the cause MUST be cor-
rected.
NOTE: If flame pulls towards draft hood, this indicates sufficient
infiltration air.
Venting to Existing Masonry Chimney
NOTE: The tables and notes referred to below are found in the
most recent printing of the United States National Fuel Gas
Code venting tables.
Use the United States National Fuel Gas Code or N FGC Tables to
size the chimney or vent. Dedicated venting of one fan assisted
furnace into any masonry chimney is restricted. The chimney
must first be lined with either type B vent sized in accordance with
tables 1 or 2 or a listed single wall, metal lining system, sized in
accordance with the vent tables.
Listed, corrugated metallic chimney liner systems in masonry
chimneys shall be sized by using United States National Fuel
Gas Code tables for dedicated venting and United States Na-
tional Fuel Gas Code tables for common venting with the maxi-
mum capacity reduced by 20% (0.80 X maximum capacity) and
the minimum capacity as shown in the applicable table. Corru-
gated metal vent systems installed with bends or offsets require
additional reduction of 10% of the vent capacity for each 90 ° el-
bow.
NOTE: Two(2) 45° elbows are equivalent to one (1) 90° elbow.
Combined Venting into a Masonry Chimney
Venting into a masonry or concrete chimney is only per-
mitted as outlined in the United States National Fuel Gas
Code venting tables. Follow all safe venting requirements.
5. Horizontal Venting
Category ] Furnaces With External Power
Venters
In order to maintain a Category ]classification of fan assisted fur-
naces when vented horizontally with sidewall termination, a power
venter is REQUIRED to maintain a negative pressure in the vent-
ing system. Please consult the Fields Controls Co. or Tjernlund
Products, Inc. for power Venters certified for use with our fur-
Races.
Vent Termination
Venting Through a Non-Combustible and
Combustible Wall
CAUTION
It is the responsibility of the installer to properly termi-
nate the vent and provide adequate shielding. This is
essential in order to avoid water/ice damage to build-
ing, shrubs and walk-ways.
Consult External Power Venter manufacturer instructions.
6. Gas Supply and Piping
Poison carbon monoxide gas hazard.
Models designated for Natural Gas are to be used with
Natural Gas ONLY, unless properly converted to use
with LP gas.
Failure to follow these instructions can result in death,
personal injury and/or property damage.
Gas Supply Requirements
•Use only the Type of gas approved for this furnace. See rat-
ing plate for approved gas type.
• Gas input must not exceed the rated input shown on the rat-
ing plate. Overfiring will result in failure of heat exchanger
and cause dangerous operation.
• Do not allow minimum supply pressure to vary downward.
Doing so will decrease input to furnace. Refer to Table 2for
Gas supply and manifold pressures.
Gas Pressures
•________________________________________________________________________________________________
Gas Supply Pressure
Type Recom- Max. Min.
mended
Natural 7" 14" 4.5"
(1.7 kPa) (3.5 kPa) (1.1 kPa)
Propane 11" 14" 11"
(2.7 kPa) (3.5 kPa) (2.7 kPa)
Manifold
Pressure
High Low
3.5" 1.7"
(0.9 (0.42
kPa) kPa)
10" 4.3"
(2.5 (1.07
kPa) kPa)
Manifold Gas Pressure Adjustments (Hi& Lo
Fire)
NOTE: Gas supply pressure MUST be within minimum and maxi-
mum values listed on rating plate. Pressures are usually set by
gas suppliers.
Make adjustment to manifold pressure with burners operating and
combustion air box cover removed.
1. Remove combustion air box cover.
2. Connect manometer to the tapped opening on the outlet
side of gas valve or on the manifold pipe. Use a manometer
with a 0 to 12" minimum water column range.
3. Turn gas ON. Operate the furnace on high fire by using a
jumper wire on the R to Wl &W2 thermostat connections
on the fan board.
_] 441 01 2016 02
4. Removetheadjustmentcoveronthegasvalve.Turnad-
justingscrewcounterclockwisetodecreasethemanifold
pressureandclockwisetoincrease.SeeFigure29.
5. Setthe manifold pressure to value shown in Table 2,
Table 3 or Table 4.
6. Operate the furnace on low fire by using a jumper wire on
the Rto Wl thermostat connections on the fan board.
Note: The fourth (4th) DIP switch should be in the on posi-
tion to set the low fire manifold pressure. (See wiring dia-
gram)
7. Repeat steps 4 and 5 for low fire operation.
8. When the manifold pressures are properly set, replace the
adjustment screw covers on the gas valve.
9. Removethejumper wires from the thermostat connections
on the fan board. Remove manometer and replace plug in
manifold.
10. Replace combustion air box cover.
11. Return fourth (4th) DIP switch to previous setting.
Natural Gas Input Rating Check
NOTE: The gas meter can be used to measure input to furnace.
Rating is based on a natural gas BTU content of 1,000 BTU's per
cubic meter. Check with gas supplier for actual BTU content.
1. Make sure combustion air box cover is in place and closed
before performing the following steps.
2. Turn OFF gas supply to all appliances and start furnace.
Use jumper wire on R to W1 and W2 for Hi fire.
3. Time how many seconds it takes the smallest dial on the
gas meter to make one complete revolution. Refer to Ex-
ample.
4. Repeat steps 2 and 3 with jumper wire on R to Wl for low
fire. NOTE: Fourth (4th) DIP switch must be in on position.
(See furnace wiring diagram). Return fourth (4th) DIP
switch to previous setting after check.
Example
NaturaIGas No. of Seconds TimePer Cubic | BTU Per
BTUContent Per Hour Foot inSeconds ] Hour
1,000 3,600 48 75,000
1,000 x 3,600 + 48 = 75,000 BTUH
NOTE: If meter uses a 2 cubic foot dial, divide results (seconds) by
two.
5. Relight all appliances and ensure all pilots are operating.
Orifice Sizing
NOTE: Factory sized orifices for natural and LP gas are listed in
the furnace Technical Support manual.
Ensure furnace is equipped with the correct main burner orifices.
Refer to Table 3 &Table 4 for correct orifice size for a given heat-
ing value and specific gravity for natural and propane gas.
Operation Above 2000' Altitude
Fire, Explosion, Poison carbon monoxide gas hazard.
This conversion shall be done by a qualified service
agency in accordance with the Manufacturer's
instructions and all applicable codes and require-
ments, or in the absence of local codes, the applicable
national codes.
Failure to follow these instructions exactly can result in
death, personal injury and/or property damage.
These units may be used at full input rating when installed at alti-
tudes up to 2000'. When installed above 2000', the high fire input
must be decreased 2% (natural) or 4% (LP) for each 1000' above
sea level. This may be accomplished by a simple adjustment of
manifold pressure or an orifice change, or a combination of a pres-
sure adjustment and an orifice change. The changes required de-
pend on the installation altitude and the heating value of the fuel.
Table 3 & Table 4 showthe proper furnace manifold pressure and
gas orifice size to achieve proper performance based on elevation
above sea level for both natural gas and propane.
To use the natural gas table, first consult your local gas utility for
the heating value of the gas supply. Select the heating value on the
vertical border and follow across the table until the appropriate
elevation for the installation is reached. The first value in the box at
the intersection of the heating value and elevation will be the man-
ifold pressure required. If a gas orifice change is also required, the
box is shaded. The required orifice size is shown at the bottom of
the table.
Sea Level
High Altitude Input Rate = Nameplate x (Multiplier)
Input Rate
Elevation
2000'-2999'
3000'-3999'
4000'-4999'
5000'-5999'
6000'-6999'
7000'-7999'
High Altitude Multiplier
Natural LP Gas
0.96 0.92
0.94 0.88
0.92 0.84
0.90 0.80
0.88 0.76
0.86 0.72
441 01 2016 02 [_
MANIFOLDPRESSUREAND ORIFICESIZE FORHIGH ALTITUDEAPPLICATIONS
Table3 NATURAL GAS
MEAN ELEVATION FEET ABOVE SEA LEVEL
HEATING VALUE 3000 to 4000 to 5000 to
BTU/CU. FT, 3999 (" wc) 4999 (" wc) 5999 (" wc)
0to 1999 2000 to
("wc) 2999("wc)
Hi Lo Hi Lo Hi Lo Hi Lo Hi Lo
800 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7
850 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7
900 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7
950 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.3 1.6
1000 3.5 1.7 3.4 1.7 3.3 1.6 3.2 1.5 3.0 1.5
1050 3.2 1.6 3.1 1.5 3.0 1.5 2.9 1.4 2.7 1.3
1100 2.9 1.4 2.8 1.4 2.7 1.3 2.6 1.3 2.5 1.2
Orifice Size #42 #42 #42 #42 #42
Table 4
HEATING VALUE
BTU/CU, FT.
2500
Orifice Size
6000 to 7000 to
6999 (" wc) 8000 (" wc)
Hi Lo Hi Lo
3.5 1.7 3.5 1.7
3.5 1.7 3.5 1.7
3.5 1.7 3.4 1.7
3.2 1.6 3.1 1.5
2.9 1.4 2.8 1.4
2.6 1.3 2.5 1.2
2.4 1.2 2.3 1.1
#42 #42
LPG or PROPANE
0 to 1999
(" wc)
Hi I Lo10.0 4.9
#54
2000 to
2999 (" wc)
Hi I Lo10.0 4.9
#54
MEAN ELEVATION FEET ABOVE SEA LEVEL
3000 to 4000 to 5000 to
3999 (" wc) 4999 (" wc) 5999 (" wc)
Hi I Lo9.4 4.6
#54 #55 #55
6000 to
6999 (" wc)
7000 to
8000 ("wc)
#55 #55
NOTE: NATURAL GAS DATA BASED ON 0.60 SPECIFIC GRAVITY. PROPANE DATA BASED ON 1.53 SPECIFIC GRAVITY. FOR
FUELS WITH DIFFERENT SPECIFIC GRAVITY CONSULT THE LATEST EDITION OF THE NATIONAL FUEL GAS CODE ANSI
Z223.1 and CAN B149.
Changing Orifices
1. After disconnecting power and gas supply to the furnace,
remove the access door, exposing the burner compart-
ment.
a. Remove the five (5) screws holding the burner box cover
to expose the manifold and burners. (Figure 7 or Figure 8)
2. Disconnect gas line and pilot tubing from gas valve so man-
ifold can be removed.
3. Disconnect wiring at gas valve. Be sure to note the proper
location of any and all electrical wiring disconnected.
4. Remove the four (4) screws holding the manifold and gas
valve to the manifold supports. Do not discard any screws.
See (Figure 7 or Figure 8).
Manifold (Upflow/Horizontal)
25-22-32
Manifold (Downflow)
25-22-38
5. Carefully remove the manifold assembly.
6. Remove the orifices from the manifold and replace them
with proper sized orifices. See Figure 9.
7. Tighten orifices so they are seated and gas tight. See
Figure 9.
_] 441 O1 2016 02
Changing Orifices
Measure from face of orifice
--( -{, j to the back side of the
_,,,",,,,_ mani fold.
8. Reassemble all parts in reverse order as removed. Be sure
to engage the main burner orifices in the proper opening in
the burners.
9. After reassembling, turn gas on and check all joints for gas
leaks using a soapy solution. All leaks must be repaired im-
mediately.
Gas Piping Requirements
1. Install gas piping in accordance with local codes, or in the
absence of local codes, the applicable national codes.
2. It is recommended that a manual shutoff valve be installed
in the gas supply line outside the unit. Locate valve as close
to the furnace as possible where it is readily accessible. Re-
fer to Figure 10.
Typical Gas Piping
25-22-31
3. Use black iron or steel pipe and fittings or other pipe ap-
proved by local code.
4. Use pipe thread compound which is resistant to natural and
LP gases.
5. Install a dripleg no less than 3" long totrap dirt and moisture
before it can enter gas valve.
6. Provide a 118" inch plug for test gauge connection immedi-
ately up stream of gas supply connection to furnace.
7. Use two pipe wrenches when making connections to pre-
vent gas valve from turning.
8. Flexible corrugated metal gas connector may NOT be used
inside the furnace or be secured or supported by the fur-
nace or ductwork.
9. Properly size gas pipe to handle combined appliance load
or run gas pipe directly from gas meter or LP gas regulator.
10. Install correct pipe size for run length and furnace rating.
11. Measure pipe length from gas meter or LP second stage
regulator.
Fire or explosion hazard.
Gas connector must be properly installed, cannot go
through the side of the furnace, and can not be used
inside the furnace.
Failure to properly install gas connector can result in
death, bodily injury and/or property damage.
Additional LP Piping Requirements
•Have a licensed LP gas dealer make all connections at stor-
age tank and check all connections from tank to furnace.
• If copper tubing is used, it MUST comply with limitation set
in Local Codes, or in the absence of local codes, the gas
codes of the country having jurisdiction. See Appendix.
•Two-stage regulation of LP gas is recommended.
Fire or explosion hazard.
Liquid petroleum (LP) gas is heavier than air and will
settle and remain in low areas and open depressions.
Thoroughly ventilate area and dissipate gas. Do NOT
use a match or open fla me to test for lea ks, or attempt to
start up furnace before thoroughly ventilating area.
An open flame or spark can result in death, personal
injury and/or property damage.
Final Check
• Test all pipe for leaks.
• If orifices where changed, make sure they are checked for
leaks.
• During pressure testing of gas piping system, observe the
following:
a. If test pressure does not exceed 1/2" PSIG, isolate the
furnace by closing its individual manual shutoff valve.
b. If test pressure exceeds 1/2" PSIG, the furnace and its in-
dividual shutoff valve must be disconnected from the gas
supply system.
• To check for leaks apply soap suds or a liquid detergent to
each joint. Bubbles forming indicate a leak.
• Do not use an open flame totest for gas leaks. Fire or explo-
sion could occur.
• Correct even the smallest leak at once.
441 01 2016 02 [_
7. Electrical Wiring
Electrical shock hazard.
Turn OFF electrical power at fuse box or service panel
before making any electrical connections and ensure a
proper ground connection is made before connecting
line voltage.
Failure to do so can result in death, personal injury
and/or property damage.
Power Supply Wiring
The furnace MUST be electrically wired and grounded in accor-
dance with local codes, or in the absence of local codes, the appli-
cable national codes.
Field wiring connections must be made inside the furnace connec-
tion box. A suitable strain relief should be used at the point the
wires exit the furnace casing.
Copper conductors shall be used. Line voltage wires should be
sized for the input amps stated on the rating plate. Furnace must
be connected to its own separate circuit.
Thermostat
The 2-stage furnace control will operate with either a single stage
or a two stage heating thermostat and will provide 2-stage heating
operation. For single stage thermostat installations, the R and W
wires from the thermostat connect to the R and Wl connections
on the furnace control. Note: The fourth (4th) DIP switch should
be in the off position for the furnace to operate properly with a
single stage thermostat. Failure to change DIP switch with single
stage thermostat will result in Low Fire operation ONLY. (See wir-
ing diagram) During operation, the furnace will operate on low fire
for 12 minutes. If the heat request exists for more than 12 minutes,
the furnace will automatically shift to the high fire mode for the re-
maining duration of the heating cycle. For 2-stage thermostat
installations, the R, Wl and W2 wires from the thermostat connect
to the R, Wl and W2 connections on the furnace control. During
operation, the furnace will shift from low fire to high fire as re-
quested by the thermostat. The thermostat heat anticipator should
be adjusted to a .10 setting for both types of thermostats.
Thermostat location has an important effect on the operation of
the unit. Follow instructions included with thermostat for correct
mounting and wiring.
Low voltage connections to furnace must be made on terminal
board to fan control.
Optional Equipment
All wiring from furnace to optional equipment MUST conform to lo-
cal codes or, in the absence of local codes, the applicable national
codes. Install wiring in accordance with manufacturer's instruc-
tions.
Humidifier/Electronic Air Cleaner
The furnace is wired for 115 VAC humidifier and/or electronic air
cleaner connection.
CAUTION
Do NOT exceed 115V/0.8 amp. maximum current load
for both the EAC terminal and the HUM terminal com-
bined.
NOTE: The humidifier will be powered when the furnace is fired
and the circulating air blower comes on. The electronic air cleaner
will be powered anytime the thermostat calls for air movement.
However, the electronic air cleaner is NOT energized during con-
tinuous fan operation controlled by the electronic fan control.
Dehumidification (NTV6NNE)
The fan control is wired for 24 VAC normally open (N/O) dehumi-
distat connection. Connect dehumidistat to the Rterminal and the
1/4" male quick connect Y2 terminal on the fan control (See
Figure 14 and "Furnace Wiring Diagram3 A 20% reduction of
cooling airflow will occur when the Y2 dehumidistat terminal is en-
ergized during a call for cooling from the thermostat.
I
Figure 11 IElectrical Connections
I(NTV6/VNE)
NOTE: Control is ground sensitive.
NOTE: Junction Box can be mounted to either the left or right side.
115V= 60Hz.
Ground
_Lo*Vo_go
iTerminal Board _
2
_ "rh_no_tat
(_'_,F,_ TwoStage'
_Thermostat 1 Motor
Control
Variable Speed
Motor
25-23-11
_] 441 01 2016 02
Figure 12 Electrical Connections NTP6/TNE Fan Control
(Upflow/Horizontal)
NOTE: Control is ground sensitive.
NOTE: Junction Box can be mounted to either the left or right side.
Figure 13 Electrical Connections NDP6/TDE
(Downflow)
116V._=.
iv
25-22-60
The fan control is preset at the factory with an adjustable blower
ON delay of 30 seconds in the heating mode. The blower OFF tim-
ing is preset at 140 seconds. If desired, the fan ON delay and OFF
delay can be reset to obtain the longest delay times while still
maintaining comfort levels. See "Furnace Wiring Diagram".
NOTE: It is recommended to achieve maximum efficiency that the
fan control be set to turn on at 30 seconds after the burners light.
NOTE: For single stage thermostat operation the fourth (4th) DIP
switch must be in the off position. (See furnace wiring diagram and
Figure 14). Failure to change switch with single stage thermostat
will result in Lo fire operation ONLY.
Fan Timer Connections
_L I _/ /_ Dip
_,¢-k..-./_ _ Switch
I_ _, _ _ _See"Wiring
for switch
//_ _._ _,_, _ _L_.L_ settings
FUSE
441 01 2016 02 [_
8. Ductwork and Filter (NTV6/VNE &NTP6/TNE)
Poison carbon monoxide gas hazard.
Do NOT draw return air from inside a closet or utility
room where furnace is located. Return air duct MUST be
sealed to furnace casing.
Failure to properly seal duct can result in death and/or
personal injury.
Duct Connections
When a refrigeration coil is used in conjunction with this
unit, it must be installed on the discharge side of the unit to
avoid condensation on the heat exchanger.
If separate evaporator and blower unit is used, install good
sealing dampers for air flow control. Chilled air going
through the furnace could cause condensation and shorten
furnace life. Dampers (purchased locally) can be either au-
tomatic or manual. Manually operated dampers MUST be
equipped with a means to prevent furnace or air condition-
ing operation unless damper is in the full heat or cool posi-
tion.
This furnace may be installed in only a bottom or side return ap-
plication. Return air through the back of the unit is NOT allowed.
Side connections can be made by cutting out the embossed area
shown in Figure 15.
Cutting Side Return Air Opening
Starting
Hole
Bottom returns can be made by removing the knockout panel in
the furnace base. Do NOT remove knock-out except for a bottom
return.
Duct Design (NTV6NNE & NTP6/TTNE)
Design and install air distribution system to comply with Air Condi-
tioning Contractors of America manuals or other approved meth-
ods that conform to local codes and good trade practices.
When the furnace is located in an area near or adjacent to the liv-
ing area, the system should be carefully designed with returns to
minimize noise transmission through the return air grille. Any
blower moving a high volume of air will produce audible noise
which could be objectionable when the unit is located very close to
a living area. It is often advisable to routethe return air ducts under
the floor or through the attic.
• Refer to furnace Technical Support Manual (Blower Data)
for air flow information.
• Size ductwork to handle air flow for heating and air condi-
tioning.
Duct Installation Requirements
• When furnace supply ducts carry air outside furnace area,
seal return air duct to furnace casing and terminate duct
outside furnace space.
Poison carbon monoxide gas hazard.
Cool air passing over heat exchanger can cause
condensate to form resulting in heat exchanger failure.
This could result in death and/or personal injury.
• Installation of locking-type dampers are recommended in
all branches, or in individual ducts to balance system's air
flow.
• Non-combustible, flexible duct connectors are recom-
mended for return and supply connections to furnace.
• If air return grille is located close to the fan inlet, install at
least one, 90 ° air turn between fan and inlet grille to reduce
noise.
• Ductwork installed in attic, or exposed to outside tempera-
tures require 2" of insulation with outdoor type vapor barri-
er.
• Ductwork installed in an indoor unconditioned space re-
quires a minimum of 1" of insulation with indoor type vapor
barrier.
Inspection Panel on some models
A removal access panel should be provided in the outlet duct
when the furnace is installed without a cooling coil. This will allow
smoke or reflected light to be observable inside the casing to indi-
cate the presence of leaks in the heat exchanger. This access cov-
er shall be attached in such a manner as to prevent air leaks.
Filters
A filter MUST be used. Filters may not be supplied with all models,
but can be purchased from your dealer.
The furnaces, with 1600 or less CFM rating, are supplied with a
16" x 25" high velocity filter and rack. On these models, the sup-
plied filter rack may be mounted internally for bottom return or ex-
ternally for side return.
The furnaces with greater than 1600 CFM requires that both left
and right side returns are used in side return applications. Two 16"
x 25" high velocity filters and racks are provided with furnace. Fil-
ter racks must be mounted externally. If return air must be on one
side only, an optional 20"x 25" filter standoff rack kits can be used.
(See Figure 16) For bottom return, an optional 20" x 25" filter rack
kit can be mounted internally.
_] 441 01 2016 02
iiiiiiiiiiiiiiiiiiiiiiiill!!!!!!!iilli! iili!i iil¸ii!!!iiiiiiiiii!i ii!!
Optional Duct Standoff
20 x 25 Optional
Filter Rack
Filters Installed on Two Sides
Filter Filter
Filters Rack Installation
Side Return
Center the filter rack on the side panel, flush with the bottom edge
of the furnace. Mark the fastening holes. Drill the fastening holes in
the side panel and fasten the filter rack in place with sheet metal
screws. See Figure 17 & Figure 18.
CAUTION
If filters are only suitable for heating application, advise
homeowner that filter size may need to be increased if air
conditioning is added.
Side Return Filter Rack
Filter
Bottom Return
When installing a bottom mounted filter rack, slide the two side fil-
ter clips to the back of the furnace BEFORE installing. This will al-
low the rack to clear the front raised edge of the furnace. Insert
rack into side clips first and push rack back until it is fully engaged
into back clip. When rack is in place, slide clips back into place
midway on rack as shown in Figure 19.
Bottom Mounted Filter Rack
AW3192
Slide filter clips towards back before removing
=
Sub-Bases for Combustible Floors -Furnace Only
The Subbase for Combustible Floors MUST be used when a
downflow furnace is set on combustible material even when the
furnace is installed on a coil box (cased coil).
NOTE: Supply opening is 37/8" from the rear of the furnace.
Therefore maintain a 37/8" clearance from a wall behind the fur-
nace (where applicable).
1. Cut the opening in the floor according to Table 5. The hole in
the floor must be cut to the dimensions listed in Table 5 since
the base is equipped with locating tabs that center the base
over the opening.
Ductwork and Filter (Downflow/Horizontal) on NDP6/TDE
The opening in the base is 11/4"(32mm) shorter and 11/8"(29mm)
narrower than the minimum required size of the opening in the
floor. This is done to maintain a 1" clearance between the floor and
the plenum.
2. Fabricate the plenum to the dimensions given in Table 5.
Note that the dimensions given are outside dimensions.
441 01 2016 02 [_
Table 5
sub-base for Com-
bustible Floors
Part Number
(Furnace Only)
NAHH001SB
NAHH002SB
NAHH003SB
sub=base for
Cased Coil
NAHH004SB
NAHH005SB
NAHH006SB
Sub-bases for Combustible Floors Dimensions
N _
1511116
195/16
2215116
1511/16
195/16
2215/16
sub-base for Combustible
Floor Dimensions
J* K**
283/4 149/16
283/4 183/16
283/4 2113/16
209/16 149/16
209/16 183/16
209/16 2113/16
16
16
16
16
16
16
Outside Dimension
_ Base Spacer Side To Side
3. Set the base over the opening in the floor, centering the open- 3.
ing in the base over the opening in the floor. Fasten the base
to the floor with screws or nails. See Figure 20 and
Figure 22.
4,
Opening In Floor
M N
16114 14518
16114 18114
16114 21 t/8
161/4 145/8
161/4 181/4
161/4 21 t/8
Figure 20 Exploded View of Sub-Base
for Furnace ONLY
Drop the plenum through the opening in the base. The flange
of the plenum should rest on top of the combustible floor
base.
Sub-base for Combustible Floors- Downflow Coil
Box
The Subbase for Combustible Floors MUST be used when a
downflow furnace, used with a downflowcoilbox, is set on com-
bustible flooring.
NOTE: Supply opening is 37/8" from the rear of the furnace.
Therefore maintain a 37/8 ', clearance from wall (where applica-
ble).
1. Cut the opening in the floor according to Table 6. The hole in
the floor must be cut to the dimensions listed in Table 6 since
the base is equipped with locating tabs that center the base
over the opening.
The opening in the base is 11/4"(32mm) shorter and 1 1/8" (29mm)
narrower than the recommended size of the opening in the floor.
This is done to provide a 1" clearance between the floor and the
plenum.
2. Fabricate the plenum to the dimensions given in Table 6.
Note that the dimensions given are outside dimensions.
Opening In
Base For Plenum
PR S
15 13112 15
15 17118 15
15 193/4 15
15 131/2 15
15 171/8 15
15 193/4 15
Typical Plenum
Dimensions
13112
17118
193/4
13112
17118
193/4
4, Drop the plenum through the opening in the base. The flange
of the plenum should rest on top of the combustible floor
base.
Setting the Base
Furnace
Subbase
Insulation
Wood Floor
This subbase for combustible floors has been designed so that the
height of the sub-base raises the downflow coil off the floor to al-
low easy installation of the condensate drain. See Figure 23.
441 01 201602
Exploded View of Base for
Downflow Cased Coil
25-21-46b
Figure 21 [
Set the base over the opening in the floor, centering the open-
ing in the base over the opening in the floor. Fasten the base
to the floor with screws or nails. See Figure 21 and
Figure 22.
Figure 23 Condensate Line Raised by Base Figure 24
25-20-52
Filter Rack Installation
25-21-05c
Non-Combustible Floor:
Set the furnace over the opening in the floor. If necessary, grout
around the base to seal air leaks between the base and the floor.
Filters:
The filters supplied with the furnace may be installed in the return
air plenum above the furnace. A filter rack is supplied with each
furnace. See Figure 24.
NOTE: The return air plenum MUST extend a sufficient height
above dimension "A" (Figure 25) to provide for the attachment of
a return air duct or grille above the filters.
NOTE: The furnace is provided with high velocity type filter(s).
The size, quantity, and type of filter supplied with the furnace will
handle the airflow required if central air conditioning is used with
the furnace.
2,
3
Insert end of filter rack with /4' (19ram) flange into slot in the
back of the unit. See Figure 24.
With filter rack pushed back, insert front end with 1/4" (6mm)
flange into position and push into front slot. with filter rack
pushed as far forward as it will go, bend 1/4" (6mm) flange and
3/4"(19mm) flange up 90 degrees. See Figure 24.
NOTE: Plenum must be fitted as close to the return air flange of the
unit as possible to eliminate any air bypassing the filters.
3. Filters can only be installed through the right hand side of the
unit blower opening. Slide filter into unit until it is in position to
be pushed up and over into place on the left hand side of unit.
See Figure 25.
4. Slide remaining filter into unit and up into place on left hand
side of unit. See Figure 25.
Figure 25 [ Filter Installation
T14"
(350mm)
25-21-05d
10. Checks and Adjustments
Startup
NOTE: Refer to startup procedures in the Users Information
ManuaL
441 01 2016 02
CAUTION
If any sparks, odors or unusual noises occur, immediately
shut OFF power to furnace. Check for wiring errors or ob-
struction to blower.
Gas Supply Pressure
Gas supply pressure should be within minimum and maximum
values listed on rating plate. Pressures are usually set by gas sup-
pliers.
(See L.P. Kit instruction manual for furnaces converted to L.R gas)
Adjust Pilot Burner
The furnace has a pilot flame to light the main burner. The flame
should surround 3/8" to 1/2" of the flame rod. See Figure 26. To ad-
just, remove cap from pilot adjusting screw on gas valve. Turn
screw counterclockwise to increase or clockwise to decrease
flame as required. Replace cap after adjusting screw.
Pilot Burner
Flame Rod
Hot Surface
/Igniter
10-11-65
1,
2,
Place thermometers in supply and return air registers as
close to furnace as possible, avoiding direct radiant heat
from heat exchangers.
Operate furnace on high fire for 10 minutes with all the reg-
isters and duct dampers open by using a jumper wire on R
to Wl and W2 thermostat connections on the fan board.
Note: The fourth (4th) DIP Switch should be in the on posi-
tion. (See furnace wiring diagram)
3. Take readings and compare with range specified on rating
plate.
4. If the temperature rise is not in the correct range, the blower
speed must be changed. A higher blower speed will lower
the temperature rise. A lower blower speed will increase the
temperature rise.
5. Repeat steps 2 thru 4 with the furnace operating on low fire
for 10 minutes by using a jumper wire on the R to W1 ther-
mostat connections on the fan board.
6, Remove the jumper wire after the adjustments are com-
plete. Return fourth (4th) to previous setting.
Changing Blower Speedon NTP6/TNE&
NDP6/TDE
Main Burner Flame Check
Allow the furnace to run approximately 10 minutes then inspect
the main burner and pilot flames. See Figure 27.
Check for the following (Figure 27):
• Stable and blue flames. Dust may cause orange tips or
wisps of yellow, but flames MUST NOT have solid, yel-
low tips.
• Flames extending directly from burner into heat ex-
changer.
• Flames do NOT touch sides of heat exchanger
If any problems with main burner flames are noted, it may be nec-
essary to adjust gas pressures, or check for drafts.
Main Burner
10-10-78
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii i! i !! ! !! i! !!i!ii!!i!i i i!ii!ii!ii!ii!ii!ii!i !i !! !! !!i
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
Since the manufacturer cannot establish the static pressure
that will be applied to the unit, it is the responsibility of the
installer dealer/contractor to select the proper blower
speeds for the application when the unit is installed.
If it is necessary to change speeds, refer to steps below.
1. Refer to Furnace Wiring Diagram for location of the heating
and cooling speed taps located on the electronic fan control
as well as location of unused blower motor speed leads. Use
the chart (Table 6) to determine the blower motor speed set-
tings.
Table 6 Blower Speed Chart
Wire Color
Black
Orange*
Blue
Red
Motor Speed
High
Med-High
Medium
Low
* Med-High speed may not be provided on all models.
Temperature Rise Check
The blower speed MUST be set to give the correct air temperature
rise through the furnace as marked on the rating plate. Tempera-
ture rise is the difference between supply and return air tempera-
tures.
To check temperature rise,use the following procedure:
IN
2, Change the heat or cool blower motor speed by removing the
motor lead from the "Heat" or "Cool" terminal and replace it
with the desired motor speed lead from the "Unused Motor
Lead" location. Connect the wire previously removed from
the "Heat" or "Cool" terminal to the vacated "Unused Motor
Lead" terminal.
3, If the same speed must be used for both heating and cooling,
remove the undesired motor speed lead from the "Heat" or
"Cool" terminal and connect that lead to the open terminal at
"Unused Motor Lead" location or tape off. Attach a jumper
between the "Heat" and "Cool" terminals and the remaining
motor speed lead.
441 01 201602
Note:Whenusingthesamespeedonmotorswith(4)speed
leads,itwillbenecessarytotapeofftheterminalofthemotor
speedleadremovedfromthe"Heat"or"ooor'terminalwith
electricaltapesinceanopenterminalwillnotbeavailableat
the"UnusedMotorLead"location.
Continuous Fan Operation
A terminal is provided on the electronic fan control located in the
circulating blower compartment for operation of the continuous
fan option. This connection is intended for the low speed motor
tap, and has a lower contact rating (8 amps) than the heat and cool
taps. When the low speed blower lead is connected to this termi-
ChangingBlowerSpeed on NTV6/VNE
Electrical shock hazard.
Turn OFF power to furnace before changing speed taps.
Failure to do so can result in death and/or personal injury.
nal, this will provide low speed blower operation whenever the oth-
er two speeds (Heat or Cool) are not energized.
Heating and Continuous Blower Speed the Same
If it is necessary to operate the heating speed and continuous
blower speed using the same blower speed, connect a jumper be-
tween the "Heat" and "Cont" terminals on the electronic fan con-
trol.
Note: There should be only ONE motor lead going to the "Heat"
and "Cont" terminals.
Note: The blower speeds that the manufacturer sets from the fac-
tory for this product a re based on a nominal 400 C FM per ton cool-
ing and the mid range on the temperature rise for heating.
Since the manufacturer cannot establish the static pressure
that will be applied to the unit, it is the responsibility of the
installer dealer/contractor to select the proper blower
speeds for the application when the unit is installed.
Blower Motor Control
CF"s%%cC%U",
ON 1 l
;1_8; INPUT
SIGNALOR
OFF 0 THERMOSTAT
CONNECTIONS
DIP
SWITCHES
25-23-10
010
*EXAMPLE
Cooling Airflows Switches
6,7&8:
000 3,5 Ton
001 3,0 Ton
010 2,5 Ton
011 2,0 Ton
*See "Technical Support
Manual" for correct airflow
rates.
If it is necessary to change speeds, refer to steps below.
1. The 115 VAC power supply to the furnace must be turned
OFF before making adjustments to the motor.
2, The heating, cooling and continuous blower speeds can be
adjusted by changing the switch settings that are located on
the motor control (see Figure 28). Switches #1 and #2 ad-
just the continuous blower speeds. Switches #3, #4 and #5
adjust the heating speeds. Switches #6, #7 and #8 adjust
the cooling speed. See the" Technical Support Manual"for
the switch settings for the desired airflow rates for the instal-
lation.
11. Furnace Maintenance
CAUTION
It is recommended that the furnace be inspected and serv-
iced on an annual basis (before the heating season) by a
qualified service technician.
See "User's Information Manual".
12. Sequence of Operation & Diagnostics for NTV6/VNE
The following is the normal operating sequence for the 2-stage control system.
Cooling (Y) Request:
24 VAC signals applied to Y &G terminals of EFT (electronic fan timer) control.
• Cool motor speed energized after 5 second Cool Fan On Delay time.
441 01 2016 02
Y & G signals removed from EFT.
• Cool motor speed de-energized after 60 second Cool Fan Off Delay time.
Cooling (Y) and dehumidification (Y2) requests: (Variable Speed ONLY)
• 24 VAC signals applied to Y, Y2 & G terminals of EFT (electronic fan timer) control.
• Same operation as the cooling (Y) request, except the cooling speed is reduced 20% to compensate for high humidity conditions
during cooling operation. The cooling speed returns to the normal setting after the Y2 signal is removed.
Circulating Fan (G) Request:
24 VAC signals applied to G terminals of EFT control.
• Low motor speed energized without delay.
G signal removed from EFT.
• Low motor speed de-energized without delay.
NOTE1) Furnaces with DC blower motors run a low circulating fan speed in response to G request.
NOTE2) Furnaces with PSC blower motors de-energize the Low Heat fan speed during the heat exchanger warm-up period on a
call for Heating that occurs during a G request.
NOTE3) Heating or Cooling requests received during a Fan request cause the fan speed to change to the appropriate heat or cool
speed after the selected Fan On Delay time expires. The fan returns to circulating speed after the selected Fan Off Delay time expires
following loss of the Heating or Cooling request.
Heating (W1) Request (single stage thermostat operation, 4th DIP switch on fan timer, must be in off position)
(see furnace wiring diagram):
24 VAC signals applied to Wl terminal of EFT control.
• Inducer motor turns on at high speed.
• The high fire solenoid energizes.
• Following a 3 second prepurge delay, the pilot valve opens and the ignitor begins to warm up.
• After the pilot lights, the main burners energize and light (burners now at high fire rate).
• Timed from the opening of the main gas valve, the control will delay the selected Heat Fan On Delay time before switching the
inducer to low speed, de-energizing the high fire solenoid and the fan switches to Low Heat speed.
• Timed from initial application of the Heating request, if the Wl request is still present after the Low Fire Delay time expires
(12 minutes), the inducer switches to high speed, the high fire solenoid energizes and the fan switches to High Heat speed.
Wl signal removed from EFT.
• The gas valve de-energizes and the main burners go out.
• The inducer runs at its present speed for a 5 second postpurge period.
• The fan switches to (or stays at) Low Heat speed.
• Timed from the gas valve de-energizing, the Low Heat fan speed de-energizes after the selected Heat Fan Delay time expires.
NOTE4) If a new Heating request arrives while the control is waiting in the Heat Fan Off Delay time, the fan speed switches to High
Heat until the Heat Fan Off Delay expires or the Heat Fan On Delay expires for the new Heating request.
Heating Request (two stage thermostat operation, 4th DIP switch must be in on position) (see furnace wiring
diagram):
24 VAC signals applied to Wl terminal of EFT control.
• Same response as single stage thermostat operation described above except the control will not go to high fire, High Heat fan
speed unless a W2 signal is applied.
24 VAC signals applied to Wl and W2 terminals of EFT control.
• Same light-off routine as described for the signal stage thermostat operation except that at the end of the selected Heat Fan On
Delay, the inducer remains on high fire, the high fire solenoid remains energized and the High Heat fan speed energizes.
NOTE5) The EFT control responds without delay to the presence or loss of W2 (with Wl constant). Wl & W2 results in high inducer,
high fire and High Heat fan speed. Wl only results in low inducer, low fire and Low Heat fan speed.
Heating Request with Gas Supply Line Shut Off:
24 VAC signals applied to Wl terminal of EFT control.
• Inducer motor turns on at high speed.
• The high fire solenoid energizes.
• Following a 3 second prepurge delay, the pilot valve opens and the
igniter begins to warm up.
• The igniter glows red-hot for 30 seconds, then turns off.
_] 441 01 201602
• Theigniterstaysofffor25seconds,thenbeginstowarm-upagain.
• Theigniterglowsred-hotfor30seconds,thenturnsoff.
• Thepilotvalvecloses3secondsaftertheigniterde-energizes.
• Theinducerde-energizes5secondsafterthepilotvalvecloses.
• TheSmartValveproceedstosoftlockoutandflasheserrorcode6.
• Thecontrolexitssoftlockoutafter5minutesandbeginsanother
ignitionsequence.
Gas Valve Diagnostic Codes (See Figure 29)
Steady Flash = Normal Operation
2 Flashes = Low Pressure Switch Stuck Closed
3 Flashes = Low Pressure Switch Stuck Open or
Manual ON/OFF Switch in OFF Position or
(Aux. Limit Switch Open - Upflow ONLY)
4 Flashes = Limit Switch Open (Aux. Limit Switch Open -
Downflow ON LY)
5 Flashes = Flame Sensed Out of Sequence
6 Flashes = Control in Soft Lockout (Automatic Restart or
Retry Delay)
8 Flashes = High Pressure Switch Stuck Closed
9 Flashes = High Pressure Switch Stuck Open
On/Off
Switch
INLET
Typical Gas Valve Honeywell
Diagnostic Light
(€ models)
OUTLET
Pilot
Adjustment 25-22-25a
OUTLET
_ LO Manifold Pressure
adjustments
HI
_ INLET
25-22-49a
11. Sequence of Operation & Diagnostics for NTP6/TNE & TDP6/TDE
The following is the normal operating sequence for the 2-stage control system.
Cooling (Y) Request:
24 VAC signals applied to Y &G terminals of EFT (electronic fan timer) control.
• Cool motor speed energized after 5 second Cool Fan On Delay time.
Y & G signals removed from EFT.
• Cool motor speed de-energized after 60 second Cool Fan Off Delay time.
Cooling (Y) and dehumidification (Y2) requests: (Variable Speed ONLY)
• 24 VAC signals applied to Y, Y2 & G terminals of EFT (electronic fan timer) control.
• Same operation as the cooling (Y) request, except the cooling speed is reduced 20% to compensate for high humidity conditions
during cooling operation. The cooling speed returns to the normal setting after the Y2 signal is removed.
441 01 2016 02
Circulating Fan (G) Request:
24 VAC signals applied to G terminals of EFT control.
• Low motor speed energized without delay.
G signal removed from EFT.
• Low motor speed de-energized without delay.
NOTE1) Furnaces with DC blower motors run a low circulating fan speed in response to G request.
NOTE2) Furnaces with PSC blower motors de-energize the Low Heat fan speed during the heat exchanger warm-up period on a
call for Heating that occurs during a G request.
NOTE3) Heating or Cooling requests received during a Fan request cause the fan speed to change to the appropriate heat or cool
speed after the selected Fan On Delay time expires. The fan returns to circulating speed after the selected Fan Off Delay time expires
following loss of the Heating or Cooling request.
Heating (W1) Request (single stage thermostat operation, 4th DIP switch on fan timer, must be
in off position) (see furnace wiring diagram):
24 VAC signals applied to Wl terminal of EFT control.
• Inducer motor turns on at high speed.
• The high fire solenoid energizes.
• Following a 3 second prepurge delay, the pilot valve opens and the ignitor begins to warm up.
• After the pilot lights, the main burners energize and light (burners now at high fire rate).
• Timed from the opening of the main gas valve, the control will delay the selected Heat Fan On Delay time before switching the
inducer to low speed, de-energizing the high fire solenoid and the fan switches to Low Heat speed.
• Timed from initial application of the Heating request, if the Wl request is still present after the Low Fire Delay time expires
(12 minutes), the inducer switches to high speed, the high fire solenoid energizes and the fan switches to High Heat speed.
Wl signal removed from EFT.
• The gas valve de-energizes and the main burners go out.
• The inducer runs at its present speed for a 5 second postpurge period.
• The fan switches to (or stays at) Low Heat speed.
• Timed from the gas valve de-energizing, the Low Heat fan speed de-energizes after the selected Heat Fan Delay time expires.
NOTE4) If a new Heating request arrives while the control is waiting in the Heat Fan Off Delay time, the fan speed switches to High
Heat until the Heat Fan Off Delay expires or the Heat Fan On Delay expires for the new Heating request.
Heating Request (two stage thermostat operation, 4th DIP switch must be in on position) (see
furnace wiring diagram):
24 VAC signals applied to Wl terminal of EFT control.
• Same response as single stage thermostat operation described above except the control will not go to high fire, High Heat fan
speed unless a W2 signal is applied.
24 VAC signals applied to Wl and W2 terminals of EFT control.
• Same light-off routine as described for the signal stage thermostat operation except that at the end of the selected Heat Fan On
Delay, the inducer remains on high fire, the high fire solenoid remains energized and the High Heat fan speed energizes.
NOTE5) The EFT control responds without delay to the presence or loss of W2 (with Wl constant). Wl & W2 results in high inducer,
high fire and High Heat fan speed. W1 only results in low inducer, low fire and Low Heat fan speed.
Heating Request with Gas Supply Line Shut Off:
24 VAC signals applied to Wl terminal of EFT control.
• Inducer motor turns on at high speed.
• The high fire solenoid energizes.
• Following a 3 second prepurge delay, the pilot valve opens and the igniter begins to warm up.
• The igniter glows red-hot for 30 seconds, then turns off.
• The igniter stays off for 25 seconds, then begins to warm-up again.
• The igniter glows red-hot for 30 seconds, then turns off.
• The pilot valve closes 3 seconds after the igniter de-energizes.
• The inducer de-energizes 5 seconds after the pilot valve closes.
• The SmartValve proceeds to soft lockout and flashes error code 6.
• The control exits soft lockout after 5 minutes and begins another ignition sequence.
441 01 2016 02
Gas Valve Diagnostic Codes (See Figure 30)
Steady Flash =
2 Flashes =
3 Flashes =
4 Flashes =
5 Flashes =
6 Flashes =
8 Flashes =
9 Flashes =
Normal Operation
Low Pressure Switch Stuck Closed
Low Pressure Switch Stuck Open or Manual ON/OFF Switch in OFF Position or
(Aux. Limit Switch Open - Upflow ONLY)
Limit Switch Open (Aux. Limit Switch Open - Downflow ONLY)
Flame Sensed Out of Sequence
Control in Soft Lockout (Automatic Restart or Retry Delay)
High Pressure Switch Stuck Closed
High Pressure Switch Stuck Open
OnlOff
Switch
INLET
Pilot
Adjustment
Typical Gas Valve Honeywell
Diagnostic Light
(€ models)
OUTLET
25-22-25a
_ _ LO Manifold Pressure
adjustments
HI
OUTLET
25-22-49a
441 01 2016 02 [_1
25-20-24
Upflow Models
NTV6050FBG1
NTV6075GFG1
NTV6100KJG1
NTV6125KJG1
NTP6050FBG1
NTP6075GFG1
NTP6100GFG1
NTP6100KJG1
NTP6125KJG1
VNEO50B12G1
VNEO75F14G1
VNE10OJ20G1
VNE125J20G1
TNE050B12G1
TNE075F14G1
TNE100F14G1
TNEIOOJ2OG1
TNE125J20G1
Downflow Models
NDP6050FBG1
NDP6075FBG1
NDP6100HFG1
NDP6125KJG1
TDE050B12G1
TDE075B12G1
TDElOOF16G1
TDE125J20G1
25-21-47
%_'_ } Manufactured by:
_'_, ,_ International Comfort Products Corporation (USA) _'
Lewisburg, TN USA 37091 '_....
Save This Manual For Future Reference
_] 441 01 201602
Manufacturers Number (Mfr No-See Rating Plate)
ALL Models
Specifications
General
Gas Type
Transformer Size (VA)
T'stat Heat Anticipator
Gas &Ignition
Gas Valve
Regulation Type
Manifold Press. Hi Fire (" WC)
Lo Fire (" WC)
Pilot Orifice Size
Ignition Type/Series
Combustion
Flue Outlet Size (Inches)
Std. Outlet Temp (F)
Limits & Controls
Fan Control (Type)
Fan Control On
(Timed-secs) Off
Gas Conversion Kits
Nat to LP *1011789
LP to Nat *1011787
*Must be ordered from Service Parts
Nat
40
.30
HW SV 9540
SNAP
3.5
1.7
.018
HW HSP
3
<480
LP
40
.30
HW SV 9540
SNAP
10.0
4.9
.011
HW HSP
3
<480
HWST9162A
30160
60,100,140,180
HWST9162A
30160
60,100,140,180
General
Input (Btuh) Std/AIt. Hi Fire
Lo Fire
Output (Btuh) Std/AIt. Hi Fire
Lo Fire
Temp. Rise (F) Hi Fire
Lo Fire
Electrical (Volts/Hz/FLA)
Gas & Ignition
Gas Type
Specifications
NTV6050FB/ NTV6075GF/ NTV6100KJ/ NTV6125KJ/
VNE050B12 VNE075F14 VNE100J20 VNE125J20
50,000
35,000
40,000
28,000
35-65
35-65
115/60/5.3
Nat LP
75,000
52,500
60,000
42,000
35-65
35-65
115/60/9.2
Nat LP
100,000
70,000
79,000
56,000
45-75
45-75
115160112
Nat LP
Std. Main Orifices (No/Size)
Limits & Controls
Thermal Sensor (F)
Limit Control Setting (F)
Auxiliary Limit (F)
Std. Pressure Sw. Hi Fire (Part No)
Press (Close)
Press (Open)
Std. Pressure Sw. Lo Fire (Part No)
2/#42 2/#54
30O
See Limitin Parts List
130
1010945
-0.95
-0.80
1011739
3/#42 3/#54
30O
See Limit in Parts List
130
1010945
-0.95
-0.80
1011739
4/#42 4/#54
30O
See Limit in Parts List
130
1010945
-0.95
-0.80
1011739
Press (Close)
Press (Open)
Blower Data
Type & Size
Motor Amps/Rpm
Motor Type/H.p.
Filter Type
Filter Size (")
Min. Cool Cap. (Tons)
Max. Cool Cap. (Tons)
-0.53
-0.35
10-8
4.611050
DC/1/2
Washable
14x25x1/2
1.5
3
-0.53
-0.35
10-10
6.811050
DC/1/2
Washable
16x25x1/2
1.5
3.5
-0.53
-0.35
11-10
9.81900
DC/1
Washable
16x25x1/2 (2)
3
5
125,000
87,000
89,000
72,000
40-70
40-70
115160112
Nat LP
5/#42 5/#54
3OO
See Limit in Parts List
130
1010945
-0.95
-0.80
1011739
-0.53
-0.35
11-10
9.8/900
DC/1
Washable
16x25x1/2 (2)
3
5
44101201602 THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE I_
Circulation Air Blower Data -NTV6/VNE
Heating, Cooling & Continuous Airflow Settings
Continuous Blower (CFM) @ 0,10" Static Cooling (CFM) @ 0,50" Static
Switch Settings Furnace Model
#1 #2 50K 75K 100/125K
0* 0* 600 540 1000
0 1 730 660 1260
1 0 870 780 1500
1 1 1000 900 1725
*Factory Setting
Heating Air Temperature Adjustment (° F)*
Switch Settings Furnace Model
#3 #4 #5 50K 75K 100/125K
0"* 0"* 0"* 0 0 0
001233
010477
0 1 1 6 12 11
1 0 0 9 14 14
1 0 1 -4 -4 -5
1 1 0 -7 -9 -8
1 1 1 -6 -13 -13
(See Figure 1 - 3 for complete Airflow Range)
#6
O*
0
0
0
1
1
1
1
*Factory setting
Switch Settings Furnace Model
#7 #8 50K 75K 100/125K
0* 0* 1200 1350 2100
0 1 1100 1200 2000
1 0 1000 1100 1800
1 1 900 1000 1600
0 0 800 900 1400
0 1 700 800 1200
1 0 650 600 1000
1 1 550 550 800
*Approximate air temperature change from factory setting @ 0.20" static
on high heat )low heat speed changes with change of high heat speed on
most settings)
**Factory setting
I
Blower Motor Settings
DDDDD
678)
1_ 8 INPUT
SIGNALOR
OFF 0 THERMOSTAT
DIP CONNECTIONS
SWITCHES
W
25-23-I0
010
*EXAMPLE
Cooling Airflows Switches
6,7&8:
000 3,5 Ton
001 3,0 Ton
010 2,5 Ton
011 2,0 Ton
*See "Technical Support
Manual" for correct airflow
rates.
i_ THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE 44101201602
Circulation Air Blower Data -NTV6/VNE I
n
Heating, Cooling & Continuous Airflow Settings
Figure 1
NTV6/VNE050 (CFM VS. EXTERNAL STATIC PRESSURE )
u.
o
_0
1350
1250
1150
1050
950 I
850
750
650
550
450
0.1
. ._.... _ k
0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7
ESP
SWITCH
SETTINGS
(#6,#7,#8)
_ooo
--_--001
_010
---)_--011
--I-- 100
_101
_110
_111
Figure 2
NTV6/VNE075 (CFM VS. EXTERNAL STATIC PRESSURE)
1500
I.L
O
1400
1300
1200
1100
1000 I
900
800 "-'-
700
6OO
5OO
4OO
011
,---,.,.,.,.,.,..
_ k.. ""_ _ ...._. m
0.I5 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7
ESP
SWITCH
SETTINGS
(#6,#7,#8)
_ooo
_OOl
_010
_011
•--I-- 100
_101
+110
+111
44101201602 THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE I_
Circulation Air Blower Data -NTV6/VNE I
Heating, Cooling & Continuous Airflow Settings
Figure 3
NTV6NNE100/125 PRESSURE (CFM VS. EXTERNAL STATIC PRESSURE)
22OO
2000
1800
1600 1
_ 1400'
i
1200
1000
80O
6OO
0.1
,,-----.-........_
n
0.2 0.3 0.4 0.5 0.6 0.7
ESP
SWITCH
SETTINGS
(#6,#7,#8)
•_ ooo
OOl
--_--010
•--)_ 011
•--)K_ 100
---e_ 101
+110
_e_111
_] THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE 44101201602
E
LADDER DIAG_M
1-H ERM OSTAT
SEE MANUALS FOR ADJUSTING SWITCHES FOR PROPER HEATING, COOLING & CIRCULATING SPEEDS
ONJ-_
m>
_o
©
+N
©
+N
o
9
%
o
©
©
>
m
oo
CO
CO
r_r -
CO
mz
m_
_m
mr
g_
$
z
r
C
_c
oC r
z0 ,,
o
M _
g >
< :_
>
o
0
z
m
_ e
m
©
t012522+B
_=
g
8+
DANGER: ELECTRICAL SHOCK HAZARD ON---->
CONNECTION DIAGRAM LADDER DIAGRAM
DISCONNECT BEFORE SERVICING _ _ _
FIELD i_ _iR i _ i / HOT 115V-60HZ NEUTRAL "-, _ o 7tt
CONNECTION J MAINUMtT _ _ --" G_N_ DO MOTOR _ LT'T'_ _b o
BOX INTERLOCK I ROIIOUTSEV_TCH_TO2 ./_ ' _ ......... CONTROL i_ -2" '7 -/7" DC _'_ /<: O803
SWITCH _q ....... R-CEPE_iDk_G_ CNiMOicELJ _INTERLOCK _ ........... -, _;_ k 3Z 3ZtBLOWER j _ r-r-
115V _iBK_ _ _iGAiSVALVE ---BL-- f"_ -- _SWtTCH _ ..... _1i_ 4 4_ \MOTOR/ _ _ CO
GND IGNITER -- 8 4- oou HIGH L1 .... 3 8 ©
L=.._\'l_ _11_1 Vl _1I.... _ ..... I J _J] , _w_--_1_ STAGEI SW,OHp_SWIToHPR_SSDH_II11 ....[I_ ............ i Z _ = <g>
(HIVOLT FIELD) _ I II SENSOR_ I FF_ _ I _ i _ -- -- j _ I , _ _ m
COPPER ^, BL 'I _ '_ I / I I .... J I _ _ _ O
I IZl I T i I r----_ -ii
CONDUCTORS I L- --€4 i I W I, i LPPRESSURE _=_ _ _==4 _ ; O
ONLY l .... P,: .... I II i BL SWITCH II_CIRCUITBOARD _GF !!
L_ii-- • i lt <LPMODELSONLY)it i'
I I i r- _ - , i l___--_ ii I A=__ ii : i_
I I_ j _ I U BL[I _ >
.... :::l oz
] I_-6VPRhMARY I _ ...... _Li I I I _ N
ITRANSFORMERi_ 1 7 r_O_ ....... Wr _isi_U ===@O HUM HUMO=.... O
_H
y y - I I '_,_- -- w I _ -- -- _TRANSFORMER
' 'i y. _. __ -t- J Jr _ . AUX LIMITUP TO 2 IN SERIES _ MAIN ROLLOUT SWITCH I TO 2 CO[] CO
- - zmh ....
-_.,,==,_ w L DEPENDINGON MODEl 1 -- IGNITER LIMIT MODELINSERIESDEPENDING ON _
, ------ O
i tom
e_c _ .ll!_!_ _ _= _ _. B,RI -.-._ | III II _a <,->
1111_41 ¢W2 I J _ [ Ill Z4 IBR _ _ _ I i [ _ [li i IpRESSURE I Ls M_L s m 1
F
RI', I--_-_YI_I = _ o $_ -7 I___ ____ o
BL F-- _ _ I I_1 '1 I ll_.qi n_ _ _ i _ p' _ _ F _ I _
I I i I i ,,iiJ I , _ , I IBK I "-1__ [l '_ Ii_ CAPACITOR O 40 _ GAS I (_ -<
'" .... " 'III .... _SOMEMODELS_ ;o l/Im .... VALV_F:_4_II q{_iq m_I_l s
O i _ 2 STAGE H_H AUX LIMITUPTO 2 --i
Y _1 II I Ii I# ]#_' _ iRi T T --R m _/GI.................
(#'_0] I H BRIBKI BLI_ .... CONTROL_ __y_-TT __y_ DE___ _ ___ PR_SSUREs,,,,ITOHL .............
Y W G F_5 - ---
2-STAGE HUMIDISTAT I I I _ ........... T_ ___5 5iG_UI_, P2 :_FI,I_ .... CONTROL !:_ --,_ _Jnc:X 2
THERMOSTAT (OPTIONAL) I I I _ ::<:' I,rrZZ I cO_ORCOD[' 2ba:E'l' IE _<_ -'@ "_BLO'_VER _ _ rn
____LWI,I'_ ............ r-_-_ -_4_-\MOTOR, _ _
I I i " ..... i2 7! I m m
_,oooool I'J '1_":: "r-_T] - - _ o_
L_7\ I h...... U, m BLUE BL _ _l II'lL==,::::t II }'z'l' "' _
I':":'/ - i_ i w_\i. _-_=_=_=_=_=_=_=__. GREEN G L _1 I1!I;<--_
_ --y. --1 L. _ W1 \ |-- LINE VOLTAGE FACTORY ORANGE 0 L--.--_ -- _ ,44
___ _ _ _ y /I-- LINE VOLTAGE FIELD RED R THERMOSTAT _Lr i -- -- -- -- iiII_ Jj _ = r_ _]
-- -- -- 3 i_ G -- -- LOWVOLTAGE FACTORY WHITE W
SINGLE STAGE -G" i_ G fI_-- LOWVOLTAGE FIELD YELLOW Y I" i---------_'-=-i--- ---_ U _ _ m
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE 4_ m_
THERMOSTAT ¢ I _ _-- INTERNAL CIRCUIT BOARD WIRING PURPLE p REPLACED. IT MUST BE REPLACED WITH TYPE AWM-105°C WIRE OR EQUtV
SEE MANUALS FOR ADJUSTING SWITCHES FOR PROPER HEATING, COOLING & CIRCULATING SPEEDS. I012673-B
I
i,,',!
g
I
!
NTV6/VNE
_SS
D E
21
18 T_T__ _30
18
25-23-07
441 01 2016 02
IReplacement Parts - NTV6/VN E (NaturalGas)
Models - NTV605OFBG1, NTV6075GFG1, NTV6100KJG1, NTV6125KJG1:
VNEO50B12G1, VNEO75F14G1, VNEIOOJ2OG1 &VNE125J20G1
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key Functonal
No. Description
1 Heat Exchanger
2 BlowerWheel
3 Switch,AuxiliaryLimit
4 BlowerMotor
5 Motor Mount Kit
6 ControI,FanTimer
7 Transformer,40VA
9 Switch Door
10 BurnerAssembly
11 Pilot/Igniter
12 Pilot Orifice, NAT(.018)
13 Orifice, #42 NAT
14 Tube, Pilot
15 Manifold
16 Valve,Natural& LP
17 Switch,Limit 260°F
180°F
230° F
190°F
18 Tubing,Silicone
19 CombustionBlowerAssembly
20 Relloot Switch,Limit
21 Switch,Pressure(HI)(Upper)
22 Heat ExchangerGaskets
23 Heat ExchangerFrt Partition
28 IgnitorlSensorwith clip
30 Switch,Pressure(LO)(Lower)
33 Motor Control
Functonal
Non-Description
ATop
B Field Connect Box
C Cover, Field Connect
D Gasket, Collector
Part NTV6/VNE Key Functonal
Number 050 075 100 125 No. Non-Description
1011544 1
1011363 1
1012407 1
1012408 1
601210 1
600587 1
1011420 1 1
1013105 2 2 2 2
1012478 1 1
1012479 1 1
1066700 1 1
522020024 1 1
1012084 1 1 1 1
1012722 1 1 1 1
1010886 1 1 1 1
1008723 1
1008724 1
1008725 1
1008726 1
1008731 1 1 1 1
503211 1 1 1 1
1011351 2 3 4 5
1011943 1
1011944 1 1
1011946 1
1011698 1
1011699 1
1011700 1
1011701 1
1012188 1 1 1 1
1320366 1
1008417 1
1320361 1
1008445 1
2071255 1 1 1 1
1011632 1 1 1 1
1005549 2 2 2 2
1010945 1 1 1 1
2480904 2
2480905 2
2480906 2
2480907 2
1008068 1
1008071 1
1012410 1
1012411 1
1009524 1 1 1 1
1011739 1 1 1 1
1012472 1
1012473 1
1012475 1 1
1013295 1
1013296 1
1013298 1
1011941 1 1 1
1010360 1 1 1
1093661 1 1
1093662 1
1093663
1
1
1
E Collector
F Gasket, Comb. Blower
H Door, Louvered
J Door, Blower
M Bracket, Pilot
O Manifold Supt Bracket
P Filter Rack Wrapper
Q Filter Rack Front
R Filter 14" x 25" x1/2"
16" x 25" x 1/2"
S Filter Cover Plastic
T Clip, Filter
U Fan Timer Bracket
W Blower Housing
X Blower Cutoff
Y Blower Hanger
BB Rail, Blower Slide
EE Baffle, NOx
NN Partition, Blower
OO Baffle, Burner Box
PP Top, Burner Box
QQ Cover, Burner Box
RR SightGlass
SS Bracket,PressureSwitch
TT PressureTapTee
)( PARTNOTILLUSTRATED
)( Wire Harness
)( Harness, HiVoltMotor
LoVolt Motor
)( Fuse,SAmp
)( Manual,Homeowners
)( Manual,Installation& Tech
)( GasConve. Kit (Nat.to LP.)
(LP.to Nat.)
Pan NTV6NNE
Number 050 075 100 125
1085400 1
1011048 1
1011672 1
1011738 1
1011379 1 1 1 1
1013331 1
1013332 1
1013333 1 1
1013303 1
1013304 1
1013305 1 1
1010901 1 1 1 1
1011450 2 2 2 2
741010042 1
741010039 1 2 2
741020004 1
741020001 1 2 2
1010364 1
1010365 1 2 2
2791042 1
2791043 1 2 2
1008482 3 3 3 3
1012462 1 1 1 1
1013131 1
1013132 1
1013128 1 1
721020008 1 1 1
721020013 1
1010690 2 2 2 2
57059 2 2 2 2
1009876 2 3 4 5
1013456 1
1013457 1
1013461 1 1
1011454 1 1
1011455 1
1011456 1
1011768 1 1
1011769 1
1011770 1
1011469 1 1
1011470 1
1011471
1011781 1 1 1
1011611 1 1 1
1011750 1 1 1
1011858 1 1 1
1012521 1 1 1
1012520 1 1 1
1083348 1 1 1
44102200105 1 1 1
44101201601 1 1 1
1011789 1 1 1
1011787 1 1 1
I
I
I
I
1
1
1
1
1
1
1
1
I
441 01 2016 02
Manufacturers Number (Mfr No-See Rating Plate)
ALL Models
Specifications
General
Gas Type
Transformer Size (VA)
T'stat Heat Anticipator
Gas & Ignition
Gas Valve
Regulation Type
Manifold Press. Hi Fire C WC)
Lo Fire (" WC)
Pilot Orifice Size
Ignition Type/Series
Combustion
Flue Outlet Size (Inches)
Std. Outlet Temp (F)
Limits &Controls
Fan Control (Type)
Fan Control On
(Timed-secs) Off
Gas Conversion Kits
Nat to LP *1011789
LP to Nat *1011787
*Must be ordered from Service Parts
Nat
4O
.30
HW SV 9540
SNAP
3.5
1.7
.018
HW HSP
3
<480
HW ST9162A
30/60
60,100,140,180
LP
4O
.30
HW SV 9540
SNAP
10.0
4.9
.011
HW HSP
3
<480
HWST9162A
30/60
60,100,140,180
Specifications
NTP605OFB/ NTP6075GF/ NTP6100GF/ NTP6100KJ/ NTP6125KJ/
TNEO50B12 TNEO75F14 TNE100F14 TNEIOOJ20 TNE125J20
General
Input(Btuh)Std/AIt. HiFire
Lo Fire
Output(Btuh)StdIAlt. HiFire
Lo Fire
Temp. Rise (F) Hi Fire
Lo Fire
Electrical(VoltslHzlFLA)
Gas & Ignition
GasType
Std.MainOrifices(NolSize)
Limits & Controls
Thermal Sensor (_F)
LimitControlSetting ('F)
AuxiliaryLimit (F)
Std.PressureSw. Hi Fire(PartNo)
Press (Close)
Press (Open)
Std.PressureSw. Lo Fire (PartNo)
50,000
35,000
40,000
28,000
35-65
35-65
11516015.3
Nat LP
2t#42 2/#54
300
See Limitin PartsList
130
1010945
-0.95
-0.80
1011739
75,000
52,500
60,000
42,000
25-55
25-55
11516019.2
Nat LP
31#42 3/#54
300
See Limitin PartsList
130
1010945
-0.95
-0.80
1011739
100,000
70,000
80,000
56,000
45-75
45-75
11516019.2
Nat LP
41#42 41#54
300
SeeLimit inPartsList
130
1010945
-0.95
-0.80
1011739
100,000
70,000
79,000
56,000
35-65
35-65
115160112
Nat LP
4/#42 4I#54
300
SeeLimitin PartsLi_
130
1010945
-0.95
-0.80
1011739
Press (Close)
Press (Open)
Blower Data
Type & Size
MotorAmpslRpm
MotorTypetH.p.
Cap.MfdlVolts
FilterType
FilterSize (")
Min.CoolCap. (Tons)
Max.CoolCap. (Tons)
-0.53
-0.35
10-8
6.511050
PSC/I/3
51370
Washable
14x25x1
1.5
3
-0.53
-0.35
10-10
6.511050
PSCII/2
7.51370
Washable
16x25x1
1.5
3.5
-0.53
-0.35
10-10
6.511050
PSCIII2
7.51370
Washable
16x25x1
1.5
3.5
-0.53
-0.35
11-10
11.01900
PSC/3/4
101370
Washable
16x25x1(2)
3
5
125,000
87,500
99,000
72,000
40-70
40-70
115160112
Nat LP
5/#42 5/#54
300
SeeLimitin PartsList
130
1010945
-0.95
-0.80
1011739
-0.53
-0.35
11-10
11.91900
PSCI3/4
10/370
Washable
16x25x1(2)
3
5
44101201602 THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE [_
Specifications
General
Input(Btuh)StdlAlt. HiFire
Lo Fire
Output(Btuh)StdlAlt. HiFire
Lo Fire
Temp. Rise (F) Hi Fire
Lo Fire
NDP6050FB/TDE050B12 NDP6075FB/TDE075B12 NDP6100HF/TDE100F16 NTP6125JB/TDE125J20
50,000
35,000
40,000
28,000
30-60
30-60
75,000
52,500
60,000
42,000
40-70
40-70
100,000
70,000
80,000
56,000
35-65
35-65
Electrical(Volts/Hz/FLA)
Gas & Ignition
GasType
Std.MainOrifices(No/Size)
Limits& Controls
Thermal Sensor (_F)
LimitControlSetting (F)
AuxiliaryLimit (F)
Std.PressureSw. Hi Fire(PartNo)
Press (Close)
Press (Open)
Std.PressureSw. Lo Fire (PartNo)
Press (Close)
Press (Open)
Blower Data
Type & Size
MotorAmpslRpm
MotorTypelH.p.
Cap.Mfd/Volts
FilterType
FilterSize (")
Min.CoolCap. (Tons)
Max.CoolCap. (Tons)
Nat.
2/#42
11516015.3
LP
2/#54
300
See Limitin PartsList
110
1010945
-0.95
-0.80
1011739
-0.53
-0.35
10-8
6.5/1050
PSC/I/3
5/370
Washable
16x18xl (2)
1.5
3
11516019.2
Nat. LP
31#42 4/#54
300
See Limitin Parts List
II0
1010945
-0.95
-0.80
1011739
-0.53
-0.35
10-12
6.511050
PSC/I/3
5/370
Washable
16x18x1(2)
1.5
3
115/60/12
Nat. LP
4/#42 4/#54
300
See Limitin PartsList
110
1010945
-0.95
-0.80
1011739
-0.53
-0.35
10-10
8.5/1050
PSC/I/2
10/370
Washable
16x18xl (2)
2
4
125,000
87,500
89,000
72,000
45-75
45-75
115160112
Nat. LP
5/#42 5/#54
300
See Limitin Parts Li_
110
1010945
-0.95
-0.80
1011739
-0.53
-0.35
11-10
11.9/900
PSC/3/4
10/370
Washable
16x18x1(2)
3
5
CIRCULATION AIR BLOWER DATA
NTP605OFB/TNE050B12, NDP6050FB/TNE050B12 & NDP6075FB/TNE075B12
Air Delivery in Cubic Feet per Minute (C.F.M.)
(Furnace Rated @0.5" WC ESP)
TAP LOW MED LMED MED H HIGH
,10 675 859 -- 1015 1394
q.20 662 846 -- 999 1342
.95
_.30 651 819 -- 977 1289
.40 636 795 -- 952 1227
_,50 608 765 -- 914 1163
,60 564 735 -- 870 1086
w,70 514 685 -- 818 1002
Air Delivery in Liters Per Second (L/S)
(Furnace Rated Co)0.5"WC ESP)
TAP LOW MED L MED MED H HIGH
,10 318 405 -- 479 658
_- o." .20 312 399 -- 472 633
1__ .30 307 387 -- 461 608
_, .40 300 375 -- 449 579
_,50 287 361 -- 431 549
"_ ,60 266 347 -- 411 513
uJ ,70 243 323 -- 386 473
NTP6075GF/TNEO75F14 &NTP6100GF/TNE100F14
Air Delivery in Cubic Feet per Minute (C.F.M.)
(Furnace Rated @0.5" WC ESP)
TAP LOW MED L MED MED H HIGH
,10 815 1043 -- 1324 1649
_,20 783 1030 -- 1302 1616
.95
_.30 755 1021 -- 1280 1592
.40 735 989 -- 1255 1546
E _ .50 704 988 -- 1218 1502
,60 668 941 -- 1171 1426
W,70 646 881 -- 1100 1353
Air Delivery in Liters Per Second (L/S)
(Furnace Rated @0.5" WC ESP)
oTAP LOW MED L MED MED H HIGH
_, ,10 385 492 -- 625 778
o." .20 370 486 -- 615 763
"_ "6 .30 356 482 -- 604 751
_ .40 347 467 -- 592 730
E _ ,50 332 457 -- 575 709
!_ ,60 315 444 -- 553 673
ILl ,70 305 415 -- 519 639
_] THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE 44101201602
NTP6100KJ/TNE100J20
Air Delivery in Cubic Feet per Minute (C.F.M)
(Furnace Rated @0.5" WC ESP)
TAP LOW MED L MED MED H HIGH
.10 1210 1441 -- 1773 2104
_ .20 1201 1430 -- 1740 2078
,9 _ ,30 1197 1453 -- 1740 2061
,40 1191 1441 -- 1718 2020
-8 ,50 1167 1425 -- 1707 2005
-.60 1160 1390 -- 1676 1953
w.70 1130 1365 -- 1654 1917
NTP6125KJ/TNE125J20
Air Delivery in Cubic Feet per Minute (C.F.M)
(Furnace Rated @0.5" WC ESP)
,_ TAP LOW MED L MED MED H HIGH
.10 1264 1520 1841 2161
0. o." .20 1251 1506 -- 1803 2132
-9 _ .30 1249 1486 -- 1772 2079
,40 1219 1456 -- 1736 2042
-8 ,50 1168 1427 -- 1702 1991
E_=
,60 1178 1415 -- 1672 1914
UJ .70 1143 1358 -- 1614 1838
NDP6100HF/TDE100F16
Air Delivery in Cubic Feet per Minute (C.F.M.)
(Furnace Rated @0.5" WC ESP)
TAP LOW MED L MED MED H HIGH
,10 954 1312 -- 1698 1925
_.20 950 1292 -- 1645 1853
_ .30 946 1265 -- 1596 1780
®,40 915 1231 -- 1530 1708
E _ .50 878 1175 -- 1455 1638
w,60 830 1118 -- 1362 1546
.70 778 1020 -- 1241 1435
NDP6125KJ/TDE125J20
Air Delivery in Cubic Feet per Minute (C.F.M.)
(Furnace Rated @0.5" WC ESP)
TAP LOW MED L MED MED H HIGH
_.10 1333 1573 -- 1840 2148
.9 _.20 1294 1544 -- 1816 2093
_,30 1266 1500 -- 1776 2041
-8 ,40 1240 1467 -- 1726 1981
-,50 1175 1419 -- 1665 1906
w.60 1141 1357 -- 1607 1828
.70 1054 1308 -- 1538 1751
Air Delivery in Liters Per Second (L/S)
(Furnace Rated @0.5" WC ESP)
TAP LOW MED L MED MED H HIGH
.10 571 680 -- 837 993
_- o." ,20 567 675 -- 821 981
,9 _,30 565 686 -- 821 973
e,40 562 680 -- 811 953
-8 .50 552 673 -- 806 946
_ --_ .60 548 656 -- 791 922
w.70 533 644 -- 781 905
Air Delivery in Liters Per Second (L/S)
(Furnace Rated @0.5" WC ESP)
TAP LOW MED L MED MED H HIGH
.10 597 717 -- 869 1020
_" o." ,20 590 711 -- 851 1006
-9 _ ,30 590 701 -- 836 981
_,40 575 687 -- 819 964
"8 .50 551 674 -- 803 940
E_= .60 556 668 -- 789 903
UJ .70 540 641 -- 762 868
Air Delivery in Liters Per Second (L/S)
(Furnace Rated @0.5" WC ESP)
TAP LOW MED L MED MED H HIGH
,10 450 619 -- 801 908
_.20 448 610 -- 776 874
_ .30 446 597 -- 753 840
,40 432 581 -- 722 806
E _ .50 414 555 -- 687 773
w,60 392 528 -- 643 730
.70 367 481 -- 586 677
Air Delivery in Liters Per Second (L/S)
(Furnace Rated Co)0.5" WC ESP)
TAP LOW MED L MED MED H HIGH
A- o." .10 629 742 -- 868 1014
,9 _,20 611 729 -- 857 988
_,30 598 708 -- 838 963
"_ -8 ,40 585 692 -- 815 935
-_ .50 555 670 -- 786 900
w.60 539 641 -- 759 863
.70 497 617 -- 726 826
44101201602 THIS DATA SUBJECT TO CHANGE WITHOUT NOTICE [_
I
OANOER: ELECTRICAL SHOCK HAZAR0
CONNECTION DIAGRAM DISCONNECT BEFORE SERVICING
_ID_,L_CT!ON [MZ_jTY_#'N L_ _-- ___ ROLLOUT SWITCH i TO 2 'N
BOX TNT_R_nr K NOT ON ALL --- SERIES DEPENDING ON MO_
&,x::_ pooELs /7,, ....
H_OT. = oW_Tc,. ----R-- --_ GAS VALVE _
68HZ I_./_1 , I ,- ,_ ,,__1 I PRESSURE •
_TOR,_ L' I_"__ --F=_--- _
._ L ( , W- ' _ . I _ I--
ONLY L I _ 1 W -- I _ ....
IIF _TFR--<s__-I
I--- _ _ _ i IBL SWI'-TCH
-_uu W_ j I I(Lp MODELS ONLY)I
_K III II I 14__>._ I
I _ ---- r------- 0 , P L. __ ._2¢:_/___._,,.B.L ;
TZ
' VAC ('OH
I:;:V_'qMI/"¥I _nn __ I_ I I _---°cI I
ITRANSFORMERI,I I Y iF ®_--4-- ..... I_----BL--
I I i_- _-= I I
T T__y ____ _ W AUX. LIMIT UP TO2
L J _ _ fIN SERIES DEPENDNG I
--w-- ---- w2 _ _
r- - FrTr-_ _ ................ I--I "" %1
RI/ r-----¢ Y _ . _0 o s_<R 8,R
IBL /i,---_@ s _ _,_,s_ ,.1,.1 I
.II - ICAiAP fOR 8K R
2-STAGE L
_H_RMOS_ \_ _'.Z. _
_--. R- -- -- _ SEED CODE BLUE BL
_ C \ BL_'MLO BROWN BR
I_ _ l l b' _ _ W2 /_ ORANGE-MHI RED-LO GREEN O
_,/_)('_/__y ,,___ I,_ --'_ Wl /I-- LINE VOLTAGE FACTORY ORANGE 0
_ l l ,L l ' l _ y /I--LINE VOLTAGE FIELD RED R
S_NGLE STAG F l--G--I _ 0 1I--LOW VOLTAGE FACTORY WH!TE
.^_._ _ - /I' l LOW VOLTAGE FIELD ILLLUW !
HERHOS/_ "--/ I---- INTERNAL CIRCUIT BOARD WIRING PURPLE P
'_ SEE MANUALS FOR ADJUSTING SPEEO TAPS FOR PROPER HEATING, COOLING & CIRCULATING SPEEDS.
LADDER DIAGRAM
llSV-68HZ _EUTRAL
t_dNTERLOCK (3-11, /
I_WI[CH GND.
L] _ t(_COOL F] (BK) N
_i--_ _ HEAT MLO (BL,'>"-._W II
II _3 _' _°'__ II
KDM_ _ &_&
,, __ DOP_E_TO_,,
L 4J;B 4
lit c_- __°°_ II
!= =00 HUM HU;_ =_
IIXFMR .. N--
. 5V
_TRANSFORHER _ -- _
NOT ON ALL ROLLOU SWitCH
-- --_ IGNITER MODELS I02 IN SEBES
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE
MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE
AWM - 105"C WIRE OR ITS EOUIVALENT.
u')-_ Do
--I('I
-{--I
FR
m
,@
m
n
"11
z
c)
z
r -_
3[
'-' '3
n
(.o ÷
m_
g
rm
1012146
Q
NTP6RNE
-SS
D E
RR
25-22-41a
441 01 2016 02 [_
IReplacement Parts - NTP6/TN E (NaturalGas)
Models - NTP605OFBG1, NTP6075GFG1, NTP61OOGFG1, NTP61OOKJG1, NTP6125KJG1:
TNEO5OB12G1, TNEO75F14G1, TNEIOOF14G1, TNEIOOJ2OG1 & TNE125J2OG1
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key Functonal
No. Description
1 Heat Exchanger
2 Blower Wheel
3 Switch, Auxiliary Limit
4 Blower Motor
5 Motor Mount Kit
6 Control, FanTimer
7 Transformer, 40VA
8 Capacitor 10mf370V
5mr 37BV
7.5mr 37BV
9 Switch Door
1O Burner Assembly
11 Pilot, Nat & LP
12 Pilot Orifice, NAT(.018)
13 Orifice, #42 NAT
14 Tube, Pilot
15 Manifold
16 Valve, Natural& LP
17 Switch, Limit 260°F
270"F
180°F
150"F
190"F
18 Tubing,Sificone 24"
19 Combustion BIwAssemb
20 Rollout Switch, Limit
21 Switch, Press (Hi)(Upper)
22 Heat Exchanger Gaskets
23 Ht Exchanger Frt Partition
28 Ignitor/Sensor with clip
30 Switch, Press (Lo)(Lwr)
)( PART NOT ILLUSTRATED
)( Wire Ham Asy, Low Volt
)( Fuse, SAmp
)( Manual, Homeowners
)( Manual,]nstallation&Tech
)( Nat to LP Conver Kit
)( LPto Nat Conver Kit
NTP6tTNE
Part
Number 850F 075G 1BOG 100K 125K
050B 075F 100F lOOJ 125J
1011544
1011364
1011363
1012407
1012408
601210
600587
1011420
1013105
1012514
1013341
1011404
609227
522020024
1012084
1012722
1094956
1094954
1094239
1010886
1008723
1008724
1008725
1008726
1008731
503211
1011351
1011943
1011944
1011946
1011698
1011699
1011700
1011701
1012188
1320366
1320365
1008417
1320361
1008448
2971255
1011632
1005549
1010945
2480904
2480905
2480906
2480907
1008068
1008072
1008071
1012410
1012411
1009524
1011739
7
2
1
1
1
1
7
1
1
I
I
2
I
I
I
2
I
2
1
1
1
1
1
1
77
1 1
7
2 2 2 2
1 1 i i
1 1 1 1
1 1 1 1
1 1
7
1 1
7
1 1
1 1
3 4
7
1 1
7
1 1
1 1
2 2
1 1
1 1
1011858
1083348
44102200105
44101201601
1Oll 789
1Oll 787
7
1 1
1 1
4 5
7
1 1
7
1 1
1 1
2 2
1 1
77
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
NTP6/TNE
Key Functonal Part
No, Description Number OSOF 075G 1BOG 100K 125K
050B 075F 100F lOOJ 125J
A Top 1 -
1
B Field Connect Box
C Cover, Field Connect
D Gasket, Collector
E Collector
F Gasket, Combustion BIwr
H Door, Louvered
J Door, Blower
M Bracket, Pilot
0 Manifold Support Bracket
P Filter Rack Wrapper
Q Filter Rack Front
R Filter 14" X25" X 112"
16" x25"x 1/2"
S Filter Cover Plastic
T Clip, Filter
U Fan Timer Bracket
W Blower Housing
X Blower Cutoff
Y Blower Hanger
AA Strap Capacitor
BB Rail, Blower Slide
EE Baffle, NOx
NN Partition, Blower
OO Baffle, Burner Box
PP Top, Burner Box
QQ Cover, Burner Box
RR Sight Glass
SS Bracket, Pressure Swth
TT Pressure Tap Tee
1013295
1013296
1013297 i
1013298
1011941 1 1 1
1010360 1 1 1
1093661 1 1
1093662 i
1093663
1085400 1
1011048 i
1011672 i i
1011738
1011379 1 1 1 1
1013331 1
1013332 i i
1013333 i
1013303 1
1013304 i i
1013305 i
1010901 1 1 1 1
1011450 2 2 2 2
741010042 1
741010039 i i
741020004 1
741020001 i i
1010364 1
1010365 i i
2791042 1
2791043 i i
1008482 3 3 3 3
1012321 1 1 1 1
1013131 1
1013132 i i
1013128 i
721020008 1 1 1
721020013 i
1010690 2 2 2 2
1095020 1 1 1 1
57059 2 2 2 2
1009876 2 3 4 4
1013456 1
1013457 i 7
1013461 i
1011454 1 1
1011455 i i
1011456
1011768 1 1
1011769 7 7
1011770
1011460 1 1
1011470 7 7
1011471
1011781 1 1 1 1
1011611 1 1 1 1
1011750 1 1 1 1
7
1 1
1 1
1
1
2
3
1
1
2
1
2
5
1
1
1
I
_] 441 O1 2016 02
NDP6/TDE
MM
BB
/
I
I
I
I E
I
I
15
18
22
25-22-59
441 01 2016 02 [_
IReplacement Parts - NDP6/TDE (NaturalGas)
Models - NDP6050FBG1, NDP6075FBG1, NDP6100HFG1 &NDP6125KJGl:
TDE050B12G1, TDE075F12G1, TDE100F16G1 & TDE125J20G1
Replacement part supplied will be current active part. For parts not listed, consult place of purchase,
NBP6/TDE
Key Description
No. Functional
1 Heat Exch Assembly
2 Blower Wheel
3 Switch, Limit (Auxiliary)
4 Blower Motor
5 Motor Mount Kit
6 Control, Fan Timer
7 Transformer, 4OVA
8 Capacitor 10mf 370V
5mf 370V
g Switch Door
10 Burner Assembly
11 Pilot, Natural & LP
12 Orifice, Pilot, Nat. (.018)
13 Orifice, #42, Nat.
14 Tube, Pilot
15 Manifold
16 Valve, Natural + LP
17 Switch, Limit 210"F
260°F
220"F
150°F
18 Tubing, Silicone, (24")
19 Combustion BIwr Assb.
20 Rollout Switch, Limit
21 Switch, Press (Hi) (Upper)
22 Gasket, Heat Exchanger
23 Partition, Frnt Ht Exch
28 Ignitor/Sensor with clip
30 Switch, Press (Lo) (Lower)
)( PART NOT ILLUSTRATED
)( Wire Harness Asy.
)( Fuse, 5 Amp
)( Manual, Homeowners
)( Manual, Installation& Tech
)( Manual, Vent Inst
)( Nat to LP Gas Conver Kit
)( LP to Nat Gas Conver Kit
I
Pa_
Number 050F 075F 100H 125K
050B 075B 100F 125J
1011544 1
1011364
1012406
1012408
601210 1
600587
1011420
1320368 1 1 1 1
1012514 1 1
1009052
1011404
609227 1 1 1
522020024
1012084 1 1 1 1
1012722 1 1 1 1
1094956 1 1
1094954 1 1
1010886 1 1 1 1
1008723 1
1008724
1008725
1008726
1008731 1 1 1 1
503211 1 1 1 1
1011351 2 3 4 5
1011943 1
1011944 1
1011946
1011698 1
1011699
1011700
1011701
1012188 1 1 1 1
34335001 1
1320366
1320367
1320362
2971255 1 1 1 1
1011632 1 1 1 1
1005549 1 1 1 1
1010945 1 1 1 1
2480904 2
2480905
2480906
2480907
1008068 1
1008072
1012409
1012411
1009524 1 1 1 1
1011739 1 1 1 1
1012202 1 1 1 1
1083348 1 1 1 1
44102200106 1 1 1 1
44101201601 1 1 1 1
1007374 1 1 1 1
1011789 1 1 1 1
1011787 1 1 1 1
Key Description
No. Non- Functional
A Panel,Top
B Field Connect Box
C Cover, Field Connect
D Gasket, Collector
E Collector
F Gasket, Combustion Blwr
H Door, Louvered
J Door, Blower
M Bracket, Pilot
O Manifold Support Bracket
R Filter 18114"X153/4"X1"
U Support, Control
W Blower Housing
X Blower Cutoff
Y Blower Hanger
AA Clamp, Capacitor
BB Rail, Blower Slide
EE NOx Baffle
MM Filter Holder
NN Flue Pipe
OO Vent Pipe Shield
PP Vent Shield Endplate
QQ Plate, Fill-in
RR Partition, Blower
SS Baffle, Burner Box
TT Top, Burner Box
UU Sight Glass
VV Cover, Burner Box
WW Bracket, Press Switch
XX Tee, Plastic
NDP6/TDE
Pa_
Number 050F 075F 100H 125K
050B 075F 100F 125J
1013299 1 1
1013300
1013301
1011941 1 1 1 1
1010360 1 1 1 1
1093661 1 1
1093662
1093663
1085400 1
1011048
1011672
1011738
1011379 1 1 1 1
1013334 1 1
1013335
1013336
1013310 1 1
1013311
1013312
1010901 1 1 1 1
1011450 2 2 2 2
1009750 2 2 2 2
1011178 1 1 1 1
1013129 1
101057g
1010580
721020008 1 1
721020013 7 7
33403100 2 2 2 2
1095020 1 1 1 1
33406100 2 2 2 2
1009876 2 3 4 5
33411100 1 1 1 1
613193 1 1 1 1
2311160 1 1 1 1
57083 2 2 2 2
1011071 1 1
1011072
1011073
1013476 1 1
1013474
1013475
1011454 1 1
1011455
1011456
1011772 1 1
1011773
1011774
1011781 1 1 1 1
1011469 1 1
1011470
1011471
1011611 1 1 1 1
1011750 1 1 1 1
_] 441 01 2016 02