Installation Instructions
Downflow Kit for EBP, EBX, EBW and EBV Series
These instructions must be read and understood completely before attempting installation.
Fire Hazard
The purpose of the subbase assembly is to maintain
a1" clearance to combustible materials.
Attach supply duct to inner flange of subbase.
Failure to do so can result in fire, bodily injury or
death.
The downfiow conversion for slope units
following items:
Coil bracket (1)
Coil baffle (1)
Screws (2)
Foam gasket (1)
requires the
WARNING: Before beginning any installation or
modification, be sure the main electrical disconnect
switch is in the OFF position. Tag the disconnect
switch with a suitable warning label. Electrical shock
can cause personal injury or death.
INTRODUCTION
Fan coils are factory-shipped for upfiow or horizontal-left
applications. This instruction covers the installation of
downfiow conversion kit on models EBP, EBX, EBW and
EBV fan coils. The kit provides a means of installing fan coils
in a downfiow position.
DESCRIPTION AND USAGE
The downfiow conversion kits are available for use on slope
and A-coil versions of previously mentioned fan coils. When
installed, the kit will provide proper condensate water
drainage, as well as a means of supporting the coil. See unit
Installation Instructions for proper kit part numbers.
The downfiow conversion for A-coil units requires the
following items:
Coil bracket (2)
Support strap (1)
Drainage hole plugs (2)
Angle (2)
Screws (4)
Air seal (1)
NOTE: The fan coils are factory shipped for upfiow or
horizontal-left applications. Installation of the Downfiow
Conversion Kit should be complete before the fan coil unit
is positioned to ensure side access required for installation
of the coil brackets.
NOTE: If unit has electric heat with a circuit breaker, refer
to electric heater Installation Instructions for repositioning of
breaker assembly.
7/I IDNR'D_ 1p/4E_NiHOLHE SI DES )/000/
/000 /
_-- SUPPORT STRAP
A-COIL _ ANGLE "-_
A,q8437
--_ Fig. 1--Downflow A-Coil Brackets and
Support Strap Location
A90210
Fig. 2mPosition of Angles on A-Coil
482 01 2222 00
INSTALLATION-A-COILUNITSONLY
1.Remove all panels and expose blower and coil areas.
2.Remove any shipping clips securing coil.
3.Remove complete coil/drain pan assembly.
4.Remove and discard horizontal drain pan from coil
assembly.
&Drill four 1/4-in. holes (2 on each side) in fan coil casing
at dimples provided. (See Fig. 1.)
6.Secure coil brackets (provided in kit) to casing sides. (See
Fig. 1.)
7.Install support strap (provided in kit) across front of unit as
follows:
a.Position flange on each end of strap between coil
bracket and casing insulation. (See Fig. 1.)
b.Secure support strap ends to coil brackets. (See Fig. 1.)
&Remove and discard 4 clips (on corners of coil) securing
coil assembly to rails for upflow applications.
9.Remove and discard factory-shipped air seal and drain
tube assembly. Install 1-piece sheet metal air seal
assembly provided with kit.
1&Tilt coil assembly back and slide angles (provided in kit)
over each inside wall of condensate pan. Pop- riveted flange
of angles should extend toward coil. (See Fig. 2.)
11.With fan coil in downflow position, slide coil assembly into
unit. (See Fig. 3.)
12.Reinstall all panels. Align holes in panels with tubing and
condensate connections. Casing was designed to allow 180
degree rotation of coil access panel and fitting panel.
1&Install 2 plugs that have been provided onto doors to seal
unit.
INSTALLATION- SLOPE COIL UNITS ONLY
1.Remove all panels and expose blower and coil areas.
2. Remove screw securing coil assembly to right side flange.
Remove complete coil/drain pan assembly.
&Drill two 1/4-in. holes in right side of casing at dimples
provided (unit in upflow position).
4.Place fan coil unit in downflow position.
&Secure coil bracket to left side of casing with 2 screws
provided. (See Fig. 4.)
&Remove top coil bracket from coil (2 screws).
b.Align holes in gasket with holes in top coil bracket.
c.Remove only half of the backing from the gasket.
&Apply exposed half of foam gasket to under side of top
coil bracket. (See Fig. 5.)
e.Remove remaining piece of backing from gasket and
press gasket into place.
f.Replace top bracket onto coil. The 2 screws must engage
the lanced holes.
&Install remaining coil baffle at coil end opposite the coil
headers. (See Fig. 6.)
a.Slide the longer flange of baffle between tube sheet and
end of condensate pan. Be sure notch in baffle is fully
seated below notch in tube sheet.
NOTE: The TXV sensing bulb must be insulated on slope
coils in horizontal right and downflow applications. Failure to
insulate bulb will result in performance loss.
7.Insulate TXV sensing bulb with cork tape or other
permanent insulating material.
&Invert coil assembly and slide it into unit with drain pan to
left side of fan coil. Secure coil assembly with screws. (See
Fig. 3.)
&Reinstall fitting panel, blower panel, and coil access panel.
Align holes in panels with tubing and condensate
connections.
SLOPE COIL A-COIL
-_ Fig. 3---CompletedDownflowConversion
-- --r
t/"
|/'
SLOPE COIL
--> Fig, 4_Downflow Slope Coil Bracket
SLOPE €
_J
A98438
TOP BRACKET
-_ Fig. 5--Top Coil Bracket Gasket
For Slope Coil Only
\_. COIL BAFFLE s,,/
A98439
CONDENSATE PAN
COIL BRACKET
-_ Fig. 6--Coil Baffle Location
(At End Opposite Coil Header)
A98440