Installation Instructions

SINGLE
PACKAGE
HEAT
PUMPS
PHF & HPFM Series - 2 to 5 TON

518 01 1102 O0
Printed in U.S.A.

10-25-01

Safety Labeling and Signal Words

Danger Label

Danger, Warning and Caution

White lettering on a black background except the word
DANGER which is white with a red background,

The signal words DANGER, WARNING and CAUTION are
used to identify levels of hazard seriousness. The signal
word DANGER is only used on product labels to signify an
immediate hazard. The signal words WARNING and
CAUTION will be used on product labels and throughout
this manual and other manuals that may apply to the
product.
Signal Words

Warning Label

DANGER - Immediate hazards which WILL result in
severe personal injury or death.

White lettering on a black background except the word
WARNING which is black with an orange background,

WARNING - Hazards or unsafe practices which COULD
result in severe personal injury or death.
CAUTION - Hazards or unsafe practices which COULD
result in minor personal injury or product or property
damage.
Signal Words in Manuals
The signal word WARNING is used throughout this manual
in the following manner:

Caution Label
White lettering on a black background except the word
CAUTION which is black with a yellow background,

The signal word CAUTION is used throughout this manual
in the following manner:
CAUTION

Product Labeling
Signal words are used in combination with colors and/or
pictures on product labels. Following are examples of
product labels with explanations of the colors used.

L_J

51801

110200

[I]_1111
m]
bY4
=l_[=][e]_[-!
3 TO 5 TON

All Dimensions in inches

41/2 .

Detail
46-1/2

BASE PAN - CHASSIS
42-3/4"*

©
BASE RAIL
BASE RAIL

46-1/4"*

Condensate Drain
19

SUPPLY

f

12-1/4

RETURN
19
I
I
i

1-9/16
2-3/16

2- 3/16
3-3/4

A

B

C

D

E

F

G

H

I

J

3 Ton

UNIT SIZE

29-1/2

47-1/2

47-1/2

3

9-1/2

12

14

12

14

4-112

4 TO 5 Ton

37-1/2

47-1/2

47-1/2

4

6-1/2

19

19

12

12

4-112

** Measured from inside to inside on base rails.

51801

110200

L_J

Minimum Clearances to Combustible

SAFE INSTALLATION

Condenser
Blower
Control

Service
Service

Clearance
Installation

or repairs made by unqualified

B149-1

(Side)
Side

Combustible

30"

..............................
...............................

30"
30"

3 Ft. Overhang

and Top of Unit

........................

30"

Base
(Wood

or Class

roof covering

A, B or C

material)

....................

0"

and CSA
FIGURE

The information

...................................

between

persons can result

in hazards to you and others. Installation MUST conform with
local building codes or, in the absence of local codes, with the
ANSI Z223.1 and the National Electrical Code N FPA70-1990 or
in Canada the National Standard CAN/CGA
C.22.1 - Canadian Electrical Code Part 1.

Inlet

Construction

i

Minimum Clearances(B
Chassisandshown)ACcess
Panels

contained in this manual is intended for use

by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.

I

Blower Compartment

Panel

Small Chassis - 2"
Large Chassis

Failure to carefully read and follow all instructions in this
manual can result in furnace malfunction, property damage,
personal injury and/or death.

• Seal supply and return air ducts.
• Check to see that filters are installed correctly and are
the proper type an size.
NOTE: It is the personal responsibility and obligation of the
customer to contact a qualified installer to ensure that the
installation is adequate and conforms to governing codes
and ordinances.

LOCATING THE UNIT
INSTALLATION
NOTICE

ACCESS PANELS
See FIGURE 1 for a general view of unit and location of
access panels.
CLEARANCES
The location MUST allow for minimum clearances and
should not be adjacent to a patio or other area where the
unit's operating sound level might be objectionable. (see
FIGURE 1). In addition, local codes MUST be observed.
NOTE: Units with available filter racks, need a 26" minimum
clearance at side of unit for removal of filters. See chart
below if unit is going to be placed near combustible
construction or materials.
While minimum clearances are acceptable for safety
reasons, they may not allow adequate air circulation around
the unit for proper operation in the cooling mode. Whenever
possible, it is desirable to allow additional clearance,
especially around the condenser inlet and discharge
openings.

Unit will NOT operate properly unless it is installed level front to rear and side to side. The slope MUST NOT be
greater than 1/8" per foot (10mm per meter). For side to
side leveling, the drain side MUST always be lower.
Ground Level Installation
Ground level platform requirements:
- The unit MUST be situated to provide safe access for
servicing.
- Platform may be made of either concrete or pressure
treated wood and MUST be level and strong enough to
support unit weight.
- Position platform separate from building foundation.
- Install in well-drained
above grade level.

area, with top surface of platform

- Platform must be high enough to allow for proper condensate trap installation and drainage. See FIGURE 2
and associated text for more information about condensate drainage.

Do NOT install the unit in a location that will permit
discharged air from the condenser to recirculate to the
condenser inlet.
CAUTION
Do NOT operate unit in a corrosive atmosphere containing chlorine, fluorine, or any other corrosive
chemicals.
_41

51801

110200

Rooftop Installation
Rooftop platform requirements:
- The unit MUST be situated to provide safe access for
servicing.
- The existing roof structure MUST be adequate to support the weight of the unit or the roof MUST be
reinforced.
Check the weight of the unit in relation to the roof structure and local building codes or ordinances and
reinforce roof structure if necessary. See the last page
of this manual for unit weights.

outlet from trap MUST be at least 1" (25.4mm) below top of
outlet from unit. Install the trap as near to the unit as
possible for proper drainage,
A3/4" (19.1mm) drain line MUST be installed if required by
local codes or if location of unit requires it. Run the drain line
to an open drain or other suitable disposal point.

2 /

1

Condensate
ora n,nformot oo*

3/4" (19,1mm)
Female PVC

- Support for the unit MUST be level and strong enough
to carry unit weight. The support may consist of a platform or a combination of platform and roof beams or
curb.

Fitting

- See Hoisting section for hoisting instructions.
HOISTING

(25.4mm)
80-31-32

NOTE: All access panels MUST be secured in place before
hoisting.
2" (50.8mm)

The unit should be hoisted with two lifting slings. Attach the
slings to rigging shackles that have been hooked through
holes in the base rail.
Two spreader bars MUST be placed on top of the unit to
protect the unit from damage from the pressure exerted by
the slings. Make sure that all equipment is adequate to
handle the weight of the unit and that the slings will not allow
the unit to shift.
Refer to on the back cover of this manual for illustrated
rigging instructions and weight chart.

3/4" (19.1mm)
Drain Line

* Condensate

trap MUST be installed.

ElectricalWiring

DOWNFLOW CONVERSION
NOTE: In downflow applications with roof curbs or jack
stands, the center rail under the unit must be removed. The
center rail is attached to the base rail with screws.

Electrical

These units are adaptable to downflow use. To convert to
downflow use, follow these steps:

Disconnect power at fuse box or service panel
before making any electrical connections.

1. Remove the blockoff plates found in the return air
compartment and the supply air compartment.
NOTE: Blockoff plate in the supply air compartment only
contains one screw. If reinstalling plate, back part of plate
MUST fit into mating dimples on flange. To reinstall, slant
plate into dimples, then put plate into position and fasten
with screw.
2. Install the removed plates on the horizontal return and
supply air openings.
3. Install roof curb on the building. Be sure to follow all
directions included with curb and all applicable building
codes in your installation.
Condensate Drain
The condensate drain outlet is a 3/4" (19.1 mm) female PVC
connection located at the bottom on the left hand side (see
FIGURE 2).
The circulating blower creates a negative pressure on the
condensate drain line that can prevent the condensate from
draining properly. To combat this negative pressure, a field
supplied condensate trap that will allow a standing column
of water of at least 2" (50.8mm) MUST be installed. Top of

shock hazard.

Unit MUST be grounded to electrical service panel.
Failure to follow this warning can result in property damage, personal injury, and/or death.
NOTE: All electrical work MUST conform with the requirements of local codes and ordinances and in the United
States with National Electrical Code ANSI!NFPA 70-1990
(or current edition) and in Canada with CSA C22.1 - Canadian Electrical Code Part 1 (or current edition). Provide line
voltage power supply from a separate fused circuit with a
disconnect switch (when required) located within sight of
the unit. Supply voltage, amperage, wire, fuse and disconnect switch sizes MUST conform with specifications in the
Parts List and on the unit rating plate.
Wiring MUST be protected from possible mechanical damage and MUST NOT interfere with removal of access
panels, filters, etc.
51801 110200

151

All exposed wiring and connections MUST be made with
weatherproof cable or wire unless installed in conduit,

FIGURE 4 l

ConnectionElectr°nicTherm°statDiagram
Low Voltage
Electronic Thermostat Subbase

Low Voltage Wiring
Low voltage connections are made on the electronic control
board inside the electrical control compartment (see
FIGURE 5). For access, remove the electrical control access panel).
Refer to the Parts List for the connection wiring diagram for
the applicable model and to the instructions included with
the thermostat.
Route low voltage
tom left corner of
Route low voltage
wire clip provided,

wires through the port located at the botthe blower access panel side of the unit.
wires behind unit cornerpost, through the
and up to the low voltage terminal board.

NOTE: If an Electric Heat Accessory is installed, see the
Electric Heat Accessory Installation Manual for low voltage
connections,

_

(White Rodgers:

P

-

-

"1

f

-

--

"1

1F92-71 and 1F94-71)
(2)

'

(3)

'

,

,

,

,

I

!

|

[C]

[G]

[R]

[O1

[YI]

[Wl]

(1)l

[,W21 [Ell

I

!

I

!

!

I
I

If. _
I

,

,' Jumper Wire

[C]

[&]

[1_]

[61

[_'11

[V_I ]

Com

Fan

24V

Rev.
Valve
Energ
Cool

Pump
Heat
Cool

Aux.
Emer.
Heat

_

.I

[V_/21

Low Voltage Connections on Control Board,
Thermostat

Subbase Notes:

(1) Oommon [C] may be shown as [B] or [X] on other types
of thermostats.
(2) Jumper subbase terminals [Y1] and [W1].
(3) Jumper subbase terminals [W2] and [El].

Thermostat
The location of the thermostat has an important effect on the
operation of the unit. FIGURE 3 and FIGURE 4 show typical wiring connections for both manual and electronic
thermostats, FOLLOW THE INSTRUCTIONS INCLUDED
WITH THE THERMOSTAT FOR CORRECT LOCATION,
MOUNTING AND WIRING.

FIGURE

3

l ConnectionMechnical
ThermostatDiagram
Low Voltage

Mechanical Thermostat Subbase
P

-

--

I

[G]

[R]

[O1

[Y]

"1

I

(1)

[W21 [El

i

Jumper Wire
f

[C]

[G]

[R]

[O]

[Y1]

[Wl]

Com

Fan

24V

Rev.
Valve
Ener
Cool

Pump
Heat
Cool

Aux.
Emer.
Heat

Low Voltage Terminal Board at the Unit.
Thermostat Subbase Notes:
(1) Terminals [W2] and [E] already jumpered at subbase.

L_J

A ground lug is installed on the control plate for the ground
connection (see FIGURE 5). Use a copper conductor of the
appropriate size from the unit to a grounded connection in
the electrical service panel or to a properly driven and electrically grounded ground rod, See warning above.

Line Voltage Wiring
Do NOT complete line voltage connections until unit is permanently grounded. All line voltage connections and the
ground connection MUST be made with copper wire.

(White Rodgers: 1F58-34)
(2)
'I
[C]

Ground Connections

i

[W2]

Connections for line voltage are made on the unit electrical
control plate (see FIGURE 5), For access, remove the electrical access panel.
Refer to applicable wiring diagram in the Parts List. Complete the line service connections to the contactor 'U
terminals on the electrical control plate. Check all screw terminals to ensure they are tight.
NOTE: If an Electric Heat Accessory is installed, refer to the
Electric Heat Accessory Installation Manual to determine
line voltage connections. The Electric Heat Accessory
mounts inside the unit. Field supplied line voltage wires for
the Electric Heat Accessory (separate from the field supplied line voltage wires to the unit) connect to the circuit
breaker(s) in the Electric Heat Accessory,

51801

110200

Converting

and located, MUST NOT exceed the temperature limitations for type T wire and MUST be installed according to the
manufacturer's instructions for the devices.

230V Units to 208V

To convert 230V units to 208V:
Turn electric

2.

Remove

3,

Locate the 24V control transformer.

4,

Remove wires from the terminal labeled "240V" on the
24V control transformer
and reconnect them to the
208V terminal of the 24V control transformer,

5,

OFF

the electrical

Replace

Field

power

Final Electrical

1,

the electrical

Installed

access

access

Check

panel.

Make a final wiring check to be sure system is correctly
wired. Inspect field installed wiring and the routing to ensure
that rubbing or chafing due to vibration will not occur,
NOTE: Wiring MUST be installed so it is protected from possible mechanical damage,

panel,

Equipment

Wiring to be done in the field between the unit and other devices, or between separate devices which are field installed
FIGURE 5

Typical Wiring Installation

_3

Control

ooord

Le°_iVCal_age

_

Connections

"_. _

/

_////_

,

l©

,

_

/_

_

_

'

"

I

" Contactor

Transfo_

RI c wllw_ GI o Y
Ground lug

51801

110200

h_J

Air DistributionSystem
For airflow data (blower performance data, blower speed
tap settings, etc.) see the Parts List.

Ductwork

Connections

The use of flexible, non-combustible connectors between
main trunk ducts and supply and return air plenums is recommended to minimize vibration transmission.

Ductwork
NOTE: The total heat gain!heat loss from the structure as
expressed in total Btu/hr MUST be calculated by manufacturer's method or in accordance with "A.S.H.R.A.E. Guide"
or "Manual J - Load Calculations" published by the Air
Conditioning Contractors of America or in Canada"H.R.A.I.
Residential Heating and Cooling Load Calculation Manual."
The total heat qain calculated should be equal to or less
than the cooling capacity output based on D.O,E. test
procedures, steady state efficiency times input.
Ductwork, supply registers, and return air grilles MUST be
designed and sized to handle the unit's cooling air volume requirements. If the unit is connected to an existing
system, the ductwork MUST be checked to make sure it is
adequate. Extra runs or larger duct sizes may have to be
installed.
Maximum recommended velocity in trunk ducts is 1000 feet
per minute (5.08m/s). Velocity in branches should not exceed 800 feet per minute (4.06m/s). Refer to the Parts List
for unit air volume requirements and system sizing recommendations.

NOTE: Connect supply and return air plenums to unit in a
manner that will allow the top of the unit to be removed without removing plenums. Plenums MUST be individually
sealed to unit casing. Ducts MUST be terminated inside
structure.

Filters
All return air MUST pass through a filter before entering the
unit. An electronic air cleaner, optional filter racks or other
accessible filter arrangements MUST be installed in the return air ductwork. Minimum recommended filter areas are
based on a velocity of 300 ft/min (1.2m/s) for disposable filters and 500 ft/min (2.54m/s) for washable high velocity
filters.

CAUTION
Do NOT operate the unit without

all filters in place.

NOTE: Ductwork sizing affects temperature rise and cooling temperature differential. Be sure to properly size
ductwork to the capacity and airflow characteristics of your
unit. Failure to do so can affect limit controls, compressors,
motors, and other components and will lead to premature
failure of components. This will also adversely affect dayto
day unit performance.
Refer to unit rating plate for proper Electric Heat Accessory
sizing and see the Temperature Rise Check section in the
Electric Heat Accessory Installation Instructions.
Ductwork

Insulation

It is recommended that ductwork installed outdoors have a
minimum of 2" (51 mm) of fiberglass insulation and be covered by a weatherproof vapor barrier that is protected
against damage. Caulking and flashings, or other means
adequate to provide a permanent weather seal, must be
used.
It is recommended that ductwork installed in attics or other
areas exposed to outdoor temperatures have a minimum of
2" (51 mm) fiberglass insulation and have an indoor type vapor barrier.

[_d

51801

110200

Start-up Procedures
Cooling,
Electric
Electrical shock hazard.
Use extreme care during
checks and procedures.

all of the following

Make sure electric power is turned
instructed in appropriate steps.

OFF as

Failure to follow this warning can result in property damage, personal injury, and/or death.

Determining

Check

1.
2.

Air Blower
Blower

Speed

Auxiliary

2.

Before

Starting

Check that the blower motor speed terminal block is
set to the proper speed. Refer to the unit wiring diagram and the Technical Labels in the Parts List.
Check to see that clean, properly sized field supplied
air filters are installed in the return air duct.

3,

From the system design, determine the external static
pressure (ESP) for the supply ducts, return ducts and
registers, diffusers, grilles, dampers, heaters and filters.

Inspect the inside of the unit to be sure that all wires
are in place and all tools, etc. are removed,

4.

Replace all service access panels.

To your system ESP determined in Step 2, add 0.05
In. W.C. for a wet coil.

4.

From the system design, determine the desired cooling airflow in cubic feet per minute (CFM).

6.

and

Turn electric power OFF,

3.

5,

Pump)

NOTE: The cooling, heat pump and strip heat airflows
are all on the same speed tap. The refrigerant system
requires the same specific CFM for proper operation in
the cooling and the heat pump mode. For this reason,
cooling and heating airflow must be the same. DO NOT
SPLITOUT INTO A COOLING SPEED AND HEATING
SPEED.

1,

Circulating

Heating
(Heat
Strip Heat

Locate the unit's Blower Performance Data table in
the tech data sheet for the unit's voltage. (The tech
data sheet is attached to the inside of the electrical access panel and is also published in the Parts List.)
From the table, determine the speed tap the desired
airflow requires.
See next section, Speed Taps, to set the blower motor
speed terminal block (speed taps) determined in the
following steps.

Speed Taps
After determining the required CFM and speed tap data
from the tech data sheet, follow the steps below to change
speeds if necessary.
NOTE: The yellow lead MUST always be connected to the
speed tap block at the common quick connect terminal. The
terminal is identified as COM. Also, this is the only lead
which is 3/16" wide. All other quick connects are 1/4" wide.
Refer to the unit's wiring diagram, which is attached to the
inside of the electrical access panel and is also published in
the Parts List for the desired speed tap to achieve the required CFM for the applicable model.

Check the unit's operation as outlined in the following
instructions. If any unusual sparking, odors or noises are
encountered, shut OFF electric power immediately. Recheck for wiring errors, or obstructions in or near blower
motors.

Sequence

of Operation

Cooling Mode: Energized
De-energized
(N/A)
(a) When
to unit:

(R,G,O,Y1)

high and low voltage

is initially

applied

(1) On a call for cooling ......... :
The compressor and condenser fan will have a delay
on and will energize after 5 minutes. The evaporator
blower motor will energize immediately. The delay on
for the compressor and the condenser fan can be bypassed by jumpering the test pins on the defrost
board control.

(2) When

the cooling setpoint has been satisfied ......... :
The compressor and condenser fan will de-energize
immediately. The evaporator blower motor will have a
delay off and will de-energize after 30 seconds,

(b) When high and low voltage has
to unit for more than 5 minutes:

been

applied

(1) On a call for cooling ......... :
The compressor and condenser fan will energize immediately. The evaporator blower motor energize
immediately.

51801

110200

191

(2) When the cooling setpoint

has been satisfied ......... :
The compressor and condenser fan will de-energize
immediately. The evaporator blower motor will have a
delay off and will de-energize after 30 seconds.

Heating Mode: Energized
De-energized
(0)
(a) When
to unit:

(R,G,Y1)

high and low voltage

is initially

applied

The compressor and condenser fan will have a delay
on and will energize after 5 minutes. The evaporator
blower motor will have a delay on and will energize after 30 seconds. The delay on for the compressor and
the condenser fan can be by-passed by jumpering
the test pins on the defrost board control.

(2) When the heating setpoint

has been satisfied ......... :
The compressor and condenser fan will de-energize
immediately. The evaporator blower motor will have a
delay off and will de-energize after 30 seconds.
has

the heating setpoint has been satisfied ......... :
The compressor and condenser fan will de-energize
immediately. The evaporator blower motor will have a
delay off and will de-energize after 30 seconds.

Defrost Mode:Energized
(R,G, Y1) De-energized
(0) Defrost Sensor Closed

(1) On a call for heating ......... :

(b) When high and low voltage
to unit for more than 5 minutes

(2) When

been

applied

(1) On a call for heating ......... :
The compressor and condenser fan will energize immediately. The evaporator blower motor will have a
delay on and will energize after 30 seconds.

(1) On a call for defrost .........
When the defrost sensor closes (this can be simulated by placing a jumper across the DFST and
T'STAT terminals on the control board) in the heating
mode,there is a 30,60 or 90 minute defrost on delay
before the defrost mode begins. This delay is determined by the jumper selection on the control board.
See Figure 7.

(2) When defrost has been completed .........
This condition will be maintained until the defrost sensor opens or for a mzximum of 10 minutes, whichever
comes first.
The TEST selection will speed up the defrost/heating cycle
for diagnostic purposes. When the jumper is in the TEST
position and Y is energized, the unit will cycle from heating
(10 seconds) to defrost (2 seconds) to heating (10 seconds)
to defrost (2 seconds) for a maximum of 8 times, tf the
jumper is left in the TEST position, the control will ignore the
call for TEST and default to a 90 minute defrost cycle. If the
jumper is not installed, the control will default to a 90 minute
defrost cycle.
NOTE: A jumper across the DFST and T'STAT terminals is
not necessary in order to check out the defrost control.

51801

110200

Blower

Motor Speed Taps (3-Speed

and 4-Speed

Motors)

/
/'

/

YELLO_L

SPEED DATA IN UNITS
TECHNICAL INFORMATION LABEL
I BE SURE TO CHECK BLOWER MOTOR I
ON THE UNIT

/

Operation
and prevent possible reverse rotation of the scroll compressor,
Electrical shock hazard.

Loss of Charge

Pressure Switch

Turn OFF electric power supply at disconnect

A low pressure switch on the liquid line (high side) has been

switch or service panel before removing any access or service panel from unit.

The switch will open and de-energize

Failure to follow this warning can result in property damage, personal injury, and/or death.

installed to prevent system damage due to a loss of charge.
the contactor if the

high side pressure drops below the set point of the switch,

Defrost Control Time Interval

Adjustment

Features
Electrical shock hazard.

Scroll Anti-Cycle

Timer

All single phase heat pumps with scroll compressors are
equipped with a defrost control board which features an internal anti-short cycle timer that delays the start of the
compressor in the event of a power interruption. This feature is to allow pressure equalization throughout the system

Turn OFF electric power supply at disconnect
switch or service panel before removing any access or service panel from unit.
Failure to follow this warning can result in property damage, personal injury, and/or death.

51801

110200

Illl

To adjust defrost interval:

Turning

1.

Turn off all power to Heat Pump.

2.

Remove control box cover.

3.

Locate electronic control board.

4,

1,

Set the thermostat selector switch to OFF and set the
fan switch to AUTO. To restart, set thermostat selector switch to COOL and set thermostat to temperature
desired.

The Control Board has a jumper that allows you to
change the defrost time interval. (See Figure Below)
Change the desired time by removing the jumper and
placing the jumper on 30, 60, or 90.
30 = 30 minutes, 60 = 60minutes, 90 = 90 minutes.
FIGURE 7

The Unit Off

2.

To shut the unit down completely, turn electric power
OFF.

Thermostat

Fan Switch Operation

Defrost Control
With the thermostat fan switch in the ON position, the circulating air blower will run continuously,

Control
Board

Jumper placed
here for defrost
check
Defrost
Settings

With the thermostat fan switch in the AUTO position, the circulating air blower will only run during a cooling or heating
cycle and when the electric heat accessory is required if the
electric heat accessory is installed.

Adjusting

Room Temperatures

If the temperature in individual rooms is not as desired, balance the system by adjusting the dampers in the branch
ducts. Adjust a little at a time and wait a day after each
change to judge the effect. Once the dampers are adjusted
for normal weather conditions, it is best to leave them that
way. Compensate for temporary weather changes by adjusting the thermostat setting.

1S31

FIGURE 8

Typical Branch Duct Dampers

Cooling
Adjust thermostat setting to desired temperature and set
thermostat Heat-Cool switch to COOL. The unit will come
on and operate automatically under control of the thermostat. Close all doors and windows. The unit may run
continuously for several hours or longer on the initial run because of residual heat and moisture in the house. This is
normal for any air conditioning system.

CAUTION
Do NOT operate unit on cooling when the outdoor temperature is below 40°F (4.4°C). This is necessary to
prevent possible damage to the compressor.

1L_

51801

110200

Maintenance
Oil the condenser fan motor after five years of operation and

Air Filters, Condenser Coil and
Condensate Drain Maintenance

every five years thereafter.

Refer to Home Owners Manual supplied with your heat
pump for information on filter sizes, condenser coil clearances
from
allowances.

shrubbery

and

condensate

drainage

CAUTION
Do NOToperate unit without filters in place. Inspect filters monthly and clean and/or replace as needed.

Refrigeration

Access Ports

This unit is equipped with refrigeration access ports
mounted on the side ofthe unit, Refer to FIGURE 9 for iden-

Use SAE lOW30 motor oil. To oil, remove the hole plugs from
the motor end bells and add several drops (approximately
1/2 teaspoonful) of oil with a squeeze type, flexible tube oiler. Replace hole plugs after oiling. Do NOT over oil.
Clean the surrounding area and the condenser and evaporator coils. Use caution to avoid damage to coil fins. Do not
use an acid-based cleaner on coated fin material.

Blower

Motor

Access

To remove the blower motor and/or the blower motor housing assembly, remove the blower access panel.

tification of ports.
Refer to FIGURE 10 for a view of blower motor and
This unit is also equipped with internal access ports on the

compartment.

suction and discharge tubing line which can be used for
evacuation, pull down and recharging of the refrigeration
system.

FIGURE 10 l

FIGURE 9

Typical Access Ports

Annual Maintenance
Condenser

Blower Motor and Housing

and Inspection

Fan Motor

Blower Wire Color Identification
CAUTION
Use FIGURE 11 to identify wires on blower motor,
Do NOT use 3 in 1 oil, penetrating oil, WD40 or similar
oils to oil motor bearings.
To change speed tap settings, see Speed Taps in the Startup Procedures section of this manual.
51801 110200

L_J

Wire Colors

Circulating

Air

Blower

Visually inspect the blower wheel for accumulations of dirt
or lint. Clean the compartment and the blower wheel. If accumulation is excessive on blower wheel, or does not easily
remove, it will be necessary to remove the blower assembly.

CAUTION
Do NOT use 3 in 1 oil, penetrating oil, WD40 or similar
oils to oil motor bearings.
Oil the blower motor by adding

1/2

teaspoonful (1cc) of SAE

10W30 to each motor bearing. The blower motor should be
oiled after five years of operation and every five years thereafter.

1141

51801

110200

INTERNATIONAL COMFORT PRODUCTS
LIMITED WARRANTY CERTIFICATE
For Cooling
SAVE THIS CERTIFICATE.
province

It gives you specific

& Heating Products

legal rights, and you may also have other

rights which

may vary from state to state and

to province.

If your unit needs servicing, contact a qualified dealer or qualified service technician of your choice. When requesting service, please have the model
and serial number from each unit in your heating and/or cooling system readily available. If your dealer needs assistance, the distributor is available to
provide support and we, in turn, support its efforts.
Fill in the installation date and model and serial numbers of the unit in the space provided below and retain this Limited Warranty for your files.

GENERAL TERMS
Subject to the conditions and limitations stated herein, during the term of this Limited Warranty, we will provide a replacement for any functional
component part (as defined below) of your unit found to be defective in materials or workmanship. The term of this Limited Warranty is five years from
installation on Residential Products and one year from installation on Commercial Products. Except as otherwise stated in the "Additional Terms"
section, this Limited Warranty covers only the original purchaser and subsequent transferees, and only while the unit remains at the site of the original
installation (except for mobile home installations), and onty if the unit is installed inside the continental United States, Puerto Rico, Alaska, Hawaii or
Canada. In addition, the Limited Warranty applies only if the unit is installed and operated in accordance with the printed instructions accompanying the
unit, and in compliance with alt applicable installation and building codes and good trade practices. As used in this Limited Warranty, "installation"
means the original installation of the unit.
TH ERE ARE EXCEPTIONS to this Limited Warranty as described on the reverse side of this page. All replacement parts will be warranted for the
unused portion of the warranty coverage period on the unit. The part to be replaced must be returned by the dealer to a distributor that sells products for
International Comfort Products, in exchange for the replacement part. In lieu of providing a replacement part, we may, at our sole option, refund to you
an amount equal to the distributor's component purchase price from us, or provide to you a credit equal to that amount to be applied toward the purchase
of any new unit that we distribute. If a credit for a new unit is given in tieu of a replacement part, the rating plate from the unit being replaced must be
submitted on a warranty claim, and you r dealer must make the unit being replaced available to our distributor for disposition. As a condition to warranty
coverage, the unit must receive yearly maintenance, as described in the owner's manual, by a dealer. Satisfactory proof of yearly service by a dealer
may be required.
"Functional component parts" include only the following: blower motor, unit-mounted sensors & timers, condenser motor, evaporator coil, condenser
coil, condenser fan, capacitor, transformer, single-phase strip heat elements, expansion device, reversing valve, solenoid valve, service valve,
electronic and electro-mechanical control board, ignitor, ignition module, draft inducer assembly, burner pilot, gas valve, limit control, pressure switch,
relays and contactors, blower wheel, interlock switch, crosslighter, pilot shield, gas & oil burners, oil pump assembly, accumulators and factory installed
driers and strainers.
This Limited Warranty DOES NOT COVER any labor, material, refractory chambers, oii nozzles, refrigerant, refrigerant inspection and refrigerant
reclaiming, freight and/or handling charges associated with any repair or replacement and such charges will be your responsibility.
To establish the installation date for any purpose under this Limited Warranty, you must retain the original records that can establish the installation date
ofyour unit. Ifyou donot providesuchdocumentsthe
start dateoftheterm ofthis LimitedWarrantywillbe
based uponthedate ofunit manufacture, ptus
thirty (30) days. In establishing that the required yearly service has occurred, you must furnish proof of yearly service by a qualified service technician.
This Limited Warranty does not cover: (a) failure or damages caused by accident, abuse, negligence, misuse, riot, fire, flood, or Acts of God (b)
damages caused by operating the unit where there is a corrosive atmosphere containing chlorine, fluorine, or any other damaging chemicals (other
than those found in a normal residential environment) (c) damages caused by an unauthorized alteration or repair of the unit affecting its stability or
performance (d) damages caused by improper matching or application of the unit or the unit's components (e) damages caused by failing to provide
proper maintenance and service to the unit in accordance with this Limited Warranty Certificate and the printed instructions originally provided with the
unit (f) any expenses incurred for erecting, disconnecting, or dismantling the unit (g) parts or supplies used in connection with service or maintenance,
such as refrigerant, refractory chambers, oil nozzles, filters, or belts (h) damage, repairs, inoperation or inefficiency resulting from faulty installation or
application (i) electricity or fuel costs or any increase in electricity or fuel cost whatsoever including additional or unusual use of supplemental electric
heat (j) units which have not had the required yearly maintenance described elsewhere in this limited warranty.
In no event shall we be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure of this unit.
We have not made. do not make. and hereby disclaim any implied condition or implied warranty of fitness for a particular use or purpose, and
anv implied condition or implied warrantv of merchantabilitv, to the fu Ilest extent allowed bv law. We make no express or implied warranties
except as stated in this Limited Warrantv certificate.
No one is authorized to change this Limited Warranty or to create for us any other obligation or liability in connection with this unit. Any implied
warranties shall last for the term of the expressed warranty contained herein. Some states and provinces do not allow the exclusion or limitation of
incidental or consequential damages or do not allow limitations on how long an implied warranty or condition lasts, so the above limitations or exclusions
may not apply to you. The provisions of this Limited Warranty are in addition to and not a modification of or subtraction from any statutory warranties and
other rights and remedies provided by law.

Please refer to reverse side of this page for additional terms.
Model No.
Serial No.

Effective

Date Installed

on units installed

After July 1, 2002,

USA: International Comfort Products Corporation (USA) • 650 Hell-Quaker Avenue * P.O. Box 128 • Lewisburg, Tennessee 37091 • (931-270-4100)
CANADA: International Comfort Products division of UTC Canada Corporation • 6060 Burnside Court, Unit 1, Mississauga, Ontario L5T 2T5
(905-795-8113).
Manufacturers of Airquest, Arcoaire, Clare, Comfortmaker, Dettson, Hell, Keeprite, Lincoln, Tempstar and other quality brand name private label
products.
Part No. 401 06 1010 18 (Orig. 8/9/2002)

ADDITIONAL

TERMS FOR RESIDENTIAL

APPLICATIONS

ONLY

The Additional Terms for the components listed below are in addition to, and subject to, the General Terms on the reverse side of this page.
Warranty coverage is limited to parts that fail due to defect in materials or workmanship during the specified term.

CENTRAL GAS & OIL FURNACE HEAT EXCHANGERS*
Gas Model Series: C9MPV. HgMPV. TgMPV. CgMPT. H9MPT. T9MPT. C9MPD. HgMPD. TgMPD: Limited Lifetime Warranty on heat exchangers. If
a heat exchanger on one of these furnaces fails due to defect in the part, we will provide a replacement part or, at our option, credit toward the purchase
of a new furnace manufactured by us. This additional Limited Warranty runs only to the original purchaser, and tasts only for as tong as the originat
purchaser tives in the home where the furnace is initially installed.** It is not transferable to any subsequent owner. Ifthe furnace was not installed in the
home owned by the original purchaser, if the original purchaser setls the home to a subsequent owner, or if proof of originat purchase cannot be
provided, then the limited warranty is only for 20 years from the date of original installation.
Gas Model Series: GDL. GNL. TNE. TDE. NTC7. NDC7. NTP6. NDP6. TDE. NTV6. VNE: A replacement heat exchanger will be provided for any
heat exchanger that fails in one of these furnaces due to defect for 25 years from the originat date of installation.
Gas Model Series: NTC6. GNE. GDE. NDN6. NTG3. NDN3. FBF. NBF. NDF. NTN3. NTN6. NNE. N9MPI. N9MP2. FUH: A replacement heat
exchanger witt be provided for any heat exchanger that faits in one of these furnaces due to defect for 20 years from original date of installation.
Oil Model Series: OLR(105, 160, 182), OCF, OLE OUF, NOLE NOUF, OLB, OHB, ODH, FLO, MBO, LBO, NOMF: Limited Lifetime Warranty on
heat exchangers. Ifa heatexchangerononeofthesefurnacesfailsduetodefectinthepart,
wewitl provide a replacement part or, at our option, credit
toward the purchase of a new furnace manufactured by us. This additional Limited Warranty runs only to the original purchaser, and tasts only for as
long as the original purchaser lives in the home where the furnace is initially installed.** It is not transferable to any subsequent owner. If the furnace
was not installed in the home of the original purchaser, if the original purchaser sells the home to a subsequent owner, or if proof of original purchase
cannot be provided, then the limited warranty is only for 20 years from the date of original installation.
Oil Fired Floor Furnace: NFO: A replacement heat exchanger witl be provided for any heat exchanger that faits due to defect for 10 years from
installation with the following limitation: during the sixth through tenth year, any credit toward your purchase of a component or toward the purchase of
any new unit wilI be in an amount equal to the distributor's purchase price reduced by 20 percent for each year after the fifth year.

ADDITIONAL

TERMS FOR OIL FURNACE APPLICATIONS

ONLY

1) OIL BURNERS - A replacement for 5 years from date of original installation for Oil Burner Parts.
2) OPTIONAL ACCESSORIES AND FUNCTIONAL PARTS: A replacement for 5 years from date of original
oil nozzles not included)

GAS/ELECTRIC
Model series:

PACKAGED

installation.

(Refractory

and

UNITS HEAT EXCHANGERS

PGAD. PGAA. PGMD. PGME. PGF. GPFM. PGC. GPCM:

A replacement for 10 years from original date of installation.

COMPRESSORS:*
1) Premium Model Units: HAC0. HAC2. HAC4. CAC0. CAC2. CAC4. KAC0. TCA0. TCA2. TCA4. HHP0. HHP2. HHP4. CliP0. CliP2. CliP4.
TCH0. TCH2. TCH4. PGME. PYMC. PHAD. PGAD. PA95. PAPC. PAK. APK: To the original purchaser a replacement for 10 years from original date
of installation, only if the unit is installed with factory matched coils, except air conditioner condensing units with a nominal SEER of 10 may be matched
with evaporator coils of the same nominal tonnage regardless of manufacturer and in accordance to factory recommendations. This limited 10-year
warranty is not transferable to any subsequent owner. HOWEVER, if the unit was not installed in the home owned by the original purchaser, if the
purchaser sells the home to a subsequent owner, or if proof of original purchase cannot be provided, then the limited warranty is only for 5 years from the
original date of installation.**
2) All Other Models: Air Conditioners.
Heat PumPs. & Combination
Gas/Electric Units: NAC0. NAC2. NHP0. NHP2. AO. A2. HO. H2. PGF.
PGC, GPFM, GPCM, PAE APFM, PHE HPFM, PGAA, PGMD, PA55, PH55, PAPA, PYPA: A replacement for 5 years from date of original
installation, onty if: (a) air conditioner condensing units with SEER rating in the range of 10 to 11 SEER are matched with evaporator coils of the same
nominal tonnage regardless of manufacturer and in accordance to factory recommendations, or (b) heat pump condensing units are used with factory
matched coils, unless written approval to do otherwise is obtained from manufacturer.

ADDITIONAL

TERMS FOR COMMERCIAL

APPLICATIONS

ONLY

For purposes of this warranty a commercial application is one in which: the product has over 5 tons nominal cooling capacity, or is designed
for operation with 3 phase electrical power, or is installed in a commercial establishment such as a beauty or hair salon, hospital, school,
restaurant, church, hotel etc..
3-Phase Models: PGF, GPFM, GPF, PGAD, PGME, PGB, PGMG, PGMF, PGS, PGE, APE, PAE, PAB, PAMD, PAS, PAl=,APFM, APF, PHB, PHE,
PYMD, HPB, PHS, CAC, ACC, CAE, ACE, CHC, HCC, CHE, HCE:
The additional

Terms of the components

listed below are in addition to and subject to the General Terms on the reverse side of this page.

1) GAS FIRED HEAT EXCHANGERS (ALL MODELS):* A replacement for 10 years from date of originat installation.
2) COMPRESSORS (ALL MODELS):* A replacement for 5 years from date of original installation.
3) OPTIONAL ACCESSORIES AND FUNCTIONAL COMPONENT PARTS (ALL MODELS):*
A replacement for 1 year from date of original installation.
4) COMMERCIAL OIL MODELS: OLR210, OLR350, OTF210, AMT3, AMT4, AMP3: Ten(10) Year Limited Warranty on heat exchangers.
*To receive advantage of your limited warranty, you must provide proof of yearly service by a qualified service technician.
**To receive advantage of your warranty, you must retain the original records that can establish the installation date and proof of purchase of the unit.

MINI SPLITS:
Summary - Mini Splits Warranted for one (1) year on all replacement parts.
Additional terms for Mini Splits:
The additional Terms of the components listed below are in addition to, and subject to, the General Terms on the reverse side of this page.
1) Compressors
installation.

(All Models):

A replacement compressor wili be provided for atI compressors that faii due to defect for 5 years from date of original

2) Optional Accessories and Functional Components Parts (All Models):
A replacement part will be provided for alt parts that fail due to defect for one (1) year from date of original installation.
Failu re to maintain the equipment through annual maintenance by a qualified service technician shall void the warranty. Proof of service wili be required
with ati warranty claims. Proof of purchase and installation date must be submitted with ali claims.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 16
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Thu Apr 05 01:04:27 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu