ICP Air Handler (indoor Blower&evap) Manual L0523222

User Manual: ICP ICP Air Handler (indoor blower&evap) Manual ICP Air Handler (indoor blower&evap) Owner's Manual, ICP Air Handler (indoor blower&evap) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 12

DownloadICP  Air Handler (indoor Blower&evap) Manual L0523222
Open PDF In BrowserView PDF
INSTALLATION
INSTRUCTIONS
Models
MV08B1500A2
MV12F1900A2
MV16J2200A2
MV20N2600A2
Require
AMF001NHA
Accessory

Use ONLY factory listed electric heaters.

Modular Blower

No Heat Kit

General Information / Installation ............
Installations
...............................
Horizontal Installations
.....................
Ductwork Connections
.....................
Filter Installation ...........................
Electrical Connections ......................

2
3
3
4
4
5

Motor speeds and Airflow ...................
Blower Performance ........................
Airflow Check ..............................

6
8
9

Wiring Diagram ............................
Replacement Parts .........................

11
12

(Variable Speed)
Safety Labelingand Signal Words
Danger,Warning and Caution
The signal words DANGER, WARNING and CAUTION
are used to identify levels of hazard seriousness. The
signal word DANGER is only used on product labels to
signify an immediate hazard. The signal words WARNING and CAUTION will be used on product labels and
throughout this manual and other manuals that may apply to the product.
DANGER - immediate hazards which WILL result in severe personal injury or death.
WARNING
- Hazards or unsafe practices which
COULD result in severe personal injury or death.
CAUTION - Hazards or unsafe practices which COULD
result in minor personal injury or product or property
damage.

Printed in U.S.A.

Signal Words in Manuals
The signal word WARNING is used throughout
manual in the following manner:

this

The signal word CAUTION is used throughout
manual in the following manner:

this

CAUTION
Product Labeling
Signal words are used in combination with colors and/or
pictures on product labels.

442 01 2303 02
June 2002

_ Installation

Modular Blower I

Instructions

Figuie

Nominal

Installation

Dimensions

and Clearances

38-20-17

14-1/2" (11/2- 3Ton) MV08
17-3/4" (11/2- 3Ton) MV12
21-3/8 '' (2 - 4 Ton) MV16
25"
;Ton) MV20

CLEARANCES
NO HEATERS
All Sides ..................................
From Supply Duct ..........................
Recommended Service From Front ..........
(Service for blower, filter if installed)

Low Voltage
Entrance

WITH HEATERS
All Sides ..................................
From First Three
Feet of Supply Duct to Combustibles
........
From Duct after Three Feet .................
Recommended Service From Front ..........
(Service for blower, heaters if installed)

24"

/
15-1/2'' (11/2- 3 Ton) MV08
19-1/8'' (11/2- 3Ton) MV12
22-3/4'' (2- 4 Ton MV16
26-3/8'' (31/2 - 5 Ton) MV20

0"
0"
20"

0"
1"
0"
20"

Fire Hazard

Bottom Return Air Opening
14-3/8"
X 20"
MV08
18" x 20"
MV12
21-5/e'x20"
25-1/4 '' x 20

MV16
MV20

When heaters are installed maintain clearances from combustible materials as specified on unit rating plate. Do not use plastic
lined or combustible flexible ducting within 36
inches of the supply end of the air handler.
Failure to do so can result in fire, property
damage, personal injury and/or death.

GeneralInformation

Installation or repairs made by unqualified persons can
result in hazards to you and others. Installation MUST
conform with local building codes and with the
National Electrical Code NFPA70 current edition.
The information contained in this manual is intended
for use by a qualified service technician familiar with
safety procedures and equipped with the proper tools
and test instruments.
Failure to carefully read and follow all instructions in
this manual can result in equipment malfunction,
property damage, personal injury and/or death.

_J

The blower cabinet may be used for cooling or heat pump
operation with or without electric heat. Installations without
electric heat, require a No Heat Kit. The cabinet can be installed in
an upflow, downflow or horizontal position (Figure 3, 4).

Location
Select the best position which suits the installation site conditions.
The location should provide adequate structural support, space in
the front of the unit for service access, clearance for return air and
supply duct connections, space for refrigerant piping connections
and condensate drain line connections. If heaters are being
installed make sure adequate clearance is maintained from
supply ductwork, See Clearances and Warning in Figure 1.
Ifthe unit is located in an area of high humidity, nuisance sweating
of casing may occur. On these installations a wrap of 2" fiberglass
insulation with a vapor barrier should be used.

442 01 2303 02

I Modular Blower

Installation

Instructions

Installations
The unit is ready to install

in any position

without

modifications.

Figure

Refer to the coil instructions
for information
on drain pan
configurations
etc. Make sure coil is set up properly for desired
position of blower cabinet.
Coil must be secured to blower cabinet with the three tabs that are

3

J

Airflow Positions

UPFLOW
POSITION

DOWNFLOW
POSITION

HEAleR

part of the blower cabinet base. Bend the tabs out from the bottom
so they fit over the coil cabinet.

Position coil cabinet in relation to the blower so they will be correct
for desired application.
For upflow
and horizontal
around top of coil cabinet.
seal strip around bottom of
cabinet so they are flush.
three tabs on the bottom of

applications
apply foam seal strip
For downflow
application
apply foam
coil cabinet.
Set blower on top of coil
Secure cabinets together
using the
the cabinet. Bend the tab out from the

bottom so it fits over the coil cabinet.
drill a hole as required for a screw.

If no pilot holes are present,
HEA'_R

Figule 2

1

Subbase

Attach Coil to Blower Cabinet
Panels removed
for clarity only

4

i

Downflow Installations
Refer to instructions

Place seal
on top of
Cabinet
around
perimeter

with Subbase

Kit.

Non-Ducted Return Air Closet Installation
The cabinet

can be installed

in a closet with a false bottom

to form

a return air plenum, or mounted
on an open platform
inside the
closet. Platform should be high enough to provide a free (open)
area for adequate
return airflow into the bottom of the cabinet.
The open area can be on the front side or a combination
of front
and sides, providing
there is clearance
on the sides between
cabinet and closet. Refer to ACCA Manual D for sizing and free
area recommendations.
NOTE:
ducted

Local codes may limit application
return to single story dwellings.

of systems

without

a

Horizontal Left and Right Installations
Bend Tabs (both sides
and back) on Bottom of
Blower Cabinet to Fit
over Coil Cabinet

Coil cabinets
that are shipped
with the horizontal
drain pan
installed are set up for horizontal
left hand airflow. They must have
the drain pan repositioned
for right hand airflow. Refer to coi!
installation
manual.

CAUTION
Afield fabricated
auxiliary drain pan, with a separate drain is
REQUIRED
for all installations
over a finished living space or
in any area that may be damaged
by overflow from the main
drain pan. In some localities,
local codes require an auxiliary
drain pan for ANY horizontal
installation.

442 01 2303

02

3L_

_ Installation

Modular Blower I

Instructions

Duct Connections

1

Airflow Positions

Supply Duct
Supply duct must be attached to the outside of flange on outlet
end of unit, Flexible connectors may be used if desired. Maintain
clearances from supply duct to combustibles when heaters are
installed. See Figure 1 and unit rating plate.
Return Duct

HORIZONTAL RIGHT POSITION

Return duct should be attached to bottom of unit using sheet
metal screws or other fasteners.

Filter Installation
Filters must be field supplied. A remote filter grille or other means
must be provided.
Refer to ACCA Manual
D for remote filter
sizing.

HORIZONTAL LEFT POSITION

.o ,zon,a,
o'0
See Note
Below

Suspended Cabinet Installation
1. The cabinet may be supported
be suspended.

on a frame or shelf, or it may

2. Use metal strapping
or threaded
rod with angle iron
supports under the auxiliary drain pan to suspend cabinet.
These supports
MUST run parallel with the length of the
cabinet (Figure 5 ).
3. Ensure
access

that there is adequate
panels after installing

4. Place Styrofoam
cabinet.

blocks

room to remove service
supporting
brackets.

in auxiliary

drain

and

pan to support

Lines
Refrigerant
Lines
_Styrofoam

Field-Fabricated
locks

Supports

MUST

run parallel

Drain Pan
with blower

cabinet

NOTE
If increased
structural
strength
is needed
in the horizontal
position, use the two connecting
plates that are shipped with the
Multipoise
Coil Cabinet in place of the tabs on the bottom of the
blower.

_J

442 01 2303 02

I

Modular

Blower

Installation

Instructions

ElectricalConnections
Connect field wiring to appropriate
terminals on electric
lugs on the No Heat Kit. All line voltage connections
made with copper wire.

Electrical shock hazard.

heater or
must be

LineVoltageConnection
Turn OFF electric power at fuse box or service
panel before making any electrical connections
and ensure a proper ground connection is made
before connecting line voltage.

1. Provide line voltage power supply
separate
circuit(s).
Size per table
electric heater manual.

Grounding Connection

All electrical work MUST conform with the requirements
of local
codes and ordinances
and the National Electrical Code NFPA 70
current edition.

Use a copper conductor(s)
from the ground lug on the No Heat Kit
or ground lugs on the electric heater to a grounded connection
in
the electric service panel or a properly installed grounding
rod.

The low voltage transformer
and the fan control are standard on
all models
and are prewired
at the factory.
Line voltage
connections
are made to the heater accessory or the lugs on the
No Heat Kit.

Figure

Overcurrent Protection

6

I Electrical

Controls

Low Voltage

For blower
used.

cabinets

without

unit MUST be provided
with
codes may require this to be

heaters,

a 15 amp

circuit

from a
table in

2. Connect line voltage to the lugs on the No Heat Kit., or to
circuit breakers or wire leads from heaters. Refer to Figure
6 and wiring diagram.

Failure to do so can result in property damage,
personal injury and/or death.

The power supply wiring to the
overcurrent
protection.
Governing
fuses ONLY or circuit breakers.

(208V-240V)
below or the

Matching Receptacle

Connections

_

For No Heat Kit
or Electric Heater

may be

No Heat Kit Installation
If electric

heat is not used,

1. Locate
adapter
package.
2. Attach adapter
match cabinet,
3. Secure

install

and

accessory

filler

plates,

No Heat Kit.
with

screws

Filler Plate
inside
Adapter

plate and filler plate to bracket
Refer to Figure
6.

the No Heat Kit accessory

if required

Plate

\

to
No Heat Kit

with four screws.

4. Connect
the plug from No Heat Kit wiring
into the
receptacle
on the control board on the side of the cabinet.

CAUTION
Do not attempt

to force

plug as it only fits one way.
Lugs for
Line Voltage
and Ground
Connections

Line Voltage Connections
Line voltage wiring may be brought into the unit through the top
right-hand corner. A hole for a 1/2" or 3/4" conduit fitting is
provided.

Recommended

Maximum

Supply Circuit

Overcurrent

Supply Wire
75ec. Copper

Supply

Nominal

Maximum

Branch

Protective

Circuit

Motor
H,P.

Motor

Total

Circuit

Device

AMP$.

AMP$.

Ampacity*

(AMP$.)

No.

Size

Length (Ft)

No.

Size

Ground

Max.

Wire

Volts

Phase

Hertz

No,

240

1

60

Single

1/2

33

33

3.8

15

2

14

104

1

14

208

1

60

Single

1/2

33

33

3.8

15

2

14

90

1

14

240

1

60

Single

1

66

66

6.9

15

2

14

104

1

14

208

1

60

Single

1

66

66

6.9

15

2

14

90

1

14

* Based on maximum ampacity allowed by Magellan control program.

442 01 2303

02

5L_

_ Installation Instructions

Modular Blower I

LowVoltage Control Connections

Adjusting ThermostatAnticipator

The 24 volt power supply is provided by an internally wired low
voltage transformer which is standard on all models. If power
supply is 208 volt, the low voltage transformer must be rewired to
the 208 volt tap. See the unit wiring label.

Set the heat anticipator
instructions
provided
adjustment.

Field supplied low voltage wiring enters the unit on the top left
hand corner.
Install the strain relief bushing (supplied with unit) in the hole.
Connect the field wiring at the screw terminals of the control
board. Refer to Figure 6.
Keep the low voltage wiring as short as possible inside the control
box.
Complete connections between indoor blower, outdoor section,
indoor thermostat and electronic outdoor thermostat (accessory)
according to instruction provided with the Condenser Installation
Instructions or those provided with the accessory and refer to
Figures 7 and 8.

Figure 7

[ Typical Low Voltage Schematic

Cooling Only

--

W

O0
W2 W 1

J
0

G

Adding Humidistat or Outdoor Thermostat
Adding a humidistat
or outdoor thermostat
allows the airflow to be
reduced
to 80% of normal
allowing
greater
humidity
control.
Humidistats
are preferred but an outdoor thermostat
can be used
but can only be set based on temperature.
Suggested
starting
point is 85 °F, but this will vary depending
on several factors.
The control must be wired differently
on air conditioners
and heat
pumps.
On air conditioners
connect
to Y and H (Dehum)
terminals,
ref Figure 7.

HEAT PUMPS ONLY: Heat pumps must use only the outdoor
thermostat, because it is powered instead of just performing a
switching function. This allows it to be out of the circuit when
continuous circulation is desired, which is required for the system
to operate on Fan Only for circulation, which is 60% airflow. On
heat pumps connect to Y and H (Dehum) terminals, and C and O
to power the outdoor thermostat, ref Figure 8.

The heater elements are turned on in increments.
Refer to Heater
Staging Table in the Heater installation
Manual. In addition on
heaters larger than 5KW, the heat can be staged (1 st & 2nd) either
through an indoor thermostat
or by using an outdoor thermostat.
This satisfies
staging requirements
imposed
by some electric
utilities on heaters larger than 6 kilowatts.

Outdoor Unit

R

Y

See
this

ElectricHeater Staging

Thermostat

G

of the thermostat
to the proper value.
with the thermostat
before making

Y
Y

A control signal (24V) from Wl on the Indoor T'stat to Wl on the
control board energizes
the 1st stage of heat. A control signal
(24V) to W2 on the control board energizes
the second stage of
electric heat. To turn ON both stages atthe same time, using one
control signal, W1 and W2 are jumpered
together.

0

Y 0
H
Indoor Blower

()

() /

C

R

If the indoor
thermostat
does not have staging
capabilities,
accessory
electronic
outdoor thermostats
are available that will
control two stages of electric heat.

J

Motor Speeds and Airflow
Air Conditioner - Adding Control for 80% Airflow

See

Figure

g and

Pages

8 & g,

The motor speed can be set on one of eight speeds and the air
flow will adjust between
60%, 80% and 100% depending
on
settings. Time ON / OFF settings can also be adjusted.

lo oololoo
W2 W 1

G

Y 0
H
IndoorBlower

C

R

Determine
coil static pressure
drop,
measure
duct system static pressure,
speed setting from blower charts.

consult
coil manual and
then determine
required

For Cooling - Set switches 6, 7, and 8 on the motor end bell to
position 0 (off) or 1 (on) as specified on blower charts.
For Heating - Set switches 3, 4, and 5 on the motor end bell to
position 0 (off) or 1 (on) as specified on blower charts.

Humidistat or Outdoor Thermostat

Set switches
1 and 2 to position 0 (off) or 1 (on) as specified
Figure 9 to control Fan delay ON - OFR
NOTE:
switch

_J

in

Power must be completely
OFF to unit any time
settings are changed or settings will not take effect.

442 01 2303 02

I Modular Blower

Figure

8I

Installation

Instructions

Typical Low Voltage Control Schematic
L

Staging

Cooling with Electric Heat

Heat Pump with Electric Heat

_ermostat
R

Thermostat

R

R
BL

G

--

Y
Outdoor

W

o t

Y

Unit

--

y

Outdoor

Unit

W 2

t

C
r

o,ndJ[
rB,Oower C

R

w

Air Conditioner - Adding Control for 80% Airflow

o oooo

W 2 W 1

G

Y

Indoor

0

H

C

Heat Pump - Adding Control for 80% Airflow

R

Blower

W 2 W 1

G

Y
Indoor

0

H

C

R

Blower

Humidistat or Outdoor Thermostat
Outdoor Thermostat

Figure

9[

Motor Speeds
See next page for switch positions and CFM range
Heat
CFM
Select

Time
Delay Select

=1

Cool
CFM
Select

=

II

=

I
1 Positions

1

2

3

4

5

6

7

(on)

8
0

Switch (off)

Available Selections:
Time Delays:
00 0 sec. on/60 sec. off (default)
01 0 sec. on/90 sec. off

Motor Controller mounted to blower housing

10 0 sec. on/30
11 0 sec. on/0

442 01 2303

02

sec. off
sec. off

7L_ J

Modular Blower I

_ Installation Instructions

Airflow and Motor Speeds

NOTE:
Both sets of
switches must be set

MVO8B1500A
Dip Switch Settings
are set at switches
6, 7 and 8 for
Cooling, 3, 4, and 5
for Heating.

14OO
1200
1000
,,

Dip Switch Settings

800

000 Highest Speed
111 Lowest Speed

0

6OO
4OO

/

i

/

i

/

i

0.2

0.3

0.4

0.5

0.6

0.7

External

Static

2OO
0.1

For Heat Pumps both
sets of switches should
be set the same.

0.8

For electric heat the
heat switches can be set
to obtain a comfort level
within the specified heat
rise of the unit.

MV12F1900A Airflow
1600
I

I

0.2

0.3

I

I

I

I

I

I

0.8

0.9

I

1500
1400
1300
1200
1100
1000
900
800
700
6OO
5OO
4OO
0.1

0.4

0.5

0.6

0.7

1.1

External Static

442 01 2303 02

I Modular Blower

Installation

Airflow and Motor Speeds

Instructions

NOTE:
Both sets of
switches must be set

MV16J2200A Airflow

Dip Switch Settings
are set at switches
6, 7 and 8 for
Cooling, 3, 4, and 5
for Heating.

2100,
2000,
1900,
1800,
1700,
1600,
1500,

Dip Switch Settings

1400,
,,_ 1300,

000 Highest Speed
111 Lowest Speed

1200,
1100,
1000,
900,

For Heat Pumps both
sets of switches should
be set the same.

800,
700,
600,
500,
4OO
0.1

0.2

0.3

0.4

0.5

0.6
External

0.7

08

0.9

1.1

0.8

0.9

1.1

Static

For electric heat the
heat switches can be set
to obtain a comfort level
within the specified heat
rise of the unit.

MV20N2600AAirflow
2200'

7

T

2100'
2000'
1900'
1800,
1700,
1600,
1500,
1400,
1300,
O3

1200'
t100'
1000,
900'
800'
700,
600,
500,
400

0.2

0.1

0.3

0.4

0.5

0.6

0.7

External Static

442 01 2303

02

9L_

_ Installation Instructions

Modular Blower I

Air Flow Check

TemperatureRise Check

For proper system operation,
the air flow through the indoor coil
should be between 350 and 450 cfm per ton of cooling capacity.
The air flow through the unit can be determined
by measuring the
external static pressure to the unit and selecting the motor speed
tap that will most closely provide the required air flow.
1. Set up to measure
external
and return duct connections

static pressure
(Figure 10).

2. Drill holes in the ducts for pressure
taps,
other accurate pressure
sensing devices.

NOTE:
heating

or

Figuie ! 0

J

rise

ALL

greater

registers

3. Set thermostat

_?

5. Turn electric

60

and return

by changing
block.

OF (33.3

°C)

the

is

not

and duct dampers.

power

NOTE:

8. Turn electric

LEAST

5

as high as it wil! go.

minutes,

air temperature

to normal
power

to HEAT.

setting

ON.

The maximum
outlet
is 200 OF (93.3 °C).

7. Set thermostat

selector

temperature

6. Operate
unit
AT
temperature
rise.

Indoor
Section

than

Heat-Cool

4. Set the thermostat

s p,,r

the supply

1. To check the temperature
rise through
the unit, place
thermometers
in the supply and return air ducts as close to
the unit as possible.
2. Open

Static Pressure Check

between

The temperature
rise can be adjusted
speed tap at the unit's blower terminal

A temperature
recommended.

at the supply
pitot tubes,

Temperature
rise is the difference
air temperatures.

temperature

then

check

for all models
setting.

OFE

9. Be sure to seal all holes in ducts if any were created
this process.

during

Maintenance
Filters
3. Connect
gauge.

these taps to a level inclined

4. Ensure the coil and filter are clean,
open.
5. Determine
operating.

the

external

static

manometer

or draft

and all the registers

are

with

the

blower

The bearings of the blower motor are permanently

6. Refer to the Air Flow Data tables, page 8 to find the Dip
Switch Speed setting that will most closely provide the
required air flow for the system.

8. Recheck the external static pressure
and confirm speed switch selection.

1_

must be cleaned when they become dirty. Inspect at least
per month. The frequency
of cleaning depends
upon the
of operation
and the local atmospheric
conditions.
Clean
keep unit efficiency
high.

Lubrication

pressure

7. Refer to Motor Speeds and Airflow
the speed is to be changed.

Filters
once
hours
filters

in these

instructions

with the new setting,

if

lubricated.

Condensate Drains
During the cooling season check the condensate
drain lines to be
sure that condensate
is flowing from the primary drain but not
from the secondary
drain. If condensate
ever flows from the
secondary
drain the unit should be promptly
shut off and the
condensate
pan and drains cleaned
to insure a free flowing
primary drain.

442 01 2303 02

I Modular Blower

Installation

BASE LIMIT OPTIONAL
NO-HEAT
KIT AMFOO1NH
INSTALLED
*SEE INSTALLATION
MANUAL
FOR PROPER
HEATING
AND COOLING
FACTORY
PRF-RFT
RPFFI3
CONNFCTIONR
FOR YOI JR I JNIT

B

I_ o_,Io

II

AMFK2OAH

ELECTRIC

Instructionsl

HEATER

--

_ Ln

"II

5 Kw

B___

_ '----"_L,M,T
IV _-r_
GRD

BKT"_

B_HI

Y
AMFK05AH

ELECTRIC

B_'d.L
_
',ILL

--1

r'_

L,J,.v
__ __il_ BK.

HEATER

,_,_
A

--I

7.5&

10 Kw

L,J_I
a___GZI

R

BK__
'_

,

AMFK07AH

--

/ AM FK10AH

,
ELECTRIC

_'

HEATER

LIMIT

15 Kw

I_

, B_

''-t.._.r'+_---'nl
! p3oip_op3_

,, Lo ,_ Tv
,y

BK

AMFK14AH

ELECTRIC

HEATER

*AMFK15AH

ELECTRIC

HEATER

442 01 2303

02

gl"
BK'

t2 LIMITS)

AMFK30AH

ELECTRIC

HEATER

1087574

Fan Coils I

_ Installation Instructions

ReplacementParts

KEY
NO.

DESCRIPTION

PART
NUMBER

_
_

Q

O

_
_

_
_

9
10

Control, Fan Timer
Transformer

1085914
1082611

I
I

1
1

11
1I

Motor, Blower

I012478
1012479

I

1

12
12

Mount,

1086700
1057955

I

13

Wheel,

Blower

Motor

Blower

600586

13
13
14
14

Control,

Motor

FI
F2

Panel, Side (Right)
Panel, Rear

I
I

1085863
1085864

F3
G
G

I

1069603
1069604

I

G

1069606

O
O

Panel,

Rear Blower

Deck

I082604
1082844

O

1082845

O

1082846

1

I

1

I

1

I

1

1
1

1

PART
NUMBER

DESCRIPTION

Panel, Front Blower

Deck

1086694
1085372

¢.4

04

¢_1

_
_n

_
,,'7

_
_

z

CO

_1

LO

O

Panel,Side

Blower Deck

1082622
1082847
1082848

Q

1082849
Bracket, Control
Panel, Top

Fan

1085371
1085857
1085865

V
V
W
W

I

1

Housing,

Blower

1087195
1087193

I
1
I
1

Panel, Blower Cutoff

1082607
1082616

1

ZI

Rai!, Blower

Z2
BB
BB

Rai!, Blower L.H.
Door, BIowerAccess

DD
EE
)(
)(

I
2
2
2
2
I
I

1

R.H.

I
I
1

1
I

I

1

I

I

1085521
1085856
1085858

I
I

1

I

I

Harness,
Harness,

1087049
1087519
1087518

Harness,
Manual,

Wire
Installation

I

I

1084606
1084608

)(

I
I

1085504

Plate, Heater Adapter
Plate, Heater Filler

)(

I

I

1

1085859
1085860

Wire
Wire

I

1

1082949

BB
BB

I

I

1087194

X
1

1

1085866
1085867

W
X
X

I

1085373
1085374

Q
R
V
V

1

1085855

1069605

Q
Q

1

I

Brace,

G

1

P
P

1

Panel, Side (Left)
Bottom

P
P

1

1085854
1085861
1085862

1
1

I

I

F2
F2

I
I

I

1012476
1012477

F2

KEY
NO.

I

600587
96839

¢_
Q

44201230300

I
I
1

1
I

I
I

I
I

1
1

I
I

I
I

I

1

I

I

I

1

I

I

o

R9

10

V

--Q
F2
13
F3

_Jl/

1

BB

G

38-11-26

442 01 2303 01



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 12
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Fri Apr 20 13:19:24 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu