ICP Evaporator Coils Manual LR708241

User Manual: ICP ICP Evaporator Coils Manual ICP Evaporator Coils Owner's Manual, ICP Evaporator Coils installation guides

Open the PDF directly: View PDF PDF.
Page Count: 14

DownloadICP  Evaporator Coils Manual LR708241
Open PDF In BrowserView PDF
I Installation

Instructions

Fan Coils

I

INSTALLATION
INSTRUCTIONS
Models
EBV
2-5 Ton

General Information / Installation

Use ONLY factory listed electric

Variable
Safety

Labeling

2

Upflow Installations ...................
Downflow Installations ................
Horizontal Installations ................
Ductwork Connections ................
Electrical Connections .................
Diagrams .............................
Transformer Information ...............

3
3
3
4
5
6
7

Refrigerant Tubing ....................
Refrigerant Flow Control ...............
Condensate Drains ....................

8
8
9

Condensate Drain Diagrams ...........
Start-Up Procedures ..................
Sequence of Operation ................
Airflow Curve Charts ..................

10
11
13
14

heaters.

Speed
and Signal

Danger, Warning

.......

Fan Coils

Words
Signal

and Caution

The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness.
is only used on product lahazard. The signal words
WARNING and CAUTION will be used on product labels and throughout
this manual and other manuals that
may apply to the product.

Words

in Manuals

The signal word WARNING is used throughout
manual in the following manner:

this

The signal word CAUTION
is used
manual in the following
manner:

this

The signal word DANGER
bels to signify an immediate

DANGER
severe

- Immediate

personal

hazards

which

WILL

result in

injury or death.

WARNING COULD result

Hazards
in severe

or unsafe
practices
which
personal injury or death.

CAUTION COULD result

Hazards
in minor

or unsafe
practices
which
personal
injury or product or

property

throughout

Product

Labeling

Signal words are used in combination with colors and/or
pictures on product labels.

damage.

496 01 4113 03
June 2005

I Installation

Figure

Instructions

1

Fan Coils

J Clearances&

I

Dimensions

Unit Sizes
2400
3600
4800
6000

A
15-3/4"
19-1/4"
19-1/4"
22-3/4"

B
11"
11"
11"
11"

C
1_1_1_'
1_1_1_'
1_1_1_'
1_1_1_'

D
15-5/8"
19-1/8"
19-1/8"
22-11/16"

E
F
22-1/16" 17-5/8"
22-1/16" 21-1/8"
22-1/16" 21-1/8"
22-1/16" 24-11/16"

G
47-11/16"
53-7/16"
53-7/16"
59-3/16"

CLEARANCES
NO HEATERS
All Sides ...................................
From Supply Duct ..........................
Recommended Service From Front ..........
(Service for blower, filter if installed)

0"
0"
20"

WITH HEATERS
All Sides ..................................
0"
From First Three Feet of Supply Duct to Combustibles ......................................
1"
From Duct after Three Feet .................
0"
Recommended Service From Front ..........
20"

Fire Hazard
When heaters

are installed

maintain

clearances

from combustible
materials as specified on unit
rating plate. Do not use plastic lined or combustible
flexible ducting within 36 inches of the supply end of
the air handler.
Failure to do so can result in fire, property damage,
personal injury or death.

General

Information

Installation or repairs made by unqualified persons
can result in hazards to you and others. Installation
MUST conform with local building codes and with the
National Electrical Code NFPA70 current edition.
The information

contained

in this manual

is intended

for use by a qualified
service
technician
familiar
with
safety
procedures
and equipped
with
the proper
tools and test instruments.

Failure to carefully read and follow all instructions in
this manual can result in equipment malfunction,
property damage, personal injury and/or death.

The blower cabinet may be used for cooling or heat pump operation with
or without
electric heat. The cabinet can be installed in an upflow or
horizontal
position (Figure 2, 3). EBV models are shipped with the horizontal kit already installed.

Location
Select the best position which suits the installation
site conditions.
The
location should provide adequate structural support, space in the front of
the unit for service access, clearance for return air and supply duct connections,
space for refrigerant
piping connections
and condensate
drain line connections.
If heaters are being installed
make sure adequate clearance
is maintained
from supply ductwork,
(see Fig. 1).
NOTE: Internal
filter can be accessed from separate filter door.
filter can NOT be easily accessed, a remote filter is recommended.
fer to ACCA Manual D for remote filter sizing.

If the
Re-

If the unit is located in an area of high humidity, nuisance
sweating of
casing may occur. On these installations
a wrap of 2" fiberglass
insulation with a vapor barrier is recommended.

UJ

Installation

i Fan Coils

Instructions

INTRODUCTION
The EBV model

is designed

for flexibility

Slope

and can be used for upfiow,

Coil Unit In Upflow

Application

horizontal,
or downfiow (kit required) applications.
These units are available for systems of 24,000 through 60,000 Btuh nominal cooling capacity. Factory authorized
electric heater packages are available in sizes 5

SUPPLY

through 30kw. See Product
sory kits.

ENTRY
OPTIONS

HEATER

Specification

Literature

for available

DUCT

acces018-06021

PACKAGES

IN,

070

FRONT

24-1N

SERVICE

CLEARANCE

Unit

A factory approved,
field installed UL listed heater package is available
from your equipment
supplier.
See unit rating plate for a list of factory
approved
heaters. Heaters that are not factory approved
could cause

A

2400-3600
4200-6000

17 in
19 in

UPFLOW/DOWNFLOW

damage

which

would

not be covered

under

the equipment

warranty.

½-

INSTALLATION
FIELD

PROCEDURE
Unpack

1 - CHECK

EQUIPMENT

unit and move to final location.

A

Remove

carton

taking

SLOPE
UNITS

care not

to damage unit. Inspect equipment
for damage prior to installation.
claim with shipping company
if shipment is damaged or incomplete.

File
Lo-

UP

2- MOUNT

To ensure

be installed

proper

drainage

so it is within

A. Upflow

UP

ceiling

for horizontal

or wall. Allow

installations,

118 in. level of the length

If return air is to be ducted, install
over opening. Only use return-air

B. Modular

DRAIN

FLOW/DOWNFL
PRIMARY

and width

NOTE:

space

unit must
of unit.

DRAIN

For

optimum

condensate

drainage

duct flush with floor. Set unit on floor
opening provided. All return air must

the coil. (See Fig. 2.)

dates

small scuttle

holes

D. Horizontal-Right
NOTE: Gasket
coil conversion

Units

and limiting

Conversion

box and blower
To disassemble

3. Remove coil assembly.
4. Lay fan coil on its right side and reinstall

2

to installation

with

Slope

blower and coil access panels
screw securing coil assembly

coil assembly

with conden-

screws which secure brackets.
(See Fig. 4) Remove either 2 screws in
each front corner of coil box, or 2 screws in blower box. Do not remove
all 4 screws in each corner. (See Fig. 4) Sections may now be separated
by lifting top section from lower section. To reassemble,
reverse above
procedure.
Be certain to reinstall all fasteners when reassembling.

6. Make sure the pan cap in the fitting door is properly seated
ting door to retain the low air leak rating of the unit.

C. Horizontal

7. Add gaskets

Be sure installation
require installation

complies with all applicable building
of secondary
condensate
pan.

1. Arrange support
sate drain.

for unit by setting

it in or above

codes

secondary

that may

conden

6. Align

holes

unit from ceiling, dimples in casing indicate proper
for mounting
metal support straps (See Fig. 3)

this caution

may result

in property

damage.

or in any area that may be damaged
by overflow
from a restricted
main drain pan. In some localities,
local codes
require

an auxiliary

drain

pan for

ANY

horizontal

installation.

and condensate

pan connec-

Install

sweating.
Right

after brazing.

Conversion

1. Remove

blower

2. Remove

metal clip securing

of Units

and coil access

panel

fitting

With

A-Coil

and fitting

panel.(See

panel to condensate

Fig. 6).

pan. Remove

panel.
2 snap-in

clips

securing

A-coil

in unit.

out of unit.

5. Remove horizontal drain pan support bracket from coil support rail on
left side of unit and reinstall on coil support rail on right side of unit.
6. Convert

A field fabricated
auxiliary
drain pan, with a seperate drain is
REQUIRED
for all installations
over
a finished
living space

per kit instructions.

connections

4. Slide coil and pan assembly

to follow

on the fit

cabinet

fitting

Failure

previously

access panels and fitting panel. Make sure liquid
grommets
are in place to prevent
air leaks and

3. Remove

UNIT or PROPERTY DAMAGE HAZARD

screw

tions, and reinstall
and suction tube

E. Horizontal
2. When suspending
location of screws

from kit EBAC01GSK
with tubing

slope

and fitting panel. (See Fig. 5.)
to right side casing flange.

sate pan down. (See Fig. 5.)
5. Attach coil to casing flange using coil mounting
removed.

Installation

sites.

Coils

kit number EBAC01GSK
is required for horizontal
to maintain
low air leak/low sweat performance.

1. Remove
2. Remove

(See Fig. 4)
brackets
by removing

in hori-

and components
moved
This process accommo-

entrances

of Units

The EBV Fan Coil in size 6000 is a 2-piece
modular
unit. Modular
construction
allows installer to disassemble
unit into 2 components,
coil
box, for ease of installation.
unit, remove
rear
corner

performance

zontal installations,
unit should be leveled
along it's length or
raised 1/4" at the air inlet. The unit should
also be pitched forward
1/4" to 1/2" toward the front condensate
drains.
NOTE: Modular
units can be disassembled
separately
to installation
area for reassembly.

Installation

pass through

COIL
ONLY

--

FAN COIL

Unit can stand or lie on floor, or hang from
for wiring, piping, and servicing unit.
NOTE:

FLOW/DOWNFLOW
SEOONDARy

cate unit rating plate which contains
proper
installation
information.
Check rating plate to be sure unit matches job specifications.

PROCEDURE

MODIFIED

SIDE
RETURN
LOCATION
FOR

air-seal

A. Remove

assembly

air-seal

for horizontal

assembly

right. (See

from coil by removing

B Remove coil drip flanges from A-coil and reinstall
coil (same side as horizontal
drain pan).
C. Remove
plate.

filler

plate (A) and install

air splitter

Fig. 6).
4 screws.
on right side of

(B) in place

of filler

I Installation

Instructions

D. Install filler
E. Remove
sheets.
R install
7. Install
8. Slide

plate (A) as shown

condensate

in horizontal

troughs

hose onto plastic

horizontal

(C) and

right application.

install

3. Recommended

on opposite

spout.

into casing.

pan engages

Be sure coil bracket

coil support

structure
coil.

horizontal

11. Remove

insulation

12. Reinstall

access

PROCEDURE

knockouts
fitting

on right side of coil access

panels,

aligning

holes

with tubing

leaks and cabinet
F. Downflow

tube grommets

are in place

and

Mobile

Home

2. Allow

a minimum

Figure3

Housing

of 24" clearance

from

to prevent

Metal

Instruc-

3-AIR

screws

and to wall stud using 5116-in.

NA

DUCTS

FIELD
SUPPLIED
HANGING

STRAPS

install

factory

authorized

accessory

Acoustical

duct systems

construction

standard

on fibrous

glass ducts.

Left Application

_

_,_]

018-060

I 6F

21-IN.

UNIT)

LOW VOLT
ENTRY
OPTIONS
_

(FULL

I
I

-t1_,
F_/__ll
"_'.._.)_J.!_

DRAIN
SECONDARY
ENTRY

UJ

DRAIN
OPTIONS

space

Treatment
that do not have a 90 degree

FRONT
SERVICE
CLEARANCE

POWER

kit.

elbow

and 10 ft. of

Both acoustical

and fibrous ductwork shall comply with National Fire Protection
tion as tested by UL Standard
181 for Class 1 air ducts.

panels.

UNIT

lag

main duct to first branch take off may require internal acoustical
insulation lining.
As an alternative,
fibrous
ductwork
may be used
if
constructed
and installed in accordance
with the latest edition of SMAC-

Slope Coil In Horizontal

]

both sides of fan

discharge
connection.
Ductwork
passing through unconditioned
must be insulated and covered with vapor barrier.

air

using field-supplied

access

Typically

Use flexible connectors
between
ductwork and unit to prevent
transmission of vibration. When electric heater is installed, use heat-resistant material
for flexible
connector
between
ductwork
and unit at

metal

Applications

to the structure

lag screws.

required,

Ductwork

1. Fan coil unit must be secured
hardware.

5/16-in.

connec-

Installations

G. Manufactured

applications

panel

sweating.

To convert units for downflow
applications,
refer to Installation
tions supplied with kit for proper installation.

for typical

Connect supply-air
duct over the outside of 3/4-in. flanges provided on
supply-air
opening.
Secure duct to flange, using proper fasteners
for
type of duct used, and seal duct-to-unit
joint. If return-air
flanges are

into holes on left

tions and condensate
pan connections.
Be sure to reinstall
clip between fitting panel and vertical condensate
pan.
Make sure liquid and suction

using

ing No. 10 self tapping
screws. (See Fig. 9).

pan.

10. Remove 2 oval coil access panel plugs and reinstall
side of coil access panel and fitting panel.

of securing

b. If fan coil is against wall, secure fan coil to wall stud using
1/8-in. thick right-angle
brackets.
Attach brackets to fan coil us

on each corner

rails.

9. Reinstall 2 snap-in clips to correctly position and secure coil assembly in unit. Be sure clip with large offsets is used on right side of unit
to secure

method

I

a. If fan coil is away from wall, attach pipe strap to top of fan coil
using No. 10 self tapping screws. Angle strap down and away
from back of fan coil, remove all slack, and fasten to wall stud of

tube

pan on right side of coil assembly.

coil assembly

of vertical

Fan Coils

FAC i

FtLTERACCESS
CLEARANCE

lining

Associa-

I Fan Coils

Installation

Figure 4

Instructions

J

' Ure1

Removal of Brackets on Modular Units

Conversion
Horizontal
Applications for
Using
a SlopeRight
Coil

COiL MOUNTING

BLOWER
ASSEMBLY

{

EWS
I
COIL
RAIL

BRACKET

2 SCREWS
COiL

SLOPE COIL,
SKI

80X

"PRIMARY
CONNECTIONS

-OVERFLOW
' SECONDARY

PROCEDURE 4-ELECTRICAL

DRAIN

CONNECTIONS

On units with a factory installed disconnect
with pull-out
removed, service and maintenance
can be safely performed
on only the load side of
the control

DRAIN
HOLE

Figure 6

I

ApplicationsC°nversi°n
fOrusingHOrizontalA_coil
Right

package.

CONNECTIONS

-AIR SEAL
ASSEMBLY
HORtZONTAL
RIGHT
APPLICATION

SHOCK and UNIT DAMAGE HAZARD
Failure to follow
this warning
death and unit damage.
Field

wires

on the

line side

could

SUPPORT
RAIL

result

in personal

injury

or
BRACKET

of the disconnect

found

in the fan

coil unit remain
live, even when the pull-out
is removed.
Service
and maintenance
to incoming
wiring
can not be performed
until the main disconnect
switch
(remote
to the unit)
is turned
off. Failure
to do so will result
in electrical
shock
causing

Before

proceeding

voltage,

frequency,

ing plate.
wiring.

personal

See unit

injury

wiring

Make all electrical

label

or ordinances
a separate
located

make certain

are as specified

for proper

connections

unit must have

switch

connections,

and ampacity

any local codes
disconnect
the unit.

COIL_
SUPPORT
RAIL

or death.

with electrical
phase,

SUPPORT
BRACKET

field

high-

in accordance

and low-voltage
with the NEC and

that may apply. Use copper
branch

within

electric

sight

circuit

that supply

on the unit rat-

wire only. The

with a field-supplied

from and readily

accessible

from

HORIZONTAL

RIGHT

SECONDARY
HORIZONTAL

DRAIN
RIGHT

I Installation

Instructions

Fan Coils

I

4" MAX

SECURE
UNIT
AWAY
FAN
FROM
COILTO
WALLSTRUCTURE
PIPE STRAP
(TYPICAL BOTH SIDES)
OR
UNIT AGAINST

WALL

1/8-IN,THICK
ANGLE
MOUNTING
BRACKET
(TYPICAL BOTH SIDES)

HORIZONTAL LEFT

13_
FLOW
BASE KIT

-7

(EBAC)
SECURE UNITTO
ANGLE BRACKET

FLOOR
OR PiPE STRAP

4" MAX

A. Line Voltage
Connections
If unit contains an electric heater,

remove

and discard

power

plug from

fan coil and connect
male plug from heater to female plug from unit wiring harness. (See Electric Heater Installation
Instructions.)
For units without electric heat:
1. Connect
_I 0-;_6_;0£b(1133
VIOSS

208/230v

power

leads

from field disconnect

black stripped leads.
2. Connect ground wire to unit ground

and formation

and

lug.

NOTE: Units installed without electric heat should
sheet metal
block-off
plate covering the heater
duce air leakage

to yellow

of exterior

have a field-supplied
opening. This will re-

condensation.

ELECTRIC SHOCK HAZARD

Failure to follow
this warning
or death and unit damage.

could

result

in personal

injury

Before installing
or servicing
er to system.
There may be

system,
always turn off all powmore than I disconnect
switch.

Turn

power

NOTE:
supply

off

accessory

Before proceeding
voltage, frequency,

heater

if applicable.

with electrical connections,
make certain that
and phase are as specified on unit rating

plate. Be sure that electrical service provided by the utility is sufficient
to handle the additional
load imposed by this equipment.
See unit wiring label for proper field high- and low-voltage
wiring. Make all electrical connections
in accordance
with NEC and any local codes or
ordinances
that may apply. Use copper wire only. The unit must have
a separate
branch
electric
circuit
with a field-supplied
disconnect
switch located within sight from, and readily accessible
from the unit.

Installation

I Fan Coils
B. 24-v Control
CONNECTION

Instructions

System
TO UNIT

(Cooling

Wire low voltage in accordance
with wiring label on the blower. (See Fig.
8, 10, 11, 12, 13 and 14). Use no. 18 AWG color-coded,
insulated
(35

and 1-Stage Heat)

Thermostat

C minimum)
wire to make the low-voltage
connections
between
the
thermostat,
the unit, and the outdoor equipment.
If the thermostat
is lo-

_.

cated more than 100 ft. from the unit (as measured
along the low-voltage wire), use No. 16 AWG color-coded,
insulated
(35 C minimum)
wire. All wiring must be NEC Class 1 and must be separated
from incoming power leads. Refer to outdoor unit wiring
additional
wiring procedure
recommendations.

TRANSFORMER
Transformer
disconnect
connect

instructions

Y

t_Hf_r

I Inif

for any

INFORMATION

is factory-wired
for 230v operation.
For 208v applications,
the black wire from the 230v terminal on transformer
and

it to the 208v terminal.

(See

Air Conditioner

- Adding Control for 80% Airflow

Fig. 14).

HEATER STAGING
The controls are factory circuited for single-stage
operation.
When 2
or 3 stages are desired, remove J2 (Jumper-2)
from the control board.

©^_2_
W 2 W 1 ©G

©O

Y

Indoor

Blower

H ©C O R

(See Fig. 13).

Figure 10

I

Wiring Layout A/C Unit, No Heat
Dehumidistat

Thermostat

Cooling

or Outdoor

Thermostat

Only

R

G

--

Y
Y

Y
W

Outdoor

(Cooling

and 2-Stage

Heat)

Unit

Electric

_2

Heat

Staging

Thermostat

©©
W2 W1 G

Air Conditioner

Y O H
IndoorBlower

- Adding Control for 80% Airflow
*J2 Removed

Air Conditioner

O©O
W2 W 1

O
G

Y O
H
IndoorBlower

- Adding Control for 80% Airflow

OO
C

R

O

O

G

l>

W2 W1 G

Y

Indnnr

O
O

O

Blnw_r

O

H C

*J2 Removed

Dehumidistat
Dehumidistat

or Outdoor Thermostat

or Outdoor Thermostat

O
R

I Installation

C. Ground

Fan Coils

Instructions

I

Set switches 1 and 2 to position 0 (off) or 1 (on) as specified
to control Fan delay ON - OFF.

Connections

NOTE: Power must be completely
OFF to unit any
settings are changed
or settings
will not take effect.

in Figure
time

12

switch

Adding Humidistat or Outdoor Thermostat
ELECTRICAL

SHOCK HAZARD

Failure to follow
fire, or death.

this warning could

Adding a humidistat
or outdoor thermostat
allows the airflow to be
reduced
to 80%
of normal
allowing
greater
humidity
control.
Humidistats
are preferred but an outdoor
thermostat
can be used but
can only be set based on temperature.
Suggested
starting point is 85 F,
but this will vary depending
on several factors.

result in electric shock,

According to NEC, ANSI/NFPA 70, and local codes, the cabinet
must have an uninterrupted or unbroken ground to minimize
personal injury if an electrical fault should occur. The ground
may consist of electrical wire or metal conduit when installed
in accordance with existing electrical codes. If conduit connection uses reducing washers, a separate ground wire must
be used.

NOTE: Use UL-listed
conduit
supply wire(s) to unit to obtain
be accomplished
D. Fan Control

by using
Board

and conduit connector
for connecting
proper grounding.
Grounding
may also

grounding

Jumper

The control
must be wired differently
on air conditioners
and heat
pumps. On air conditioners
connect to Y and Dehum terminals
H, (see
Figure 10).

lugs provided

in control

box.

NOTE:

The fan control board (see Fig. 8) has two jumpers.
Jumper
1 (JP1)
jumpers two of three pins. The control unit should be factory set to the
VS (variable speed) position and should be left in this position in most
cases.
speed replacement
is
a PSC motor until the
can be accessed
by
motor can replace the

Jumper 2 (J2) is used to stage electric heaters. When in place, J2 ties
Wl and W2 together which should be used for single stage heat. When
J2 is removed, it allows Wl and W2 to be controlled separately
and is for
applications
using two stage electric heating.

Figure

thermostat

in the cooling

is not used for this application

and if W

at the same time, the unit will not run. The powered
only allows H to be energized
when the system is

mode.

PROCEDURE

5-REFRIGERANT

Field-supplied

tubing

TUBING

must be of refrigerant

AND

FLOW

grade.

CONTROL

Suction

tube

UNIT DAMAGE
Failure

to follow

HAZARD
this

caution

may

result

in unit

damage.

15

The motor speed can be set on one of eight speeds and the air flow will
adjust between 60%, 80% and 100% depending on settings. Time ON /
OFF settings can also be adjusted.
Determine
coil static pressure
duct
system static pressure,
from blower charts.

drop, consult coil manual
then determine
required

For Cooling/HP
Heating - Set switches
to position 0 (off) or 1 (on) as specified

must

be insulated.
Do not use damaged,
dirty, or contaminated
tubing because it may plug refrigerant
flow-control
device. ALWAYS
evacuate
the coil and field-supplied
tubing to 500 microns
before opening outdoor unit service valves.

Braze with SiI-Fos
or Phos-copper
on copper to copper joints
and wrap a wet cloth around
rear of fitting to prevent
damage
to TXV.

Motor Speedsand Airflow
See

The outdoor

and H are energized
outdoor thermostat

Instructions

If there is a motor or control failure, and a variable
not readily available, it may be necessary
to use
proper part can be ordered.
This "limp mode"
moving JP 1 to the PSC pins. In this position a PSC
VS motor.

HEAT
PUMPS
ONLY:
Heat pumps
must use only the outdoor
thermostat,
because it is powered instead of just performing
a switching
function.
This allows
it to be out of the circuit
when continuous
circulation is desired, which is required for the system to operate on Fan
Only for circulation,
which is 60% airflow. On heat pumps connect to Y
and Dehum terminals
H, and C and O to power the outdoor thermostat
(see Figure 12).

and measure
speed setting

6, 7, and 8 on the motor
on blower charts.

For Electric Heating - Set switches 3, 4, and 5 on the motor
position 0 (off) or 1 (on) as specified on blower charts.

control

control

to

UNIT DAMAGE HAZARD
Failure

to follow

this

caution

If using an EBV model
tion with a single-phase
pressor

hard

start

may

result

in unit

damage.

with field installed
TXV in conjuncreciprocating
compressor,
a com-

kit is required.

I Fan Coils

Installation

_u,e W,.n_.a_out
Heat
Pu_,.o
.oat
Heat

Pump

Staging

Heat Pump Only

Thermostat

R

--R
G

BL
C

w
O

Y
Y

o
W

Outdoor Unit

J2

W2

W1

G
Y O
H
IndoorBlower

C

R

Heat Pump - Adding Control for 80% Airflow

©0o
W2

k
Outdoor Thermostat

W1

G
Y
O
H
IndoorBlower

C

Instructions

J

I Installation
Instructions
Figure !3
Heat

I

Typical Low Voltage Control Schematic For Heat Pumps
Heat Pump with 1 -Stage

Pump

Staging

FanCoils

Electric Heat

Electric
Heat

Thermostat

Heat Pump

R

Staging

Heat Pump with 2-Stage Electric Heat
Thermostat

R

R
G

R

G

BL

BL
C
W

W

O

O
Y
Y

Y

Y
O

O

W
Outdoor

W 1

Unit

Outdoor Unit

W 2

m

* J2 Removed

C
l W

W1

GIndoorY

O
Blower

)

R

H

G
Y
O
H
indoorBlower

C

R

Heat Pump - Adding Control for 80% Airflow
Heat Pump - Adding Control for 80% Airflow

J2

0©000000
W 2

W 1

G
Indoor

O000oo()o
Y

O

H

C

R

Blower
W 2

W 1

G

Y

Indoor

O

H

Blower

* J2 Removed

Outdoor Thermostat
Outdoor Thermostat

llj2J

C

R

I Fan Coils

,gure,, 1

Installation

Instructions

J

Transformer Connections

Heat
CFM
Select

Time
Delay Select

Cool
CFM
Select

I
1 Positions

1

2

3

4

5

6

7

8

0

Switch

(on)

(off)

RED
Time Delays:

BLK

(0,0) = 30 Seconds
(0,1) = 60 Seconds
(1,0) = 90 Seconds (factory setting)
(1,1) = 0 Seconds

UNIT or PROPERTY DAMAGE HAZARD
Failure to follow
PROCEDURE 6-CONDENSATE
Units are equipped

with primary

nections. For proper condensate
7. To prevent property damage

DRAINS
and secondary

approved
condensate
traps
sure to install plastic push-in
It is recommended
pan. Finger-tighten
dope.

Shallow, running traps are inadequate and DO NOT allow proper condensate drainage. (See Fig. 18).
3/4-in.

FPT drain con-

line installations
see Fig. 2, 3, 5, 6 and
and achieve optimum drainage perfor-

mance, BOTH primary and secondary
and include properly-sized
condensate

this caution may result in property damage

drain lines should be installed
traps. (See Fig. 17). Factory-

are available (Kit No. EBAC01CTK1).
Be
plugs in unused condensate
drain fittings.

that PVC fittings be used on the plastic condensate
plus 1-1/2 turns. Do not over-tighten.
Use pipe

When connecting
condensate
drain lines,
cess panel, thus preventing
filter removal.
both primary
NOTE:

When

and secondary
connecting

condensate

condensate

drain

avoid blocking filter acAfter connection,
prime

traps.
lines,

access panel, thus preventing
filter removal. After
both primary and secondary
condensate
traps.

avoid

blocking

connection,

filter
prime

NOTE: If unit is located in or above a living space where damage may
result from condensate
overflow, a field-supplied,
external condensate

I Installation
pan should
condensate

Instructions

Fan Coils

be installed
underneath
the entire unit, and a secondary
line (with appropriate
trap) should be run from the unit into

Recommended

the pan. Any condensate
in this external condensate
pan should be
drained to a noticeable
place. As an alternative to using an external condensate
pan, some localities may allow the use of a separate
3/4-in.

Condensate

condensate
line (with appropriate
trap) to a place where the condensate
will be noticeable.
The owner of the structure
must be informed
that
when condensate
flows from the secondary
drain or external
condensate pan, the unit requires servicing or water damage will occur.

UNIT

2" MIN

Trap

I

I Fan Coils

Figure

Installation

18 I 1 Insufficient

Condensate

Instructions

!

Trap

O

o

{
ER
ACCESS

/

PANEL
SECONDARY DRAIN REQUIRED
(USE FACTORY KITOR
FIELD*SUPPLIEDTRAP)

DO NOT USE SHALLOW RUNNING TRAPS[
PRIMARYTRAP REQUIRED_
(USE FACTORYKIT OR
FIELD-SUPPMEDTRAP OF
SUFFICIENT DEPTH.
STANDARDPRIMARYTRAPS
ARE NOT SUFFICIENT.SEE
RGUREOFRECOMMENEDI_
CONDENSATETRAP)

Install traps in the condensate
the condensate
pan to prevent
area.

Condensate

drain

lines as close to the coil as possible. (See Fig. 19). Make sure that the outlet of each trap is below it connection
to
condensate
from overflowing
the drain pan. Prime all traps, test for leaks, and insulate traps if located above a living

lines should

restrictions or precautions.
PROCEDURE 7-SEQUENCE

be pitched

downward

at a minimum

OF OPERATION

slope

of 1 in. for every

E. Electric

Heat or Emergency

Thermostat
A. Continuous
Thermostat
which
gized,

Fan
closes

R to G. G energizes

fan relay on electronic

completes
circuit to indoor blower motor. When
there is a 90 sec delay before relay opens.

fan board

G is de-ener-

electric

START-UP
Refer

B. Cooling

closes

completes
circuit
through normally
gized,

Mode

Consult

local codes

for additional

Heat Mode

R to W. W energizes

electric

heat

relay(s)

which

to heater element(s).
Blower
motor is energized
closed contacts
on fan relay. When W is de-ener-

heat relay(s)

opens.

PROCEDURES

to outdoor

structions

10 ft of length.

unit installation

and refrigerant

charging

instructions
method

for system

start-up

in-

details.

Thermostat
energizes
R to G, R to Y, and R to O (heat pump only). G
energizes
fan relay on electronic
fan board which completes
circuit to
indoor

blower

before

fan relay opens.

C. Heat

motor.

Pump

Thermostat

When

Heating

energizes

G is de-energized,

there

is a 90 sec delay

UNIT DAMAGE HAZARD
Failure to follow this caution
may result
performance
or unit damage.

Mode
R to G and R to Y. G energizes

tronic fan board which completes
circuit to indoor
G is de-energized,
there is a 90 sec delay before

fan relay on elec-

blower motor. When
fan relay opens.

plied
CARE

Thermostat
energizes
R to G, R to Y, and R to W. G energizes fan relay
on electronic
fan board which completes
circuit to indoor blower motor.
W energizes

electric

heat relay(s)

which

completes

ment(s). When W is de-energized,
electric
off heater elements. When G is de-energized
fore fan relay opens.

circuit to heater

ele-

heat relay(s) open, turning
there is a 90 sec delay be-

unit

operation,

Never operate unit without a filter. Damage to blower
motor
or coil may result. Factory
authorized
filter kits must be used
when locating
the filter inside the unit. For those applications
where

D. Heat Pump Heating with Auxiliary Electric Heat

in poor

access
filter
AND

To continue

must

to an internal

filter

be installed

is impractical,

in the

return

duct

a field-supsystem.

MAINTENANCE
high performance

and minimize

possible

equipment

failure,

it is essential that periodic maintenance
be performed
on this equipment. Consult your local dealer as to the proper frequency
of maintenance contract.
The ability to properly
perform
maintenance
on this
equipment
requires
certain mechanical
skills and tools. If you do not
possess
these, contact
your dealer
for maintenance.
The only consumer service recommended
ing on a monthly basis.

or required

if filter replacement

or clean-

I Installation

Instructions

Fan Coils

I

Airflow Curves

EBV2400B

EBV3600B

1200

1600

1100

_

"_"

1000
900

_
-_

_
_
_

8OO

_

_

_

__

_'_

_
_
_

700
600

_'_

_

"'--,.,,

500

1400

000

_

_

r_t

_

olo

_

011

1200

1000
_"'_

_

_
_

_

_

800

1oo

--_

"_"_

_

"_'_-_

101

400

_

O0q
010

_

o11
1oi

_

111

110
111

200

400
0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0.1

0.2

0.3

External Static Pressure

0.4

___. _

_

_
_ _

_
_._
_

__._._

0.2

0.3

0.4

0.5

0.6

0.8

0.9

1.0

_

001

_
_""__

010
011
IO0
101

o

_

_._

_

_

0.7

0.8

0.9

_

Ol_

lC

_

_110
"_

11'

1.0
0.1

External Static Pressure

.._

110
111

0.1

0.7

001

_ _._

__

0.6

EBV6000B

_
_

0.5

ExternalStatic Pressure

EBV4800B

U#J

_"_.-_

_

600
300

000

---.......

0.2

0.3

0.4

0.5

0.6

0.7

ExternalStaticPressure

0.8

0.9

1.0



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 14
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Sun Oct 21 03:04:57 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu