260-CO SafeAir Carbon Monoxide Detector
Installation Sheet
Information about carbon monoxide
WARNINGS
•

Read these installation instructions in their entirety before
proceeding. Leave these instructions with the owner/user
of this CO detection equipment.

•

This product is intended for use in indoor locations of
dwelling units. It is not designed to comply with
Occupational Safety and Health Administration (OSHA)
commercial or industrial standards.

•

The detector only indicates the presence of CO gas at the
detector. Carbon monoxide gas may be present in other
areas.

•

Failure to properly install, test, and maintain a CO detector
may cause it to fail, potentially resulting in loss of life.

WARNING: The carbon monoxide (CO) alarm indicates the
presence of CO, which can kill you. If the alarm signal sounds
four times, pauses for five seconds, and then repeats the
pattern:

•

Installation of this detector is not a substitute for proper
installation, use, and maintenance of fossil fuel-burning
appliances, including appropriate ventilation and exhaust
systems.

1.

Press the Test/Hush button at the detector or at the
control panel.

•

To reduce the risk of CO poisoning, test the detector
operation when not in use for 10 days or more.

2.

Move to fresh air immediately — outdoors or by an open
door or window. Check that all persons are accounted for.
Do not reenter the premises or move away from the open
door or window until emergency services responders have
arrived, the premises have been aired out, and your
detector remains in normal condition.

•

This detector does not operate without electrical power. As
fires frequently cause power interruption, discuss further
safeguards with the authority having jurisdiction (AHJ).

•

Do not paint the detector.

Carbon monoxide alarm procedure

3.

Notes

Call emergency services, the fire department, or 911:

•

Regulatory code may require that the system generate a
three-pulse temporal code (TC3) for fire alarms and a fourpulse temporal code (TC4) for CO alarms.

•

The CO sensor is calibrated at the factory. CO sensitivity
is set to conform to UL 2034 requirements and cannot be
changed by the user. See “Specifications” on page 7 for
specific sensitivity values.

•

To reduce the likelihood of nuisance alarms, ventilate
accommodation spaces when using household cleaning
supplies or similar contaminants. If a detector has been
exposed to such contaminants, test it promptly afterwards.

Phone:
4.

After following steps 1 to 3, if your detector reactivates,
repeat steps 1 to 3 and call a qualified appliance
technician to check for sources of CO from fuel-burning
equipment and appliances, and to inspect for proper
operation of this equipment.
Phone:

5.

If problems are found during this inspection, have the
equipment serviced immediately. Note any combustion
equipment not inspected by the technician and consult the
manufacturer directly for more information about CO
safety for the equipment. Make sure that motor vehicles
are not, and have not been operating in an attached
garage or adjacent to the premises.

© 2012 UTC Fire & Security. All rights reserved.

Symptoms of CO poisoning
The following symptoms related to CO poisoning should be
discussed with all occupants of the protected site.

1/8

P/N 3102002-EN • REV 01 • ISS 27AUG12

Mild exposure: Slight headache, nausea, vomiting, fatigue,
runny nose, sore eyes (often described as "flu-like" symptoms).
Medium exposure: Severe throbbing headache, dizziness,
drowsiness, confusion, fast heart rate.
Extreme exposure: Unconsciousness, brain damage,
convulsions, cardiorespiratory failure, death.
Many cases of reported CO poisoning indicate that while
victims are aware they are not well, they become so
disorientated that they are unable to save themselves by either
exiting the building or calling for assistance. Young children
and pets may be the first affected.
CO sources
The CO sensor in this detector is designed to detect carbon
monoxide gas from any source of combustion. It is not
intended to detect fire, smoke, or any other gas. Potential CO
sources include fuel-fired appliances (e.g., space heater,
furnace, water heater, range, oven, clothes dryer); other
sources of combustion (e.g., kerosene-burning stove or heater,
or gas log fireplace); or internal combustion engines.

A detector installed outside a bedroom may not awaken a
sleeper. Normal noise due to stereos, television, etc. may also
prevent the detector from being heard if distance or closed or
partly closed doors muffle the sounder. This unit is not
designed for the hearing impaired.
CO detectors are not a substitute for designated life safety
devices. Though these detectors will warn against increasing
CO levels, we do not warrant or imply in any way that they will
protect lives from CO poisoning. They should only be
considered as an integral part of a comprehensive safety
program.

Detector locations
Selecting a suitable location is critical to the operation of CO
detectors. Figure 1 shows appropriate detector locations.
Figure 1: Detector locations

In addition, excessive exhaust spillage or reverse venting of
fuel-burning appliances can produce dangerous transient
levels of CO. This can be caused by external conditions:
•

Wind direction, velocity, or a combination of both,
including high gusts of wind or insufficient draft in vent
pipes

•

Temperature inversions that can trap exhaust gases near
the ground

•

Negative pressure differential resulting from the use of
exhaust fans

•

Simultaneous operation of several fuel-burning appliances
competing for limited internal air

•

Vent pipe connections vibrating loose from dryers,
furnaces, or water heaters

•

Obstructions in vent pipes or unconventional vent pipe
designs which can amplify the above situations

•

Poorly designed or maintained chimneys and/or vents

•

Extended operation of unvented fossil fuel-burning devices
(range, oven, fireplace, etc.)

•

Idling cars in an open or closed attached garage, or near
the premises

General limitations of CO detectors
This detector is designed to protect individuals from the acute
effects of CO exposure. It will not fully safeguard individuals
with specific medical conditions. People with special medical
problems should consider using specialized detection devices
with less than 30 ppm (parts per million) alarming capabilities.
If in doubt, consult a medical practitioner.
If the unit is in trouble or at the end of its life, it may not sense
CO and cannot be relied upon to monitor CO levels. Replace
the CO detector within ten years from the date of manufacture
or when the detector indicates an end of unit life condition,
whichever comes first.

2/8

Recommended CO detector location

Description
The 260-CO SafeAir Carbon Monoxide Detector detects
carbon monoxide gas, monitors the levels of CO gas, and
gives early warning when potentially dangerous levels exist. It
includes a built-in sounder that acts as a primary alarm
notification device. (The control panel is the supplementary
alarm notification device.)
The 260-CO SafeAir Carbon Monoxide Detector is a four-wire
device that uses a Class 2 output from a control panel (listed to
the UL 985 or 864 standards), or from an auxiliary power
supply. It is intended for indoor-dwelling unit applications in
both residential and commercial occupancies, including single
and multiple family residential occupancies, hotel rooms, dorm
rooms, and other areas approved by the authority having
jurisdiction (AHJ).
The 260-CO detector meets UL 2075 Standard for Gas and
Vapor Detectors and Sensors. It does not detect fire, smoke, or
any other gases.
Alarms and Signals
The 260-CO detector produces varying sounds in addition to
the alarm signal. It also flashes a multicolored LED to indicate
the detector status. Table 1 lists status indications of the
detector.

P/N 3102002-EN • REV 01 • ISS 27AUG12

Table 1: Detector status indications
Status

LED

Sounder

Description

Safe air

Green, 1 pulse every
15 seconds

No sound

The detector has power and is functioning properly.

Alarm

Red, pulses with
sounder

Sounds four rapid beeps every
five seconds or every minute
after five minutes in the alarm
state

Dangerous levels of CO are present. Evacuate the premises.

Sounds one rapid beep every
45 seconds

There is a problem with the detector and the detector is not working
properly. Contact the service company to correct the trouble and
replace the detector, if necessary.

Trouble

Amber, pulses with
sounder

Press the test/hush button to silence the sounder for five minutes.
Activates the alarm relay. If connected, the control panel activates.

Press the test/hush button to silence the detector for nine hours.
Activates the trouble relay.
End of unit life

Amber, pulses with
sounder

Sounds one rapid beep every
15 seconds

Replace the detector as soon as possible.

Loss of power

No LED

No sounder

Activates the trouble relay.

Tandem
interconnect

No LED

Sounds four rapid beeps every
five seconds or every minute
after five minutes

The detector in alarm causes the sounds to activate on the detectors
that are not in alarm. Evacuate the premises.

Press the test/hush button to silence the detector for 36 hours.
Activates the trouble relay.

Distinct 85 dB temporal-four alarm: The 85 dB sounder
provides a distinctive temporal-four alarm notification that is
easy to differentiate from smoke detector notification devices.
The alarm beeps four times, pauses five seconds, and then
repeats the pattern.
End of unit life indicator: The detector uses both a flashing
amber LED and intermittent sounder chirps (one rapid beep
every 15 seconds) to indicate that the detector needs
replacing. The detector also activates the trouble relay, which
can be monitored by a panel. As soon as possible, replace a
detector that reaches end of life because it may no longer
detect carbon monoxide accurately.
Common trouble relay: When connected to a listed control
panel, the trouble relay can report a trouble condition locally at
the panel and optionally at the monitoring station, if the system
is monitored. The trouble relay opens to indicate a trouble
condition upon lost power, CO sensor cell trouble, or unit end
of life.

Press the test/hush button to silence the sounder for five minutes.

floor. For ceiling mounted applications, place detectors at least
1 ft. (0.3 m) from any wall.
The recommended CO detector locations are:
•

Outside each separate sleeping area in the immediate
vicinity of the bedrooms (including areas such as hotel
rooms and dorm rooms)

•

On every occupied level of a dwelling unit, including
basements, but excluding attics and crawl spaces

•

Centrally located on every habitable level of the building
and in every HVAC zone based on an engineering
evaluation considering potential sources and migration of
carbon monoxide

•

On the ceiling in the same room as permanently installed
fuel-burning appliances

•

In any area required by local building codes, legislation, or
the authority having jurisdiction

•

In a suitable environment per the detector specifications
(see “Specifications” on page 7 for details)

•

On a firm, permanent surface

Installation
WARNING: Potential loss of life. Failure to properly install,
test, and maintain a CO detector may cause it to fail. Connect
the CO detector only to a zone that is dedicated exclusively to
CO detection and that is monitored 24 hours a day. Do not
connect it to an initiating circuit with fire or security devices.
The 260-CO detector can connect to either UL 985 (Household
Fire Warning) or UL 864 (Commercial Fire) control panels. It is
not intended for use in industrial applications such as gasoline
refineries or parking garages, which require different listings.
Detector placement

Do not install the CO detector:
•

Within 5 ft. (1.5 m) of any cooking appliance

•

Within 10 ft. (3 m) of a fuel-burning appliance

•

Near air conditioners, heating registers, or any other
ventilation source that may interfere with CO gas entering
the detector

•

Where furniture or draperies may obstruct the airflow

•

In a recessed area

Install detectors according to applicable codes and standards.
Place wall-mounted detectors at least 5 ft. (1.5 m) up from the

P/N 3102002-EN • REV 01 • ISS 27AUG12

3/8

To install the 260-CO detector:

To install the detector with the 250-COPLT adapter plate:

1.

Run the 260-CO detector wiring to the detector location.

1.

Run the 260-CO detector wiring to the detector location.

2.

Carefully remove the cover from the detector using a
small, flat screwdriver blade in the slot on the left side of
the detector cover.

2.

Using the 250-COPLT wall plate for a template, trace the
perimeter of the two square holes on the mounting
surface. Also mark the two screw locations.

3.

The mounting hole pattern is for a single-gang electrical
box or mounting ring. Use the base as a template to mark
the two screw hole locations on the mounting surface or
mount on a single-gang box (not provided). The unit can
be mounted vertically or horizontally.

3.

Cut out the two square holes.

4.

Install two screws on the marks. If necessary, use wall
anchors. See Figure 3.

5.

Mount the wall plate but do not fully tighten the screws.

4.

Install two screws on the marks. If necessary, use wall
anchors.

6.

5.

Line up the base with the screws, pull the wires through
the square holes, and then slide the base over the screws.
See Figure 2.

Carefully remove the cover from the detector using a
small, flat screwdriver blade in the slot on the left side of
the detector cover.

7.

Pull the wires through the square holes on both the wall
plate and the 260-CO base, and then slide the detector
base over the screws.

8.

Strip 3/8 in. of insulation from each wire.

9.

Determine the correct wiring, and then insert the wires
under the appropriate screw terminals. See “Wiring.”

6.

Strip 3/8 in. of insulation from each wire.

7.

Determine the correct wiring, and then insert the wires
under the appropriate screw terminals. See “Wiring” on
page 5.

8.

Tighten both screws to secure the base to the wall.

10. Tighten both screws to secure the base to the wall plate.

9.

Replace the detector cover.

11. Replace the detector cover.

10. Apply power. The LED should flash green for about four
seconds, and then pulse green.

12. Apply power. The LED should flash green for
approximately four seconds, and then pulse green.

11. Test in accordance with “Testing” on page 6.

13. If required by the AHJ or local codes, affix the supplied CO
Warning Label (P/N 10634757) in proximity to the
detector.

Figure 2: Installing the 260-CO detector

14. Test in accordance with “Testing” on page 6.
(1)
Figure 3: Installing the 260-CO detector with the adapter plate

(3)

(1)

(3)

(2)
(1)
(2)
(3)

Trouble relay and power wiring hole
Alarm relay wiring hole
Mounting screws (2X)

(2)

The 250-COPLT adapter plate
The 260-CO detector has an optional adapter mounting plate.
Use the 250-COPLT adapter plate when replacing a 240-COe
with a 260-CO to cover the footprint of the 240-COe. To
purchase the plate, order P/N 250-COPLT-5PKG.

4/8

(1)
(2)
(3)

Trouble relay and power wiring hole
Alarm relay wiring hole
Mounting screws for detector and mounting plate (2X)

P/N 3102002-EN • REV 01 • ISS 27AUG12

Figure 5: Multiple devices, single zone configuration

Wiring
All wiring must conform to the NFPA 70 National Electric Code,
UL 2075 Standard for Gas and Vapor Detectors and Sensors,
NFPA 720 Standard for the Installation of Carbon Monoxide
(CO) Detection and Warning Equipment, applicable codes, and
the local AHJ.

(1)
C
NC

Wire the 260-CO detector as appropriate for your facility. There
are three typical wiring configurations:
•
•
•

Single device and single zone (Figure 4)
Multiple devices in a single zone (Figure 5)
Multiple devices with separate alarm and trouble zones
(Figure 6)

NC
C
NO

Figure 4: Single device, single zone configuration
C
NC

(1)
C
NC

NC
C
NO

NC
C
NO

(2)

C
NC

+ –

(3)
(1)

(1) End-of-line device (provided by the life safety system)
(2) Alarm initiating device circuit (IDC)
(3) Power (see “Specifications” on page 7)
Note: Relay is shown in the normal state for this detector.

(2)

NC
C
NO

Tandem Interconnect:
When wiring your facility with multiple 260-CO detectors for
tandem interconnect, you must use a Single Circuit Reversal
Module (see Table 2). On alarm, the module disconnects the
detector from its normal power supply and applies reverse
polarity from the notification appliance circuit. Applying reverse
polarity causes the sounders to activate on other 260-CO
detectors that are on the same loop. Only the initiating detector
will sound and blink red. All others in tandem mode will sound
but not blink red.
Table 2: Models [1]
Number

Description

ESL 405-01

24 VDC Single Circuit Polarity Reversal Module

ESL 405-03

12 VDC Single Circuit Polarity Reversal Module

ESL 405-05

12/24 VDC Single Circuit Polarity Reversal Module [2]

(4)

(5)

(6)

(3)

(7)
(1)
(2)

End-of-line device (supplied by life safety system)
ESL 405-03 (12 VDC) or ESL 405-01 (24 VDC) polarity reversal
module
(3) Control panel
(4) Alarm IDC
(5) Power 12/24 VDC
(6) Notification appliance circuit (NAC) from 12 VDC control panel
(7) Notification appliance circuit (NAC) from 24 VDC control panel
Note: Relay is shown in the normal state for this detector.

[1] A 204 series power supervision relay is not required.
[2] When using the ESL 405-05 model, refer to the wiring instructions
that came with the device.

P/N 3102002-EN • REV 01 • ISS 27AUG12

5/8

Figure 6: Multiple devices, separate alarm, trouble zone config.

Features
The 260-CO includes several features, as shown in Figure 7.

(1)
C
NC

Figure 7: 260-CO features

(1)

(4)

(2)

(1)

NC
C
NO

(3)
(5)
C
NC

(1)
(2)
(3)
(4)
(5)

Sensor port
LED alarm light
Test/hush button
Trouble relay and power wire hole
Alarm relay wire hole

Testing

NC
C
NO

Caution: To reduce the risk of carbon monoxide poisoning,
test alarm operation when not in use for 10 days or more.
C
NC

Note: Before beginning any test, notify all persons and
facilities that receive alarms and troubles to prevent any
unnecessary responses.
(1)

(2)

NC
C
NO

(4)

(5)

After installation and once a week, test the detector to verify
that it is functioning properly. Check the common trouble relay
and the panel’s response, and then use the test/hush button to
verify that the detector is functioning properly. If the detector
fails the test, verify all connections, wait briefly, and then try
again. If the detector fails again, replace it.
The detector features a SAFEtest mode. In SAFEtest mode
you can perform a functional carbon monoxide gas test using a
can of CO testing agent.

(6)

(7)

(3)

(8)
(1)
(2)

End-of-line device (supplied by life safety system)
ESL 405-03 (12 VDC) or ESL 405-01 (24 VDC) polarity reversal
module
(3) Control panel
(4) Supervisory IDC
(5) Alarm IDC
(6) Power 12/24 VDC
(7) Notification appliance circuit (NAC) from 12 VDC control panel
(8) Notification appliance circuit (NAC) from 24 VDC control panel
Note: Relay is shown in the normal state for this detector.

To test the trouble relay:
1.

Momentarily disconnect the power supply from the
detector and verify that the common trouble relay opens.

2.

Verify that the control panel reacts correctly to the relay
activation.

Notification

Test/hush button: (See Figure 7.) Use the test/hush button to
test the detector and silence an activated detector. When in
alarm, momentarily pushing the test/hush button silences the
integral sounder for five minutes. The red LED alarm light stays
on, and if CO is still present after five minutes, the detector
once again sounds in the temporal-four pattern. The detector
automatically resets when CO is no longer detected.

Notification of carbon monoxide detectors should be consistent
with NFPA 720 and the local AHJ. Notification zones should be
consistent with the emergency plan for the protected premises.

You can perform three different tests by pressing the test/hush
button. How long the button is pressed determines which tests
are performed. See Table 3.

6/8

P/N 3102002-EN • REV 01 • ISS 27AUG12

Table 3: Press duration and resulting test

Maintenance

Duration

Test

Description

Short press

Buzzer test only

Generates the temporal-four
pattern twice.

Note: The 260-CO is shipped from the factory as an
assembled unit; it contains no user-serviceable parts and
should not be disassembled.

Two seconds

Buzzer test

Generates the temporal-four
pattern twice.
Allows functional CO gas
testing [1].

Clean the outside of the detector each month with a clean cloth
(either dry or dampened with water) to keep openings free from
dust and dirt.

SAFEtest
Five seconds

Buzzer test
SAFEtest
Alarm relay test

Generates the temporal-four
pattern twice.
Allows functional CO gas
testing [1].
Activates the alarm relay.

[1] Use the UL Certified “Solo C6” canned CO product from SDi

To test the buzzer:
1.

Momentarily press the test/hush button.
The sounder generates four quick beeps, followed by five
seconds of silence, and then four quick beeps.

To perform the functional test with CO test spray:
1.

Press and hold down the test/hush button until the red
LED illuminates (approximately 2 seconds).

2.

Wait for the buzzer test to complete.
The red LED flashes every 4 seconds and the green LED
flashes every 16 seconds indicating that the device is in
CO test mode.

3.

Direct a UL Approved CO testing agent spray to the
sensor port of the 260-CO.
The unit immediately goes into an alarm state upon
sensing the applied gas. The sounder and red LED
activates in a temporal-four pattern with a five second
pause in between. The alarm relay activates.
If the level of applied CO gas is still significant, the device
continues to alarm in this pattern.

4.

Exit the SAFEtest mode by either:
•
•

Pressing the test/hush button until the green LED
illuminates (approximately 2 seconds)
Waiting five minutes, until the unit automatically exits
out of the SAFEtest mode

To perform the alarm relay test:

Do not paint the detector or expose it to cleaning solutions.

CO detector replacement
The 260-CO SafeAir Carbon Monoxide Detector has a long-life
carbon monoxide electrochemical sensor. Replace the detector
with a new 260-CO detector after 10 years from the date of
manufacture (found on the product label on the back of the
detector) or when the control panel goes into trouble and an
audible/visible annunciation occurs signaling “operational end
of life”.

Specifications
Input voltage

Current consumption
Normal
Alarm

20 mA
40 mA (75 mA in test)

Alarm relay
Type
UL rating

150 mA at 33 VDC
Form C
Zone

Common trouble relay
Type

150 mA at 33 VDC
Normally opened held closed with power
applied
Common

UL rating
Sounder

85 dB

Compatible control panel

Listed to UL 985 or 864 standards

Compatible electrical box

2-1/2 in. (64 mm) single-gang

Wire size

14 to 22 AWG (0.25 to 2.0 mm²)

Dimensions (W × L × D)
Detector
Adapter plate

3.1 × 4.6 × 1.4 in. (7.8 × 11.7 × 3.6 cm)
4.5 × 6.5 × 0.2 in. (11.4 × 16.5 × 0.5 cm)

Color

White

40 to 100°F (4.4 to 37.8°C)
10 to 90% noncondensing

1.

Press the test/hush button for approximately 5 seconds to
start a test cycle.

Operating environment
Temperature
Relative humidity

2.

Wait for the buzzer test to complete.

CO sensitivity

3.

Verify that the control panel reacts correctly to the alarm
relay activation.

4.

The alarm relay test mode ends automatically after
10 seconds.

P/N 3102002-EN • REV 01 • ISS 27AUG12

12 or 24 VDC supplied by control panel or
resettable auxiliary power supply

70 ppm, 60 to 240 minutes
150 ppm, 10 to 50 minutes
400 ppm, 4 to 15 minutes

7/8

Regulatory information
Manufacturer

Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA

Year of
manufacture

The first two digits of the DATE MFG number
(located on the product identification label) are
the year of manufacture.

UL rating

Regulated 12 DC, Regulated 24 DC

North American
standards

UL 2075
This detector has been evaluated to the CO
alarm sensitivity limits of UL 2034.

Environmental
class

Indoor

Contact information
For contact information, see www.interlogix.com.

8/8

P/N 3102002-EN • REV 01 • ISS 27AUG12



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Author                          : 218023003
Create Date                     : 2012:08:27 15:54:59-04:00
Modify Date                     : 2012:08:27 15:54:59-04:00
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Format                          : application/pdf
Creator                         : 218023003
Title                           : Microsoft Word - 3102002-EN R01 260-CO SafeAir Carbon Monoxide Detector Installation Sheet.doc
Creator Tool                    : PScript5.dll Version 5.2.2
Producer                        : Acrobat Distiller 10.1.4 (Windows)
Document ID                     : uuid:ddd14f4e-0a8f-4d25-bd89-b1a05240f306
Instance ID                     : uuid:e7f15027-c9d9-411e-9c9a-ee89f17e6556
Page Count                      : 8
EXIF Metadata provided by EXIF.tools

Navigation menu