JRI 10620-03 SIRIUS BOX User Manual Notice SiriusWeb 012014 EN Mise en page 1

JRI MAXANT SIRIUS BOX Notice SiriusWeb 012014 EN Mise en page 1

User Manual

réf : 08869 G®Installation guideCongratulations -  you have just purchased a SiriusWeb solution. Onceinstalled, SiriusWeb will allow you to monitor your storage or living areas andconsult the measurements from any PCconnected to the Internet.
© JRI 1Function diagramUnpack carefully your parcel and check that you have all the below mentioned items. Then proceedwith the installation of the SPY RF and your SiriusBox as described below. 1- The SPY RF recorders  3- One wall mounting bracket for each SPY RF recorder (only supplied with remote probe SPY RF recorders).2- The SiriusBox includes a wall mounting bracket and apower supply cord.4- Double-sided adhesive tape for each SPY RF recorder(only supplied with remote probe SPY RF recorders).Provided materialAmbient probe model SPY RFT+, Green, Air and THRemote probe model SPY RFU, N and C
Your         step installation guide© JRI 2Note: Go straight to Step 2 if you have an orange SPY RF T+, Mini SPY Green or SPY RF TH -type recorder.Connect the probes to the SPY RF only if you have a model with a remote probe (refer to the usermanual of the SPY RF recorders).Note: JRI advises you to consult your certified SPY RF installer in order to carry out the installationof the recorders properly.>  Ambient recorders (SPY RF T+, TH, Green, Air)Place the recorder(s) in an upright position inside the compartment/chamber/area you want to monitor, about two thirdsup.or>  Remote recorders (SPY RF U, N or C)Place the recorder(s) outside the compartment/chamber/area in anupright position as high up as possible on the exterior partition (ofthe compartment/chamber). A wall mounting bracket and double-sided adhesive tape are provided for this purpose. The probe connected to the recorder must be placed in the centreinside the compartment/chamber/area in order to register a tempe-rature as uniform as possible.Put the flat cable of the probe through the door seal at the level ofthe hinges of your compartment/chamber.1Connect your probes2Install your SPY RF recorders12
3Install your SiriusBox4Connect your SiriusBoxFasten the SiriusBox on the wall mountingbracket by sliding it upwards, then downwardsuntil you hear a click. (note: to unfasten the SiriusBox, push gentlyon the release lever, push the box upwards andthen downwards).© JRI 3Fix the wall mounting bracket to the wall in anupright position (at a height of 2 m minimum and50 cm from the ceiling).The release lever shouldturn upwards. Depending on the surface of thewall, use two screws or double-sided adhesivetape or Velcro.Choose an appropriate place on the wall close to a socket. It is important that you are in a GSM coverage area. The SiriusBox must be placed at a reasonable distance from the SPY RF recorders(max. 50 m).Plug the adapter into the socket. At the bottom of the box, the first green LED lights up indicating that the SiriusBox is powered.
© JRI 4If the temperature is not displayed on the SPY RF recorder(s), press the push-button for at least 5seconds to set it going (refer to the user manual of the recorders...). Your system is now working.The yellow LED indicates that data exchanges between the SiriusBox andthe SPY RF recorders are taking place.The second green LED lights up when the connection to the GSM networkis  established. It turns on 10-30 seconds after being connected. If it doesnot, this means that there is an insufficient GSM coverage. In this case,move the device and try again.The red LED indicates that an alert is on.5Start your recorders
7Display6Log on to the SiriusWebLog on to the www.jri-maxant.com website using your login and password. Click "CUSTOMER ACCESS" in the upper right corner. A window appears. Enter your login and password, then click "OK” .General consultation of all your monitored units (M.U.) straight from the home page.Note : Generally, the locally recorded data is transferred to the SiriusWeb platform every 3 hours to bedisplayed.© JRI 5Last measurement transferred to SiriusWebplatform State of alarm colourGraph display of the last24 hoursDigital display of the last24 hours
98Activate your threshold alarms and your time delaysManage your profiles (Site manager only)© JRI 6Click on the button        to open the monitored unit parameters. Enter the name of your monitored unit and activate the alarm of your recorder. Set also your alarmthresholds and time delays. Once these fields are filled in, click on "FINISH INSTALLATION".If you have more than one monitored unit to configure, click on “CONTINUE  INSTALLATION”. After having registered/entered all your devices, click on “FINISH INSTALLATION”.When you click “PROFILE”    , you can set different logins and passwords to access the SiriusWeb website and then manage multiple profiles: user, administrator... Note : JRI advises to have data for each monitored unit for at least a couple of days in order to determine the threshold values and the time delays.(Site manager only)Enter the name of your monitored unitActivate the alarmSet your alarm thresoldsand time delays
10 Activate your alarms (Site manager only)© JRI 7JRI advises to set several different types of alarms.Click on the “ALARM MANAGENENT” icon A- Remote alertsConfigure your alert types (SMS text message, email, phone call) and your remote alarms.  The remote alarms planning  is used to activate the monitored units’ alerts during a specific periodof time. Once the type of alerts is selected, click on “ADD”.Alarm types Remote alarmsscheduleSMS / Text message Phone call Email2 phone numbers can be configured2 phone numbers can be configured Unlimited email addressesOne single SMS text message issent 3 attempts every 15 minutes Every email is sent onceAcknowledgment is possible Acknowledgment is possible No acknowledgment
© JRI 8You can shut down the buzzer by pressing on push buttonHowever, it is necessary to give the reason of the alarm on the SiriusWeb interface.If necessary (persistent default or problem to connect to SiriusWeb), it is possible to reset the SiriusBox by inserting a metal rod (paperclip) into the hole provided for this purpose (RESET).B- Local alertsIf you want to be locally alerted, click on “SiriusBox parameters” and activate the buzzer of your SiriusBox which beeps in case of alarm.In case of alert, click on “ALARM LIST” and indicate the reason of the alarm.In case of alarm, acknowledgment of the buzzer is achieved in the same way as for remote alarms.Current alarmBuzzer activation
CommonRelay output :Connection with an additional alarm system NC (normally closed)No (normally opened)Note : It is possible to install an additional alarm system allowing to send alarms even if the GPRSsignal is down (voice dialer, sound and visual alarm device, transmission to a telemonitoring com-pany ...).While clicking on       , you can review the complete list of operated actions  on your installation.You can sort the information per type of events. © JRI 911 Review the Audit trail12 Configure a weekly report by emailFiltersYou can receive a weekly report (every Tuesday) presenting a sum up of your data. In “Preferences” select the case “Activate the remote reading” and type the email address of theaddresse(s) of the report.To configure it, access your profile by clicking on the icon
© JRI 10Unplug the Sirius Box. You should receive an alert depending on the pre-programmed alerts. If you don’t receive any alert, follow the steps:1/ Check your alerts programming (Buzzer and/or text message, email, voice message) on Sirius-Web.2/ Check the connection of the power supply of the SiriusBox. 3/ Check the GPRS communication level. Click on “SIRIUSBOX PARAMETERS” to access the information on the SiriusBox. The minimum levelof communication is 2 grades. 4/ Check the connection of the backup battery. Backup batteryConnectorYour installation should now be working. However if you still don’t have any communication, pleasecontact our technical support. Before going through the checking steps, please wait for 8 hours while the system is turned on.Open the Sirius Box with the help of a penplacing it inside both holes on the upper anddown sides of the SiriusBox.Check that the connector of the backup battery is connected to the electronic board.Advice to check that your installation is working
Advice to check measurement uploadIn case of failureIcons glossary© JRI 111/ Check that temperature is displayed on the LCD screen or that the leds are blinking. 2/ Check that the measurements of your monitored units displayed on SiriusWeb are less than 8 hours.If the lights are off, check the power of the SiriusBox by checking the plug.If the SiriusBox does not work, perform a soft reset by inserting a metal rod (such as a paper clip)into the hole provided for this purpose (RESET). If there are no longer measurements on SiriusWeb, check that the recorders are on. If they are off,press at least 5 sec their push button to turn them on. If they still do not start, replace the batteryand turn on the recorders.Refreshmeasurements of all monitored units linked to the SiriusBoxPrint thepageDisplay measurementslistAdd a comment Adapt the display ofthe curve according tothe selected interval
© JRI 12Emission band ISM 868 MHzMaximum radiated power 10 dBm (10 mW)Range with SpyRF satellites in buildings Up to 50 meters depending on theenvironmentRadio featuresEmission band GSM 900 MHz or DCS 1800 MHz(depending on the operator of the mobile subscription)Maximum radiated power 2W in GSM mode1W in DCS modeGPRS featuresPower supply Adapter plug (European model) with regulated output voltage :input: 230 V CAoutput: 9 V CC - 650 mAcord fixed: 1,80 mPower consumption Average consumption : 0,5 W Peak consumption : 5 WBackup battery NiMH capacity 650mAhBackup battery lifetime Fully operational autonomy : 12h rsLoading time : 100hrsElectrical featuresDimensions 154x84x37 mmWeight 270g (without adapter)Protection index IP20 - to be used indoors onlyConditions of use 0°C to 50°C - 0 to 90% RHPollution / altitude (IEC 61010-1) Degree of pollution : 2 Operating altitude: 0 to 2000mMechanical and environmental featuresInstallation PrecautionsSiriusBox hub must be fixed in a vertical position (such as that SpyRF satellites). A wall mounting bracket is provided.This support can be fixed to the wall with two screws, or with a double-sided adhesive (also provided).The SiriusBox should not be fixed on a metal surface and in a place with insufficient GSM network coverage.A socket should be available nearby (within a maximum of 3m) to allow plugging in the AC adapter. It serves as the disconnecting device.Key featuresWARNINGThis unit contains a rechargeable NiMH battery. Never attempt to disassemble, to charge and to short circuit. Alwaysuse the battery correctly, do not expose to temperatures above 100 ° C, do not wet and respect the polarities. Keepthe battery out of the reach of children. Always replace the battery with the templates provided by JRI. They have a undeceived connector to prevent polarity reversal.JRI disclaims all liability for use of a different battery. In case of non-compliance with these instructions, alcalins hydroxides may leak from the valve safety.
© JRI 13SymbolsMaintenanceRECYCLING: Do not dispose in a landfill or in a container collection waste. Comply with the legislation for thedisposal.ELECTRICAL POWER: This unit is DC powered from a 230 V AC adapter. Comply with the safety rules in theuse of electric power. Use an electrical installation complies with the legislation.CE MARKING: This device is certified to the European regulations for electrical safety, flamability, radiation emission disturbing and immunity to electrical interference nearby.ELECTRICAL INSULATION: This device is protected by a double electrical insulation or electrical insulation rein-forced.No maintenance is necessary. For cleaning, do not use water but a dry cloth.Safety / CertificationsCE radio compliant : EN 301 489 / EN 300 220 / EN 61010 /  EN 301 511WarrantyJRI products carry a one year warranty and guarantee against defects in their components or workmanship.During this period if any product supplied by the Company proves on inspection to be defective, the Company will atits own option replace the same or refund to the Buyer the price of the product.In no circumstances will JRI' liability exceed the price of the product paid by the   buyer or the cost of replacement.JRI shall not in any event be liable to the Buyer for any indirect or consequential loss or damage costs or expenses what-soever which might arise out of or in connection with the supply of the product or its consequent use.Consequently, the products warrantee and guarantee specified above, does not cover damage caused by fair wear andtear, abnormal storage conditions, incorrect use, accidental misuse, abuse, neglect, misapplication or modification, oruse with non-JRI' hardware/software. No warranty of fitness for a particular purpose is offered and the user assumes theentire risk of using the product.In line with our policy of continuous development, we reserve the right to amend our product specification without priornotice.FCC ID Box=W4510620-03 FCC ID GPRS=N7NWISMO228FREQUENCYThis device is designed to operate in the band  [902.22 – 904.149] MHz.FCC COMPLIANCE STATEMENTThis device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: This devicemay not cause harmful interference, and must accept any interference received, including interference that may causeundesired operation.INFORMATION TO THE USERThe user’s manual or instruction manual for an intentional or unintentional radiator shall caution the user that changesor modifications not expressly approved by the party responsible for compliance could   void the user's authority to ope-rate the equipment.FCC RADIATION EXPOSURE STATEMENTThe antenna(s) used for this transmitter must be installed to provide a separation distance of at least 20 cm from allpersons.RecyclingImportant noteIf it must be discarded, this equipment must be in compliance with the legislation on electronic equipment. It shouldnever be disposed in the landfill or never be treated by the services of the road. For more information, call the JRI cus-tomer service.
© JRI 14SiriusWeb iPhone AppMinimal configurationYou can now have SiriusWeb on your iPhone. Go on AppStore, downloadthe App and enter your login and password.- Display all your monitored units : temperature values, thresholds, measurement graph- Management of alarms and history- Send email to our technical supportIt is also available in German, Spanish, Italian, Portuguese and Dutch.The iPhone SiriusWeb App offers the following functions: Internet Browser :Internet Explorer 7 +, FireFox 1.0 + and Chrome 1.0 + and Safari 2.0 +.Screen resolution: 1280px * 680px at leastJavascript must be enabled.
Our technical support is at your disposal on+33 3 63 15 80 07Indicate your SiriusWeb loginclick       in the upper right corner of the siriusweb.fr site in order to forward us your question.orclickIn the upper right corner of the SiriusWeb.fr website to access the FAQTechnical assistance

Navigation menu