GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Installation
and
Operation
Instructions

WARNING:

IF THE INFORMATION IN THESE INSTRUCTIONS
ARE NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE,
PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY:
DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
INSTALLATION:
INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER, SERVICE
AGENCY OR LICENSED GAS SUPPLIER.
THIS PRODUCT MUST BE INSTALLED BY A
LICENSED PLUMBER OR GAS-FITTER WHEN
INSTALLED IN THE COMMONWEALTH OF
MASSACHUSETTS.
A CARBON MONOXIDE (CO) DETECTOR SHALL
BE INSTALLED IN THE SAME ROOM AS THE
APPLIANCE.
WHAT TO DO IF YOU SMELL GAS:
• DO NOT TRY TO LIGHT ANY APPLIANCE.

Jøtul GF 100 DV II
Nordic QT

• DO NOT TOUCH ANY ELECTRICAL SWITCHES.
• DO NOT USE THE PHONE IN YOUR BUILDING.
IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A
NEIGHBOR’S PHONE.
• FOLLOW YOUR GAS SUPPLIER’S INSTRUCTIONS.
• IF YOU CANNOT REACH YOUR GAS SUPPLIER,
CALL THE FIRE DEPARTMENT.
AVERTISSEMENT:
ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUCTIONS DANS CETTE NOTICE POUR REDUIRE AU
MINIMUM LE RISQUE D’INCENDIE OU POUR EVITER
TOUT DOMMAGE MATERIEL, TOUTE BLESSURE OU
MORTALIT’E.
NE PAS ENTREPOSER NI UTILISER D’ESSENCE NI
OU LIQUIDES INFLAMMABLES DANS LE VOISINAGE
DE CET APPAREIL OU DE TOUT AUTRE APPAREIL.

Jøtul GF 200 DV II
Lillehammer

L’INSTALLATION LE SERVICE DOIVENT ETRE
EXECUTES PAR UN INSTALLATEUR QUALIFIE,
AGENCE DE SERVICE OU LE FOURNISSEUR DE
GAZ.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ.
• NE PAS TENTER D’ALLUMER L’APPAREIL
• NE TOUCHEZ A AUCUM NTERRUPTEUR.
• NE PAS VOUS SERVIR DES TELEPHONES SE
TROUVANT DANS LE BATIMENT OU VOUS VOUS
TROUVEZ.
• APPELEZ IMMEDIATEMENT VOTRE FOURNISSEUR
DE GAZ CHEZ UN VOISIN. SUIVEZ LES INSTRUCTIONS DU FOURNISSEUR.
• SI VOUS NE POUVEZ REJOINDRE LE
FOURNISSEUR DE GAZ, APPELEZ LE SERVICE DES
INCENDIES.

1

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Welcome to Jøtul...
Congratulations on the purchase of your new
Jøtul gas heater.
We at Jøtul are glad you’ve made the decision to
warm your hearth with a Jøtul product. Your new
stove exemplifies over 150 years experience as the
world’s largest manufacturer of solid fuel burning
appliances. We’ve been making fine quality cast
iron wood and coal stoves and fireplaces
continuously since 1853.
Great things come in small packages: both the
Nordic QT and Lillehammer stoves combine
advanced gas technology with the warm,
traditional elements of cast iron. With proper use
and care, your Jøtul stove will provide you with
many years of safe, dependable and satisfying
service.
Both of these stoves are direct vented gas heaters
designed and approved for installation into a
variety of configurations where close clearance to
combustible material is required. Please take a
few minutes to familiarize yourself with this
manual and the features of your new Jøtul stove.

2

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Table of Contents
Specifications, GF 100 DV II .................. 4
Specifications, GF 200 DV II .................. 5
General Information ............................... 6
Service Tools .............................................. 6
Safety Information .................................. 7
Installation Requirements
Location ................................................. 7
Hearth Protection .............................. 7
Clearances ........................................... 8
Mantel & Trim ..................................... 8
Alcove ..................................................... 8
Vent Requirements
Adding Restriction.............................. 9
Vertical Termination ........................ 10
Horizontal Termination................... 12
Vent Terminal Clearances ............... 14
Mobile Home Installation ................... 15
Fuel Conversion ...................................... 15
Gas Connection ...................................... 17
Gas Pressure ............................................ 18
High Altitude Adjustment .................. 18
Air Shutter Adjustment ....................... 19
Wall Thermostat .................................... 20
Remote Control ...................................... 20
Log Set Installation ............................... 20
System Check .......................................... 21
Operation ................................................. 22
Maintenance ........................................... 22
Glass Replacement ............................ 22
Optional Blower ..................................... 24
Illustrated Parts Breakdown ........ 26, 27
Replacement Parts List .................. 28, 29
Addendum - Brick Panel Kit ................ 30
Lighting Instructions ............ Back Cover

THIS PRODUCT MUST BE
INSTALLED BY A LICENSED
PLUMBER OR GAS-FITTER WHEN
INSTALLED IN THE COMMONWEALTH OF MASSACHUSETTS.

Jøtul GF 100 DV II Nordic QT
and

Jøtul GF 200 DV II Lillehammer
Direct Vent Gas Heaters
Manufactured and Distributed by:
Jøtul A.S.A.
Fredrikstad, Norway
Jøtul North America
Gorham, Maine

MEA No. 369-04-E

Test Standards
This appliance complies with National
Safety standards and is tested and listed by
Intertek Testing Services of Middleton,
Wisconsin to
ANSI Z21.88-2002•CSA 2.33-M02 and
CSA P.4.-01.2 for Canada.
DO NOT ATTEMPT TO ALTER OR MODIFY
THE CONSTRUCTION OF THE APPLIANCE OR
ITS COMPONENTS. ANY MODIFICATION OR
ALTERATION WILL VOID THE WARRANTY,
CERTIFICATION AND LISTING OF THIS
APPLIANCE.

We recommend that our gas
products be installed and
serviced by professionals who
are certified in the U.S. by the
National Fireplace Institute®
(NFI) as NFI Gas Specialists.

3

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Jøtul GF 100 DV II Nordic QT
Specifications

20 5/8”
524 mm

Input Rates
Natural Gas
17,000 BTU/hr. maximum input
9,900 BTU/hr. minimum input

22 1/4”
565 mm

Propane
16,000 BTU/hr. maximum input
8,700 BTU/hr. minimum input

Inlet Pressure:

MIN

MAX

Natural Gas: 5.0 WC (1.24 kPa)
Propane:
12.0 WC (2.98 kPa)

7.0 WC (1.74 kPa)
14.6 WC (3.63 kPa)

Manifold Pressure:

MAX
3.8 WC (0.94 kPa)
11.0 WC (2.74 kPa)

MIN
Natural Gas: 1.2 WC (0.29 kPa)
Propane:
2.9 WC (0.72 kPa)
Piezo Ignitor / Standing Pilot

18 1/4”
464
mm

16 3/4 ”
425 mm

Weight: 150 lbs.

The Jøtul GF 100 DV II Nordic QT is a Direct Vent
gas heater designed as a sealed combustion, air
circulating gas appliance for residential applications.
This appliance is approved for installation using
6 5/8" X 4" vent pipe from the following manufacturers:
Simpson Dura-Vent GS
Security Vent, Ltd.
Amerivent Inc.
Selkirk Metalbestos
The Jøtul GF 100 DV II Nordic QT gas stove is
designed to burn NATURAL GAS or PROPANE only. It
is shipped from the factory equipped to burn Natural
Gas. If use with Propane is desired, the stove must
first be converted for use with that gas. Use the LP
Fuel Conversion Kit 155628 included with this stove
See page 14 for instructions.

16 3/4”
425 mm

Leg To
Leg

14”
356 mm

GF 100 DV II Miscellaneous Kit Contents

GF 100 DV II Accessories

• Fuel Conversion Kit - LP ................................ 155628

• Blower Kit ......................................................... 155631

• Rear Air Intake Restrictor Plate, Black -22111092
or Jøtul Iron - 22111085

• Antique Brick Kit ............................................ 155815

• Side Air Intake Restrictor Plates, (2) .... 22099192
or Jøtul Iron - 22099185

• Wall Thermostat ............................................ 750003

* Decorative Wall Shield, Black ................ 22092692
or Jøtul Iron..... 22092692

4

Flue Collar
Centerline

• Fuel Conversion Kit - NG .............................. 155629
• Remote Control .............................................. 129706
• Mobile Home Floor Bracket Kit ................. 154342

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Jøtul GF 200 DV II Lillehammer
Specifications
24 3/4”
630 mm

Input Rates
Natural Gas
20,000 BTU/hr. maximum input
11,400 BTU/hr. minimum input

Propane
22 3/4”
560 mm

18,000 BTU/hr. maximum input
8,450 BTU/hr. minimum input

Inlet Pressure:

MIN

Natural Gas: 5.0 WC (1.24 kPa)
Propane:
12.0 WC (2.98 kPa)

Manifold Pressure:

MIN
Natural Gas: 1.2 WC (0.29 kPa)
Propane:
2.9 WC (0.72 kPa)

MAX
7.0 WC (1.74 kPa)
14.6 WC (3.63 kPa)
MAX
3.8 WC (0.94 kPa)
11.0 WC (2.74 kPa)

Leg To
Leg

17 1/4”
13”
438 mm
330 mm

18 1/2”
470 mm

Piezo Ignitor / Standing Pilot
Weight: 180 lbs.

The Jøtul GF 200 DV II Lillihammer is a Direct
Vent gas heater designed as a sealed combustion, air
circulating gas appliance for residential applications.
This appliance is approved for installation using
6 5/8" X 4" vent pipe from the following manufacturers:
Simpson Dura-Vent GS
Security Vent, Ltd.
Amerivent Inc.
Selkirk Metalbestos
The Jøtul GF 200 DV II Lillehammer gas stove is
designed to burn NATURAL GAS or PROPANE only.
It is shipped from the factory equipped to burn
Natural Gas. If use with Propane is desired, the stove
must first be converted for use with that gas. Use
the LP Fuel Conversion Kit 155626 included with this
stove See page 14 for instructions.

24 3/4”
630 mm
21 1/8”
537 mm
18 ”
457 mm

As shipped
with 6”
(152 mm)
Legs

Height Dimensions with Optional Legs
Plinth Kit - subtract I” (25 mm)
Long Legs - add 2 1/4” (57 mm)

GF 200 DV II Accessories
• Fuel Conversion Kit - NG ..................................................... 155627
• High Altitude Adjustment Kit - NG ................................ 155808
• High Altitude Adjustment Kit - LP ................................. 155809
• Blower Kit ................................................................................ 155631
• Antique Brick Kit ................................................................... 155815

GF 200 DV II Miscellaneous Kit Contents
• Fuel Conversion Kit - LP ................................ 155626
• Rear Air Intake Restrictor Plate, Black -22111092
or Jøtul Iron - 22111085
• Side Air Intake Restrictor Plates, (2) .... 22099192
or Jøtul Iron - 22099185
* Decorative Wall Shield, Black ................ 22092692
or Jøtul Iron..... 22092692

• Wall Thermostat .................................................................... 750003
• Remote Control ...................................................................... 129706
• Mobile Home Floor Bracket Kit .... GF 200 DV II (6”) / 154923
............................................................. for Long Legs (8”) / 750304
....................................................................... for Plinth Kit / 154342
• Long Leg Kits ............................................. Matte Black / 154929
.......................................................................... Blue Black / 154930
..................................................................... Forest Green / 154931
.................................................................................. Ivory / 154932
............................................................................. Jøtul Iron / 155366
• Plinth Kits .................................................. Matte Black / 350081
.......................................................................... Blue Black / 350082
.................................................................................... Ivory / 350083
.................................................................. Forest Green / 350084
............................................................................. Jøtul Iron / 350085

5

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

General Information
„ THIS HEATER MUST BE INSTALLED AND MAINTAINED
BY A QUALIFIED SERVICE AGENCY.

„ The installation and repair of this appliance must be
done by a qualified service person. Failure to properly
install and maintain this heater could result in an
unsafe or hazardous installation, which may result in a
fire, explosion, property damage, personal injury or loss
of life.

„ This appliance should be inspected before use and at
least annually. More frequent cleaning may be
required due to excessive lint from carpeting, bedding
material, etc. It is imperative that control compartments, burners, and circulating air passageways of the
appliance be kept clean.

Stove Setup
Inspect the stove for damage and contact your dealer
immediately if any is found. Check contents of the
Miscellaneous Kit against the lists on p. 4-5. Complete
the installation steps in the following order:
1.

Remove the Top Plate.
Simply lift it from the stove body.

2.

GF 100 DV II ONLY : Remove the Front Plate.
Slide it straight up to disengage it from the Side
Plates.

3.

GF 200 DV II ONLY: Open the Front Doors.
Cut the two cable ties that secure the doors closed.

4.

Remove the Glass Panel.
Open the two trunk latches at the top of the
firebox to disengage the Glass Panel Frame. Lift
the frame up and out of its channel. Set it aside,
out of the way, on a soft surface.

5.

Install Optional Blower if appropriate.

6.

Install Vent System / Air Restriction as appropriate.

7.

Install Fuel Conversion / High Altitude Adjustment if necessary.

8.

Plumb gas line to the stove. Leak Test.

9.

Install optional Brick Panels.

„ THIS APPLIANCE MUST NOT BE CONNECTED TO A
CHIMNEY OR FLUE SERVING ANY OTHER APPLIANCE.

„ The installation must conform to local codes. Your
local Jøtul dealer can assist you in determining what
is required in your area for a safe and legal installation. Some areas require a permit to install a gas
burning appliance. Always consult your local building
inspector, or authority having jurisdiction, to determine what regulations apply in your area.

„ NOTE: Your local officials have final authority in
determining if a proposed installation is acceptable.
Any requirement that is requested by the local
authority having jurisdiction, that is not specifically
addressed in THIS manual, defaults to local code. In
the absence of local codes, the installation requirements must comply with the current National codes.
In the U.S., these requirements are established in the
National Fuel Code, ANSI Z223.1.(NFPA 54). In Canada,
the codes have been established in CAN/CGA B149
Fuel Installation Code.

„ Installer l’appareil selon les codes ou reglements
locaux, ou, en l’absence de tels reglements, selon les
Codes d’installation CAN/CGA-B149.

„ DO NOT OPERATE THIS STOVE IF ANY PART HAS BEEN
UNDER WATER. Call a qualified service technician to
inspect the heater and to replace any part of the
control system and any gas control which may have
been under water.

„ Ne pas se servir de cet appareil s’il a ete’ plonge dans
l’eau, completement ou en partie. Appeler un
technicien qualifie pour inspecter l’appareil et
remplacer toute partie du syste’me de controle et
toute commande qui ont ete plonges dans l’eau.

6

10. Install Log Set and Ember Stones.
11. Replace Glass Panel. Test Burner and adjust air
shutter if necessary.
12. Replace Front Panel and Top Plate.
13. Install optional Remote Control or Thermostat.

Suggested Tools for
Installation and Service
•
•
•
•
•
•
•
•
•
•
•
•
•
•

External regulator (for Propane only)
Piping which complies with local code
Manual shut-off valve (T-Handle in Massachusetts)
Sediment trap - if required by code
Tee joint
Pipe wrench
Pipe sealant
10 mm open end wrench
1/2”, 7/16” open end wrench or deep socket
Phillips head screwdriver
• Safety glasses
Flat head screwdriver
• Torx T20 screwdriver
1/4” nut driver
• Leak test solution
4 mm allen wrench
• Reciprocating Saw
Gloves
• Power Drill

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Safety Information

Location

Your stove will reach high surface temperatures
during normal operation. Please note the following
cautionary information.

In selecting a location for the stove, consider the
following points:
1) Heat distribution
2) Vent termination requirements
3) Gas supply line routing
4) Traffic areas, furniture, draperies, etc.

„ Due to the high operating temperatures, this
appliance should be located out of traffic areas
and away from furniture and draperies.

„ Children and adults should be alerted to the
hazards of high surface temperatures and
should stay away to avoid burns and/or clothing
ignition.

„ Young children should be supervised while they
are in the same room as the gas stove.

„ Clothing or other flammable materials should
not be placed ON or NEAR the stove. Surveiller
les enfants. Garder les vetements, les meubles,
l’essence ou autres liquides a vapeur
inflammables loin de l’appareil.

„ NEVER store or use gasoline or any other flammable vapors or liquids in the vicinity of the
stove.

„ Never burn any other materials in your gas
stove, it is strictly designed for use with natural
gas or propane fuel ONLY.
·„ Any safety screen, glass or guard removed for
servicing the appliance must be replaced prior
to operating the appliance.

Glass Front
Do not operate the this appliance if the glass panel has
been removed, cracked, or broken. Replacement of the
glass should be done by a licensed or qualified service
person. Only remove glass for routine service. Always
handle glass carefully.

The stove may be located on or near conventional construction materials, however, proper
clearance to combustibles must be maintained in
order to provide adequate air circulation around the
appliance. Also, it is important to provide adequate
access around the stove for servicing and proper
operation.
The clearance and hearth specifications listed in
this manual are the minimum requirements for
combustible material. A combustible material is
anything that can burn (i.e. sheet rock, wall paper,
wood, fabrics etc.). These surfaces are not limited to
those that are visible and also include materials that
may be located behind non-combustibles.
If you are not sure of the combustible nature of a
material, consult your local fire officials. Remember,
“Fire Resistant” materials are considered combustible: they are difficult to ignite, but will burn. Also,
“fire-rated” sheet rock is considered combustible.

Hearth Requirements
The GF 100 DV II and GF 200 DV II should not be
installed directly on carpeting, vinyl, linoleum or
Pergo®.
If the appliance will be installed on any combustible material OTHER THAN WOOD, a floor pad must
be installed that is either metal or wood, or a listed
hearth pad. This floor protection must extend the
full width and depth of the appliance. It is not
necessary to remove carpeting, vinyl or linoleum
from underneath the floor protection. See fig. 1.
Figure 1. Suggested hearth dimensions shown are
slightly larger than the minimum requirement.

18”
(457 mm)

24”
(609 mm)

7

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer
Max. Mantel
Depth

Stove and Vent Clearance
Requirements

11.5”

9.5”
7.5”
5.5”

Max. Top Trim
Depth = 1”

For Both Stoves
Rear:

0” (0 mm)

Ceiling:

42” (1066 mm)

Corner:

2” (50 mm)

Sides:

3” (76 mm)

A
B

F

D
G

Horizontal Run:
Off the top of the pipe

2” (50 mm)

Off the sides and bottom

1” (25 mm)

Vertical Run:
1” (25 mm)

Alcove Installation
Maximum Alcove Depth:

24” (610 mm)

Minimum Alcove Width:

34” (864 mm)

Minimum Ceiling Height
from stove top:

E

C

Minimum Clearances between Vent Pipe and
Combustible Materials:

All sides

Min. Mantel
Depth

3.5

Minimum Clearances from the Stove to Combustibles:
Measured from the stove top plate. See figs. 2-4.

GF 100 DV II
Nordic QT

A
B
C
D
E
F
G

GF 200 DV II
Lillehammer

50 in. (1270 mm)

52 1/2 in. (1333 mm)

48 1/2 in. (1232 mm)

51 in. (1295 mm)

47 in. (1194 mm)

49 1/2 in. (1257 mm)

45 1/2 in. (1156 mm)

48 in. (1219 mm)

44 in. (1118 mm)

46 1/2 in. (1181 mm)

4 1/4 in. (108 mm)

4 1/4 in. (108 mm)

22 1/4 in. (565 mm)

24 3/4 in. (629 mm)
Plinth Kit: 23 3/4 in. (603 mm)
Long Legs: 27 in. (686 mm)

Figure 3. Mantel Clearances - stove flush with fireplace face.
Max. Mantel
Depth

42” (1066 mm)

11.5”

9.5”
7.5”
5.5”
3.5

CLEARANCE TO REAR WALL = ZERO (0”)

GF 100 DV
or
GF 200 DV

Min. Mantel
Depth
Max. Top Trim
Depth = 1”

A
Max. Depth
24”
(610mm)

B

F

E

C
D

G

Min. 34”
(864 mm)

Max.
6 1/2”

GF 100 DV II
Nordic QT

Figure 2. Alcove Installation Clearances.
A
B
C
D
E
F
G

GF 200 DV II
Lillehammer

49 in. (1245 mm)

51 1/2 in. (1308 mm)

47 1/2 in. (1206 mm)

50 in. (1270 mm)

46 in. (1168 mm)

48 1/2 in. (1232 mm)

44 1/2 in. (1130 mm)

47 in. (1194 mm)

43 in. (1092 mm)

45 1/2 in. (1156 mm)

17 3/4 in. (451 mm)

17 3/4 in. (451 mm)

22 1/4 in. (565 mm)

24 3/4 in. (629 mm)
Plinth Kit: 23 3/4 in. (603 mm)
Long Legs: 27 in. (686 mm)

Figure 4. Mantel Clearances - stove set back into fireplace,
6 1/2” maximum.

8

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Venting Requirements

Intake Air Restriction

Both stoves may be installed with a vertical or horizontal
termination and must conform to the configuration
requirements described in this section. Vent components
from the manufacturers listed below are approved for use:
• Simpson Dura-Vent GS
• Selkirk Metalbestos
• Security Vent Ltd.
• Amerivent Corporation
Use parts of one manufacturer only - DO NOT MIX VENT
COMPONENTS FROM DIFFERENT MANUFACTURERS IN
THE SAME SYSTEM.
Installation of any components not manufactured or
approved by Jøtul or failure to meet all clearance requirements will void all warranties and could result in property damage, bodily injury, or serious fire.
The approved vent configurations described in this
manual are derived from extensive testing under controlled laboratory conditions. Gas appliance performance
can be negatively affected by variables present in the
installation environment, i.e: atmospheric pressure,
strong prevailing winds, adjacent structures and trees,
snow accumulation, etc. These conditions should be
taken into consideration by the installer and stove owner
when planning the vent system design.

You may need to restrict air intake to the burner, depending on the stove vent configuration. Two Side Restrictor
Plates and one Rear Restrictor Plate are included in the
Miscellaneous Kit for this purpose. Use the following
guidelines to determine the proper restriction, if any, for
your installation.

Horizontal Termination
No air restriction should be necessary. Do not install the
restrictor plates.

Vertical Termination
1. For Any Vertically Terminated Stove - Fig. 5.
Remove the Recirculator Plate from the back of the
Burner Skirt. It is secured by a single sheet metal screw.
2. Optional Restriction - Fig. 6.
A) Termination less than 8 ft. high:
Install Rear Restrictor Plate. Engage the plate with the
two pins on the back of the Burner Skirt.
B)
Termination 8 - 15 ft. high:
Install the Side Restrictor Plates, in addition to the Rear
Restrictor Plate. The plates are interchangeable.
Engage each plate with the pin on either side of the
Burner Skirt.

IMPORTANT
• JOINT SEALING REQUIREMENT: APPLY A 1/8” BEAD OF
HIGH-TEMPERATURE SEALANT (SUCH AS MIL-PAC®) TO
THE MALE SECTION OF THE INNER
VENT PIPE. THE CEMENT
SHOULD FORM A SEAL
BETWEEN THE INNER AND
OUTER PIPES.
• NEVER MODIFY ANY
VENTING COMPONENT, OR
USE ANY DAMAGED
VENTING PRODUCT.

SE
AL
AN
T

• THE GAS APPLIANCE AND
VENT SYSTEM MUST BE
VENTED DIRECTLY TO THE
OUTSIDE OF THE BUILDING
AND NEVER ATTACHED TO
A CHIMNEY SERVING A SOLID FUEL OR GAS BURNING
APPLIANCE. EACH DIRECT VENT GAS APPLIANCE MUST
HAVE ITS OWN SEPARATE VENT SYSTEM. COMMON
VENT SYSTEMS ARE PROHIBITED.
• IF VENTING SYSTEM IS DISASSEMBLED FOR ANY
REASON, REINSTALL PER THE INSTRUCTIONS PROVIDED
FOR THE INITIAL INSTALLATION.

Recirculator Plate

Figure 5. Remove Recirculator Plate.
Rear Restrictor Plate

Side Restrictor Plates

Figure 6. Installing the Air Intake Restrictor Plates.

9

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Vertical Vent Termination

15 Ft.

(457.2 cm)

„ The termination should fall within the shaded area of
the grid depicted in fig.7 below.
Maximum Vertical must not exceed 15 ft. (4.57 m)
measured from the top of the stove.

„ In no case shall any discharge opening on the termination cap be less than 18” (457 mm) horizontally
from the roof surface. See fig. 8.

„ In addition the 90° elbow attached to the stove, a
vertical vent run may utilize one 90° or two 45°
elbows. Whenever possible use 45° elbows instead of
a 90° elbow as they are less restrictive to exhaust gas
and intake air flow.

VERTICAL RUN

The Jøtul GF 100 DV II and Jøtul GF 200 DV II are approved for vertical venting through a ceiling or to a roof
termination following these guidelines:

10 Ft.

(305 cm)

5 Ft.

(152.4 cm)

„ Steep roofs, nearby trees, and predominantly windy
conditions can contribute to poor draft and/or
promote down-draft occurrences. Increasing the
height of the vent may alleviate these conditions.

4 Ft.
(121.9 cm)

HORIZONTAL RUN

„ Use approved vent manufacturer’s Wall Straps to
„ A firestop is required at every floor. Firestops are
available from all vent manufacturers. The opening
should be framed to 10" X 10" inside dimension.

„ Always maintain a minimum 1" clearance from all
sides of the vertical vent system.

„ Remove the Recirculator Plate from the back of the
Burner Skirt as shown in fig. 5. Determine which Air
Intake Restrictor plates should be used by following
the guidelines on page 9.

• ANY VENTING WITH A VERTICAL RISE MUST
TERMINATE (END) WITHIN THE SHADED AREA.
• MAXIMUM ELBOWS: TWO 90° OR ONE 90°
AND TWO 45°.
• ALWAYS MAINTAIN THE PROPER CLEARANCES
TO COMBUSTIBLES.
Figure 7. Vent Termination Diagram - any termination
must fall within the shaded area dimensions.

Horizontal Overhang

18”.
min.

Termination
Cap

18”.
min.

Vertical Wall

support an offset pipe run at three feet intervals to
avoid excessive stress on the offsets.

Lowest Discharge
Opening

18” min.

Figure 8. Minimum vertical termination height and roof
clearance.

10

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

High Wind
Cap

Exhaust Gas

Venting Through a Fireplace
Co-linear Vent Installation
This appliance may be vented through a masonry or
Class A prefabricated chimney using a Co-linear Flexible
Vent system approved for use with a solid-fuel burning
fireplace. When installed in the manner described below,
this system can improve the performance of the appliance in cold climate situations, as well as simplify the
vent installation. See fig. 9.

Intake Air

Max.
Co-linear
Height 15 ft.
(10.66 m)
Min.
Co-linear
Height 8
ft.
(2.44 m)

These installation requirements must be followed:
1. Prior to the installation the chimney flue must be
thoroughly cleaned and inspected by a qualified
chimney service person.
2. In a masonry chimney, a fireclay liner must be present
the entire length of the chimney.
3. Prefabricated chimneys must be UL 103 or ULC S-629
listed and have a minimum INSIDE diameter of 6
inches, (150 mm).
4. No appliance can be installed into a chimney flue
serving any other appliance of any kind.
5. THE AIR INTAKE FLEX PIPE MUST EXTEND BEYOND THE
DAMPER AREA OF THE FIREPLACE. If the intake flex
duct does not extend the full length of the chimney
and connect to both the unit and the termination
cap, A METAL BLOCK OFF PLATE MUST BE CONSTRUCTED AND INSTALLED ABOVE THE UNIT PRIOR TO
THE END OF THE INTAKE FLEX AND MUST COMPLETELY SEAL THE CHIMNEY FLUE FROM THE ROOM.

Air Intake Flex
pipe must
extend above
the damper.

Consult with the local code authority having jurisdiction before proceeding with this type of installation.
Refer to the vent manufacturer’s instructions for
specific installation requirements.
WARNING: FAILURE TO POSITION THE PARTS AND
STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR
FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED
FOR USE WITH THIS APPLIANCE, MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY. BE SURE TO
MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES
AS DEFINED IN THIS MANUAL AND IN THE INSTRUCTIONS PROVIDED WITH EACH VENT COMPONENT.

Sealed
Damper

Max.
Offset 24”
(609 mm)

Figure 9.
Co-linear Adaptor installed through a masonry chimney.

A

B

Figure 10. Simpson Dura-Vent #923GCL Co-linear Adaptor.
GF 100 DV II:
A : 16 3/4”
B : 20 3/4”
GF 200 DV II:

A : 18”
B : 22”
Add 2 1/4” with Long Legs.
Subtract 1” with Plinth

11

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Horizontal Vent Termination
„ Wall Cut-out Opening: A minimum 10" X 10"
(250 mm x 250 mm) square hole is required for proper
pipe clearances through a combustible wall. Use one of
the approved vent manufacturers’ WALL THIMBLE for
the wall penetration.

Decorative
Wall Shield

Zero
Clearance
to Rear

DO NOT FILL AIR SPACE WITH ANY TYPE OF INSULATION.

Min. 6 in.
Max. 48 in.
Horizontal Run

„ The minimum horizontal run made directly off the
rear of the stove into a standard horizontal cap shall be
no less than a 6” (152 mm) vent section. See fig. 11.

„ The maximum horizontal run made directly off the

Standard
Horizontal
Termination

rear of the stove into a standard horizontal termination must not exceed 4 ft. (1219 mm) See fig. 11.

„ Corner Installation: Max. Horizontal Run is 2 ft. (610 mm).
See Fig. 12.

„ A horizontal termination must fall within the shaded

Figure 11. Min. / Max. Horizontal Run

area illustrated in fig. 7, Vent Termination Diagram.

„ The horizontal termination cap must maintain a 3"
clearance to any overhead combustible projections
2 1/2" or less. It must also maintain 12" clearance
from projections exceeding 2 1/2". See fig. 14.

45°
Elbow

Min. 6” (152 mm)
Max. 24” (610 mm)

„ Any horizontal run of vent must be level or have a
1/4" rise for every foot of run toward the termination
cap. NEVER ALLOW THE VENTING TO RUN DOWNWARD FROM STOVE TO TERMINATION; DOWNWARD
VENT RUNS TRAP HEAT AND CAUSE HIGH TEMPERATURES TO DEVELOP WITHIN THE VENT THAT COULD
START A FIRE.

See Note F
Fig. 17
Min. 2”
51 mm
Standard
Horizontal
Termination
Cap

„ Install a Vinyl Siding Standoff between the vent
termination and an exterior wall covered by vinyl
siding material to prevent potential heat damage to
the siding.

„ Do not recess the termination cap into a wall or
siding.

12

Wall Thimble
and Trim Collar
Min. 2”
51 mm

Figure 12. Corner Installation, Horizontal Termination
directly off rear. Maximum Horizontal run is 2 ft.
(610 mm).

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Max. 4 ft.
Horizontal
Run

Wall Thimble
and Trim Collar

Wall Shield Installation
Max. Two
90° Elbows
or One 90°
and Two
45° Elbows

Max. 15 ft.
Vertical Vent
Run

The decorative Wall Shield, included in the Miscellaneous
Hardware bag, is used to obscure the vent hole in the
wall in installations vented directly off the rear of the
stove. Follow this procedure:
1. Remove the top two 1/4” hex head screws from the
rear shroud of the stove.
2. Align the holes in the wall shield with the holes in the
rear shroud.
3. Secure the wall shield to the stove with the two 1/4”
hex head screws. See fig. 16.

Figure 13. Horizontal Termination with Vertical Rise.

12 ”
305
mm

2 1/2”
64 mm
3”
76 mm

Figure 15.
Wall Shield installation.

Figure 15. Termination Clearance to overhangs

13

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Horizontal Termination Clearance

Figure 17. Vent Terminal Clearances - National Fuel Gas Code.
A = Clearance above grade, veranda, porch , deck, or
balcony : 12 inches (30 cm) minimum.

I = Clearance to service regulator vent outlet:
3 feet (91 cm) minimum.

B = Clearance to window or door that may be opened:
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN.
We recommend 12in. minimum to prevent condensation on the window.

J = Clearance to nonmechanical air supply inlet to building or
the combustion air inlet to any other appliance:
12 inches (30 cm) minimum.

C = Clearance to permanently closed window:
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN
We recommend 12 in. minimum to prevent condensation on the window.
D = Vertical clearance to ventilated soffit located above
the terminal within a horizontal distance of 2 feet (60 cm)
from the centerline of the terminal: 18 inches
(46 cm) minimum.

L = 1 Clearance above paved sidewalk or a paved driveway
located on public property: 7 feet (2.1 m) min.
M = Clearance under veranda, porch, deck, or balcony:
12 inches (30 cm) minimum. 2

E = Clearance to unventilated soffit: 12 inches (46 cm)
minimum.

* In accordance with CSA B149.1 Installation Codes.

F = Clearance to outside corner: **Min. 9 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.

** In accordance with the current ANSI Z223.1/NFFPA 54,
National Fuel Gas Code. Note: Local Codes and Regulations may
require different clearances.

G = Clearance to inside corner: ** Min. 6 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
H = *Not to be installed within 15 feet (4.5 m) above a
meter/regulator assembly within 3 feet (90 cm)
horizontally from the center-line of the regulator.

14

K = Clearance to a mechanical air supply inlet:
**Min. 3 feet (91 cm) above if within 10 feet horizontally,
U.S. / *6 feet (1.83 m) minimum / CAN

A vent shall not terminate directly above a sidewalk or driveway
which is located between two single family dwellings and serves
both dwellings.
2
Only permitted if veranda, porch, deck, or balcony, is fully open
on a minimum of two sides beneath the floor.*
1

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Mobile Home Installation

Fuel Conversion

These appliances can be installed for use in a mobile
home in the U.S. and Canada provided:

Your gas stove is shipped from the factory equipped to
burn NATURAL GAS only. If PROPANE gas is to be used as
fuel, the appliance must first be converted for use with
propane.

1. The stove is secured to the floor of the mobile home.
Use the Jøtul Floor Bracket Kit appropriate for your
stove’s leg; see the Accessories listing on p. 29.
2. Provision must be made to secure an electrical ground
between the stove and the mobile home chassis.
3. The stove is installed in accordance with Title 24 CFR,
Part 3280- Manufactured Home Construction and
Safety Standard, in the U.S. In Canada, comply with
CSA Z240.4, Gas Equipped Recreational Vehicles and
Mobile Housing.
4. Always contact your local officials about installation
restrictions and requirements in your area.
THIS APPLIANCE MAY BE INSTALLED AS AN
OEM INSTALLATION IN A MANUFACTURED
(MOBILE) HOME AND MUST BE INSTALLED IN
ACCORDANCE WITH THE MANUFACTURER’S
INSTRUCTIONS AND THE MANUFACTURED
HOME CONSTRUCTION AND SAFETY STANDARD, TITLE 24 CFR, PART 3280. THIS APPLIANCE IS ONLY FOR USE WITH THE TYPE OF
GAS THAT IS INDICATED ON THE STOVE’S
RATING PLATE. A GAS CONVERSION KIT IS
PROVIDED WITH THE NORDIC QT DIRECT
VENT GAS STOVE.
THIS APPLIANCE MAY BE INSTALLED IN AN
AFTERMARKET PERMANENTLY LOCATED,
MANUFACTURED (MOBILE) HOME, WHERE
NOT PROHIBITED BY LOCAL CODES.
CET APPAREIL PEUT ETRE INSTALLE DANS
UN MAISON PREFABRIQUEE (MOBILE) DEJA
INSTALLEE A DEMEURE SI LES REGLEMENTS
LOCAUX LE PERMETTENT. CET APPAREIL
DOIT ETRE UTILISE UNIQUEMENT AVEC LES
TYPES DE GAS INDIQUES SUR LA PLAQUE
SIGNALETIQUE. NE PAS L’UTILISER AVEC
D’AUTRES GAS SAUF SI UN KITDE CONVERSION CERTIFIE EST INSTALLE.

GF100 DV II Nordic QT: Use Propane Conversion Kit
155628, supplied with the appliance.
GF200 DV II Lillehammer: Use Propane Conversion Kit
155626, supplied with the appliance.
WARNING:
THE CONVERSION KIT IS TO BE
INSTALLED BY AN AUTHORIZED JØTUL
SERVICE TECHNICIAN IN ACCORDANCE
WITH THE MANUFACTURER’S
INSTRUCTION AND ALL CODES AND
REQUIREMENTS OF THE AUTHORITY
HAVING JURISDICTION. FAILURE TO
FOLLOW THESE INSTRUCTIONS COULD
RESULT IN SERIOUS INJURY OR
PROPERTY DAMAGE. THE QUALIFIED
AGENCY PERFORMING THIS WORK
ASSUMES RESPONSIBILITY FOR THIS
CONVERSION.
IN CANADA:
THE CONVERSION SHALL BE CARRIED
OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND
IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN1-B149.1 AND .2
INSTALLATION CODE.
Tools required:
• 1/2” open ended wrench or deep-well socket, Torx T20
or slotted screwdriver, 4 mm allen wrench.
Conversion Kit Contents:
• 1, regulator tower labeled for propane
• 3, regulator tower screws
• 1, burner orifice (GF 100: #48 for NG, #56 for LP)
(GF 200: #46 for NG, 1.20 mm for LP)
• 1, pilot orifice (#51 for NG, #30 for LP)
• Label A - to be completed and applied to
the back of the stove
• Label B - apply to the stove’s Rating Plate
• Small valve label - apply to valve body
Conversion instructions are also shipped in the stove
with the conversion kit.

15

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Gas Conversion Procedure
1. Turn off gas supply to stove.
2.

15. Apply gas to the system and check for leaks using a
soapy water solution or electronic gas detector.

Remove the stove Top Plate (3).

3. GF 100 DV II Only: Remove the front plate from the
stove. Pull the casting straight up and out away from
the side panels. Pull the panel upward with one hand
while the other pushes against the top of the firebox.
4. Release the trunk latches at the top of the firebox.
Carefully lift the glass frame up and out.
5. Remove the Log Set using care not to scratch or
damage logs.
6. Remove the burner skirt. Using one hand, lift from
under the rear lip and let the skirt rotate vertically.
Then rotate counterclockwise to clear the firebox
opening as shown in fig. 18.
7.

Change the Main Burner Orifice. Fig. 19. Using a ½”
open ended wrench or deep-well socket remove the
burner orifice and replace with the appropriate orifice
supplied in the kit.
GF 100 DV II - #48 for NG
#56 for LP
GF 200 DV II - #46 for NG

1.20 mm for LP

8 CHANGE THE PILOT ORIFICE: From within the firebox,
remove the Pilot Head by pulling it straight up from
the pilot base. See fig. 20.
Using the 4 mm allen wrench that is included with
the conversion kit, unscrew the pilot orifice (counterclockwise). Replace with the appropriate orifice:
#51 for natural gas
#30 for propane gas

NEVER USE AN OPEN FLAME TO CHECK FOR GAS LEAKS.
Correct gas pressure is essential for efficient and safe
operation of this appliance. Correct gas pressure
must be established at the time of installation.
NOTE: Minimum LP Inlet pressure is 12.0 w.c.
For more details, see the Gas Pressure section of this
manual (page 17).
ALWAYS REFER TO THE LIGHTING INSTRUCTIONS ON
THE INSIDE BACK COVER OF THIS MANUAL WHEN
LIGHTING THE STOVE.
16. Adjust the Air Shutter: Locate and loosen the wingnut that secures the Air Shutter. See fig. 26. It is
under the stove, in the center toward the rear. Push
the shutter stem back to restrict air and forward to
increase air to the burner. You will need to experiment to find the best setting for your particular
installation. The shutter is set at the halfway position at the factory.
Be sure to tighten the wingnut on the Air Shutter
stem snugly after any adjustment. This ensures that
the burner remains locked in place.

Figure 18.
Remove the Burner
Skirt from the stove.

9. Tighten orifice into the base of the pilot assembly. To
prevent bypass leaks, be sure the orifice is secured
tightly and flush with the base. Replace pilot head by
pushing it down onto the pilot base. See fig. 20.
10. Replace the Variable Regulator. Using a Torx T-20
screwdriver, remove the three specialty screws from
the front of the valve regulator. See fig. 21.
11. Remove the Regulator Tower, Gasket, white plastic
disk, and Spring. Discard these parts.
12. Install the new variable regulator tower being sure that the
gasket is properly positioned and tighten screws securely.
13. Install the identification labels to the stove so that they can
be seen by any person that may be servicing the stove.
Label A: apply to back of stove.
Label B: apply to stove’s rating plate.
Small valve Label: apply to valve.
14. Reassemble the stove. CAUTION: Correct Burner
position is critical to proper function. Be certain that
the burner plate is properly engaged with the pins on
the firebox walls. The pins fit into the adjacent
notches on the sides of the burner plate. See figure 22.

16

Pilot
Assembly

Air Shutter

Orifice

Figure 19.
Burner orifice
and pilot
assembly
locations.

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Gas Supply Connection
Pilot Head

NOTE: If the optional Blower will be installed, use a 90°
Elbow off the valve to create adequate clearance for the
main gas line.

Orifice
Retainer
Clip

Pilot Base
Figure 20.
Pilot orifice removal and replacement.

Apply
small
label

Regulator
Tower

The use of a Flexible Gas Appliance Connector is
acceptable in many areas in the U.S. However, Canadian
methods vary depending on local code.
ALL INSTALLATIONS MUST COMPLY WITH LOCAL
CODE OR IN THE ABSENCE OF LOCAL CODE, MUST
COMPLY WITH THE MOST RECENT EDITION OF THE
NATIONAL FUEL GAS CODE ANSI Z223.1/NFPA 54 OR
CAN-B149.

Gasket

Mounting
Screws

The gas supply line connection is made to the valve just
inside the left rear leg. The gas supply line should be 3/8"
npt with a 1/2" diameter supply, or the appropriate size
to provide sufficient gas pressure to the valve regardless
of the input setting.

Figure 21. Regulator Assembly.

Figure 22.
Burner plate engagement.

Burner
Notch

All codes require a gas shut-off valve (gas cock) and
union, to be installed in the supply line, and in the same
room as the appliance. This allows for the disconnection
of the stove for servicing and maintenance. See fig. 23.
A T-HANDLE GAS COCK IS REQUIRED IN
MASSACHUSETTS TO COMPLY WITH CODE
248CMR.

Secure all joints tightly using appropriate tools and
sealing compounds. For propane units be sure to use
compounds that are propane resistant. Turn on gas
supply and test for gas leaks using a soapy water solution.
Never use an open flame to check for leaks.
Leak test:
1. Mix a 50-50 solution of water and dish soap.
2. Light appliance- see lighting instructions on the inside
back cover of this manual or on the stove’s rating plate.
3. Brush or spray all joints and connections with the soapy
water solution.
4. If bubbles appear at any connection or seam or a gas
odor is detected, immediately turn gas control knob to
the OFF position.
5. Tighten or reconnect the leaking joint and retest for any
gas leaks.

Pin
Figure 23.
Supply
valve
coupling.

17

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Gas Pressure

High Altitude Adjustment

Correct gas pressure is essential for efficient and safe
operation. It is important that the correct pressure is
established at the time of the installation. Proper gas
pressure provides a consistent flow of gas to the appliance and is instrumental in checking for gas leaks.

The decreased atmospheric pressure of higher altitudes
affects heat value of gaseous fuels. Most gas suppliers
derate the gas intended for use at elevations above 2000
feet. Check with your gas supplier before performing
derate adjustment to the burner.

Pressure Test: Attach a manometer to the appropriate test point on the valve. See fig. 24. The gauge connections are located on the front of the valve under the On/
Off/Pilot- knob. Gauge connections are identified by:

The GF 100 DV II Nordic QT does not require adjustment
for elevations up to 4500 ft. DO NOT DERATE.

A - for Manifold Pressure (the amount of gas that is
coming out of the valve to the burner.)

The GF 200 DV II Lillehammer may be adjusted for
altitude over 2000 ft. (610 - 1371 m). Check with your
gas supplier and, if necessary, install High Altitude
Adjustment Kit 155808 for Natural Gas, or Kit 155809
for Propane.

ALWAYS TEST PRESSURES WITH VALVE CONTROL KNOB
SET ON HIGH.

See the chart below for appropriate orifice sizes and
part numbers.

NECESSARY INLET GAS PRESSURES
(inches water column)

IN THE U.S:
THE DERATING KIT MUST BE INSTALLED BY AN
AUTHORIZED SERVICE TECHNICIAN IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS AND ALL CODES AND REQUIREMENTS
OF THE AUTHORITY HAVING JURISDICTION.
THE INFORMATION LABEL MUST BE FILLED
OUT BY THE INSTALLER AND APPLIED TO THE
APPLIANCE AT THE TIME OF THE CONVERSION.
THE QUALIFIED SERVICE AGENCY PERFORMING THIS WORK ASSUMES RESPONSIBILITY
FOR THIS DERATING.
IN CANADA,
THIS UNIT HAS BEEN TESTED FOR INSTALLATION AT HIGH ALTITUDES IN ACCORDANCE
WITH CANADIAN TEST STANDARD CAN/CGA2.17.
THE DERATING SHALL BE CARRIED OUT IN
ACCORDANCE WITH THE REQUIREMENTS OF
THE PROVINCIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE WITH
THE REQUIREMENTS OF THE CAN1-B-149.1
AND .2 INSTALLATION CODE.

E - for Inlet or Supply Pressure (the amount of gas
coming to the valve.)

NATURAL GAS
PROPANE

MIN

MAX

5.0
12.0

7.0
14.5

The appliance and its appliance main gas valve must
be disconnected from the gas supply piping system
during any pressure testing on that system at test
pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply
line by closing its individual manual gas shut-off valve
(gas cock) during any pressure testing of the gas supply
piping system that is equal to or less than pressures of
1/2 psig (3.5 kPa).
MANIFOLD PRESSURES
(inches water column)
MIN
MAX

NATURAL GAS
PROPANE

1.2
2.9

3.8
11.0

For high altitude installations, consult your local gas
distributor or the authority having jurisdiction for proper
rating methods. If the appliance is converted for high
altitude, the Conversion Label, supplied with the kit,
must be filled out by the installer and applied to the
appliance at the time of the conversion. See fig. 25.

E

A

Figure 24. Pressure test points.

18

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Flame Appearance Air Shutter Adjustment
WARNING: AIR SHUTTER ADJUSTMENTS SHOULD ONLY BE
PERFORMED BY A QUALIFIED PROFESSIONAL SERVICE
TECHNICIAN.

High Altitude Orifice Chart
GF 200 DV II Only
Elevation

Fuel

Orifice
Size

Part No.

0 - 2000 ft.
(0 - 610 m)

Natural Gas
Propane

#46
1.20 mm

220975
221185

2001 - 4500 ft.
(611 - 1370 m)

Natural Gas
Propane

#47
#56

220976
129466

Derating Procedure:
1. To derate this unit, install the appropriate orifice per
the High Altitude chart.
2. Remove the Burner Skirt and Burner Plate to expose
the main burner orifice.
3. Using a 1/2” open ended wrench or a deep-well
socket remove the burner orifice.
4. Replace with the appropriate orifice from the high
altitude kit.
5. Be sure to apply the high altitude conversion label
provided to the rating plate on the appliance.

THIS STOVE HAS BEEN CONVERTED FOR USE AT AN
ALTITUDE OF: ________________
Orifice Size: ____________ Manifold Press. _____
Input Btu/Hr. ___________ Fuel Type __________
Date of Conversion ___________

The air shutter setting at the burner orifice can be
adjusted to achieve the desired flame appearance. The
shutter is set in the mid-range at the factory, however,
you will want to adjust it if a fuel conversion kit has been
installed or if the flame pattern is not as desired. The
adjustment stem is located under the firebox, directly
behind the gas control valve. Generally, flame appearance
is a matter of preference, however most people enjoy a
warm yellowish flame.
Too much air - the appliance will generate a flame
that is blue and transparent, or an “anemic” flame.
Not enough air - the burner will generate very long
yellow flames resulting in soot. Sooting produces black
deposits on the logs, on the inside walls of the appliance,
and potentially on the exterior termination cap.
Sooting is caused by incomplete combustion in the
flames and lack of combustion air entering the air shutter
opening. Open the shutter setting to allow more air.
To adjust the air shutter:
1. Locate and loosen the adjustment stem wingnut
protruding from the bottom of the firebox, directly
behind the gas valve. See fig. 26.
2. Push the stem back to decrease air, or pull it forward to
increase air. Make adjustments in small increments
(1/8”) and allow the burner to “ settle in” for a few
minutes before making another one. Small shutter
adjustments can produce dramatic changes to flame
characteristics.
4. Re-tighten the wing nut when the desired flame
appearance has been achieved.

Figure 25. This label must be filled out and applied to the
appliance by the installer.
Open

Close

Figure 26.
Air Shutter adjustment

19

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Optional Wall Thermostat or
Remote Control
Use only a 750 millivolt DC two-wire circuit thermostat
with this appliance. The thermostat should be placed in
the same room as the heater, typically 5 feet off the
floor. Avoid drafty areas or any area that may affect the
accuracy of the thermostat.
The thermostat should be connected to the Nordic
QT using a minimum of 16 gauge wire with a maximum
length of 35 feet of wire.
Connect the two thermostat wire leads to the two
lower terminals on the terminal block located directly
to the right of the valve. Do not overtighten the connections. IT IS NOT NECESSARY TO DISCONNECT ANY
OTHER WIRES. See Fig. 27.
For thermostatic operation, the On/Off/T-Stat
switch on the back of the stove must be in the T-stat
position, and the pilot light must be running, as it is the
power source for the thermostat.
At the thermostat, the two wires should be connected to the two connection screws on the thermostat
base plate per the manufacturer’s instructions.

Log Set Installation
NOTE: Install the optional Brick Kit, if appropriate, before
installing the Log Set. See page 30.
The Log Set and Ember Stones are packaged in foam
inside the firebox. These must be installed in the firebox
prior to burner operation. Wear gloves to prevent skin
irritation from the ceramic fibers.
Position the Rear Log assembly as shown in fig 28,
engaging the pins on the burner skirt with the adjacent
holes in the underside of the log.
Locate the Middle Log as shown in fig. 29.
Also included is a bag of ember stones that simulate
glowing coals when the burner is operating. These
should be spread thinly over the burner plate.
NOTE: Keep the ember stones 1/4” away from the
edge of the Burner Skirt. All the embers do not have to
be used.

Remote Control
When using a remote, the remote receiver should be
wired to the terminal block the same way the thermostat would be. See the instructions above.
Follow the operating instructions included with the
Remote Control unit.
CAUTION:
LABEL ALL WIRES PRIOR TO DISCONNECTION
WHEN SERVICING THE CONTROLS. WIRING
ERRORS CAN CAUSE IMPROPER OR DANGEROUS
OPERATION. ALWAYS VERIFY PROPER OPERATION AFTER SERVICING THE APPLIANCE.

Figure 28. Install Rear Log.

Pilot
Assembly
THERMOPILE

ROCKER
SWITCH
ON

TH

OFF

TP

STAT

TH
TP
VALVE

OPTIONAL
THERMOSTAT
or
REMOTE
CONTROL

TERMINAL
BLOCK

Figure 27. Accessory wiring diagram.

20

1/4”
6 mm

1/4”
6 mm

Figure 29. Middle Log and ember stones in place.

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

System Check
1. PURGING THE GAS LINE: When lighting the appliance for the first time, it will take a few moments to
clear the gas line of air. Once this purge is complete,
the appliance will operate as described in the
lighting instructions. See the inside back cover of
this manual or the stove Rating Plate attached the
bottom of the stove. Subsequent burner starts will
not require purging the gas line unless the supply
line is shut off.
2. PILOT FLAME: You can monitor the pilot flame
through the opening at the upper left corner burner
skirt, under the rear log. See fig. 29. The pilot flame
should be steady - not lifting or floating. The flame
should be blue in color around the pilot hood, with
traces of yellow toward the outer edges.
The pilot flame should engulf the top 3/8” of the
thermopile (to generate millivolt current) and the
top 1/8” of the thermocouple. The pilot flame
should project out of the pilot hood 1” at all three
ports. See figs. 30.
3. BURNER ADJUSTMENT: This stove is equipped with a
variable gas control valve that allows easy adjustment of the flame height appearance and heat
output. To adjust the flame, rotate the HI/LOW knob,
located in the center of the valve face.

1”
(25mm)
1/8”
(3mm)
Min.

3/8”
(8mm)
Min.

Figure 30. Proper pilot flame appearance.

CAUTION:
DO NOT ATTEMPT TO ALTER THE FLAME
APPEARANCE BY POSITIONING THE GAS
VALVE IN ANY OTHER POSITION OTHER
THAN THE FULL “ON” POSITION.

NO SMOKE OR SOOT SHOULD BE PRESENT. CHECK
LOG PLACEMENT IF ANY SOOT OR SMOKE IS
PRESENT. IF SOOT OR SMOKE PERSISTS, THE AIR
SHUTTER MAY NEED TO BE ADJUSTED.
See Air Shutter/Flame Appearance section of this
manual for proper air shutter settings and adjustments. Note: the more offsets there are in the vent
system, the greater the need for an air shutter
adjustment. See page 30.

Figure 31. Flame appearance on the “high” setting after
approximately 15 to 20 minutes burning.

WARNING:
AIR SHUTTER ADJUSTMENTS SHOULD ONLY BE
PERFORMED BY A QUALIFIED PROFESSIONAL
SERVICE TECHNICIAN.

21

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Operation
Familiarize yourself with the controls of your stove. Make
sure that anyone else using the appliance is also familiar
with the controls and operation procedures. Always
follow the Lighting Instructions on the inside back cover
of this manual and also located on the Rating Plate
attached to the burner assembly.
1. Once the pilot is lit, burner operation is controlled by
the rocker switch located at the left rear corner of the
stove. Use the T-STAT position for the optional thermostatic or remote control functions. See fig. 32.
2. During the first few fires, you may notice odor and/or
smoke from the stove. This is normal and results from
burn-off of manufacturing residue and curing of
materials. You may find it helpful to provide additional ventilation and fresh air to alleviate this condition.
3. Condensation may occur on the glass upon each
lighting of the appliance. This “fog” will disappear as
the appliance heats up.
4. Keep the controls and the area under the appliance
free of debris, vacuum this area frequently. Always
keep the appliance area clear and free from combustible materials, gasoline and other flammable liquids.
If a vacuum is used during any service on the stove,
ALWAYS be sure the stove is cold and there are NO
hotembers or sparks.
5. This appliance has a continuous burning pilot flame.
Exercise caution when using products having combustible vapors. Always shut-off gas supply while servicing the stove.
6. CAUTION: DO NOT OPERATE THIS APPLIANCE WITH
THE GLASS REMOVED CRACKED OR BROKEN. Replacement of the glass should be done by a licensed or
qualified service person. Use only replacement glass
provided by your authorized Jøtul dealer. Never use
any substitute materials.
WARNING: OBSERVE CAUTION WITH THE GLASS. THE
GLASS PANEL MAY SHATTER UNEXPECTEDLY IF STRUCK
WITH AN OBJECT. ALWAYS HANDLE THE GLASS PANEL
WITH CARE. WHEN SERVICING THE STOVE ALWAYS
PULL THE GLASS ASSEMBLY STRAIGHT UP FOR REMOVAL.
7. Clean the glass only when necessary. Wipe surface
with a clean, damp soft cloth. Follow with a dry, soft
towel as desired. Take care not to scratch the glass
surface.
WARNING: DO NOT USE ABRASIVE CLEANERS ON THE
GLASS. NEVER CLEAN THE GLASS WHEN IT IS HOT.

22

Figure 32. Burner Control Switch location.

Maintenance
This appliance and its venting system should be inspected before use and at least annually by a qualified
service technician.
IMPORTANT:
ALWAYS TURN OFF THE GAS SUPPLY TO THE STOVE BEFORE
ANY SERVICE WORK IS PERFORMED ON THE STOVE.
Vent System: The vent components should be inspected
annually to confirm it is clear of obstructions and all
connections are secure. Any joints disconnected must be
resealed using high temperature sealant when reassembled.
Firebox Cleaning: The firebox should be vacuumed
annually to remove any surface build up. Be sure to
vacuum or wipe off the pilot assembly and burner orifice
and burner tube. Handle the logset carefully as it is very
fragile.
Glass Cleaning: Use warm water and a soft cloth. Do not
use abrasive cleaning agents or strong detergents on the
glass. Be sure the glass is cool before cleaning.
Gasket Inspection: Inspect the glass gasket at least
annually. Examine the ribbon gasket for signs of deterioration and make sure the gasket has a positive seal.
Replace the gasket if it appears worn or damaged. Refer
to the replacement parts list on page 27.

Glass and Gasket Replacement
Only Use Replacement Kit 155599.
1. Use a small screwdriver to pry the four retainer clips off
of the glass frame. See fig. 33.
2. Peel away all remnants of the old gasket material and
clean any adhesive residue off the glass.
3. Peel the paper backing off the replacement gasket to
expose the adhesive.
4. Apply the gasket to the panel, wrapping the adhesive
side down around the panel edge. See fig. 34.
5. Insert the gasketed glass panel into the frame and
press the retainer clips back into place as shown.

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Record the following information to help
your dealer determine what you will need for
parts and service.
MODEL NAME: ________________________
SERIAL NUMBER: ______________________
DATE OF PURCHASE: ___________________
PURCHASED FROM: ____________________
NAME OF INSTALLER: ___________________
Figure 33. Removal and replacement of the glass panel.

TYPE OF FUEL: ________________________
WAS STOVE CONVERTED? _______________
NOTES:

Figure 34. Wrap the gasket around the glass panel.

Always replace any damaged or broken parts with
JØTUL AUTHORIZED PARTS ONLY. These are available
through your Jøtul dealer. Never use any substitute parts
on your stove.
With proper care and maintenance your appliance
will provide you with many years of enjoyment. If you
experience any problems or inconsistency with your
stove, contact your authorized Jøtul dealer for assistance.
RETAIN THIS MANUAL FOR REFERENCE AND
MAKE IT AVAILABLE TO ANYONE USING OR
SERVICING THE STOVE.

23

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Optional Blower # 155631
CONNECT THE GAS SUPPLY TO THE
STOVE BEFORE INSTALLING THIS
BLOWER. USE A 90° ELBOW OFF THE
GAS VALVE TO CREATE ADEQUATE
GAS LINE CLEARANCE.

„ THIS BLOWER MUST BE

ELECTRICALLY GROUNDED IN
ACCORDANCE WITH LOCAL CODES
OR, IN THE ABSENCE OF LOCAL
CODES, WITH THE CURRENT ANSI/
NFPA 70, NATIONAL ELECTRICAL
CODE OR CSA C22.1-CANADIAN
ELECTRICAL CODE.

„ THIS UNIT IS SUPPLIED WITH A

THREE-PRONG (GROUNDING) PLUG
FOR PROTECTION AGAINST SHOCK
HAZARD AND SHOULD BE PLUGGED
DIRECTLY INTO A PROPERLY
GROUNDED THREE-PRONG
RECEPTACLE. DO NOT CUT OR
REMOVE THE GROUNDING PRONG
FROM THE PLUG.

„

Contents
1. Blower
2. Snapstat Wire Harness
3. Control Box
4. Snapstat Bracket
5. Rheostat Knob
6. Snapstat
7. Mounting Bracket (GF100 DV II ONLY)
8. M6 Flange Nuts, (2)
9. M6 x 12 Hex Bolts, (2)
10. #8 x 1/2” Sheet metal screw, (4)

7
Upper Holes
for GF100
DV II
Lower Holes
for GF200
DV II

6

4

10

10
2
5

3

8

Figure 35. Blower Kit Components

Installation
1. Unpack and check the contents of the blower kit. Contact your dealer if any damage
is evident or parts are missing.
See fig. 35.

3. Attach the Control Box to the
studs located underneath the
stove in the middle of the
firebox floor using the two M6
hex nuts and a 10 mm socket
driver or wrench. See fig. 36.

24

• 10 mm socket
driver or wrench

10

ALWAYS DISCONNECT THE POWER
SUPPLY WHEN PERFORMING ANY
SERVICE ON THE FIREPLACE INSERT.

2. Attach the Control Box to the
Snapstat Bracket using two
#8 x 1/2” sheet metal screws.
As shown in fig. 35, use the
pair of mounting holes appropriate for your stove.

Tools Required
• 1/4” socket driver

MANUAL

Snapstat

OFF
AUTO

BLOWER

Secure with
two Hex Head
Flange Nuts

Figure 36. Attach Control Switch Box.

1

9

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Figure 37 . Attach Blower to
the stove bottom and
connect wires to Snapstat.

Mounting Bracket
for GF100 DV II
Snapstat
Connectors

#8 x 1/2” sheet
metal screws

M6 x 20 mm
Hex Bolts
4. Attach the Blower to the stove.
GF 100 DV II: First install the Mounting Bracket to
the holes in the bottom of the rear shroud using
two #8 x 1/2” sheet metal screws. Then attach the
Blower to the Mounting Bracket using the two M6
flange head hex bolts as shown in fig. 35 and 37.
GF 200 DV II: Attach the Blower directly to the
tapped hole in the cast iron stove bottom using the
two M6 flange head hex bolts.
5. Attach either Snapstat wire connector to either
Snapstat terminal. See figs.35 and 37.
6. Connect power cord to the nearest outlet.

BLOWER
G

W

BK

W

G

W

BL

BK

BK

POWER
SUPPLY

RHEOSTAT

SNAPSTAT
GY

BK

BL

SWITCH
MANUAL OFF AUTO

Figure 38. Blower Wiring Diagram

Blower Operation
The variable-speed blower will enhance heat circulation
around the firebox and out into the room. The blower is
controlled by a heat activated switch (snapstat) that
will ONLY function when the control switch is in AUTO
setting. After the fire has been burning for a time, the
snapstat will react to the heat and activate the blower.
Fan speed may be manually adjusted with the rheostat
knob. If the burner turns off, the blower will be shut off
automatically when the stove cools down.
If automatic blower circulation is not desired, place
the blower control switch in the MANUAL position.

CAUTION:
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING
ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION.
VERIFY OPERATION AFTER SERVICING.
ATTENTION:
Au moment de l’entrentien des commandes,
etiquietez tous le fils avant le
debranchement. es erreurs de ceblage
peuvent entra tun fonctionnement inadequat
et dangereux.

25

Figure 39.

26

8

7

6

14

26

17
21 22

18 63 19 23

25
31 30 20

22

47b

47a

16
24 29

22

48

65
66

4

49

34

35

38

37

36

10

46

44
45

42
43

51
64

41

52
50

59

40

61

60

39

53

4

27

24

33

4

56

13

D

57

15

C

62

5

4

4

54

28

B

58

12

11

A

10

4

4

3

2

1

55

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

GF 100 DV II / GF 200 DV II
Illustrated Parts Breakdown / Firebox Assembly

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Parts List - GF 100 DV II / GF 200 DV II Firebox Assembly
Part Description
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
A.
B.
C.
D.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.

24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.

Part Description

Part Number

Rear Shroud, Matte Black .............. 22055592
Rear Shroud, Jøtul Iron ................... 22055585
Burner Control Switch........................ 129123
Switch Box, Matte Black ................ 22092592
Switch Box, Jøtul Iron .....................22092585
Sheet Metal Screw, #8 x 1/2” ........... 117117
Air Diverter ............................................ 220981
Rating Plate ........................................... 220920
Rivet, 1/8” .............................................. 117946
Lanyard Cable ....................................... 129159
Bolt, M6 x 20 ......................................... 117117
Screw, #8 x 3/4” Hex ........................... 117986
Pilot Assembly ...................................... 129471
Electrode ................................................ 129765
Thermocouple ...................................... 129766
Pilot Line w/ Fittings ........................... 129446
Thermopile .......................................... 3094527
Pilot Spacer ........................................... 220546
Pilot Gasket ........................................... 129670
Air Shutter ............................................. 220928
Air Shutter Gasket ............................... 221107
Wing Nut ............................................... 117975
Washer, 25 x 1 1/2” ............................ 118029
Jam Nut .................................................. 129152
Orifice Holder ....................................... 220643
Main Gas Flex Tube ............................. 129390
Compression Nut ................................. 129464
Compression Sleeve ............................ 129463
Burner Orifice, #48 NG / GF100 ...... 129407
Burner Orifice, #56 LP / GF100 ........ 129466
Burner Orifice, #46 NG / GF200 ...... 220975
Burner Orifice, 1.20 LP / GF200 ....... 221185
Screw, 10-32 x 3/8” Phillips .............. 117911
Ignitor Bracket .................................... 3902576
Ignitor ................................................... 3902573
Screw, M4 x 8 Phillips ......................... 117920
Gas Valve, 50% Turn-down - NG ...... 220520
Terminal Block Bracket ...................... 220930
Screw, M4 x 12 Phillips ...................... 117921
Terminal Block, 2 Pole ........................ 129154
Nut, M4 Hex .......................................... 117922
Valve Retainer ....................................... 220924
Glass, Ceramic ...................................... 220576
Glass Gasket, Tadpole ......................... 129124
Glass Frame, Matte Black .............. 22136592
Glass Frame, Jøtul Iron ................... 22136585
Glass Replacement Kit ....................... 155599

Part Number

37.
38.

Middle Log ............................................ 221105
Rear Log .................................................. 221104
Log Set w/ Embers .............................. 155816
*Ember Stones, 4 oz. ........................... 129123
39. Dilution Air Cover ................................ 221108
40. Burner Skirt ........................................... 220797
41. Burner Plate .......................................... 220793
42. Burner Gasket ....................................... 220941
43. Burner Fastener, M6 AS Series ......... 118007
44. Burner Base ........................................... 104253
45. Venturi Tube .......................................... 220796
46. Tube Holder, Cast Iron ........................ 103992
47a. Valance Bolt, M6 x 100 Hex Hd ....... 117955
(for GF 100 DV II)
47b. Valance Bolt, M6 x 130 Hex Hd ....... 118033
(for GF 200 DV II)
48. Valance Door, Matte Black ............ 22093192
Valance Door, Jøtul Iron .................22093185
49. Firebox .................................................... 221324
50. Hex Nut, M6 ............................................... 9930
51. Exhaust Baffle ...................................... 220927
52. Glass Frame Latch ............................... 129135
53. Relief Door Guide ................................ 129499
54. Relief Door Gasket ............................... 220735
55. Relief Door ............................................. 220589
56. Adapter Pipe Gasket ........................... 129118
57. Adapter Pipe ......................................... 129322
58. Wallshield, Matte Black .................22092692
Wallshield, Jøtul Iron ...................... 22092692
59. Air Deflector, Burner Skirt ................. 221109
60. Rear Restrictor Plate, Matte Blk ... 22111092
Rear Restrictor Plate, Jøtul Iron ... 22111085
61. Side Restrictor Plate, Matte Blk ... 22099192
Side Restrictor Plate, Jøtul Iron .... 22099185
62. Wire Harness, Burner Control .......... 155813
63. Star Washer ........................................... 118032
64. Burner, Complete ................................. 155600
65. Valance Hinge Spacer, 1” GF200 only . 118039
66. Valance Hinge Spacer, 3” ................... 118040
67. *Orifice Retainer .................................. 221367
68. *Tinnerman Clip (4) ............................. 220044

* Parts not illustrated
ALWAYS USE REPLACEMENTS PARTS
PROVIDED BY AN AUTHORIZED JØTUL
DEALER ONLY.

27

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Illustrated Parts Breakdown / Cast Iron and Associated Hardware
GF 100 DV II Nordic QT
1

4
4

2

3

2
Figure 40 .

GF 200 DV II Lillehammer
1
3

2

2
11

10

12

10

8

10
7

6
4
5
Figure 41.

28

9
10

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Cast Iron Parts List
GF 100 DV II Nordic QT
1.
2.
3.

Cast Iron Parts
Top Casting
Side Panel
Front Panel

Matte Black
10391092
10426992
10390992

Blue Black
10391027
10426927
10390927

Ivory
10391029
10426929
10390929

4.

Screw, M6 x 12 Truss Head Phillips, (4) ........ 118045

Forest Green
10391032
10426932
10390932

Jøtul Iron
10391085
10426985
10390985

Jøtul Iron Enamel
10391046
10426946
10390946

GF 200 DV II Lillehammer
Cast Iron Parts
Top Casting
Side Panel
Front Panel
Bottom Plate
Leg, 6”
Left Door
Right Door
Front Assembly*

1.
2.
3.
4.
5.
6.
7.

Matte Black
10390692
10390792
10390592
10390092
10195292
10425592
10425692
15592392

Blue Black
Ivory
10390627
10390629
10390727
10390729
10390527
10390529
10390027
10390029
10195227
10195229
10425527
10425529
10425627
10425629
155925
155927
* Front Assembly includes Front,

Hardware- GF 200 DV II
8.
9.
10.
11.
12.

Hinge Pin, (4) ................................................. 129560
Fender Washer, M6 (4) ............................... 120004
Bolt, M6 x 20, (4) .......................................... 117117
Bolt, M6 x 10 Hex Hd Flange ......................... 9962
Door Catch .................................................... 220919

Forest Green
10390636
10390736
10390536
10390036
10195236
10425536
10425636
155929

Jøtul Iron Jøtul Iron Enamel
10390685
10390646
10390785
10390746
10390585
10390546
10390085
10390046
10195285
10195246
10425585
10425546
10425685
10425685
15592385
156156

Left & Right Doors, and Hinge Pins

GF 200 DV II Accessories
• Fuel Conversion Kit - LP ......................................... 155626
• Fuel Conversion Kit - NG ....................................... 155627
• High Altitude Adjustment Kit - NG ................... 155808
• High Altitude Adjustment Kit - LP .................... 155809
• Blower Kit .................................................................. 155631
• Antique Brick Kit ...................................................... 155815

GF 100 DV II Accessories
• Blower Kit ......................................................... 155631
• Antique Brick Kit ............................................ 155815
• Fuel Conversion Kit - LP ................................ 155628
• Fuel Conversion Kit - NG .............................. 155629
• Wall Thermostat ............................................ 750003
• Remote Control .............................................. 129706
• Mobile Home Floor Bracket Kit ................. 154342

• Wall Thermostat ...................................................... 750003
• Remote Control ........................................................ 129706
• Mobile Home Bracket Kit .... GF200DVII (6”) / 154923
............................................... for Long Legs (8”) / 750304
......................................................... for Plinth Kit / 154342
• Long Leg Kits ................................ Matte Black / 154929
............................................................ Blue Black / 154930
....................................................... Forest Green / 154931
.................................................................... Ivory / 154932
................................................................ Jøtul Iron / 155366
• Plinth Kits ...................................... Matte Black / 350081
............................................................ Blue Black / 350082
...................................................................... Ivory / 350083
.................................................... Forest Green / 350084
................................................................ Jøtul Iron / 350085

29

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

Optional
Antique Brick Panel Kit 155815
Installation
CAUTION!
THE BRICK PANELS ARE EXTREMELY
FRAGILE. HANDLE WITH CARE. WEAR
SAFETY GLOVES TO PROTECT HANDS.

Tools Required: Safety glasses and gloves

Left Panel
221114

Upper Panel
221117

Right Panel
221115

1. Remove the Top Plate. Simply lift it up off of the
stove body. It is not fastened.
2. GF 100 DV II ONLY: Remove the Front Plate by lifting
straight up to disengage it from the sides.
3. Remove the Glass Frame. Disengage the two trunk
latches located at the top of the firebox and lift the
glass frame up and out of the firebox.
4. If installed, remove the Logset.
These parts are not fastened. Simply lift them out
of the firebox. You do not have to remove the
embers.

Lower Panel
221116

Figure 42. Brick Panel Kit Contents.

5. Install the Lower Panel.
Position it up against the back wall, resting on the
Burner Skirt. Fig. 43.
6. Install one of the Side Panels, pushing it up against
the firebox wall. Fig. 44
7. Position the Upper Panel. You should seat the
Upper Panel down and forward so that no gaps are
evident at the panel joints, as in Fig. 44.

Burner Skirt

8. Install the other Side Panel while holding the Upper
Panel in position.
Adjust the panels so that the mortar joints align with
those adjacent.
9. Install the Logset. Refer to pg. 20.
BE CERTAIN THAT NO EMBERS ARE BLOCKING THE PILOT
ASSEMBLY OPENING.

Figure 43. Install the Lower Rear Panel

10. Replace the Glass Frame.
Slide the frame down the slot in the front of the firebox.
Be sure to push the frame into the slot in the bottom to
ensure it is fully seated. The gasket at the top of the
frame should be flush with the top of the firebox.
Re-engage the trunk latches with the top lip of the glass
frame.
11. Replace the Top Plate.

Figure 44 . Install the Upper and Side Panels.

30

LIGHTING INSTRUCTIONS

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

FOR YOUR SAFETY, READ BEFORE LIGHTING.
WARNING:
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.

A. This appliance has a pilot which must be lit
by hand. When lighting the pilot, follow
these instructions exactly.
B. BEFORE LIGHTING, smell all around the
appliance area for gas. Be sure to smell next
to the floor because some gas is heavier than
air and will settle to the floor.
WHAT TO DO IF YOU SMELL GAS:
• Extinguish any open flame.
• Open windows.
• Do not light any appliance.
• Do not touch any electrical switches.
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone.

• If your gas supplier cannot be reached, call the
fire department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not push in or turn by hand, do not try to repair
it. Call a qualified technician. Force or attempted
repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to
replace any part of the control system and any
gas control which has been under water.

LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Access the lower controls.

7. Push in gas control knob slightly and turn counterclockwise
to “PILOT”.

8. Push in control knob all the way and hold in.
Immediately light the pilot by triggering the spark
ignitor (push the red button repeatedly) until pilot
4. Confirm that the gas supply line shut-off valve is open.
lights. Continue to hold the control knob in for
about one minute after
the pilot lights. Release
Control
knob and it should
Knob
ON
spring back. The pilot
should remain lit. If it
goes out, repeat Steps 5
through 8.
OFF

PILOT

3. Turn the stove ON/OFF switch to “OFF”, or set the
thermostat to lowest setting (if used).

Control Valve
5. Push in gas control knob slightly and turn clockwise
to “OFF”.
NOTE: Knob cannot be turned from “PILOT” to “OFF”
unless the knob is pushed in slightly. Do not force.
6. Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Follow “B” in the safety information
above on this page. If you do not smell gas, go to the
next step.

• If knob does not
Pilot Assembly
return when released,
stop and immediately call your service technician
or gas supplier.
• If pilot will not stay lit after several tries, turn
the control knob to OFF and call your service
technician or gas supplier.
9. Turn gas control knob counterclockwise

to “ON”.

10.Turn the stove ON/OFF switch to “ON”, or set
thermostat (if used) to desired temperature.

TO TURN OFF GAS TO THE APPLIANCE:
1. Turn ON/OFF switch to” OFF”. The pilot will remain lit for
normal service.
2. For complete shutdown, turn ON/OFF switch to “OFF”.

3. Access the lower controls.
4. Depress gas control knob slightly and turn clockwise
to “OFF”. Do not force.

31

GF 100 DV II Nordic QT
GF 200 DV II Lillehammer

August 2005
138003 D

This appliance must be installed in conformance with local and national building regulations. Before
beginning the installation, it is important that the these instructions be carefully read and understood.
Jøtul maintains a policy of continual product development. Consequently, products may differ in
specification, color or type of accessories from those illustrated or described in various publications.
Jøtul vise sans cesse a ameliorer ses produits. C’est pourquoi, il se reserve le droit de modifier les
specifications, couleurs etequipement sans avis prelable.

Jøtul AS
P.O. Box 1411
N-1602 Fredrikstad
Norway
Jøtul North America
55 Hutcherson Drive
Gorham, Maine 04038-2634

32



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
XMP Toolkit                     : 3.1-701
Producer                        : Acrobat Distiller 5.0.5 (Windows)
Create Date                     : 2005:08:18 09:52:35-04:00
Modify Date                     : 2005:11:10 08:46:10+01:00
Metadata Date                   : 2005:11:10 08:46:10+01:00
Creator Tool                    : PageMaker 7.0
Format                          : application/pdf
Creator                         : jholliday
Title                           : 138003-D GF100-200 DVII Manual.pmd
Document ID                     : uuid:4988d785-0676-474e-b94a-1509eb034764
Instance ID                     : uuid:57b4e804-f147-499e-9d7f-d50e0c4fb8be
Page Count                      : 32
Author                          : jholliday
EXIF Metadata provided by EXIF.tools

Navigation menu