KROHNE 70 Level Radar User Manual JH5 70 Manual
Krohne America Inc Level Radar JH5 70 Manual
KROHNE >
Contents
- 1. Manual
- 2. Manual addendum
Manual
© KROHNE 11/2000 DIN A4: 7.02182.37.00 US size: 7.02182.77.00 GR/LP Installation and operating instructions (Reference Manual) Level Radar BM 70 A / BM 70 P Non-contact level gauging using electromagnetic waves Variable area flowmeters Vortex flowmeters Flow controllers Electromagnetic flowmeters Ultrasonic flowmeters Mass flowmeters Level measuring instruments Status: 05 -1998 Communications engineering Engineering systems & solutions Contents: General advice on safety ................................3 Product liability and warranty .........................3 Items included with supply ..............................3 Software history ..............................................4 1. Range of application ................................6 2. Mode of operation and system structure.6 2.1 Operating principle ...................................6 2.2 Signal processing (digital) .........................7 2.3 Modularity (signal converter, flange, antenna)....................................................7 3. Input...........................................................8 3.1 Measured variable (distance, level, volume, reflection) ....................................8 3.2 Measuring range [0.5-35/40 m (1.64-115/131 ft)] .....................................8 3.3 Block distance...........................................8 3.4 Out-of-range performance.........................8 4. Output........................................................9 4.1 Variants.....................................................9 ® 4.2 Ex-e current output HART .................... 10 ® 4.3 Ex-i current output HART (type of protection: Ex de [ia]) ................ 10 ® 4.4 HART communication............................ 11 4.5 Current output (non-communicable) ....... 11 4.6 Digital interface RS 485 ......................... 11 4.7 Breakdown signal .................................... 13 4.8 Digital input ............................................. 13 5. Measuring accuracy................................ 14 5.1 Reference conditions............................... 14 5.2 Error of measurement ............................ 14 5.3 Repeatability ........................................... 15 5.4 Measured value resolution/hysteresis ..... 15 5.5 Transient recovery time .......................... 16 5.6 Turn-on drift / turn-on characteristics ...... 16 5.7 Long-term drift ....................................... 16 5.8 Effect of ambient temperature ................ 16 6. Operating conditions ............................. 17 6.1 Installation conditions ............................. 17 6.2 Ambient conditions.................................. 25 6.3 Product conditions................................... 26 6.4 Maintenance ......... ................................. 27 8. User interface ..........................................35 8.1 Local display .........................................35 8.2 Function of the keys ...............................36 8.3 Operator control concept ........................37 8.4 Table fo settable functions (Version 3.00, 3.03, 4.02, 4.03) .............39 8.5 Configuration examples..........................42 8.6 Description of functions ..........................44 8.7 Functional checks...................................55 8.8 Pointers and error messages during measurements.......................................56 8.9 Messages on start-up.............................58 8.10 Faults and symptoms during start-up and measurement .................................58 8.11 Calculation of the measured value .......61 8.12 User program PC-CAT for Windows .........................................62 9. Power supply ..........................................63 9.1 Options, technical data...........................63 9.2 Fuses ....................................................63 9.3 Changeover of operating voltage and replacement of fuses .............................63 9.4 Advice on safety.....................................64 10. Certificates and approvals....................66 10.1 Hazardous-duty approvals .....................66 10.2 Other approvals and certificates ...........66 10.3 Explosion proof acc. to ATEX ...............67 10.4 Radio approval .....................................68 10.5 CE manufacturer’s declaration...............69 11. Order information .................................70 12. External standards, codes and directives ..............................................71 13. Quality assurance .................................71 Annex Annex A: Annex B: Annex C: Annex D: Technical Data ............................72 Type code / nameplates...............74 Spare parts .................................77 Signed declaration to accompany a device returned to KROHNE ....80 Annex E: Table on documentation of device configuration ....................81 Annex F: Index............................................82 7. Design...................................................... 28 7.1 Models ..... ............................................. 28 7.2 Dimensions and weights ......................... 29 7.3 Replacement of the signal converter ....... 30 7.4 Field assembly ........................................ 30 7.5 Selection of antenna type and size.............. 31 7.6 Materials of construction ......................... 32 7.7 Process connection ................................. 32 7.8 Electrical connection ............................... 33 7.9 Terminating resistor for the RS 485 interface ..................................... 34 BM 70 A/P Montage- und Betriebsanleitung Seite: 2 11/00 General advice on safety: • To carry: the device will weigh between approx. 16 kg (35.5 lb) and 30 kg (66.1 lb) or more! To carry, use both hands to lift the device carefully by the converter housing. If necessary, use lifting gear. • When handling the BM 70 A/P, avoid hard blows, jolts, impacts, etc. Product liability and warranty: The BM 70 A/P level gauge is designed solely for measuring the distance, level, volume and reflection of liquids, pastes, slurries, solids and particulate materials. The BM 70 A/P level gauge does not form part of an overfill protection system as defined in WHG. Special codes and regulations apply to its use in hazardous areas. Responsibility as to suitability and intended use of these level gauges rests solely with the user. Improper installation and operation of our level gauges may lead to loss of warranty. In addition, the "General conditions of sale", forming the basis of the purchasing contract, are applicable. If you need to return the level gauge to the manufacturer or supplier, please refer to the information given in Annex D. Items included with supply: The scope of supply encompasses, in the version as ordered: • Signal converter bolted to waveguide window and antenna Optionally: antenna extension, sunshade (with fastening material in each case) • Shielding material with strap retainer (not for the US market) • Report on factory settings for the signal converter • Bar magnet for operator control / parameter assignment (only in version with local display) • Wrench for the covers Installation material (stud bolts, flange gasket and cabling) not supplied, to be provided by customer! Documentation supplied: • Condensed instructions: installation, connection, start-up and safety advice in condensed form, but sufficient for most applications. Please read through these instructions first! • Instruction card: overview of the configuration menu and meaning of the markers in cheque card format. • Installation and operating instructions (this manual): detailed user manual and reference book, including description of special versions and functions. This documentation is structured on lines similar to those given in the DIN V 19259 Standard. • Approval documents, unless reproduced in the installation and operating instructions. Installation and operating instructions BM 70 A/P Page: 3 11/00 Software history Signal Converter Firmware For BM 70 A: Introduction Mth./Yr 06/97 01/98 Firmware Version 3.00PREnn 3.00 Device Instructions 06/97 11/97-11/00 05/98 3.01 11/97-11/00 07/99 3.02 05/98-11/00 11/99 3.03 05/98-11/00 Remarks Test versions First serial version. Errors when empty spectrum recorded with WAVE-STICK; automatic reset when signal is extremely weak. Elimination of errors in V. 3.00; improved application of empty spectrum at tank bottom. Implementation of the ModBus protocol; adaptation to PROFIBUS interface; improved application of empty spectrum at tank bottom; improvement of PC-CAT protocol switching in multidrop operation; definition of 3.6 mA as lower error current for the IS current output; improved tank bottom tracing; improved spectrum evaluation at tank heights > 15 m. Correction of a bug in the mode "Hold on Error" (output current went to 1 mA or 3.6 mA; only V. 3.02); Adaption of the HART protocol for operation with the program AMS, and some smaller error corrections; Improved "tank bottom recognition" (measured value now always goes to the programmed tank bottom position); If no measured value is found after start-up, the instrument goes directly into "tank bottom recognition" and the local display to level = 0, if Fct. 3.2.5 Error Messages = NO is set. For BM 70 P: Introduction Firmware Mth./Yr Version 05/98 4.00PREnn 4.01PREnn 4.02PREnn 07/99 4.02 11/99 4.03 Device Instructions 05/98 Remarks 05/98-11/00 05/98-11/00 First serial version. Correction of a bug in the mode "Hold on Error" (output current went to 1 mA or 3.6 mA; only V. 4.02); Adaption of the HART protocol for operation with the program AMS, and some smaller error corrections; Improved "tank bottom recognition" (measured value now always goes to the programmed tank bottom position); If no measured value is found after start-up, the instrument goes directly into "tank bottom recognition" and the local display to level = 0, if Fct. 3.2.5 Error Messages = NO is set. Test versions Installation and operating instructions BM 70 A/P Page: 4 11/00 Compatibility between PC-CAT Software and BM 70x Level-Radar Instruments Software (1) Operating System BM 70 BM 70 Nautic YES (2) NO (3) NO YES YES NO YES Up to firmw. 3.02/4.02 (5) PC-CAT (DOS) 1.00 (4) PC-CAT (DOS) 2.00 PC-CAT (DOS) 2.10/2.11 (4) PC-CAT (DOS) 2.30 DOS ≥ 3.00 DOS ≥ 3.00 DOS ≥ 3.00 DOS ≥ 5.00 (7) PC-CAT (DOS) 3.00 DOS ≥ 5.00 (7) YES PC-CAT (DOS) 3.01 PC-CAT Windows 4.00/4.01 DOS ≥ 5.00 (7) Windows 95,98,2000,NT Windows 95,98,2000,NT YES NO PC-CAT Windows Lite 4.01 INSTRUMENTS BM 70 A BM 700 BM 70 P NO NO NO NO Up to firmw. 5.02 (5) Up to firmw. Up to 3.02/4.02 firmw. 5.02 YES YES YES YES YES YES BM 702 NO NO NO NO NO (6) YES YES YES (1) table is not including PRE versions of PC-CAT limited to configuration parameters up to firmware 2.02/2.10 (3) limited to configuration parameters up to firmware 2.20 (4) Attention!! Does not run on fast PCs !! (5) with reduced display and configuration capability (6) not with firmware 7.00/PRE0x (7) or DOS-Window in Windows 3.1x, 9x (not Windows NT, 2000) (2) Installation and operating instructions BM 70 A/P Page: 5 11/00 1 Range of application The BM 70 A/P Level-Radar level gauging system is designed to measure the distance, level, volume and reflection of liquids, pastes, slurries, solids and particulate materials. It can be operated on storage and process tanks and also on stilling wells. BM 70 P is specially designed for applications on storage tanks with highest precision requirements. BM 70 A/P Ex hazardous-duty versions are suitable for use in Ex-Zone 0, 1 and 2. In Germany (and, depending on the respective radio approval, in some other countries as well) its use is restricted to closed tanks or containers made of metal or concrete. Because of the low output involved, however, the microwaves are not harmful to human beings. 2 Mode of operation and system structure 2.1 Operating principle (FMCW-Radar) A radar signal is given via an antenna, reflected on the measuring surface and received after a delay time t. FMCW: Frequency Modulated Continuous Wave The FMCW-radar uses a high frequency signal (~10 GHz) which transmit frequency increasing linearly 1 GHz during the measurement (frequency sweep) (1). The signal is emitted, reflected on the measuring surface and received time-delayed (2). For further signal processing the difference ∆f is calculated from the actual transmit frequency and the receive frequency (3). The difference is directly proportional to the distance i.e. a large frequency difference correspond to a large distance and vice versa. The frequency difference is transformed via a Fourier transformation (FFT) into a frequency spectrum and then the distance is calculated from the spectrum. The level results from the difference between tank height and distance. Linearity of frequency sweeps The measuring accuracy of a FMCW radar is determined from the linearity of the frequency sweeps and their reproducibility. The linearity correction is deduced via reference measurement of the oscillator. The non-linearity is corrected up to 98% (BM 700/BM 70 A). An immediate frequency regulation is necessary with the BM 70 P device because of the higher demand on the measuring accuracy. With the PLL technology (Phase Locked Loop) the signal frequency is directly recorded as a digital data and the converter oscillator locks automatically on the right frequency. 3) differential frequency formed 1) radar frequency linearly changed fStop non-linear sweep ∆f antenna linear sweep ∆f fStart 2) delay time due to wave propagation Installation and operating instructions BM 70 A/P Page: 6 11/00 PLL structure As the transmit frequency is changed during a short time interval by FMCW radar the transmitted frequency has to follow the nominal frequency within micro seconds. This ensues via modern, fast electronic and processors. Microprocessor Reference control oscillator Microwave Phase oscillator detector Loop filter Antenna 2.2 Signal processing (digital) The radar signals are digitally processed by a microprocessor. The processing system is based on intelligent procedures that allow for plausibilities and history. The following diagram describes the path of internal signal processing: gain switch measurement signal filter analog to digital conversion Fourier transform spectrum plausi- spectrum bility interpolation distance corrected spectrum gain control empty tank spectrum After automatic gain control, the measuring signal is filtered, digitized and converted into a frequency spectrum by means of the Fourier transform. Plausibility of the value obtained is assessed with the aid of the so-called empty-tank spectrum, which contains information about constant interference reflectors. Interpolation of the spectrum helps to improve resolution of the measured value. 2.3 Modularity (signal converter, flange, antenna) The measuring system consists of the flange system and the signal converter. The flange system contains the microwave window separating product from pressure, and the antenna system. The compact signal converter contains the microwave generator and the entire signal processing system, including provision of a standardized output signal (4 - 20 mA or digital interface). The signal converter can be separated from the flange system under process conditions, without loss of pressure or escape of product. Converter Flange with microwave window Antenna system Installation and operating instructions BM 70 A/P Page: 7 11/00 3 Input 3.1 Measured variable (distance, level, volume, reflection) The primary measured variable is the distance between a reference point (as standard: tank mounting flange) and a reflecting surface (e.g. surface of the liquid). The filling level is determined by allowing arithmetically for the entered tank height. Volume measurements are possible by entering a conversion table (max. 50 points). The strength of the reflected signal can be measured for qualitative assessment of the tank product or its surface. 3.2 Measuring range [0.5-35/40 m (1.64-115/131 ft)] Minimum tank height Maximum measuring 0.5 m (1.64 ft) 40 m (131 ft) / optionally 100 m (328 ft) 20 m (65.62 ft) 35 m (115 ft) BM 70 A BM 70 A mit Wave-Stick BM 70 P The useful range will depend on the antenna size, the reflection properties of the tank product, the installation position, and the presence of interference reflectors (see Sections 6.1 and 7.5). 3.3 Block distance The block distance is the minimum measured distance between the mounting flange (reference point) and surface of the tank product. Recommended minimum values: see following sketches. Horn antenna without stilling well: Block distance Antenna size* = Type3: 22cm/8.7"; Type4: 34cm/13"; Maximum level * Hastelloy: +3cm / 1,2 " Recommended antenna distance: Storage tanks: 10cm/4"; Process tanks: 20cm/8" Product surface The length of any antenna extension used must be added on! Stilling well / Wave-Guide Wave-Stick Antenna size * = Type1: 11cm/4"; Type2: 15cm/5.5"; Type3: 22cm/8.7" Wave-Stick SW: 6cm/2.4" (Wave-Guide: no antenna) Recommended antenna distance = 30 cm / 12" Standard: 384 mm/15.1" Product max. 200 mm 8" * Hastelloy: 3 cm (0.4") Product Minimum block distance = Standard: 184 mm Normal: Rod length - 200 mm (7.87") 3.4 Out-of-range performance When the level measuring range is exceeded (including flooding) the measured value will stick at the (adjustable) block distance (see Sect. 8.6.14). If the measured value drops below the level range, it will stay put at the set lower range limit (distance = tank height). Installation and operating instructions BM 70 A/P Page: 8 11/00 4 Output 4.1 Variants Variants Remarks ® Ex-e current output HART Ex-i current output HART® Current output RS 485 + current output PROFIBUS-PA Foundation Fieldbus (FF) ® Ex-e; active; HART protocol; together with switching output and digital input intrinsically safe; passive; HART® protocol (optionally with intrinsically safe switching output) Ex-e; active; non-communicable BM70 protocol or ModBus-RTU or HART® intrinsically safe; see Supplementary Instructions intrinsically safe; see Supplementary Instructions Described in Section 4.2 + 4.4 4.3 + 4.4 4.5 4.6 + 4.5 All versions with HART® or BM70 protocols can be operated with the PC-CAT PC program (see Section 8.12). Overview of digital Communication possibilities: BM 70 A Modbus PROFIBUS-PA ........... Other communication interfaces RS 485 RS 485 4 ... 20mA + HART ® 4mA (Ex i) + HART® Converter HART FIELD COMMUNICATIONS PROTOCOL F1 F2 F3 F4 HART Communicator >> >>>> ABC DEF JKL HART FIELD COMMUNICATIONS PROTOCOL YZ/ PQR VWX MNO STU # %& GHI * _: + F1 F2 F3 F4 HART Communicator HARTHHC >>> >>> ABC DEF JKL MNO STU PC-CAT or HART specific software and operating devices YZ/ PQR GHI VWX # %& * _: + HARTHHC Point-to-point Installation and operating instructions BM 70 A/P Tank Inventory System HART-Master Multidrop Page: 9 11/00 ® 4.2 Ex-e current output HART Function Level, distance, volume (conversion table) or reflection, and error identification; galvanically isolated from digital input and switching output Current 4-20 mA; without or with error message (2 mA and 22 mA) Accuracy/linearity 0.05 % (rel. 20 mA; at T = 20°C, 100Ω load impedance and nominal operating voltage) Temperature drift < 100 ppm/K (typically 30 ppm/K) Load impedance < 500 Ω Effect of load impedance < 0.02 % (rel. 20 mA for RB = 0...500 Ω) Effect of power < 0.02 % (rel. 20 mA for UB within limits of tolerance) Hazardous-duty version: Ex e Note: together with switching output and digital input Digital input (terminals 81/82): Can be used to suspend the entire measurement procedure, i.e. measurements are "frozen" (standard setting), or to hot start the device (reprogra mming by KROHNE Service). Applicable voltage: 5...28 V DC Input resistance: > 1 kΩ Switching output (terminals 41/42): Can be progra mmed as a limit switch, alarm contact or error message. The contact is open in the de-energized condition. Operating data: max. 100 mA / 30 V DC or 30 V AC. Internal resistance: < 20 Ω ® 4.3 Ex-i current output HART (type of protection: Ex de [ia]) Function Level, distance, volume (conversion table) or reflection; and error identification; passive output (current sink) Current 4-20 mA; without or with error message (3.6 mA / 22 mA); 4 mA constant, adjustable for HART -Multidrop Temperature drift < 100 ppm/K (typically 30 ppm/K) Accuracy/linearity 0.05 % (rel. 20 mA; at T = 20°C, 10 V supply voltage and nominal operating voltage) Supply voltage U 8-30 V (between terminals 31 and 32) Load impedance < (US - 8V) / 22 mA (US = external supply voltage) Effect of supply voltage < 0.02 % (rel. 20 mA for U = 8...30 V) Effect of power < 0.02 % (rel. 20 mA for UB within limits of tolerance) Note: Digital input not available. Optional switching output (terminals 41/42): can be progra mmed as limit switch, alarm contact or error message. The contact is open in the de-energized condition. Operating data: 6...30 V; ILow < 110 mA; ULow < 2V; IHigh < 900 µA (U=30V) and IHigh = 200 µA (U=8V) Ex-i safety limits Signal circuit in type of protection: Intrinsic Safety EEx ia IIC/IIB or EEx ib IIC/IIB for connection to a certified intrinsically safe circuit with the following peak values: Uo = 30 V; Ik = 250 mA Effective inner capacitance ≈ 0; effective inner inductance ≈ 0 Installation and operating instructions BM 70 A/P Page: 10 11/00 4.4 HART® communication The HART Communications protocol can, in accordance with the Rosemount Standard, be used with a BM 70 A/P. Electrical connection: see Section 7.8. There are two ways of using the HART® Communication: a) As a point-to-point connection between the BM 70 A/P and the HART® master equipment. ® A BM 70 A/P can be used either with an Ex-e current output HART or with an Ex-i current output ® HART . HART Master 4...20 mA b) As a multipoint connection (multidrop) with up to 15 devices (BM 70, BM 70 A/P or other ® HART equipment), in parallel on a 2-wire bus: A BM70 A/P is normally used with Ex-i current output, but an Ex-e current output can also be used (constant 4 mA in both cases.) HART Master 4mA 4mA 4mA 4mA other other HART device HART device 4.5 Current output (non-communicable) Function Level, distance, volume (conversion table) or reflection, and error identification Current 4-20 mA; without or with error message (2 mA and 22 mA) Accuracy/linearity 0.3 % (rel. 20 mA; at T = 20°C, 100 Ω load impedance and nominal operating voltage) Temperature drift < 200 ppm/K (typically 70 ppm/K) Load impedance < 250 Ω Effect of load impedance < 0.1 % (rel. 20 mA for RB = 0...250 Ω) Effect of power < 0.1 % (rel. 20 mA for UB within limits of tolerance) Hazardous-duty version: Ex e When operated as a switching output (digital output): Function limit switch, alarm contact or error message Low status current < 2 mA High status current = 22 mA (when load < 250 Ω) No-load voltage < 18 V 4.6 Digital interface RS 485 RS 485 is a bus that allows two-way Communication (half-duplex operation) with the BM 70 A/P Level-Radar. When the computer system sends out a request, the BM 70 A/P transmits: level, distance; volume (conversion table), reflection, setting parameters and status. A PC can configure any BM 70 A/P via the bus (RS 485/RS232 converter required) by means of the PC-CAT program, provided no master is active. The maximum cable length - excluding amplifier - is 2000 m. Installation and operating instructions BM 70 A/P Page: 11 11/00 Transmission rate: Address: Protocols: V.3.02/4.02) 1200 to 38400 bauds 0 to 255 KROHNE Protocol, Additional current output: Note: ® HART , Modbus RTU (from firmware Additional information: see "BM 70 A/P Communication RS 485" instructions The current output is conductively coupled to the RS 485 interface. Technical data: see Section 4.5 Switching contact and digital input are not available. However, the current output can be configured as a switching output. Various bus configurations A) Connection of a BM 70 A/P as a single RS 485 user: Computer system Bus line (2 shielded wires) RS485 connection must be terminated with 120 ohms (if necessary insert resistor between A and B) with termination resistance 120 ohms B) Connection of several BM 70 A/P in the RS 485 bus system via stubs to the bus cable: Computer system Bus line (2 shielded wires) RS485 connection must be terminated with 120 ohms (if necessary insert resistor between A and B) ........... without termination resistance with termination without resistance termination 120 ohms resistance without termination resistance C) Connection of several BM 70 A/P in the RS 485 bus system, with bus cable looped through to further field instruments: Computer system Bus line (2 shielded wires) RS485 connection must be terminated with 120 ohms (if necessary insert resistor between A and B) ........... without termination resistance without termination resistance without termination resistance with termination resistance 120 ohms Notes: • If other devices are operated together with the BM 70 A/P Level-Radar on one bus, all devices must use the same Communications protocol (e.g. ModBus devices of different makes or BM 70 A/P and TTM 70 with KROHNE Protocol). ® ® • When "HART " is set as the protocol type, use only the protocol in keeping with the "HART ® Specification". The "Hardware Implementation RS 485" does not conform to the HART Standard (see Sections 4.2 and 4.3). Installation and operating instructions BM 70 A/P Page: 12 11/00 • Since signal reflections at the line ends can interfere with Communication, both the line beginning (at the computer system) and the line end (at the last device) should be terminated with the typical surge impedance of the cable (120 Ω). To do this inside the BM 70 A/P: see Section 7.9. 4.7 Breakdown signal Breakdown information can be called up via the following interfaces: • Local display: flashing display, plain text information • Current output: error signal 2 mA (Exi = 3.6 mA) or 22 mA • Switching output: contact opens or closes • Digital interfaces: interrogation of error flags 4.8 Digital input The digital input (for electrical data: see Section 4.2) can be used for temporarily "freezing" measure® ments or for carrying out a hot start. It is only available in the "Ex-e current output HART " version. The "freeze" function can be used to blank out larger, temporary interferences, e.g. very slow agitator, slide gate, ball valve in the stilling well. The last measured values in each case are present at outputs I and S, and in the display. The digital input is also taken into account when the empty-tank spectrum is being recorded (totalizer does not continue). marker 6 in the display indicates that the digital input is active in the "freeze" function. NOTE: The function of the digital input is set as standard to "freeze". To switch the function to "hot start" or to deactivate it completely, the setting will need to be changed in the Service menu of the BM 70 A/P Installation and operating instructions BM 70 A/P Page: 13 11/00 5 Measuring accuracy 5.1 Reference conditions • • • • • • • Temperature = +20°C / +68°F Pressure = 1013 mbar abs. / 14.5 psia Air humidity = 65% Highly reflecting product (e.g. water) with calm surface Tank diameter > 5 m / 16.4 ft Mounted at least 1/7 x tank height away from tank edge (BM 70 P: 1/5 x tank height) No interference reflections inside the radiation lobe (± 6...9°; see Section 6.1.1) 5.2 Error of measurement Since the measuring process primarily determines distance, measuring accuracy can only be specified as a function of the distance. For that reason, all figures given in this Section 5 refer to the measured distance. BM 70 A: With antenna type 3 (139 mm / 5.47") or type 4 (200 mm / 7.87") or stilling well or WaveGuide Accuracy inch cm 4.8 12 10 3.2 2.4 1.6 0.8 -0.8 -2 -1.6 -4 -2.4 -6 -3.2 ± 0.3 % ± 1 cm (0.4") -8 -4 -10 -4.8 -12 block 3 distance 16 10 33 15 49 20 66 Distance to flange 25 82 30 98 35 115 40 m 131ft 25 82 30 98 35 115 40 m 131ft BM 70 A Wave-Stick: Accuracy inch cm 12 4.8 10 3.2 2.4 1.6 0.8 -0.8 -2 -1.6 -4 -2.4 -6 -3.2 ± 1.5 cm (0.6") ± 0.3 % -8 -4 -10 -4.8 -12 0 0.18 1 0.6 3 16 10 33 15 49 20 66 Distance to flange Installation and operating instructions BM 70 A/P Page: 14 11/00 BM 70 A Precision (with special calibration and certificate): Only with antenna type 4 (200 mm / 7.87") or stilling well 80 - 200 mm dia. (3 - 8") Accuracy inch cm 4.8 12 10 3.2 2.4 1.6 0.8 -0.8 -2 -1.6 -4 -2.4 -6 -3.2 ± 0.1 % ± 5 mm (0.2") -8 -4 -10 -4.8 -12 16 block 3 distance 10 33 15 49 20 66 Distance to flange 25 82 = calibration range 30 98 35 115 40 m 131ft = not verified by calibration BM 70 P Only with antenna type 4 (200 mm / 7.87") or stilling well 100 - 200 mm dia. (4 - 8") Accuracy inch mm 0.48 12 0.4 10 0.32 0.24 0.16 0.08 -0.08 -2 -0.16 -4 -0.24 -6 -0.32 -0.4 ± 20 ... 30 mm ± 0.01 % ± 1 mm (0.04") -8 -10 -0.48 -12 Blockdistance 16 10 33 15 49 20 66 25 82 30 98 35 115 40 m 131ft Distance to flange 5.3 Repeatability Repeatability is equal to half the value for the error of measurement. 5.4 Measured value resolution/hysteresis Measured value resolution is: 1 mm / 0.04" for BM 70 A, and 0.1 mm / 0.004" for BM 70 P Hysteresis is at least 20 times less than the error of measurement. Installation and operating instructions BM 70 A/P Page: 15 11/00 5.5 Transient recovery time The transient recovery time is determined by the setting parameter "time constant" (1 ... 100 s). The transient recovery time relative to 1% deviation from the steady-state value is approx. 4.6 times the time constant. However, in the case of unusually rapid changes in level, the transient recovery time may deviate from this figure. 5.6 Turn-on drift / turn-on characteristics A rough measured value is initially displayed about 1 minute after the BM 70 A has been switched on. The first self-calibration is completed after about 2 minutes. Full measuring accuracy is attained after 30 minutes operating time. The measured value from the BM 70 P is accurate directly after the startup phase (approx. 1.5 minutes). Typical turn-on drift (example): Measured value BM 70 A BM 70 P 30 Time/min 5.7 Long-term drift The long-term drift is within the specified error of measurement. 5.8 Effect of ambient temperature Temperature coefficient, signal output: Ex-e current output HART®: Ex-i current output HART®: Current output: Digital interfaces: < 100 ppm/°C (typically: 30 ppm/°C) < 100 ppm/°C (typically: 30 ppm/°C) < 200 ppm/°C (typically: 70 ppm/°C) no temperature effect The temperature has no effect on the measured value as the device carries out a regular self-calibration. The effect of temperature of the atmosphere above the liguid product results theoretically in 1ppm/°C for air. In respect of proof of temperature effect with the aid of reference measurements in liquid tanks, it needs to be borne in mind that liquids generally have a high coefficient of cubic expansion (organic liquids: typically 0.15 %/°C)! Installation and operating instructions BM 70 A/P Page: 16 11/00 6 Operating conditions Hazardous-duty systems • The BM 70 A/P is certified in conformity with European Standard (ATEX) for use in Zone 0, 1 and 2 hazardous locations. • The BM 70 A/P also has FM Approval (Factory Mutual) for CLASS I, DIV 1, GROUPS B,C,D; CLASS II/III, DIV 1, GROUPS E,F,G. • Attention is drawn to the information given on the approval certificates. nameplate and the specifications in the • When carrying out installation, dismantling work or making electrical connections in the hazardous area, be sure to observe the pertinent wiring and installation regulations, e.g. as specified in VDE 0165. • Within the scope of routine checks required to be carried out on systems operated in hazardous areas (maintaining the system in good working order), the "flameproof enclosure" (large cover on signal converter) should also be visually inspected for signs of external damage and corrosion. • Before opening the "flameproof enclosure" (e.g. to inspect the inside or for repair purposes) make absolutely certain in the hazardous location: - that the BM 70 A/P Level-Radar is disconnected from voltage, and then allow the prescribed waiting time of 22 minutes to elapse first, - and that there is no explosion hazard (gas-free certificate!). Safety • Operator control via the keys: on electrical safety grounds, operator control of the keys (below the display, with the housing open) may only be carried out by specialist personnel for service and repair work, on no account, however, when there is risk of explosion! • Surface temperature: the housing of the signal converter can, in extreme ambient conditions, assume temperatures of more than 70°C (158°F)! 6.1 Installation conditions Refer to Section 7.5 for selection of the optimum antenna type 6.1.1 Transmission angle The transmission angle is defined as the angle α to the vertical, in which the power density of the radar waves assumes half the value of the maximum power density (half-power beamwidth): α α Antenna Type Diameter mm (inches) Type 4 Type 3 Type 2 * Type 1 * Wave-Stick Wave-Guide / stilling well 200 (7.87) 140 (5.51) 100 (3.94) 80 (3.15) 25 (0.98) 25-200 (0.98-7.87) TransLobe expansion s per mission metre distance angle α 6° 10 cm (3.94”) 8° 14 cm (5.51”) 12° * 22 cm (8.67”) 16° * 30 cm (11.8”) 9° 16 cm (6.3”) Propagation only inside the stilling well * Should only be used in stilling wells; the transmission angle given applies to line-of-sight propagation, i.e. without stilling well. Installation and operating instructions BM 70 A/P Page: 17 11/00 6.1.2 Recommendations for positioning on the tank A) Horn antenna or Wave-Stick without stilling well Antenna Type 3 or Wave-Stick Recommended distance from the tank wall: >1/7×H, but max. 1/3×D Antenna Type 4 >1/10×H, but max. 1/3×D BM 70 P : > 1/5 x H min. measurable level Lower measuring range limited when tank has tapered bottom. Do not position in tank centreline! (multiple reflections!) Several BM 70 A/P can be operated in one tank. Do not mount dead centre on manhole cover! (multiple reflections!) Do not position above internals! (interference reflections!) If these recommendations cannot be followed because of the tank geometry, please consult KROHNE. Installation and operating instructions BM 70 A/P Page: 18 11/00 B) Stilling well or Wave-Guide A stilling well or Wave-Guide may be mounted in any position on the tank. (For design layout: see also Section 6.1.4; for block distance: see Section 3.3). Stilling well application In a side vessel BM 70 A Wave-Guide A stilling well or Wave-Guide is positively recommended for horizontal cylindrical tanks (to avoid multiple reflections): 6.1.3 Mounting on tank fitting A) Horn antenna Should be mounted on the tank fitting as close to the horizontal as possible (deviation < ± 2°). Exception: if product surface is not horizontal, (e.g. particulate materials) the flange can be aligned roughly parallel to it. The antenna should project out of the fitting: Antenna Diameter D Type 4 200 mm (8”) Type 3 140 mm (5.5”) * Hastelloy: + 30 mm (1.2”) Length l* 335 mm (13.2”) 223 mm (8.8”) (subject to change without notice) Tank nozzle Installation and operating instructions BM 70 A/P Page: 19 11/00 An antenna extension should be added if the antenna does not project out of the fitting: Antenna extension Tank nozzle Antenna extensions are available from 100 to 2000 mm (3.94" to 78.74") in steps of 100 mm (3.94"). Several extensions can be joined up: Exception: When the tank fitting is sy mmetrical, the antenna may end in the fitting so as to enlarge the measuring range (minimum dead zone to tank cover, see Sect. 3.3 "block distance" and Sect. 5.2 "error of measurement"): Tank nozzle Narrow tank fitting If the inside diameter of the fitting is smaller than the diameter of the antenna, and the fitting is accessible from inside the tank for mounting purposes, the antenna with extension can be mounted from the inside (not for versions made of titanium or tantalum). The antenna extension should be about 100 mm (3.94") longer than the height of the fitting. Tank nozzle Installation and operating instructions BM 70 A/P Antenna extension Page: 20 11/00 B) Wave-Stick Note the requirements pertaining to diameter and length of the tank fitting: Version Length L max. height of fitting X 384 mm 150 mm (15.12”) (15.12”) 500...1000 mm L - 234 mm (19.7” - 39.4”) (L - 9.2”) max. X Tank nozzle Standard min. 50 mm/2" Option 6.1.4 Mounting on stilling wells Antenna Type 1s 2, 2s 3s 4, 4s Outside diameter 80 mm (3.15”) 76 mm (2.99”) 100 mm (3.94”) 140 mm (5.51”) 152 mm (5.98”) 200 mm (7.87”) If necessary, turn antenna to size! Antenna size must match inside diameter A standard Wave-Stick will not function in a stilling well! For stilling wells 40-55 mm a type Wave-Stick SW can be used. 60mm Further requirements concerning stilling wells: • The well must be electrically conductive. • Minimum inside diameter of well: 40 mm (1.57"). (BM 70 P: 80 mm, better > 100 mm). • If possible, use only smooth walled, straight stilling wells. If nevertheless an assembled stilling well is necessary, abrupt changes in diameter along the pipe should be less than 1 mm (0.04"). Surface roughness of the inside of the pipe should not be more than + 0.1 mm (0.004"). • For the BM 70 P the antenna types 1s, 2s, 3s or 4s have to be used to achieve a high measuring accuracy. Installation and operating instructions BM 70 A/P Page: 21 11/00 It is possible to measure through a full-bore open ball valve if the valve and the pipe adapters above and below the valve are relatively smooth-walled. • It is not possible to measure levels below the end of the stilling well. • To ensure equalization of pressure, drill one or two small holes in the stilling well above the maximum filling level. • If necessary, several holes can be drilled along the whole length of the pipe. All holes must be deburred. The holes should be as small as possible and spaced wide apart (Recommendation: see drawing on the right). Ø max. 10 mm • It is advisable to fit a reference point at the end of the stilling well in the form of a rod or screw of approx. 6 mm (0.24") diameter. See drawing below. / 0.4" min. 50 mm/ 1.97" 6 mmØ 6Ø mm Ø 0.24" 6.1.5 Wave-Guide The "Wave-Guide" is a pipe with an outside diameter of 30 mm (1.18") and an inside diameter of 25 mm (0.98"), that is bolted direct to the BM 70 A flange system (in the same way as an antenna extension). It functions like a stilling well and can be used for clean products. The Wave-Guide is not practical in conjunction with the BM 70 P as it will not provide high measuring accuracy. maximum length: Ex: max. 3 m (9.84 ft) (except tantalum: max. 1 m (3.28 ft)). Non-Ex: up to 3 m (9.84 ft) without additional support Pipes longer than 3 m (9.84 ft) need to be fixed at two points. 6.1.6 Curved antenna extensions Rectangular and S-shaped extensions are available for particularly difficult operating conditions. Such extensions can be used in cases where the antenna is exposed to especially high temperatures and where there are problems of space, (e.g. to avoid internals; positioning the antenna away from the centre of sy mmetry; lateral mounting of the signal converter). Standard sizes (others on request): 300 (11.81") 323 (12.72") 271 (10.67") 271 (10.67") R 110 (4.33") Dimensions in mm (inches) Installation and operating instructions BM 70 A/P Page: 22 11/00 6.1.7 Special options for the flange Antenna heating/cooling device (> DN150/6") Double-walled antenna for cooling or heating, e.g. to avoid condensation (recommended for liquid sulphur). max. differential pressure at antenna: Standard DN150 = 6 bar (87 psig) (information on other pressure levels provided on request) Hazardous-duty systems: 1. In Zone 0, the temperature of the heating system and antenna may not exceed 80 % of the ignition temperature of the stored material. 2. Continuous monitoring shall ensure, and operational inspections shall verify, that the 80% level of the ignition temperature stated in Point 1 above is not exceeded. Purging device (> DN100) With connection for purging the inside surface of the antenna to prevent heavy deposits of product or to heat or cool the antenna. If a liquid is used for purging, this may interfere with the functioning of the BM 70 A/P during the process. Continuous purging with gas is not a problem as it does not interfere with measurements. The purge connection is closed off by the manufacturers with a ¼" screw. When this screw is removed to connect up a purging system, the operator is responsible for ensuring conformity with "Ex" requirements in connection with the purging circuit (e.g. fitting a flame trap). 6.1.8 Ultimate installation on the tank • After carefully positioning the BM 70 A/P on the tank fitting flange (not forgetting the gasket), align the BM 70 A/P and the gasket. • Insert stud bolts and tighten nuts slightly (by hand). (These items not included with supply). • Press shielding strip C* in the gap between tank flange and the BM 70 A/P flange and secure with strap retainer S* (both items included with supply). • Strap retainer S* must fit closely and overlap both flanges. * only required for European radio approvals • Tighten down stud bolts and nuts firmly. The torque is dependent on the strength properties of the stud bolts and the pressure rating of the C* = shielding strip tank. S* = strap retainer Installation and operating instructions BM 70 A/P Page: 23 B = BM 70 A/P flange F = tank flange 11/00 6.1.9 Sunshade 315 (12.40") 353 (13.89") A sunshade SD is recommended to protect the signal converter from the effects of direct sunshine from above. This will increase the overall installation height by approx. 20 mm. The sunshade is easily fitted/dismantled with the aid of 4 screws S (included). An Allen key (size 4 mm) is required. Dimensions in mm (inches) Installation and operating instructions BM 70 A/P Page: 24 11/00 6.2 Ambient conditions 6.2.1 Hazardous locations BM 70 A/P Ex is suitable for use in hazardous locations of the following zones: 0, 1, 2 Temperature classes: T6...T2; danger groups: IIA...IIC For further information: see Section 10. 6.2.2 Ambient temperature of signal converter BM 70 A/P with horn antenna or Wave-Guide: -20 ... +55°C (-4 ... +131°F) A "BM 70 sunshade" should be fitted if the converter is located in the open with the likelihood of strong insolation (see Section 6.1.9). 6.2.3 Flange temperature Horn antenna, Wave-Guide (Tamb* ≤ 50°C): Horn antenna, Wave-Guide (Tamb* ≤ 55°C): High-temperature version with distance piece and FFKM gasket (Kalrez 4079 or Parofluor V3819-75): Kalrez 2035 gasket: Viton gasket: FEP-sheathed gasket: -30 ... +130°C -30 ... +120°C (-22 ... +266°F) (-22 ... +248°F) -30 ... +250°C ** -30 ... +210°C -30 ... +200°C -30 ... +200°C (-22 ... +482°F) (-22 ... +410°F) (-22 ... +392°F) (-22 ... +392°F) Wave-Stick, permanently: -20 ... +100°C (-4 ... +218°F) Wave-Stick, pressure-dependent (see 6.3.5), with no mechanical loading radial to the rod: bis +150°C (302°F) Wave-Stick, steam cleaning (CIP, SIP) for 30 minutes: max. +160°C (320°F) * Tamb is the ambient temperature of the signal converter ** Safety limit: +280°C (536°F) 6.2.4 Ambient temperature limits Signal converter: Measuring function OK, but LCD "freezes up": Functional upper limit, for max. 2 hours: Flange system: see Section 6.2.3 min. - 40°C (-40°F) max. +70°C (+158°F) 6.2.5 Storage temperature -20 ... +60°C (-4 ... +140°F) 6.2.6 Environment class Locations exposed direct to open-air climate, D1 Severity in conformity with EN 60654-1 6.2.7 Protection category Signal converter: IP 66 / IP 67 (equivalent to NEMA 6) Installation and operating instructions BM 70 A/P Page: 25 11/00 6.2.8 Shock resistance The device has been found to withstand the impact test in conformity with EN 61010, Section 8.2, with 0.5 J energy, and the drop test to prEN 50178:1994. 6.2.9 Vibration endurance limit Type test conditions: to IEC 68-2-6 and prEN 50178 (10-57Hz: 0.075 mm / 57-150 Hz: 1 g) 6.2.10 EMC The devices satisfy the requirements of EN 50081-1, EN 50082-2 and the NAMUR Recommendation. 6.3 Product conditions 6.3.1 Physical properties of the products Physical properties (such as density, viscosity, conductivity, relative permittivity, magnetic properties, etc.) have no effect on measurement results. The relative permittivity is merely required to have a minimum value in order to ensure reliable measurements (see Section 6.3.2). 6.3.2 Relative permittivity (εεr ≥ 1.5) The (relative) permittivity of the product (εr , Epsilon-R) determines the strength of the reflected signal. Measurement results are not affected so long as the reflected signal is strong enough, but reliability and the maximum measuring range are dependent upon the relative permittivity. At εr < 3, a stilling well should be used. The minimum relative permittivity of the product is approximately εr = 1.5. See also Section 7.5. If the Wave-Stick is also to take measurements when immersed, εr will need to be > 4. Dielectric Constant and Reflection Factor 70% 60% 50% 40% 30% 20% 10% 0% 1.2 1.6 2.5 3.2 6.3 LPG Benzene Phosgene Paraffin Toluene Petrol Sulfur Chlorine 10 12 Phenol Methanol SEABLE Installation and operating instructions BM 70 A/P 16 20 25 32 Sulfuric acid 40 50 Glycol 63 80 Water εr Nitrobenzene RANGE Page: 26 11/00 6.3.3 Product limitations Radar-based level measuring devices are not suitable for the following products: • liquid a mmonia (NH3) • liquid hydrogen (H2) • liquid helium (He) 6.3.4 Product temperature (unrestricted) The product temperature is not a relevant factor, provided the ambient temperature (see 6.2.2) and the flange temperature (see 6.2.3) are within the specified limits. 6.3.5 maximum allowable operating pressure (max. 64 bar / 928 psig) Flange system with horn antenna or Wave-Guide: PN 16 PN 25 PN 40 PN 64 DN 80 16 bar (232 psig) --- 40 bar (580 psig) 64 bar (928 psig) DN 100 16 bar (232 psig) --- 38 bar (551 psig) 55 bar (798 psig) DN 150 16 bar (232 psig) --- 34 bar (493 psig) 47 bar (682 psig) DN 200 16 bar (232 psig) 25 bar (363 psig) 32 bar (464 psig) 45 bar (653 psig) Information on higher pressures (up to 400 bar / 5800 psig) supplied on request Wave-Stick without plate resp. LP flange system: max. 2 bar / 29 psig Wave-Stick with plate: max. 16 bar, dependent on temperature: bar psig +16 232 (46 - 0.3·T[°C]) bar (740 - 2.4·T[°F]) psig Pressure +1 +15 -1 -15 -20 -4 Temperature T +100 +212 +150 °C +302 °F 6.4 Maintenance Cleaning the antenna Particular process applications can cause severe contamination of the antenna. Microwaves cannot be properly emitted or received when reflected from deposits on the antenna. In such cases, the BM 70 A/P will usually indicate maximum level (volume) or minimum distance. The level of contamination at which such errors occur depends firstly on the product concerned, and secondly on the reflection index, which is mainly determined by the relative permittivity εr. Regular cleaning, or use of the purging device (see Sect. 6.1.7), is advisable if the product has a tendency to form deposits, etc. When spraying, washing down, or cleaning with mechanical aids, take special care not to damage either the horn antenna or the bottom Teflon plug at the waveguide window (see Section 7.4 "Field assembly of the BM 70 A/P"). If cleaning agents are used, take material resistance into account! Installation and operating instructions BM 70 A/P Page: 27 11/00 7 Design Hazardous-duty systems The BM 70 A/P-Ex is approved to European Standard EN 50014/18/19/20 for use in hazardous locations of Zones 0, 1 and 2. • Electronics compartment: Flameproof Enclosure "d" • Terminal compartment: Increased Safety "e" for signal output and power supply Optionally: Intrinsic Safety "i" for the signal output and Increased Safety "e" for the power supply. Special version: Flameproof Enclosure "d" • Pin coupler compartment: Increased Safety "e" • Further details are given in the Certificates of Conformity, see Section 10, and in the "Hazardous-duty systems" boxes (shaded grey in the text, e.g. at the beginning of Section 6), which should without fail be additionally heeded for the BM 70 A/P-Ex. 7.1 Models BM 70 A/P with horn antenna BM 70 A Wave-Guide Installation and operating instructions BM 70 A/P BM 70 A Wave-Stick Page: 28 11/00 7.2 Dimensions and Weights Basic version: High-temperature version: 313 (12.32") 226 (8.89") 313 (12.32") 214 (8.42") 226 (8.89") 420 (16.54") 176 (6.89") Meter size DN ( mm) ANSI (") 80 100 150 200 80 100 150 200 Typ 1s 2s 3s 4s Standard antenna ØA ( mm) ØA (") 80 3,15 100 3,94 140 5,51 200 7,87 76 2,99 100 3,94 152 5,98 200 7,87 Lenght* f ( mm) f (") 110 4,33 148 5,83 223 8,78 335 13,19 420 16,54 620 24,41 820 32,28 820 32,28 Weight kg 17 18 23 30 18 19 25 32 lb 37,48 39,68 50,71 66,14 39,68 41,89 55,12 70,55 * Hastelloy: + 30 mm (1.12”) Wave-Stick: Wave-Stick with hygienic connections: (DIN 11851 "dairy") (with adapter for Tri-Clamp) 313 (12.32") 226 (8.89") 292 260 Ø25 (Ø0.98") L = 384 mm Standard 500 – 1000 mm optional 60 mm Typ SW Flange size dia. A in mm (inches) DN 50 / ANSI 2" 100 (3.94) ANSI 3" 127 (5.0) DN 80 138 (5.43) DN 100 / ANSI 4" 158 (6.22) DN 150 / ANSI 6" 216 (8.5) 351 384 Options: Tri-Clamp 2", 3", 4" SMS 51 mm, 63 mm, 76 mm DIN 11851 (dairy) DN 50, DN 65, DN 80 Weight in kg (lb) 16 (35.27) 17 (37.5) 17 (37.5) 18 (39.7) 23 (50.7) Installation and operating instructions BM 70 A/P Page: 29 11/00 7.3 Replacement of the signal converter Always disconnect from power source before commencing work! Hazardous-duty systems Before replacing the signal converter (instrument "head") in the hazardous location, make absolutely certain that there is no explosion hazard (gas-free certificate). Allow the prescribed waiting time of 22 minutes to elapse before opening the housing! 1. Remove safety lock (see Sect. 9.3) with machinist's wrench, size 4 mm, and unscrew cover from the terminal box with the special wrench. If a sunshade is fitted, remove this first (see Section 6.1.9). 2. Disconnect all cables from the terminals in the terminal compartment, see Section 7.8. 3. Remove the 4 Allen screws M (Allen key size 5 mm) and lift off the signal converter. The flange unit (incl. waveguide window) will remain tight, also on pressurized tanks. Caution On pressurized tanks, do not on any account remove the 4 screws H connecting the waveguide window to the BM 70 A/P flange! DANGER TO LIFE! 4. Install the new BM 70 A/P signal converter. 5. Check power voltage and fuse(s) (refer to instrument nameplate) and change or replace if necessary, see Sect. 9.2 and 9.3. 6. Reconnect all cables in the terminal compartment as described in Sect. 7.8. 7. Check against the attached report on settings whether the factory-set parameters are correct for your application. If not, reset the parameters as described in Sect. 8. 8. Subsequently, record the empty-tank spectrum, see Sect. 8.6.12. Important: Ensure that the screw thread of the covers on the terminal and electronic compartments is well greased at all times. 7.4 Field assembly • When the BM 70 A/P needs to be field assembled, all required parts are included with the supply (stud bolts, washers, etc.). • If supplied loose, bolt the waveguide window (flange assembly) or the distance piece to the BM 70 A/P. Tightening torque for the 4 Allen screws M (key size SW 5 mm): max. 8 Nm ~ 0,8 kpm. signal converter distance piece (for high-temperature version up to 250°C (482 °F) BM70 A connecting flange • Note: The upper Teflon plug must be absolutely dry and clean! Moisture and dirt will negatively affect functionability of the BM 70 A/P! • Bolt antenna and antenna extension together: torque for the 3 stud bolts: max. 8 Nm ~ 0.8 kpm. O-ring antenna extension upper Teflon plug O-ring lower Teflon plug • Do not on any account detach screws H! antenna Installation and operating instructions BM 70 A/P Page: 30 11/00 7.5 Selection of antenna type and size This BM 70 A recommendation for the optimum application range is based on application experience and designed to minimize potential problems. If the recommended antenna is unacceptable, any other configuration may also be tested. Type 1 and 2 antennas should only be used with stilling wells. For BM 70 P always antenna type 4 or a stilling well > 100 mm / 4" is recommended. tank height/ range 130ft 40m 115ft 35m 100ft 30m stillwell stillwell antenna type 4 85ft 25m 65ft 20m 45ft 15m stillwell antenna type 4 antenna type 3 Wave-Stick 30ft 10m 15ft 5m 5ft 1.5m stillwell Wave-Stick stillwell 1.6ft 0.5m Dielectric constant of the medium for: storage tank with 1.5 ∞ ε r smooth surface process tank 10 15 ∞ ε r or foam ∞ ε r with vortex agitator tank 15 30 How to use the diagram: • Determine the following application parameters: a) Tank height or maximum measuring range/distance (e.g. H=15m) b) Tank type (one of the three types shown, e.g. process tank) c) Relative permittivity of the product (e.g. εr=5) • Find the relative permittivity on the relevant horizontal axis (e.g. 5 on the middle axis) • Draw a line up to the required tank height = vertical axis (e.g. 15 m) • The end of the line defines the application range. The text contained in that area indicates the suitable antenna types (in the example: stilling well or Type 4). Installation and operating instructions BM 70 A/P Page: 31 11/00 7.6 Materials of construction Check the materials of the antenna, extension, flange, gaskets, and PTFE (contained in all versions) for compatibility with the product! 7.6.1 Signal converter Housing: Aluminium with electrostatic powder coating to DIN 55990-3. Sight window: Glass 7.6.2 Flange system (Antenna, extensions and flange or flange plating) Available materials for BM 70 A/P flange systems (in contact with the product): DIN No. Versions mit horn antenna or Wave-Guide: Stainless steel 1.4571 Stainless steel 1.4435 Hastelloy C4 2.4610 Hastelloy B2 2.4617 Titanium 3.7035 Tantalum Monell 400 2.4360 Inconell 600 2.4816 AISI equivalent 316 Ti 316 L (Information on other materials supplied on request) Wave-Stick: In the versions with PTFE flange plate, only PTFE is in contact with the product (no metal in contact with the tank contents) Flange made of stainless CrNi steel 1.4571 / 316 Ti 7.6.3 Seals and gaskets Responsibility as to suitability rests solely with the user. Available materials for internal device seals and gaskets in the flange system in contact with the product: Material FFKM (Kalrez 4079 or Parofluor V8545-75) DuPont Kalrez 2035 Viton (FPM) FEP-coated Temperature resistance 250°C/482°F (safety limit 280°C / 536°F) 210°C/410°F 200°C/392°F 200°C/392°F 7.7 Process connection The process connection is by way of standard flanges sized DN 50-200 or equivalent ANSI sizes (dependent on the version). Various hygienic connections are additionally available for the WaveStick (DIN 11851, Tri-Clamp, SMS). Refer to Section 7.2 for further information on the various versions. Installation and operating instructions BM 70 A/P Page: 32 11/00 7.8 Electrical connection The electrical connection for supply power and signal inputs/outputs is made in the terminal compartment (Ex-e) of the signal converter. Observe requirements specified in VDE 165, and consult the safety advice given in Section 9.4. In the BM 70 A/P version with intrinsically safe signal output, only certified intrinsically safe equipment may be connected to the blue terminals, even if the device is not operated in the hazardous area! Terminals: conductor cross-section 0.5 - 2.5 mm² (solid conductor: max. 4 mm²) PE safety conductor and/or FE functional ground: U-clamp terminal (max. 4 mm² conductor cross-section) (see also terminal assignments below and in Sect. 9.4) Cablel entries: 3x M25x1.5 (with standard cable gland: cable clamping area = 9-16 mm) Signal cable shielding: required for RS 485 line, recommended for current output when line lengths > 100 m (350 ft) "Ex" equipotential bonding: U-clamp terminal (max. 4 mm² conductor cross-section) on "neck" of signal converter Rated temperature of power cables: Version Max. flange temperature ≤ 100°C/212°F > 100°C/212°F ≤ 200°C/392°F > 200°C/392°F w/o high temperature distance piece with high temperature distance piece Rated temperature of power cables 70°C/158°F 80°C/176°F 70°C/158°F 80°C/176°F Terminal assignment Supply power: Inputs/Outputs +(-) 24V DC -(+) Inputs/Outputs PE Connections for 115/230 V AC 24V AC FE Connections for 24 V DC/AC (any polarity) Connection of an FE functional ground is not mandatory. ® Current output HART , Ex e: Switching output ® Ex-i current output HART : Current output max. 100mA/30V DCAC Digital input Current output 32 31 - + U min.= 8V 82 81 42 41 32 31 - + - + 4-20mA 5...28V= 4-20mA max.500 Ω Installation and operating instructions BM 70 A/P Ex-i (IS) supply unit Page: 33 U max.= 30V 11/00 ® Ex-i Current output HART with switching output: Current output (non-communicable): Switching output max. 110mA/30V Current output unassigned Currentoutput 32 31 - + 42 41 32 31 - + U min. = 8V 4-20mA max.250 Ω 4-20mA U max.= 30V Ex-i-supply unit RS 485 version: PROFIBUS-PA or Foundation Fieldbus (FF) Current output A 32 31 32 31 - + Busconnection 4-20mA max.250 Ω RS 485 input RS 485 output PROFIBUS-PA / FF with current output: current output PROFIBUS-PA / FF with switching output: switching output max. 110mA/30V 42 41 32 31 + U min. = 8V 4-20mA Ex-i-supplyunit 42 41 32 31 Busconnection Busconnection U max.= 30V 7.9 Terminating resistor for the RS 485 interface A selector plug on the RS 485 board allows optionally a high-resistance termination (presetting) or a terminating resistor of 120 Ω at the RS 485 connections A and B. For this purpose, the housing (flameproof enclosure) of the BM 70 A/P signal converter needs to be opened (see Sect. 9.3) and the selector plug turned 180°, see sketch on the right. RS485 signaloutput board high- 120 impedance Ω .... .... Installation and operating instructions BM 70 A/P Page: 34 11/00 8 User interface 8.1 Local display In the versions with local display at the BM 70 A/P signal converter, configuration can be carried out directly at the device. If a local display is not featured, the PC-CAT program (see Sect. 8.12) must be used to change the parameter setting (assuming a communicable interface is provided). Two variants of the display are available: - Standard display with 2-line LCD display (7 mm high digits for the measured value). - Jumbo display with single-line LCD display and 16 mm high digits for the max. 5-digit measured value (restricted user friendliness for parameter setting, because 2nd line not visible). Standard display c Numerical display of measured value d Alphanumeric display of function/unit e 6 markers to indicate measuring status f 3 keys for configuration and error inquiry g magnetic sensors for control through the closed housing (function same as the 3 keys) h Compass field, signals actuation of a key Jumbo display c Numerical display of measured value (5 places) e 6 markers to indicate measuring status f 3 keys for configuration and error inquiry g magnetic sensors for control through the closed housing (function same as the 3 keys) Installation and operating instructions BM 70 A/P Page: 35 11/00 8.2 Function of the keys The three keys have the following functions: → (Cursor key): - selects the configuration menu, - branches the menu to the next lower level, - moves the cursor* to the right to the next column. ↑ (Select key): - branches the menu to the next digit in the same level, - changes the content (digit, character) at the cursor* position. ↵ (Enter key): - selects the error memory, - branches the menu to the next higher level, - stores newly entered parameters, - executes displayed functions. * The cursor position is signalled by flashing of the character or selected point at the appropriate place. To start operator control: Measuring mode Operator control mode 627 F c t. 1.0 → cm Please note: OPERATION When "YES" is set under Fct. 3.4.2 and ENTRY CODE "CodE1 -------" appears in the display, the → key must be pressed. The 9-keystroke Entry Code1 must then be entered: Factory setting: → → → ↵ ↵ ↵ ↑ ↑ ↑ (each keystroke confirmed in the display by "*".) To terminate operator control: Press key ↵ repeatedly until one of the following menus is displayed. Fct. 1.0 OPERATION, Fct. 2.0 TEST or Fct. 3.0 INSTALL. ↵ Press key ... F c t. 3. 0 I N S T A L L. New parameters not to be stored Press ↑ key to display "STORE.NO". Measuring mode continued with the "old" parameters after pressing the ↵ key; the "START" message is shown until a measured value is determined. If instead you wish to return to Configuration, press the ↑ key first until "RETURN" is displayed, and then the ↵ key. ↵ S T O R E Y E S Store new parameters Confirm by pressing the ↵ key, "START" is displayed, and the measuring mode is continued with the new parameters. Installation and operating instructions BM 70 A/P Page: 36 11/00 8.3 Operator control concept main menu column Submenu column Functions column Data column Measuring mode 627 cm When this displayed, enter the 9-keystroke Entry Code1, see Fct. 3.4.3 Factory setting: → → → ↵ ↵ ↵ ↑ ↑ ↑ CodE1 --------- 3.0 INSTALL. 3.6 SW.OUTPUT.S 3.6.1 - 3.6.4 3.5 APPLICAT. 3.5.1 - 3.5.9 3.4 USER DATA 3.4.1 - 3.4.4 3.3 SIGNAL OUTP. 3.3.1 - 3.3.7 3.2 DISPLAY 3.2.1 - 3.2.5 3.1 BASIS.PARAM 3.1.1 - 3.1.8 2.4 FIRMWARE 2.4.1 - 2.4.2 2.3 SW.OUTP.S 2.3.1 2.2 CUR.OUTP.I 2.2.1 - 2.2.2 2.0 TEST 2.1 HARDWARE 2.1.1 - 2.1.3 1.0 OPERATION 1.1 DISPLAY 1.1.1 - 1.1.3 Setting level ↵ → Directions for using the keys in the menu levels and columns. The flashing part of the display (cursor) can be changed. ↵ ↵ Selection of main Parameter check and return to measuring mode menu with the ↑ key → Selection of submenu with the ↑ key ↵ ↵ Setting the Selection of function with the ↑ key → → data with the → ↑ ↵keys ↵ NO ERROR Return to measuring mode or ↵ CodE2 -- ↑ → Error QUIT → ↵ Error display leaf through the error list by pressing ↑ or → QUIT NO ↑ QUIT YES ↵ Note: If after pressing a key "NO ACCESS" is displayed, this means that the keypad is temporarily blocked owing to a configuration access via the signal output. The keys are available again after Communication has finished. Installation and operating instructions BM 70 A/P Page: 37 11/00 Examples of key functions The cursor (flashing part of display) is shown boxed in by dotted lines in the following description. To change numbers Increase value 627 637 ↑ cm cm To shift cursor (flashing position) Shift to right 637 637 → → cm cm To change the text Select next text ↑ LEVEL DISTANCE To change the unit (tank height) Numerical values are converted automatically Select next unit 6370 637 ↑ cm mm To revert from unit to number setting Change to number setting 6370 mm 6370 → mm To revert to function display 6370 mm 3.1.1. ↵ Installation and operating instructions BM 70 A/P TANKHEIGHT Page: 38 11/00 8.4 Table of settable functions (Versions 3.00, 3.01, 3.02, 3.03, 4.02, 4.03) Function (Fct.) Enter range 1.0 OPERATION 1.1 DISPLAY 1.1.1 FCT.DISP Options 1.1.2 UNIT.LENGTH Options 1.1.3 UNIT. CONV. Options 2.0 2.1 2.1.1 2.1.2 2.1.3 Special function Special function Options TEST HARDWARE MASTER DISPLAY STATUS 2.2 CUR.OUTP.I 2.2.1 VALUE I 2.2.2 TEST I 2.3 SW.OUTPUT 2.3.1 TEST S LEVEL DISTANCE CONVERSION REFLECTION cm mm inch Ft PERCENT BARGRAPH m3 US Gal GB Gal Ft3 bbl PERCENT BARGRAPH USER UNIT Value display Options Options Default value Description LEVEL Select function of display (value to be displayed). Meter [m] Select unit for value of length to be displayed (level/distance). Cubic meter [m3] Select unit for conversion value to be displayed ("volume table"). Tests the hardware of the master. Tests the hardware of the display. Displays ID-Number and Status Bytes Module DIS Module MW 2 mA 4 mA 6 mA 8 mA 10 mA 12 mA 14 mA 16 mA 18 mA 20 mA 22 mA OPEN CLOSED Displays the actual value of the current output. Output of selected value to the current output. 2 mA IMPORTANT !!! With safety inquiry because of direct access to the current output !!! (Exi = min. 3.6 mA) OPEN Switching output on/off. IMPORTANT !!! With safety inquiry because of direct access to the switching output !!! 2.4 2.4.1 2.4.2 3.0 3.1 3.1.1 FIRMWARE MASTER DISPLAY INSTALL. BASIS.PARAM TANKHEIGHT Display Display Displays the firmware version of the master. Displays the firmware version of the display. Options, unit cm mm inch Ft To input the tank height. The tank height is defined as the vertical distance between the bottom edge of the flange and the tank bottom. Enter 0.50 [m] ... max. tank height 3.1.2 BLOCKDIST Enter 10.00 m* / 20.00 m * 0.50 m * 0.10 [m] ... tank height 3.1.3 ANTENNA Options 3.1.4 ANT.EXTENS. Enter STANDARD WAVE STICK STANDARD * 0.00 m * The unit entered here is also used for all other length inputs. To input the block distance. The block distance marks the non-measurable range below the bottom edge of the flange. Selection of the antenna type. (WAVE STICK only for BM 70 A) To input the length of the antenna extension. 0.00 [m] ... Tank height 3.1.5 DIST.PIECE Enter 0 mm * 0 ... 2000 [mm] Installation and operating instructions BM 70 A/P To input the length of the flange distance piece in [mm] (high-temperature version = 120 mm). Page: 39 11/00 Function (Fct.) Enter range 3.1.6 STILLWELL Options NO YES Default value Description NO Select: with or without stilling well. If "YES": Enter (restraint) STILLWELL DIA. 25 ... 200 [mm] 3.1.7 REF.OFFSET Enter When "YES" selected, the inside diameter of the stilling well is additionally entered in [mm]. 100 mm 0.00 m To input the reference offset (relocation of the upper reference point). To input the tank bottom offset (relocation of the lower reference point). -10.00 ... + 10.00 [m] 3.1.8 TB. OFFSET Enter 0.00 m -100.00 ... + 100.00 [m] 3.2 DISPLAY 3.2.1 FCT.DISP. Options 3.2.2 UNIT.LENGTH Options 3.2.3 UNIT.CONV. 3.2.4 USER UNIT Options LEVEL DISTANCE CONVERSION REFLECTION cm mm inch Ft PERCENT BARGRAPH m3 US Gal GB Gal Ft3 bbl PERCENT BARGRAPH USER UNIT Text entry 3.2.5 ERROR MSG. Options 3.3 SIGNAL.OUTP. 3.3.1 FUNCTION I Options 3.3.2 RANGE I Options 3.3.3 SCALE 4 mA Enter LEVEL Select function of the display (value to be displayed). Meter [m] Select unit for length value to be displayed (level/distance). The unit selected here is used only for display of length values. Cubic meter [m3] The unit selected here is used only for display of the conversion value. __________ 10 ASCII characters NO YES OFF LEVEL DISTANCE CONVERSION REFLECTION SW.OUTP. 4-20 mA/E22 4-20 mA/E2 4-20 mA -200.00 ... +200.00 [m] 0.00 ... 99999.99 [m3] YES Select function of the current output (measured value to be displayed, or OFF = current output switched off = constant 4 mA). 4-20 mA/E22 Select the range for the current output and error output. 0.00 m 0.00 m3 Enter -200.00 ... +200.00 [m] 0.00 ... 99999.99 [m3] 0 ... 100 [Refl.] 3.3.5 BAUDRATE Options 3.3.6 ADDRESS Enter 3.3.7 PROTOCOL Options 1200 Bd. 2400 Bd. 4800 Bd. 9600 Bd. 19200 Bd. 38400 Bd. 0 ... 255 ® HART KROHNE/PC (MODBUS) (PROFIBUS-PA) (F.FOUND.) Input of freely programmable unit for the conversion table (max. 10 characters). Select whether error messages are to be shown in the display. LEVEL 0 ... 100 [Refl.] 3.3.4 SCALE 20 mA Select unit for conversion values to be displayed ("volume table"). 10.00 m * 10.00 m3 100 19200 Bd. * HART ® Installation and operating instructions BM 70 A/P Input the lower range value for output to the current output. (Input is dependent on the selected function of the current output. The values for level and distance include the tank bottom and reference offset, resp.). Input of the full-scale range for output to the current output. (Input is dependent on the selected function of the current output. The values for level and distance include the tank bottom and reference offset, resp.). Select the baud rate for the Communication interface (not relevant to HART via current output). (For Fct. 3.3.7 = PROFIBUS-PA or F.FOUND.: deviating options.) Input of the device address for Communication. (For Fct. 3.3.7 = PROFIBUS-PA or F.FOUND.: deviating input range) Select the Communications protocol. (only when appropriate hardware provided) Page: 40 11/00 Function (Fct.) 3.4 Enter range Description GB/USA * Select language to be used in the display (English, German, French, Italian, Spanish, Portuguese, Swedish) Switch the access lockout for the configuration menu on/off. Input of the Entry Code. Input of a max. 8-character device identifier. USER DATA 3.4.1 LANGUAGE Options GB/USA, D, F, I, E, P, S 3.4.2 ENTRY CODE 1 Options NO YES 3.4.3 CODE 1 3.4.4 LOCATION Enter code Text 3.5 APPLICAT. 3.5.1 AUTO TANKH. 3.5.2 EMPTY.SPEC. Special function Options 3.5.3 TIMECONST. Value OFF ON RECORD 3.5.4 TRACING.VEL. Value 0.01 ... 10.00 [m/Min] (BM 70 A) 0.01 ... 1.00 [m/Min] (BM 70 P) 3.5.5 MULT.REFL. Options 3.5.6 BD-DETECT. Options 3.5.7 FUNCT. FTB Options 3.5.8 EPSILON R Enter 3.5.9 TANKTYPE Options 3.6 SW.OUTP.S. 3.6.1 FUNCTION S Options 3.6.2 TYPE S Option 3.6.3 THRESHOLD Value NO YES NO YES OFF PARTIAL FULL 1.1000 ... 8.0000 STORAGE TANK PROC.TANK. AGITATOR OFF LEVEL DISTANCE CONVERSION REFLECTION ERROR OPEN ERROR CLOSED HIGH LOW -200.00 ... +200.00 [m] 0.00 ... 99999.99 [m3] 0 ... 100 [Refl.] 3.6.4 HYSTERESIS NO RRREEEUUU BM70A-00 BM70P-00 1 ... 100 [s] (BM 70 A) 10 ... 100 [s] (BM 70 P) OFF * 10 s (BM 70 A) 30 s (BM 70 P) 0.50 m/min (BM 70 A) 0.10 m/min (BM 70 P) NO 0 ... 100 [Refl.] Automatic determination of the tank height. Switch the empty-tank spectrum (profile of the empty tank) on/off, or make new recording. Input of the time constant for measured-value filtering (low-pass). Input of the maximum rate of change in the level that can occur in operation. Switch the multi-reflection identifier on/off. YES Switch the block distance (overfill) detector on/off. OFF Select function of the tank bottom tracking system. (FULL for BM 70 A only) 2.0000 Input of the relative permittivity of the product for the tank bottom tracking system. Select the tank type. (AGITATOR for BM 70 A only) PROC.TANK. ERROR OPEN Select the function of the switching output. HIGH 50 Select type of limit value for the switching output. (not applicable to Function OFF, ERROR OPEN or ERROR CLOSED) Input of the threshold value for the switching output. (Input is dependent on the function of the switching output. The values for level and distance include the tank bottom and reference offset, resp.) 0.10 m 0.10 m3 Input of the hysteresis for the switching output. (Input is dependent on the function of the switching output.) 5.00 m 5.00 m3 Value 0.00 [m] ... Tank height 0.00 ... 99999.99 [m3] *: Default value 10 Default values following a parameter reset (use of a new EEPROM not yet described). The factory setting for the parameters marked with * is dependent upon the device version and customer specifications (if the tank height is known at the time the order is placed). Installation and operating instructions BM 70 A/P Page: 41 11/00 8.5 Configuration examples upper reference point (top edge of tank connecting flange) Fct. 3.1.5 Fct. 3.1.4 block distance (Fct. 3.1.2) response threshold tank height (Fct. 3.1.1) nonmeasurable zone 20 Imax mA (Fct. 3.3.4) measuring range current output mA Sump Imin (Fct. 3.3.3) lower reference point (tank bottom / datum point) 8.5.1 Level measurement (example) Tank height (Fct. 3.1.1): Antenna extension (Fct. 3.1.4): Block distance (Fct. 3.1.2): 6.00 m 0.20 m 0.70 m Response threshold or maximum measurable level = 5.30 m (calculated from lower reference point) = tank height - block distance (Fct. 3.1.1) (Fct. 3.1.2) = 6.00 m 0.70 m Current output I Function I (Fct 3.3.1): Range I (Fct. 3.3.2): Scaling 4 mA (Fct. 3.3.3): Scaling 20 mA (Fct. 3.3.4): LEVEL 4 - 20 mA 0.00 m, equivalent to 4 mA 5.00 m, equivalent to 20 mA Switching output Function S (Fct. 3.6.1): Type S (Fct. 3.6.2): Threshold (Fct. 3.6.3): Hysteresis (Fct. 3.6.4) LEVEL LOW (= below threshold) 5.00 m 0.10 m Display Function, display (Fct. 3.2.1): Unit, length (Fct. 3.2.2): LEVEL m (meters) Please note Display and outputs can also be used for different measured variables, e.g.: display for conversion, current output I for level, and switching output S for error messages. The value for Scaling 20 mA should not be greater than the response threshold. Installation and operating instructions BM 70 A/P Page: 42 11/00 8.5.2 Volume measurement (example) • In order to be able to measure volume with the BM 70 A/P, a conversion table (volume table) needs to be compiled with the PCCAT program (see Sect. 8.12). • By means of the volume table, various levels are allocated to specific volumes previously calculated or measured out. • In the case of non-sy mmetrical tanks, e.g. tanks with dished bottom, the accuracy of volume measurement will depend on the number of set "level/volume pairs". The maximum number of pairs (points) that can be set is 50; the volume is linearly determined (interpolated) between 2 points. • In the following example, 4 data pairs have been progra mmed. Unit volume (Fct. 3.2.3): m 3 Set table (PC-CAT): Volume table Point Tank height (Fct. 3.1.1): 6.00 m Antenna extension (Fct. 3.1.6): 0.20 m Block distance (Fct. 3.1.2): 0,70 m Level 0.00 0.25 0.50 5.30 Volume 0.25 m³ 0.70 m³ 1.40 m³ 16.80 m³ Response threshold, maximum measurable level = 5.30 m, equivalent to a volume of 16.80 m ³ (calculated from lower reference point) = tank height - block distance (Fct. 3.1.1) (Fct. 3.1.2) 6,00 m 0,70 m Current output I Function I (Fct 3.3.1): Range I (Fct. 3.3.2): Scaling 4 mA (Fct. 3.3.3): Scaling 20 mA (Fct. 3.3.4): CONVERSION 4 - 20 mA 0.00 m3 , corresponds to 4 mA 16.80 m3 , corresponds to 20 mA Switching output Function S (Fct. 3.6.1): Type S (Fct. 3.6.2): Threshold(Fct. 3.6.3): Hysteresis (Fct. 3.6.4) LEVEL LOW (=if level drops below threshold) 5.00 m 0.10 m Display Function, display (Fct. 3.2.1): Unit, conversion (Fct. 3.2.2): CONVERSION m 3 (cubic meter) Installation and operating instructions BM 70 A/P Page: 43 11/00 8.6 Description of functions Reflection units 8.6.1 Choice of units Level/distance units Select under Fct. 3.1.1 TANKHEIGHT • • inch • cm • Ft • mm The unit selected here is also valid for the following functions: - Block distance Fct. 3.1.2 - Antenna extension, Fct. 3.1.4 - Scaling 4 mA value, current output, Fct. 3.3.3 - Scaling 20 mA value, current output, Fct. 3.3.4 - Range for partial tank bottom tracing, Fct. 3.5.2 - Threshold (limit value), switching output, Fct. 3.6.3 - Hysteresis, switching output, Fct. 3.6.4 - Tracking speed, Fct. 3.5.4 (in m/min when Fct.3.1.1 = m, cm or mm or in ft/min when Fct.3.1.1 = inch or ft) The Fct. 3.2.2 (length unit for display) can be set independently of the unit selected under Fct. 3.1.1. The measuring range for "reflection" has a fixed setting of 0...100 (whole numbers). The "reflection" measured value is a relative measure of the strength of the reflected signal, converted into an exponential scale: each number step is approximately equivalent to a change by 0.4 dB; in other words, about 8 steps signify a doubling of the signal strength. At full reflection, a value of approx. 90...100 is measured. Where measuring distances are greater, the natural weakening of the signal is automatically allowed for in the measured value (does not apply to stilling wells, i.e. when Fct. 3.1.6 = YES). The measured reflection can be regarded as being a measure of the reflectivity of a product. Conversion units By conversion is meant the transposition of an arbitrary level value into a "conversion value" (usually volume), so as, for example, to realize a non-linear function as a factor of the level. Options under Fct. 3.2.3 UNIT.CONV. • m³ z l ( = litres) • US Gal z GB Gal (Gal = gallons) • Ft3 z bbl (petroleum barrels) The unit selected here is also valid for the following functions: - Scaling 4 mA value, current output, Fct. 3.3.3 - Scaling 20 mA value, current output, Fct. 3.3.4 - Threshold (limit value), switching output, Fct. 3.6.3 - Hysteresis, switching output, Fct. 3.6.4 • Display range: 0.00 - 30000.00 m3 - 9999999 Liter - 7925161 US Gal - 6599265 GB Gal 0.0 - 999999.9 Ft3 0.0 - 99999.9 bbl (petroleum barrel) Note: When the display is set to Liter, ft³ or Barrel, it is possible that the max. volume will no longer be shown. In such cases, the special symbol " == " is displayed and a change possibly made to a different unit. The current output will in any case output the correct value. Conversion measurement requires that a conversion table be set with the PC-CAT program. By means of this table a conversion value is allocated to each level value (level / conversion pairs). The values are linearly established (interpolated) between 2 points. Also, for the local display an arbitrary (max. 10-character) text (Fct. 3.2.4) can be defined as a unit under Fct. 3.2.4. Internally, this "user unit" is treated in the conversion in the same way as " m³ ". Examples of application and setting: see Sect. 8.5 Installation and operating instructions BM 70 A/P Page: 44 11/00 8.6.3 Block distance, antenna type and antenna extension datum plane for distance O-Ref (+) DS Bottom edge of flange AV BD distance Product surface Level tank bottom O-TB (+) BD AV - tank height - block distance - Antenna extension DS - distance piece O-Ref - reference offset O-TB - tank bottom offset Fct. 3.1.1 [0.00 m ... max. tank height] Fct. 3.1.2 [0.10 m ... Tank height] Fct. 3.1.4 [0.00 m ... Tank height] Fct. 3.1.5 [0 ... 2000 mm] Fct. 3.1.7 [ -10.00 ... + 10.00 m] Fct. 3.1.8 [ -100.00 ... + 100.00 m] datum plane for level 8.6.2 Vessel (tank) height Fct. 3.1.1 TANKHEIGHT • Definition of the tank height for the BM 70 A/P: Distance between the top edge of the tank fitting and the lower reference point. • The lower reference point is that "point" in the vessel on which the microwaves emitted by the BM 70 A/P impinge and from which they are reflected. This can be the tank bottom (sy mmetrical tank with flat bottom) or the non-horizontal part of the bottom (e.g. tank with dished bottom) or an additionally fitted plate. The BM 70 A/P cannot measure below the lower reference point (usually a "sump" is left in the tank, see diagram in Sect. 8.5). • Selection of unit, see Sect. 8.6.1. • Setting ranges for the tank height BM 70 A (standard): • 00.50 40.00 m • 0050 - 4000 cm • 00500 - 40000 mm • 0019.7 - 1574.74 inch • 001.64 - 131.22 ft For BM 70 P: max. 35m / 1377.9 inch / 114.8 ft • Depending on the version, it is also possible to set an upper limit for the tank height (e.g. Wave-Stick: 20 m). The maximum value can be increased by KROHNE Service to up to 100 m. (For BM 70 A only) • The tank height set at this point is simultaneously the upper limit of the setting ranges for the following functions: - Block distance, Fct. 3.1.2 - Antenna extension, Fct. 3.1.4 - Hysteresis, switching output, Fct. 3.6.4 • If the tank height is changed to a value greater than 30 m, a new empty spectrum must subsequently be recorded, see Sect. 8.6.12. (not applicable to BM 70P). Installation and operating instructions BM 70 A/P Fct. 3.1.2 BLOCKDIST • Caked deposits or contamination of the antenna, for example, can cause faulty measurements directly below the antenna. The function "block distance" is used to specify a zone below the flange in which measurements are not to be carried out. • Signals within the block distance are suppressed; a rise in the level above this limit will result in a measurement corresponding to a distance = block distance, when Fct. 3.5.6 BD-DETECT = ON. • Unit and setting range: same as Fct. 3.1.1 TANKHEIGHT. • Recommended minimum value (see also Sect. 3.3): - for "Wave-Stick": 200 mm - for stilling wells and "Wave-Stick SW": antenna length + 300 mm - all other versions in storage tanks: antenna extension + antenna length + 100 mm - all other versions in process tanks: antenna extension + antenna length + 200 mm Fct. 3.1.3 ANTENNA • The antenna type is factory-set here. • STANDARD (all versions incl. "Wave-Stick SW" but excl. "Wave-Stick") • WAVESTICK (not for "Wave-Stick SW") • BM 70 P: only STANDARD setting possible. Fct. 3.1.4 ANT.EXTENS. The length of the supplied antenna extension is factory-set here. • Unit and setting range: same as Fct. 3.1.1 TANKHEIGHT. This setting may only be changed when a longer or shorter antenna extension is installed. Otherwise faulty measurements may result because the BM 70 A/P allows for this length when measuring. After changing any antenna extension, record a new empty spectrum, see Sect. 8.6.12. When a curved antenna extension is used, only the vertical component (vertical offset) should be entered here. Example (S-shaped extension): Fct. 3.1.4 = 323 mm. 323 mm (Fct. 3.1.4) 300 mm (Fct. 3.1.5) 8.6.4 Distance piece Fct. 3.1.5 DIST.PIECE The length of any supplied distance piece above the mounting flange is factory-set here. • Setting range: 0 ... 2000 mm • Default value: 0 mm The value of 120 mm should be entered for the hightemperature version of the flange system. When a curved antenna extension is used, the horizontal component of this extension should additionally be entered (= geometric length of the pipe minus the vertical offset). Example (see drawing above): Fct. 3.1.5 = 300 mm. Page: 45 11/00 8.6.5 Stilling well Fct. 3.1.6 STILLWELL If the device is operated with a stilling well, the option Stilling well = YES and the inside diameter of the pipe should be entered here in mm. • NO : operation without stilling well • YES : operation with stilling well If YES has been selected, proceed with ↵ and enter the inside diameter: • Setting range: 25 ... 200 mm • Default value: 100 mm If the diameter of the stilling well is greater than 200 mm, enter the maximum value = 200 mm. Example 2: Reference point for level measurement differs from the progra mmed tank bottom position (in the example, 2 m below the tank bottom). Let the tank height be H = 6 m. BM 70 Reference point Blockdistance 8m Level H = 6m Tank bottom 8.6.6 Reference and tank bottom offsets TBO = 2m Fct 3.1.7 REF. OFFSET An arbitrary reference offset is added to the measured distance (positive when the reference point is above the flange; negative when the reference point is below the flange): see Example 1 below. The offset is effective for all distance values (local display, current output, switching output, digital information). • Setting range: -10 m ... +10 m (32.8 ft) • Default value: 0 Fct 3.1.8 TB.OFFSET An arbitrary tank bottom offset is added to the measured level (positive, when the reference point is below the set tank height; negative, when the reference point is above the tank bottom): see Examples 2 and 3. The offset acts on all level values (local display, current output, switching output, conversion table, digital information). • Setting range: -99.99 m ... +99.99 m (328 ft) • Default value: 0 Reference plane for level measurement Input the following parameters: Tank height = 6 m Tank bottom offset = + 2 m Reference offset = 0 The possible measuring range is: Level = 2 m to (8 m - block distance). Example 3: Only a specific part of the level in a very tall tank is to be measured (in the example, levels 50m ... 60m). BM 70 Reference point Block distance 10m Level Examples of setting the reference offset and tank bottom offset: Example 1: Reference point for distance measurement (ullage) differs from flange position (in the example, 1 m above the flange). Let the tank height be H = 6 m. programmed tank bottom 60m TBO = 50m Reference plane for distance measuring RO = 1m BM 70 Reference point Blockdistance Reference plane for level measurement H = 6m "Ullage" 7m Input the following parameters: Tank height = 6 m Reference offset = + 1 m Tank bottom offset = 0 Input the following parameters: Tank height = 10 m Tank bottom offset = + 50 m Reference offset = 0 The possible measuring range is: Level = 50 m to (60 m - block distance). The possible measuring range is: Distance = (1 m + block distance) to 7 m. Installation and operating instructions BM 70 A/P Page: 46 11/00 8.6.7 Display 8.6.8 Current output I Fct. 3.2.1 (or Fct. 1.1.1) FCT.DISP. This function is used to select the measured variable. • • • • LEVEL DISTANCE CONVERSION REFLECTION Measuring range, see Figure in Sect. 8.5. If the conversion value is to be displayed, a conversion table must be progra mmed first otherwise a parameter error will occur. Fct. 3.2.2 (or Fct. 1.1.2) UNIT.LENGTH Use this function to select the unit for displaying level and distance. • m • cm • mm • inch • Ft • PERCENT • BARGRAPH The "percent display" refers to the scaling range of current output I. Therefore the current output must also be set to level or distance, otherwise a parameter error will occur. Under "Bargraph", a maximum of 25 segments are displayed in the form of vertical lines in the first line of the display (0% = 1 segment, 100% = 25 segments). Fct. 3.2.3 (or Fct. 1.1.3) UNIT.CONV. Use this function to select the unit for conversion display. • m3 z litres • US Gal z GB Gal (Gal = gallons) • ft3 z bbl (petroleum barrels) • PERCENT z BARGRAPH • User Unit (see Fct. 3.2.4) The "percent display" refers to the scaling range of current output I. Therefore the current output must also be set to conversion, otherwise a parameter error will occur. Under "Bargraph" in the first line of the display a maximum of 25 segments as vertical lines are displayed (0% = 1 segment, 100% = 25 segments). Fct. 3.2.4 USER UNIT Enter the text for the conversion "user unit" (see Fct. 3.2.3) here. It consists of a maximum of 10 alphanumeric characters. • Characters assignable to each of the 10 places: alpha characters A-Z / a-z numbers 0-9 or special signs + blank characters (= underscore) Fct. 3.2.5 ERROR MSG. Use this function to select whether errors are to be displayed during measurement. • NO Error messages shown only in the error list, see Sect. 8.8 • YES When errors occur during measurement,display of the measured value will alternate with error messages. Fct. 3.3.1. FUNCTION I Use this function to select the measured variable. • OFF (= deactivated, the output supplies a constant 4 mA, e.g. necessary for HART® Multidrop; Fct. 3.3.2 to 3.3.4 cannot then be selected, i.e. they are skipped over). • LEVEL • DISTANCE • CONVERSION • REFLECTION • SW.OUTP. (function and switching threshold are set in Fct. 3.6). Fct. 3.3.2 RANGE I Use this function to define the current in error condition. E = Error at 2 mA or 22 mA. • • • 4-20 mA (hold last measured value when error occurs) 4-20 mA/E=2 (min. 3.6 mA for Ex-i output!) 4-20 mA/E=22 Fct. 3.3.3 SCALE 4 mA • This function does not appear (is skipped over) when "OFF" is set under Fct. 3.3.1. • This function is used for Imin = 4 mA to define the lower value for level, distance, conversion or reflection (scaling 4 mA). • • • Setting LEVEL or DISTANCE under Fct. 3.3.1: Setting range and unit for SCALE 4 mA same as for Fct. 3.1.1 TANKHEIGHT. If a reference or tank bottom offset is set, this must be allowed for! Setting CONVERSION under Fct. 3.3.1: Unit for SCALE 4 mA same as in Fct. 3.2.3 UNIT.CONV. But value must be smaller than the maximum value in the conversion table. Setting REFLECTION under Fct. 3.3.1: The setting range for SCALE 4 mA is 0...99. Fct. 3.3.4 SCALE 20 mA • This function does not appear (is skipped over) when "OFF" is set under Fct. 3.3.1. • This function is used für I max = 20 mA to define the upper value for level, distance, conversion or reflection (scaling 20 mA) • Setting LEVEL or DISTANCE under Fct. 3.3.1: Setting range and unit for SCALE 20 mA as for Fct. 3.3.1 TANKHEIGHT. The value set here should not be greater than the response threshold. (Response threshold = tank height (Fct. 3.1.1) - block distance (Fct. 3.1.2)). If a reference or a tank bottom offset is set, this must be allowed for! • Setting CONVERSION under Fct. 3.3.1: Unit for SCALE 20 mA same as in Fct. 3.2.3 UNIT.CONV. The value set here must be greater than that of Fct. 3.3.3, otherwise error during Parameter Check. • Setting REFLECTION under Fct. 3.3.1: The setting range for I max = 20 mA is 1...100. The value set here must be greater than that of Fct. 3.3.3, otherwise error during Parameter Check. Application and setting examples: see Sect. 8.5 Installation and operating instructions BM 70 A/P Page: 47 11/00 8.6.9 Communication interfaces Fct. 3.3.5 BAUDRATE • This function defines the transmission rate for RS 485 Communication. • 1200 Bd. • 2400 Bd. • 4800 Bd. • 9600 Bd. • 19200 Bd. • 38400 Bd. Default value = 19200 bauds • For devices with PROFIBUS-PA (Ex-i) output the value has been set to 31250 bauds. and cannot be changed. • The value set here is not relevant for digital ® Communication via the current output (e.g. HART ). For this, 1200 bauds are on principle processed, independent of the setting in Fct. 3.3.5! Fct. 3.3.6 ADDRESS • This function is used for entering valid addresses from 0 to 255 (PROFIBUS: 0 to 126). • If several devices are operated on one digital bus or via HART®-Multidrop, each device must be set to an individual address under which it can then be addressed in the bus. • The default value is the address "0". PROFIBUS-PA: (special signal output required) The PROFIBUS-PA is defined and standardized in DIN 19245, Parts 1 and 2. A large number of devices with PROFIBUS-PA capability are available on the market. The BM 70 A/P is easy to connect to such bus systems; it has a purely slave function and allows access to all dynamic values and to setting parameters. The hardware interface we use is the intrinsically safe bus interface. For further information, please ask for the "BM70A/P PROFIBUS-PA" description. F.FOUND.: (special signal output required) Bus interface in conformity with the "Foundation Fieldbus" (FF). For further information, please ask for the "BM70A/P Foundation Fieldbus " description. - in preparation - Fct. 3.3.7 PROTOCOL The following Communications protocols are available: HART®: ® The HART protocol is a Communications protocol of the ® "HART Communication Foundation". In addition to the "universal commands" and "common practice commands" there are "device-specific commands" for access to all parameters and functions of the BM 70 A/P. In addition there is the "device description" (DD) for BM 70 A/P, which ® can be used for universal HART control units, such as the ® HART Communicator or SIPROM. The standard hardware platform for HART® is the current output 4-20 mA with superimposed FSK signals. For ® HART -Multidrop (max. 15 devices on one bus), the version with Ex-i current output, set to a constant 4 mA (Fct. 3.3.1 = OFF) should be selected. KROHNE/PC (KROHNE protocol): The standard Communications protocol between the BM 70 A/P and the evaluation system is the standardized KROHNE protocol, which allows all dynamic values and setting parameters to be read and changed. If the BM 70 A/P is connected to existing user systems, this protocol must be applied to such systems. The protocol can also be used when the BM 70 A/P is connected to the KROHNE Tank Inventory System. For further information, please ask for the "BM70A/P PC Communication" description. MODBUS: (not yet included in V. 3.00/3.01/4.00) The Modbus protocol constitutes a quasi-standard for linking to progra mmable logic controls (PLC) and other systems. The BM 70 A/P uses the Modbus RTU Protocol with extended facilities to permit access to all dynamic values and setting parameters. For further information, please ask for the "BM70A/P Modbus" description. Installation and operating instructions BM 70 A/P Page: 48 11/00 8.6.10 Display Language of display texts A choice of languages for the display texts is offered in Fct. 3.4.1. • GB/USA English y E Spanish (Español) • D German y P Portuguese • F French y S Swedish • I Italian If the message: NO MEAS.VAL. appears, this means that the quality of measurement is not adequate (inadequate bottom reflection or too many interferences) for automatic determination of the tank height. Press key ↵ to abort the operation. In this case you will need to enter the tank height manually with Fct. 3.1.1. Coding desired for entry into setting level? Set NO or YES in Fct. 3.4.2 ENTRY.CODE1. • If NO set, simply press key → to get into the setting level. • If YES set, press key → and then a 9-keystroke combination to get into the setting level. • Factory-set Entry Code 1: →→→↵↵↵↑↑↑ • To change Entry Code 1 Select Fct. 3.4.2 ENTRY CODE 1: set to YES. Select Fct. 3.4.3 CODE 1. Press key → , display shows: CODE 1 _ _ _ _ _ _ _ _ Key-in required 9-keystroke combination; each keystroke confirmed by "*". Then press the same keystroke combination again. "WRONG CODE" (= incorrect entry) appears if 1st and 2nd entries are not equal. Press keys ↵ and → and repeat entries. Take good note of the selected entry code! Measuring-point identification (tag name) • A max. 8-figure tag name can be set under Fct. 3.4.4 LOCATION (e.g. L123 A53) • Characters assignable to each of the 8 places: alpha characters A-Z / a-z; numbers 0-9; special signs: + - ; blanks (= underscore character) Factory setting: BM70A-00 or BM70P-00 8.6.11 Auto tank height FCT. 3.5.1 AUTO TANKH. With this function the height of the tank can be determined by the BM 70 A/P itself, provided the following conditions are met: • The tank has been completely drained for at least 2 minutes. • The tank bottom has good reflectivity (not suitable for dished and tapered bottoms without reference plate). • The functions Fct. 3.1.3 (antenna), Fct. 3.1.4 (extension), Fct. 3.1.5 (distance piece) and Fct. 3.1.6 (stilling well) must previously have been correctly set. • If the tank is taller than 30 m, the approximate tank height must previously be set manually with Fct. 3.1.1, as otherwise the measuring range will not suffice to locate the bottom. After pressing the → key the display shows the currently measured value for the tank height. Press key ↵; the inquiry "SURE NO" now appears. If you are not sure whether the measured value coincides with the true tank height, reject the value by pressing key ↵. If the measured value seems plausible for the tank height and you wish to store it, change the option to "SURE YES" by pressing key ↑, and then press key ↵. Installation and operating instructions BM 70 A/P Page: 49 11/00 8.6.12 Empty spectrum What is an empty spectrum ? • Fixed and moving internals in the tank (including perhaps the tank wall) produce interference signals (reflections) that can result in incorrect measurements. • To enable the BM 70 A/P to identify and blank out such interference signals, the tank profile (empty spectrum) needs to be recorded once only prior to (initial) startup. • For this purpose, the tank should if possible be completely empty and all moving parts (e.g. agitators) switched on. If these conditions cannot be met during startup, the tank profile (empty spectrum) can also be recorded at a later time. Until it is recorded, however, measurements may be inaccurate. • • • Recording of the tank profile involves 1000 measurements that are carried out by the BM 70 A/P and stored in the form of a so-called "empty spectrum". This allows the BM 70 A/P to discriminate between constant or regularly recurring interference signals and the actually useful or wanted signals (level). Interference signals are suppressed and only the useful signal is processed. If no appreciable interference from internals is to be expected, recording of the empty spectrum can also be omitted, because a partial empty spectrum (see below) of the flange system has been stored by the factory. Recording of the empty spectrum (sequence, example) Key Displayed Description → 2x↑ → 4x↑ → ↑ → 1.0 3.0 3.1 3.5 3.5.2 ↑ EMPTY.SPEC. ON Partial empty spectrum already recorded by factory ↵ RECORD AVERAGE ↑ ↵ MAX. VALUES TOTAL ↑ PARTIAL ↵ 40000 mm Enter distance value down to which the empty spectrum is to be recorded. WAIT 1000...0 Empty spectrum being recorded. Duration: approx. 1.5 minutes. Countdown is from "1000" to "0". ↵ ↵ 3.5.2 4x↵ Installation and operating instructions BM 70 A/P OPERATION INSTALL. BASIS.PARAM. APPLICAT. If "9 underscores" now shown, key in the 9-keystroke Entry Code 1. Page: 50 READY EMPTY.SPECT. Factory-set is here AVERAGE (= normal empty spectrum). This setting is suitable for most applications (possible alternative) Recording of the empty spectrum over the full range. If the tank cannot be drained over the full range After 1.5 minutes. Tank profile recorded. Revert to measuring mode with display of actual level, distance or conversion. Empty spectrum is now stored and will be taken into consideration for measurements. 11/00 FCT. 3.5.2 EMPTY.SPEC. Under this function the empty spectrum is activated or deactivated, or recorded and stored. The display first gives information as to whether the empty spectrum is currently switched ON or OFF. You can then choose between: • OFF: The empty spectrum is not considered for measurements but remains stored in the BM 70 A/P and can be activated again at a later date. • ON: The empty spectrum is (again) activated and considered for measurements. • RECORD: The previous empty spectrum is to be deleted and a new one recorded. Conditions: - Tank must be totally or partially drained. - All moving parts, e.g. agitators, must be switched on. - Tank height, antenna extension, distance piece and still well must be set correctly. Note: where a Wave-Stick is involved Due to an error in Firmware Version 3.00, before the empty spectrum can be re-recorded, parameter 3.1.3 ANTENNA (see Section 8.6.3) must first be set to STANDARD and then set to WAVE-STICK after the empty spectrum recording has been made. If these directions are not observed, the "SPECT.ERR" error will be indicated, and the recording will need to be carried out again (correctly). This error has been rectified in subsequent firmware version (V. 3.01 and higher), and the empty tank spectrum can be recorded in the usual way for the WaveStick. When you select "RECORD", the procedure is as follows: If other configuration parameters have previously been changed, you will first be asked by "STORE YES" whether you wish to store the data. Confirm by pressing key ↵. The next step is a choice of the following: • AVERAGE Values are averaged. This setting can be used for most applications. • MAX. VALUES Only maximum values considered when the empty spectrum is recorded. Of advantage in conjunction with "difficult" agitators, for example. If the tank is not completely drained, the empty tank spectrum can nevertheless still be recorded up to a certain range. In this case, select menu item PARTIAL. • After selecting AVERAGE or maX. VALUES, press key ↵. Then select PARTIAL or TOTAL with key ↑, as follows. • If TOTAL selected, the empty-tank spectrum is recorded over the complete range. • If PARTIAL selected, interrogation is carried out via the ↵ key concerning input of the distance value up to which the empty-tank spectrum shall be recorded. • The tank area below the current product level is excluded from the recording of the empty-tank spectrum. • The distance value is entered in the same unit as used for the tank height, in the range of 0 m to tank height. • It is recommended to maintain a safe distance of 20 to 30 cm (8" to 12") to the actual distance. Subsequently press key ↵ to start recording of the emptytank spectrum. "WAIT" appears briefly in the display. Then countdown of measurements from "1000" to "0". "READY" is displayed after approx. 1.5 Minutes. Press ↵ key 5 times to store the empty spectrum, which will then be taken into consideration during measurements. Recording of the empty spectrum can be aborted by pressing key ↵ . Displayed: BREAK. Confirm by pressing key ↵ . The "old" empty spectrum is retained in this case. Installation and operating instructions BM 70 A/P 8.6.13 Time constant and tracking speed Fct. 3.5.3 TIMECONST. • New measured values are damped (filtered) with the time constant so as to avoid abrupt changes in measured values and thus also in the current output I and the display. • Setting range: 001 - 100 Sec (BM 70 A) 010 - 100 Sec (BM 70 P) • The tank bottom must supply a measurable reflection signal, so the method cannot be applied e.g. when a dished bottom is involved. • Default value and recommended setting: 010 Sec (BM 70 A) 030 Sec (BM 70 P) Fct. 3.5.4 TRACING.VEL. To avoid faulty measurements, the BM 70 A/P places a sy mmetrical "plausibility range" around the last valid measured value in which the next measured value is expected. Measured values outside this range are identified as invalid and are suppressed. If no valid measured value is identified, the BM 70 A/P enlarges the plausibility range with the tracing speed (Fct. 3.5.4) until a valid (plausible) measured value has again been found. The measured value for level/distance cannot change at a faster rate than the set tracing speed. • Under Fct. 3.5.4 the maximum rate at which the level can change in the tank should be set as the minimum value. • Setting ranges: BM 70 A 0.01 - 10.00 m/min (if Fct. 3.1.1. Unit m/ cm/ mm) 0.03 - 32.80 ft/min (if Fct. 3.1.1. Unit inch/ft) BM 70 P 0.01 - 1.00 m/min (if Fct. 3.1.1. Unit m/ cm/ mm) 0.03 - 3.28 ft/min (if Fct. 3.1.1. Unit inch/ft) • Default: 0.5 m/min (BM 70 A); 0.1 m/min (BM 70 P) • See also Sect. 8.8 (error message: NO M.VALUE) 8.6.14 Multiple reflections and block distance detection Fct. 3.5.5 MULT.REFL. Multiple reflections frequently occur in storage tanks with an extremely calm surface, typically when the BM 70 A/P is mounted on a dome or centred on a "dished cover", or the vessel is fitted with a flat or only very slightly convex head. Such multiple reflections tend to simulate lower-thanactual levels. In such cases, activate the multiple reflections identifier, and see also references in Sect. 8.8. • NO (default) Measurement without identification of multiple reflections. • YES Measurement with identification of multiple reflections. A better solution, however, is to change the mounting location of the BM 70 A/P so as to prevent the occurrence of multiple reflections in the first place, or at least to diminish the strength of the multiple reflections (see Sect. 6.1.2). To ensure satisfactory identification of the first measured value after the BM 70 A/P has been switched on, always carry out measurements with the "empty spectrum" (Fct. 3.5.2) when the "multiple reflection identifier" is activated, see Sect. 8.6.12. Page: 51 11/00 Fct 3.5.6 BD-DETECT. • NO • YES (default) To activate the block distance (overfill) detector: So long as a significant signal is detected within the block distance, the measured value is "held" at the block distance limit. This avoids any possibility of the measured value skipping to a multiple reflection should the level rise into the block distance range. The block distance can have a value that is at least equal to that specified in Sect. 8.6.3 as a recommendation! marker 6 in the display indicates when the block distance detector is active. If the measured value skips (e.g. contamination of the antenna) erroneously to the block distance limit, the BD-DETECT should be deactivated. 8.6.15 Tank bottom tracing system Description • The BM 70 A/P firmware includes an additional function for measuring in tanks with poorly reflecting (i.e. relative permittivity εR ↑ 3) yet non-absorbing products. This function is designated "tank bottom tracing" (abbreviated to FTB) and utilizes the apparent shift of the tank bottom signal resulting from different microwave propagation rates in the air and in the tank product. • It is necessary that the tank bottom is reflecting. Therefore this method is not applicable e.g. in tanks with a conical bottom. • This requires that the relative permittivity εR of the tank product be as exact as possible. (This parameter can also be determined by a KROHNE Service technician from the recording of a tank filling or draining operation with the user program (see Sect. 8.12). The level in the tank should in this case change over the largest possible range.) • When measurements are taken with activated FTB, an expectancy range for the measured value is determined on the basis of the shifted tank bottom signal, and inaccuracy of the εR value of ± 10% is taken into consideration. If no evaluable measuring signal is obtained within this range, a substitute measured value is calculated direct from the tank bottom signal. This feature of the FTB even allows measurement in tanks without a direct useful signal, provided the tank bottom remains visible for the microwaves through the product. • Since the exact position of the tank bottom must be known for this process, it is advisable when using the FTB to determine the tank height automatically with a completely empty tank, using Fct. 3.5.1, see Sect. 8.6.11. • It needs to be borne in mind that, when measuring with the substitute measured value determined by way of the tank bottom signal, measuring accuracy will decrease by the factor (√εR - 1)! For a εR of 2.25, accuracy decreases by one-half, i.e. the possible deviation will double; if εR is only 1.56, accuracy decreases to one-quarter. • With BM 70 P: when the (Partical) tank bottom tracing system is used, the maximum measuring range is approx. 10% smaller, i.e. max. tank height = 31.5 m ! The tank bottom tracing system is operated by way of Fct. 3.5.7 and Fct. 3.5.8. Installation and operating instructions BM 70 A/P Fct. 3.5.7 FUNCT. FTB The tank bottom tracing system is activated under this function: • OFF The FTB is deactivated; the device operates in the standard mode. • PARTIAL When this option has been selected, the tank bottom tracing system is activated only in the vicinity of the tank bottom, i.e. at low levels (max. 20% of the tank height but a minimum of 0.6 m). Given higher levels, the normal measuring method is used (reflection from the product surface). This method is sufficient for most applications with poorly reflecting products. The parameter EPSILON R (Fct. 3.5.8) must be as exact as possible. • FULL ( for BM 70 A only) When this option is selected, the tank bottom tracing system is activated over the total measuring range (tank height). For tank heights above 16 m, however, measuring accuracy is additionally affected. The parameter EPSILON R (Fct. 3.5.8) must be as exact as possible. Fct. 3.5.8 EPSILON R Use this function to enter the relative permittivity. • Allowable input range: 1.1000 - 8.0000 • Default: 2.0000 Enter the figure of 2.0000 if the relative permittivity is not known, as numerous products have a εR value ≈ 2. However, expect reduced measuring accuracy and/or skipping of the measured value on changeover from tank bottom tracing to the normal measuring mode (= evaluation of reflection from the product surface), see following diagram: level example of a tank filling EPSILON R too low correct too high time Page: 52 11/00 8.6.16 Tank type, movement of product surface 8.6.17 Switching output For optimum results, data acquisition and evaluation must bematched to typical tank characteristics: movement of the product surface, rapid or slow changes in the product level, agitators, etc. The functions for the switching output can be applied to: a) the additional switching output in the Version "Ex-e or ® Ex-i current output HART ", or b) the current output if Fct. 3.3.1 FUNCTION I is set to "SW.OUTP.". Fct. 3.5.9 TANKTYPE • STORAGE T. Storage tank, still surface, slow rate of change in level • PROC.TANK Process tank, slight surface movement, rapid rate of change in level • AGITATOR (for BM 70 A only) Process tank with agitator, turbulent product surface It is normally not critical if the tank type is set one step out. However, "AGITATOR" should not be set for a storage tank, and "STORAGE T." should not be set when an agitator is fitted. It is possible, for instance, that the measured value will change in small steps rather than linearly or will "freeze" at times when the setting is grossly incorrect. Fct. 3.6.1. FUNCTION S Use this function to select the measured variable. • OFF (= deactivated; Fct. 3.6.2, 3.6.3 and 3.6.4 are no longer selectable, i.e. they are skipped over). • LEVEL • DISTANCE • CONVERSION • REFLECTION • ERROR OPEN (default) • ERROR CLOSED (Explanatory notes: see Table overleaf) Fct. 3.6.2. TYPE S • This function is not shown (is skipped over) when OFF or ERROR OPEN or ERROR CLOSED is set under Fct. 3.6.1. Not significant is this case! • Use this function to set the type of switching output: HIGH (= contact closes when upper limit of threshold + hysteresis / 2) exceeded LOW (= contact closes when lower limit of threshold hysteresis / 2) exceeded. Fct. 3.6.3 THRESHOLD • This function is not shown (is skipped over) when OFF, ERROR OPEN or ERROR CLOSED is set under Fct. 3.6.1. Not significant in this case! • Use this function to define the threshold (limit value). • Setting of LEVEL or DISTANCE under Fct. 3.6.1: Unit same as for Fct. 3.1.1 TANKHEIGHT. If a reference or tank bottom offset is set, this must be taken into consideration! • • Setting: CONVERSION under Fct. 3.6.1: Unit same as in Fct. 3.2.3 UNIT.CONV. Setting: REFLECTION under Fct. 3.6.1: Setting range : 0...100. Fct. 3.6.4 HYSTERESIS • This function is not shown (is skipped over) when OFF, ERROR OPEN or ERROR CLOSED is set under Fct. 3.6.1. Not significant in this case! • Use this function to define the hysteresis. • • • Setting: LEVEL or DISTANCE under Fct. 3.6.1: Setting range and unit same as for Fct. 3.1.1 TANKHEIGHT. Setting CONVERSION under Fct. 3.6.1: Unit same as in Fct. 3.2.3 UNIT.CONV. Setting REFLECTION under Fct. 3.6.1: Setting range: 0...100. Examples of application and setting see Sect. 8.5 Installation and operating instructions BM 70 A/P Page: 53 11/00 Switching output characteristics FUNCTION S: LEVEL Fct. 3.6.1 DISTANCE CONVERSION REFLECTION Overflow = Threshold + Hysteresis / 2 HYSTERESIS Fct. 3.6.4 THRESHOLD Fct 3.6.3 Underflow = Threshold + Hysteresis / 2 TYPE S Fct. 3.6.2 Switching output Sw.output application Examples see Sect. 8.5 Error message Contact opens when error occurs Contact closes when error occurs Limit value, level - Contact closes when upper limit exceeded - Contact closes when lower limit exceeded Limit value, distance - Contact closes when upper limit exceeded - Contact closes when lower limit exceeded Limit value, conversion - Contact closes when upper limit exceeded - Contact closes when lower limit exceeded Limit value, reflection - Contact closes when upper limit exceeded - Contact closes when lower limit exceeded e.g. operation indicator Contact closed when supply power applied and open at power fail HIGH open closed LOW closed open open closed closed open Switching function settable by way of ... Fct. 3.6.1 Fct. 3.6.2 FUNCTION S TYPE S Further parameters settable via ... Fct. 3.6.3 Fct. 3.6.4 THRESHOLD HYSTERESIS ERROR OPEN ERROR CLOSED no * no * no* no * no * no* LEVEL HIGH yes yes LEVEL LOW yes yes DISTANCE HIGH yes yes DISTANCE LOW yes yes CONVERSION HIGH yes yes CONVERSION LOW yes yes REFLECTION HIGH yes yes REFLECTION LOW yes yes OFF no * no * no * Installation and operating instructions BM 70 A/P Page: 54 * Setting has no effect on the function of the switching output! Overflow = Measured value higher than limit value (= threshold plus hysteresis / 2) Underflow = Measured value lower than limit value (= threshold minus hysteresis / 2) 11/00 8.7 Functional checks 8.7.1 main menu 2.0 Test functions 8.7.3 Test of current output Function (Fct.) Input range Description 2.0 TEST 2.1.0 HARDWARE 2.1.1 MASTER Special function Test of master hardware. 2.1.2 DISPLAY Special function Test of display hardware. 2.1.3 STATUS Select Module DIS Module MW Display of ID Number and status bytes. 2.2.1 VALUE I Display of value 2.2.2 TEST I Options Display of actual value of the current output. Output of selected value to the current output. 2.2.0 CUR.OUTP.I 2 mA 4 mA 6 mA 8 mA 10 mA 12 mA 14 mA 16 mA 18 mA 20 mA 22 mA NOTE !!! With safety inquiry because current output is accessed direct !!! (Exi = min. 3.6 mA) 2.3.0 SW.OUTP. 2.3.1 TEST S Options OPEN CLOSED Switches the switching contact on/off. NOTE !!! With safety inquiry because current output is accessed direct !!! 2.4.0 FIRMWARE 2.4.1 MASTER Display 2.4.2 DISPLAY Display Display of master firmware version. Display of master firmware version. Fct. 2.2.1 VALUE I • Select Function 2.2.1, as described in Sect. 8.2 and 8.3. • Press → key to display the actual value of the current output (terminals 31 and 32) in "mA". • Terminate test by pressing the ↵ key. Fct. 2.2.2 TEST I • A millia mmeter should be connected to terminals 31 and 32 for this test, see Sect. 7.8 • Select Function 2.2.2, as described in Sect. 8.2 and 8.3. • Press → key. • Safety inquiry: SURE NO } Select with SURE YES ↑ key After SURE YES, press the ↵ key for the 1st value in the following list to be present at the current output. • Select current values with the ↑ key: 2 mA 14 mA 4 mA 16 mA 6 mA 18 mA 8 mA 20 mA 10 mA 22 mA 12 mA • • 8.7.2 Hardware test Testing of the BM 70 A/P hardware can be initiated as required with these functions when the device is operating. When an error is established, a message appears in the display (see Sect. 8.8). This hardware test is carried out automatically every time the BM 70 A/P is started up. Fct. 2.1.1 MASTER • Select Function 2.1.1, as described in Sect. 8.2 and 8.3. • "TEST" is shown in the display during the automatic test, followed by "READY" on completion of the test. • During the test the current output holds the last measured value; digital Communication is not possible during that time. Fct. 2.1.2. DISPLAY • Select Funtion 2.1.2, as described in Sect. 8.2 and 8.3. • Press the → key; all segments in the display are switched on. • Press ↑ key; all segments are switched off. • This procedure (switching on/off) can be repeated any number of times with the ↑ key. • Press the ↵ key to terminate the test. • The connected millia mmeter indicates the selected current value. For instruments with Ex-i current output: in the 2 mA setting the minimum current of 3.6 mA is output. Terminate the test by pressing the ↵ key, and the actual measured value is again present at the current output. 8.7.4 Test of switching output Fct. 2.3.1 TEST S • In this test, the switching contact (terminals 41 and 42) can be closed or opened. • Select Function 2.3.1 as described in Sect. 8.2 and 8.3. • Press the → key. • Safety inquiry: SURE NO Select with ↑ SURE YES key • After SURE YES, press ↵ key. • Displayed: OPEN = switching contact is open. • Press the ↑ key. • Displayed: CLOSED = switching contact is closed. • Terminate the test by pressing the ↵ key, and the switching output will resume its normal operating condition. 8.7.5 Display of firmware version Fct. 2.1.3 STATUS After selecting "Module DIS" or "Module MW" after pressing the ↵ key in each case an Identity Number and an 8-digit binary number are displayed. If an undefined error occurs, please inform KROHNE Service of these values. Terminate the test by pressing the ↵ key twice. Installation and operating instructions BM 70 A/P Fct. 2.4.1 MASTER This function shows the current main firmware version (e.g. V.3.00) in the configuration menu. Fct. 2.4.2 DISPLAY This function shows the current firmware version of the display part. Page: 55 11/00 8.8 Pointers and error messages during measurement 8.8.1 Different kinds of messages a) Pointers (operating conditions) during measurement provided by 6 markers the display, see Sect. 8.8.2. in the 3rd (bottom) line of b) Application errors, indicating an application error condition in which no valid measured values are currently established. By changing the tank conditions (e.g. filling) this error can usually be remedied, see "Error list" in Sect. 8.8.3. c) Minor errors, indicating the failure of functions that usually do not affect measurement, see "Error List" in Sect. 8.8.3. d) Correctable errors, which can be remedied by operator action (manual) at the BM 70 A/P, or possibly by KROHNE Service, see "Error List" in Sect. 8.8.3. e) FATAL ERROR renders operation of the BM 70 A/P impossible; occurs only when the device is switched on (powered) or after special test functions have been executed, when the self-test identifies an error in the electronics of the BM 70 A/P, see "Error List" in Sect. 8.8.3. 8.8.2 Pointers provided by 6 markers during measurement Marker Cause No current measured value Signal too strong Explanation The device is currently searching for a new measured value in which the "measuring window" is opened. If the search for a plausible level fails, "SIGNAL DOWN" appears in the Error List, see Sect. 8.8.3. Mean of reflected microwaves is very high. Gain is automatically stepped down. Brief showing of this marker, e.g. while tank is being filled or drained, is insignificant. In conjunction with stilling wells, the marker can also show for a longer time. Poor Number of acceptable spectra is too low. Brief showing of this marker has no spectrum significance. If permanently on, this may result in uncertain (incorrect) measured values or the error message "NO M.VALUE", see Sect. 8.8.3. No measured Evaluable measured values not available after the device has been started up. value as yet Measured value automatically set to the level of the tank bottom. This marker disappears when the first valid measured value is obtained. Tank bottom In tanks with dished bottom, for example, the measuring signal can "disappear" if measurements are carried out near the bottom (within a range of 10% of the tank height, see Fct. 3.1.1, but minimum of 20 cm or 8" and maximum of 60 cm or 24"). The measured value is then automatically set to the level of the tank bottom. Measurement The digital input is active (voltage at terminals 81,82) or the device is in the frozen range of the block distance detector (see Sect. 8.6.12). Measurement is thus suspended (frozen); last measured values present at the outputs and in the display. Installation and operating instructions BM 70 A/P Page: 56 11/00 8.8.3. Error messages and their representation in display and at outputs The following list gives all error messages that can occur: Error messages Type (Sect 8.8.1) Description of error To correct device fault Text In 2nd line of display Output of errors via display and outputs, depending on setting Display ERROR MSG. Fct. 3.2.4 Current output I RANGE I Fct. 3.3.2 Switching output S FUNCTION S Fct. 3.6.1 b) NO M.VALUE Evaluable measuring signals not available If this error is displayed for a lengthy period, this could mean applicationinduced errors. Check the application conditions! yes no yes no yes OFF LEVEL DISTANCE CONVERSION REFLECTION no c) LINE INTERRUPT SWEEP LOW Power failure detected During restart following a brief power failure. Display vanishes as soon as a valid measured value is again present. Measurement continued, possibly with reduced accuracy. If error present for longer time or "VCO SWEEP" error (see below) occurs, consult KROHNE Service! If error present for longer time, this means an error on the CPU board; needs to be replaced by KROHNE Service! The current empty-tank spectrum does not match the changed operating parameters. Remedy: record new empty spectrum (Fct 3.5.2). Reset parameters for the displayed units (Fct. 3.2.2, 3.2.3). Calibration data of the current output need to be checked by KROHNE Service and reset if necessary. yes no yes no yes no yes no no no no no yes no no no no no yes no no no no no yes yes no no no no yes no yes (22 mA) no yes no Check all operating parameters and reset if necessary. If error persists: EEPROM defective. Needs to be replaced by KROHNE Service! yes yes yes (22 mA) no yes yes EEPROM defective Analog/digital converter defective Integrator defective Measuring signal too weak for evaluation Fault on microwave board Fault on microwave board EEPROM defective. Needs to be replaced by KROHNE Service! CPU board defective. Needs to be replaced by KROHNE Service! yes no yes no yes no yes no yes no yes no CPU board defective. Needs to be replaced by KROHNE Service! No measuring signal, usually caused by a defect in the electronics. yes no yes no yes no yes no yes no yes no Microwave board defective. Needs to be replaced by KROHNE Service! yes no yes no yes no Microwave board defective. Needs to be replaced by KROHNE Service! yes no yes no yes no CPU board defective After a device start-up. If still possible, invoke Error List and note down any other errors. Consult KROHNE Service! yes yes no no no no Restricted functioning of microwave board Processor monitoring WATCH DOG SPECT. ERR. Empty spectrum faulty NO DISP. Configuration faulty EEPROM error: current output calibration data EEPROM error: parameters faulty CAL. DATA CONFIG. ERR d) EEPROM ERR. ADC ERR. INTEGR. SIGNAL DOWN VCO RISE VCO SWEEP e) FATAL ERROR YES NO 4-20/2=E 4-20/22=E 4-20 ERROR OPEN ERROR CLOSED 8.8.4 Error display during measurement In the setting level under Fct. 3.2.4 ERROR MSG. (error messages), it is possible to select whether errors are to be displayed during measurement. When YES set: "error message(s)" are displayed automatically to alternate with the measured value. The errors will continue to be displayed until their cause has been eliminated. 8.8.5 Error list All errors are stored in an Error List in the BM 70 A/P. The errors are retained in this list until: 1. the cause(s) of the error(s) has been eliminated and 2. the error has been acknowledged. Errors that have been acknowledged but whose cause has not been eliminated are retained in the Error List. To invoke the Error List, press keys ↵ ↑ → →. With → you can page through the list. For further information on the Error List: see Sect. 8.3. Installation and operating instructions BM 70 A/P Page: 57 11/00 8.9 Messages on start-up When the BM 70 A/P is powered it will take about 1 minute before the first measured value is displayed (see also Sect. 5.6). During this time the following flashing messages appear in sequence in the display: STARTUP - READY - START. After a short line failure (lasting up to several minutes) it is possible that "LINE INTERRUPT" will be displayed. In such a case, measurement is continued subsequently taking into account the history prior to the interruption. 8.10 Faults and symptoms during start-up and measurement • • • You will be able to eliminate most of the faults and symptoms likely to occur with the BM 70 A/P by consulting the following chart. For easy reference, faults and symptoms are divided into the following groups: Group D Display Group A Signal output Grop DA Display and signal output Group M markers 1 - 6 in the display Group S Switching output Please go through these charts before contacting KROHNE Service. Thank you! Group D Display No. Fault / Symptom D1 Display totally "dead". D2 D3 D4 Display flashes "FATAL ERROR" shortly after power has been switched on. Display flashes "MIN VALUE" or " MAX VALUE" when numerical values are being set. Display shows "START". D5 Display flashes "SPECT.ERR.". D6 Display indicates error message alternating with the measured value. Group A Signal output No. Fault / Symptom A1 Receiver instruments connected to current output indicate "zero". A2 2 or 22 mA present at the current output. Cause Power source switched off. Primary fuse defective. BM 70 A/P is defective. The set numerical value is outside the acceptable setting range. Device carries out a hot start after a parameter change. Newly set operating parameters do not tally with the stored spectrum when e.g. the tank height (Fct. 3.1.1) and/or the antenna extension (Fct. 3.1.4) have been changed. An error has occurred. Corrective action Switch on power source. Change primary fuse as described in Sect. 9.3. Replace BM 70 A/P signal converter (instrument head) as described in Sect.7.3 . Note MIN. or MAX.VALUE displayed and set higher or lower numerical value. Wait until measured value appears. Record new empty spectrum as described in Sect. 8.6.12 (Fct. 3.5.2). Note down error messages, eliminate as described in Sect. 8.8 Cause Polarity (connection) of receiver instruments is incorrect. BM 70 A/P current output board or connected receiver instruments defective. Corrective action Connect up properly as described in Sect. 7.8. Test current output as described in Sect. 8.7.3. - All tests OK: Check receiver instruments and replace if necessary. - Test reveals faults: current output board defective; consult KROHNE Service or replace BM 70 A/P signal converter (see Sect. 7.3). "OFF" (= current output deactivated) Depending on the application, set is set under current output I, Fct. LEVEL, CONVERSION, DISTANCE 3.3.1, "FUNCTION I". or REFLECTION under Fct. 3.3.1, see Sect. 8.6.8 Invoke display of error list, see Sect. An error has occurred. 8.8. For cause and elimination, see Sect. 8.8. If error message not to be displayed via the current output, set 4-20 mA without error message, as described in Sect. 8.6.8 (Fct. 3.3.2). Installation and operating instructions BM 70 A/P Page: 58 11/00 A3 A4 The measured value at the current output is incorrect, but the measured value in the BM 70 A/P display is correct. Data Communication via the digital interface not functioning. Settings of the current output are incorrect. Set current output correctly as described in Sect. 8.6.8 (Fct.3.3.1 - 3.3.4). Communication interface set incorrectly. The computer system for Communication with the BM 70 A/P is incorrectly configured. Incorrect connection to the interface. Communication interface is defective. Set Communication interface, Sect. 8.6.9, correctly (Fct.3.3.5 - 3.3.7). Check computer system. Group DA Display and signal output No. Fault / Symptom Cause Display and current output supply Display and current output are set DA1 incorrect measured values. incorrectly. DA2 DA3 DA4 DA5 DA6 DA7 Display and current output supply a largely constant measuring error of approx. 19 cm. Display and current output supply a largely constant and large-size measuring error. Measuring error in the stilling well increases steadily in step with increasing distance. major measuring errors (> 3 cm) with Wave-Stick in the close range (up to approx. 1 m distance) When the empty tank is being filled, the measured value initially stays at "zero" and then, at 20...100 cm level, suddenly skips to the correct value. Display and signal output do not respond to changes in level. DA8 Display and signal output indicate "zero" measured value, marker 5 is ON. DA9 Display and signal output indicate max. level but tank is empty. Check connection. Consult KROHNE Service or replace BM 70 A/P instrument head as described in Sect. 7.3. Corrective action Set display (Fct. 3.2.1 -3.2.4) and current output (Fct. 3.3.1 - 3.3.4) correctly, as described in Sect. 8.6.7 and 8.6.8. Invoke Error List, see Sect. 8.8, also for cause and elimination. An error has occurred. Display and current output are, however, not set for error messages; markers 1-6 are If (also) one or several markers are perhaps ON. ON, see Sect. 8.8.2. Distance piece is provided but not Set Fct. 3.1.5 DIST.PCE. (see configured correctly. Sect.8.6.4) to 120 mm when distance piece fitted, otherwise to 0 mm. Tank height set incorrectly (level Set Fct. 3.1.1 TANKHEIGHT (see measurement). Sect.8.6.2) correctly; if possible, use automatic tank height determination, Fct. 3.5.1 (see Sect. 8.6.11) Reference offset (distance Set offset values correctly, Fct. 3.1.7 measurement) or tank bottom offset 3.1.8 (see Sect. 8.6.6). (level measurement) incorrectly progra mmed. Stilling well not included in the Set Fct. 3.1.6 STILLWELL correctly configuration. (see Sect. 8.6.5). Antenna type is incorrectly set. Set Fct. 3.1.3. ANTENNA to "WAVESTICK" (see Sect. 8.6.3) The BM 70 A/P is receiving an additional signal from the tank bottom. Activate "tank bottom tracking system", see Sect. 8.6.15 (Fct. 3.5.7 - 3.5.8) Digital input is activated, marker 6 is ON, measurement is suspended (frozen). Device is within block distance detection range, marker 6 is ON; level too high or antenna contaminated. Foaming in vessel, inadequate reflectivity of the tank product, εR too small; additionally, markers 1+3 may be ON. Tank with dished bottom: tank is more than 20% full, the BM 70 A/P is mistakenly located in the "tank bottom detection" range. Tank with dished bottom: the BM 70 A/P has stored an incorrect or incomplete empty spectrum. Deactivate the digital input, see Sect. 4.8. Installation and operating instructions BM 70 A/P Page: 59 Reduce level and/or clean antenna, or deactivate Fct. 3.5.6 BD-DETECT (see Sect. 8.6.14) or reduce size of Fct. 3.1.2 BLOCKDIST. (see Sect. 8.6.3). On tall storage tanks, mount the BM 70 A/P farther away from the tank wall. Select distance as recommended in Sect. 6.1.2. Drain tank or switch the BM 70 A/P off for a short while. If unsuccessful, please consult KROHNE Service. Record new empty tank spectrum, see Sect. 8.6.12 (Fct. 3.5.2), or enlarge block distance (Fct. 3.1.2) as described in Sect. 8.6.3. 11/00 Group DA Display and signal output No. Fault / Symptom Cause DA10 Display and signal output frequently Excessive amounts of vapour, indicate the maximum level. condensate or dust in the tank, or heavy contamination (deposits thicker than approx. 3 - 7 mm or 0.1" - 0.3") on the antenna. Antenna cleaning operations cause strong reflections. DA11 Display and signal output indicate sizeable step changes in the direction of the maximum (possibly also mimimum) level. DA12 Display and signal output indicate step changes: during filling → upwards during draining → downwards DA13 Signal output (recorder) shows sinusoidal variations about the actually measured value (deviation: up to ± 2 cm) in the upper part of the tank (approx 2 m). DA14 Display and signal output indicate constant measured values, although the level changes. DA15 Display and signal output indicate measured values at the level of the agitator blades. DA16 Display and/or signal output indicate incorrect conversion values, but level indication is correct. DA17 Display and signal output go suddenly to "zero" or block distance limit when tank continuously topped up. Corrective action Clean antenna (install cleaning device if necessary). If unsuccessful, enlarge BLOCKDIST. under Fct. 3.1.2 (see Sect. 8.6.3) or deactivate Fct. 3.5.6 BD-DETECT (see Sect.8.6.14). Activate digital input during cleaning (marker 6 is ON), measurement suspended (frozen), see Sect. 4.8. Change position of the BM 70 A/P. For Storage tank: BM 70 A/P mounted recommended distance from tank wall, centrically or on dome (manhole see Sect. 6.1.2, and note installation cover). conditions in Sect. 6.1.3! Or activate "multiple reflection identifier" under Fct. 3.5.5, see Sect. 8.6.14. Process tank with extremely Switch on tank type AGITATOR under turbulent product surface. Fct. 3.5.9, see Sect. 8.6.16. Storage tank, smooth surface, Set correct tank type (STORAGE steady filling or draining procedures, TANK) under Fct. 3.5.9, see Sect. incorrect tank type set. 8.6.16. This has physical reasons and occurs mostly with slow changes in level when sources of interference are located in the upper part of the tank. Fixed tank internals unfavourably positioned, thus permanently simulating a constant level to the BM 70 A/P. No empty spectrum recorded and/or measurements carried out without empty spectrum. Digital input is activated, marker 6 is ON, measurement is suspended (frozen). Tank with "difficult" agitator blades. Conversion table set incorrectly. Level located in range of block distance in front of antenna, see Fct. 3.1.2 in Sect. 8.6.3. Group M markers 1-6 & in display No. Fault / Symptom Cause M1 markers 1-5 (one or several) ON. Reference(s) to possible faulty measurements. M2 marker 2 ON for long periods or Note: very strong reflection signal (e.g. measurement in the stilling permanently. well). Digital input is activated, M3 marker 6 ON. measurements suspended (frozen). Device located in block distance detection range. This is a status display and not an M4 markers 3 and 4 ON. error. This usually occurs on tanks Level indicator is "zero". with dished bottom, when the tank is empty, after the BM 70 A/P has been switched on or after a new empty spectrum has been recorded. Installation and operating instructions BM 70 A/P Page: 60 Avoid all sources of interference in the upper part of the tank. A bigger antenna might help to solve the problem. Activate the empty spectrum under Fct. 3.5.2 if measurements carried out without empty spectrum. If empty spectrum not recorded, record under Fct. 3.5.2, see Sect. 8.6.12. Deactive the digital input, see Sect. 4.8 Record new empty spectrum with " MAX. VALUES" under Fct. 3.5.2. Or change position of the BM 70 A/P on the tank. Note conditions described in Sect. 6.1.2. Reset conversion table with the PCCAT program. Avoid this operating condition or, if empty spectrum (Fct. 3.5.2) is sufficiently good, reduce block distance (Fct. 3.1.2) as described in Sect.8.6.3. Corrective action See Sect. 8.8 for significance of markers and elimination of possible faults. Not important if measured value is correct. Deactivate digital input, see Sect. 4.8. Check conditions for block distance detection, see Sect. 8.6.14. Fill tank! 11/00 Group S Switching output No. Fault / Symptom S1 Switching output does not operate at the desired limit value (threshold) or does so in the wrong mode (opens/closes). S2 Switching output does not operate. Cause Setting of switching function is incorrect. Corrective action Set switching output correctly as described in Sect. 8.6.17 (Fct. 3.6.1 3.6.4). Switching output defective. Check switching output as described in Sect. 8.7.4: - Test OK: check setting and receiver instruments. - Test reveals faults: switching output defective. Consult KROHNE Service or replace BM 70 A/P signal converter as described in Sect. 7.3. 8.11 Calculation of the measured value The following describes how the individual items of information are calculated from the measured distance: tank height Fct 3.1.1 Offset BM 70 measured (internal) distance – Distance – Level Ref.Offset + Fct 3.1.7 conversion table TB Offset Fct 3.1.8 function display Fct 3.2.1 BM 70 digital communication function I output Fct 3.3.1 BM 70 local display BM 70 current output The measured primary distance is corrected by the offset and consequently standardized to the reference point ( = flange). The level is calculated as the difference between tank height and distance. Optionally, distance, level or a converted function can be output to the signal output and the local display. All items of information can be accessed via the digital Communication. In addition, the measured value can be shifted by a reference offset (reference point for distance not equal to flange) or by a tank bottom offset (reference point for level not equal to tank bottom). Installation and operating instructions BM 70 A/P Page: 61 11/00 8.12 User program PC-CAT for Windows Our instruments of the BM 70 product line are easy to install. To facilitate configuration, each unit is supplied with the intuitive and time-tried software, PC-CAT for Windows. PC-CAT provides a number of useful features including: • Quick on-site configuration • Print-out of configuration protocol • Simple conversion, volume or correction tables • Check routine to monitor functionality of the instrument • Monitoring and recording of the radar signal during operation • Trend and evaluation of the signal during operation PC-CAT works on all IBM-compatible PC’s using Windows 9x or NT. PC-CAT Version 4.00 and higher can communicate with all current KROHNE level radar gauges ® including BM 70 A/P, BM 700, BM 702 versions, also with HART protocol and RS 485. The PC-CAT kit includes a PC adapter for current output. The adapter can be connected to the PC’s standard RS 232 interface. PC-CAT allows convenient remote control of all functions of the signal converter. The vessel can be shown in schematic form together with the associated measured values and the measured spectrum. A trend graph of the output signal and threshold signal strength is also provided. All relevant instrument data can be recorded in the form of a data set small enough to be stored on a floppy disk or transfered electronically. Stored data can also be used for configuring other units of the BM 70 product line. PC-CAT files can later be used to analyse the performance of the level gauge. All graphs and screens can be exported a word processing systems or other programs. The customer’s PC containing PC-CAT is connected to the current output via the supplied Pcadapter Pcadapter, max. distance from the level gauge: 1000 m or 3300 ft. The PC adapter has no effect on in-line instruments such as milliammeters, recorders, etc., connected to the current output. Installation and operating instructions BM 70 A/P Page: 62 11/00 9 Power supply 9.1 Options, technical data A choice is offered of 2 supply power versions: Version Voltage U 24V DCAC 24 V DC 24 V AC 115/230V AC 115 V AC 230 V AC Tolerance = voltage Frequency range -25% 18-31.2 V +30% -25% 18-26.4 V 45-66 Hz +10% -25% 85-127 V 45-66 Hz +10% -25% 170-254 V 45-66 Hz +10% Power (typical) * 7.5 - 10 W 10 VA max. ripple / harmonics within limits of tolerance 10% 12 VA 10% 12 VA 10% * Hazardous-duty limit: 20W / 40 VA 9.2 Fuses Device-internal fuses for power: 24 V DCAC* 115 V AC** 230 V AC** T 1.25 A T 315 mA T 160 mA *: Terminals 1 and 2 are both fuse-protected. **: Only connection L (for TN system) is fuse-protected; optionally also both connections N and L (for IT system), see Sect. 9.3. Location of fuses on the "line" board and replacement of fuses: see Sect. 9.3. In accordance with operative regulations, it may be necessary to provide additional fuse protection when installing the system. Recommended line fuse protection: 24 V DCAC min. T 2 A 115 V AC min. T 0.5 A 230 V AC min. T 0.25 A 9.3 Changeover of operating voltage and replacement of fuses Always switch off power source before commencing work! Hazardous-duty systems: Before opening the "flameproof enclosure" (large cover on the signal converter) in the hazardous area, make absolutely certain that there is no explosion hazard. Allow the prescribed waiting time of 10 minutes to elapse first! 1. Unscrew sunshade SD, if fitted. 2. Detach safety lock SV using Allen key (size 4 mm). 3. Remove cover DE from the electronic compartment (flameproof enclosure) with the supplied special wrench. Installation and operating instructions BM 70 A/P Page: 63 11/00 4.1 Replacement of power fuse(s) Location of fuses: see drawings below. Use only the specified types. 4.2 Changeover of operating voltage (AC Version only) Through a different orientation of the voltage selector switch on the "line" board you can switch over between 115 V AC (85-127V) and 230 V AC (170-254V). For this purpose, pull the plug next to the fuse holders up and out (see drawing below), turn it 180° and plug it back into the holder. Also change the two fuses F2 and F3 to suit the selected voltage. Do not forget to alter the voltage information on the signal converter nameplate and in the terminal compartment! 4.3 Changeover between 1 fuse (TN system) and 2 fuses (IT system) (AC-Version only) Plug the blue wire on the "line" board into the desired position "TN" or "IT". Do not forget to alter the information TN or IT on the signal converter nameplate ("field power"). 5. Reassemble in reverse order, Points 3-1. Important: Ensure that the screw thread of cover DE on the electronic compartment is well greased at all times. Power supply unit 115/230 V AC Signal output 24V -5V Power supply unit 24 V DCAC +5V light-emitting diodes for voltage control light-emitting diodes for voltage control -5V +5V 24V signal output voltage selector 230V 115V T 1.25A fuse F2 fuse F3 Fuses 230V: T 160mA 115V: T 315mA F3 F4 L IT TN isolated system (IT): brown blue brown blue grounded system (TN): brown blue 9.4 Advice on safety Insulation rating The insulation of type BM 70 A/P level gauges is rated in conformity with VDE 0110/01.89, equivalent to IEC 664, and takes into account the following ratings: · Overvoltage category for the power line circuit: III · Overvoltage category for the output circuit: II · Insulation contamination level: 2 (inside the device) Disconnecting device, miniature fuse Type BM 70 A/P level gauges do not feature any device for switching or disconnection. Class of protection The BM 70 A/P level gauge is designed for Safety Class 1 in conformity with VDE 0106 Part 1. Installation and operating instructions BM 70 A/P Page: 64 11/00 24 V DCAC supply When connected to a "functional extra-low voltage with safety separation" power source (SELV or PELV) in accordance with VDE 0100, Part 410 or equivalent (inter)national regulations, connection of a safety conductor (PE) is not required. 115/230 V AC supply Connection to a power source with dangerous contact voltage: if due to protective measures in conformity with VDE 0100 a safety conductor PE is stipulated, it must be connected to the separate U-clamp terminal in the terminal compartment of the signal converter. HAZARDOUS-DUTY SYSTEMS • The incoming cables for power supply are not of intrinsically safe design, not even in the BM 70 A/P i version. • Electrical connection to be in conformity with VDE 0165, Section 5.6, or equivalent national regulations. • Before making the electrical connection, make sure all cables leading into the BM 70 A/P-Ex are disconnected from supply! • When used in hazardous locations, the BM 70 A/P-Ex must, in conformity with VDE 0165, be incorporated in the PA equipotential bonding system, irrespective of the type of power supply. If the PA is connected via a separate conductor, this must be connected to the outer U-clamp terminal on the "neck" of the BM 70 A/P-Ex. Cancellation of equipotential bonding is only permitted when the BM 70 A/P-Ex is disconnected from supply. Installation and operating instructions BM 70 A/P Page: 65 11/00 10 Certificates and approvals 10.1 Hazardous-duty approvals Country Germany/Europe Authority Certificate No. PTB PTB99 ATEX 2061X USA FM J.I.3000813 USA FM J.I.3006165 Canada Japan CSA RIIS in preparation in preparation Class EEx de IIC T6..T1 (Z.0) EEx de [ia]/[ib] IIC/IIB T6..T3 (Z.0) I Div.1 Gr.B/C/D II/III Div.1 Gr.E/F/G I/II/III Div.2 Gr. B/C/D/F/G I Div.1 Gr.B/C/D II/III Div.1 Gr.E/F/G I Div.2 Gr. A/B/C/D II/III Div.2 Gr. P/G Device type BM 70 BM 70 i BM 70 BM 70 BM 70.i BM 70.i BM 70. BM 70. The texts of valid "Ex" certificates of conformity and type approvals are reprinted in the attached "Ex" documentation. 10.2 Other approvals and certificates Type Radio approval Radio Licence Preliminary approval to German pressure vessel code DruckbehV/TRB511 (flange V 96) Installation and operating instructions BM 70 A/P Company BZT FCC Date/Certificate No. Vfg1117/1989; Vfg241/1995 JH5BM70 RWTÜV No. 5636602 Page: 66 11/00 10.3 Explosion proof acc. to ATEX The instruments BM 70 A, BM 70 P and BM 700/702 are approved according to the new hazardous area directives ATEX 100a (certificate: PTB 99 ATEX 2061X). Instruments were divided up to the following Categories according to the operating range: Probability of hazardous atmosphere Ex zone Always, long-term or frequent Occasional Not or seldom and then only short-term Zone 0 Zone 1 Zone 2 Device in (G = gas/vapour/mist) Device category 1G Device category 2G Device category 3G The marking of the BM 70 x instrument depends on the converter and the flange system: Flange system for zone 0 (1G) Flange system for zone 1 (2G) Converter with outputs in Ex-e 1/2 G 2G Converter with outputs in Ex-i 1/2 G (1)2 G Means: 1/2 G 2G (1)2 G Antenna system in zone 0 (1G), converter in zone 1 (2G) Converter as well as antenna system only in zone 1 (2G) Converter and antenna system in zone 1 (2G), but intrinsically safe current loops can go to/through zone 0 (1G) The available flange systems for BM 70 A, BM 70 P and BM 700/702 are: Construction Horn antenna or Wave-Guide (with Metaglass) Wave-Stick with flange plate and Metaglas Wave-Stick with flange plate Wave-Stick without flange plate LP flange system (horn antenna/Wave-Guide) Short term in ATEX certificate V96 Device category 1G 2) Installation in Ex zone Zone 0 WS 1C 1) 1G 2) Zone 0 WS 1B WS 2A or 2B Not in approval 2G 2G Non-Ex Zone 1 Zone 1 Non-Ex Remarks: 1) For the Wave-Stick 1C (Zone 0) any electrostatic charging of the stick must be avoided in operation (otherwise only Zone 1). 2) Zone 0 is only defined for "atmospheric conditions". Therefore in the ATEX certificate the conditions T = -20...+60 °C and p = 0.8...1.1 bar are assigned to the 1G versions for installation in Zone 0. This is not new, but now explicitly mentioned in the type test. Installation and operating instructions BM 70 A/P Page: 67 11/00 10.4 Radio approval Gazette 129, 20.11.1989 TeleCommunications Decree 1117/1989 General licence No. 353 for radio transmitting and receiving installations The installation and operation of the radio transmitting and receiving system "BM 70 Level Radar" and "BM 70-Ex Level Radar"manufactured by Firma KROHNE Messtechnik GmbH & Co. KG, 4100 Duisburg, for telecontrol purposes (level gauging in metal tanks) at a frequency in the 8.1 - 9.4 Ghz frequency range, is hereby authorized pursuant to §§ 1 and 2 of the law concerning teleCommunication systems as adopted in the official announcement dated 03.07.1989. The radio systems may only be operated inside totally enclosed metal tanks. 1. Other teleCommunication systems and teleCommunication equipment serving the public sector, including radio systems, must not suffer any interference. 2. Radio systems that are put onto the market under the above-mentioned type designations do not individually require special approval if they are electrically and mechanically consistent with the models examined and tested by the Central Approval Office for TeleCommunications (ZZF), and bear the following certification mark of the Deutsche Bundespost: "Postsignum Z G490353X" and the name of KROHNE Messtechnik GmbH & Co. KG, 4100 Duisburg, and the type designation "BM 70 Level Radar" or "BM 70-Ex Level Radar". 3. The identification mark must be embossed or engraved on the housing or on a plate made of metal or similarly strong material. The plate must be attached to the housing in such a way that it is impossible to remove or can only be removed by the use of force. The identification mark must be visible at all times from the outside. 4. The operator of such radio systems has no benefit of protection whatsoever against interference from other teleCommunication systems or teleCommunication equipment (e.g. including radio systems that are duly operated in the same frequency range). 5. The above-mentioned radio systems may not be linked to other teleCommunication systems or teleCommunication equipment without special approval from the Deutsche Bundespost. 6. This "general licence" can at any time be revoked in toto - or in isolated cases can also be revoked for individual radio systems by the relevant local licensing authority. Additional notes for manufacturer and users 1. The manufacturer of these generally licensed radio systems has the responsibility towards the Deutsche Bundespost to ensure that a reprint of this "general licence" accompanies each and every instrument brought onto the market under the above-mentioned certification mark. 2. The licence to link these radio systems with other teleCommunication systems or teleCommunication equipment is governed by the respective requirements (provisions concerning private-sector cabled teleCommunication equipment, and the teleCommunication regulations). Information in this respect is available from the appropriate teleCommunication offices (acceptance and testing service). 281-3 A 3552-2/A Bundesministerium für Post und Telekommunikation 1421 Gazette 23/95 Decree 241/1995 Extension of the general licence No. 353 for radio transmitting and receiving installations To Gazette Decree 1117/1989, page 2066 The above-mentioned general licence for radio installations issued to the company of KROHNE Messtechnik GmbH & Co. KG, 47058 Duisburg, shall with immediate effect also include radio installations that operate at a frequency in the frequency range of 8.1 - 9.9 GHz, for the same purpose are placed by the company on the market and which are marked in accordance with the general licence. At the same time, the purpose is extended to level measurements in concrete tanks having a minimum wall thickness of 19 cm. The radio installations may only be operated in fully enclosed tanks. 314-1A 3552-2/A Installation and operating instructions BM 70 A/P Page: 68 11/00 10.5 CE Manufacturer's declaration DECLARATION OF CONFORMITY We, KROHNE Messtechnik GmbH & Co.KG Ludwig - KROHNE - Straße D - 47058 Duisburg declare on our own responsibility that the products • BM 70 A/P Level-Radar 24V DC/AC - Ex-e current output / RS 485 • BM 70 A/P Level-Radar 115/230V AC - Ex-e current output / RS 485 to which this declaration refers, are in conformity with the following standards: • • • • EN 50081 - 1 : 1993 - 3 EN 50082 - 2 : 1995 - 3 pr EN 50178 : 1994 - 8 EN 61010 - 1 : 1993 - 4 in accordance with the provisions of Directives 89 / 336 / EEC und 73 / 23 / EEC. Duisburg, 01.09.1997 (Place and date of issue) (signed: Company management) Installation and operating instructions BM 70 A/P Page: 69 11/00 11 Order information Technical information relevant to the order BM 70 A/P Level-Radar ♦ Connecting flange: ................... ________________________________________________ ♦ Flange and antenna material:... ________________________________________________ ♦ Waveguide seal: ...................... Viton FFKM Kalrez2035 Other _____________ ♦ Antenna type:........................... Type 4 (200 mm) Type 3 (140 mm) ................................................ Type 1 (74 mm) Type 2 (100 mm) [for stilling well dia.: _ ] ................................................ Wave-Stick Wave-Guide (length: _______________ ) ♦ Antenna extension:................... ________________________________________________ ♦ Power supply:........................... 24V DCAC 200-240V AC 100-120V AC ♦ Signal output: ........................... Current output: active (Ex-e) Ex-i passive alternatively: ................. Digital: RS 485 Bus: __________________________ ♦ Explosion protection................. none Zone 0 Zone 1 Special items Additional calibration (BM 70 A Precision) High-precision version (BM 70 P) 90° Antenna extension ............. S-shaped antenna extension Purge connection ..................... Antenna heating Others: ____________________________________________ Installation and operating instructions BM 70 A/P Page: 70 11/00 12 External standards, codes and directives DIN V 19259: 1996-10. Documentation of devices, Data types with classsification scheme for measuring equipment with analog or digital output for industrial process measurement [in German] VDI/VDE 3519 (part 2): 1994-12. Level measurement of liquids and solids (bulk solids) [in German] DIN VDE 0165: 1991-02. Installation of electrical apparatus in hazardous areas [in German] DIN EN 50014: 2000-02. Electrical apparatus for potentially explosive atmospheres, General requirements DIN EN 50018: 1995-03. Electrical apparatus for potentially explosive atmospheres, Flameproof enclosure "d" DIN EN 50019: 1996-03. Electrical apparatus for potentially explosive atmospheres, Increased safety "e" DIN EN 50020: 1996-04. Electrical apparatus for potentially explosive atmospheres, Intrinsic safety "i" DIN EN 50284: 2000-02. Special requirements for construction, test and marking of electrical apparatus of equipment group II, category 1 G DIN EN 50081-1 (VDE 0839 part 81-1): 1993-03. Electromagnetic compatibility (EMC), Generic emission standard, Part 1: Residential, commercial and light industry EN 50082-2: 1995-03. Electromagnetic compatibility, Generic immunity standard, Part 2: Industrial environment NE 21 NAMUR recommendation „Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment“, 1998-08 DIN EN 61010-1 (VDE 0411 part 1):1993-04. Safety requirements for electrical equipment for measurement, control and laboratory use, general requirements pr EN 50178 / DIN EN 50178: 1994-08: Electronic equipment for use in power installations Directive 89/336/EWG (CE marking) DIN EN 60068-2 (IEC 68-2): 1995-03. Environmental tests DIN IEC 68-2-6: 1990-06. Electrical engineering, Basic environmental test procedures DIN EN 60654, part 1 (IEC 654-1): 1994-02: Industrial process measurement and control equipment; Operating conditions; Climatic Conditions DIN EN 60529: 2000-09: Degrees of protection by enclosures (IP Code) DIN 2501: 1972-02: Flanges - Fitting dimensions [in German] DIN 2527: 1972-04: Blind flanges [in German] ANSI B 16.5: 1988: Pipe Flanges and Flanged Fittings DIN 11851: 1998-11: Fittings for food, chemical and pharmaceutical industry - Stainless steel screwed pipe connections - Design for rolling in and welding-on DIN EN 10088, Teil 1: 1995-08: Stainless steels - Catalogue of the stainless steels DIN 55990: 1979-12: Verification of paints and similar coating materials; Powder mould coatings .... [in German] HUG-3: HART FSK Physical Layer Specification Rev. 7.2: 1993-05 13 Quality assurance KROHNE Messtechnik GmbH & Co. KG is certified to: • DIN ISO 9001 / EN 29001 and • KTA 1401 QSP 4A (nuclear power engineering) Installation and operating instructions BM 70 A/P Page: 71 11/00 Annex A: Technical data Range of application Distance, level, volume and reflection measurement of liquids, pastes, slurries, solids and particulate material on storage and process tanks or containers made of metal or concrete, and also in stilling wells Mode of operation / system structure FMCW-Radar in the X-Band (8.5-9.9 GHz) with digital signal processing; compact device, modular design Input Measured variable Measuring range Block distance Rate of change in level Output Variant 1 ® Ex-e current output HART with switching output: and digital input: Variant 2 ® Ex-i current output HART with optional switching output: Variant 3 RS 485 interface with additional current output Variant 4: PROFIBUS-PA (Ex-i) Hardware Physical Bus characteristics Base current Default current Variant 5: Foundation Fieldbus (FF) Breakdown signal 6.1 6.2 Measuring accuracy Error of measurement Repeatability Measured-value resolution Effect of ambient temperature Operating conditions Installation conditions Ambient conditions Hazardous locations Ambient temperature at signal converter Flange temperature Primary variables: distance, reflection; derived variables: level, volume Min. tank height: 0.5 m max. measuring range: 40 m (optionally upto 100m); Wave-Stick: 20 m, BM 70 P = 35m Min. 0.2 to 1.0 m; see Sect. 3.3 ≤ 10 m/min; BM 70 P ≤ 1m/min Type Current range Accuracy/linearity Temperature drift Load impedance active (current source); Ex-e 4-20 mA (error: 2 mA or 22 mA) 0.05 % (rel. 20 mA; 25°C) ≤ 100 ppm/K (typically 30 ppm/K) ≤ 500 Ω max. 100 mA / 30 V DC or 30 V AC; internal resistance ≤ 20 Ω; potentialfree to "freeze" the measured value; voltage: 5 to 28 V DC; input resistance: ≥ 1 k Ω; potential-free Type passive (current sink); Ex-i Current range 4-20 mA (error 3.6 or 22 mA); ® 4 mA constant for HART -Multidrop ≤ 100 ppm/K (typically 30 ppm/K) Temperature drift Accuracy/linearity 0.05 % (rel. 20 mA; 25°C) Supply voltage 8-30 V (terminals 31 and 32) Load impedance ≤ (US - 8 V) / 22 mA, (US = external supply voltage) 6 ... 30 V; I Low ≤ 2 V; I High ≤ 900 µA (U = 30 V), I High = 200 µA (U = 8 V) Transmission rate 1200 to 38400 bauds Address: 0 to 255 Protocols: KROHNE Protocol, ® Modbus-RTU, HART active (current source); not communicable; Type Ex-e 4-20 mA (error 2 mA or 22 mA) Current range 0.3 % (rel. 20 mA; 25°C) Accuracy/linearity Temperature drift ≤ 200 ppm/K (typically 70 ppm/K) Load impedance ≤ 250 Ω When operated as switching Low: I < 2 mA; High: I = 22 mA output: (R ≤ 250 Ω) and no-load voltage ≤ 18 V to IEC 61 158-2 and the FISCO model 9 ... 30 V; 0.3 mA max.; 4.2 W max. 10 mA 6 mA see Supplementary Instructions Current output: error signal 2/22 mA or 3.6 mA (Ex-i), plain text in local display Switching contact: opening or closing of the contact Digital interfaces: error flags Reference conditions and error curves: see Sect. 5.1 and 5.2 ≤ 0.5 × error of measurement BM 70 A: 1 mm; BM 70 P: 0.1 mm No significant effect on measured value(- 1 ppm/°C); (see also signal outputs) Avoid interference reflections and multiple reflections BM 70 A/P Ex: Zone 0,1,2; IIC/IIB, T6...T2 Functional range: Horn antenna, Wave-Guide (Tamb ≤ 50°C/122°F): Installation and operating instructions BM 70 A/P Page: 72 -20...+55°C (-24...+131°F) -40...+70°C (-40...+158°F) -30...+130°C (-22...+266°F) 11/00 Horn antenna, Wave-Guide (Tamb ≤ 55°C/131°F): High-temperature version with: - FFKM gasket (Kalrez 4079/Parofluor V8545-75): - Kalrez 2035 gasket: - Viton gasket: - FEP-sheathed gasket: Wave-Stick: Environment class Protection category Shock resistance Vibration endurance limit EMC 6.3 -30...+120°C (-22...+248°F) -30...+250°C (-22...+482°F) (safety limit 280°C/536°F) -30...+210°C (-22...+410°F) -30...+200°C (-22...+392°F) -30...+200°C (-22...+392°F) -20...+100°C (-4...+212°F) pressure-dependent up to +150°C/302°F Locations exposed direct to open-air climate, D1 Severity in conformity with EN 60654-1 (signal converter) IP 66 / IP 67 Impact test to EN 61010, Sect. 8.2 with 0.5 J energy; drop test to prEN 50178 IEC 68-2-6 and prEN 50178 (10-57Hz:0.075 mm/57-150 Hz:1 g) EN 50081-1, EN 50082-2; NAMUR Recommendation Product conditions Relative permittivity No effect on measurement results; to ensure reliable measurements, the relative permittivity should have the following minimum values: εr > 1.5; εr < 3: stilling well recommended; Wave-Stick immersed: εr > 4 Limitations Liquid a mmonia (NH3); liquid hydrogen (H2); liquid helium (He) Temperature of product Operating pressure Horn antenna/Wave-Guide unrestricted (but be aware of ambient and flange temperatures) Physical properties Wave-Stick dependent on flange size and pressure rating (see Table) Standard: max. 64 bar (higher on request) bar psig +16 232 (46 - 0.3·T[°C]) bar (740 - 2.4·T[°F]) psig Pressure +1 +15 -1 -15 -20 -4 Component parts Dimensions and weights Materials Housing: signal converter Flange system, antenna, extension Gaskets Wave-Stick Process connection Horn antenna/Wave-Guide Wave-Stick Dairy screw connection Tri-Clamp connection Electrical connection User interface Keypad Magnetic sensors Local display User language Units of measurement Power supply 24 V DCAC 115/230 V AC Power consumption Temperature T +100 +212 +150 °C +302 °F see Sect. 7.2 Aluminium with electrostatic powder coating; sight window: glass Stainless steel 1.4571 or 1.4435, Hastelloy C4 or B2, titanium, tantalum; (other materials on request) FFKM (Kalrez 4079 or Parofluor V8545-75); Kalrez 2035; Viton (FPM); FEPsheathed (basically, all versions include PTFE as the material in contact with the product) only PTFE in contact with product; flange made of 1.4571 (316 Ti) DIN 2501 / DIN 2526, Form C DN 50 … DN 200 / PN 6 … PN 64; ANSI B 16.5 2‘‘ … 8‘‘, Class 150/300 lb/RF; DIN 2501 / DIN 2526, Form C DN 50 … 150; ANSI B 16.5 2‘‘ … 6‘‘; DIN 11 851 DN 50, DN 65, DN 80 SMS 1145 51 mm, 63 mm, 76 mm ISO 2852 2‘‘ … 4‘‘ Cable entries: 3x M25×1,5 Terminals: 0.5-2.5 mm² (solid conductor: max. 4 mm²) PE or FE and PA: U-clamp terminal (max. 4 mm²) Shielding for RS 485 cable and for current output cable > 100 m 3 keys operation with magnetic pin without opening the housing 2-line illuminated LCD + 6 status markers German, English, French, Italian, Spanish, Portuguese, Swedish Length: m, cm, mm, inch, ft, % Volume: m³, Liter, US Gal, GB Gal, ft3, bbl, % Conversion unit: any text 18-31.2 V DC or 18-26.4 V AC (45-66 Hz) optionally: 100-120 V AC (tolerance: 85-127V), 200-240 V AC (tolerance: 170-254V); 45-66 Hz Typically 7.5 - 10 W / 12 VA Installation and operating instructions BM 70 A/P Page: 73 11/00 Annex B: Type code / nameplates Type code See nameplate on signal converter and flange system (places not needed in the type code may be omitted): BM70 . . / . / . - E Ex 2 3 4 5 1: 2: Tank level gauge Signal converter series 70A : Advanced 70P : Precision 700 : Low Cost 702 : 2-wire 3: Symbol for type of protection for the signal outputs : intrinsically safe I/O function unassigned : non intrinsically safe I/O function 4: Symbol for type of protection for the terminal compartment : terminal compartment in Increased Safety “e“ (standard) : terminal compartment as Flameproof Enclosure “d“ (option) unassigned : intrinsically “ia“ (BM 702) 5: Ambient temperature range : Extended range –40°C ... +55°C unassigned : Standard range –20°C ... +55°C 6: Territory of application for explosion protection certification : Europe (EG, CENELEC) 7: Safety function Ex : explosion-protected electrical equipment Kennzeichnung des Flanschsystems (siehe Flansch-Datenschild): ..(1).. ..(2).. ....(3)...... nicht-explosionsgeschützte Ausführung ..(1).. ..(2).. ....(3)...... – E Ex ..(4).. explosionsgeschützte Ausführung (1) Flange system series V96 : Flange system V96 WS : Flange system Wav-Stick EA : Enamel antenna system LP : LP flange system (2) Material of waveguide window unassigned : standard (stainless steel) : Hastelloy window (T min = -60°C) (3) Materials of wetted parts - Flange system V96: » Antennas and flanges, including coating: SS : stainless steel HB : Hastelly B HC : Hastelloy C Ti : Titanium Ta : Tantalum Mo : Monel » Gasket materials: FFKM : Kalrez™ 4079 or Parofluor™ V8545-75 K2035 : Kalrez™ 2035 K1091 : Kalrez™ 1091 FPM : Viton™ FEP : FEP-sheathed gasket Installation and operating instructions BM 70 A/P Page: 74 11/00 - Flange system WS LPTFE : PTFE conductive PTFE : PTFE non-conductive SS PTFE : stainless steel / PTFE non-conductive SS PP : stainless steel / PP non-conductive - Flange system EA EM PTFE : Enamel + PTFE (4) Field of application, Device Group II 1G : Category 1G (application in Zone 0) 2G : Category 1G (application in Zone 0) Informationen on nameplates (example) Signal converter: Manufacturer Version European conformity Type acc. to type code 0102 Sales order number Firmware version no. Serial number Year of manufacture Certification information Inscription as requestes by customer 2061 99 II (1) 2G Radio approval Power supply Voltage with tolerances Type, terminal marking and connection data of the intrinsically safe signal outputs Safety information Flange system: Year of manufacture Baujahr Hersteller Manufacturer Type acc. to dem Typ gemäß type code Typenschlüssel Seriennummer Serial number Operating/test Betriebspressure / Prüfdruck 99 2061 Operating temperature Betriebstemperatur Inscription as nach requestedby customer Beschriftung Kundenwunsch Installation and operating instructions BM 70 A/P Page: 75 11/00 Sanitary connection / G 1 ½“ thread: Operating temperature Operating/test pressure Year of manufacture Serial number Type acc. to Type code Manufacturer Approval information Attention! When mounting the G 1½" screw connection you have to take care that the marking on the wrench faces will not be damaged (do not use pipe wrench!) Operating/test pressure Manufacturer Betriebs-/Prüfdruck Operating temperature Hersteller Year of manufacture Betriebstemperatur Baujahr Beschriftung nach Inscription as requested by Kundenwunsch customer Typ gemäß Type acc. to dem type code Typenschlüssel Approval information Zulassungsinformation Serial number Seriennummer Installation and operating instructions BM 70 A/P Page: 76 11/00 Annex C: Spare parts Installation and operating instructions BM 70 A/P Page: 77 11/00 Installation and operating instructions BM 70 A/P Page: 78 11/00 Installation and operating instructions BM 70 A/P Page: 79 11/00 Annex D: Signed declaration to accompany a device returned to KROHNE If you need to return level gauges for testing or repair to KROHNE If installed and operated in accordance with these operating instructions, your level gauge will rarely present any problems. Should you nevertheless need to return a device for checkout or repair, please pay strict attention to the following points. Due to statutory regulations concerning protection of the environment and the health and safety of our personnel, KROHNE may only handle, test and repair returned level gauges that have been in contact with liquids if it is possible to do so without risk to personnel and environment. This means that KROHNE can only service your unit if it is accompanied by a certificate in line with the following model confirming that the device is safe to handle. If the unit has been operated with toxic, caustic, flammable or water-endangering liquids, you are kindly requested • • to check and ensure, if necessary by rinsing or neutralizing, that all cavities are free from such dangerous substances, to enclose a certificate with the level gauge confirming that it is safe to handle and stating the liquid used. KROHNE regret that they cannot service your level gauge unless it is accompanied by such a certificate. S P E C I M E N certificate Company: ............................................................ Address: ................................................................. Department: ....................................................... Name: ............................................................ Tel. No.: .................................................................. The enclosed level gauge BM70A/P: ................................................ KROHNE Order No. or Series No.: .................................. has been operated with the following liquid ....................................................................................................... Because this liquid is water-endangering * / toxic * / caustic * / flammable * we have - checked that all cavities in the unit are free from such substances * - flushed out and neutralized all cavities in the unit * (* delete where not applicable) We confirm that there is no risk to man or environment through any residual liquid contained in this level gauge. Date: ...................................................... Signature: ................................................... Company stamp: Installation and operating instructions BM 70 A/P Page: 80 11/00 Annex E: Table on documentation of device configuration CHECK LIST PARAMETERS BM 70 A/P.Vers.:.............. Date: ............... Device No. ..................................................: Comm. No.... :....................... ........................ Location......................................................: ...................... ........................ ........................ Contact person...........................................: Telephone.... ........................ : ....................... Remarks :................................................... ....................... ........................ ........................ ........................................................ ....................... ........................ ........................ Menu item....................................................Changed on .... :....................... :.......................: Fct. Configuration parameters (excerpt) 3.1.1 Tank height ....................................: ...................... :....................... :.......................: 3.1.2 Block distance ...............................: ...................... :....................... :.......................: 3.1.3 Antenna ..........................................: ...................... :....................... :.......................: 3.1.4 Antenna extension.........................: ...................... :....................... :.......................: 3.1.5 Distance piece ...............................: ...................... :....................... :.......................: 3.1.6 Still well / diameter ........................: ...................... :....................... :.......................: 3.1.7 Offset, reference ............................: ...................... :....................... :.......................: 3.1.8 Offset, tank bottom........................: ...................... :....................... :.......................: 3.3.1 Current output, function ...............: ...................... :....................... :.......................: 3.3.2 Current output, range/error...........: ...................... :....................... :.......................: 3.3.3 Min. scale for current ....................: ...................... :....................... :.......................: 3.3.4 max. scale for current....................: ...................... :....................... :.......................: 3.3.5 Baud rate........................................: ...................... :....................... :.......................: 3.3.6 Address ..........................................: ...................... :....................... :.......................: 3.3.7 Protocol..........................................: ...................... :....................... :.......................: 3.5.2 Empty-tank spectrum ....................: ...................... :....................... :.......................: 3.5.3 Time constant ................................: ...................... :....................... :.......................: 3.5.4 Tracking speed ..............................: ...................... :....................... :.......................: 3.5.5 Multiple reflections (Yes/No) .........: ...................... :....................... :.......................: 3.5.6 Block distance detect.(Yes/No) .....: ...................... :....................... :.......................: 3.5.7 Function FTB .................................: ...................... :....................... :.......................: 3.5.8 Epsilon-R .......................................: ...................... :....................... :.......................: 3.5.9 Tank type .......................................: ...................... :....................... :.......................: 3.6.1 Switching output, function ...........: ...................... :....................... :.......................: 3.6.2 Switching output, limit type..........: ...................... :....................... :.......................: 3.6.3 Switching output, threshold .........: ...................... :....................... :.......................: 3.6.4 Switching output, hysteresis ........: ...................... :....................... :.......................: Installation and operating instructions BM 70 A/P Page: 81 11/00 Annex F: Index Address Agitator Ambient temperature Antenna extension Antenna size Antenna type Application range Approvals Assembly Baud rate Block distance Block distance detection BM 70 A Precision Breakdown information Cable entries Configuration Configuration menu Connecting cable Connection diagrams Conversion table Cooling device Current output Curved extension Cylindrical tank Device configuration Digital Communication Digital input Dimensions Display Distance piece Documentation Electrical connection EMC Empty (-tank) spectrum Environment class Error Error message Error of measurement Firmware version Flameproof enclosure Flanges Flange system Flange temperature FMCW-Radar Foundation Fieldbus (FF) Freeze Frequency sweep FTB Functional checks Functional ground Fuses Gaskets HART® Hazardous-duty "Ex" 4.6, 8.6.9 7.5, 8.6.16 5.8, 6.2.2 6.1.3, 7.4, 8.6.3 5.2, 6.1.4, 7.2, 7.5 8.6.3 6, 10 7.4 4.6, 8.6.9 3.3, 8.6.3 3.4, 8.6.14 5.2 4.7 7.8 8.4, 8.5, 8.6, Annex E 8.3, 8.4 7.8 7.8 8.5.2, 8.6 6.1.7 4.2, 4.3, 4.5, 7.8, 8.6.8, 8.7.8 6.1.6, 8.6.3, 8.6.4 6.1.2 8.4, 8.6, Annex E 4.1, 4.6, 8.6.9 4.2, 4.8 7.2 8.1, 8.6.7 6.2.3, 7.4, 8.6.2 Page 3 7.8 6.2.10, 10.5 8.6.12 6.2.6 8.6.7, 8.6.8, 8.6.17, 8.8 4.7, 8.6.17, 8.8.3 5.2 page 4, 8.7.5 7, 9.3 7.2; 7.4 2.3, 7.4 6.2.3 2.1 4.1, 8.6.9 4.8 2.1 8.6.15 8.7 7.8 9.2, 9.3 6.2.3, 7.6.3 4,1, 4.4 6, 6.2.1, 7, 9.3, 10 Heating device 6.1.7 High-temperature version 6.2.3, 7.2, 7.4, 7.8, 10.3 Horn antenna 3.3, 6.1.2, 6.1.3, 6.3.5, 7.2 Hot start 4.2, 4.8 Hysteresis 5.4, 8.6.17 Impact resistance 6.2.8 Installation 6.1 Insulation 9.4 Interference 4.8, 8.10 Internals 6.1.2, 6.1.6, 8.6.12 Intrinsic safety 4.3, 7, 7.8 IT system 9.2, 9.3 Keys 8.1, 8.2 KROHNE Protocol 4.6, 8.6.9 Language of display texts 8.6.10 Load impedance 4.2, 4.3, 4.5 Local display 8.1 Long-term drift 5.7 magnetic sensors 8.1 maintenance 6.4 manhole cover 6.1.2 markers 4.8, 8.1, 8.8.2 materials of construction 7.6 Measured value, calculation of 8.11 Measured value, resolution of 5.4 Measured variables 3.1 Measurement principle 2.1 Measuring accuracy Measuring range 3.2 ModBus 4.1, 8.6.9 Modularity 2.3, 4.1 Multidrop 4.1, 4.4 Multiple reflections 8.6.14 Nameplate Annex B Operating pressure 6.3.5 Operating voltage 9.1, 9.3 Operating voltage, changeover of 9.3 Operator control concept 8.3 Order information 11 Order numbers Annex C Out-of-range performance 3.4 Output Parameter setting, see Configuration PC-CAT 8.12 Point-to-point 4.1, 4.4 Positioning 6.1.2 Post Office /Radio approvals 10 Power supply Pressure separation 2.3 Product conditions 6.3 Product temperature 6.3.4, 10.3 Profibus 8.6.9 Protection category 6.2.1, 6.2.7, 7 Installation and operating instructions BM 70 A/P Page: 82 11/00 Protocol Purging device Quality assurance Reference conditions Reference offset Reflection Rel. Permittivity Repeatability Replacement of signal converter Returning the device RS 485 Safety conductor Safety lock Safety, advice on Setting, see Configuration Shielding strip Side vessels Signal converter Signal output Signal processing Software history Spare parts Spectrum Standards Stilling well 8.6.5 Storage temperature Sunshade Supply scope Supply voltage Switching output Tag name Tank bottom offset Tank bottom tracking Tank fitting Tank height Tank type Tank wall Technical data Temperature Temperature drift Terminals Terminating resistor Test functions Threshold Time constant TN system Tracking speed Transient recovery time Transmission angle Transport Turn-on characteristics Type code Units Vessel, see Tank Vibration endurance limit 8.6.9 6.1.7 13 5.1 8.6.6 3.1, 8.6.1 6.3.2 5.3 2.3, 7.3 Annex D 4.1, 4.6, 8.6.9 9.4 9.3 Page 3, 6, 9.4 Volume measurement Warranty Wave-Guide Wave-Stick Weight 3.1, 8.5.2 Page 3 6.1.2, 6.1.5, 7.1 3.3, 6.1.3, 7.1, 7.2, 7.5 7.2 6.1.8 6.1.2 7.6.1, 2.3, 7.4 4, 5.8 2.2 page 4 Annex C 2.2, 8.6.12 12 3.3, 6.1.4, 6.1.2, 6.2.5 6.1.9, 6.2.2 Page 3 4.3 4.2, 7.8, 8.6.17 8.6.10 8.6.6 8.6.15 6.1.3, 6.1.8 3.2, 8.5, 8.6.2, 8.6.11 8.6.16 6.1.2 9.1, Annex A 5.8, 6.2.2, 6.2.3, 6.2.4, 6.2.5, 6.3.4, 10.3 5.8 7.8 7.9 8.7.1 8.6.17 5.5, 8.6.13 9.2 8.6.13 5.5 6.1.1 Page 3 5.6 Annex B 8.6.1 6.2.9 Installation and operating instructions BM 70 A/P Page: 83 11/00
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : No Create Date : 2002:04:16 11:37:50-04:00 Modify Date : 2002:04:16 11:37:50-04:00 Page Count : 83 Creation Date : 2002:04:16 15:37:50Z Mod Date : 2002:04:16 15:37:50Z Producer : Acrobat Distiller 5.0 (Windows) Author : Barry Quinlan Metadata Date : 2002:04:16 15:37:50Z Creator : Barry Quinlan Title : JH5-70 - Manual.pdfEXIF Metadata provided by EXIF.tools