Kamstrup A S FLOW2102 Water Flow Meter User Manual UserMan b

Kamstrup A/S Water Flow Meter UserMan b

Contents

UserMan b

Download: Kamstrup A S FLOW2102 Water Flow Meter User Manual UserMan b
Mirror Download [FCC.gov]Kamstrup A S FLOW2102 Water Flow Meter User Manual UserMan b
Document ID2655007
Application ID6OyjGuxCRaSx9P9XHQFpiQ==
Document DescriptionUserMan b
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize114.68kB (1433504 bits)
Date Submitted2015-06-23 00:00:00
Date Available2015-06-23 00:00:00
Creation Date2015-06-02 12:19:14
Producing SoftwareAdobe PDF Library 11.0
Document Lastmod2015-06-02 12:19:42
Document TitleUserMan b
Document CreatorAdobe InDesign CC 2014 (Windows)

Optical eye for reading and configuration
Optional customer label,
e.g. water company logo (15 x38 mm)
Graphical flow indicator
Bar code with serial number
Type number
(includes information on meter size,
Serial number and production year
Configuration
(with information on display resolution
Expiry year of battery
Temperature class according to OIML R49
flowIQ® 3100
Meter size Q3
FCC ID: OUY-FLOW2102
Pressure stage and protection class
Accuracy class 2 according to OIML R49
Environment class: Electrical E2 and Mechanical M1
Environment class B and C according to OIML R49
(indoors/outdoors)
The sealing surface
of the threaded
connection must be
clean and level
Software version and dynamic range
FCC identification
FCC Cautions
Caution: Changes or modifications not expressly approved
by the party responsible for compliance could void the user’s
authority to operate the equipment.
RF Exposure compliance statement: This device may be used
with no restrictions, since the source-based time-averaged
output power is ≤ 60/f(GHz) mW.
ALWAYS use new gaskets.
The piping must be parallel and fit the meter.
flowIQ® 3100
draft3100-5512XXXX_A1_GB_CL_06.2015
Installation guide
1. General information
If meters are mounted in meter wells or outdoors, both the meter
well and the meter must be protected against freezing.
Read this guide before installing the water meter.
flowIQ® 3100 is a compact electronic water meter used for water
consumption measurement in the tap water supply of homes,
commercial and industrial buildings. The meter is watertight and
thus well suited for mounting in small pump stations and meter
wells, which are frequently filled with water. flowIQ® 3100 has
been constructed for maintenance-free operation for up to 16
years.
flowIQ® 3100 is hermetically closed and it is, therefore, not
possible to service the meter without breaking the seal. This
means that all service including battery change, must be carried
out by an authorized Kamstrup Service Centre.
Certain changes of configuration, however, are possible via
the built-in optical eye without dismounting the meter from
the installation. Further details appear from data sheet and
technical description.
Threaded meters, sizes 4.0, 6.3 and 10.0 m3/h 		
– of the flowIQ® 3100 series – are prepared for mounting of
a coarse-mesh strainer (filter) in the meter inlet connection.
Furthermore, a nonreturn valve can be mounted in the meter
outlet connection.
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) this device may not cause harmful interference, and
(2) this device must accept any interference received,
including interference that may cause undesired operation.
Service
When the meter has been mounted in the system neither
welding nor freezing is allowed. Dismount the meter from the
system before starting such work.
In order to facilitate replacement of the meter, closing valves
should be mounted on either side of the meter.
Under normal operating conditions no pipe strainer is required
in front of the meter. Nonreturn valves must be mounted in
accordance with local regulations.
1.3 Installation angle of flowIQ® 3100
flowIQ® 3100 can be mounted at all angles and positions.
Kamstrup A/S recommend that the display is mounted so that it
is easy to read, if possible.
Thus, the meter can be mounted in a usual horizontal
installation. It can be mounted vertically on an ascending pipe,
it can be mounted at any angle and it can be mounted with its
display pointing downwards, e.g under a roof.
1.6 Info codes and display
When flowIQ® 3100 leaves Kamstrup A/S, it has been tested and
verified and the counter has been reset.
m3 are displayed by five large digits. The small digits after the
dot are decimals.
A number of info codes can be displayed, of which ‘DRY’ and
‘RADIO OFF’ will be activated and will flash upon delivery.
Furthermore, the two small squares in the bottom right-hand
corner will flash to indicate that the meter is active.
Info code ‘DRY’ indicates that there is air in the meter. The info
code disappears when the meter is water-filled. As long as the
meter is not water-filled nothing is measured. Blowing through
the meter with air does not influence the meter either.
The info code ‘RADIO OFF’ indicates that the meter is still in
transport mode with the built-in radio transmitter turned off. The
transmitter turns on automatically when the first liter of water
has run through the meter. The radio transmitter remains on,
and the info code signal in the display switches off.
The flow arrows in the left side of the display indicate water flow
through the meter. If the water is stagnant, all arrows will be off.
The table below describes the different info codes in the display.
1.1 Permissible operating conditions / measuring
ranges
Temperature of medium
water meter:
Pressure stage:
Mechanical environment:
Electromagnetic
environmental class:
Protection class:
Climatic environment:
0.1°C...50°C
PN16
M1 (MID) Fixed installation with
minimum vibration.
E1 and E2 (MID).
Housing and trade.
IP68
2°C...55°C. Condensing humidity.
(indoors mounted in utility rooms
and outdoors in meter wells).
Installation in direct sunlight ought
to be avoided.
Recommended water meter position.
Recommended water meter position.
Used for "well installation". Air build-up may occur.
The meter functions optimally, but the display is "upside
down".
1.2 Installation requirements
1.4 Straight inlet
Prior to installation of flowIQ® 3100 the system should be
flushed while a fitting piece replaces the meter.
Please check that stop valves are tight and operate as intended
and that the pipe system is without corrosion and damages.
Damaged components, if any, must be replaced.
Close the main stop valve in front of the meter and let a tap
run until the pressure in the system has been equalized. Close
the stop valve after the meter before disassembling the pipe
system.
Having assembled the pipe system, all sealing surfaces
of existing couplings must be cleaned to remove possible
remaining pieces of gasket. Remove adhesive wafers from the
meter’s inlet and outlet and mount the meter. Always use new
gaskets in original quality.
flowIQ® 3100 requires neither straight inlet nor straight outlet
to meet the Measuring Instruments Directive (MID) 2004/22/EC
and OIML R49. A straight inlet section will only be necessary in
case of heavy flow disturbances before the meter.
Info code
flashes in display
Meaning
LEAK
During the latest 24 hours the water in
the meter has not been stagnant for
minimum one continuous hour.
This can indicate a leakage in the pipe
system.
The water flow has exceeded a
preprogrammed limit for minimum
30 minutes which is a sign of a burst
pipe.
Tampering attempt. The meter is no
longer valid for billing purposes.
The meter is not water-filled.
The water flows in the wrong direction
through the meter.
The meter is still in transport mode
with the built-in radio transmitter
turned off. The transmitter turns on
automatically when the first litre of
water has run through the meter.
Two small squares that flash
alternately indicate that the meter is
active.
1.5 Operating pressure
In order to avoid cavitation and secure correct measurement
under all conditions, the operating pressure in the pipe system
must observe the test conditions of OIML R49, which means that
the static pressure immediately after the meter (downstream)
must always be minimum 0.03 MPa (0.3 bar).
BURST
Ul
tra
TAMPER
Wa
nic
so
DRY ter
REVERSE
er
et
The flow direction is indicated by an arrow on the side of the
meter. Install the meter with an orientation that makes it easy
for the consumer to read the display.
The figure after the ‘A’ indicates how many times the meter has
been adjusted or reset. In a completely new meter both of these
indicators will be switched off.
Laboratories which have reverified and adjusted or reset
the meter, shall attach a label with information on the valid
adjustment number to the meter.
63123456RADIO OFF
At the same time make sure that the threaded length of the
couplings does not prevent proper tightening of the sealing
surface and that PN10 or PN16 couplings are used.
2023
63123456
During installation it must be secured that the meter is mounted
without mechanical bias in the connection pipes. Do not attempt
to correct oblique piping by means of the meter.
(two square ‘dots’)
MULTICAL® 21
Type:
S/N:
Con:
Class:
02166A0A819
63123456/2011
010600002313
2 (E2, M1)(B/C)
T50: 0.1°C...50°C
Q3:
1.6 m3/h
Q3/Q1: 100/1, SW:E1
PN16, PS16 – IP68

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.6-c014 79.156797, 2014/08/20-09:53:02
Create Date                     : 2015:06:02 12:19:14+02:00
Metadata Date                   : 2015:06:02 12:19:42+02:00
Modify Date                     : 2015:06:02 12:19:42+02:00
Creator Tool                    : Adobe InDesign CC 2014 (Windows)
Instance ID                     : uuid:efe86215-d6b8-43c6-b709-dbbde1fb7f37
Original Document ID            : xmp.did:CE01E6A1DFEFE0118D6AC478EE4E4D07
Document ID                     : xmp.id:8b556104-46f4-8a45-9e40-4c7f6e699c9c
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:af855414-3686-fa49-aed0-4c82942742b8
Derived From Document ID        : xmp.did:a2b3462b-c106-6043-88fc-f052d2a6ebd5
Derived From Original Document ID: xmp.did:CE01E6A1DFEFE0118D6AC478EE4E4D07
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CC 2014 (Windows)
History Changed                 : /
History When                    : 2015:06:02 12:19:14+02:00
Format                          : application/pdf
Producer                        : Adobe PDF Library 11.0
Trapped                         : False
Page Count                      : 2
Creator                         : Adobe InDesign CC 2014 (Windows)
EXIF Metadata provided by EXIF.tools
FCC ID Filing: OUY-FLOW2102