Kenmore 867736349 User Manual SEARS GAS FIRED FORCED AIR WALL FURNACE Manuals And Guides L0904199

KENMORE Furnace/Heater, Gas Manual L0904199 KENMORE Furnace/Heater, Gas Owner's Manual, KENMORE Furnace/Heater, Gas installation guides

User Manual: Kenmore 867736349 867736349 KENMORE SEARS GAS-FIRED FORCED AIR WALL FURNACE - Manuals and Guides View the owners manual for your KENMORE SEARS GAS-FIRED FORCED AIR WALL FURNACE #867736349. Home:Heating & Cooling Parts:Kenmore Parts:Kenmore SEARS GAS-FIRED FORCED AIR WALL FURNACE Manual

Open the PDF directly: View PDF PDF.
Page Count: 29

Sears GAS.FIRED
FORCED AIR
WALL FURNACE
@
.Installation
.Operation
Repair Parts
FOR YOUR SAFETY FOR YOUR SAFETY
Do not store or use gasoline or
other flammable vapors and liquids in
the vicinity of this or any other
appliance.
If you smell gas:
1. Open windows.
2. Don't touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
Sears, Roebuck and Co., Chicago, II. 60684 U.S.A.
PRINTED IN U.S.A.
Contents
Introduction ................................... 2
Sears Warranty ................................ 2
Sears Installation Policy ........................ 2
Sears Installation Warranty ..................... 2
safety Rules ................................. 2-3
Basic Tools Needed ............................ 3
Basic Materials ................................ 3
Optional Accessories ........................... 4
Furnace Data .................................. 4
Unpack Your Furnace .......................... 4
Installation Steps .............................. 5
Locating Furnace .............................. 5
Combustion Air .............................. ; .5
_'-*_l I IIIIIIIIIIIIIIIIIIIII IIIIUIIIIIIIIIIIII
,ntroduction
Installation
Surface Mount Installation.................. 6-9
Recessed Installation.................. ,...9-13
Connecting Gas Line .......................... 13
ElectricalWiring .............................. 14
Thermostat Installation ........................ 14
Checks and Adjustment._ .................... 14,15
Lighting ..................................... 16
How To Use Your Furnace ...................... 16
How To Care For Your Furnace."................. 17
SERVICE HINTS ............................... 17
Wiring Diagram .............................. 18
Repair Parts............................... 19-27
............. IIIIIIIIIIIIIIIIIIIII I'IIIIIIIIIIIIIIIIIIIII I
Please read our instructions before you install and use your furnace. This will help you obtain the full value from
this furnace. It will also help you avoid any needless service costs, if the problem is something we cannot control
and cann°tc°ver in our Warranty.
i I _II l I l IIB III I Iml I Im Mil lllii I l I Hi lliI I l I l I _III II lie I l I l I I i I I _
-FULL ONE YEAR WARRANTY ON SEARS WALL FURNACE JJ
For one year from the date of purchase, when thisfurnace is installedand maintained in
accordance -withour instructions,Sears willrepair defects in material or workmanship in
the furnace, free of charge, a
LIMITED WARRANTY ON HEAT EXCHANGER II
! After one year and through len years from the date of purchase, Sears will furnish a=,
rep]acement Heat Exchanger, if the Heat Exchanger in the furnace is defective. You pay for .1
warranty gives you specific legal rights, you may vary I
This and also have other rights which from state
!,o,,ote -I.
Sears, Roebuck and Co.
II BSC 41-3, Sears Tower
. Chicago, Illinois 60684 I
1_lil I miD I i I aim I Hi I i ! a I Im I Nil i am III It I i III Ill I l I imami I I i ! mam H am I am l:ll'iiil _
To function properly, your furnace must be installed correctly. You must know how tO Us_the tools:ilOlDd;eq_ipment
and understand electrical wiring and potential hazards. If there is any doubt we ask thaf;_ou contact your Sears
Salesman. He will arrange for professional installation.
Iill Iill iI I II I m IJI l iI IJ I I l Ill I l ! I! n 11m !Ill I ImI I IJm II I Ill IIE I I IIi i
nSEARSlNSTA"ATIONPOUCY i SEARSINSTA"ATIONWARRANTYn
ALl installation labor arranged by Sears shall be "_. In addition to any warranty extended to you on the ,,,
I performed in a neat, workmanlike manner in I Sears merchandise involved, which warranty be-I
,= accordance withgenerallyacceptedtrade practices. _ comes effective the date the merchandise is =
J Further, ai[ installations shall comply with all local I installed, should the workmanship of any Sears I
.= laws, codes, regulations, and ordinances, The " arranged installation prove faulty within one year, _"
!customersha.alsobeprotecteddu.nginsta,,ation,ISears uponooticefromyou.causesuchfaultstoI!
mby insurance relating to Property Damage, Work- : be corrected at no additional cost to you.
imen's Compensation and Public Liability. _ll
IIIIIIIIiIIIIIIlllllIII IIilIIIIIIIlilIIIIIIIlil I
If[fill II'IIIIIIIIIIIIIIIII
Safety Rules
1. Read these rules and the instructions carefully.
Failure to follow these rules and instructions
could cause amalfunction of the furnace. This
could result in death, serious bodily injury,
and!or property damage.
2. This furnace must be installed in accordance 2
with local codes and ordinances or, in their
'absence with the National Fuel Gas Code,
ANSI Z223.I-1974.
3. Do not install this furnace in an alcove.
4. Do not install this furnace in a mobile home,
trailer or recreational vehicle.
5. Maintainall clearancesspecifiedon page5,
LocatingTheFurnace.
6. Be sure furnaceis equippedfor type of gas
(Naturalor LP)to be used.Checkthe rating
plate.
7. Gassupplypressuretothefurnacecontrolvalve
must be at least5 incheswater columnfor
Naturalgas and 11 inches,watercolumnfor
LPgas.It mustnot bemorethan14inches,
8. Thefurnacemustbeventedto the outdoorsso
that harmfulgaseswill not collectinsidethe
building.Followthe venting instructionsfor
your type installation exactly. Use only the type
and size of vent pipe and fittings specified.
9. Be sure to provide enough combustion and
ventilation air. See page 5. The flow of this air
to the furnace must not be blocked.
10. Never test for gas leaks with an open flame. Use
soap suds to check all gas connections. This will
avoid the possibility of fire or explosion.
11. Before servicing, allow furnace to cool. Always
shut off electricity and gas to furnace when
IIIII I
Basic Tools Needed
12.
13.
14.
15.
16.
working on it. This will prevent any electrical
shocks or burns.
Due to high temperatures, the furnace should
be located out of traffic and away from furniture
and draperies.
Children and adults should be alerted to the
hazards of high surface temperature and should
be kept away to avoiTJ"!_urns or clothing ignition.
Young children should be carefully supervised
when they are in the same room with the
furnace.
Do not place clothing or other flammable
material on or near furnace.
Installation and repair should be done by a
qualified service person. The furnace should be
!nspected before use and at least annually by a
professional service person. More frequent
cleaning may be required due to excessive lint
from carpeting, bedding material, etc. it is
i-mperative that control compartments, burners,
and circgiafing a!r passage ways of the furnace
be kept clean.
IIIIIIIIIl_llllllllUII_
Hand drill or properly grounded electric drill
Expansion bit 7/8" to 1-5/8"
3/32" drill bit (metal)
6 ft. folding rule or tape
Screwdrivers
Pliers (wire cutting)
Hammer
I II]1 III I I I
Basic Materials
Tin Snips
8" adjustable wrench
12" adjustable wrench
Key hole saw
Hack'saw
2- 10" or 12" pipe wrenches
Gloves
IIIIIIIIIIIIIIIIIIIIIIII II III
Black iron or steel pipe and fittings to make
connections from gas meter to furnace.
Pipe joint compound
Electrical wiring supplies as needed (See page 14).
Vent Shield Kit, Sears Stock No. 42-7311, if furnace is
to be mounted on a wall surface (not recessed in
wall).
Sears Stock No. 42-99767 gas vent kit for vertical
venting or Sears Horizontal Vent Kit, Stock No.
42-7369 for Horizontal venting.
Extra lengths of round, double wall vent pipe may be
needed. You must use 4inch pipe for vertical venting
and 5inch pipe for horizontal venting, it must be
Type B-1 vent (listed by Underwriters Laboratories
for Type B installation at 1 inch clearance .to
combustible materials).
I
Helpful Information
The following booklets will help you in makingthe installation.
Available at Sears from the Plumbing, Heating or
Electrical Departments at nominal cost:
Do It Yourself Plumbing Handbook
Basic Wiring
American National Standard Z223.1-1974 "National
Fuel Gas Code".
Obtain from- American National Standards
Institute, Inc., 1430 Broadway, New York, N.Y.
10018,
3
Optional Accessories
1. Tall Register Kit, Sears Stock No. 42-7312, For use
when replacing a "Dual Wail" furnace. Tall
register covers existing walt opening.
2. Shot;r Rear Wall Register Kit, Sears Stock No.
42-7313. For use when installing two-room
heating but not replacing "Dual Wall" furnace,
3. Vent Shield Kit, Sears Stock No. 42-7311. is
required when mounting the furnace on the sur-
face of the wall.
4. Horizontal Vent Kit, Sears stock No, 42-7369 is
required if furnace ;s to be vented horizontally
into on existing chimney.
I.I IIIIIIIIIII I II IIIIIIIIIIIIIJ II I IIIIIIIIIIIII IIIIIIIIIIIIIIIII II IIIII/11] IIIIIIIIII I IIIIIIIllll IIIIIIII
Furnace Data
MODEL
NUMBER
....867.736349
867.736389
INPUT**
TYPE RATING
GAS Btuh***
Nat. : 65,000
L,P.* 65,000
MAIN BURNER ORIFICE
2 REQUIRED
DRILL DEC.
...... 36 .1o65"
52 .0655"
PILOT ORIFICE
DECIMAL
.018"
.010"
*Liquefied Petroleum.
**For elevations above 2000 ft. reduce ratings 4% for each 1000 ft. above sea level.
***Btuh = British Thermal Units per hour.
BE SURE YOUR FURNACE IS EQUIPPED FOR THE TYPE OF GAS TO BE USED, EITHER NATU_,AL OR L.P. GA,5. THE
CONNECTIONS FROM THE L.P. BULK STOlYAGE TANK TO THE FURNACE CAN ONLY BE MADE BY A LICENSED
L.P. DEALER.
I ...................................................... __..I "L -
Unpack Your Furnace
The shipping carton contains the furnace and the
following items needed to install it.
1, Thermostat and wire -- packed inside lower
cabinet door (Fig. 1).
2. Top trim piece and small parts bag -- taped to
inside end of carton.
3. Vent support assembly -- in package taped to
end of furnace.
Store these items where they cannot be lost or
damaged.
Grasp each side of the cabinet door. Pull forward
and upward to remove (Fig. 1).
BE SURE YOUR FURNACE IS EQUIPPED FOR THE TYPE
OF GAS TO BE USED, EITHER NATURAL OR L.P.
CHECK THE RATING PLATE. IT IS ON THE PANEL JUST
ABOVE THE GAS VALVE.
Remove the cabinet door knob screw. Reinstall the
,knob on the outside.
Remove the two (2) screws holding the upper panel
(Fig. 1). Remove the panel for access to fan,
Remove the shipping bracket and tape from the fan
motor. Untape and remove the spacers between the
motor mount wires (Fig. 1).
t' [.</_L_-_ _ \ i !---=------': uPPeR
.- //! llUlli__ -_
'SHIPPING BRACKET _ r
SHIPPING RUNNER
CABINET --
SHIPPING
RUNNER _---,._._.
CABINET DOOR "
SELECTOt_
SWITCH
KNOB
Reinstall the upper front panel, Stand the furnace
upright. Remove the runners (Fig. 1).
Place the selector switch knob (shipped in parts bag)
on the shaft sticking through the front panel (Fig. t).
4
Installation Steps
The following steps ar.e all needed For proper
installation and safe operation of your wall furnace.
If you have any doubts as to any requirements, check
with local authorities.
I IIIIIIIIIIII II
Locating the Furnace
IIIIII
Obtain professional help where needed. The Checks
and Adjustments on page 14 are vital to proper and
safe furnace operation. Be sure they are done.
I I II
This furnace can be:
1. installed between (Recessed Mount) 2"x4" wall
studs spaced on 16 inch centers, or
Attached to (Surface Mount) an inside or outside
wall.
A. You need Vent Shield Kit, Stock No. 42-7311
(sold separately) for surface mounting.
2. Installed to vent vertically, or horizontally into on
existing chimney.
A. To vent horizontal¥ use Horizontal Vent Kit
Stock No. 42-7369 (sold separately). This kit
mmmlllml _
mmemi emtmmmm(ml
ammlIn mliit tiimq
aimammgpmaillmmm!
mm Iqm immli_
_mmnm
'mimmm
Imimmllm |
6" mman
MtN. E_J_]
BETWEEN
will require five inch type B-I (round _doub)e
w,alt) vent pipe (sold separately) leadlng
from it to the chimney.
B. To vent vertically, use type BW (oval double
wall) gas vent pipe and fittings. Sears gas vent
kit, Stock No. 42-99767, may be used.
3. Installed with arear wall register (optional
accessory kit). If it is to be used, follow instruc-
tions with the kit. Cut opening in rear wall for
register before mounting furnace in front wall.
Consider the following points before attempting to
install the furnace.
1. Check the minimum spacing needs as shown in
Fig. 2. Do not place furnace closer than 7/8 inch
R
EITHER
RIGHT OR
LEFT SlOE
AND
WALL
I mlllllll _lit _
mulm
mm_m
mmmnmm!l Immllummmt
gnnl|nPmm
|iHH
FLOOR
+ f
6" MIN,
tCEILING
to floor or floor covering.
2. Place the furnace near the center of the space
to be heated for good_ air circulation. Do not put i_
behind a door or draperies. Do not install it in a
closet, alcove, hallway or other confined space.
3. After picking a location, inspect the wall, floor,
attic and roof areas. Make sure there are no
IIIIIIIIIII lI_lIIIIIIIIIIIIIIIIIIIIIIIm I
Combustion Air
(
'i_J__
7tg"/WN., 4" RECOMMENIDEO
+
pipes, wiring, bracing, etc., that would interfere
with furnace or vent installation. Move them or
pick a new location.
4. Be sure that gas piping and electrical wiring can
be brought to the' location. See sections on gas
piping and electrical wiring for your h/pe of
furnace mounting.
I I IIIIIIIIIIIIIIIIIIIIIIJJJI I II I II I
WARNING
I E SURE TO PROVIDE ENOUGH FRESH AIR FOR
COMBUSTION AND VENTILATION.
outside air must enter the house to replace that
used by the burner.
Homes usually have enough leakage around doors
and windows to provide all the air needed.
If the furnace is installed in on unusually tight.home
(with well fitting =term window; and doors, weather
stripping, cracks caulked, etc.) fresh air must be
brought in from the outside through a permanent
opening at least 13 square inches in free area.
Comply =with ANSI standard 7.223.1-1974 "The .
National Fuel Gas Code", and with your local codes
and ordinances, m
5
Surface Mount Installation
(FOR RECESSED MOUNT INSTALLATION, TURN TO PAGE 9)
For ease of installation, servicing and cleaning,
install the furnace at least four (4) inches above the
floor (Fig. 2).
FIND THE STUDS
Use a stud tocator or four 8 penny finishing nails.
Repeatedly drive and remove a nail into the wall in
the area of the stud until it is located. Then find one
side. Leave the nail at this location. Drive another
nail just on the other side of the same stud. The
other stud should be about 16 inches from the one
found. Drive finishing nails on both sides of this stud.
Draw centerline on walt for each stud (Fig. 3).
FLOOR LAYOUT
FLOOR j
LINE
GAS _T
PIPE I""
OPENING RICAL OPENING
i,IlL
WALL LAYOUT
FLOOR
4
li
i
i'
1
t
I
J
I
t
I
I
_-- TOP SUPPORT
BRACKET LINE
I
I
[
14-3/B"
I
i
e=*
I_l
I'
I
73"
GAS AND ELECTRICAL SUPPLY
OPENINGS
Drill a 1Y=" hote in floor for gas line (Fig. 4).
The electrical supply opening must be at the lower
right of the furnace, either in the floor or wall
beneath the furnacebottom (Fig. 3 or 4).
Decide which location to use and drill a I inch hole.
Run the electrical supply and ground wires to the
opening. Leave enough length to connect in the
junction box after the furnace is installed, See
section "Electrical Wiring", page 14.
INSTALL FURNACE SUPPORTS
Use a surface mount vent shield kit, Sears Stock No.
42-7311. Obtain from your local Sears store.
Remove the support brackets from the kit. Center
and fasten the small support bracket to the wall four
inches from the floor {Fig. 3). Use four #10x11/2 flat
head wood screws furnished.
For vertical venting, center and fasten the top
support bracket to wall with the flange turned up 73
inches above the bottom bracket as shown in Fig. 5.
For horizontal venting fasten the bracket with the
flange turned down. See page 8. Use four 8x11/_"
round head wood screws furnished.
SURFACE MOUNT
BW VENT BASE
PLATE
BOTTOM PLATE
INSULATION SEAL
FLUE
COLLAR
TOP
SUPPORT
BRACKET
MENDED
BOTTOM
SUPPORT BRACKET
6
VERTICAL VENT INSTALLATION
Use a Type B-W gas vent installation kit, Sears Stock
No. 42-99767 (Fig, 6).
VENT INSTALLATION
2 FEET
VENT TOP
COLLAR
4" IB-1
VENT PIPE
OVAL TO ROUND
ADAPTER
BW VENT
BASE PLATE
CUT CEILING OPENING
Cut a ceiling opening 14-3/8" wide by 3-5/8" deep,
This must be directly above support brackets. The
back edge of the opening must be flush with the
wall (Fig. 7),
INSTALL CEILING PLATE SPACERS
CEILING PLATE SPACERS
PLATE
HEADERS SPACERS CEILING JOISTS
PARALLEL TO
HOLE IN
CEILING
Two ceiling plate, spacers are in the B-W vent kit.
They must be fastened along each tong edge of the
ceiling hole to hold the oval vent pipe in the center of
the hole (Fig. 7).
If your ceiling joists run at right angles to the wall
and are in line with the studs, nail the plate spacers
to the ]oists. Be sure they tine up with the long edges
of the holes.
If the joists run parallel to the wall, install 2"×6"
headers between two joists as shown in Fig. 7. If the
joists and studs do not.line up, install headers as
required to support the plate spacers.
INSTALL FURNACE VENT
Remove two screws in vent support assembly (Fig.
8). Discard the vent support. Attach the bottom
plate, ftue collar, seal, and base plate from B-W gas
vent kit to the top support on wall (Fig. S).
VENT SUPPORT
SEAL
COLLAR
VENT
SUPPORT
DISCARD
BoI'rOM PLATE
II III IIIII IIIIII lie
Lower a4foot length of oval, double wall vent pipe
through the ceiling hole to the base plate. The first
length of pipe must reach from the base plate to at
least 6 inches above the ceiling (Fig. 6). if it does not,
you must use alonger length. Force the vent pipe
into the base plate. Be sure the seal is in place. Lock
the pipe to the base plate with screws furnished in
the B-W gas vent kit.
7
SURFACE MOUNT INSTALLATION (CONTINUED)
install ovat to round adopter. Complefe the piping,
extending it through the roof. Use 4" round, double
wall (Type B-l) vent pipe, roof flashing, storm collar,
and vent top as shown in Fig. 6. The vent top must be
at least 2 feet above the highest point of the roof
within 10 feet, There must be at least 1 inch
clearance between the vent pipe and any combusti-
ble material.
If an existing brick chimney is used, follow the
directions above for the section from the base plate
through the ceiling. Then you may adapt to a Type
B-1,4" round, double wall pipe for the horizontal run
to the chimney. Connect into a chimney only in
accordance with local codes and ordinances.
HORIZONTAL VENT INSTALLATION
The furnace can be vented horizontally only by using
the horizontal vent kit, Stock No. 42-7369.
lnstafl top support with flange facing down as shown
in Fig. 9. Cut a 14-3/8 inch wide by 8l/2 inch hole in
front wal! above top support. Make bottom edge of
hate even with top edge of top support.
HOLE
IN
II,ACK
WALL
TOP
SUPPORT
Ii
i I
Ii
II
iBOTTOM
iSUPPORT
II
1
I
I
I t
I n
I
II
HOLE IN
FRONT
WALL
Remove the round knockout from wall shield in the
horizontal vent kit. Insert the wall shield into the
81/2"x14-3/8" opening so that round hole faces
chimney. Use hole in wall shield to mark opening to
be cut in back wall for vent pipe. If walt is less than
3-7/8 inches, trim shield so front edge is flush with
wail covering. Cut round hole. Nail wall shield to
studs (Fig. 10).
HORIZONTAL VENTING
BACK
WALL
VENT
SH_LD
TEE
NAIL
TO
Remove the plate, flue collar and insulation seat
from the vent support assembly furnished with the
furnace (Fig. 8). Install these with the Tee to 'the top
support as shown in Fig. 10. Discard vent support.
Complete the vent from the Tee to the chimney,
using S" Type B-t vent pipe. The horizontal run
should slope upward 1/4" per foot of run. Keep at
least one inch clearance between the vent pipe and
any combustibJe material.
Make sure that the end of the vent pipe does not go
into the chimney further than the inner surface. Seal
it in place with furnace cement.
MOUNT FURNACE ON SUPPORTS
Hold the furnace at a sIight angle with top toward
wall. Insert the flue in the openings in the top
support and flue collar. Straighten the furnace by
bringing it to rest onthe bottom support.
Install cabinet door and front panel.
8
INSTALL VENT SHIELD
The vent shield is 35-t/8 inches long. Measure from
top of furnace to ceiling. Cut the vent shield to this
dimension less 1/8 inch. Be sure to cut from the top
(end opposite flange) (Fig. 11).
Place vent shield on top of furnace and against the
wall. Drill holes in the furnace top through holes in
vent shield. Fasten to furnace with sheet metal
screws. Screw sides to wall,
install wood trim moulding if desired, if 3/4 inch
quarter round trim is used, trim 1/8 inch from both
side flanges before installing vent shield.
FLANGE
WOOD
TRIM
(NOT FURN|SHED!
IIIIIIIIIIIIIIIIII I II IIIIIIIIIIIIIIIIIIIIIII I I I llli IIIIIII
Recessed Mount Installation
For ease of installation, servicing and cleaning,
install the furnace at Least four (4) inches above the
floor (Fig. 12).
FIND THE STUDS
Use astud Iocator or four 8penny finishing nails.
Repeatedly drive and remove a nail into the wall in
the area of the stud until it is located. Then find one
side. Leave the nail at this location. Drive another
nail just on the other side of the same stud.
Inside edge of the other stud should be about 14-1/2
inches from the one found. Drive finishing nail on
inside edge of this stud.
CUT WALL OPENING
Lay out and cut a 14-3/8" by 74-1/2" opening as
shown in Fig. 12.
WALL LAYOUT
I
14-I/2"
STUDS
/\
! • 74-I/2"
t
I
i
| i 4_
• " : LRECOMA_ENDtEO
F J_.'iM.' H. iHJHJ'i , 11
I
iLL Ill :
9
\
RECESSED MOUNT INSTALLATION (CONTINUED)
FURNACE SUPPORT BLOCKS
Cut two (2) 3-1/8" high, 2 x 4blocks, and nail to floor
plate and studs (Fig. 13).
GAS AND ELECTRIC
SUPPLY OPENINGS
GAS LINE OPENING BOTTOM OF
IN BACK WALL FURNACE
2x4
SUPPORT _--__ _BLOCKS
ELECTRICAL
SUPPLY OPENING
IN FLOOR PLATE
OR WALL STUD
OR FLOOR
I" D4A.
CEILING PLATE SPACERS
,j
GAS LINE
OPENING FINISHED
IN FLOOR FLOOR LINE
GAS AND ELECTRICAL SUPPLY OPENINGS
Decide whether the gas fine will come through lhe
floor or back wall.
Drill a 1 ]/2" hole in ",vail or floor (Fig. t3).
The electrical supply opening must be at the lower
right of the furnace, either in the floor or stud
beneath the furnace bottom (Fig. 13).
Decide which location to use and drill a 1 inch hole.
Run the electrical supply and ground wries to the
opening. Leave enough length to connect in the
junction box after the furnace is installed. See
section "Electrical Wiring", page 14.
VERTICAL VENT INSTALLATION
Use a Type B-W gas vent installation kit, Sears Stock
No. 42-99767 (Fig. 17).
INSTALL CEILING PLATE SPACERS
Cut away the ceiling plate between the studs "where
the furnace is to be installed. Work from the top in
the attic.
If there is no access to the top, remove the wall
covering between the two wall studs, all the way to
the ceiling. Work through this opening.
Cut out the entire ceiling plate so the plate edges.
will be even with the inner face of the 2" x4" studs
(Fig. t4),
Nail the ceiling plate spacers (furnished with gas
vent kit) across the cut out section of ceiling plate
(Fig. 14). The spacer lugs are to center the oval vent
pipe in the stud space.
INSTALL VENT SUPPORT
Measure up 73 inches from the top of the support
block. Pl_ce a mark on each stud :_t this distance
(Fig. 15).
VENT SUPPORT INSTALLATION
BASE PLATE
TOP OF
VENT SUPPORT
VENT SUPPORT
ASSEMBLY
SUPPORT
BLOCKS
I I
I 1
/
BOTTOM OF WALL OPENING
10
Remove two screws from vent support assembly
(Fig. 16). Place Base plate (furnished with gas vent
kit) on top of seal. Fasten base plate, seal, ftue
collar, vent support and bottom plate together with
screws (Fig. 15).
VENT SUPPORT
ASSEMBLY
SEAL
FLUE
COLLAR
VENT
SUPPORT
SO'frOM PLATE
Place the vent support between the studs with the
top even with marks on the studs (Fig. 15).
Drill pilot holes in the studs through the two holes in
each side of vent support.
Fasten vent support to the studs. Use four (4) #10 x
V2" wood screws (furnished),
INSTALL FURNACE VENT
Lower a 4 foot length of oval, double wall vent pipe
through the ceiling hole to the base plate. The first
length of pipe must reach from the base plate to at
least 6 inches above the ceiling (Fig. 17). If it does
not, you must use a longer length. Force the vent
pipe into the base plate. Be sure the seal is in place.
Lock the pipe to the base plate with screws furnished
in the B-W gas vent kit.
VENT INSTALLATION
CElUNG PLATE
SPACERS
6_' MIN. \
TOP
STORM COLLAR
ROOF FLASHING
OVAL TO
ROUND
ADAPTER _
CEILING
PLATE
SPACER
LUGS
12 FT, M|N. /
INSULATION
SEAL
BWVENT PIPE
VENT IASE
PLATE
VENT
.SUPPORT
2"'X4"
WALL STUDS
Install oval to round adapter. Complete the piping,
extending it through the roof. Use 4" round, double
wall (Type B-1 vent pi_e, roof flashing, storm collar
and vent top as shown In Fig. 17. The vent top must
be at least 2 feet above the highest point of the roof
within 10 feet. There must be at least 1 inch
clearance between the vent pipe and any combus-
tible material.
If an existing brick chimney is used, follow the
directions above for the section from the base plate
through the ceiling. Then you may adapt to a Type
B-1,4" round, double wall pipe for the horizontal run
to the chimney. Connect into a chimney only in
accordance with tocai codes and ordinances.
HORIZONTAL VENT INSTALLATION
The furnace can be vented horizontally only by using
the horizontal vent kit, Stock No. 42-7369.
On the back wall behind recess location, measure up
71-1/2 inches above the bottom of furnace location
(Fig. 18). Cut an opening between the studs 14-3/8
inches by 10 inches in back wall.
11
o
o
o
o
b.-
o
cD
o
iu'_:
_o
o
o
_0o
_E
.... , ,,,,
_0
c
"c
o)
o
o
o_
REAR WALL CUT-OUT
.........T
74.V=" FRONT"
WALL CUT
OUT
I'
10"
,q
J
7I- V_" ON
REAR WALL
...... ,.-I
I I
!I
4" RECOMMENDED
Measure up 73 inches from top of the support block.
Place amark on eoch stud at this distance (Fig. "19).
•VENT TEE AND SHIELD
Screw the BW type Tee from the vent kit to the vent
support assembly provided with the furnace. Put the
round opening in Tee toward back of vent support
(Fig. 19). Use s crews in vent support (Fig. 16).
Fasten the wall shield to the vent support with four
#10xV=" screws as shown in Fig. 19. The open side of
wall shield must face chimney. Screws are in parts
bag in vent kit.
Place the assembled vent support, Tee and wall
shield through the 10" x 14-3/8" opening in back wall
(Fig. 20).
Be sure the top of the vent support is even with the
marks on the 2 x 4 studs (Fig. 19).
Drill pilot holes in the studs through the two holes in
each side of vent support.
Fasten vent support to the studs. Use four (4) #10 x
V2" wood screws (furnished).
Nail wall shield to studs (Fig. 20).
HORIZONTAL VENTING
BACK
WALL
WALL
SHIELD
NAIL
TO
STUDS
VENT
SUPPORT
71 -V="
TO BOTTOM
OF FURNACE
Complete the vent from the Tee to the chimney. Use
5" Type B-1 vent pipe. Keep at least one inch
clearance between the vent pipe and any combusti-
ble material.
The horizontal run should be as short as possible and
should slope upward 1/4" per foot of run,
Make sure that the end of the vent pipe does not go
into the chimney further than the inner surface. Seal
it in place with furnace cement.
12
MOUNT THE FURNACE
Hold the furnace at o slight angle with top toward
wall opening. Enter the flue into the vent support.
Straighten the furnace by bringing it in to rest on the
support b]ocks or floor plate (Fig. 2t).
TRIM
Place the top metal trim on top of the furnace and
flush with sides. Fasten to wall with bronze screws
furnished (Fig. 21).
If the interior wall material was removed to install
ceiling plate spacers, replace it and refinish to match
the rest of wail.
Install wood trim moulding around sides and top of
furnace.
II lUlIIIII IIIIIIIIII I IFII
Connecting Gas Line
Observe local codes and ordinances. If there are
none, comply with the National Fuel Gas Code. If
installation is for L.P. Gas, you must have a licensed
L.P. installer make all connections between storage
tank and furnace.
Fig. 22 shows basic piping needed. It is difficult to
use rigid pipe to connect to gas valve. Check with
your local building inspector and use a flexible
GAS SUPPLY
118" N.P.T. FURNACE
PLUGGED GAS VALVE
HOLE
UNION
13
VENT SUPPORT
METAL TO P
TRiM PIECE
(FURNISHED)
FLUE
WOOD
TRIM
4- MOULDING
(NOT FURNISHEC
Iiiii1'111 I I Ilmllllll
connector if permitted. If not, use 1/2 inch steel oi"
wrought iron pipe and fittings,
1. Turn off all gas appliances in the house. Shut off
the gas supply at the main meter.
.
.
4.
5.
Use pipe joint compound on male threads only.
Pipe joint compound must be resistant to the ac-
tion of LP gases.
Use ground joint unions.
Instal1 a drip leg to trap dirt and moisture.
Provide a 1/8 NPT (National Pipe Thread) plugged
hole for test gauge connection immediately
upstream of the gas supply connection to the
furnace.
6. install a manual shut-off valve.
7. Tighten all joints securely,
TEST FOR GAS LEAKS
Open the manual shut-off valves in gas supply lines.
Relight pilots to any other appliance. Test for leaks.
Never use a lighted match or other open flame.
Apply a creamy solution of soap suds to each joint; tf
there is a leak, bubbles will form and burst. Correct
even the smallest leak at once.
Electrical Wiring
WARNING
J For your personal safety, turn off electric
power at.serviceentrance panel before making
any electrical connecti6ns.
All electrical work must conform to your local codes
and ordinances or in their absence, with National
Electrical Code, ANSt-C1-1978. If you are not familiar
with wiring and codes in general, have a competent
electrician do this job.
GROUNDING
CONNECTING SUPPLY WIRING
i
ACK RED
WHITE
BLACK
To avoid possible electrical shock hazard, perma-
nently ground your furnace according to local codes
and the National Electrical Code, A grounding
terminal is on back of the furnace junction box in
lower cabinet. Run a No. 14 copper wire from the
terminal to a grounded connection in electrical
service panel or a properly driven and electrically
grounded ground rod (Fig. 23)/
CAUTION
Do not ground to agas supply pipe. Do not
connect to electric power supply until furnace
is permanently grounded,
ELECTRIC POWER SUPPLY
Run a separate 115V., 60 Hz., 15 Ampere circuit from
aseparate circuit breaker or fuse _your set/ice
entrance panel to the furnace junction box. Do not
run these supply wires inside the furnace cabinet
(Fig.23).
COMPLETEWIRING DIAGRAM IS ON PAGE 18.
................... I II I IIIIIIIII IIIIIII
Checks and Adjustments
If you have installed your own furnace, we ask that
you call Sears Service for an ;_spection by a service
GROUND
TO115V 60HZ 15 AMP
"FUSED CIRCUIT
WALL THERMOSTAT INSTALLATION
Follow the instructions included in the thermostat
box. Run thermostat wire to the right end of the
furnace and connect to gas valve. Connect one wire
to terminal marked "TH" and other wire to terminal
marked "TH-TR" (Fig. 24).
LOW VOLTAGE CONNECTIONS
RY
D TO
TRANSFORMER
GAS VALVE
TERMINALS
TO THERMOSTAT
technician. The peace of mind and assured
performance are well worth the cost involved. He is
equipped to make the following necessary checks
and adjustments.
ADJUST THERMOSTAT ANTICIPATOR
Set the thermostat heat anticipator at .60. Instruc-
tions are with the thermostat.
LIGHT PILOT BURNER
Light the pilot. Follow the Lighting instructions on
page 16.
IIII I
ADJUST PILOT BURNER
Thepilot flame should surround 3/8" to 1/2" of the
thermocouple tip (Fig. 25). If the flame needs
PILOT FLAME
I3/8-1/2
INCH
adjustin_L
THERMOCOUPLE
PILOT
BURNER
14
KNOB
,GAS CONTROL
GA$ COCK POSIT|ON PILOT
INDICATOR ADJUSTING
SCREW COVER
t, Remove the screw cover over the pilot adjusting
screw (Fig. 26).
2. Insert a small screwdriver and adjust flame as
needed. Turn screw clockwise (--_)to decrease
flame. Turn counterclockwise (---):to increase
flame.
3. Turn the thermostat to its highest setting. The
main burner should light quickly and smoothly.
Turn the thermostat to its lowest setting. Main
burner shoutd go out. Pilot should remain lit.
4. Replace the pilot adjusting screw cover,
CHECK GAS INPUT AND PRESSURES
Push Hi-Lo knob on gas valve down (Fig. 26). This
sets pressure for highest firing rate.
Gas input to the burners must not exceed the rated
input shown on the rating plate below the burner.
Gas manifold pressure with the burner on high fire
must be as shown on the rating plate.
Gas supply pressure must be at least 5" water
column for Natural gas and 11" water column for L.P.
gas. it must not be more than 14" water column for
Natural gas or LP gas.
,MAIN BURNER ADJUSTMENT
[I-LO
NOB
I
These points must be checked by a qualified service
technician. He should make any changes or
adjustments necessary. Failure to have this done
cou!d result in premature furnace failure, or
unsatisfactory or possibly hazardous furnace oper-
ation.
ADJUST AIR FOR BURNERS
When the furnace is lighted the first time, the air to
each burner will have to be adjusted, A proper
setting of the air shutter (Fig. 28) gives a soft, blue
flame with no yellow tips.
1. Set thermostat to highest setting.
2. Loosen the wing screw that holds the air shutter
(Fig. 28).
3. Turn the air shutter counterclockwise ((-',) until
the flame has yellow tips. Turn clockwise (,-J)until
the yellow tips just disappear (Fig. 27).
4. Tighten wing screw to hold the shutter in place.
AIR SHUTTER
ROTATE AIR SHUTTER IN ORDER
TO GET PROPER AIR MIXTURE
/
IMPROPER FLAME PROPER FLAME
ADJUSTMENT ADJUSTMENT
CHECK THERMOSTAT
Check the thermostat, when it is set above
temperature shown on the thermometer, furnace
burner should light. Be sure the thermostat turns off
the furnace when room temperature reaches the
selected setting and starts the furnace when room
temperature falls afew degrees.
Set the thermostat for the desired temperature.
CORRECT
JmIIIAIIJlI|IA IIAdAdlAIAIAAI
/a_u.uuuuuuuuuuuuuu °uuuuuuuu uu5
1t AI II! I BtlB• II ll_ _ • It | I |JILL1
_,__.uuuuu,uu,uu_u uu uuuu,uuu,_uuuu D_.,)
TOO MUCH AIR, CONES BRIGHT
INNER CONES LIGHT BLUE POINTED TOP
OUTER MANTLE LIGHT BLUE
PROPER FLAME 'l/2" TO _1/4" HIGH
BLUE AND REAL SHARP POINTS
INSUFFICIENT AIR -- LON_ OPEN
END CONES, YELLOW IN COt.OR
15
How To Use Your Furnace
LIGHTING THE FURNACE
I. Set selector switch knob on front pane_ to
Automatic.
2. Turn on the electricpower. Set thermostatto
lowestsetting.Remove lower door.
3. Turngas cock knob OFF (Fig.29).Wait 5minutes
for any unburned gas to vent,
4. Turn on manual gas shutoff valve(s).
5. Turn gas cock knob to PILOT.
6. Apply alighted match to the pilot burner.
7. Push gas cock knob in as far as it will go. Hold it
for 30 seconds after pilot lights.
8. ReLeasegas cock knob. The pilot should stay lit.
Proceed to Step 9. If pilot flame goes out, repeat
Steps 3, 5, 6 and 7.
NOTE
It may take several tries to purge the air out of the
piping in a new installation.
9. Turn gas cock knob to ON.
10. Set the thermostat to the desired temperature.
1t. Replace cabinet door,
GAS CONTROLS
©
GAS
COCK GAS COCK POSITION
KNOB INO1CATOR
|-LO
NOB
!
After the furnace has been lit and adjusted, you
need only to set the thermostat to the temperature
you want. The thermostat will turn the furnace on
and off as needed to keep that temperature.
The furnace works like this:
1. Thermostat turns on the main burners.
2. Heat builds up in the furnace and starts the fan.
The heated air comes out the front panel louvers at
floor level.
3. When the thermostat setting is reached, it shuts
off the main burners.
4. The fan runs until the heat is removed from
furnace, then turns off.
The fan has two speeds. It will start on low speed. It
may switch to high speed as the air temperature
increases. This is automatic. No manual switching is
needed.
LIMIT CONTROL
The furnace has a limit switch which will prevent
overheating, if anything should back the ftow of air
through the furnace, the switch will turn the main
burners off. This switch cannot be adjusted.
MANUAL SELECTOR SWITCH
The furnace has a manual fan switch on the control
panel. This switch must be set at "AUTOMATIC" for
heating. If not, the furnace will not work.
Set the fan switch at the "SUMMER" position if you
want only the fan to run.
HI-LO SETTING
The Hi-Lo knob on the gas control valve (Fig.'29) lets
you set the burners for high or medium heat output.
Push the knob in for Hi. Pull it out for Lo.
On LO, the burners will work at medium firing rate.
The fan will run at low speed. This is the best setting
for all normal winter weather.
If more heat is needed, push the knob to" Rh The
burners will work at high firing rate. The fan will
start on low speed then shift to high.
TURNING OFF THE FURNACE
1. Set the thermostat to the lowest setting.
2. Turn the gas cock knob to "OFF".
3. Turn electrical power off.
16
How To Care For Your Furnace
DANGER: PERSONAL INJURY HAZARD. DISCONNECT ELECTRIC POWER BEFORE
SERVICING.
ANNUAL UPKEEP NEEDED
CLEANING AND OILING CABINET FINISH
Remove cabinet door and front panel. Clean any lint
or dirt from fan blades, fan motor, air shutters and
exposed air passages. Use a brush.
Put 5drops of SAE 20 non-detergent oil in each of the
two oil cups on fan motor. Replace front panel and
cabinet door (Fig. 1).
VENTING SYSTEM
Make sure that no parts of the venting system are
blocked or rusted. Clean or replace before using
furnace.
BURNER AND PILOT FLAME
Look at the burner flame. See "Checks and
Adjustments". Contact Sears Service Department at
once if an abnormal flame appearance should
develop (Fig. 27).
Apply asmall amount of furniture wax to a soft cloth
and wipe cabinet. Never use abrasives or clean
when furniture is hot.
FURNACE AREA
The area near the furnace must be kept clear and
free from combustible materials, gasoline, and other
flammable liquids and vapors.
COMBUSTION AND VENTILATION AIR
The combustion and ventilation air supply must not
be blocked. See page 5.
Do not put anything in, on or under the furnace
cabinet.
If you wish, call for a Sears service technician to perform this maintenance for you. The peace of mind and assured
performance are well worth the cost involved.
Service Hints
If your furnace fails to work right, you may avoid a service call by checking the following points before you call for
service.
No Heat or Not Enough Heat....
POSSIBLE CAUSE WHAT TO DO
Thermostat not set right.
No electric power to furnace.
Gas is shut off.
Pilot is out.
Selector switch set on Summer.
Gas controlvalve set on Lo.
Set above room temperature.
Check fuse or circuit breaker. Replace blown fuse.
Reset breaker. Turn switch on.
Turn gas valve on. See page 16.
Light pilot. See page 16.
Turn knob to Automatic. See page 16.
Turn to Ht. See page 16.
t7
WIRING DIAGRAM MODELS 867.736349 AND 867.736389
FAN
MOTOR
I
I
I
I
I
IGAS
VALVE
THERMOSTAT
iii
CONNECTION DIAGRAM
I I IIIIIII I U
TH
BK
W
R TAPED
BK HI SPEED
BL MED. SPEED
LIMIT CONTROL
BK
MANUAL
SELECTOR
SWITCH
FURNACE JUNCTION
TRANSFORMER
FAN JUNCTION
BOX
BL
HIGH
FAN
SWITCH
LOW
FAN
SWITCH
w
i i
LADDER DIAGRAM
_15 AMP
FUSED
DISCONNECT
SWITCH
RECOMMENDED
115 VOLT 60 HZ
TO APPROVED
ROUND
SUMMER MANUAL
SELECTOR
0SWITCH
HIGH FAN SPEED
SWITCH
JGA@
VALVE
THERMOSTAT
R RED
W WHITE
BK BLACK
BL BLUE
TAPED
---low voltage field wiring
IIIIIIIIIIIII1_ II I'
11sv §0HZ
SUPPLY
IF ANY OF THE ORIGINAL WERE SUPPLIED WITH THE FURNACE
MUST BE REPLACED, TYPE A-i orAF (IS0oC) WIRE MUST fie USED.
I IIIIIIIIIIIIIIIIILIIUIIIIIIIIIIIIIH I II
v
18
repair parts
SEARS GAS-FIRED FORCED AIR WALL FURNACE
867.736389
MODELS 867.736349 AND
12
|
8
5
13
2
17\
14 16
8
2O
FOR PARTS LIST SEE
TOP OF PAGE 20
19
CABINET
23
13
19
repair parts
SEARS GAS-FIRED FORCED AIR WALL FURNACE MODELS
867.736389
867.736349 AND
KEY
NO.
1
2
3
4
5
6
7
8
9
I0
II
12
13
14
15
16
17
18
19
2O
21
22
23
PARTNUMBERS
503898
507245
STD510602
503941
39238
502787
505155
501812
505228
507453
5O4447
505158
STD610803
507126
503906
503908
503911
88868
STD611005
504114
504239
5041O6
507128
507674
* Standard Hardware Item.
Part Not 111ustrated.
KEY
NO.
1
2
3
4
5
6
7
8
9
I0
II
12
13
14
15
16
17
18
19
2O
21
22
23
24
25
26
27
28
29
3O
PART NUMBERS
503989
STD610803
503928
CABINET
DESCRI#TION
Rail, Botto'm
Insulation, Cabinet Door
*Screw, 6-32 x I/4" Machine
Door, Cabinet
Knob, Door
Catch, Bullet
Panel, Front
Knob, Selector Switch
Insulation, Front Panel
Panel, Control
Support, Panel
Panel, Upper Louver
*Screw, 8 x 3/8" Sheet Metal (30 Req.)
Panel, Left Side
Plate
Support, Vent
Collar, Flue
Seal
*Screw, lO x I/2" Sheet Metal (8 Req.)
Panel, Back
Trim, Top
Top, Body
Panel, Right Side
Manual, Owners (F642-18880)
Purchase Locally. FOR PARTsiL(uSTRATION
SEE PAGE 19
RODY
DESCRIPTION
Shield, Burner Box
*Screw, 8 x 3/8" Sheet Metal (20 Req.)
Plate, Bottom
504016 Gasket, Bottom Plate
STD611007 *Screw, I0 x I" Sheet Metal (4 Req.)
504336 Plate, Combustion Chamber Bottom
504337
504751
503884
503971
503883
504264
504247
504059
503977
Gasket, Combustion Chamber Bottom Plate
Chamber, Combustion (2 Req.) (Includes 7 & 9)
Gasket, Combustion Chamber to Radiator (2 Req.)
Radiator
Gasket (Radiator to Diverter)
Extension, Diverter
Gasket (2 Req.)
Gasket
Diverter
STD511005 *Screw, 10-24 x I/2" Machine C2 Req.)
STD55_IIO *Lockwasher, No. 10 Split (2 Req.)
STD541010 *Nut, I0-24 Hex (2 Req.}
504828 Support, Shield
503987
503986
507129
502043
504522
504521
507133
507131
507132
STD610805
STD611005
* Standard Hardware Item.
_ Part Not Illustrated.
Shield, Body
Cover, Switch
Support, Switch
Switch, Selector
Baffle, Switch
Support, Switch (Selector Switch)
Switch, High Temperature Fan
Switch, Low Temperature Fan
Switch, Limit
*Screw, 7 x 3/8" Sheet Metal (6 Req,)
*Screw, I0 x I/2" Sheet Metal (6 Req.)
Purchase Locally. FOR PARTS ILLUSTRATION
20 SEE PAGE 21
repair parts
SEARS GAS-FIRED AIR WALL FURNACE MODELS 867.736349 AND 867.736:389
2O 19
BODY
8_
7
7
3
2
21 22
2
26
j27
o @ 28
2t
25
FOR PARTS LISTSEE
BOTTOM OF PAGE 20
repair parts
SEARS GAS-FIRED AIR WALL FURNACE MODELS 867.736349 AND 867.736389
......
14 13 12 11 9 7 1
__,1" ,, '
21 16 , /L
.! I l,
'l / 1
....... ...... 1¢_"
KEY
NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
PART NUMBERS
507467
507466
504517
504516
507462
5O2191
502287
500757
503873
507461
504027.
507683
507684
STD541010
STD551110
504449
STD551210
STD511005
STD541006
504507
STD510603
606234
27207
500370
504871
DESCRIPTION
Wire,
Wire,
Wire,
Wire,
Wire,
Wire,
Wire,
Wire,
Wire,
Wire,
Wire,
(Black) Selector Switch to Junction Box (57 't Long)
(White) From Junction Box to Junction Box (77" Long)
(Black) From High Fan Switch to Junction Box (22" Long)
(Red) From High Fan Switch to Junction Box (24" Long)
(White) From Selector Switch to High Fan Switch (40" Long)
(White) From High Fan Switch to Fan Switch (4" Long)
(White and White) (Includes No. 5 and 6)
(Black) Fan Switch to Limit Switch (4" Long)
(Red and Black) (Includes Nos. 8 and I0)
(Red) From Selector Switch to Fan Switch (40" Long)
(Red) From Limit Switch to Junction Box (92" Long)
Wire, (White) "C" on Transformer to "TR" on Gas Valve (7" Long)
Wire, (Black) "R" on Transformer to "TH-TR" on Gas Valve (7" Lon{
*Nut, 10-24 Square
*Lockwasher, No. I0 Split
Box, Junction
*Lockwasher, No. I0 External Tooth
*Screw, 10-24 x I/2" Machine
*Nut, 6-32 Hex (2 Req.)
Cover, Junction Box
*Screw, 6-32 x 5/16" Machine (2 Req.)
Transformer, 24V./20VA.
*Screw, 6-32 x I-I/4" Machine (2 Req.)
Wire, 25 Feet, 2-Wire Thermostat
Thermostat, Wall
* Standard Hardware Item. Purchase Locally.
Part Not Illustrated. 22
repair parts
SEARS GAS-FIRED AIR WALL FURNACE MODELS 867.736349 AND 867.736389
KEY
NO.
1
2
3
4
5
6
7
8
9
I0
II
12
13
14
PART NUMBERS
507121
STD610805
501503
506299
STD551110
STD5111 O3
505764
505433
505760
STD622503
5O4073
502519
STD610803
STD611005
DESCRIPTION
Orifice, Fan
*Screw, 7 x 3/8" Sheet Metal (2 Req.)
Clamp, Wire (2 Req.)
Support, Motor (2 Req.)
*Lockwasher, No. I0 Split (4 Req.)
*Screw, 10-32 × 3/8" Machine (4 Req.)
Mount, Motor (2 Req.)
Ring, Support (2 Req.)
Motor, Fan 120V._ 60 Hz.
*Screw, I/4-28 x 3/8" Set
Blade, Fan (Includes No. I0)
Box, Junction
*Screw, 8 x 3/8" Sheet Metal (2 Req.)
*Screw, I0 x I/2" Sheet Metal (4 Req.)
* Standard Hardware Item. Purchase Locally.
,,,,,,,,,,,,,,,,,,,,,,
I IIIIIIIIIIIIIIIIII
SEARS VENT SHIELD KIT NO. 42-1311 (OPTIONAL ACCESSORY)
1
KEY
NO. PART NUMBER
- 504386
1
2
3
23
504375
504241
504398
504393
DESCRIPTION
Kit, 42"7311 Vent Shield
(Optional Accessory)
Cover, Vent
Support, Bottom
Support, Top
Sheet, Instruction
repair parts
SEARS GAS-FDRED FORCED AIR WALL FURNACE
867.736389
MODELS 867.736349 AND
16
T
15
27
26
2O
17
2O
BURNER COMPARTMENT
18
17
11
6 7
12
13
4
15
14
16
3
2
FOR PARTSLIST
SEEPAGE 25
24
repair parts
SEARS GAS-FIRED FORCED AIR WALL FURNACE
867.736389
MODELS 867.736349 AND
BURNER COMPARTMENT
KEY
NO.
1
2
3
4
4
5
6
7
8
9
9
I0
I0
II
12
13
14
14
15
16
17
18
19
2O
21
22
23
24
25
26
27
PARTNUMBERS
867.736349
504826
STD611005
504072
507677
505118
STD511107
89030
FOR MODELS
867.736389
29441
503036
504455
507552
503758
46958
30368
STD511003
22000
5O5757
STD511005
503961
STD541010
64479
505755
STD511007
505756
STD510803
STD551110
STD611007
506537
504826
STD611005
504072
507678
505118
STD511107
89O30
29441
503037
mm--
504456
507552
503758
46958
46852
STD511003
22000
505757
STDSIIO05
503961
STD541010
64479
505755
STD511007
505756
STD510803
STD551110
STD611007
506537
DESCRIPTION
Shield, Burner Hea't
*Screw, I0 x I/2" Sheet Metal (7 Req.)
Plate, Division
#Valve, Gas (Nat.)
#Valve, Gas (L.P.)
Support, Valve
*Screw, 10-32 x 3/4" Machine
Tubing, Pilot
Ferrule and Nut
#Orifice, Pilot (Nat. Gas)
#Orifice, Pilot (L.P. Gas)
#Pi_ot, Burner (Nat. Gas) (Includes No. 9)
#Pilot, Burner (L:P. Gas) (Includes No. 9)
Manifold
Thermocouple
Sleeve, Manifold (2 Req.)
#Orifice, Burner (Nat. Gas) (No. 36 Drill Size)
#Orifice, Burner (L.P. Gas) (No. 52 Drill Size)
*Screw, 10-24 x 5/16" Wing (2 Req.)
Shutter, Air (2 Req.)
Burner (2 Req.)
*Screw, 10-24 x I/2" Machine (2 Req.)
Bracket, Burner (2 Req.)
*Nut, 10-24 Square (4 Req.)
*Nut, "J" Speed (2 Req.)
*Nut, 8-32 "U" Speed
*Screw, 10-24 x 5/8" Machine (2 Req.)
Support, Pilot
*Screw, 8-32 x 3/8" Machine
*Lockwasher, No. I0 Split (2 Req.)
*Screw, I0 x I" Sheet Metal (2 Req.)
Plate, Lighting Instruction
*-Standard Hardware Item. -- Purchase Locally.
Part Not Illustrated.
# Be Sure Parts Being Ordered Are For Type
of Gas Being Used.
i i|ll i i
.... FORPARTSILLUSTRATION
SEE PAGE24
(2 Req.)
(2 Req.)
rlit Ilml I"11IIII
SEARS HORIZONTAL VENT KIT NO. 42-1369 (OPTIONAL ACCESSORY)
_, ,,, i,
1
KEY
NO. PART NUMBER DESCRIPTION
- 506591
1
2
506590
506588
506592
Kit, 42-7369 Horizontal Vent
(Optional Accessory)
Tee, Horizontal Flue
Shield, Wall
Sheet, Instruction
25
repair parts
SEARS GAS-FIRED FORCED AIR WALL FURNACE MODELS 867.736349 AND
867.736389
............ i I ,= --
Sears Rear Wall Register
Stock No. 42-7313
(,Optional Accessory)
Kit -
1
. ',--
IIIIIIIIIIIII | I I
KEY
NO.
1
3
4
5
6
7
PART NUMBER
130358
506953
STD610805
506942
506943
506957
506939
506951
DESCRIPTION
*Screw, I0 x I" Round Head Wood (3 Req.)
Panel, Rear Register
*Screw, 7 x 3/8" Sheet Metal (12 Req.)
Panel, Side Collar (2 Req.)
Panel, Top and Bottom Collar (2 Req.)
Deflector, Air
Bracket, Hanger
Manual, Installation (F642-i2176)
Standard Hardware Items.
Purchase Locally.
Part Not lllustrated.
26
repair parts
SEARS GAS-FIRED FORCED AIR WALL FURNACE MODELS 867.736349 AND 867.736389
Sears Rear Wall Register
__ Stock No. 42-7312
,3/_?ptionai Accessory)
L,1"_4
2 ' i _. • 7
_._ _ _'1 ._-.-_
<,,,. "" _
i i | i i i
Kit -
_EY
NO.
1
2
3
4
5
PART NUMBER
130358
506946
506939
506957
506943
STD610805
506942
5O6947
DESCRIPTION
*Screw, I0 x I" Round Head Wood (3 Req.)
Panel, Rear Register
Bracket, Hanger
Deflector, Air
Panel, Top and Bottom Collar (2 Req.)
*Screw, 7 x 3/8" Sheet Metal (12 Req.)
Panel, Side Collar (2 Req.)
Manual, Installation (F642-12276)
* Standard Hardware Items.
Purchase Locally.
Part Not lllustrated
27
GAS-FIRED
FORCED AIR
WALL FURNACE
Now that you have purchased your wall furnace, should a
need ever exist for repair parts or service, simply contact any
Sears Service Center and most Sears, Roebuck a_d Co.
stores. Be sureto provide all pertinent facts when you call or
visit.
The model number of your Wall Furnace will be found on the
Rating Plate located on the Panel directly above the Gas
Valve.
When ordering repair parts always give the following
information:
PART NUMBER
MODEL NUMBER
.PART DESCRIPTION
NAME OF ITEM
Atl parts listed may be ordered from any Sears Service:
Center and most Sears stores.
If the parts you need are not stocked locally, your order will
be electronically transmitted to a Sears Repair Parts Distribu-
tion Center for handling.
When Sears arranges the installation, you can be sure the
job is done right. We will arrange for pLofessional Workman-
ship .... and we'll take care of the entire project. What's
more, during installation you get insured protection ....
against property damage and also against accidents to
workmen. AII you have to do is talk to your Sears salesperson
Or call your nearest Sears store today for detailed
information.
Sears, Roebuck and Co., Chicago, I!. 60684 U.S.A.
F642-18880 507674
11-3-80
L.T,I