NXT 4x4
Installation Guide
Section 1 – Wiring and Layout Diagrams
Section 2 – Specifications and Cable Requirements
Section 3 – Keri Contact Information

1.0

Wiring and Layout Diagrams

1.1

NXT-4x4 I/O Module
Shielded CAT-5 Cabling
total
cable length
500 feet max
(150 m)

Shielded 4-Conductor Cabling

Brown/Green/Orange w/o Stripe

Power (Red)

Brown/Green/Orange with Stripe
Blue

Ground (Black)
IO Plus (Green)

Blue with Stripe

IO Minus (White)

RS-485
4 3 2 1

TB21

Port 1

1

NO - Relay
Common - Relay
NC - Relay
Input
Ground

2

Relay

3

5

4

4

5

3

J23
Relay

TB22

2
1

a
JP1

NXT-4x4
Installation Drawing

Port 4

TB25

J2
cde

Ground
Input
NC - Relay
Common - Relay
NO - Relay

Tamper Switch Input
J1

TB23

Port 2

NO - Relay
Common - Relay
NC - Relay
Input
Ground

f gh i

1
2

Relay

b
TB24
5

3

4

4

Relay

5

3
2
1

Ground
Input
NC - Relay
Common - Relay
NO - Relay

Port 3

PCB Earth Ground Lug
J24

P/N: 01998-002 - Rev. E

See Table 1 on page 2 for LED definitions.
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.

Page 1 of 4

P/N: 01998-001 Rev. G

NXT 4x4
Installation Guide

Table 1: 4x4 LEDs
Power

Utility

Purpose

LED

indicator

a

Purpose

LED

RS-485 Tx

Purpose

LED

undefined

b

Purpose

LED

c

Bus 1

f

User 1

d

Bus 2

g

User 2

e

Bus 3

h

Bus 4

i

2.0

Specifications

2.1

NXT-4x4 Dimensions

•

•

2.2
•

2.3
•

Future Application

Relay State

4x4 PCB
- 5.25 inches tall by 3.10 inches wide by 1.00 inches deep, not including wiring connectors
- 13.33 cm by 7.87 cm by 2.54 cm
4x4 Enclosure
- 8.00 inches tall by 7.00 inches wide by 2.75 inches deep
- 20.32 cm by 17.78 cm by 6.98 cm

Power Requirements
10 to 14 VDC @ 0.5 A (maximum current draw for a fully loaded NXT-4x4)

Current Requirements at 12 VDC
250 mA max for each NXT-4x4

NOTE: If you are driving an electronic locking device (magnetic lock, door strike, etc.) using the same power supply as
the 4x4, ensure the power supply provides enough current to drive every device connected, including an adequate safety
margin.

2.4
•

2.5
•

2.6

Relay Contact Rating
1 A @ 24 VDC

Operating Conditions
32°F to 150°F (0°C to 60°C) – 0% to 90% Relative Humidity, non-condensing

Cable Options

RS-485 bus runs can daisy-chain together an NXT-4x4 and NXT-Reader on one line. The total cable run distance should
be less than 500 feet from the NXT controller for runs with 4x4s and less than 1,000 feet for Reader-only runs.
NOTE: Cable resistance causes a drop in voltage at the end of long cable runs. Ensure the appropriate power and current
for your device is available at the device at the end of the cable run. Heavier gauge cable reduces this affect.
NOTE: Keri does not recommend hot-plugging a Reader, RIM, or 4x4 into an NXT controller. 
Remove power from the controller prior to connecting these devices.

Page 2 of 4

P/N: 01998-001 Rev. G

NXT 4x4
Installation Guide

Table 2: Reader and 4x4 Cable Options

Connection Type

RS-485 bus 
from NXT-2D/-4D 
to NXT-4x4 only

Total
Run
Length
up to
500 feet

Shielded, Stranded,
2 Twisted-Paira
AWG

Suggest

18 - Data plus
4x4 Power

Belden
8723

CAT-5b

unshielded

22 - Data only
RS-485 bus 
from NXT-2D/-4D 
to NXT-4x4 
and NXT Readers

up to
500 feet

RS-485 bus 
from NXT-2D/-4D 
to NXT Readers only

up to
1,000 feet

Shielded, Stranded,
4-Conductorc
AWG

Suggest

18 - Data plus
4x4 Power

Windy City:
414302-S
West Penn: 244
Tappan:
1880AB4M-CM

22 - Data only

18 - Data plus
4x4 Power

Belden
8723

shielded

22 - Data only

18 - Data plus
4x4 Power
22 - Data only

22 for Data

Belden
8723

shielded

22 for Data

Windy City:
414302-S
West Penn: 244
Tappan:
1880AB4M-CM
Windy City:
416303-S
West Penn: 241
Tappan:
2280AB4M-CM

a. Keri recommends this cable type for best system performance.
b. Keri’s preferred low-cost option. Keri has no suggested vendor for this type of cable.
c. Use care when routing this type of cable as it can make the system more susceptible to EMI.

Table 3: Controller Power, Inputs, and Outputs Cable Requirements
Connection

Total Run
Length

# of
Conductors

Shielded

Stranded

Twisted
Pair

AWG

Belden
Equivalent

controller power

250 feeta

2

N

Y

Y

18

8461

earth ground

shortest
pathb

1

N

N

n/a

18

no specific
requirement

inputs and outputsc

500 feet

2

N

Y

n/a

22

no specific
requirement

a. To meet CE and C-tick regulations, the length of the controller power line can be no longer than 3 Meters
(9.85 feet).
b. Use the shortest possible path from earth ground point to PCB. Connect the earth ground only to the 
designated pin on the terminal block. This is important as all transient protection for the unit is made through
this earth ground connection. For unit protection, the earth ground connection should always be made first.
c. Values listed are minimums. Individual input and output devices may have more specific requirements.

Page 3 of 4

P/N: 01998-001 Rev. G

NXT 4x4
Installation Guide

3.0

Contact Keri Systems
Keri USA

Keri UK, Ireland, Europe

2305 Bering Drive
San Jose, CA 95131

Unit 17
Park Farm Industrial Estate
Ermine Street
Buntingford
Herts SG9 9AZ UK

Telephone: (800) 260-5265
(408) 435-8400

Telephone: + 44 (0) 1763 273 243

Fax: (408) 577-1792

Fax:+ 44 (0) 1763 274 106

Web: www.kerisys.com

Web:www.kerisystems.co.uk

E-mail: sales@kerisys.com
techsupport@kerisys.com

E-mail:sales@kerisystems.co.uk
tech-support@kerisystems.co.uk
End of document.

Page 4 of 4

P/N: 01998-001 Rev. G



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Tagged PDF                      : Yes
Page Mode                       : UseOutlines
XMP Toolkit                     : Adobe XMP Core 4.0-c320 44.293068, Sun Jul 08 2007 18:10:11
Producer                        : Acrobat Distiller 9.4.6 (Windows)
Creator Tool                    : FrameMaker 8.0
Modify Date                     : 2011:09:19 14:41:51-07:00
Create Date                     : 2005:10:04 15:10:28Z
Metadata Date                   : 2011:09:19 14:41:51-07:00
Format                          : application/pdf
Title                           : 4x4_Installation_Guide_G.fm
Creator                         : GGRIGSBY
Document ID                     : uuid:b75e2c26-1534-49fd-8cfe-4e0bc0267cf4
Instance ID                     : uuid:28ac6879-73aa-420e-b567-5ffa3db0c8ed
Page Count                      : 4
Author                          : GGRIGSBY
EXIF Metadata provided by EXIF.tools

Navigation menu