NXT 4x4
Installation Guide
Page 1 of 4 P/N: 01998-001 Rev. G
Section 1 – Wiring and Layout Diagrams
Section 2 – Specifications and Cable Requirements
Section 3 – Keri Contact Information
1.0 Wiring and Layout Diagrams
1.1 NXT-4x4 I/O Module
See Table 1 on page 2 for LED definitions.
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
TB24
TB25
TB22
TB23
TB21
J23
Relay
Relay
Relay
Relay
IO Minus (White)
Power (Red)
Ground (Black)
4321
Ground
Input
NC - Relay
Common - Relay
NO - Relay
NO - Relay
Common - Relay
NC - Relay
Input
Ground
Port 3
Port 4
Port 1
P/N: 01998-002 - Rev. E
1
2
3
4
5
5
4
3
2
1
1
2
3
4
5
5
4
3
2
1
J1
IO Plus (Green)
NO - Relay
Common - Relay
NC - Relay
Input
Ground
Port 2 Ground
Input
NC - Relay
Common - Relay
NO - Relay
JP1
J2
RS-485
J24
PCB Earth Ground Lug
cde
a
fghi b
NXT-4x4
Installation Drawing Tamper Switch Input
Shielded 4-Conductor CablingShielded CAT-5 Cabling
Blue with Stripe
Brown/Green/Orange w/o Stripe
Brown/Green/Orange with Stripe
Blue
total
cable length
500 feet max
(150 m)
NXT 4x4
Installation Guide
Page 2 of 4 P/N: 01998-001 Rev. G
2.0 Specifications
2.1 NXT-4x4 Dimensions
4x4 PCB
- 5.25 inches tall by 3.10 inches wide by 1.00 inches deep, not including wiring connectors
- 13.33 cm by 7.87 cm by 2.54 cm
4x4 Enclosure
- 8.00 inches tall by 7.00 inches wide by 2.75 inches deep
- 20.32 cm by 17.78 cm by 6.98 cm
2.2 Power Requirements
10 to 14 VDC @ 0.5 A (maximum current draw for a fully loaded NXT-4x4)
2.3 Current Requirements at 12 VDC
250 mA max for each NXT-4x4
NOTE: If you are driving an electronic locking device (magnetic lock, door strike, etc.) using the same power supply as
the 4x4, ensure the power supply provides enough current to drive every device connected, including an adequate safety
margin.
2.4 Relay Contact Rating
1 A @ 24 VDC
2.5 Operating Conditions
32°F to 150°F (0°C to 60°C) – 0% to 90% Relative Humidity, non-condensing
2.6 Cable Options
RS-485 bus runs can daisy-chain together an NXT-4x4 and NXT-Reader on one line. The total cable run distance should
be less than 500 feet from the NXT controller for runs with 4x4s and less than 1,000 feet for Reader-only runs.
NOTE: Cable resistance causes a drop in voltage at the end of long cable runs. Ensure the appropriate power and current
for your device is available at the device at the end of the cable run. Heavier gauge cable reduces this affect.
NOTE: Keri does not recommend hot-plugging a Reader, RIM, or 4x4 into an NXT controller.
Remove power from the controller prior to connecting these devices.
Table 1: 4x4 LEDs
Power Purpose LED Future Application Purpose LED
indicator a undefined b
Utility Purpose LED Relay State Purpose LED
RS-485 Tx c Bus 1 f
User 1 d Bus 2 g
User 2 e Bus 3 h
Bus 4 i
NXT 4x4
Installation Guide
Page 3 of 4 P/N: 01998-001 Rev. G
Table 2: Reader and 4x4 Cable Options
Connection Type Total
Run
Length
Shielded, Stranded,
2 Twisted-Paira
a. Keri recommends this cable type for best system performance.
CAT-5b
b. Keri’s preferred low-cost option. Keri has no suggested vendor for this type of cable.
Shielded, Stranded,
4-Conductorc
c. Use care when routing this type of cable as it can make the system more susceptible to EMI.
AWG Suggest AWG Suggest
RS-485 bus
from NXT-2D/-4D
to NXT-4x4 only
up to
500 feet 18 - Data plus
4x4 Power
22 - Data only
Belden
8723 unshielded 18 - Data plus
4x4 Power
22 - Data only
Windy City:
414302-S
West Penn: 244
Tappan:
1880AB4M-CM
RS-485 bus
from NXT-2D/-4D
to NXT-4x4
and NXT Readers
up to
500 feet 18 - Data plus
4x4 Power
22 - Data only
Belden
8723 shielded 18 - Data plus
4x4 Power
22 - Data only
Windy City:
414302-S
West Penn: 244
Tappan:
1880AB4M-CM
RS-485 bus
from NXT-2D/-4D
to NXT Readers only
up to
1,000 feet 22 for Data Belden
8723 shielded 22 for Data Windy City:
416303-S
West Penn: 241
Tappan:
2280AB4M-CM
Table 3: Controller Power, Inputs, and Outputs Cable Requirements
Connection Total Run
Length # of
Conductors Shielded Stranded Twisted
Pair AWG Belden
Equivalent
controller power 250 feeta
a. To meet CE and C-tick regulations, the length of the controller power line can be no longer than 3 Meters
(9.85 feet).
2 N Y Y 18 8461
earth ground shortest
pathb
b. Use the shortest possible path from earth ground point to PCB. Connect the earth ground only to the
designated pin on the terminal block. This is important as all transient protection for the unit is made through
this earth ground connection. For unit protection, the earth ground connection should always be made first.
1 N N n/a 18 no specific
requirement
inputs and outputsc
c. Values listed are minimums. Individual input and output devices may have more specific requirements.
500 feet 2 N Y n/a 22 no specific
requirement
NXT 4x4
Installation Guide
Page 4 of 4 P/N: 01998-001 Rev. G
3.0 Contact Keri Systems
End of document.
Keri USA Keri UK, Ireland, Europe
2305 Bering Drive
San Jose, CA 95131 Unit 17
Park Farm Industrial Estate
Ermine Street
Buntingford
Herts SG9 9AZ UK
Telephone: (800) 260-5265
(408) 435-8400 Telephone: + 44 (0) 1763 273 243
Fax: (408) 577-1792 Fax:+ 44 (0) 1763 274 106
Web: www.kerisys.com Web:www.kerisystems.co.uk
E-mail: sales@kerisys.com
techsupport@kerisys.com E-mail:sales@kerisystems.co.uk
tech-support@kerisystems.co.uk

Navigation menu