Kidde XV™ Control System
Effective: August 2013
K-87-027

P/N: 87-120099-002

FEATURES
•

For Use in:
•

•
•
•
•

WHDR™

Commercial Cooking Fire
Suppression Systems

• IND™ Industrial Fire Suppression Systems
Pneumatic Release of up to 20 Agent Cylinders
Two Discrete Mechanical Detection Lines
Cylinder or Wall Mount
Up to 400 ft. Mechanical Detection Cable

•
•
•
•
•
•
•
•

Operates 2 Gas Valves
Available 24 V Electrical Actuation
Multiple Remote Release Options
Rugged, Die-Cast Aluminum Body
Tamper/Lock Port for Cover
Easy to Install and Maintain
UL & ULC Listed
FM Approved for IND Systems

DESCRIPTION
The Kidde XV Control System is a compact, versatile unit
used to actuate agent cylinders on Kidde WHDR and IND
Pre-Engineered fire suppression systems. The control
head can be operated via:
•
•
•

Two Distinct Automatic Mechanical Detection Lines
(fusible links or thermo-bulb links)
Optional Electrical Solenoid
Remote or Local Manual Mechanical Control

Upon actuation, the XV Control System discharges the
nitrogen System Cartridge, pressurizing the actuation
lines and System Valve Actuators (SVA) mounted on the
cylinder valve(s). The SVA(s) open the cylinder valve(s),

discharging the WHDR wet chemical or IND dry chemical
suppression agent. The XV can be mounted on a wall or
directly to an SVA mounted on the cylinder.
The XV Control System is UL and ULC Listed with
WHDR Wet Chemical and IND Dry Chemical Fire
Suppression Systems. The XV is FM approved with the
IND Dry Chemical Systems.
The XV comes ready to install, with three EMT
connectors, one System Valve Actuator (SVA), two
microswitches, one nitrogen System Cartridge, and one
nitrogen test cartridge.

Figure 1. XV Control System, P/N 87-120099-002

TECHNICAL DATA
Table 1. Mechanical Cable Parameters for WHDR & IND Systems
Max. Cable
Length

Max. Corner
Pulleys

Max.
Detectors

Max. Tee
Pulleys

Detection and Manual Release-to-Trip Line 1

200 ft. (60.96 m)

50

40

*

Detection and Manual Release-to-Trip Line 2

200 ft. (60.96 m)

50

40

*

Pull-to-Trip Remote Manual Release Line

100 ft. (30.48 m)

30

-

1*

Mechanical Gas Valve Line

100 ft. (30.48 m)

30

-

1*

XV Cable Line

*Tee pulleys count as two Corner Pulleys. Maximum is from XV Control, through the pulley, to each device.

Table 2. Actuation Parameters for WHDR Wet Chemical Systems
Operating
Temperature
Range

Number of
Extinguishing
System Cylinders

Maximum Total Length
Copper Actuation Tubing

0°F to 120°F
(-18°C to 49°C)

1-12

106 ft. (32.30 m)

13-20

91 ft. (27.73 m)

Minimum Total Length of Copper
Actuation Tubing
5 ft. (1.52 m)

Table 3. Actuation Parameters for IND Industrial Dry Chemical and Open-Face Spray Booth Systems
Operating
Temperature
Range

Number of
Extinguishing
System Cylinders

Maximum Total Length
Copper Actuation Tubing

-40°F to 120°F
(-40°C to 49°C)

1-14

166 ft. (50.60 m)

15-20

121 ft. (36.88 m)

Minimum Total Length of Copper
Actuation Tubing
5 ft. (1.52 m)

Table 4. Actuation Parameters for IND Dry Chemical for Vehicle Spray Booths
Operating
Temperature
Range
0°F to 120°F
(-18°C to 49°C)

Number of
Extinguishing
System Cylinders

Maximum Total Length
Copper Actuation Tubing

1-8

200 ft. (60.96 m)

9-15

160 ft. (48.76 m)

16-20

140 ft. (42.67 m)

Minimum Total Length of Copper
Actuation Tubing

5 ft. (1.52 m)

NOTES
1.
2.
3.

Braided high pressure nitrogen tubing (P/N 87-120045-00X), is required to connect the XV Control System to the
System Valve Actuator (SVA) when the XV Control System is cylinder mounted.
Copper tubing shall be 1/4-inch O.D. x 0.031-inch wall high pressure tubing.
When Control System is cylinder mounted and two or more cylinders are being actuated, a minimum of 5 ft.
(1.52 m) of 1/4-inch O.D. x 0.031-inch wall tubing shall be used for actuation lines.

-2-

4.
5.
6.
7.

When Control System is wall mounted, a minimum of 5 ft. (1.52 m) of 1/4-inch O.D. x 0.031-inch wall tubing shall
be used in the overall actuation line.
High pressure nitrogen tubing (P/N 87-120045-00X) may be used in place of copper tubing, not to exceed a maximum length of 30 feet (9 m).
In every system, either single cylinder or multiple cylinder, a 1/8-inch NPT plug or vent check (P/N WK-877810000) shall be used in the outlet port of the last System Valve Actuator(s) in the actuation line.
A maximum of 2 Pressure Switches (P/N 486536) may be used in the actuation line.

SYSTEM NITROGEN CARTRIDGE, P/N 87-120043-001
The XV Control System uses a nitrogen cartridge for actuating the system cylinders and is charged with dry nitrogen
(see Figure 2). The cartridge is mounted inside the XV Control System to protect it from tampering and provides the
date of manufacturing and space (gray band) for recording the installation date.
5-1/8 in.
(130 mm)

1-9/16 in.
(40 mm)

GRAY BAND

Figure 2. System Nitrogen Cartridge,
P/N 87-120043-001
TEST CARTRIDGE, P/N 87-120044-001
The Test Cartridge is used for functional testing of the Kidde WHDR Wet Chemical System and IND Dry Chemical
System*. The cartridge has a red band and is labeled “TEST CARTRIDGE” as shown in Figure 3.
*Note: The System Nitrogen Cartridge P/N 87-120043-001 is required for actuation and full discharge or "puff" tests,
and when a time delay is included (as in systems protecting Vehicle Spray Booths).

4 in.
(102 mm)
1 in.
(25 mm)

Figure 3. Test Cartridge, P/N 87-120044-001

-3-

SYSTEM VALVE ACTUATOR (SVA), P/N 87-120042-001
A System Valve Actuator (SVA) must be mounted to every system cylinder valve assembly (see Figure 4). The SVA
has ports for low profile tubing runs, and is also equipped with a spring loaded plunger that locks the piston in the
discharged position, ensuring complete discharge of the cylinder(s) contents.
5/16-18 UNC
THROUGH HOLE (TYP)
(NOT SHOWN)
1/8 in.
NPT PORT
1-3/4 in.
(44 mm)

1/8 in. NPT PLUG
(IF APPLICABLE)

SVA PISTON IN
SET POSITION

SPRING LOADED
PLUNGER

PISTON IN ACTUATED
POSITION (TOWARDS
CYLINDER VALVE)

Figure 4. System Valve Actuator (SVA), P/N 87-120042-001
HIGH-PRESSURE NITROGEN TUBING, P/N 87-120045-00X
The High-Pressure Nitrogen Tubing is used to connect the XV Control System to the SVA on all installations in which
the XV Control System is mounted to a wet or dry chemical cylinder. (see Figure 5). A 1/8-inch NPT (male) x 3/8-24 JIC
Adapter is included with the High Pressure Nitrogen Tubing.

1/8 in. NPT
THREAD

SEAT

1/2 in. HEX,
1/4 in. 37 DEGREE
FLARE, SWIVEL

1/8 in. NPT
(MALE) x 3/8-24
JIC ADAPTER

A
(END TO SEAT)

Figure 5. External Tubing for XV Control System, P/N 87-120045-00X
Table 5. External Tubing for XV Control System
Part Number

Length "A"

87-120045-001

7-1/2 in. (191 mm)

87-120045-002

24 in. (610 mm)

87-120045-003

60 in. (1524 mm)

-4-

SOLENOID, P/N 83-100034-001

WIRE TYPE KEY

An optional solenoid can be installed into the XV Control
System, just under the actuation latch. The solenoid
operates directly on the actuation latch to activate the
system. This installation allows simultaneous usage of
mechanical detection lines, or the lines can be locked
out. The solenoid includes two mounting bolts, the
bracket and a push plate which mounts onto the solenoid
body (Figure 6). The solenoid coil is 24 Vdc at 1.5 Amp
and at 70°F (21°C). Refer to Figure 7 for Release Wiring with
Terminal Type Microswitch.

MICROSWITCH (INTERNAL)
ALARM WIRES FROM
CONTROL PANEL

XV SOLENOID
P/N 83-100034-001

24 VDC ONLY

RELEASING CIRCUIT
IN COMPATIBLE CONTROL
PANEL (24 VDC ONLY)
SPLICE SOLENOID LEAD
TO RELEASING CIRCUIT

9/64 in. ALLEN SCREWS (2)

MOUNTING BRACKET
(DO NOT REMOVE)

OPEN TERMINAL 2
TERMINAL 2 NOT USED

FLAG ENGAGED
BY XV

ATTACH SOLENOID LEAD TO
TERMINAL 1 OF MICROSWITCH

When actuating the XV Control System with an optional
solenoid, a UL Compatible and Listed fire control panel
with a supervised power supply is required, such as the
Kidde AEGIS or Kidde ARIES.
PUSH PLATE
(DO NOT REMOVE)

ALARM WIRES TO XV
SOLENOID AND/OR OTHER
DEVICES

ATTACH RELEASING CIRCUIT TO
TERMINAL 4 OF MICROSWITCH

COMMON
TERMINAL 1

CLOSED TERMINAL 4

SWITCH POSITION WHEN XV FLAG/CAM IS IN SET POSITION

Figure 7. Release Wiring with Terminal Type Microswitch
Note:

ELECTRICAL LEADS
24 in. (610 mm)

SOLENOID BODY

Figure 6. Solenoid, P/N 83-100034-001

Where electric detection and/or actuation is provided, supervision shall be provided in accordance with NFPA 72, National Fire Alarm and
Signaling Code. Alarms and indicators, along
with a supervised power source, shall be provided in accordance with NFPA 72. Electrical wiring and equipment shall be provided in
accordance with NFPA 70, National Electric
Code. All installations are subject to the approval
of the Authority Having Jurisdiction (AHJ).

KEEPER PIN, P/N 60-9197108-000
The Keeper Pin (P/N 60-9197108-000) is used to prevent
actuation while installing the system.

Figure 8. Keeper Pin, P/N 60-9197108-000

-5-

ORDERING INFORMATION
Description
XV Control System includes:
(1) 87-120042-001 System Valve Actuator
(1) 87-120043-001 System Nitrogen Cartridge
(1) 87-120044-001 Test Cartridge
(1) 87-120058-001 EMT Connector Kit
(1) 87-120039-001 Microswitch Kit
(1) 87-120039-501 Microswitch Kit

87-120099-002

System Valve Actuator

87-120042-001

System Nitrogen Cartridge

87-120043-001

Test Cartridge

87-120044-001

High Pressure Hose for Cylinder Mount

87-120045-001

EMT Connector Kit

87-120058-001

Solenoid Electric Actuator Kit

83-100034-001

Microswitch Kit (SPDT), Solid Color Leads

87-120039-001

Microswitch Kit (SPDT), Striped Color Leads

87-120039-501

Terminal Type Microswitch Kit (SPDT)

87-120047-001

REFERENCE INFORMATION
•
•

Part Number

WHDR Systems designed and installed according to
manual P/N 87-122000-001.
IND Systems designed and installed according to
manual P/N 220423.
MOUNTING
HOLE

•

Vehicle Spray Booth Systems designed and installed
according to manual P/N 83-100036-001.

MOUNTING
HOLE

5-1/2 in.
(140 mm)

TO OPERATE

PULL PIN

9-3/4”
(248 mm)

7-5/8 in.
(194 mm)

TURN HANDLE

FIRE SUPPRESSION SYSTEM

3/4 in.
(19 mm)
MOUNTING
HOLE

1-5/16 in.
(34 mm)

4-3/8 in.
(112 mm)

8-1/2”
(216 mm)

3-3/4”
(95 mm)
MOUNTING
HOLE

Figure 9. XV Control System Dimensions
Kidde is a registered trademark of Kidde-Fenwal, Inc.
WHDR, IND, XV, AEGIS, and ARIES are trademarks of Kidde-Fenwal,

This literature is provided for informational purposes only. KIDDE-FENWAL, INC.
assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular question, contact
KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
K-87-027 Rev AG

© 2013 Kidde-Fenwal Inc.

400 Main Street
Ashland, MA 01721
Tel.: 508-881-2000
Fax: 508-881-8920
www.kiddefiresystems.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Author                          : Anita.Tsiagras
Create Date                     : 2007:01:16 09:11:07Z
Modify Date                     : 2013:07:22 17:33:30-04:00
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Format                          : application/pdf
Creator                         : Anita.Tsiagras
Title                           : K-87-027.fm
Creator Tool                    : FrameMaker 9.0
Metadata Date                   : 2013:07:22 17:33:30-04:00
Producer                        : Acrobat Distiller 10.1.5 (Windows)
Document ID                     : uuid:aaf6b670-be3a-4c79-8d91-8648e86c0731
Instance ID                     : uuid:ce21375d-e8ee-43f3-bbaa-bdacdcf63d2f
Page Layout                     : SinglePage
Page Mode                       : UseNone
Page Count                      : 6
EXIF Metadata provided by EXIF.tools

Navigation menu