Kidde XV™ Control System
P/N: 87-120099-002
FEATURES
For Use in:
•WHDR
Commercial Cooking Fire
Suppression Systems
•IND
Industrial Fire Suppression Systems
Pneumatic Release of up to 20 Agent Cylinders
Two Discrete Mechanical Detection Lines
Cylinder or Wall Mount
Up to 400 ft. Mechanical Detection Cable
Operates 2 Gas Valves
Available 24 V Electrical Actuation
Multiple Remote Release Options
Rugged, Die-Cast Aluminum Body
Tamper/Lock Port for Cover
Easy to Install and Maintain
UL & ULC Listed
FM Approved for IND Systems
DESCRIPTION
The Kidde XV Control System is a compact, versatile unit
used to actuate agent cylinders on Kidde WHDR and IND
Pre-Engineered fire suppression systems. The control
head can be operated via:
Two Distinct Automatic Mechanical Detection Lines
(fusible links or thermo-bulb links)
Optional Electrical Solenoid
Remote or Local Manual Mechanical Control
Upon actuation, the XV Control System discharges the
nitrogen System Cartridge, pressurizing the actuation
lines and System Valve Actuators (SVA) mounted on the
cylinder valve(s). The SVA(s) open the cylinder valve(s),
discharging the WHDR wet chemical or IND dry chemical
suppression agent. The XV can be mounted on a wall or
directly to an SVA mounted on the cylinder.
The XV Control System is UL and ULC Listed with
WHDR Wet Chemical and IND Dry Chemical Fire
Suppression Systems. The XV is FM approved with the
IND Dry Chemical Systems.
The XV comes ready to install, with three EMT
connectors, one System Valve Actuator (SVA), two
microswitches, one nitrogen System Cartridge, and one
nitrogen test cartridge.
Figure 1. XV Control System, P/N 87-120099-002
- 2 -
TECHNICAL DATA
NOTES
1. Braided high pressure nitrogen tubing (P/N 87-120045-00X), is required to connect the XV Control System to the
System Valve Actuator (SVA) when the XV Control System is cylinder mounted.
2. Copper tubing shall be 1/4-inch O.D. x 0.031-inch wall high pressure tubing.
3. When Control System is cylinder mounted and two or more cylinders are being actuated, a minimum of 5 ft.
(1.52 m) of 1/4-inch O.D. x 0.031-inch wall tubing shall be used for actuation lines.
Table 1. Mechanical Cable Parameters for WHDR & IND Systems
XV Cable Line Max. Cable
Length
Max. Corner
Pulleys
Max.
Detectors
Max. Tee
Pulleys
Detection and Manual Release-to-Trip Line 1 200 ft. (60.96 m) 50 40 *
Detection and Manual Release-to-Trip Line 2 200 ft. (60.96 m) 50 40 *
Pull-to-Trip Remote Manual Release Line 100 ft. (30.48 m) 30 - 1*
Mechanical Gas Valve Line 100 ft. (30.48 m) 30 - 1*
*Tee pulleys count as two Corner Pulleys. Maximum is from XV Control, through the pulley, to each device.
Table 2. Actuation Parameters for WHDR Wet Chemical Systems
Operating
Temperature
Range
Number of
Extinguishing
System Cylinders
Maximum Total Length
Copper Actuation Tubing
Minimum Total Length of Copper
Actuation Tubing
0°F to 120°F
(-18°C to 49°C)
1-12 106 ft. (32.30 m) 5 ft. (1.52 m)
13-20 91 ft. (27.73 m)
Table 3. Actuation Parameters for IND Industrial Dry Chemical and Open-Face Spray Booth Systems
Operating
Temperature
Range
Number of
Extinguishing
System Cylinders
Maximum Total Length
Copper Actuation Tubing
Minimum Total Length of Copper
Actuation Tubing
-40°F to 120°F
(-40°C to 49°C)
1-14 166 ft. (50.60 m) 5 ft. (1.52 m)
15-20 121 ft. (36.88 m)
Table 4. Actuation Parameters for IND Dry Chemical for Vehicle Spray Booths
Operating
Temperature
Range
Number of
Extinguishing
System Cylinders
Maximum Total Length
Copper Actuation Tubing
Minimum Total Length of Copper
Actuation Tubing
0°F to 120°F
(-18°C to 49°C)
1-8 200 ft. (60.96 m)
5 ft. (1.52 m)9-15 160 ft. (48.76 m)
16-20 140 ft. (42.67 m)
- 3 -
4. When Control System is wall mounted, a minimum of 5 ft. (1.52 m) of 1/4-inch O.D. x 0.031-inch wall tubing shall
be used in the overall actuation line.
5. High pressure nitrogen tubing (P/N 87-120045-00X) may be used in place of copper tubing, not to exceed a max-
imum length of 30 feet (9 m).
6. In every system, either single cylinder or multiple cylinder, a 1/8-inch NPT plug or vent check (P/N WK-877810-
000) shall be used in the outlet port of the last System Valve Actuator(s) in the actuation line.
7. A maximum of 2 Pressure Switches (P/N 486536) may be used in the actuation line.
SYSTEM NITROGEN CARTRIDGE, P/N 87-120043-001
The XV Control System uses a nitrogen cartridge for actuating the system cylinders and is charged with dry nitrogen
(see Figure 2). The cartridge is mounted inside the XV Control System to protect it from tampering and provides the
date of manufacturing and space (gray band) for recording the installation date.
Figure 2. System Nitrogen Cartridge,
P/N 87-120043-001
TEST CARTRIDGE, P/N 87-120044-001
The Test Cartridge is used for functional testing of the Kidde WHDR Wet Chemical System and IND Dry Chemical
System*. The cartridge has a red band and is labeled “TEST CARTRIDGE” as shown in Figure 3.
*Note: The System Nitrogen Cartridge P/N 87-120043-001 is required for actuation and full discharge or "puff" tests,
and when a time delay is included (as in systems protecting Vehicle Spray Booths).
Figure 3. Test Cartridge, P/N 87-120044-001
5-1/8 in.
(130 mm)
1-9/16 in.
(40 mm)
GRAY BAND
4 in.
(102 mm)
1 in.
(25 mm)
- 4 -
SYSTEM VALVE ACTUATOR (SVA), P/N 87-120042-001
A System Valve Actuator (SVA) must be mounted to every system cylinder valve assembly (see Figure 4). The SVA
has ports for low profile tubing runs, and is also equipped with a spring loaded plunger that locks the piston in the
discharged position, ensuring complete discharge of the cylinder(s) contents.
Figure 4. System Valve Actuator (SVA), P/N 87-120042-001
HIGH-PRESSURE NITROGEN TUBING, P/N 87-120045-00X
The High-Pressure Nitrogen Tubing is used to connect the XV Control System to the SVA on all installations in which
the XV Control System is mounted to a wet or dry chemical cylinder. (see Figure 5). A 1/8-inch NPT (male) x 3/8-24 JIC
Adapter is included with the High Pressure Nitrogen Tubing.
Figure 5. External Tubing for XV Control System, P/N 87-120045-00X
Table 5. External Tubing for XV Control System
Part Number Length "A"
87-120045-001 7-1/2 in. (191 mm)
87-120045-002 24 in. (610 mm)
87-120045-003 60 in. (1524 mm)
1/8 in. NPT PLUG
(IF APPLICABLE)
5/16-18 UNC
THROUGH HOLE (TYP)
(NOT SHOWN)
PISTON IN ACTUATED
POSITION (TOWARDS
CYLINDER VALVE)
1-3/4 in.
(44 mm)
SPRING LOADED
PLUNGER
1/8 in.
NPT PORT
SVA PISTON IN
SET POSITION
1/8 in. NPT
THREAD
1/2 in. HEX,
1/4 in. 37 DEGREE
FLARE, SWIVEL
A
(END TO SEAT)
SEAT
1/8 in. NPT
(MALE) x 3/8-24
JIC ADAPTER
- 5 -
SOLENOID, P/N 83-100034-001
An optional solenoid can be installed into the XV Control
System, just under the actuation latch. The solenoid
operates directly on the actuation latch to activate the
system. This installation allows simultaneous usage of
mechanical detection lines, or the lines can be locked
out. The solenoid includes two mounting bolts, the
bracket and a push plate which mounts onto the solenoid
body (Figure 6). The solenoid coil is 24 Vdc at 1.5 Amp
and at 70°F (21°C). Refer to Figure 7 for Release Wiring with
Terminal Type Microswitch.
When actuating the XV Control System with an optional
solenoid, a UL Compatible and Listed fire control panel
with a supervised power supply is required, such as the
Kidde AEGIS or Kidde ARIES.
Figure 6. Solenoid, P/N 83-100034-001
Figure 7. Release Wiring with Terminal Type Microswitch
Note: Where electric detection and/or actuation is pro-
vided, supervision shall be provided in accor-
dance with NFPA 72, National Fire Alarm and
Signaling Code. Alarms and indicators, along
with a supervised power source, shall be pro-
vided in accordance with NFPA 72. Electrical wir-
ing and equipment shall be provided in
accordance with NFPA 70, National Electric
Code. All installations are subject to the approval
of the Authority Having Jurisdiction (AHJ).
KEEPER PIN, P/N 60-9197108-000
The Keeper Pin (P/N 60-9197108-000) is used to prevent
actuation while installing the system.
Figure 8. Keeper Pin, P/N 60-9197108-000
ELECTRICAL LEADS
24 in. (610 mm)
MOUNTING BRACKET
(DO NOT REMOVE)
PUSH PLATE
(DO NOT REMOVE)
SOLENOID BODY
9/64 in. ALLEN SCREWS (2)
FLAG ENGAGED
BY XV
TERMINAL 2 NOT USED
OPEN TERMINAL 2
ATTACH SOLENOID LEAD TO
TERMINAL 1 OF MICROSWITCH
COMMON
TERMINAL 1
ATTACH RELEASING CIRCUIT TO
TERMINAL 4 OF MICROSWITCH
CLOSED TERMINAL 4
SPLICE SOLENOID LEAD
TO RELEASING CIRCUIT
RELEASING CIRCUIT
IN COMPATIBLE CONTROL
PANEL ( )24 VDC ONLY
XV SOLENOID
P/N 83-100034-001
24 VDC ONLY
SWITCH POSITION WHEN FLAG/CAM IS IN SET POSITIONXV
ALARM WIRES TO
SOLENOID AND/OR OTHER
DEVICES
XV
WIRE TYPE KEY
MICROSWITCH (INTERNAL)
ALARM WIRES FROM
CONTROL PANEL
This literature is provided for informational purposes only. KIDDE-FENWAL, INC.
assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular question, contact
KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
K-87-027 Rev AG © 2013 Kidde-Fenwal Inc.
400 Main Street
Ashland, MA 01721
Tel.: 508-881-2000
Fax: 508-881-8920
www.kiddefiresystems.com
9-3/4”
(248 mm)
8-1/2”
(216 mm)
3-3/4”
(95 mm)
TO OPERATE
PULL PIN
TURN HANDLE
FIRE SUPPRESSION SYSTEM
ORDERING INFORMATION
Description Part Number
XV Control System includes:
(1) 87-120042-001 System Valve Actuator
(1) 87-120043-001 System Nitrogen Cartridge
(1) 87-120044-001 Test Cartridge
(1) 87-120058-001 EMT Connector Kit
(1) 87-120039-001 Microswitch Kit
(1) 87-120039-501 Microswitch Kit
87-120099-002
System Valve Actuator 87-120042-001
System Nitrogen Cartridge 87-120043-001
Test Cartridge 87-120044-001
High Pressure Hose for Cylinder Mount 87-120045-001
EMT Connector Kit 87-120058-001
Solenoid Electric Actuator Kit 83-100034-001
Microswitch Kit (SPDT), Solid Color Leads 87-120039-001
Microswitch Kit (SPDT), Striped Color Leads 87-120039-501
Terminal Type Microswitch Kit (SPDT) 87-120047-001
MOUNTING
HOLE
MOUNTING
HOLE
MOUNTING
HOLE
5-1/2 in.
(140 mm)
7-5/8 in.
(194 mm)
4-3/8 in.
(112 mm)
1-5/16 in.
(34 mm)
3/4 in.
(19 mm)
MOUNTING
HOLE
REFERENCE INFORMATION
WHDR Systems designed and installed according to
manual P/N 87-122000-001.
IND Systems designed and installed according to
manual P/N 220423.
Vehicle Spray Booth Systems designed and installed
according to manual P/N 83-100036-001.
Figure 9. XV Control System Dimensions