Kidde Engineered Fire
Suppression System

A UTC Fire & Security Company

Designed for use with 3M™ Novec 1230™ Fire Protection Fluid

Effective: April 2008
K-45-9049

Explosion Proof Solenoid,
Electric Control Head Data Sheet
FEATURES
•

•
•

Explosion Proof:
– UL Listed as Suitable for Hazardous Locations
Class I Div 1 Groups C and D
Class II Div 1 Groups E, F and G
FM Approved
Compatible with UL Listed and FM Approved
Suppression Systems:
– FM-200® Systems, Including the ADS
– Carbon Dioxide Systems
– FE-13™ Systems

•

•
•
•

•
•

Operated By:
– Control Panel
– Mechanical Manual Actuator
Nominal 24 Vdc Operation
Low Current Consumption
Operates:
– Cylinder Valves
– Stop Valves
– Directional Valves
Wide Operating Temperature Range
Rugged Brass Body

P/N: 81-100000-001
DESCRIPTION
The Explosion Proof Control Head is designed to operate
FM-200 , ADS, Carbon Dioxide and FE-13™ cylinder
valves, stop valves and directional valves. The Explosion
Proof Control Head can be operated electronically from
the Detection and Control system, or by local manual
operation via an affixed manual control head. The Explosion Proof Control Head has a continuous current draw,
which must be accommodated for at the Control Panel.
The actuating pin latches in the released position and
must be mechanically reset prior to re-arming the system.
®

A suitable Control Panel, Listed and/or Approved for use
with the Explosion Proof Control Head, shall be provided
for supervision of the releasing circuit per NFPA requirements.
The Explosion Proof Control Head is designed and rated
for use in the following hazardous areas: Class I Division
1 Group C and D and Class II Division 1 Group E, F and
G.

INSTALLATION
The Explosion Proof Control Head can be mounted
directly on either the cylinder valve, stop/directional
valve.

WARNING

3.0 in.
(76 mm)

7.8 in. (198 mm)

Figure 1. Assembly Drawing

Care should be taken to ensure that
the actuating pin is in the set position
when attaching the control head to the
cylinder or the stop/directional valve.
Accidental system discharge could
occur, which could cause property
damage, personal injury and/or death.

Tighten the swivel nut securely in place.

When installing the Explosion Proof Control Head in hazardous locations, wiring connections must be terminated
in explosion proof junction boxes.
The lead wires must be connected using the indicated
polarity (red to positive, black to negative) in order to
obtain correct operation.

MAINTENANCE
Regular scheduled maintenance should be performed on
the Explosion Proof Control Head to ensure that the unit
operates correctly if and when required.

SPECIFICATIONS
Part Number:
Applications:

81-100000-001
FM-200, ADS, Carbon Dioxide
and FE-13 Suppression Systems

Approval/Listing:
Releasing Device–
HazLoc–
HazLoc Ratings:

MONTHLY
The Explosion Proof Control Head should be inspected
for any signs of physical damage, deterioration, corrosion, distortion, cracks, dirt ingress and loose couplings.
Tighten any loose couplings. Replace damaged or missing caps. Replace control head if damage is found.
Ensure that all explosion proof control heads are in the
“set” position.
SEMI-ANNUALLY
The Explosion Proof Control Head should be tested for
proper operation.

WARNING

All Explosion Proof Control Heads
should be removed from agent cylinders (Carbon Dioxide, FM-200 or FE13) to avoid accidental system discharge, which could cause property
damage, personal injury and/or death.

Operating Voltage:
Current Draw:
At 24 Vdc–
At 30 Vdc–
Wiring Connections:
Wire Size–
Lead Length–
Ambient Temperature:
Construction:
Material–
Weight–
Dimensions:

This literature is provided for informational purposes only. KIDDE-FENWAL, INC.
assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
© 2008 Kidde-Fenwal Inc.

Printed in USA

270 mA continuous
500 mA continuous
18 AWG
36 in. (914 mm)
-40°F to 130°F (-40°C to 55°C)
Brass body
8.1 lb. (3.7 kg)
3 in. D x 7.8 in. L
(76 mm D x 198 mm L)

ORDERING INFORMATION

Remove control heads from all master cylinders within
the hazard area being tested. Let the Explosion Proof
Control Head hang freely from the flexible electrical conduit connections. Operate the Explosion Proof Control
Head, either by actuation at the system control panel or
via manual operation of an electric pull station. Ensure
that the control head has operated. Observe that the
actuating pin has moved to the fully released position. If
any control heads have not operated, check circuit for
electric continuity. Replace all damaged control heads.
Repeat operation test if any control heads have been
replaced. Replace any damaged control head, which fails
to reset properly. Make certain that electric control heads
are in the set position before reconnecting to agent cylinders. Reattach all control heads to threaded ports on cylinder valves and tighten swivel nuts securely.

K-45-9049 Rev AC

UL, FM
UL, FM
Class I Division 1 Group C
and D
Class II Division 1 Group E, F
and G
18 Vdc @ 0.20 A to
30 Vdc @ 0.50 A

Part Number

Description

81-100000-001

Explosion Proof Solenoid
(Electric Control Head)

870652

Mechanical Manual Actuator

81-129958-001

Reset Tool Assembly

A UTC Fire & Security Company
400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
www.kiddefiresystems.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Page Mode                       : UseNone
XMP Toolkit                     : 3.1-701
Producer                        : Acrobat Distiller 7.0 (Windows)
Creator Tool                    : FrameMaker 7.1
Modify Date                     : 2008:04:11 10:34:18Z
Create Date                     : 2007:01:16 09:11:07Z
Format                          : application/pdf
Title                           : K-45-9049.fm
Creator                         : Bernice.Parker
Document ID                     : uuid:f7f5719f-4182-47b9-bfdf-dcf569edb9c9
Instance ID                     : uuid:f2eb15f8-fa1e-4689-871e-5b3b6bd5eaf8
Page Count                      : 2
Author                          : Bernice.Parker
EXIF Metadata provided by EXIF.tools

Navigation menu