Kidde Fire Systems Smoke Alarm K 73 06 Users Manual

2015-02-09

: Kidde-Fire-Systems Kidde-Fire-Systems-Kidde-Fire-Systems-Smoke-Alarm-K-73-06-Users-Manual-568183 kidde-fire-systems-kidde-fire-systems-smoke-alarm-k-73-06-users-manual-568183 kidde-fire-systems pdf

Open the PDF directly: View PDF PDF.
Page Count: 2

Effective: March 2013
K-73-06
LHS
Linear Heat Sensor
FEATURES
Fixed Temperature Digital Heat Detector
Five Alarm Temperatures Available: 142°F - 158°F,
180 °F, 220°F, 350°F, 452°F
Compatible with All Fire Control Panels
Connect Directly to Initiating Circuit
Cost-Effective Solution for Hazardous Locations
Ideal for Use in Applications Where Spot-Type
Heat Detectors are Unsuitable
Fire Zone Location Using LHS with
SmartOne®-compatible panels
FM Approved
DESCRIPTION
The LHS™ Linear Heat Sensor cable is a flexible, dura-
ble and cost-effective fixed-temperature fire detector,
suitable for protecting a wide range of commercial and
industrial fire applications.
LHS is a small diameter cable capable of detecting heat
from a fire over its entire length. The sensor cable con-
sists of a twisted pair of 19 AWG copper coated steel
conductors covered by a temperature sensitive insula-
tion, and protected by either a plastic braid or jacket for
various environmental applications.
The LHS Linear Heat Sensor is Factory Mutual Approved
and is designed for open area as well as proximity detec-
tion. A wide range of jackets and operating temperatures
are available for proper system design, including con-
fined areas or harsh environments which prohibit the use
of other forms of detection. LHS is compatible with any
fire control panel that is capable of accepting contact clo-
sure type initiating devices.
APPLICATIONS
Open Area Protection
Belt Conveyers
• Tunnels
Aircraft Hangars
Cable Trays
Floating Roof Tanks
Classified Hazardous Areas (when used with intrinsic
safety barriers)
OPERATION
The heat from a fire causes the LHS cable’s special insu-
lation to melt at a specific temperature, allowing the two
conductors to short together, thus creating an alarm con-
dition on the fire control panel. The LHS cable may also
be used as a stand-alone contact device. The LHS nor-
mal operating state is an open circuit. For installation
details refer to “LHS Installation Instructions” (73-202).
Jacket
Thermoplastic strip
braid, PVC, nylon, or
fluoropolymer
Insulation
Temperature-sensitive
thermoplastic or
fluoropolymer
Conductor
Tinned
copper-covered
steel
400 Main Street
Ashland, MA 01721
Tel.: 508-881-2000
Fax: 508-881-8920
www.kiddefiresystems.com
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes
no responsibility for the product’s suitability for a particular application. The product must be
properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or question,
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
K-73-06 Rev AC © 2013 Kidde-Fenwal Inc.
SmartOne and Kidde are registered trademarks of Kidde-Fenwal, Inc. LHS is a trademark of Kidde-Fenwal, Inc.
FIRE ZONE LOCATION WITH LHS
An Intelligent Linear Heat Detection System is recom-
mended for applications where fire zone location requires
zone output control for notification appliances, HVAC
control, suppression control and annunciation. In this sys-
tem, each discrete addressable LHS cable zone will
report an individual alarm to the SmartOne®-compatible
fire control panel.
Addressable LHS cable zones are created by attaching
each LHS cable zone to an Addressable Input module
(P/N 70-407008-001). Each discrete LHS cable zone
location can be displayed on the SmartOne-compatible
panel 80-character LCD display with programmable text
zone description. Up to 255 devices (any mix of devices
including smoke detectors, manual pull stations, water-
flow switches, LHS zones, etc.) can be connected to a
single SmartOne-compatible’s addressable loop.
Installing an Intelligent Linear Heat Detection System
results in substantial installation cost savings over tradi-
tional hard-wired linear heat detection systems.
Table 1: LHS Sensor Cable Specifications
Part Number:
656 ft (200 m) length roll
3,280 ft (1000 m) length roll 73-200000-011
73-201000-011 73-200000-012
73-201000-012 73-200000-003
73-201000-003 73-200000-004
73-201000-004 73-200000-005
73-201000-005
Alarm Temperature Range 145-158ºF
(63-70ºC) 180ºF
(82ºC) 220ºF
(105ºC) 350ºF
(177ºC) 452F
(233ºC)
Ambient Storage Temp.* Up to 113ºF (45ºC) Up to 158ºF (70ºC) Up to 221ºF (105ºC) Up to 392ºF (200ºC)
Min. Installation Temp. 5ºF (-15ºC) 32ºF (0ºC) -4ºF (-20ºC)
Min. Operating Temp.** -40ºF (-40ºC) -22ºF (-30ºC) -40ºF (-40ºC) -58ºF (-50ºC)
Application Indoor/Outdoor Indoor/Outdoor Indoor/Outdoor Indoor/Outdoor Indoor/Outdoor
Approved Spacing 20 ft (6m) max Proximity Detection
Flame Detection 5 seconds (max) 12 seconds (max) 20 seconds (max)
Outer Jacket Material Nylon Nylon PVC FEP
Outer Jacket Color Black
Marked H8040N Black
Marked H8045N Black Red White
Conductor Insulation EVA Polythene Polypropylene FEP
Conductor Color 1 Black
1 Red 1 Black
1 Black/White 1 Black
1 White
External Diameter 0.13 in. (3.35 mm) 0.13 in. (3.35 mm) 0.17 in. (4.35 mm) 0.17 in. (4.35 mm) 0.14 in. (3.5 mm)
Electrical Rating 1 Amp maximum, 110 Vdc maximum
Conductor Resistance 30.48 ohms/1000 ft. @ 68ºV (100 ohms/1000 m) @ 20ºC
Conductor Capacitance 20.21 pF/ft.
(66.32 pF/m) 25.42 pF/ft.
(83.31 pF/m) 19.96 pF/ft.
(65.48 pF/m) 17.52 pF/ft.
(57.48 pF/m) 19.22 pF/ft.
(63.07 pF/m)
Insulation Rating 1000 megohm per 3280 ft. (1000 m) after 1 minute @ 500 Vdc Minimum
Weight 10.65 lb./1000 ft.
(15.85 kg/km) 10.65 lb./1000 ft.
(15.85 kg/km) 15.25 lb./1000 ft.
(22.7 kg/km) 12.67 lb./1000 ft.
(18.85 kg/km) 14.65 lb./1000 ft.
(21.8 kg/km)
*Do not store in direct sunlight. **When not subjected to vibration.

Navigation menu