Kohler 100Efoz 125Eoz Users Manual Kfc
23EFOZ28EOZ to the manual 5c7f0fd8-af57-4032-ab34-3aaba29f438e
2015-01-21
: Kohler Kohler-100Efoz-125Eoz-Users-Manual-220075 kohler-100efoz-125eoz-users-manual-220075 kohler pdf
Open the PDF directly: View PDF .
Page Count: 92
Download | ![]() |
Open PDF In Browser | View PDF |
Installation Marine Generator Sets Models: 3.5EFOZ/4EOZ, 4EFOZ/5EOZ 6.5EFOZ/8EOZ, 8.5EFOZ, 9EFOZ/10EOZ 11EFOZ/13EOZ, 11.5EFOZ/14EOZ 13EFOZ/15.5EOZ, 16EFOZ/20EOZ 17.5EFOZ/20EOZ, 19EFOZ/23EOZ 20EFOZ/24EOZ, 23EFOZ/28EOZ 27EFOZ/32EOZ, 33EFOZ/40EOZ 40EFOZ/50EOZ, 55EFOZ/65EOZ 70EFOZ/80EOZ, 80EFOZ/99EOZ 100EFOZ/125EOZ, 125EFOZ/150EOZ TP-6069 6/03d Table of Contents Safety Precautions and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I Section 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Section 2 Location and Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1 General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 3 3 Section 3 Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1 Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2 Cooling System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.1 Intake Through-Hull Strainer (Seacock Cover) . . . . . . . . . . . . . . . . . . . . . 3.2.2 Seacock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.3 Seawater Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.4 Water Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.5 Closed Heat Exchanger (4--125EFOZ/5--150EOZ Models) . . . . . . . . . . 3.2.6 Direct Water Cooled (3.5EFOZ/4EOZ Models) . . . . . . . . . . . . . . . . . . . . . 5 5 5 5 6 6 6 6 6 Section 4 Exhaust System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2 Exhaust Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3 Exhaust System Location, Mounting, and Installation . . . . . . . . . . . . . . . . . . . . . . . 4.3.1 Above-Waterline Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.2 Mid/Below-Waterline Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 11 11 12 12 14 Section 5 Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1 Fuel Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2 Fuel Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3 Fuel Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.4 Fuel Pump Lift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5 Fuel Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 17 18 18 18 18 Section 6 Electrical System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1 AC Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2 Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.1 Circuit Breaker Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.2 Circuit Breaker Installation (4--27EFOZ and 5--32EOZ Models) . . . . . . 6.2.3 Circuit Breaker Installation (33--125EFOZ and 40--150EOZ Models) . . 6.3 Installation In Steel or Aluminum Vessels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4 Installation Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.5 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.6 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.7 Remote Start Switch Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 19 19 19 21 22 23 23 24 24 25 Section 7 Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Section 8 Reconnection/Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1 Four-Lead Reconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1.1 100--120-Volt Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1.2 100--120/200--240-Volt Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1.3 200--240-Volt Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.2 Twelve-Lead Reconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.3 Decision-Maker 3+ Controller Overvoltage Shutdown Adjustment . . . . . . . . . . . . 8.4 Voltage Regulator Adjustment (4--27EFOZ and 5--32EOZ Models) . . . . . . . . . . . 67 67 67 67 68 68 69 72 Appendix A Generator Selection and Wattage Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1 Appendix B Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2 Appendix C Generator Set Output Ratings Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4 TP-6069 6/03 Table of Contents Safety Precautions and Instructions IMPORTANT SAFETY INSTRUCTIONS. Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS. This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice. DANGER Danger indicates the presence of a hazard that will cause severe personal injury, death, or substantial property damage. WARNING Warning indicates the presence of a hazard that can cause severe personal injury, death, or substantial property damage. CAUTION Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage. NOTICE Notice communicates installation, operation, or maintenance information that is safety related but not hazard related. Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals. TP-6069 6/03 Accidental Starting WARNING Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Place the generator set start/stop switch in the STOP position. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch. Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set on/off button to shut down the generator set. All indicator lamps dim. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch. Battery WARNING Sulfuric acid in batteries. Can cause severe injury or death. Wear protective goggles and clothing. Battery acid may cause blindness and burn skin. Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid. Safety Precautions and Instructions I Battery acid cleanup. Battery acid can cause severe injury or death. Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area. Engine Backfire/Flash Fire Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases. Battery short circuits. Explosion can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together. II Safety Precautions and Instructions Exhaust System WARNING WARNING Fire. Can cause severe injury or death. Carbon monoxide. Can cause severe fainting, or death. Do not smoke or permit flames or sparks near fuels or the fuel system. The exhaust system must be leakproof and routinely inspected. Servicing the fuel system. A flash fire can cause severe injury or death. Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor. Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is a poisonous gas present in exhaust gases. Carbon monoxide poisoning symptoms include but are not limited to the following: D Light-headedness, dizziness D Physical fatigue, weakness in joints and muscles D Sleepiness, mental fatigue, inability to concentrate or speak clearly, blurred vision D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air. Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator set with the air cleaner/silencer removed. Combustible materials. A sudden flash fire can cause severe injury or death. Do not smoke or permit flames or sparks near the fuel system. Keep the compartment and the generator set clean and free of debris to minimize the risk of fire. Wipe up spilled fuels and engine oil. Combustible materials. A fire can cause severe injury or death. Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures. nausea, Copper tubing exhaust systems. Carbon monoxide can cause severe nausea, fainting, or death. Do not use copper tubing in diesel exhaust systems. Sulfur in diesel exhaust causes rapid deterioration of copper tubing exhaust systems, resulting in exhaust/water leakage. TP-6069 6/03 Inspecting the exhaust system. Carbon monoxide can cause severe nausea, fainting, or death. For the safety of the craft’s occupants, install a carbon monoxide detector. Consult the boat builder or dealer for approved detector location and installation. Inspect the detector before each generator set use. In addition to routine exhaust system inspection, test the carbon monoxide detector per the manufacturer’s instructions and keep the detector operational at all times. Operating the generator set. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Use the following precautions when installing and operating the generator set. Do not install the exhaust outlet where exhaust can be drawn in through portholes, vents, or air conditioners. If the generator set exhaust discharge outlet is near the waterline, water could enter the exhaust discharge outlet and close or restrict the flow of exhaust. Never operate the generator set without a functioning carbon monoxide detector. Be especially careful if operating the generator set when moored or anchored under calm conditions because gases may accumulate. If operating the generator set dockside, moor the craft so that the exhaust discharges on the lee side (the side sheltered from the wind). Always be aware of others, making sure your exhaust is directed away from other boats and buildings. Avoid overloading the craft. Fuel System WARNING The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly explosive. Use extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation. Draining the fuel system. Explosive fuel vapors can cause severe injury or death. Spilled fuel can cause an explosion. Use a container to catch fuel when draining the fuel system. Wipe up spilled fuel after draining the system. Installing the fuel system. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an explosion. Do not modify the tank or the propulsion engine fuel system. Equip the craft with a tank that allows one of the two pickup arrangements described in the installation section. The tank and installation must conform to USCG Regulations. Pipe sealant. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an explosion. Use pipe sealant on all threaded fittings to prevent fuel leakage. Use pipe sealant that resists gasoline, grease, lubrication oil, common bilge solvents, salt deposits, and water. Ignition-protected equipment. Explosive fuel vapors can cause severe injury or death. Gasoline vapors can cause an explosion. USCG Regulation 33CFR183 requires that all electrical devices (ship-to-shore transfer switch, remote start panel, etc.) must be ignition protected when used in a gasoline and gaseous-fueled environment. The electrical devices listed above are not ignition protected and are not certified to operate in a gasoline and gaseous-fueled environment such as an engine room or near fuel tanks. Acceptable locations are the wheelhouse and other living areas sheltered from rain and water splash. Hazardous Noise CAUTION Hazardous noise. Can cause hearing loss. Never operate the generator set without a muffler or with a faulty exhaust system. Engine noise. Hazardous noise can cause hearing loss. Generator sets not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set. Hazardous Voltage/ Electrical Shock WARNING Explosive fuel vapors. Can cause severe injury or death. Use extreme care when handling, storing, and using fuels. Hazardous voltage. Moving rotor. Can cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place. TP-6069 6/03 Safety Precautions and Instructions III CAUTION Welding the generator set. Can cause severe electrical equipment damage. Never weld components of the generator set without first disconnecting the battery, controller wiring harness, and engine electronic control module (ECM). Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution. Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect the generator set from the load by opening the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load. IV Safety Precautions and Instructions Welding the generator set. Can cause severe electrical equipment damage. Before welding the generator set perform the following steps: (1) Remove the battery cables, negative (--) lead first. (2) Disconnect all engine electronic control module (ECM) connectors. (3) Disconnect all generator set controller and voltage regulator circuit board connectors. (4) Disconnect the engine batterycharging alternator connections. (5) Attach the weld ground connection close to the weld location. Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment. Testing the voltage regulator. Hazardous voltage can cause severe injury or death. High voltage is present at the voltage regulator heat sink. To prevent electrical shock do not touch the voltage regulator heat sink when testing the voltage regulator. (PowerBoostt, PowerBoostt III, and PowerBoostt V voltage regulator models only) Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Connect the generator set to the building/marina electrical system only through an approved device and after the building/marina main switch is opened. Backfeed connections can cause severe injury or death to utility personnel working on power lines and/or personnel near the work area. Some states and localities prohibit unauthorized connection to the utility electrical system. Install a ship-to-shore transfer switch to prevent interconnection of the generator set power and shore power. Testing live electrical circuits. Hazardous voltage or current can cause severe injury or death. Have trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically. (600 volts and under) Hot Parts WARNING Hot coolant and steam. Can cause severe injury or death. Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure. WARNING Hot engine and exhaust system. Can cause severe injury or death. Do not work on the generator set until it cools. Checking the coolant level. Hot coolant can cause severe injury or death. Allow the engine to cool. Release pressure from the cooling system before removing the pressure cap. To release pressure, cover the pressure cap with a thick cloth and then slowly turn the cap counterclockwise to the first stop. Remove the cap after pressure has been completely released and the engine has cooled. Check the coolant level at the tank if the generator set has a coolant recovery tank. TP-6069 6/03 Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The engine and exhaust system components become extremely hot during operation. Moving Parts WARNING Hazardous voltage. Moving rotor. Can cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place. WARNING Rotating parts. Can cause severe injury or death. Operate the generator set only when all guards, screens, and covers are in place. Tightening the hardware. Flying projectiles can cause severe injury or death. Loose hardware can cause the hardware or pulley to release from the generator set engine and can cause personal injury. Retorque all crankshaft and rotor hardware after servicing. Do not loosen the crankshaft hardware or rotor thrubolt when making adjustments or servicing the generator set. Rotate the crankshaft manually in a clockwise direction only. Turning the crankshaft bolt or rotor thrubolt counterclockwise can loosen the hardware. Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death. Keep hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set. Sound shield removal. Exposed moving parts can cause severe injury or death. The generator set must be operating in order to perform some scheduled maintenance procedures. Be especially careful if the sound shield has been removed, leaving the belts and pulleys exposed. (Sound-shield-equipped models only) Notice WARNING NOTICE This generator set has been rewired from its nameplate voltage to Airborne particles. Can cause severe blindness. injury or Wear protective goggles and clothing when using power tools, hand tools, or compressed air. 246242 NOTICE Hardware damage. The engine and generator set may use both American Standard and metric hardware. Use the correct size tools to prevent rounding of the bolt heads and nuts. NOTICE When replacing hardware, do not substitute with inferior grade hardware. Screws and nuts are available in different hardness ratings. To indicate hardness, American Standard hardware uses a series of markings, and metric hardware uses a numeric system. Check the markings on the bolt heads and nuts for identification. NOTICE Electrostatic discharge damage. Electrostatic discharge (ESD) damages electronic circuit boards. Prevent electrostatic discharge damage by wearing an approved grounding wrist strap when handling electronic circuit boards or integrated circuits. An approved grounding wrist strap provides a high resistance (about 1 megohm), not a direct short, to ground. NOTICE Fuse replacement. Replace fuses with fuses of the same ampere rating and type (for example: 3AB or 314, ceramic). Do not substitute clear glass-type fuses for ceramic fuses. Refer to the wiring diagram when the ampere rating is unknown or questionable. NOTICE Saltwater damage. Saltwater quickly deteriorates metals. Wipe up saltwater on and around the generator set and remove salt deposits from metal surfaces. NOTICE Voltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer. TP-6069 6/03 Safety Precautions and Instructions V Notes VI Safety Precautions and Instructions TP-6069 6/03 Section 1 Introduction Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever. marine generator set. For operating instructions, refer to the operation manual. x:in:001:002:a Use the specification sheets as a guide in planning your installation. Use current dimension drawings and wiring diagrams. Marine generator set installations must comply with all applicable regulations and standards. The safe and successful operation of a marine power system depends primarily on the installation. See Figure 1-1. Use this manual as a guide to install the 2 1 17 3 16 KOHLER 15 4 14 5 13 9 8 6 12 11 7 10 585711 1. 2. 3. 4. 5. 6. 7. 8. 9. Exhaust mixer elbow (exhaust/water outlet) (not shown) Heat exchanger (not shown) Coolant recovery tank (located on the unit on some models) Seawater strainer * Seawater pump (seawater inlet) Seawater line * Seacock * Craft stringers Fuel feed pump (fuel inlet) * Figure 1-1 Fuel return line * Hose clamps Fuel supply line * Mounting tray (mounting skid on 33--150 kW models) Battery/battery storage box Battery cables Exhaust hose or exhaust line * Electrical leads (AC output leads/remote start panel leads) * Indicated components must conform to USCG regulations. Typical Generator Set Location and Mounting Note: See text for complete explanation of installation requirements. TP-6069 6/03 10. 11. 12. 13. 14. 15. 16. 17. Note: Use two hose clamps on each end of all flexible exhaust hose connections. Section 1 Introduction 1 Notes 2 Section 1 Introduction TP-6069 6/03 Section 2 Location and Mounting 2.1 General Considerations The key to installation is location. Before making final plans for locating a generator set, consider the following. Installation Location Considerations Allow clearance for vibration and cooling during operation. Allow a minimum of 38 mm (1.5 in.) clearance on all sides (top, front, rear, and sides) of a generator set without an optional sound shield. Refer to the instruction sheet for minimum clearances for sound-shielded units. Also, allow space for the power takeoff (PTO) option, if equipped. 1. Choose a location that allows adequate space for cooling and exhaust system installation, fuel system installation, ventilation, and service access to the generator set (engine and generator). Diesel generator sets are not ignition-protected. USCG Regulation 183.410 requires ignition-protected devices only in gasoline/gaseous-fueled environments. 2. Use craft stringers or other available structural members capable of supporting the generator set’s weight. 2.3 Mounting 3. Seal the generator set compartment from the cabin to prevent exhaust gases and fuel vapors from entering the cabin. See the current generator set specification sheet or Section 7 of this manual for generator set dimensions and weights. See Figure 1-1 for a typical installation. m:is:101:001 2.2 Location Locate the generator set to allow easy service access to the generator set’s engine, controller, cooling, and fuel system components. The engine compartment is often the ideal location for the generator set if the propulsion engine(s) does not obstruct access to the generator set and controller. Mount the generator set as high as possible to avoid contact with bilge splash and lower-lying vapors and to allow for downward pitch of the exhaust line toward the exhaust outlet. Craft stringers generally provide the best generator set support. Ensure that the structural members can support the generator set’s weight and withstand its vibration. The generator set includes vibration mounts and a mounting tray or skid. If desired, install additional vibration isolating pads underneath the generator set’s base. Use the four mounting holes in the mounting tray to mount the generator set securely to the craft. For angular operating limits, consult the operation manual. Marine Generator Set Installations in European Union Member Countries This generator set is specifically intended and approved for installation below the deck in the engine compartment. Installation above the deck and/or outdoors would constitute a violation of European Union Directive 2000/14/EC noise emission standard. TP-6069 6/03 Section 2 Location and Mounting 3 Notes 4 Section 2 Location and Mounting TP-6069 6/03 Section 3 Cooling System 3.1 Ventilation Engine combustion, generator cooling, and expulsion of flammable and lethal fumes require ventilation. Provide ventilation compliant with USCG Regulations governing sizing of vents and other considerations. 1 As a rule, size each inlet- and outlet-vent area to a minimum of 13 sq. cm/30.5 cm (2 sq. in. per ft.) of the craft’s beam. Should this rule conflict with USCG Regulations, follow USCG Regulations. For applications with screened inlets, double the size (4 sq. in. per ft.) of the hull/deck openings. Extend the vent ducts to bilges to expel heavier-than-air fumes. 2 3 4 For generator sets mounted in the engine compartment, increase the air flow to allow for the generator set’s requirements. Install optional detection devices to cause alarm, warning, or engine shutdown should dangerous fumes accumulate in the compartment. See the generator set specification sheet that shipped with the generator set for air requirements. The air intake silencer/cleaner provides combustion air to the engine. Do not compromise the recommended minimum clearance of 38 mm (1.5 in.) between a duct opening and enclosure wall. The engine/generator performance will decline if you compromise these guidelines. See Figure 3-1 for allowable intake restriction. Note: ISO 3046 derates apply. See Appendix C. Model Allowable Intake Restriction 3.5EFOZ/4EOZ 200 mm H2O (1.96 kPa or less) 5 1. 2. 3. 4. 5. 1-789 Inside packing Outside packing Seacock cover Direction of vessel movement Typical intake through-hull strainers Figure 3-2 Seacock Installation Do not align the strainer (in relation to the craft’s direction of travel) with any other through-hull intakes. See Figure 3-3. Flush mount the recommended through-hull strainer. Install slotted-hole-design strainers with the slots parallel to the direction of the vessel’s movement. 4--125EFOZ/5--150EOZ 635 mm H2O (6.23 kPa or less) Figure 3-1 Combustion Air Intake Restriction 2 3.2 Cooling System Components 1 The marine generator set’s cooling system requires the following components. 4 3.2.1 Intake Through-Hull Strainer (Seacock Cover) Install a screened-intake, through-hull strainer to prevent entry of foreign objects. Use perforated, slotted-hole, or unrestricted-hole design strainers. See Figure 3-2 for examples of typical strainers. The inner diameter of the strainer opening must be equal to or greater than the inner diameter of the water-line hose to the seawater pump. TP-6069 6/03 3 Note: Position the intakes in relation to the vessel’s 1-789 travel so neither is in the wake of the other. 1. 2. 3. 4. Generator set intake Main engine intake Aft (rearward) Fore (forward) Figure 3-3 Intake Strainer Section 3 Cooling System 5 Do not use a speed scoop or cup design intake through-hull strainer because it can cause a ramming effect and force water upward, past the seawater pump, and into the engine cylinders when the vessel is moving and the generator set is shut down. Do not use hulls incorporating sea chests or other designs that provide a positive pressure to the raw water pump for the intake through-hull strainers. Positive pressure forces water past the raw water pump and into the engine. A sea chest is a concave molded-in-the-hull chamber that aligns to the vessel’s direction of travel. A sea chest configuration applies positive pressure similar to a scoop-type through-hull strainer. 3.2.2 Seacock 3.2.4 Water Lines Water lines from the seacock to the engine-driven seawater pump are usually constructed of flexible hose. Connect a flexible section of hose to the seawater pump to allow the generator set to vibrate during operation. Support a nonflexible water line within 102 mm (4 in.) of its connection to the flexible section. Keep the seawater hose as straight and short as possible. If the hose is too long, usually over 4.6 m (15 ft.), water draw problems may occur. See Section 7 for the inlet water line hose size and the seawater connection to the seawater pump inlet. Avoid running the inlet pipe above the generator. See Figure 3-5 for the seawater hose connection to the seawater pump inlet. Mount the seacock to the hull, assemble it to the intake, and ensure that it is accessible for operation. Figure 3-2 shows a typical installation. Avoid overcaulking the seacock. Excess caulk reduces water flow and, in some cases, develops a barrier that can force water upward, past the seawater pump, and into the engine cylinders when the vessel is moving and the generator set is shut down. 3.2.3 Seawater Strainer Mount the seawater strainer to the seacock or permanent structure at a point not higher than the seawater pump. Ensure that the strainer is accessible for service. See Figure 3-4 for a typical installation. Some seawater strainers include a seacock and an intake through-hull strainer. 1 1. Seawater pump inlet Maximum seawater inlet pressure at the seawater pump is 34.5 kPa (5 psi). Excessive pressure will cause water ingestion. Figure 3-5 3.2.5 TP-5586-6 Seawater Inlet Connection, Typical Closed Heat Exchanger (4--125EFOZ/5--150EOZ Models) A closed heat exchanger is the best cooling method for most applications. See Figure 3-6 or Figure 3-7 for a typical installation. Provide space to access the water-cooled exhaust manifold pressure cap. 1 2 3.2.6 3 1. Seawater pump 2. Seawater strainer 3. Seacock Figure 3-4 6 Seawater Strainer Section 3 Cooling System 1-789 Direct Water Cooled (3.5EFOZ/4EOZ Models) In a direct seawater cooling system, the impeller pump circulates the seawater around the cylinder and through the cylinder head. A thermostat controls the cooling water circuit temperature. Consult Figure 3-8 and the engine operation manual for the cooling water circuit diagrams. TP-6069 6/03 2 1 3 4 6 8 5 7 14 9 Arrow Description Direction of Flow 10 Seawater Freshwater (Coolant/Antifreeze) 11 12 13 TP-5586-6 1. 2. 3. 4. 5. 6. 7. Engine block Exhaust manifold Exhaust mixer elbow Outlet flapper (exhaust/water discharge) Silencer (customer supplied) Thermostat open Thermostat Figure 3-6 TP-6069 6/03 8. 9. 10. 11. 12. 13. 14. Thermostat closed Heat exchanger Engine-driven seawater pump Seawater strainer Seacock Intake strainer Engine-driven water pump Typical Closed/Heat Exchanger Cooling System (4/6.5/8.5/9/23/27EFOZ and 5/8/10/28/32EOZ Models) Section 3 Cooling System 7 1 2 3 4 5 7 6 8 9 14 13 12 11 Seawater Freshwater (Coolant/Antifreeze) 10 TP-5592-6 1. 2. 3. 4. 5. 6. 7. Oil cooler Engine block Thermostat Water-cooled manifold Heat exchanger Exhaust mixer elbow Water-cooled turbocharger Figure 3-7 8 8. 9. 10. 11. 12. 13. 14. Silencer (customer-supplied) Exhaust outlet Intake strainer Seacock Seawater strainer Engine-driven seawater pump Engine-driven water pump Typical Closed/Heat Exchanger Cooling System (11--20EFOZ,13--24EOZ, 33--125EFOZ and 40--150EOZ Models) Section 3 Cooling System TP-6069 6/03 7 6 8 9 10 3 5 4 2 1 TP-6134- 1. 2. 3. 4. 5. Intake strainer Seacock Seawater strainer Engine-driven seawater pump Oil exchanger Figure 3-8 TP-6069 6/03 6. 7. 8. 9. 10. Zinc plug Exhaust manifold elbow Exhaust hose Silencer (customer supplied) Outlet flapper (exhaust/water discharge) Direct Water-Cooled Cooling System (3.5EFOZ and 4EOZ Models) Section 3 Cooling System 9 Notes 10 Section 3 Cooling System TP-6069 6/03 Section 4 Exhaust System WARNING Carbon monoxide. Can cause severe fainting, or death. nausea, The exhaust system must be leakproof and routinely inspected. Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is a poisonous gas present in exhaust gases. Carbon monoxide poisoning symptoms include but are not limited to the following: D Light-headedness, dizziness D Physical fatigue, weakness in joints and muscles D Sleepiness, mental fatigue, inability to concentrate or speak clearly, blurred vision D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air. Inspecting the exhaust system. Carbon monoxide can cause severe nausea, fainting, or death. For the safety of the craft’s occupants, install a carbon monoxide detector. Consult the boat builder or dealer for approved detector location and installation. Inspect the detector before each generator set use. In addition to routine exhaust system inspection, test the carbon monoxide detector per the manufacturer’s instructions and keep the detector operational at all times. TP-6069 6/03 Operating the generator set. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Use the following precautions when installing and operating the generator set. Do not install the exhaust outlet where exhaust can be drawn in through portholes, vents, or air conditioners. If the generator set exhaust discharge outlet is near the waterline, water could enter the exhaust discharge outlet and close or restrict the flow of exhaust. Never operate the generator set without a functioning carbon monoxide detector. Be especially careful if operating the generator set when moored or anchored under calm conditions because gases may accumulate. If operating the generator set dockside, moor the craft so that the exhaust discharges on the lee side (the side sheltered from the wind). Always be aware of others, making sure your exhaust is directed away from other boats and buildings. Avoid overloading the craft. 4.1 Types Kohlerr generator sets covered in this manual use either wet or dry exhaust systems. Dry exhaust systems are common in commercial applications. See the engine manual for specifications. 4.2 Exhaust Lines Use water-cooled exhaust lines in all marine installations. Keep the lines as short and straight as possible. NFPA 302 Fire Protection Standard for Pleasure and Commercial Motor Craft, Clause 4-3, recommends using two corrosion-resistant hose clamps with a minimum width of 13 mm (1/2 in.) on each end of the flexible exhaust hose connections. Kohler Co. requires a downward pitch of at least 13 mm per 30.5 cm (1/2 in. per running foot). Use a flexible exhaust hose that conforms to UL Standard 1129 for the engine’s wet exhaust components between the mixer elbow and the exhaust outlet. Section 4 Exhaust System 11 4.3 Exhaust System Location, Mounting, and Installation Mount the silencer independently to eliminate stress on the exhaust system and the exhaust manifold/mixer elbow. See Section 7 for the mixer elbow water line hose size. See Figure 4-1 for the exhaust connection to the mixer elbow. Provide an adequate hose length from the exhaust mixer to the silencer to allow for generator set movement. Locate the exhaust outlet at least 10 cm (4 in.) above the waterline when the craft is loaded to maximum capacity. Install an exhaust port with the flap at the exhaust (transom) outlet to prevent water backup in following seas or when moving astern (backward). A lift in the exhaust piping before the piping exits the craft prevents backwash. See Figure 4-4, item 1. Support the exhaust lines to prevent the formation of water pockets. Exhaust system installation guidelines for various generator set locations follow. Information and illustrations of stern- (rear) exhaust installations also apply to side-exhaust installations. Where exhaust lines require passage through bulkheads, use port (left)- or starboard (right)- side exhaust outlets, also in applications in which long exhaust lines to the transom (rear) could cause excessive back pressure. See Figure 4-3 for allowable back pressures. Should any information regarding installation conflict with USCG Regulations, follow USCG Regulations. Model 4/8.5/9/23/27EFOZ and 5/10/28/32EOZ 6.5EFOZ and 8EOZ 1 1. Water/exhaust outlet Figure 4-1 TP-5586-6 Mixer Elbow/Exhaust Connection, Typical 1. Water/exhaust outlet Figure 4-2 12 Mixer Elbow/Exhaust Connection, 3.5EFOZ/4EOZ Model Only Section 4 Exhaust System 11.77 (1200) 6.37 (650) 3.5/11.5/13/19/20EFOZ and 4/14/15.5/23/24EOZ 4.90 (500) 33/40/55/70/80/100/125EFOZ and 40/50/65/80/99/125/150EOZ 7.47 (762) 4.3.1 TP-6134- 9.81 (1000) 11/16/17.5EFOZ and 13/20EOZ Figure 4-3 1 Allowable Exhaust Back Pressure, ≤ kPa (mm H2O) Allowable Exhaust Back Pressures Above-Waterline Installation Install a customer-supplied silencer with the silencer’s outlet at a maximum of 3 m (10 horizontal ft.) from the center of the engine’s exhaust outlet. See Figure 4-4. Mount a typical silencer with the inlet and outlet horizontal and with the drain plug down. Use an exhaust hose pitch of at least 13 mm per 30.5 cm (0.5 in. per running foot). Some silencers require two support brackets or hanger straps for installation to stringers or other suitable structure. Follow the instructions provided with the silencer. Install any lift (see Figure 4-4, item 1) in the exhaust line below the engine exhaust manifold outlet. TP-6069 6/03 4 5 6 3 2 1 7 8 13 9 15 Waterline 12 16 10 14 11 1. Slight lift improves silencing and prevents water backwash into the silencer (keep below the level of the exhaust manifold outlet) 2. Silencer (customer-supplied) 3. Exhaust manifold outlet 4. Exhaust mixer elbow 5. Heat exchanger (locations vary by model) 6. Coolant recovery tank (located on the unit on some models) 7. Locate the coolant recovery tank at the same height as the heat exchanger 8. Maximum seawater pump lift of 1 m (3 ft.) 9. Seawater strainer 10. Seacock 11. Intake strainer 12. Engine-driven seawater pump Figure 4-4 TP-6069 6/03 TP-5856-4 13. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.) 14. Maximum distance between silencer and exhaust mixer elbow of 3 m (10 ft.) 15. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.) 16. Minimum exhaust outlet distance above waterline of 10 cm (4 in.). Note: Vessel fully loaded. Note: Data applies to both rear- and side-exhaust installations. Note: Use two hose clamps on each end of all flexible exhaust hose connections. Note: Read the text for complete explanation of dimensions and other installation considerations. Typical Above-Waterline Installation Section 4 Exhaust System 13 4.3.2 Mid/Below-Waterline Installation 1 Follow USCG Regulations for installing an antisiphon provision to prevent raw water entry into the engine. Use the siphon break if the exhaust manifold outlet is located less than 23 cm (9 in.) above the waterline when the craft is loaded to maximum capacity. Install the siphon break at least 31 cm (1 ft.) above the waterline using the instructions provided with the siphon break kit. Note: An improperly installed siphon break will cause engine damage and may void the warranty. Install the siphon break above the highest point in the exhaust line between the heat exchanger and the exhaust mixer. See Figure 4-5 for the siphon break connection. Support the siphon break and hoses to maintain their position and function. Allow a slight offset to clear the stringers or other permanent structures. Protect the siphon break air inlet from dirt and debris. Note: To prevent water leakage on the generator set, do not mount the siphon break directly over the generator set. 14 Section 4 Exhaust System TP-5586-6 1. Cut hose and connect siphon break and hardware Figure 4-5 Siphon Break Connection (4EFOZ/5EOZ model shown) Mount a typical silencer’s base no more than 1.2 m (4 ft.) below the highest point in the exhaust line. Attach a separate wood mounting base to the hull stringers or other suitable structures. Use the silencer manufacturer’s recommendation for securing the silencer to the hull. Mount the silencer with the outlet not more than 3 m (10 horizontal ft.) from the engine’s exhaust manifold outlet. Use a USCG-type certified marine exhaust hose. TP-6069 6/03 2 7 3 8 9 10 1 6 21 5 Waterline 11 4 19 20 16 12 18 15 13 17 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. Mounting base Retaining cap Reed valve assembly Maximum silencer vertical lift of 1.2 m (4 ft.) Exhaust mixer elbow distance above waterline; if less than 23 cm (9 in.), a siphon break is required Minimum siphon break distance above waterline of 30.5 cm (1 ft.) Siphon break Exhaust mixer elbow Heat exchanger (locations vary by model) Coolant recovery tank (located on the unit on some models) Indicates the coolant recovery tank is at the same height as the heat exchanger Seawater strainer Seacock Intake strainer Figure 4-6 14 15. Engine-driven seawater pump 16. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.) 17. Maximum distance between silencer and exhaust mixer elbow of 3 m (10 ft.) 18. Silencer (customer-supplied) 19. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.) 20. Minimum exhaust outlet distance above waterline of 10 cm (4 in.) 21. Exhaust hose (see Figure 4-7 for hose sizes) Note: Read the text for complete explanation of dimensions and other installation considerations. Note: Use two hose clamps on each end of all flexible exhaust hose connections. Note: Data applies to both rear- and side-exhaust installations. Typical Mid and Below Waterline Installation Models with Sound Shield Exhaust Hose Diameter mm (in.) 3.5/4/6.5/8.5/9EFOZ 4/5/8/10EOZ 4/6.5/8.5/9/11/11.5/13/16/17.5/19/20EFOZ 5/8/10/13/14/15.5/20/23/24EOZ 51 (2.0) 11/11.5/13/16/17.5/19/20/23/27EFOZ 13/14/15.5/20/23/24/28/32EOZ 27EFOZ 32EOZ 76 (3.0) 33EFOZ 40EOZ 33EFOZ 40EOZ 89 (3.5) 40/55/70/80/100/125EFOZ 50/65/80/99/125/150EOZ 40/55/70/80/100/125EFOZ 50/65/80/99/125/150EOZ Models without Sound Shield Figure 4-7 TP-6069 6/03 TP-5856-4 102 (4.0) Exhaust Hose Sizes Section 4 Exhaust System 15 Notes 16 Section 4 Exhaust System TP-6069 6/03 Section 5 Fuel System 2 WARNING 1 Explosive fuel vapors. Can cause severe injury or death. Use extreme care when handling, storing, and using fuels. Installing the fuel system. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an explosion. Do not modify the tank or the propulsion engine fuel system. Equip the craft with a tank that allows one of the two pickup arrangements described in the installation section. The tank and installation must conform to USCG Regulations. Note: Fuel system installations must conform to USCG Regulations. 1-788 1. Fuel line to propulsion engine 2. Fuel line to generator set Figure 5-1 Multiple Dip Tube Arrangement m:is:102:001 5.1 Fuel Tank Most marine generator sets draw fuel from the same fuel tank as the craft’s propulsion engine(s). If the tank’s fuel pickup opening allows a multiple dip tube, use a multiple dip tube arrangement. See Figure 5-1. The multiple dip tube arrangement incorporates a shorter dip tube for the generator set and a longer dip tube for the propulsion engine. With this arrangement, the generator set runs out of fuel before the propulsion engine during a low fuel supply situation. Equip the fuel system with a fuel/water separator to remove any accumulated dirt and water. TP-6069 6/03 Section 5 Fuel System 17 5.2 Fuel Lines 5.3 Fuel Filters Locate the fuel return line as far as practical from the fuel pickup to allow the tank fuel to cool the return fuel before delivery back to the fuel injectors. Incoming fuel cools the injectors to achieve maximum engine efficiency. Conform to USCG Regulations regarding inline fuel filters or strainers. Note: Do not tee into the main propulsion engine’s fuel line. Under no circumstances should the propulsion engine and generator set share pickup or return lines (through a tee arrangement) that would allow the larger engine to starve fuel from the smaller engine. It is possible that the operation of either engine could completely drain the fuel line of the other engine and make starting difficult. Use a flexible hose section to connect the metallic line from the fuel tank to the engine’s fuel pump inlet connection point. Also, use a flexible hose section to connect the metallic line from the fuel tank to the fuel return connection point. The flexible section allows the generator set to vibrate during operation. Model Fuel Line ID Size mm (in.) 3.5EFOZ and 4EOZ 6.4 (1/4) 4--125EFOZ and 5--150EOZ 9.7 (3/8) Figure 5-2 5.4 Fuel Pump Lift See Figure 5-3 for fuel pump lift capabilities. Model Fuel Pump Lift m (ft.) 3.5/4/6.5/8.5/9/11/11.5/13/16/17.5/19/20/23/ 27EFOZ and 4/5/8/10/13/14/15.5/20/23/24/28/32EOZ 1.2 (4) 33/40/55/70/80/100/125EFOZ and 40/50/65/80/99/125/150EOZ 0.9 (3) Figure 5-3 Fuel Pump Lift 5.5 Fuel Consumption Consult the current generator set specification sheets for generator set fuel consumption rates. Fuel Line ID Size See Figure 5-2 for the ID size of the customer-supplied fuel line that connects to the fuel pump and fuel return. Route the fuel lines from the fuel tank in a gradual incline to the engine—do not exceed the height of the generator set and do not route fuel lines above the generator set. Comply with USCG Regulation 46CFR182.20 regarding fuel lines and supports. See Section 7 for fuel feed pump inlet connection and fuel return line connection. 18 Section 5 Fuel System TP-6069 6/03 Section 6 Electrical System 6.1 AC Voltage Connections WARNING Hazardous voltage. Moving rotor. Can cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place. Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Connect the generator set to the building/marina electrical system only through an approved device and after the building/marina main switch is opened. Backfeed connections can cause severe injury or death to utility personnel working on power lines and/or personnel near the work area. Some states and localities prohibit unauthorized connection to the utility electrical system. Install a ship-to-shore transfer switch to prevent interconnection of the generator set power and shore power. 1 2 3 Make AC connections to the generator set inside the controller box (4--27EFOZ and 5--32EOZ models) or inside the junction box (33--125EFOZ and 40--150EOZ models). Typically, the generator set connects to a ship-to-shore transfer switch that allows the use of shore/utility power when docked or generator set power when docked or at sea. The wiring then connects to a main circuit breaker box (panel board) that distributes branch circuits throughout the craft. See Figure 6-1 for AC voltage connections to the generator set. See Section 8 for reconnection of the generator set. 6.2 Circuit Protection The AC circuit breakers (optional) protect the wiring from the AC circuit breakers to the vessel’s distribution panel. AC circuit breakers trip when they detect a fault in the output circuit. After correcting the fault, reset the AC circuit breaker(s) by placing them in the ON position. Restart the unit. Do not start the unit under load. See Figure 6-2 or Figure 6-3 for AC circuit breaker ratings. The unit’s voltage configuration determines the circuit breaker selection. Note: Circuit breaker ampere rating and availability are subject to change. 4 6.2.1 5 6 1. 2. 3. 4. 5. 6. Line side AC circuit breaker Load side L1/L2 phase (black) leads GRD ground (green) lead L0 neutral (white) lead Figure 6-1 585771 AC Voltage Connections in Controller Box (5--32EOZ Models, Typical) Circuit Breaker Considerations Mounting location. Mount the circuit breakers in the generator set’s controller (4--27EFOZ and 5--32EOZ models) or the generator set’s junction box (33--125EFOZ and 40--150EOZ models). See Section 6.2.2 or Section 6.2.3. Note: 3.5EFOZ and 4EOZ models already have circuit breakers installed. Sizing. Use the generator set voltage/frequency configuration to determine the circuit breaker amperage. If the generator set voltage configuration changes, change the circuit breaker to provide optimum protection. For circuit breaker application and selection information, contact an authorized distributor/dealer. Have a qualified electrician or technician install circuit breakers and reconnect the generator set. Comply with all governing standards and codes. TP-6069 6/03 Section 6 Electrical System 19 Amps 20 Max. Voltage 250 Number of Poles 1 Model(s) 4EFOZ Number of Poles Type Model(s) 60 600 3 UL/IEC 33EFOZ, 40EOZ 70 600 3 UL/IEC 40EFOZ, 40EOZ 80 480 3 UL/IEC 40EFOZ, 50EOZ 100 480 3 UL/IEC 55EFOZ, 50/65EOZ 600 3 8.5/11.5EFOZ, 14EOZ 22 250 2 4EFOZ, 5EOZ 25 250 2 5EOZ 1 6.5EFOZ 2 6.5EFOZ 100--125 600 3 IEC 33/55EFOZ, 40/65EOZ 600 3 11.5/17.5/20EFOZ, 14/20/24EOZ—3 phase 100--125 600 3 IEC 70EFOZ, 80EOZ 250 2 8EOZ 125 600 3 UL 1 4EFOZ 33/55EFOZ, 40/65EOZ 2 8EOZ 125 600 3 UL 70EFOZ, 80EOZ 250 1 5EOZ 128--160 600 3 IEC 600 3 11.5EFOZ, 14/20/24EOZ—3 phase 33/40EFOZ, 40/50EOZ 1 9EFOZ 128--160 600 3 IEC 70/80EFOZ, 80/99EOZ 2 9EFOZ, 8/10EOZ 150 600 3 UL 1 11/13EFOZ 33/40EFOZ, 40/50EOZ 2 11/11.5/17.5EFOZ 150 600 3 UL 250 2 9EFOZ, 10EOZ 70/80EFOZ, 80/99EOZ 480 3 20/23/27EFOZ, 20/28/32EOZ—3 phase 160--400 600 3 UL 70/80/100EFOZ, 80/99/125/150EOZ 250 1 5EOZ 160--400 600 3 IEC 70/80/100/125EFOZ, 80/99/125/150EOZ 200 600 3 UL 40/55EFOZ, 50/65EOZ 200 600 3 UL 100EFOZ, 99/125EOZ 200--250 600 3 IEC 40/55EFOZ, 50/65EOZ 200--250 600 3 IEC 70/100/125EFOZ, 80/125/150EOZ 240--600 600 3 UL 125EFOZ, 125/150EOZ 250 30 33 35 40 42 250 250 240 50 55 240 60 250 600 240 70 90 100 125 13EFOZ 2 11/13EFOZ, 13/14EOZ 1 6.5EFOZ 3 17.5/20EFOZ, 20/24/28/32EOZ—3 phase 1 16EFOZ 2 13/20EFOZ, 15.5EOZ 1 6.5EFOZ, 8EOZ 600 3 20/24EOZ—3 phase 1 16/19EFOZ 2 16EFOZ, 20EOZ—1 phase, 20/24EOZ—3 phase 250 600 3 UL 55EFOZ, 65EOZ 250 1 8EOZ 250 600 3 UL 70/125EFOZ, 80/125/150EOZ 480 3 23EFOZ—3 phase 250 1 9EFOZ, 10EOZ 250--630 600 3 IEC 125EFOZ, 125/150EOZ 240 85 1 250 80 1 19EFOZ 2 19EFOZ—1 phase 20/23EOZ 480 3 27EFOZ—3 phase 240 2 23EOZ 3 23/27EFOZ, 28/32EOZ—3 phase 2 23/27EFOZ, 28EOZ— 1 phase, 27EFOZ—3 phase 3 23/27EFOZ, 28/32EOZ—3 phase 240 480 600 150 600 2 28/32EOZ—1 phase, 32EOZ— 3 phase 175 600 2 32EOZ—1 phase Figure 6-2 20 Max. Voltage Amps AC Circuit Breaker Ratings (4--27EFOZ and 5--32EOZ Models), Listed By Amps Section 6 Electrical System Figure 6-3 AC Circuit Breaker Ratings (33--150 kW Models), Listed By Amps WARNING Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. TP-6069 6/03 Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Place the generator set start/stop switch in the STOP position. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch. WARNING 3. Remove the controller cover screws and remove the access cover. 4. Remove the screws and nuts to remove the circuit breaker cover plate. Save the mounting hardware. 5. Install the circuit breaker from the inside of the cutout panel and mount it using existing screws removed in step 4. Position the circuit breaker with the ON in the normal upright position or to the left side. Cover the cutout opening, if applicable, with the circuit breaker cover plate. Use existing screws to mount the cover plate. 6. See Section 8 for voltage reconnection. Hazardous voltage. Moving rotor. Can cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place. Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution. Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment. Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Connect the generator set to the building/marina electrical system only through an approved device and after the building/marina main switch is opened. Backfeed connections can cause severe injury or death to utility personnel working on power lines and/or personnel near the work area. Some states and localities prohibit unauthorized connection to the utility electrical system. Install a ship-to-shore transfer switch to prevent interconnection of the generator set power and shore power. 6.2.2 Circuit Breaker Installation (4--27EFOZ and 5--32EOZ Models) 1. Place the generator set start/stop switch in the STOP position. 2. Disconnect the generator set engine starting battery, negative (--) lead first. TP-6069 6/03 Note: Kohlerr marine diesel generator sets are fully frequency adjustable and voltage reconnectable. To determine reconnection options, check the model’s specification sheet. 7. Install insulation boots over stator lead terminals if the kit includes insulation boots. Note: See Section 8 for wiring instructions. 8. Make the recommended connections for the following four reconnection systems using circuit breakers: Two-pole circuit breaker with a single-voltage system (example: 120-volt, 3-wire). Attach stator leads marked 2 and 4 to the side of the circuit breaker marked LINE. Install the jumper lead across the LINE side of circuit breaker terminals (see Section 8). Attach stator leads 1 and 3 to L0. Single-pole circuit breaker with a 120-volt, 2-wire, single-voltage system. Attach stator leads marked 2 and 4 to the side of the circuit breaker marked LINE (see Section 8). Attach stator leads 1 and 3 to L0. Two-pole circuit breaker with a dual-voltage system (example: 120/240-volt, 3-wire). Attach stator leads marked 1 and 4 to the side of the circuit breaker marked LINE. Do not use a jumper lead (see Section 8). Attach stator leads 2 and 3 to L0. Single-pole circuit breaker with a 240-volt, 2-wire, single-voltage system. Attach the stator lead marked 2 to the side of the circuit breaker marked LINE (see Section 8). Bolt together leads 1 and 4 and tape to insulate from ground. Attach the stator lead marked 3 to L0. 9. Connect the stator lead(s) used for neutral connection to the L0 stud. See the illustrations in Section 8. Section 6 Electrical System 21 10. Connect the side of the circuit breaker marked LOAD to the ship-to-shore switch or craft wiring. Attach insulation boots to the black leads if the kit includes insulation boots. With a single-pole circuit breaker use one black lead (L1). With a two-pole circuit breaker use two black leads, L1 and L2. Connect the neutral (white) lead to the L0 stud. Connect the equipment ground (green) lead to GRD stud. Note: Wire material. Use stranded copper for all wiring. Use wire gauges and insulation, conductor temperature ratings, sheath stripping, conductor support and protection, conductor terminals and splices, and overcurrent protection (circuit breakers, fuses) that conform to standards and codes. Note: Follow USCG Regulations CFR33, Part 183 (Pleasurecraft) and CFR46 (Commercial Craft) for marine applications. Note: Wire protection. Use rubber grommets and cable ties as necessary to protect and secure wiring from sharp objects, the exhaust system, and any moving parts. 11. Replace the controller cover or circuit breaker box access panel. 6.2.3 Circuit Breaker Installation (33--125EFOZ and 40--150EOZ Models) 1. Place the generator set master switch in the OFF position. 2. Disconnect the generator set engine starting battery, negative (--) lead first. 3. Remove the six screws from the right side junction box panel and remove the panel. 4. Install the circuit breaker on the new panel with the screws and washers. Position the ON side of the circuit breaker toward the rear of the junction box. See Figure 6-4. 5. Attach stator leads L1, L2, and L3 to the extension leads (if supplied) or to the line side of the circuit breaker. See Figure 8-5. Note: Insulate leads with electrical tape after connecting extension leads to stator leads. 6. Connect the neutral connection stator leads to the L0 stud. Note: Verify that terminal positions and previously made line lead connections allow room for load connections to load studs. 12. Reconnect the generator set engine starting battery, negative (--) lead last. 7. Connect the load side of the circuit breaker to customer-supplied craft wiring. Connect the neutral lead to the L0 stud. See Figure 8-5. 13. Make voltage or frequency adjustments according to Section 8. 8. Attach the new panel to the junction box using the original six screws. See Figure 6-4. Note: Voltage/frequency adjustable. Some four-lead generator sets are not voltage/frequency adjustable. To determine adjustment possibilities, check the model’s specification sheet or service manual. If you are reconnecting the generator set from a single-voltage to a dual-voltage configuration (example: from 120-volt to 120/240-volt) or a dual voltage to a single voltage (example: from 120/240-volt to 120-volt) with the same primary voltage, do not adjust the voltage/frequency adjustment. Adjust the voltage/frequency for frequency changes or setting changes of the primary voltage (example: from 120-volt to 100-volt). Refer to the model’s specification sheet for reconnection capability. 9. Check that the generator set master switch is in the OFF position. Reconnect the generator set engine starting battery, negative (--) lead last. 22 Section 6 Electrical System TP-6069 6/03 8 9 1 2 3 4 5 6 ASSEMBLY VIEW C-C 6 7 ASSEMBLY VIEW A 1 5 ASSEMBLY VIEW B DX-250000-B 1. 2. 3. 4. 5. Existing mounting hardware Load lead access panel Screw Hang tag Circuit breaker Figure 6-4 6. 7. 8. 9. Circuit breaker panel Extension leads, if equipped Rear connection used on 125-250 amp circuit breaker Spacer used on 125-250 amp circuit breaker Circuit Breaker Mounting 6.3 Installation In Steel or Aluminum Vessels Installation of a generator set in a vessel constructed of a material capable of conducting current (e.g., steel or aluminum) is subject to considerations not normally encountered in fiberglass or wood vessels. These differences include equipment grounding, grounding of neutral conductors, ground-fault protection, and isolation of galvanic currents. The scope of these topics is too extensive to be fully discussed here. Consult your local marine authority for more information. Before installing the generator set, check the available wiring diagrams in the operation manual to become familiar with the electrical system. 6.4 Installation Regulations The U.S. Coast Guard governs generator set installation in U.S. pleasurecraft and commercial vessels. Refer to the applicable regulations below: U.S. Pleasurecraft Installation Regulations Title 33CFR, Chapter I, U.S. Coast Guard, Part 183 1. Subpart I—Electrical Equipment 2. Subpart J—Fuel Systems U.S. Commercial Vessel Installation Regulations Title 46CFR, Chapter I, U.S. Coast Guard 1. Part 111—Electrical Systems 2. Part 182—Machinery Installation m:sc:001:001 TP-6069 6/03 Section 6 Electrical System 23 6.5 Battery Batteries and their installation must conform to USCG Regulations 183.420 (a) through (g). Provide generator sets with batteries separate from the propulsion engine’s whenever possible. The starting/charging systems of both the generator set and the engine must have a common negative (--) ground. USCG Regulation 183.415, Grounding, requires connection of a common conductor to each grounded cranking-motor circuit. Size the conductor to match the larger of the engine’s two battery cables. Figure 6-5 lists cable sizes for generator set battery connections at various ambient temperatures. Connecting a common conductor to each grounded cranking motor circuit prevents the starting motor current from using alternative electrical paths should the cranking motor ground circuit be restricted or open because of oxidation or loose hardware. Alternative electrical paths include metallic fuel lines that can pose a fire hazard. See Figure 6-7 and Section 7 for battery connections to the generator set. Distance between Generator Set and Battery m (ft.) 12.2 (40) Cable Size (AWG) At –18°C (0°F) 00 At 0°C (32°F) 0 At 24°C (75°F) 1 9.1 (30) 0 1 2 7.6 (25) 1 2 4 6.1 (20) 2 2 6 4.6 (15) 2 4 6 3.0 (10) 4 6 8 1.5 (5) 6 6 8 0.8 (2.5) 8 8 8 Figure 6-5 Battery Cable Sizes Kohler Co. recommends using one 12-volt or 24-volt battery (as the spec requires) to start the generator. See Figure 6-6 for minimum cold cranking amps (CCA) recommendations. 1 5 3 4 1. 2. 3. 4. 5. 2 TP-5586-6 Starter solenoid Battery positive (+) connection Equipment ground Battery negative (--) connection Engine block mount Figure 6-7 Battery Connections (5EOZ/4EFOZ model shown) 6.6 Wiring Use only stranded copper wire. Conform to USCG Regulations 183.425 through 183.460 for wire gauges and insulation, conductor temperature ratings, sheath stripping, conductor support and protection, conductor terminals and splices, and over-current protection (circuit breakers, fuses). Use rubber grommets and cable ties as necessary to protect and secure the wire from sharp objects, the exhaust system, and moving parts. 12-Volt Starting Battery Size CCA at --18°C (0°F) or 100 Amp. Hr. Models CCA 3.5–20EFOZ and 4--24EOZ 500 23/27/100/125EFOZ and 28/32/125/150EOZ 800 33--80EFOZ and 40--99EOZ 640 Figure 6-6 24 Battery Recommendations Section 6 Electrical System TP-6069 6/03 6.7 Remote Start Switch Connection Kohler Co. offers several remote panels for connection to the generator set. Contact your local Kohlerr distributor/dealer for detailed descriptions. See Figure 6-8 for remote start panel connection to the generator set controller. Kohler Co. also offers a wiring harness with a connector keyed to the controller box connector. The other end of this harness has pigtails that the installer can use to connect to a customer-supplied start/stop switch or separate lights and hourmeter. Consult wiring diagrams and instruction sheets for connection information/details. Note: Gauge senders. Gauge senders are available for most generator sets. If using customersupplied gauges, be sure they are compatible with generator set senders. Contact an authorized Kohlerr service distributor/dealer. Gauges and senders are available as service items from an authorized Kohlerr service distributor/dealer. 33--150 kW Models: Various wiring harnesses, Y-connectors, pigtail harnesses, remote control panels, and remote annunciator panels (Decision-Makert 3+ only) are available. See Figure 6-9 and Figure 6-10 for wiring options. 3.5EFOZ/4EOZ Models: See Figure 7-3 for the optional remote panel wiring. 1 DA-250000-H 1. Controller remote connector Figure 6-8 TP-6069 6/03 Controller Remote Connector, Typical Section 6 Electrical System 25 ADV--6115A-A Figure 6-9 26 Remote Controller and Harness Options (33--150 kW Models) Section 6 Electrical System TP-6069 6/03 Figure 6-10 Remote Controller and Harness Options (33--150 kW Models) TP-6069 6/03 Section 6 Electrical System 27 Notes 28 Section 6 Electrical System TP-6069 6/03 Section 7 Installation Drawings Use the drawings in this section for installation purposes. Consult the supplier and verify that the drawings are the most current for your specifications. Installation drawings show exhaust outlet locations, fuel inlet and return connections, siphon break locations, and battery connections. See Figure 7-1 for installation drawing identification. Model No. 3.5EFOZ and 4EOZ with remote options Drawing ADV-6652A-B ADV-6652B-B Page 30 31 4EFOZ and 5EOZ with sound shield 6.5EFOZ and 8EOZ with sound shield 8.5/9EFOZ and 10EOZ ADV-5850A-H ADV-5850B-H ADV-6284A-J ADV-6284B-J ADV-6026A-K 32 33 34 35 36 with sound shield 11EFOZ and 13EOZ with sound shield 11.5/13EFOZ and 14/15.5EOZ with sound shield ADV-6026B-K ADV-6512A-D ADV-6512B-D ADV-6513A-C ADV-6513B-C 37 38 39 40 41 16/17.5EFOZ and 20EOZ with sound shield 19/20EFOZ and 23/24EOZ with sound shield 23/27EFOZ and 28/32EOZ ADV-6481A-D ADV-6481B-D ADV-6494A-C ADV-6494B-C ADV-6285A-F 42 43 44 45 46 with sound shield 33EFOZ and 40EOZ with fuel/water separator and dry exhaust elbow with sound shield with electric clutch ADV-6285B-F ADV-6581A-E 47 48 ADV-6581B-E ADV-6581C-E ADV-6581D-E 49 50 51 40EFOZ and 50EOZ with fuel/water separator and dry exhaust elbow with sound shield with electric clutch 55EFOZ and 65EOZ ADV-6582A-E 52 ADV-6582B-E ADV-6582C-E ADV-6582D-E ADV-6583A-E 53 54 55 56 ADV-6583B-E ADV-6583C-E ADV-6583D-E ADV-6603A-D 57 58 59 60 ADV-6603B-D 61 ADV-6603C-D ADV-6603D-D ADV-6594A-D ADV-6594B-D ADV-6594C-D 62 63 64 65 66 with fuel/water separator and dry exhaust elbow with sound shield with electric clutch 70/80EFOZ and 80/99EOZ with fuel/water separator and dry exhaust elbow with sound shield with electric clutch 100/125EFOZ and 125/150EOZ with sound shield with dry exhaust elbow Figure 7-1 TP-6069 6/03 Installation Drawings Section 7 Installation Drawings 29 NOTE: Dimensions in [ ] are inch equivalents. Figure 7-2 30 ADV-6652A-B Dimension Drawing, 3.5EFOZ/4EOZ Section 7 Installation Drawings TP-6069 6/03 ADV-6652B-B Figure 7-3 TP-6069 6/03 Remote Options, 3.5EFOZ/4EOZ Section 7 Installation Drawings 31 NOTE: Dimensions in [ ] are inch equivalents. Figure 7-4 32 ADV-5850A-H Dimension Drawing, 4EFOZ/5EOZ Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. Figure 7-5 TP-6069 6/03 ADV-5850B-H Dimension Drawing, 4EFOZ/5EOZ with Sound Shield Section 7 Installation Drawings 33 NOTE: Dimensions in [ ] are inch equivalents. Figure 7-6 34 ADV-6284A-J Dimension Drawing, 6.5EFOZ/8EOZ Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. Figure 7-7 TP-6069 6/03 ADV-6284B-J Dimension Drawing, 6.5EFOZ/8EOZ with Sound Shield Section 7 Installation Drawings 35 NOTE: Dimensions in [ ] are inch equivalents. Figure 7-8 36 ADV-6026A-K Dimension Drawing, 8.5/9EFOZ and 10EOZ Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. Figure 7-9 TP-6069 6/03 ADV-6026B-K Dimension Drawing, 8.5/9EFOZ and 10EOZ with Sound Shield Section 7 Installation Drawings 37 NOTE: Dimensions in [ ] are inch equivalents. ADV-6512A-D Figure 7-10 Dimension Drawing, 11EFOZ/13EOZ 38 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6512B-D Figure 7-11 Dimension Drawing, 11EFOZ/13EOZ with Sound Shield TP-6069 6/03 Section 7 Installation Drawings 39 NOTE: Dimensions in [ ] are inch equivalents. ADV-6513A-C Figure 7-12 Dimension Drawing, 11.5/13EFOZ and 14/15.5EOZ 40 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6513B-C Figure 7-13 Dimension Drawing, 11.5/13EFOZ and 14/15.5EOZ with Sound Shield TP-6069 6/03 Section 7 Installation Drawings 41 NOTE: Dimensions in [ ] are inch equivalents. ADV-6481A-D Figure 7-14 Dimension Drawing, 16/17.5EFOZ and 20EOZ 42 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6481B-D Figure 7-15 Dimension Drawing, 16/17.5EFOZ and 20EOZ with Sound Shield TP-6069 6/03 Section 7 Installation Drawings 43 NOTE: Dimensions in [ ] are inch equivalents. ADV-6494A-C Figure 7-16 Dimension Drawing, 19/20EFOZ and 23/24EOZ 44 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6494B-C Figure 7-17 Dimension Drawing, 19/20EFOZ and 23/24EOZ with Sound Shield TP-6069 6/03 Section 7 Installation Drawings 45 NOTE: Dimensions in [ ] are inch equivalents. ADV-6285A-F Figure 7-18 Dimension Drawing, 23/27EFOZ and 28/32EOZ 46 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6285B-F Figure 7-19 Dimension Drawing, 23/27EFOZ and 28/32EOZ with Sound Shield TP-6069 6/03 Section 7 Installation Drawings 47 NOTE: Dimensions in [ ] are inch equivalents. ADV-6581A-E Figure 7-20 Dimension Drawing, 33EFOZ/40EOZ 48 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6581B-E Figure 7-21 Dimension Drawing, 33EFOZ/40EOZ with Fuel/Water Separator and Dry Exhaust Elbow TP-6069 6/03 Section 7 Installation Drawings 49 NOTE: Dimensions in [ ] are inch equivalents. ADV-6581C-E Figure 7-22 Dimension Drawing, 33EFOZ/40EOZ with Sound Shield 50 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6581D-E Figure 7-23 Dimension Drawing, 33EFOZ/40EOZ with Electric Clutch TP-6069 6/03 Section 7 Installation Drawings 51 NOTE: Dimensions in [ ] are inch equivalents. ADV-6582A-E Figure 7-24 Dimension Drawing, 40EFOZ/50EOZ 52 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6582B-E Figure 7-25 Dimension Drawing, 40EFOZ/50EOZ with Fuel/Water Separator and Dry Exhaust Elbow TP-6069 6/03 Section 7 Installation Drawings 53 NOTE: Dimensions in [ ] are inch equivalents. ADV-6582C-E Figure 7-26 Dimension Drawing, 40EFOZ/50EOZ with Sound Shield 54 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6582D-E Figure 7-27 Dimension Drawing, 40EFOZ/50EOZ with Electric Clutch TP-6069 6/03 Section 7 Installation Drawings 55 NOTE: Dimensions in [ ] are inch equivalents. ADV-6583A-E Figure 7-28 Dimension Drawing, 55EFOZ/65EOZ 56 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6583B-E Figure 7-29 Dimension Drawing, 55EFOZ/65EOZ with Fuel/Water Separator and Dry Exhaust Elbow TP-6069 6/03 Section 7 Installation Drawings 57 NOTE: Dimensions in [ ] are inch equivalents. ADV-6583C-E Figure 7-30 Dimension Drawing, 55EFOZ/65EOZ with Sound Shield 58 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6583D-E Figure 7-31 Dimension Drawing, 55EFOZ/65EOZ with Electric Clutch TP-6069 6/03 Section 7 Installation Drawings 59 NOTE: Dimensions in [ ] are inch equivalents. ADV-6603A-D Figure 7-32 Dimension Drawing, 70/80EFOZ and 80/99EOZ 60 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6603B-D Figure 7-33 Dimension Drawing, 70/80EFOZ and 80/99EOZ with Fuel/Water Separator and Dry Exhaust Elbow TP-6069 6/03 Section 7 Installation Drawings 61 NOTE: Dimensions in [ ] are inch equivalents. ADV-6603C-D Figure 7-34 Dimension Drawing, 70/80EFOZ and 80/99EOZ with Sound Shield 62 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6603D-D Figure 7-35 Dimension Drawing, 70/80EFOZ and 80/99EOZ with Electric Clutch TP-6069 6/03 Section 7 Installation Drawings 63 NOTE: Dimensions in [ ] are inch equivalents. ADV-6594A-D Figure 7-36 Dimension Drawing, 100/125EFOZ and 125/150EOZ 64 Section 7 Installation Drawings TP-6069 6/03 NOTE: Dimensions in [ ] are inch equivalents. ADV-6594B-D Figure 7-37 Dimension Drawing, 100/125EFOZ and 125/150EOZ with Sound Shield TP-6069 6/03 Section 7 Installation Drawings 65 NOTE: Dimensions in [ ] are inch equivalents. ADV-6594C-D Figure 7-38 Dimension Drawing, 100/125EFOZ and 125/150EOZ with Dry Exhaust Elbow 66 Section 7 Installation Drawings TP-6069 6/03 Section 8 Reconnection/Adjustments 8.1 Four-Lead Reconnection The following information illustrates the reconnection of four-lead generator sets. In all cases, conform to the National Electrical Code (NEC). breaker. Application of two single-pole circuit breakers does not conform to NEC requirements for supplying a 200--240-volt load, even if the breakers are mechanically attached together. Leads L1 and L2 are for different phases; never connect them together. NOTICE L0 (Neutral) Voltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer. 8.1.1 Ground Load Side 100--120-Volt Configurations If the installation requires a factory two-pole circuit breaker, do not connect the load-side terminals of the circuit breaker together; see Figure 8-1. If the installation requires a 100--120-volt, 2-wire system, use a single-pole circuit breaker. See Figure 8-2. When connecting stator phase leads together, size the output lead (L1) to handle the amperage. Use a jumper lead on the line side of the circuit breaker to balance the load of the generator set. Line Side 4 3 2 100--120 Volt 100--120 Volt Figure 8-2 Figure 8-1 2 100--120 Volt 100--120 Volt 100--120-Volt, 2-Wire Configuration L1 L2 L0 (Neutral) L0 GRD. Ground Two-Pole Circuit Breaker L2 L1 Load Side Jumper lead 3 50 Hz L0 GRD. Load Side 4 Single-Pole Circuit Breaker Stator Leads L0--L1 L0--L2 Ground Line Side L1 1 60 Hz L0 (Neutral) L0 GRD. Factory Two-Pole Circuit Breaker Line Side 1 100--120-Volt, 3-Wire Configuration 4 3 2 1 100--120/200--240-Volt, 3-Wire Stator Leads 8.1.2 100--120/200--240-Volt Configurations The 100--120/200--240-volt configuration does not use a jumper lead. If the unit was originally wired for straight 100--120 volt, 3-wire, remove the jumper lead (see Figure 8-1 for location). Select a two-pole circuit TP-6069 6/03 60 Hz L0--L1 L0--L2 L1--L2 Figure 8-3 100--120 Volt 100--120 Volt 200--240 Volt 50 Hz 100--120 Volt 100--120 Volt 200--240 Volt 100--120/200--240-Volt, 3-Wire Configuration Section 8 Reconnection/Adjustments 67 8.1.3 200--240-Volt Configurations The 200--240-volt configuration does not use a jumper lead. If the unit was originally wired for straight 100--120 volt, 3-wire, remove the jumper lead (see Figure 8-1 for location). L0 (Neutral) L0 GRD. Ground L1 Load Side Line Side Single-Pole Circuit Breaker Tape to insulate from ground regulator. See the generator set service manual for information regarding frequency adjustment. The following information illustrates the reconnection of twelve-lead generator sets. In all cases, conform to the National Electrical Code (NEC). Reconnect the stator leads of the generator set to change output phase or voltage. Refer to the following procedure and connection schematics. Follow all safety precautions at the front of this manual and in the text during the reconnection procedure. NOTICE Voltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer. Twelve-Lead Reconnection Procedure 4 3 2 1 Stator Leads 60 Hz L0--L1 Figure 8-4 200--220--240 Volt 2 Wire 50 Hz 200-240 Volt 200--220--240 Volt 200--220--240-Volt, 2-Wire Configuration 8.2 Twelve-Lead Reconnection The reconnection procedure details voltage reconnections only. If the generator set requires frequency changes, adjust the governor and voltage 1. Place the generator start/stop switch in the STOP position. 2. Disconnect generator set engine starting battery, negative (--) lead first. 3. Disconnect power to battery charger, if equipped. 4. Use Figure 8-5 to determine the generator set voltage configuration. Note the original voltage and reconnect the generator set as needed. Route leads through current transformers (CTs) and connect the leads according to the diagram for the desired phase and voltage. EM-250000-E Note: Current Transformers (CTs) are not used on all sets. CT dot or “HI” toward generator. Figure 8-5 68 Generator Reconnection Section 8 Reconnection/Adjustments TP-6069 6/03 Note: Position the current transformers with the dot or HI side CT marking toward the generator set. Note: Only generator sets equipped with AC meter controllers and/or safeguard circuit breakers require CTs. 5. If the controller has meters, remove the controller cover and reposition the meter scale lamp jumper (see Figure 8-6) matching the position of the desired voltage (shown in Figure 8-5). 1 Note: Equipment damage. Verify that the voltage ratings of the transfer switch, line circuit breakers, and other accessories match the desired line voltage. 8. Reconnect the starting battery, negative (--) lead last. Place the generator set master switch in the RUN position to start the generator set. Observe the voltmeter and verify that the unit has the desired line voltage connection. Adjust the voltage using the voltage adjustment potentiometer on the generator controller front panel. See Figure 8-7. 9. Stop the generator set after completing the voltage adjustment. 10. Disconnect the external voltmeter if used. Replace the controller cover. UPPER METER SCALES 1 OFF 3 L0--L1 HERTZ A--C VOLTS L2 L1--L2 A--C AMPERES L3 L3--L1 L1 L1--L2 L1 L1--L2 L2 AMPS L2--L3 VOLTS LOWER METER SCALES OIL PRESS ADJUST EMERGENCY STOP ONLY WATER TEMP S O VOLTAGE 00000 TOTAL HOURS PREALARM HIGH ENGINE TEMPERATURE HIGH ENGINE TEMPERATURE AUXILIARY FAULT AUXILIARY PREALARM PREALARM LOW OIL PRESSURE LOW OIL PRESSURE BATTERY CHARGER FAULT AIR DAMPER LOW WATER TEMPERATURE EMERGENCY STOP LOW BATTERY VOLTAGE SYSTEM READY LOW FUEL OVERSPEED OVERCRANK RUN BATTERY OFF/RESET AUTO GENERATOR SWITCH NOT IN AUTO SILENCE NORMAL ALARM LAMP 1 TEST ADV-5849A- 1. Output voltage adjustment potentiometer TP-5353-6 1. Lamp Jumper Figure 8-6 Meter Scale Lamp Jumper 6. The overvoltage shutdown is standard on Decision-Makert 3+ controllers. The 139/240-volt (low wye) and 277/480-volt (high wye), 3-phase, 4-wire, 60 Hz configurations use different overvoltage shutdown settings than all other configurations. Recalibrate the overvoltage shutdown if the reconnection changes the voltage to or from one of these configurations. See Section 8.3, Decision-Maker 3+ Controller, Overvoltage Shutdown Adjustment. Do not recalibrate the overvoltage adjustment for other voltage changes. 7. If the controller has meters, set the phase selector switch to the L1-L2 position (1-phase or 3-phase configuration depending on generator set connection). Connect a voltmeter across leads L1 and L2 if the controller has no meters. TP-6069 6/03 Figure 8-7 Voltage Adjustment This is bpid 8.3 Decision-Maker 3+ Controller, Overvoltage Shutdown Adjustment Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect the generator set from the load by opening the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load. Section 8 Reconnection/Adjustments 69 Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment. Figure 8-8. The generator set should shut down on an overvoltage fault in approximately 2 seconds. 1 2 Overvoltage Shutdown Adjustment Procedure 1. Disconnect the generator set engine starting battery, negative (--) lead first. Disconnect power to the battery charger (if equipped). R41 2. With the generator set shut down, open the output line circuit breaker to disconnect the load from the generator set. LED4 P2 3. Remove the controller cover. P1 A-336415-A 4. Wrap the shaft of an insulated-handle screwdriver with electrical tape to insulate the metal shaft. Turn the overvoltage potentiometer (R41) on the main circuit board fully clockwise. See Figure 8-8. 1. Overvoltage adjustment potentiometer (R41) 2. LED4 (red) Figure 8-8 5. Connect a digital AC voltmeter (or other 1% minimum accuracy voltmeter) to terminals V0 and V7 on the controller terminal block. See Figure 8-6. 6. Reconnect the battery, negative (--) lead last. 7. Start the generator set by placing the generator set master switch in the RUN position. 8. Adjust the output voltage to 115% of the nominal output voltage using the voltage adjustment potentiometer. If the voltage configuration is 139/240 volts (low wye) or 277/480 volts (high wye), 3-phase, 4-wire, 60 Hz, adjust output voltage to 160 volts across terminals V0 and V7. For all other voltages, adjust the output to 140 volts across terminals V0 and V7. Adjust the voltage using the voltage adjustment potentiometer on the generator controller front panel. See Figure 8-7. 9. Use the insulated screwdriver to slowly rotate the overvoltage adjustment potentiometer (R41) counterclockwise until red LED4 lights. See 70 Section 8 Reconnection/Adjustments Overvoltage Shutdown Adjustment on Main Circuit Board 10. Turn the voltage adjustment potentiometer counterclockwise to prevent overvoltage shutdown upon restart. Restart the generator set. Slowly increase the voltage by turning the voltage adjustment potentiometer clockwise. Verify the shutdown voltage point (115% of the nominal output voltage) by observing the voltmeter and noting when LED4 lights. The generator set should shut down on overvoltage fault in approximately 2 seconds. If the shutdown voltage point is not 115% of nominal voltage, repeat the calibration output procedure; otherwise, continue to step 11. 11. Turn the voltage adjustment potentiometer counterclockwise to prevent overvoltage shutdown upon restart. Restart the generator set. Readjust the generator set output to the nominal voltage using the voltage adjustment potentiometer. 12. Stop the generator set by placing the generator set master switch in the OFF/RESET position. Seal the overvoltage adjustment potentiometer (R41) with RTV sealant or equivalent. Replace the controller cover. TP-6069 6/03 Electroswitch 2-Wire Generator Sets 3-Wire Generator Sets L1 To Generator Set L1 2 1 3 4 7 8 To Shore Power L2 2 1 6 5 3 4 L2 6 5 To Generator Set 7 8 11 12 To Shore Power L0 10 9 To Load To Load Kraus Naimler/American Solenoid (Early Rectangular Design) 2-Wire Generator Sets 3-Wire Generator Sets L1 L1 To Generator Set 1 2 3 4 6 5 To Shore Power 1 2 6 3 4 8 9 10 14 5 L2 L2 8 7 To Generator Set 7 To Shore Power L0 13 To Load To Load Kraus Naimler/American Solenoid (Newer Round Design) 2-Wire Generator Sets 3-Wire Generator Sets L1 L1 To Generator Set L2 3 2 7 6 4 1 To Shore Power 3 2 7 6 11 10 4 1 L2 8 5 To Generator Set 8 5 To Shore Power L0 12 9 To Load To Load TP-5399-5 Figure 8-9 TP-6069 6/03 Marine Manual (Ship-to-Shore) Transfer Switch Section 8 Reconnection/Adjustments 71 Note: Broadrange generator sets. The following adjustment procedure is for readjustment of the voltage regulator and governor for broadrange generator sets with mechanical governors. Kraus Naimler/American Solenoid 4-Wire, 3-Phase Generator Sets L1 L1 3 2 4 1 L2 To Generator 7 Set 6 8 5 10 12 9 L3 Note: Special tool. Frequency meter 50/60 Hz. L2 To Shore Power L3 11 Note: Rheostat connection. Connect a customer-provided rheostat across regulator leads/terminals 33 and 66 to adjust the generator output voltage from a location remote from the generator set. The rheostat (10 kOhms, 1/2 watt minimum) provides a 5-volt adjustment range. L0 L0 15 14 L1 L2 16 L3 13 L0 To Load I-940 Figure 8-10 Marine Manual (Ship-to-Shore) Transfer Switch, continued 8.4 Voltage Regulator Adjustment (4--27EFOZ and 5--32EOZ Models) WARNING 1 2 3 1. Voltage adjustment potentiometer 2. Stability adjustment potentiometer 3. Volts/Hz adjustment potentiometer TT-875-11 Figure 8-11 PowerBoost IIIE Voltage Regulator Hazardous voltage. Moving rotor. Can cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place. Testing the voltage regulator. Hazardous voltage can cause severe injury or death. High voltage is present at the voltage regulator heat sink. To prevent electrical shock do not touch the voltage regulator heat sink when testing the voltage regulator. (PowerBoostt, PowerBoostt III, and PowerBoostt V voltage regulator models only) The voltage regulator is typically located in the controller. Adjustments are possible without removing the voltage regulator. The voltage regulator adjustment procedure applies to both the PowerBoost IIIE (Figure 8-11) and PowerBoost V (Figure 8-12) voltage regulators. 8 7 STAB 6 5 V/HZ VOLTS 4 3 2 3 1 2 1 1. Voltage adjustment potentiometer 2. Stability adjustment potentiometer 3. Volts/Hz adjustment potentiometer TT-875-11 Figure 8-12 PowerBoost V Voltage Regulator 72 Section 8 Reconnection/Adjustments TP-6069 6/03 Stabilizer Potentiometer (Pot) fine tunes the regulator circuitry to reduce light flicker. Voltage Adjustment Pot adjusts the generator voltage output within the range of approximately 100 to 130 volts. Volts/Hz Pot determines the engine speed (Hz) at which the generator output voltage begins to drop. Note: The volts/Hz adjustment does not apply to the following models: Model 4/6.5/8/8.5/9EFOZ 5/8/9/10EOZ Note: On these models, turn the volts/Hz adjustment pot full counterclockwise to stop and seal. No further volts/Hz adjustments are required. locknut and turn it clockwise or counterclockwise to achieve the desired frequency. See Figure 8-13. If a second screw holds the governor arm, loosen the locknut and back out the screw. 9. If applicable, rotate the volts/Hz adjustment pot clockwise until the voltage level begins to drop (as measured on the voltmeter). When set to these specifications, the generator attempts to maintain normal output until the engine speed drops below the frequency set in step 8 as load is applied. 10. Readjust the engine speed to normal (63 Hz/ 1890 rpm for 60 Hz or 52.5 Hz/1575 rpm for 50 Hz). Tighten the locknut when the adjustments are complete. Turn the second screw, if used, to lock the governor arm in place and tighten the locknut. 11. Readjust the voltage adjustment pot if necessary. 12. Readjust the stability pot if necessary. Note: For optimum results, apply full load for voltage regulator adjustment. Voltage Regulator Adjustment Procedure 13. Use the remote rheostat, if equipped, to make final voltage adjustments. 14. Stop the generator set. 1. With the generator set off, turn the remote rheostat, if equipped, to the midpoint. 2. Turn the voltage, volts/Hz, and stability pots fully counterclockwise. 3. Connect the voltmeter and frequency meter to the AC circuit or an electrical outlet. 4. Start the generator set. 5. Rotate the voltage adjustment pot clockwise to increase the voltage (counterclockwise to decrease voltage) to achieve the desired output voltage. 6. Rotate the stability pot clockwise to minimize light flicker. 7. Readjust the voltage adjustment pot if necessary. 8. Adjust the engine speed to the desired cut-in frequency (factory setting 57.5–58 Hz for 60 Hz models or 47.5–48 Hz for 50 Hz models) as measured on frequency meter. To change engine speed adjust the governor arm. Loosen the TP-6069 6/03 1. Locknut 2. Speed adjusting screw 1 2 1-929 Figure 8-13 Governor Adjustment (4EFOZ/5EOZ shown) Section 8 Reconnection/Adjustments 73 Notes 74 Section 8 Reconnection/Adjustments TP-6069 6/03 Appendix A Generator Selection and Wattage Requirements are DC powered by a 12-volt battery. Make sure the calculated total wattage includes only lights actually on the generator set AC circuit. Consider total wattage requirements (lights, motors, appliances) when selecting a generator set or when sizing wattage usage in which available space and construction limit the size of the generator set. Air Conditioners Motors The starting characteristics of air conditioners vary greatly; one 12,000 Btu unit has, for example, lower starting requirements than a 10,000 Btu unit of another variety. When using only one unit, there is usually no starting problem, provided the lighting and appliance load is not too high when starting the unit. When figuring generator set capacity requirements for loads that include electric motors, consider the high current demanded by the motors during startup. The inrush or starting current is typically 2--3 times higher than that required when the motor reaches normal operating speed. Allow reserve for inrush demands plus other loads which could be on the line as the electric motor starts. Use Figure 1 as a guide when selecting generator set capacity requirements involving motor loads. Motor HP Starting (Inrush) Watts Running Watts 1/4 750 330 1/3 1000 400 1/2 1500 600 3/4 2000 750 1 3300 1100 2 4000 2000 3 5000 3000 Figure 1 Simultaneous starting of two air conditioning units, however, can present problems if the generator set capacity is marginal. Because of the variation in starting characteristics among air conditioners, this publication makes no statements regarding multiple-motor starting capabilities of the generator set covered. Consider delayed starting or use of easy-starting devices on air conditioner units whenever simultaneously starting more than one motor. See Figure 2 for typical air conditioner requirements. Information will vary with manufacturer. Appliances Generator sets often furnish AC for appliances such as TV, stereo, electric water heater, etc. With the exception of the resistance-type loads such as the water heater, requirements for appliances are usually low. Do not overlook such loads when figuring total requirements. Allow reserve capacity for anticipated appliance loads to avoid overloading a generator set. Motor Requirements Lighting To calculate lighting load, add the wattage of each generator set-operated lamp. Note that not all of the lights or lamps are on the generator set AC circuit; some Air Conditioner Size (Btu/Hr.) 7,000 9,000 12,000 16,000 24,000 Voltage 115 230 115 230 115 230 115 230 230 Full load amps 9.3 4.8 9.9 5.0 11.8 6.3 16.3 8.0 11.6 Rated load amps 7.7 4.0 7.0 3.5 8.9 4.8 13.0 6.2 10.2 Locked rotor amps 34.0 20.0 40.0 20.0 50.0 31.0 75.0 36.0 56.0 Starting (inrush) watts 3910 4600 4600 4600 5750 7130 8630 8280 12,900 886 920 805 805 1020 1100 1500 1430 2350 Running watts Figure 2 Typical Marine Air Conditioner Requirements, 60 Hz TP-6069 6/03 Appendix A-1 Appendix B Abbreviations The following list contains abbreviations that may appear in this publication. A, amp ABDC AC A/D ADC adj. ADV AHWT AISI ALOP alt. Al ANSI AO API approx. AR AS ASE ASME assy. ASTM ATDC ATS auto. aux. A/V avg. AVR AWG AWM bat. BBDC BC BCA BCI BDC BHP blk. blk. htr. BMEP bps br. BTDC Btu Btu/min. C cal. CARB CB cc CCA ccw. CEC cfh cfm ampere after bottom dead center alternating current analog to digital analog to digital converter adjust, adjustment advertising dimensional drawing anticipatory high water temperature American Iron and Steel Institute anticipatory low oil pressure alternator aluminum American National Standards Institute (formerly American Standards Association, ASA) anticipatory only American Petroleum Institute approximate, approximately as required, as requested as supplied, as stated, as suggested American Society of Engineers American Society of Mechanical Engineers assembly American Society for Testing Materials after top dead center automatic transfer switch automatic auxiliary audiovisual average automatic voltage regulator American Wire Gauge appliance wiring material battery before bottom dead center battery charger, battery charging battery charging alternator Battery Council International before dead center brake horsepower black (paint color), block (engine) block heater brake mean effective pressure bits per second brass before top dead center British thermal unit British thermal units per minute Celsius, centigrade calorie California Air Resources Board circuit breaker cubic centimeter cold cranking amps counterclockwise Canadian Electrical Code cubic feet per hour cubic feet per minute A-2 Appendix CG CID CL cm CMOS cogen. Com conn. cont. CPVC crit. CRT CSA CT Cu cu. in. cw. CWC cyl. D/A DAC dB dBA DC DCR deg., ° dept. dia. DI/EO DIN DIP DPDT DPST DS DVR E, emer. EDI EFR e.g. EG EGSA EIA EI/EO EMI emiss. eng. EPA EPS ER ES ESD est. E-Stop etc. exh. ext. F center of gravity cubic inch displacement centerline centimeter complementary metal oxide substrate (semiconductor) cogeneration communications (port) connection continued chlorinated polyvinyl chloride critical cathode ray tube Canadian Standards Association current transformer copper cubic inch clockwise city water-cooled cylinder digital to analog digital to analog converter decibel decibel (A weighted) direct current direct current resistance degree department diameter dual inlet/end outlet Deutsches Institut fur Normung e. V. (also Deutsche Industrie Normenausschuss) dual inline package double-pole, double-throw double-pole, single-throw disconnect switch digital voltage regulator emergency (power source) electronic data interchange emergency frequency relay for example (exempli gratia) electronic governor Electrical Generating Systems Association Electronic Industries Association end inlet/end outlet electromagnetic interference emission engine Environmental Protection Agency emergency power system emergency relay engineering special, engineered special electrostatic discharge estimated emergency stop et cetera (and so forth) exhaust external Fahrenheit, female fglass. FHM fl. oz. flex. freq. FS ft. ft. lbs. ft./min. g ga. gal. gen. genset GFI fiberglass flat head machine (screw) fluid ounce flexible frequency full scale foot, feet foot pounds (torque) feet per minute gram gauge (meters, wire size) gallon generator generator set ground fault interrupter GND, gov. gph gpm gr. GRD gr. wt. HxWxD HC HCHT HD HET hex Hg HH HHC HP hr. HS hsg. HVAC ground governor gallons per hour gallons per minute grade, gross equipment ground gross weight height by width by depth hex cap high cylinder head temperature heavy duty high exhaust temperature hexagon mercury (element) hex head hex head cap horsepower hour heat shrink housing heating, ventilation, and air conditioning high water temperature hertz (cycles per second) integrated circuit inside diameter, identification International Electrotechnical Commission Institute of Electrical and Electronics Engineers improved motor starting inch inches of water inches of mercury inch pounds incorporated industrial internal internal/external input/output iron pipe International Organization for Standardization joule Japanese Industry Standard kilo (1000) kelvin kiloampere kilobyte (210 bytes) HWT Hz IC ID IEC IEEE IMS in. in. H2O in. Hg in. lbs. Inc. ind. int. int./ext. I/O IP ISO J JIS k K kA KB TP-6069 6/03 kg kg/cm2 kilogram kilograms per square centimeter kgm kilogram-meter kilograms per cubic meter kg/m3 kHz kilohertz kJ kilojoule km kilometer kOhm, kΩ kilo-ohm kPa kilopascal kph kilometers per hour kV kilovolt kVA kilovolt ampere kVAR kilovolt ampere reactive kW kilowatt kWh kilowatt-hour kWm kilowatt mechanical L liter LAN local area network L x W x H length by width by height lb. pound, pounds lbm/ft3 pounds mass per cubic feet LCB line circuit breaker LCD liquid crystal display ld. shd. load shed LED light emitting diode Lph liters per hour Lpm liters per minute LOP low oil pressure LP liquefied petroleum LPG liquefied petroleum gas LS left side Lwa sound power level, A weighted LWL low water level LWT low water temperature m meter, milli (1/1000) M mega (106 when used with SI units), male m3 cubic meter m3/min. cubic meters per minute mA milliampere man. manual max. maximum MB megabyte (220 bytes) MCM one thousand circular mils MCCB molded-case circuit breaker meggar megohmmeter MHz megahertz mi. mile mil one one-thousandth of an inch min. minimum, minute misc. miscellaneous MJ megajoule mJ millijoule mm millimeter mOhm, mΩ milliohm MOhm, MΩ megohm MOV metal oxide varistor MPa megapascal mpg miles per gallon mph miles per hour MS military standard m/sec. meters per second MTBF mean time between failure MTBO mean time between overhauls mtg. mounting TP-6069 6/03 MW mW µF N, norm. NA nat. gas NBS NC NEC NEMA NFPA Nm NO no., nos. NPS NPSC NPT NPTF NR ns OC OD OEM OF opt. OS OSHA OV oz. p., pp. PC PCB pF PF ph., ∅ PHC PHH PHM PLC PMG pot ppm PROM psi pt. PTC PTO PVC qt. qty. R rad. RAM RDO ref. rem. RFI RH RHM rly. megawatt milliwatt microfarad normal (power source) not available, not applicable natural gas National Bureau of Standards normally closed National Electrical Code National Electrical Manufacturers Association National Fire Protection Association newton meter normally open number, numbers National Pipe, Straight National Pipe, Straight-coupling National Standard taper pipe thread per general use National Pipe, Taper-Fine not required, normal relay nanosecond overcrank outside diameter original equipment manufacturer overfrequency option, optional oversize, overspeed Occupational Safety and Health Administration overvoltage ounce page, pages personal computer printed circuit board picofarad power factor phase Phillips head crimptite (screw) Phillips hex head (screw) pan head machine (screw) programmable logic control permanent-magnet generator potentiometer, potential parts per million programmable read-only memory pounds per square inch pint positive temperature coefficient power takeoff polyvinyl chloride quart quantity replacement (emergency) power source radiator, radius random access memory relay driver output reference remote radio frequency interference round head round head machine (screw) relay rms rnd. ROM rot. rpm RS RTV SAE root mean square round read only memory rotate, rotating revolutions per minute right side room temperature vulcanization Society of Automotive Engineers scfm standard cubic feet per minute SCR silicon controlled rectifier s, sec. second SI Systeme international d’unites, International System of Units SI/EO side in/end out sil. silencer SN serial number SPDT single--pole, double--throw SPST single--pole, single--throw spec, specs specification(s) sq. square sq. cm square centimeter sq. in. square inch SS stainless steel std. standard stl. steel tach. tachometer TD time delay TDC top dead center TDEC time delay engine cooldown TDEN time delay emergency to normal TDES time delay engine start TDNE time delay normal to emergency TDOE time delay off to emergency TDON time delay off to normal temp. temperature term. terminal TIF telephone influence factor TIR total indicator reading tol. tolerance turbo. turbocharger typ. typical (same in multiple locations) UF underfrequency UHF ultrahigh frequency UL Underwriter’s Laboratories, Inc. UNC unified coarse thread (was NC) UNF unified fine thread (was NF) univ. universal US undersize, underspeed UV ultraviolet, undervoltage V volt VAC volts alternating current VAR voltampere reactive VDC volts direct current VFD vacuum fluorescent display VGA video graphics adapter VHF very high frequency W watt WCR withstand and closing rating w/ with w/o without wt. weight xfmr transformer Appendix A-3 Appendix C Generator Set Output Ratings Procedure Kohler Co. develops the kilowatt output rating of a Kohlerr marine generator set based upon the calculations specified in ISO 3046 and ISO 8528-1. The calculations correct for environmental variables encountered in a generator set installation. Figure 1 outlines the calculations. Figure 2 contains examples of how heat variables affect generator set ratings. Generator Output corrected = Generator Output observed x Correction Factor Output power is expected to be within ±5% of the specified rating when corrected to reference conditions. Correction factors are determined using the following formulas: 1. For naturally aspirated compression-ignition engines (power limited by excess air): C.F. = [1.175 (29.2 / Dry Barometer in. Hg)1 (Temperature _F + 460/537).75 -- .175] x Alternator Efficiency Reference / Alternator Efficiency Observed 2. For turbocharged compression ignition engines: C.F. = [1.175 (29.2 / Barometer Observed in. Hg).7 (Temperature _F + 460/537)2 -- .175] x Alternator Efficiency Reference / Alternator Efficiency Observed 3. For turbocharged and intercooled compression ignition engines: C.F. = [1.175 (29.2 / Barometer Observed in. Hg).7 (Temperature _F + 460/537)1.2 -- .175] x Alternator Efficiency Reference / Alternator Efficiency Observed Reference conditions: Temperature: 77_F; Pressure: 29.2 in. Hg dry barometer. Kohler sound shield increases ambient intake air approx. 12_F Approximate derates: Temperature: approximately 1% per 10_F (turbocharged engines have a greater derate); Pressure (altitude): approximately 4% per 1000 ft. (1 in. Hg) Figure 1 Generator Output KEY 60 Hz 50 Hz 8.0 7.9 7.8 7.7 7.6 7.5 7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.6 5.5 75 77 80 85 90 95 100 105 110 115 120 Temperature (_F) Figure 2 Example: 6.5EFOZ/8EOZ kW Derates (ISO 3046/ISO 8258-1) A-4 Appendix TP-6069 6/03 KOHLER CO. Kohler, Wisconsin 53044 Phone 920-565-3381, Fax 920-459-1646 For the nearest sales/service outlet in the US and Canada, phone 1-800-544-2444 KohlerPowerSystems.com TP-6069 6/03d E 2000, 2001, 2002, and 2003 by Kohler Co. All rights reserved. Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65)264-6422, Fax (65)264-6455
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes XMP Toolkit : 3.1-702 Producer : Acrobat Distiller 5.0.5 (Windows) Create Date : 2003:06:25 18:23:43Z Modify Date : 2007:05:07 11:53:55-05:00 Metadata Date : 2007:05:07 11:53:55-05:00 Creator Tool : AdobePS5.dll Version 5.2.1 Format : application/pdf Title : kfc Description : Installation Manual Creator : Tech. Pub. Document ID : uuid:8b067d43-f7d0-46b7-9435-3d1c669b998b Instance ID : uuid:e2e6b992-5bc3-44ed-a902-04002326aada Page Count : 92 Subject : Installation Manual Author : Tech. Pub.EXIF Metadata provided by EXIF.tools