Door closer with electronic release & Multi-point hold open
4310ME Series
Installation Instructions
1 Closer Installation
1a Closer Information
Closer is handed at the factory. The hand of the closer must match
the hand of the door (see the door handing diagram below).
1b Voltage
Voltage supplied to the door frame MUST match voltage of the
solenoid.
1c Before beginning this step, determine which type of
wiring option will be used, and follow the
corresponding instructions:
Concealed Wiring: see Figure 3 on page 3.
a. Prepare the frame per the
proper template on page
4. Be sure all the holes are
dimensioned correctly before
drilling and tapping.
b. Assemble the conduit
connector provided to the
exible conduit, then attach to
the hole in the mounting plate.
c. Secure the mounting plate
to the frame with the screws
provided.
Surface Wiring: see Figure 4 on
page 3.
LNOTE: Remove the knockout in the top of the cover.
a. Prepare the frame per the proper template on page 4. Be sure
all the holes are dimensioned correctly before drilling and
tapping.
b. Secure the mounting plate to the frame with the screws
provided.
c. Attach the surface run Z\x” EMT conduit to the hole in the
bracket on the mounting plate. Be sure the conduit is securely
attached to the bracket.
1d Wiring Connections
Make the wiring connections at this time. Connect the two black
wires to the input voltage (polarity is not important). The green wire
MUST be connected to an earth ground (see Figures 3 & 4 on page
3).
1e Spacer/Arm
Place the spacer on the closer shaft, slide the arm onto the closer
shaft, and secure it with the arm shaft screw (see Figure 1 on page
3).
1f Track Roller
Insert the track roller into the track, and end caps into both ends of
the track. Place track plugs in the track where needed. Using the
fasteners provided, mount the track on the door per the template on
page 4.
1g Set Screw
Loosen the set screw in the end of the arm, open the door
approximately 30˚, pull the arm over the top of the door and
connect to the track roller. Tighten the set screw rmly.
1h Electric Checkout
Regulate the closer and perform an electrical checkout, as
instructed on page 2, before installing the closer cover.
1i Disengage the Swing Free Arm
To disengage the swing-free action of the arm, insert the locking
screw (stored in the tube portion of the arm) into the shaft end of
the arm, and tighten securely.
!
WARNING
!
!
HAZARDOUS VOLTAGE
CAN SHOCK AND CAUSE
SEVERE INJURY
Disconnect power before
making any electrical
connections or performing
maintenance.
HOW TO TELL HAND OF DOOR:
LEFT
HAND
DOOR
RIGHT
HAND
DOOR
MAXIMUM OPENING FORCE
=
33 ft-lbs
45 N-m
58 N
Customer Service
1-877-671-7011 www.allegion.com/us
2 Regulation Instructions
See Figure 2 on the opposite page for regulating screw
location, door control diagram & spring power adjustment
2a Spring Power Adjustment
DO NOT ALLOW THE DOOR TO SLAM INTO THE FRAME. The
spring power should be adjusted only if more power is needed to
close the door. Turning the spring adjustment B\cx” Allen Wrench
clockwise will increase the spring power. Maximum adjustment is
six (6) turns.
2b Regulation
A “normal” closing time from a 90° position is five (5) to seven (7)
seconds, equally divided between the MAIN and LATCH SPEED.
If adjustments are needed, use C\cxAllen Wrench. To adjust the
MAIN SPEED, turn the regulating screw clockwise to slow the
door speed, or counterclockwise to increase the door speed.
LATCH SPEED is adjusted the same way. When adjusting the
BACKCHECK, turn the regulating screw clockwise to increase
the amount of force, or counterclockwise to reduce the amount of
force. DO NOT USE THE ABRUPT BACKCHECK SETTING OR
EXPECT THE CLOSER TO ACT AS A STOP!
CAUTION
Improper installation or regulation may result in personal
injury or property damage. Follow all instructions carefully.
For questions, call LCN at
877-671-7011
3 Electrical Checkout
After completion of installation & wiring, and with the unit
properly powered, perform the following tests:
3a Hold Open
With power on, open the door any position and release. The door
should remain in the hold-open position within 10°. For a bypass
model to hold open, the door must be opened beyond the degree of
the door swing indicated on the label.
3b Door
If the door does not remain in the hold open position, push the on/
off switch. Open the door again. If the shaft end of the arm still does
not hold open, verify the proper voltage input at the solenoid leads.
3c Power Release
Turn the power off. The shaft end of the arm should rotate and pick
up the rest of the arm, closing the door completely. Push the on/off
switch again to restore the power.
3d Put on Closer Cover
After the electrical checkout is complete, t the closer cover onto
the closer and insert cover screws in proper locations. Hold the
cover rmly against the mounting plate while tightening the cover
screws securely.
3e Rechecking the System
The system should be checked at regular intervals. It is
recommended that steps 3a-3c be repeated every 90 days.
4 Electrical Data for Door Holder Solenoid
24V AC-DC Nominal +10% - 15% @ 0.075 Amp. Max.
120V AC-DC Nominal +10% - 15% @ 0.030 Amp. Max.
24 V Hold Open Force Adjustment
If the door is hard to pull out of the hold open position, adjust as
shown.
IMPORTANT
The closer leaves the factory set at a maximum holding force.
The holding force may be decreased and increased again, but
it cannot be increased beyond the original setting.
Turn
counterclockwise
to decrease
the holding force
+
Figure 1
Cover
Mounting Bracket For
Surface Run Conduit
Hole For Concealed
Conduit Connection
Track
Roller
Arm
Assy.
Track
Plug
End
Cap
Spring
Power
Adjustment
Cover
Screws
Spacer
Arm
Shaft
Screw
Figure 2
Latch
Speed
Latch
Speed
Main
Speed
Backcheck
Figure 3 Figure 4
Connect Black
Wires to Input
Voltage Leads
(Polarity Not
Important)
Connect
Greenwire
To Earth
Ground
Connect Greenwire
To Earth Ground
Connect Black
Wires to Input
Voltage Leads
(Polarity Not
Important)
1
2
3
Backcheck
Main
Speed
6
Turns
Max.
To Increase Closing Power
Arm
Locking
Screw
®
EM 0134
Additional Notes: Revision History Revision Description:
M > Revised artwork
1. None L M N P R S
038791 043228
Material
White Paper
Edited By Approved By EC Number Release Date
D. Myers M. Sasso 043228 01-01-14
Notes
1. printed two sides
2. printed black
3. tolerance ± .13
4. printed in country may vary
5. drawings not to scale
Title
4310ME Series Instruction Sheet
Creation Date
05-10-10
Number
18762
Revision
M
Created By
N/A Activity
3899 Hancock Expwy
Security, CO 80911 © Allegion 2014Software: InDesign CS6
17.00 4.25
11.000 11.000
BEGINNING SHEET FOLDED SHEET
Front
Page 1 Page 2 Page 3 Page 4
Back

Navigation menu