Door closer with electronic release & Multi-point hold open
4410ME Series
Installation Instructions
1 Closer Installation
1a Closer Information
Closer is handed at the factory. The hand of the closer must
match the hand of the door (see the door handing diagram below).
Determine the closer mounting template to use - Standard or Flush-
Ceiling (see page 4). Refer to the proper template for the entire
installation
1b Voltage
Voltage supplied to the door frame MUST match voltage of the
solenoid.
1c Before beginning this step, determine which
type of wiring option will be used, and follow the
corresponding instructions:
Concealed Wiring: see Figure 3
on page 3.
a. Prepare the frame per the
proper template on page
4. Be sure all the holes are
dimensioned correctly before
drilling and tapping.
b. Assemble the conduit
connector provided to the
exible conduit, then attach to
the hole in the mounting plate.
c. Secure the mounting plate
to the frame with the screws
provided.
Surface Wiring: see Figure 4 on page 3.
LNOTE: Remove the knockout in the top of the cover.
a. Prepare the frame per the proper template on page 4. Be sure
all the holes are dimensioned correctly before drilling and
tapping.
b. Secure the mounting plate to the frame with the screws
provided.
c. Attach the surface run Z\x” EMT conduit to the hole in the
bracket on the mounting plate. Be sure the conduit is securely
attached to the bracket.
1d Wiring Connections
Make the wiring connections at this time. Connect the two black
wires to the input voltage (polarity is not important). The green wire
MUST be connected to an earth ground (see Figures 3 & 4 on page
3).
1e Main Arm
Place the main arm onto the shaft, approximately 90° to the closer
body, and secure with the arm shaft screw.
1f Rod & Shoe
Attach the rod and shoe to the door, per the proper template on
page 4, with the provided screws.
1g Insert the Rod
Open the door partway and insert the rod into the forearm, then
close the door. Pull the Main Arm to a right angle (90°) to the door,
insert the arm set screw, and tighten securely.
1h Regulate the Closer
Regulate the closer and perform the electrical checkout, as
instructed on page 2, before installing the closer cover.
HOW TO TELL HAND OF DOOR:
LEFT
HAND
DOOR
RIGHT
HAND
DOOR
MAXIMUM OPENING FORCE
=
33 ft-lbs
45 N-m
58 N
WARNING
!
HAZARDOUS VOLTAGE
CAN SHOCK AND CAUSE
SEVERE INJURY
Disconnect power before
making any electrical
connections or performing
maintenance.
Customer Service
1-877-671-7011 www.allegion.com/us
2 Regulation Instructions
See Figure 2 on the opposite page for regulating screw
location, door control diagram & spring power adjustment
2a Spring Power Adjustment
DO NOT ALLOW THE DOOR TO SLAM INTO THE FRAME. The
spring power should be adjusted only if more power is needed to
close the door. Turning the spring adjustment B\cx” Allen Wrench
clockwise will increase the spring power. Maximum adjustment is
six (6) turns.
2b Regulation
A “normal” closing time from a 90° position is five (5) to seven
(7) seconds, equally divided between the MAIN and LATCH
SPEED. If adjustments are needed, use a C\cx” Allen Wrench. To
adjust the MAIN SPEED, turn the regulating screw clockwise to
slow the door speed, or counterclockwise to increase the door
speed. LATCH SPEED is adjusted the same way. When adjusting
the BACKCHECK, use the least amount of force necessary
to sufficiently slow the swing of the door.To adjust the closer
BACKCHECK, turn the regulating screw clockwise to increase
the amount of force, or counterclockwise to reduce the amount of
force. DO NOT USE THE ABRUPT BACKCHECK SETTING OR
EXPECT THE CLOSER TO ACT AS A STOP!
CAUTION
Improper installation or regulation may result in personal
injury or property damage. Follow all instructions carefully.
For questions, call LCN at
877-671-7011
3 Electrical Checkout
After completion of installation & wiring, and with the unit
properly powered, perform the following tests:
3a Hold Open the Door
With power on, open the door any position and release. The door
should remain in the hold-open position within 10°. For a bypass
model to hold open, the door must be opened beyond the degree of
the door swing indicated on the label.
3b Door
If the door does not remain in the hold open position, push the on/
off switch. If the door still does not hold open, verify the proper
voltage input at the solenoid leads.
3c Power Release
Turn the power off. The door should close completely.
3d Manual Release
To release manually, pull rmly on the door. The door should close
completely.
3e Rechecking the System
The system should be checked at regular intervals. It is
recommended that steps 3a-3c be repeated every 90 days.
4 Electrical Data for Door Holder Solenoid
24V AC-DC Nominal +10% - 15% @ 0.075 Amp. Max.
120V AC-DC Nominal +10% - 15% @ 0.030 Amp. Max.
24 V Hold Open Force Adjustment
If the door is hard to pull out of the hold open position, adjust as
shown.
IMPORTANT
The closer leaves the factory set at a maximum holding force.
The holding force may be decreased and increased again, but
it cannot be increased beyond the original setting.
Turn
counterclockwise
to decrease
the holding force
+
Figure 1
Figure 2
4 erugiF3 erugiF
Cover
Mounting Bracket For
Surface Run Conduit
Hole For
Concealed
Conduit
Connection
Rod & Shoe
Assembly
Arm
Set
Screw
Cover
Screws
Arm
Shaft
Screw
Arm
Assy.
Spring
Power
Adjust.
Latch
Speed
Main
Speed
Backcheck
Connect Green
Wireto Earth
Ground Connect Black
Wires to Input
Voltage Leads
(Polarity Not
Important)
Connect Black
Wires to Input
Voltage Leads
(Polarity Not
Important)
Connect Greenwire
To Earth Ground
1
2
3
Backcheck
Main
Speed
Latch
Speed
6
Turns
Max.
To Increase Closing Power
HOLD OPEN ANY POINT TO 150°
HOLD OPEN BYPASS 80° OR 140°
HOLD OPEN ANY POINT TO 170°
HOLD OPEN BYPASS 80° OR 140°
HOLD OPEN ANY POINT TO 150°
HOLD OPEN BYPASS 80° OR 140°
HOLD OPEN ANY POINT TO 170°
HOLD OPEN BYPASS 80° OR 140°
NOTES-
1.
2.
3.
4.
5.
6.
7.
Voltage supplied to unit must match voltage shown on Sentronic label.
Locate closer and shoe from of pivot when pivots are used. For use
with swing clear hinges, consult factory.
Auxiliary stop is recommended. For use with overhead stops, shoe
must be lowered to clear holder.
Long arm required for opening beyond 160°. Reveal not exceed 3 "
(5 " FRAME).
Maximum stop thickness is ".
Electric connector provided by LCN.
Reinforcing per ANSI\SDI - 100 is recommended for hollow metal
door and frames.
7/8
3/4
5/8
C
L
®
®
HAZARDOUS VOLTAGE
CAN SHOCK AND
CAUSE SEVERE INJURY
Disconnect power before
making any electrical
connections or performing
maintenance.
WARNING
!
4410 ME
Additional Notes: Revision History Revision Description:
H > Revised artwork
1. None G H J K L M
038791 043228
Material
White Paper
Edited By Approved By EC Number Release Date
D. Myers M. Sasso 043228 01-01-14
Notes
1. printed two sides
2. printed black
3. tolerance ± .13
4. printed in country may vary
5. drawings not to scale
Title
4410ME Series Instruction Sheet
Creation Date
05-10-10
Number
15022
Revision
H
Created By
N/A Activity
3899 Hancock Expwy
Security, CO 80911 © Allegion 2014Software: InDesign CS6
17.00 4.25
11.000 11.000
BEGINNING SHEET FOLDED SHEET
Front
Page 1 Page 2 Page 3 Page 4
Back