LCN 4410ME Installation Guide LCN4410MESeries Instructions

User Manual: LCN LCN 4410ME Installation Guide Installation Guide

Open the PDF directly: View PDF PDF.
Page Count: 5

DownloadLCN  4410ME Installation Guide LCN4410MESeries Instructions
Open PDF In BrowserView PDF
*15022*

4410ME Series

15022

Door closer with electronic release & Multi-point hold open

1

Closer Installation

1a

Closer Information

Closer is handed at the factory. The hand of the closer must
match the hand of the door (see the door handing diagram below).
Determine the closer mounting template to use - Standard or FlushCeiling (see page 4). Refer to the proper template for the entire
installation

1b

Voltage

Voltage supplied to the door frame MUST match voltage of the
solenoid.

1c

Before beginning this step, determine which
type of wiring option will be used, and follow the
corresponding instructions:

!

Concealed Wiring: see Figure 3
on page 3.
a. Prepare the frame per the
proper template on page
4. Be sure all the holes are
dimensioned correctly before
drilling and tapping.
b. Assemble the conduit
connector provided to the
flexible conduit, then attach to
the hole in the mounting plate.
c. Secure the mounting plate
to the frame with the screws
provided.

Warning

Installation Instructions
Surface Wiring: see Figure 4 on page 3.
LL NOTE: Remove the knockout in the top of the cover.
a. Prepare the frame per the proper template on page 4. Be sure
all the holes are dimensioned correctly before drilling and
tapping.
b. Secure the mounting plate to the frame with the screws
provided.
c. Attach the surface run Z\x” EMT conduit to the hole in the
bracket on the mounting plate. Be sure the conduit is securely
attached to the bracket.

1d

Make the wiring connections at this time. Connect the two black
wires to the input voltage (polarity is not important). The green wire
MUST be connected to an earth ground (see Figures 3 & 4 on page
3).

1e

Disconnect power before
making any electrical
connections or performing
maintenance.

Main Arm

Place the main arm onto the shaft, approximately 90° to the closer
body, and secure with the arm shaft screw.

1f
HAZARDOUS VOLTAGE
CAN SHOCK AND CAUSE
SEVERE INJURY

Wiring Connections

Rod & Shoe

Attach the rod and shoe to the door, per the proper template on
page 4, with the provided screws.

1g

Insert the Rod

Open the door partway and insert the rod into the forearm, then
close the door. Pull the Main Arm to a right angle (90°) to the door,
insert the arm set screw, and tighten securely.

1h

Regulate the Closer

Regulate the closer and perform the electrical checkout, as
instructed on page 2, before installing the closer cover.

HOW TO TELL HAND OF DOOR:

LEFT
HAND
DOOR

RIGHT
HAND
DOOR

=

33 ft-lbs
45 N-m
58 N

MAXIMUM OPENING FORCE

Customer Service
1-877-671-7011

www.allegion.com/us

© Allegion 2014
Printed in U.S.A.
15022 Rev. 01/14-h

2

Regulation Instructions

See Figure 2 on the opposite page for regulating screw
location, door control diagram & spring power adjustment

2a

Spring Power Adjustment

DO NOT ALLOW THE DOOR TO SLAM INTO THE FRAME. The
spring power should be adjusted only if more power is needed to
close the door. Turning the spring adjustment B\cx” Allen Wrench
clockwise will increase the spring power. Maximum adjustment is
six (6) turns.

2b

Regulation

A “normal” closing time from a 90° position is five (5) to seven
(7) seconds, equally divided between the MAIN and LATCH
SPEED. If adjustments are needed, use a C\cx” Allen Wrench. To
adjust the MAIN SPEED, turn the regulating screw clockwise to
slow the door speed, or counterclockwise to increase the door
speed. LATCH SPEED is adjusted the same way. When adjusting
the BACKCHECK, use the least amount of force necessary
to sufficiently slow the swing of the door.To adjust the closer
BACKCHECK, turn the regulating screw clockwise to increase
the amount of force, or counterclockwise to reduce the amount of
force. DO NOT USE THE ABRUPT BACKCHECK SETTING OR
EXPECT THE CLOSER TO ACT AS A STOP!

Caution
Improper installation or regulation may result in personal
injury or property damage. Follow all instructions carefully.
For questions, call LCN at
877-671-7011

3

Electrical Checkout

After completion of installation & wiring, and with the unit
properly powered, perform the following tests:

3a

Hold Open the Door

With power on, open the door any position and release. The door
should remain in the hold-open position within 10°. For a bypass
model to hold open, the door must be opened beyond the degree of
the door swing indicated on the label.

3b

Door

If the door does not remain in the hold open position, push the on/
off switch. If the door still does not hold open, verify the proper
voltage input at the solenoid leads.

3c

Power Release

Turn the power off. The door should close completely.

3d

Manual Release

To release manually, pull firmly on the door. The door should close
completely.

3e

Rechecking the System

The system should be checked at regular intervals. It is
recommended that steps 3a-3c be repeated every 90 days.

4

Electrical Data for Door Holder Solenoid
24V AC-DC Nominal +10% - 15% @ 0.075 Amp. Max.
120V AC-DC Nominal +10% - 15% @ 0.030 Amp. Max.

24 V Hold Open Force Adjustment

If the door is hard to pull out of the hold open position, adjust as
shown.

Important
The closer leaves the factory set at a maximum holding force.
The holding force may be decreased and increased again, but
it cannot be increased beyond the original setting.

+
Turn
counterclockwise
to decrease
the holding force

Figure 1

Mounting Bracket For
Surface Run Conduit

Cover

Spring
Power
Adjust.

Hole For
Concealed
Conduit
Connection
Rod & Shoe
Assembly

Arm
Assy.

Arm
Set
Screw

Arm
Shaft
Screw

Cover
Screws

Backcheck

Figure 2

Main
Speed

1
2

Latch
Speed
Main
Speed

3

Latch
Speed

Backcheck

To Increase Closing Power

Figure 3
Connect Green
Wireto Earth
Ground

6
Turns
Max.

Figure 4

Connect Black
Wires to Input
Voltage Leads
(Polarity Not
Important)

Connect Black
Wires to Input
Voltage Leads
(Polarity Not
Important)

Connect Greenwire
To Earth Ground

4410 ME

HOLD OPEN ANY POINT TO 150°
HOLD OPEN BYPASS 80° OR 140°
HOLD OPEN ANY POINT TO 170°
HOLD OPEN BYPASS 80° OR 140°

HOLD OPEN ANY POINT TO 150°
HOLD OPEN BYPASS 80° OR 140°
HOLD OPEN ANY POINT TO 170°
HOLD OPEN BYPASS 80° OR 140°

! WARNING

HAZARDOUS VOLTAGE
CAN SHOCK AND
CAUSE SEVERE INJURY
Disconnect power before
making any electrical
connections or performing
maintenance.

NOTES1. Voltage supplied to unit must match voltage shown on Sentronic® label.
2. Locate closer and shoe from CL of pivot when pivots are used. For use
with swing clear hinges, consult factory.
3. Auxiliary stop is recommended. For use with overhead stops, shoe
must be lowered to clear holder.
4. Long arm required for opening beyond 160°. Reveal not exceed 3 7/8"
(5 3/4" FRAME).
5. Maximum stop thickness is 5/8".
6. Electric connector provided by LCN.
7. Reinforcing per ANSI\SDI - 100 is recommended for hollow metal
door and frames.

®

4.25

17.00
Back

Front

Page 1

Page 2

Page 3

Page 4

11.000

BEGINNING SHEET

folded SHEET

Additional Notes:
1. None

11.000

Revision History
G

H

038791

043228

Material

J

K

White Paper

Notes
1. printed two sides
2. printed black
3. tolerance ± .13
4. printed in country may vary
5. drawings not to scale

L

M

Revision Description:
h > Revised artwork

Edited By

Approved By

EC Number

Release Date

D. Myers

M. Sasso

043228

01-01-14

Title

4410ME Series Instruction Sheet
Creation Date
05-10-10
Created By
N/A
Software: InDesign CS6

Number

Revision

15022
Activity
3899 Hancock Expwy
Security, CO 80911

h

© Allegion 2014



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.3-c011 66.145661, 2012/02/06-14:56:27
Create Date                     : 2014:01:02 09:23:17-07:00
Metadata Date                   : 2014:01:02 09:23:19-07:00
Modify Date                     : 2014:01:02 09:23:19-07:00
Creator Tool                    : Adobe InDesign CS6 (Windows)
Instance ID                     : uuid:40672c71-d30f-4176-85d9-3e8c00b83c62
Original Document ID            : xmp.did:516915126ECCE1118A0D8AD340C27D6B
Document ID                     : xmp.id:306D812DCA73E311B4D0E88C51DF512F
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:2F6D812DCA73E311B4D0E88C51DF512F
Derived From Document ID        : xmp.did:47A44EA0A139E21197309D1C525C39AC
Derived From Original Document ID: xmp.did:516915126ECCE1118A0D8AD340C27D6B
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CS6 (Windows)
History Changed                 : /
History When                    : 2014:01:02 09:23:17-07:00
Format                          : application/pdf
Producer                        : Adobe PDF Library 10.0.1
Trapped                         : False
Page Count                      : 5
Creator                         : Adobe InDesign CS6 (Windows)
EXIF Metadata provided by EXIF.tools

Navigation menu