LENNOX Air Handler (indoor Blower&evap) Manual L0805330
User Manual: LENNOX LENNOX Air Handler (indoor blower&evap) Manual LENNOX Air Handler (indoor blower&evap) Owner's Manual, LENNOX Air Handler (indoor blower&evap) installation guides
Open the PDF directly: View PDF .
Page Count: 20
Download | |
Open PDF In Browser | View PDF |
INSTALLATION INSTRUCTIONS ® ,1,_2008Lennox Industries Inc, Dallas, Texas, USA Dave Lennox Signature ® Collection CB31MV Units X_ WARNING MULTI-POSITION 505,341M 04/08 Supersedes 07/07 AIR HANDLER TeCh n i cal bNcations Litho U.S.A. CAUTION CB31MV Up-flow/Down-flow Unit Dimensions CB31MV Horizontal LH/RH Unit Dimensions General Information IMPORTANT _, IMPORTANT .... ...... ........................... 4 4 Requirements 4 ................................. Installing the Unit .............................. 4 Brazing Connections ........................... 8 Installing the Condensate Drain ................. 9 Inspecting and Replacing Filters ................. 9 Sealing the Unit ............................... 9 Adjusting the BDC3 Blower Control Board ........ 9 Adjusting the Blower Speed 9 .................... .................. Repairing or Replacing Cabinet Insulation ......... THESE CHECK MOTOR SHIPPING INSTRUCTIONS FOR AND REMOVE THE 3 Shipping and Packing List ...................... Making Electrical Connections RETAIN 2 FOR FUTURE FOLLOWING ITEMS BEFORE 11 20 REFERENCE OPERATING UNIT. BOLT HOUSING SUPPORT PAD B HORIZONTAL DRAIN PAN (SEE UP-FLOW APPLICATIONS ON PAGE 4 AND DOWN-FLOWAPPLICATIONS ON PAGE 6 ) E TOP CAP SHIPPING BRACKET (REPLACE SCREWS IN TOP CAP AFTER REMOVAL) MOTOR C SHIPPING BRACKET D G REFRIGERANT LINE CAPS [SEE BRAZING CONNECTION ON PAGE 8] CONFIGURATION JUMPERS (IF NECESSARY) (SEE ADJUSTING THE BDC3 BLOWER CONTROL BOARD ON PAGE 11. F 04/08 IIIlllllllllllllllllllll Page 1 505,341M IIIHIIIIIIIIIIIIIIIIIIIII DIMENSION CB31MV-041 inches (ram) CB31MV-051, -065 inches (ram) A B C D E F G H 51 (1295) 21-1/4 (540) 22-5/8 (502) 19-3/4 (575) 21 (533) 20 (508) 26-3/8 (670) 24-5/8 (625) 58-1/2 (1486) 21-1/4 (540) 24-5/8 (625) 19-3/4 (502) 23 (584) 20 (508) 27-7/8 (708) 30-5/8 (778) SUPPLY AIR 3/4 (19) OPENING (18) 5/8 3/4 (1_ 3/4 LINE VOLTAGE INLETS (TOP ANDLEFT SIDE) LOW VOLTAGE INLETS (TOP AND RIGHT SIDE) (215) TOP VIEW t8 8 PIPING PLATE -(18) _ FILTER ACCESS FILTER \ B (SEE DETAIL BELOW LEFT) G SUCTION LINE OPTIONAL ELECTRIC HEAT ,i- (FIELD INSTALLED) /= LIQUID LINE / ................. PIPING DETAILPLATE (SEE BELOW) SUCT,ON LINE ! X LIQUI LIN ED..,....,.._€C 5/8 FILTER RETURN AIR SUPPLY 5/8 5/8 1 5/8 (18) (18) (25) (18) FRONT SIDE VIEW VIEW (16) (16) 5/8 (16) 5/8 FRONT VIEW _SUPPLy (RIGHT SIDE) LOWVOLTAGE LINE VOLTAGE (LEFT SIDE) / // t OPTIONAL HEAT (FIELD UP-FLOW DETAIL POSITION OF PIPING DOWN-FLOW PLATE Page 2 505341M 04/08 ELECTRIC INSTALLED) POSITION A l.''_'_ tz°U SIDE VIEW (1/ 5/8) DIMENSION CB31MV-041 inches (ram) CB31MV-051, -065 inches (ram) A B C D E F G H 51 (1295) 21-1/4 (540) 22-5/8 (502) 19-3/4 (575) 21 (533) 20 (508) 26-3/8 (670) 24-5/8 (625) 58-1/2 (1486) 21-1/4 (540) 24-5/8 (625) 19-3/4 (502) 23 (584) 20 (508) 27-7/8 (708) 30-5/8 (778) LIQUID LINE / CONDENSATE DRAINS (2) FILTER t I!! i I! i i C I!::!:::::::::::: J uu \ \ LIQUID LINE DETAIL OF PIPING PLATE 5/8(16) 5/8(15) SUCTION / OPTIONAL ELECTRIC HEAT LINE TOP VIEW (FIELD LINE VOLTAGE INLETS (TOP AND RIGHT SIDE) INSTALLED) 11-1/16 \ 3/4 (19) 3/4 (19) 1 (25) 3/4 (19) FILTER ACCESS LOW VOLTAGE INLETS (BOTTOM AND RIGHT SIDE) 5/8 (16) END VIEW FRONT VIEW HORIZONTAL POSITION (RIGHT-HAND END VIEW AIR DISCHARGE) FILTER SUCTION LINE LIQUID / LINE OPTIONAL (FIELD 3/4 (19) ELECTRIC HEAT SUCTION INSTALLED) LINE jU TOP VIEW (19) I D DETAIL OF PIPING PLATE 5/8(16) 5/8(16) INLETS (TOP AND LEFT SIDE) t LIQUID LINE 11q/16 LOW VOLTAGE 3/4 I1_ FILTER ACCESS / ........... 1 (25) AIR : CONDENSATE DRAINS (2) 3/4 1-1/2 (19) -'_ LINE VOLTAGE INLETS (BOTTOM AND LEFT SIDE) END VIEW 1-3/4 (44) (38) 5/8(16) FRONT VIEW HORIZONTAL POSITION (LEFT-HAND END VIEW AIR DISCHARGE) Page 3 CB31MV SERIES I A, WARNING This unit is approved for installation clearance to combustible material as stated on the unit rating plate, Accessibility and service clearances must take precedence over combustible material clearances. WARNING The CB31MV air handler units are designed for installation with optional field-installed electric heat and a matched remote outdoor unit, These units are for indoor installation only, The units are designed for multi-positional installations and are shipped (completely assembled) from the factory for installation in up-flow or horizontal right-hand air discharge applications, These instructions are intended as a general guide and do not supersede local or national codes in any way. Consult authorities having jurisdiction before installation. Check equipment for shipping damage; if found, immediately report damage to the last carrier. Package 1 of 1 contains the following: 1--Assembled air handler unit CB31MV units are factory-configured for installation in up-flow or horizontal right-hand air discharge applications. The units must be field-modified for installation in either down-flow or horizontal left-hand air discharge applications, DISASSEMBLE AND REASSEMBLE AIR HANDLER UNIT The CB31MV air handler unit consists of two sections which are shipped assembled from the factory, If necessary, the unit may be disassembled to facilitate setting the unit, Follow the steps below: To disassemble: Step 1. Remove access panels. Step 2. Remove both blower and coil assemblies. This will lighten the cabinet for lifting, Step 3. Remove one screw from the left and right posts inside the unit. Remove one screw from each side on the back of the unit, Unit sections will now separate, To reassemble: Step 1. Align cabinet sections together, Step 2, Reinstall screws, Step 3, Replace blower and coil assemblies. Step 4. Replace access panel, UP-FLOW AIR DISCHARGE APPLICATION 2--Drip shields (for down-flow application only) Use the following procedures to configure the unit for up-flow operations: In addition to conforming to manufacturer's installation instructions and local municipal building codes, installation of Lennox air handler units (with or without optional electric heat), MUST conform with the following National Fire Protection Association (NFPA) standards: • NFPA No. 90A - Standard for Installation of Air • Conditioning and Ventilation Systems NFPA No. 90B - Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems Step 1. Remove access panels. Step 2. Remove corrugated padding from the space between the blower and coil assemblies, Step 3. Discard drip shields which are shipped inside corner post packaging. The shields are used in down-flow applications only. Step 4. The horizontal drain pan must be removed when the coil blower is installed in the up-flow position, Removing horizontal drain pain will allow proper airflow and increase efficiency. Page 4 505341M 04/08 Step5. Placeunitindesiredlocation.Unitmustbelevel. Connectreturnand supply air plenumsas requiredusingsheetmetalscrews. Step6. If the applicationwill not includea returnair plenum,installtheunitona raisedstandatleast 14"fromthe floorto ensureproperair return. Lennoxoffersanoptionalup-flowunitstandas listedintable1. UP-LOAD / DOWN-FLOW DRAIN PAN HORIZONTAL PAN HORIZONTAL DRAIN DOWN-FLOW NO ADJUSTMENT HORIZONTAL Fq I; II II UP-FLOW/ 1(MUST DRAIN PAN BE REMOVED) i Remove the screws from the rail at the back of unit and at the cabinet support rail. Step 2. Step 3. Remove the down-flow rail then replace screws. Seal around the exiting drain pipe, liquid line, and suction line to prevent humid air from infiltrating into the unit. Table 1. Optional Unit Side Stand (Up-Flow Only) 1/2 IN. SCREWS -41 through -65. 45K32 HORIZONTAL RIGHT-HAND APPLICATION MAXIMUM ELECTRICAL Kit Number 45K31 IS NECESSARY Step 1. Figure 1. Up-flow Configuration -21,-26, and -31 RAIL Figure 2. Right-hand Discharge Configuration HORIZONTAL RIGHT-HAND DISCHARGE APPLICATION IN HIGH HUMIDITY AREAS For horizontal applications in high humidity areas remove the down-flow rail closest to the drain pan. To remove rail: DRAIN PAN DOWN-FLOW oo_J i Model DRIP SHIELD (-068 MODELS) ANGLE IRON OR SHEET METAL CLEARANCE INLET 4 IN. (102 MM) AIR DISCHARGE Use the following procedures to configure the unit for horizontal right-hand discharge operations: NOTE - For horizontal applications, a secondary drain pan is recommended. Refer to local codes. Step 1. Figure 3. Suspending Remove access panels and the horizontal drip shield (-068 model) and the corrugated padding between the blower and coil assembly. Discard the corrugated padding and the down-flow drip shields from the foam pads on top of the unit. Step 2. Install the horizontal shield on the front edge of the horizontal drain pan as illustrated in figure 2. Step 3. No further adjustment is necessary. Set unit so that it is sloped 1/4 inch towards the drain pan end of the unit. Step 4. FRONT VIEW END VIEW Horizontal Unit A IMPORTANT HORIZONTAL LEFT-HAND AIR DISCHARGE APPLICATION If suspending the unit, it must be supported along the entire length of the cabinet. If using chain or strap, use a piece of angle iron or sheet metal attached to the unit (either above or below) so that the full length of the cabinet is supported. Use securing screws no longer than 1/2 inch to avoid damage to coil or filter as illustrated in figure 3. Connect return and supply air plenums as required using sheet metal screws. SECURING TAB ON CABINET SUPPORT RAIL DOWNFLOW RAIL 7'_ HORIZONTAL DRIP SHIELD HORIZONTAL DRAIN PAN Figure 4. Left-hand Air Discharge Configuration Page 5 CB31MV SERIES NOTE - For horizontal applications, a secondary drain pan is recommended. Refer to local codes. Use the following procedures to configure the unit for horizontal left-hand discharge operations: Step 1, Remove access panels. Remove corrugated padding from space between the blower and coil assemblies. Discard drip shields which are shipped inside corner post packaging. The shields are used in down-flow applications only, Step 2, Slide coil assembly from unit, Remove horizontal drain pan, Step 3, Remove drain plugs from back drain holes on horizontal drain pan, Reinstall plugs on front holes, Step 4, Rotate drain pan 180 ° front to back and install it on the opposite side of coil, Step 5, Remove screws from top cap. Remove horizontal drip shield screw located in the center of the back coil end seal as illustrated in figure 5 on page 6, Step 6. Rotate horizontal drip shield 180 ° front to back. Step 7, Remove plastic plug from left hole on coil front end seal and re-install plug in back hole, Step 8, Reinstall horizontal drip shield screw in front coil end seal, Drip shield should drain downward into horizontal drain pan inside coil, DRIP SHIELD CABINET TOP CAP ROTATED TO CORRECT POSITION \ \ \ TOP CAP SCREWS / DRAIN PAN REINSTALLED HERE POSITION NOTE - For horizontal applications in high humidity areas, remove the down-flow rail closest to the drain pan. To remove rail, remove screw from rail at back of unit and at cabinet support rail. Remove down-flow rail then replace screws. Also, seal around the exiting drain pipe, liquid and suction tines to prevent infiltration of humid air. Step 11, Knock out drain seal plate from access door. Secure plate to cabinet front flange using the provided screw, Step 12. Flip access door and replace it on the unit, Step 13, Set unit so that it is sloped 1/4 inch towards the drain pan end of the unit as illustrated in figure 6. Connect return and supply air plenums as required using sheet metal screws. Step 14, If suspending the unit, it must be supported along the entire length of the cabinet, tf using chain or strap, use a piece of angle iron or sheet metal attached to the unit (either above or below) so that the full length d the cabinet is supported, Use securing screws no longer than 1/2 inch to avoid damage to coil or filter as illustrated in figure 3 on page 5, Connect return and supply air plenums as required using sheet metal screws, THIS CORNER SHOULD BE 1/4" HIGHER THAN DRAIN CORNER DRAIN PLUGS -HERE REMOVED COIL SHOWN IN UPLOAD Rotate top cap 180 ° front to back and align with unused screw holes, Holes must align with front and back coil end plates. Note that top cap has a 45 ° bend on one side and 90 ° bend on the other. The 90 ° bend must be on the same side as the horizontal drain pan as illustrated in figure figure 5, NOTE - Use extreme care when reinstalling screws into coil end plate engaging holes. Coil damage could result by misatignment. Step 10, From the up-flow position, flip cabinet 90° to the left and set into place. Replace coil assembly. Secure coil in place by bending down tab on cabinet support rail as illustrated in figures 4 and 5, DRAIN PAN SHIPPING LOCATION t -REINSTALLED the Step 9, FROM HERE FOR EASY CONVERSION THIS CORNER SHOULD BE 1/4" HIGHER THAN DRAIN CORNER ALIGN HOLES IN COIL END PLATE, TOP CAP _ 90 o BEND Figure 5. Field Modification (left-hand WITH HOLES BACK COIL END SEAL air discharge) Figure 6. Sloping for Proper Drainage DOWN-FLOW AIR DISCHARGE APPLICATIONS Use the following procedures to configure the unit for down-flow operations: Page 6 505341M 04/08 CAUTION FOR DOWN-FLOW APPLICATIONS COMBUSTIBLE FLOOR ADDITIVE BASE The following shields, table Table lists the sizes 1. Down-flow of the available Drip PROPERLY SIZED FLOOR OPENING drip Shields Unit CB31MV-41 Part No. LB-74272 Length 17.875 Width 4.6718 CB31MV-051,065 LB-89864 19.875 4.6718 Figure 8. Install Unit on Combustible Step 1, Remove the access panels. If necessary, remove the corrugated padding from the space between the blower and coil assemblies. Remove the drip shields from the inside of the cornerpost packaging, Step 2, Remove the coil assembly from the unit. Step 3, Remove the horizontal drain pan to ensure peak operating efficiency and proper air flow in the down-flow position as illustrated in figure 7. F_ 14 J Flooring SIDE VIEW APPLY TWO PIECES OF FOAM TAPE (PROVIDED) DOWN BOTH ENDS OF EACH SHIELD. THE TAPE SHOULD MEASURE 4-3/4" X 2" (120 X 25 MM). ENSURE THAT THE TAPE COVERS BOTH SIDES OF THE SHIELD EQUALLY. HORIZONTAL PAN (REMOVE DRAIN FOR DOWN-FLOW ij_oOj APPLICATION) APPLY THE LONGER PIECE OF FOAM TAPE BETWEEN THIS PIECE OF TAPE IS 1" WIDE. J UP-FLOW/DOWN-FLOW DRAIN PAN Figure 9. Applying COIL THE PIECES ON EACH END. Foam Tape to Drip Shields _ Figure 7. Down-flow Air Discharge Position Step 4. Rotate cabinet 180 ° from the upright position. It may be necessary to remove the blower assembly to lighten the cabinet for lifting. Step 5, Apply precut foam illustrated in figure seal between the prevent water from Step 6, From the underside of the coil, install the down-flow drip shield firmly in place as illustrated in figure 10. Step 7, Replace the coil assembly and blower (if it was removed), Replace the coil access panel. Step 8, Make sure the air handler unit is level. Connect the return and supply air plenums as required using sheet metal screws, DRIP PAN FDoRIAPMSHT/ELD WITHOUT _ tape to the drip shields as 9, The foam tape creates a drip shield and the coil to entering into the air stream, COIL / DR,P PAN Figure 10. Down-flow Drip Shields NOTE - For down-flow application, metal or class I supply and return air plenums must be used. For down-flow installation on combustible flooring, additive base must be used as illustrated in figure 8. an Page 7 CB31MV SERIES Cut an opening appropriately sized for combustible base. Base dimensions are illustrated in figure 11+ 1-5/8 -Inches (41) line sets may be used by cutting off flare nut. Refer to the piping section of the Lennox Unit Information Service Manual for proper size, type and application of field-fabricated lines. (mm) 1-5/8 (41) I_.1L 11-3/8 (289)-IP' 2o (5o8) 23-1/4 AIR PENING IO 1-5/8 (41) -- 5/8 UPPLY (i 91) ................................................................. TOP VIEW I. (16) "1_ _'_ 13-3/822-1/8 (340) (562) _ AIR HANDLER V ILIIsioE LIQUID Base Dimensions NOTE: CB31MV series evaporators use nitrogen or dry air as a holding charge. If there is no pressure when the rubber plugs are removed, check the coil or line set for leaks before installing. After installation, puff a vacuum on the line set and coil before releasing the unit charge into the system. NOTE: See outdoor unit instructions nitrogen through line sets. WARNÁNG IMPORTANT All CB31MV air handlers are equipped with a factory-installed, internally mounted check/expansion valve, which is suitable for use in R410-A applications. Use Lennox L15 (sweat) series line sets as listed in table 2 on page 9, or use field-fabricated refrigerant lines. L10 (flare) on how to flow Step 1. Remove access panel. Step 2+ Remove the refrigerant refrigerant lines. Step 3. Use a wet rag to protect TXV sensing bulb (or remove it) when brazing suction line connections. Step 4+ Place a wet rag against piping plate and around the suction line connection. The wet rag must be in place to guard against damage to the paint. Step 5+ With the wet rag in place, position field provided elbow fitting to air handler's suction line and line set. Start nitrogen flow before brazing. Step 6+ After the procedure is completed then remove the wet rag. Step 7. Place wet rag against piping plate and around the liquid line connection. Position liquid line elbow to air handler's suction line and to line set. Start nitrogen flow and begin brazing both connections and after procedure is completed then remove both wet rags. Step 8+ Refer to instructions provided with outdoor unit for leak testing, evacuating and charging procedures. Step 9. Install access panel. Page 8 04/08 LINE Figure 12. Brazing Connections After opening has been cut, set the additive base into opening. Connect outlet air plenum to the additive base. Set the unit on the additive base so flanges of the unit drop into the base opening and seal against the insulation strips. The unit is now locked in place. Install return air plenum and secure with sheet metal screws. 505341M UNIT SUC 51) ViEW Figure 11. Combustible FORDOWN-FLOW APPLICATIONS line caps from the Table 2. Refrigerant Line Kits CB31MV Units Vapor/ Suction Liquid Line Line 3/8 in 3/4 in. (10 ram) (19 mm) 3/8 in 7/8 in. (10 mm) (22 mm) -41 -51 • Slope horizontal runs 1 inch per 10 feet of drain line to offset friction. Line Sets • L10-41 20 ff. - 50 ft. L15-41 20ff.-50ff. • (6m-15m) (6m-15m) Leave an open vent in the drain line, as shown in figure 13 to overcome line length, friction and static pressure. Construct drains in a manner which will facilitate future cleaning. Drains must not interfere with filter access as illustrated in figure 1 3 on page 9. L10 L15 Line Sets L10-65 L15-65 30 fl, - 50 ft. 30 ft, - 50 ft, (9m-15m) (9m-15m) 3/8 in 1-1/8 in. Field Field (10 mm) (29 mm) Fabricated Fabricated -65 • Route auxiliary drain to an area where homeowner will notice it draining. The auxiliary drain line does not required venting or a trap. Refer to local codes. A IMPORTANT Connect main condensate drain and route downward to an open drain or sump. Do not connect drain to a closed waste system. Refer to figure 13 for typical condensate trap configuration. VENT MUST EXTEND ABOVE THE HEIGHT DRAIN PAN BY 2 INCHES (51 MM). OF THE COIL" VENT Filters may be duct-mounted or installed in cabinet. A filter is factory-installed. Note that filter access door fits over access panel. Air leakage will occur if access panel is placed over filter door. Filters should be inspected monthly and must be cleaned or replaced when dirty to assure proper furnace operation. DRAIN PAN TRAP MUST BE DEEP ENOUGH TO OFFSET MAXIMUM 2 INCHES STATIC DIFFERENCE [51MM]). Units are equipped with standard throw-away type filters which should be replaced when dirty. (GENERAL To replace filter: TRAP (49P66) DRAIN LINE SHOULD 10 FEET SLOPE A MINIMUM 1 INCH PER (25 MM PER 3 M) TO APPROVED Step 1. Loosen the thumbscrews holding the filter panel in place. Step 2. Slide the filter out of the guides on either side of cabinet. Step 3. Insert new filter. Step 4. Replace panel. DRAIN Figure 13. Condensate Drain Connection It is recommended that the auxiliary drain be connected to a drain line for all units. If auxiliary drain is not connected, it must be plugged with provided cap. For down-flow units, the auxiliary drain MUST be connected and routed to a drain. See figure 14 on page 9 for main and auxiliary drain locations. LEFT-HAND DISCHARGE UP-FLOW OR DOWN-FLOW [ AUXILIARY DRAIN ON LEFT oo RIGHT-HAND DISCHARGE CB31MV-41 20 x 22 (508 x 559) CB31MV-51, -65 20 x 24 (508 x 610) Seal the unit so that warm air is not allowed into the cabinet. Warm air introduces moisture, which results in water blow-off problems. This is especially important when the unit is installed in an unconditioned area. ] MAIN DRAIN ON RIGHT Figure 14. Main and Auxiliary Drain Locations The following practices condensate removal: See table 3 for replacement filter sizes. Table 3. Filter Dimensions Unit Model No. Filter Size inches (mm) are recommended to ensure • Drain piping should not be smaller than the drain connections at drain pan. • Install a trap in the main drain line. The trap must be deep enough to offset the difference in static pressure between drain pan and atmosphere. Generally, two inches is satisfactory for medium static applications. Make sure the liquid line and suction line entry points are sealed with either the provided flexible elastomeric thermal insulation, or field provided material (e.g. Armaflex, Permagum or equivalent). Any of the previously mention materials may be used to seal around the main and auxiliary drains, and around open areas of electrical inlets. CB31MV units are equipped with a variable speed motor that is capable of maintaining a specified CFM throughout the external static range. A particular CFM can be obtained by positioning jumpers (COOL, HEAT, and ADJUST) on Page 9 CB31MV SERIES the BDC3 control board. The jumpers are labeled 1,2, 3, and 4. Each of the numbers corresponds with an air volume (CFM) setting. The ADJUST jumper is labeled Test, -, +, and Norm. The + and - pin settings are used to add or subtract a percentage of the CFM selected. The Test jumper is used to operate the motor in the test mode. The delay jumper controls the timing for the fan delay. Table 4. Blower Speed Tap Selection RECOMMENDED SPEED TAP SELECTION COOL CB31MV Air Handler * Condensing Unit HEAT Heat Pump Condensing Unit With Electric Heat Only Heat Pump With Electric Heat -041 COOL PIN #3 COOL PIN #3 HEAT PIN #4 HEAT PIN #4 -051 COOL PIN #2 COOL PIN #2 HEAT PIN #1 HEAT PIN #1 -065 COOL PIN #3 COOL PIN #3 HEAT PIN #1 HEAT PIN #1 Minimum setting for heat, Figure 15 on page 10 provides an illustration of the BDC3 control board. Use tables 5 and 6 on page 12 to determine the correct air volume for heat and cool speed taps. ACCESSORY OPTIONAL RELAY CONTACTS ACCESSORY (DRIVES RELAY) The appropriate speed according to application and CFM need is selected by moving jumper pins. IMPORTANT JP1 15 PIN PLUG f (BOARD TO MOTOR) O j _ Table 4 lists the recommended factory Blower speed tap selections for CB31MV series units. These settings are for nominal tonnage match-ups with the CB31MV. When matched with other sizes, it is recommended that the CFM be adjusted to approximately 400 CFM per ton. ADJUS HEATING SPEED SELECTOR PINS To change jumper positions, gently pull the jumper off the pins and place it on the desired set of pins. The following section outlines the different jumper selections available and conditions associated with each one as illustrated in figure 15. COOLING DELAY PINS SELECTOR SPEED PINS FAN SELECTOR OPERATIONAL SELECTOR PINS (AFFECTS BOTH HEATING AND COOLING MODES) Figure 15. BDC3 Variable Speed Control Board Selections Diagnostic LEDs located on the BDC3 control board are provided to aid in identifying the unit's mode of operation. Certain scenarios will arise depending on the jumper positions. Read through the jumper settings sections before adjusting Blower speed. Refer to figure 15 for identification. After the CFM for each application has been determined, the jumper settings must be adjusted to reflect those given in tables 5 and 6. From the tables, determine which row of CFM volumes most closely matches the desired CFM Once a specific row has been chosen (+, NORMAL, or -), CFM volumes from other rows cannot be used. Below are descriptions of the jumper selections. ADJUST JUMPERS DIAGNOSTIC LEDS Step 1. RUN LED indicates there is a demand for the Blower motor to run, Step 2. CFM LED indicates the CFM at which the unit is operating. The light flashes once for approximately every 100 CFM For example, if the unit is operating at 1000 CFM, CFM LED will flash 10 times. If the CFM is 1150, CFM LED will flash 11 full times plus one fast or half fiash, At times the light may appear to flicker or glow. This takes place when the control is communicating with the motor between cycles. This is normal operation. The ADJUST pins allow the motor to run at normal speed, approximately 10% higher, or approximately 10% lower than normal speed, Table 5 gives three rows (+, NORMAL, and -) with their respective CFM volumes. Notice that the normal adjustment setting for heat speed position #3 is 1315 CFM The + adjustment setting for that position is 1445 CFM and for the - adjustment setting is 1185 CFM After the adjustment setting has been determined, chose the remainder speed jumper settings from those offered in the table in that row, The TEST pin is available to bypass the BDC3 control and run the motor at approximately 70% to test that the motor is operational, This is beneficial primarily in troubleshooting, G must be energized for motor to run. Page 10 505341M 04/08 COOLJUMPERS TheCOOLjumperis usedtodeterminetheCFMduring either1)coolingor2)heatpumpoperation withouta callfor electricheat.Thesejumperselectionsare activatedfor coolingwhenY2 and DSterminalsin the CB31MVare energized andforheatingwhenY2 isenergized, Applications withouttheSignatureStat'" humiditycontrol willprovide either70%oftheCOOLCFMduringfirst-stage coolingfortwo-speed outdoorunits.100%ofCOOLCFM is providedforsystemswitha single-speed outdoorunit, Applicationswith the SignatureStat'"humiditycontrol createdifferentCFMvolumes,For example,duringa first-stagecoolingcall (two-speedoutdoorunit) with demandfrom the SignatureStat'"thermostat,the air volumeis40%oftheCOOLjumperselection. Fora normal COOL(Pin#2settingforCB31MV-41), theCFMis 1125; thereducedspeedis 450CFM(1125x 40%=450).This arrangementprovidesfor additionaldehumidification duringstandardfirststagecooling.Seetables7 and8 for variousscenariosconcerninguseofthe SignatureStat'" humiditycontrolandtheCB31MVseriesunit, Forapplications withHarmony II(_zonecontrol,theBlower CFMvolumeis determined by the HarmonyII control center.Theminimumair handlerspeedis predetermined at650CFMfor-41seriesunitsand850CFMfor-51and -65 series units. This speed is not adjustable,See footnotes intables5 and6, Withthethermostat setfor"Continuous Fan"andwithouta callforheatingor cooling,theCB31MV willprovided50% oftheCOOLCFMselected, NOTE - For two-speed heat pumps, air handler will operate at 70% of the COOL selection until supplemental electric heat is demanded. At that time, the air handler will operate at the HEAT speed selected, This arrangement provides for warmer supply air during second-stage heating. HEAT" JUMPERS The HEAT jumper is used to determine CFM during electric heat operation only, These jumper selections are activated only when W1 is energized, DELAY JUMPERS B C NOTE - Blower OFF DELAY also applies during heat pump operation #3 Pins Jumpered -A B A oFF___/ B Once demand C BI Once demand C is met, motor ramps down to stop. #4 Pins Jumpered -A Motor runs at 50% for 30 seconds, B C D Motor then runs at 82% for approximately 7-1/2 minutes. If demand has not been satisfied after 7-1/2 minutes, Motor runs at 100% until demand is satisfied. Once demand is met, motor runs at 50% for 30 seconds. Then, B A._/ E C/ D ramps down to stop. Wiring must conform to the current National Electric Code ANSI/NFPA No, 70, or Canadian Electric Code Part I, CSA Standard C22.1, and local building codes. Refer to following wiring diagrams, See unit nameplate for minimum circuit ampacity and maximum overcurrent protection size, Select the proper supply circuit conductors in accordance with tables 310-16 and 310-17 in the National Electric Code, ANSI/NFPA No. 70 or tables 1 through 4 in the Canadian Electric Code, Part I, CSA Standard C22,1, Xk WARNING I[,,_ [_o]_i_ii_l_o]_l_l[o]i[o]_,,_ [o]_Ik'14 This unit is provided with knockouts for conduit, Refer to figure 16 for unit schematic wiring diagram. Refer to figures 17, 19, 20 and 21 for typical field wiring. B Separate openings have been provided for 24V low voltage and line voltage, Refer to the dimension illustration of specific location, is met, motor ramps down to stop. WARNING #2 Pins Jumpered -A Motor runs at 100% until demand is satisfied, A Motor runs at 82% for approximately 7-1/2 minutes. If demand has not been satisfied after 7-1/2 minutes, motor runs at 100% until demand is satisfied, A The DELAY jumper is used to set the specific motor fan operation during cooling mode. Depending on the application, one of four options may be chosen by moving the jumper to the appropriate set of pins, #1 Pins Jumpered -A Motor runs at 100% until demand is satisfied, Once demand is met, motor runs at 100% for 45 seconds, Then, ramps down to stop. c Page 11 CB31MV SERIES Table 5. CB31MV-041 Air Handler Performance 0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range BDC3 Jumper Speed Position HEAT Speed cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s COOL Speed* 2 3 cfm L/s cfm L/s 1230 580 1335 630 1445 680 1545 730 1090 515 1225 1120 530 1215 575 1315 620 1400 660 975 460 1010 475 1200 565 1185 560 1265 595 900 425 ADJUST Jumper Setting + NORM * 1 2 3 4 First-stage (two-stage units only) cooling is approximately 1 4 cfm L/s 580 1380 650 1545 730 1125 530 1275 600 1400 660 1000 470 1135 535 1265 595 70% of the COOL speed rating, Continuous fan speed is approximately 50% of COOL speed rating. Lennox Harmony II Zone Control Applications - Minimum air handler speed is approximately 380 cfm (180 L/s). NOTE - The effect of static pressure, filter and electric heater resistance is included in the air volumes listed. Table 6. CB31MV-051, -065 Air Handler Performance 0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range BDC3 Jumper Speed Position HEAT Speed cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s COOL Speed* 2 3 cfm L/s cfm L/s + 1850 875 1960 925 2090 985 2150 1015 1625 765 1820 860 2055 970 2145 1010 NORM 1705 805 1800 850 1900 895 2005 945 1425 670 1625 765 1805 850 2005 945 1560 735 1625 765 1720 810 1770 835 1205 570 1375 650 1555 735 1725 815 ADJUST Jumper Setting * 1 2 3 4 First-stage (two-stage units only) cooling is approximately 1 4 cfm L/s 70% of the COOL speed rating, Continuous fan speed is approximately 50% of COOL speed rating. Lennox Harmony II E Zone Control Applications - Minimum air handler speed is approximately 400 cfm (190 Lls). NOTE - The effect of static pressure, filter and electric heater resistance is included in the air volumes listed. Table 7. CB31MV SignatureStat'" Operating Sequence system I Thermostat System Condition Step Y1 O NO CALL FOR DEHUMIDIFICATION Normal Operation 1 On On Demand Demand G Relative Wl On and Single Stage Outdoor Unit I Humidity Status D Acceptable 24 VAC System Air I Resp°nse HandlerCFM Compressor High (COOL) 100% Comments Compressor and indoor air handler follow thermostat demand BASIC MODE (only active on a Y! thermostat demand) Normal Operation 1 On Acceptable Call 2 On PRECISION Normal Operation Dehumidification 1 On High 100% call 2 On Demand VAC High 60%/65%* MODE (operates independent of a Y! thermostat demand) 24 Acceptable VAC High 100% O Demand VAC High 60%/65%* High 60%/65%* o Dehumidification call ONLY 24 VAC o Dehumidification 1 On Demand VAC SignatureStat ' energizes Y1 and de-energizes D on a call for dehumidification Dehumidification mode begins when humidity is greater than set point SignatureSr[at " will try to maintain room humidity setpoint by allowing the room space to maintain a cooler room thermostat setpoint** Jumpers at indoor unit with a single stage outdoor unit With Condensing unit - Y1 to Y2 and R to O With Heat Pump - Y1 to Y2 Lennox SignatureStat _' used for these applications are 51 M26 - 1 heat / 1 cool or 51 M28 - 2 heat / 2 cool heat pump * During dehumidification, cooling air handler speed is as follows: 65% of COOL cfm for -41units, 60% COOL cfm for -51 and -61 units ** In Precision mode, SignatureStat _ thermostat built BEFORE October 2003 will maintain room temperature up to 3°F (1.8°C) cooler than room thermostat setting. Precision thermostat built AFTER October 2003 will maintain room temperature up to 2°F (1.2°C) cooler than the room thermostat setting. Page 12 505341M 04/08 Table 8. CB31MV, SignatureStat" Thermostat Demand System Condition Step Y1 Y2 O G On On W1 and Two-Stage Outdoor Unit Air Handler CFM Relative Humidity W2 Status D Compressor On Acceptable 24 VAC Low On Acceptable 24 VAC High (COOL) Comments NO CALL FOR DEHUMIDIFICATION Normal Operation - Y1 1 On Normal Operation - Y2 2 On ROOM THERMOSTAT CALLS On FOR FIRST STAGE 70% 100% Compressor and indoor air handler follow thermostat demand COOLING BASIC MODE (only active on a Y! thermostat demand) Normal Operation 1 On Dehumidificatio n Call 2 On On On On Acceptable 24 VAC Low On On Demand 24 VAC High 70% 60%/65%* SignatureStat energizes Y2 and de-energizes D on a call for dehumidification PRECISION MODE "operates independent of a Y1 thermostat demand) Normal Operation Dehumidificatio n call Dehumidificatio n call ONLY 1 On 2 On 1 On On On On On On On Acceptable On Demand On Demand 24 VAC 0 VAC 0 VAC Low 70% High 60%/65%* High 60%/65%* Dehumidification mode begins when humidity is greater than set point **SignatureStat _' will try to maintain room humidity setpoint by allowing the room space to maintain a cooler room thermostat setpoint ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING BASIC MODE (only active on a Y1 thermostat demand) Normal Operation 1 On On On On Acceptable 24 VAC High Dehumidificatio n Call 2 On On On On Demand 0 VAC High 100% 60%/65%* SignatureStat energizes Y2 and de-energizes D on a call for dehumidification PRECISION MODE 'operates independent of a Y! thermostat demand) Normal Operation 1 On On On On Acceptable 24 VAC High 100% Dehumidificatio n call 2 On On On On Demand 0 VAC High 60%/65%* Dehumidificatio n call ONLY 1 On On On On Demand 0 VAC High 60%/65%* Jumpers at indoor unit with a two stage outdoor unit With Condensing unit - R to O With Heat Pump - none Lennox SignatureStat" Dehumidification mode begins when humidity is greater than set point **SignatureStat" will try to maintain room humidity setpoint by allowing the room space to maintain a cooler room thermostat setpoint used for these applications are 51 M27 - 2 heat / 2 cool or 51 M28 - 2 heat / 2 cool heat pump. * During dehumidification, ** In Precision mode, SignatureStat _' thermostat built BEFORE October 2003 will maintain the room temperature up to 3°F (1.8°C) cooler than room thermostat setting. Precision thermostat built AFTER October 2003 will maintain the room temperature up to 2°F (1.2°C) cooler than the room thermostat setting. cooling air handler speed is as follows: 65% of COOL cfm for -41 units, 60% COOL cfm for -51 and -61 units Page13 CB31MV SERIES I -- -- LINE VOLTAGE FIELD WIRING CLASS ]I VOLTAGE FIELD WIRING A LLI REFER CHART TO FACTORY BELOW FOR BLOWER GLOWER FIELD WIRING WITHOUT SPEED TAP SELECTION SPEED INFORMATION FOR CIRCUIT UNITS FIELD WIRING FOR UNITS WITH CIRCUIT BREAKERS CIRCUIT A Z_ USE COPPER CONDUCTORS ONLY. REFER TO UNIT NAMEPLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE A NOTE-FOR NON-HEAT PUMP APPLICATION ONLY-WHEN TWO STAGE THERMOSTAT IS USED, CONNECT SECOND STAGE HEAT BULB TO TERMINAL "W2" AND REMOVE JUMPER BETWEEN TERMINALS "R" & "WB" /X A_ JUMPER "R" TO "0" IS USED WITH UNIT. REMOVE "R" TO "O" JUMPER PUMP IS USED. A REMOVE JUMPER BETWEEN "DO" AND "YI" WHEN HUMIDITY CONTROL (SIGNATURESTA_ IS USED, A Lg& JUMPER "YI" TO "YB" IS FOR SINGLE STAGE COOLING, REMOVE JUMPER "YI _ TO _Y2" FOR TWO STAGE COOLING. A LL& CO8 USED ON ONLY z_ EOUIPMENT IN GROUND LOCATED INDOORUNIT A LB (P) 51 AND 65 A CIRCUITLI _ A A _ EOUIPMENT GROUND CR3 A A L3 _ 3 CIRCUIT CB2 A_A A L3 "_ Z A_ CBI L3"II"" A -- EOOIPMENT EOOIRMENT GRGUNO GROUND CONDENSING WHEN HEAT BREAKERS CIRCUIT C _ GROUND EQUIPMENT J2 R 2AV POWER -Z \ / UNITS DESCRIPTION KEY COMPONENT AI5 iCONTROL=BLOWER DRIVE B3 AOTOR_BLOWER CB8 iCIRCUIT BREAKER-TRANS Fi iFUSE-TRANSFORMER J2 iJACK-ELECT. NEAT J4G iJACH-OUTPUT J48 iJACK=MOTOR.VAR SPD J49 iJACK-MGTOR.VAR SPR K20.-IUiRELAY-BLOWER PAR iPLUG-OUTPUT ISELECTRIC NOT PRESENT ON HEATERS A THE NUM6ER OF CIRCUITS VARY ACCORDING TO HEATER MODEL, REFER TO FAN COIL NAMEPLATE FOR ACTUAL NUMBER EMPLOYED A CONNECT POWER WIRES HEATER LABELED LI,L2 FROM ON "P* VOLTAGE UNITS ANO LI,LG,L5 ON "Y" VOLTAGE UNITS TO TB2 TERMINAL STRIP IN INDOOR UNIT, _ -8 PAR PA9 T_ TRI DS Ti W_ WG Y2 iP_UG-MDTQR,VAR 5P# iPIUG-MGTGR.VAR RPR iTRANSFDRWPR-CGNTRDJ iTFRM STRIPED ASS II CIRCUIT K20 L_ Yl I z_ \ o _ BLACK L_> _ ORANGE RECOMMENENED BLOWER SPEED SPEED TAP SELECTION TAP SELECTION "COOL" CBBIMV BLOWER COIL / "HEAT" *CONDENSING UNIT WITH ELECTRIC HEAT ONLY HEAT PUMP -41 COOL PIN _3 COOL PIN #3 HEAT PIN _A HEAT PIN _A -Sl COOL PIN _2 COOL PIN _G HEAT PIN #1 HEAT PIN _I _65 COOL PIN 13 COOL PIN #3 HEAT PIN #I HEAT PIN #I Figure BLACK ORANGE CONDEN5ING UNIT *MINIMUM HEAT PUMP WITH ELECTRIC HEAT SETTING 16. R PoD I L4"5.4_00000o FOR 04/08 o o _oo° O000 HEAT CB31MV Blower Coil Unit Typical Wiring Page 14 505341M G4V COMMON EV / Diagram R ° R o ooo R _°p 0 o j L2 LI 208-250/60/I K20 INDOOR BLOWER RELAY _LI BLACK '_'_LZ ORANGE REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE CIRCUIT FIELDSUPPLIED WIRE NUTS o o o LU TRANSFORMER o -J 0co 0 0 _ FUSE o o u_oz ---JO 0 ? 0 0 0 Al--7-_r-_ GROUND DS+ 0(_)Y _ I L ,- -, r I I I H I i--- I.... I !rJ EL_. J ]] YZ(_ ,' l (i I I iA ILL x--I----I-_ .- s, A THERMOSTAT J FF: rk! ______ "q-I-" [ r' l r_m ITERMINAL A s-l_ Fi1@_ °LI_TI_ iBLOCK /ZX ' ........ LINE VOLTAGE - FIELD-INSTALLED CLASS 2 VOLTAGE - FIELD-INSTALLED NEC/CEC NOTE -ALL REMAINING WIRES FACTORY-INSTALLED TO EXTERNAL LOAD 24VAC AT .5 AMP MAXIMUM Z_ NEC/CEC CLASS 2, 3 VA Z_ FACTORY INSTALLED JUMPERS. - "R" to "0" USED ONLY IN CONDENSING UNIT APPLICATIONS. REMOVE IN HEAT PUMP APPLICATIONS. REMOVE 'DS" TO "YI" JUMPER WHEN HUMIDITY CONTROL THERMOSTAT (SIGNATURESTAT _'>IS USED. REMOVE "Y1" TO "Y2" JUMPER IN TWO-STAGE COOLING APPLICATIONS. Z_ FACTORY INSTALLED JUMPER NOTE - USE COPPER CONDUCTORS ONLY Figure 17. Cooling Application Page 15 CB31MV SERIES L2 LI 20B-2,f>O/60/I HEAT ELEMENT _1 c_ K20 INDOOR BLOWER RELAY K32 HEAT RELAY *I ---_---L,BLAOK /_ CIRCUIT REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE _---L_0RAN0_ I FIELDSUPPLIED WIRE NUTS o o LU _,. o 0 o (z:o 0 0 _ TRANSFORMER o 0 LnOZ --JO 0 o o o o__A GROUND i]_ L.... F----F- s,AA THERMOSTAT I I I I I ,- ...., # ( i ; (L( ' l_ I ! I__.U.T] 11 IL---I,--4 II 1--t Ir ' l I I.... F--- !r# ....r' B ;j-_2-_-+-, "7--r"" sq i FzE ........ r_r_ ITERMINAL _ LINE VOLTAGE - FIELD-INSTALLED CLASS 2 VOLTAGE - FIELD-INSTALLED NOTE -ALL REMAINING NEC/CEC WIRES FACTORY-INSTALLED /'_ TO EXTERNAL LOAD 24VAC AT .5 AMP MAXIMUM /'_ NEC/CEC CLASS 2, 3 VA Z_ FACTORY INSTALLED JUMPERS. - 'R" to "0" USED ONLY IN CONDENSING UNIT APPLICATIONS. REMOVE IN HEAT PUMP APPLICATIONS. REMOVE "DS" TO "YI" JUMPER WHEN HUMIDITY CONTROL THERMOSTAT (SIGNATURESTAT°'° IS USED. REMOVE "YI" TO "Y2" JUMPER IN TWO-STAGE COOLING APPLICATIONS. ,_ FACTORY INSTALLED JUMPER //_ NOTE - USE COPPER CONDUCTORS WHEN TWO-STAGE JUMPER BETWEEN ONLY THERMOSTAT IS USED, CONNECT TERMINALS "R" AND "W2" THERMOSTAT HEAT ANTICIPATION Figure SECOND-STAGE SETTING .4 AMP (ELECTRIC 18. Cooling Application Page 16 505341M 04/08 HEAT BULB TO TERMINAL 'W2," REMOVE HEAT) with Electric Heat L2 LI 208-230/60/I HEAT ELEMENT _I K20 INDOOR BLOWER RELAY FIELD-SUPPLIED WIRE NUTS + ?? K32 HEAT RELAY O_) (Orange) CIRCUIT > 0 0 0 0 _: o W o d cl::o wn-I.gl 0 Z --_Jo _: rn t_) wl REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE TRANSFORMER 0 0 0 FUSE 0 0 0 0 0 0 GROUND ,II _e-:--n ° 7i ii ,- -, I I I L I I I IL i .I1 I I---I--L-I-. --]----_ F7 I i I ! .I LINE VOLTA6E FIELD INSTALLED CLASS 2 VOLTA6E FIELD INSTALLED NEC/CEC NOTE-ALL REMAINING WIRES FACTORY INSTALLED I r i , LI_ L II i _in 11 H--_II I I s,AA THERMOSTAT I I I I I [-" It ___l__. I. _ .¢---4-" ..... I I FI--,,I1 A @@E_@N%D TERMZNAL BLOCK Z_TO EXTERNAL LOAD 24VAC AT .50AMP MAXIMUM A FACTORY INSTALLED JUMPER z_NEC/CEC A NOTE-USE COPPERCONDUCTORSONLY A WHEN TWOSECONDSTAGE STAGE THERMOSTAT IS USED, CONI_CT I_AT BULB TO TERMINAL"W2," REMOVEJUMPER BETWEEN TERMINALS"R" AND "W2" A THERMOSTAT HEAT(ELECTRIC ANTICIPATION SETTIN6.4 AMP HEAT) A CLASS 2 3VA FACTORY INSTALLED JUMPERS " - "R" to "0" used , only. in con..... densmg unit apphcatlons, Remove in heat pump apphcatlons. Remove "DS" to "YI" jumper when humidity control (SignatureStatt) is used. Remove "YI" to "Y2" jumper in two-stage cooling applications. Figure 19. Cooling Application with Electric Heat Page 17 CB31MV SERIES Remove "R" to "0" factory-installed in heat pump applications. jumper \ SI THERMOSTAT A "' r i I / IS ir ll -- -l. " fl'l I fii] I I i I ' I I l i t _[!___[ II,I III i I'---I ) )/....... "f,/ ,>9® 1 7_-!F-m- T T "q "-----I" '-it- I I I I I I I- _ r I' II I1 'I !! I t '-I----I-- 1 I I _.7----- I I -- J----I.------, L 1------ --i I 7 t i t--T--__--_ -- I I! _--H---[ I . I ! i "-_-' _ / I I CCB I - 1 TERMINAL BLOCK A CLASS 2 VOLTAGE FIELD INSTALLED NEC/CEC NOTE-ALL REMAINING WIRES FACTORY INSTALLED L_ NEC/CEC CLASS 2 3VA A FACTORY INSTALLED JUMPERS - 'R" to '0" used only in condensing unit applications. Remove in heat pump applications. Remove 'DS" to 'YI" jumper when CCB1 humidity control (A20) is used, L_ Remove 'YI" to 'Y2" jumper in two-stage cooling applications. FACTORY INSTALLED JUMPER HEAT PUMP CLASS 2 VOLTAGE TERMINALS Figure 20. Heat Pump Page 18 505341M 04/08 /_K EM HT RELAY ___ _-- -iK22 _I Remove 'R"to'0" factoryinstalled jumper inheat pump applications. I /_ r,_ f I ('%) i T$23 HERMOST.AT OUTOOORz_ [I F USED) -- _ _ o I'" I r",,'i iI I II I ,I I I , _ ii I ,'!'-I:_ ......... .... ,._: __.._1-- 11 1111,___ _L_-_.:-I__. I II ............ i-I L_ -H- __T_. ............ III II I LL .... L__D ............ , Ii L+--_,,Z--t---d ,, I t ] ,Z - ---k- / J- 4 --,_ ---['_-_ ........ ' I .__--__'t_--_--_- I I i --I ----i- ............. I--I --I ----jd_---T ----_l- ....... I T-T-T---F,_---._J--------_------------ L-__-__T L- --i-_ ..-[ I I I I I I I L-F---I------- I I _ .... I ,---J L _ I I I "--J-q-_ I | DDD_ _ _l-I]['R]r_ t--t--_ ', THERMOSTAT SETTING ', TERMINAL I,_ BLOCK ,I I I ccB- HEAT.ANTICIPATION .€ AMP (ELECTRIC _ _o E _ a: C_ _ I I I I I I - E o _. I I ' ; _ <_ rE !I_° _: _ J _- ] oo li . n" (j HEAT} FACTORY INSTALLED JUMPER (._) 3 ; _ _ ,,,_ _ - i _ "-' _ LU >" _ __ _ L _ L_EMERGENCY HEAT RELAY (USED ONLY IF OUTDOOR THERMOSTAT IS USED) FIELD PROVIDED AND INSTALLED NEAR INDOOR UNIT 2#VAC 5VA MAX NEC CLASS 2 !_NEC/CEC I I I - "T-" o_ _ DIB E'] z_WHEN OUTDOOR IS USED, CONNECT LEADS THERMOSTAT TO TERMINALS "R" AND "W"Z? AND RBAOVE JUMPER BETWEEN "R" AND "W2" Z_ ,, i i i i _ i'' I I I ._7 ..... I __._ , _ ._!,--,-I--, ,J , ,I -.1- ,_ CLASS 2 VOLTAGE FIELD INSTALLED NEC/CEC NOTE-ALL REMAINING WIRES FACTORY INSTALLED Z_ /x I I I Z_ THERMOSTAT r,nL/'n 1.r.__-,-:--,, IIII .... -IT.__ __--'_..__ II , ,",',,lli, I I I i I S I r_ ; (_ w _. W HEAT PUMP CLASS VOLTA6E TERMINALS 2 CLASS 2 3VA FACTORY INSTALLED JUMPERS, - "R" TO "0" USED ONLY IN CONDENSING UNIT APPLICATIONS. REMOVE IN HEAT PUMP APPLICATIONS. REMOVE "DS" TO "YI" JUMPER WHEN CCB1 HUMIDITY CONTROL (A20) IS USED. REMOVE "YI" TO "Y2" JUMPER IN TWO-STAGE COOLING APPLICATIONS. Figure 21. Heat Pump with Electric Heat Page19 CB31MV SERIES IMPORTANT Matt- or foil-faced insulation is installed in indoor equipment to provide a barrier between outside air conditions (surrounding ambient temperature and humidity) and the varying conditions inside the unit. If the insulation barrier is damaged (wet, ripped, torn or separated from the cabinet walls), the surrounding ambient air will affect the inside surface temperature of the cabinet. The temperature/humidity difference between the inside and outside of the cabinet can cause condensation on the inside or outside of the cabinet which leads to sheet metal corrosion and subsequently, component failure. REPAIRING DAMAGED INSULATION Areas of condensation on the cabinet surface are an indication that the insulation is in need of repair. If the insulation in need of repair is otherwise in good condition, the insulation should be cut in an X pattern, peeled open, glued with an appropriate all-purpose glue and placed back against the cabinet surface, being careful to not overly compress the insulation so the insulation can retain its original thickness. If such repair is not possible, replace the insulation. If using foil-faced insulation, any cut, tear, or separations in the insulation surface must be taped with a similar foil-faced tape. Page 20 505341M 04/08 Figure 22. Repairing Insulation WARNÁNG
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 20 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Mon Jun 30 04:18:27 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools