LENNOX Air Conditioner/heat Pump(outside Unit) Manual L0805442

User Manual: LENNOX LENNOX Air conditioner/heat pump(outside unit) Manual LENNOX Air conditioner/heat pump(outside unit) Owner's Manual, LENNOX Air conditioner/heat pump(outside unit) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 12

,?u2006 Lennox industries Inc,
Dallas, Texas, USA
X_ WARNING
INSTALLATION
INSTRUCTIONS
10ACE Series Units
CONDENSER UNITS _ Technical
505,128M LL.L[ Publications
03/06 Litho U.S.A.
Supersedes 01/06
X_ IMPORTANT
10ACE Outdoor Units .......................... 1
Shipping & Packing List ........................ 1
General Information ........................... 2
Unit Dimensions ............................... 2
Setting the Unit ............................... 2
Electrical ..................................... 3
Refrigerant Piping ............................. 4
Refrigerant Metering Devices ................... 4
Manifold Gauge Set ........................... 5
Service Valves ................................ 5
Leak Testing .................................. 6
Evacuation ................................... 6
Start-Up ...................................... 7
Refrigerant Charging ........................... 8
System Operation ............................. 10
Maintenance .................................. 10
Optional Accessories .......................... 11
Start-Up & Performance Check List .............. 11
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
AI_CAUTION
_I_WARNING
03/06
IIIIIIIIIIIIIIIIIIIIIIHIllllllllllll
Lennox Merit® 10ACE outdoor units are designed for use
in either fixed orifice or expansion valve (TXV) systems,
The TXV may require a field-installed hard start kit. Refer
to the Lennox Engineering Handbook for expansion valve
kits which must be ordered separately.
1 - Assembled outdoor unit
1 - Fixed orifice refrigerant metering device
Check the unit for shipping damage. Consult last carrier
immediately if damage is found.
Page 1 505,128M
IIIIIIIIIIIIlllllll]lllllllllllllllllllllllllllll
©
AIR
.---11_4 -3/8 I._l-- ---I,44-3/8 _1--.
AIR f I(111) F - li!11)1 f
-_ _. 4-3/8I,_I" ' _-%1 4-3/8
_'_ (111)1,/,.k, .,-k_
il
'/fT_'_%JJf/_.\ [I OPTIONALUNIT YI[U I xU]l ,
!/ i _\1 Yt_J_\ LI -- STAND-OFFKIT(4)/ILH C°MPRESSOR HII
I (Fieldlnstalled)" 14fl \'- --' UI
\\J__/II A_R COILDRAINOUTLETSfII! IF --- _11 .
_llllll\\\\\\XX_"'_/..-_ (Around perimeter of base) T II f2, Illl ,I,
------ VAPOR LINE "_11/_ I_._X_ c:z:::_ (_
AIR LIQUID LINE --I_ 6-3/8 _ _1,,_4-3/8__1
CONNECTION Vl (162) I_ vI(111)I
TOP VIEW BASE SECTION
111-- C,.._I OUTDOOR
_I COIL FAN
OPTIONAL
UNIT
STAND-OFF
KIT (4)
(Field
Installed) \
\
I
11
I
g
L.J. _ 2 (51)
3/4%,
ELECTRICAL
INLETS
10ACE Model A B C
-024 25 (635) 24-1/4 (616) 24-1/4 (565)
-036 33 (635) 32-1/4 (616) 24-1/4 (565)
-048 33 (838) 32-1/4 (819) 24-1/4 (616)
-060 33 (940) 32-1/4 (921) 24-1/4 (718)
These instructions are intended as a general guide and do
not supersede national or local codes in any way. Consult
authorities who have jurisdiction before installation,
When servicing or repairing HVAC components, ensure
the fasteners are appropriately tightened. Table 1 shows
torque values for fasteners.
COMPRESSOR
VAPOR &
LIQUID LINE
CONNECTION
2-3/4 (70)
-- C i .._1
DISCHARGE AIR _1
• I\
I I
'LLJ
SIDE VIEW
Table 1
Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.- lb. 11NM
Sheet metal screws 16 in.- lb. 2 NM
Machine screws #10 28 in.- lb. 3 NM
Compressor bolts 90 in.- lb. 10 NM
Gauge port seal cap 8 ft.- lb. 11NM
Refer to unit dimensions for sizing mounting slab, plat-
forms or supports. Refer to figure 1 for installation clear-
ances.
505128M 03/06
Page 2
Slab Mounting
When installing unit at grade level, install on a level slab
high enough above grade to allow adequate drainage of
water. Top of slab should be located so run-off water from
higher ground will not collect around unit,
Installation Clearances
(as noted) (as noted)
*A service clearance of 30" (762 mm) must be maintained on one of
the sides adjacent to the control box. Clearance to one of the other
three sides must be 36" (914 mm). Clearance to one of the remaining
two sides may be 12" (304 mm) and the final side may be 6" (152
ram),
A clearance of 24" (610 mm) must be maintained between two units.
48" (1219 mm) clearance required on top of unit. Maximum soffit over-
hang is 36" (914 mm).
Figure 1
.Roof Mounting
Install the unit at a minimum of 4 inches (102 mm) above
the surface of the roof, Ensure the weight of the unit is
properly distributed over roof joists and rafters, Redwood
or steel supports are recommended,
In Canada, wiring must conform with current local codes and
the current Canadian Electrical Code (CEC),
_WARNING
Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
1, Install line voltage power supply to unit from a properly
sized disconnect switch.
2. Install line voltage power supply to unit from a properly
sized disconnect switch. Any excess high voltage field
wiring should be trimmed or secured away from the
low voltage field wiring (see figures 2 and 3),
Separating High/Low Voltage Field Wiring
// /
High Voltage
WIRE Field Wiring
TIES -- Low Voltage
Field Wiring
---- Factory
Wiring
Figure 2
Typical Field Wiring Diagram
OUTDOOR _ START *
_FAN CAPACITOR CE2
DUAL
CAPACITOR
I BLACK
ORANGE __
RED K31 *A&
POTENT[AL RELAY *TIMED OFF CONTROL
BLACK COMPRESSOR F-
CONTACTOR (_
G (SEE
-048 & NOTE)
208-230/60/1
-060
models I I _IL2
LE
I
GROUND
WARNING! - ELECTRIC SHOCK HAZARD Can cause INJURY
or DEATH, Unit must be grounded in accordance with national and
local codes.
NOTE - For use with copper conductors only. Refer to unit rating
plate for minimum circuit ampacity and maximum over-current
protection size.
Figure 3
3. Ground unit at unit disconnect switch or to an earth
ground.
NOTE -To facilitate conduit, a hole is located in the
bottom of the control box. Connect conduit to the con-
trol box using a proper conduit fitting. Units are ap-
proved for use only with copper conductors.
24V, Class II circuit connections are made to the low
voltage pigtafs. Refer to figure 3for field wiring dia-
gram. A complete unit wiring diagram is located inside
the unit control box cover.
4. Install room thermostat (ordered separately) on an in-
side wall approximately in the center of the conditioned
area and 5 feet (1.5 m) from the floor. It should not be
installed on an outside wall or where it can be effected
by sunlight, drafts or vibrations.
Page 3
10ACE SERIES
NOTE -For proper voltages, select thermostat wire
gauge per the following chart:
Wire run length AWG # Insulation type
less than 100' (30m) 18 color-coded, temperature
more than 100' (30m) 16 rating 35°C minimum
5. Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit, See figure 4.
Typical Field Low Voltage Wiring Diagram
Thermostat Indoor Unit
p.....
Outdoor Unit
@ heat
Q ooo,,nq
Qindoor blower @
NOTE -see unit wiring diagram for power supply connec-
tions. If indoor unit is not equipped with blower rela_zItmust
be field-provided and installed (P-8-3251 or equivalent).
Figure 4
Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections) to the indoor coil
(flare or sweat connections). Use Lennox L15 (sweat, non-
flare) series line sets as shown in table 2 or use field-fabri-
cated refrigerant lines, Refer to Refrigerant Piping Guide
(Corp. 9351-L9) for proper size, type, and application of
field-fabricated lines. Valve sizes are also listed in table 2.
Table 2
Refrigerant Line Kits
Valve Field Size
Connections Recommended Line Set
Liquid Vapor Liquid Vapor L15
Model Line Line Line Line Line Sets
-024 3/8 in 3/4 in. 3/8 in 3/4 in. L15-41
-036 (10mm) (19mm) (10mm) (19mm) 15 ft,- 50 ft.
(4.6 m - 15m)
-048 3/8 in 7/8 in. 3/8 in 7/8 in. L15-65
(10 mm) (22 mm) (10 mm) (22 mm) 15 ft,- 50 ft.
(4.6 m - 15m)
-060 3/8 in 1-1/8 in. 3/8 in 1-1/8 in. Field
(10 mm) (29 mm) (10 mm) (29 mm) Fabricated
NOTE - Units are designed for line sets of up to 50 feet (15 m), For
applications longer than 50 feet, consult the Lennox Refrigerant Piping
Guide (Corp. 9351-L9), Select line set diameters from table 2 to en-
sure that oil returns to the compressor.
Sweat Connection Procedure
1, Cut ends of the refrigerant lines square (free from
nicks or dents), Debur the ends. The pipe must remain
round, do not pinch end of the line,
2. Wrap a wet cloth around the valve body and copper
tube stub to protect it from heat damage during braz-
ing, Wrap another wet cloth underneath the valve body
to protect the base paint,
3, Quench the joints with a wet cloth to prevent possible
heat damage to the valve core and opening port.
4. Install a field-provided filter dryer as close as possible
to the expansion device,
Use 10ACE units in either TXV systems or fixed orifice sys-
tems, See the Lennox Engineering Handbook for ap-
proved TXV and fixed orifice match-ups and application in-
formation. Table 2 lists the unit liquid and vapor line sizes
and corresponding line sets,
Fixed Orifice Systems
10ACE units are shipped with a fixed orifice refrigerant me-
tering device. Replace the existing indoor unit fixed orifice
with the orifice supplied with the outdoor unit. Place the
supplied fixed orifice sticker on the indoor cabinet after
installation. See table 3 for the fixed orifice size for each
unit, In nonstandard applications, the provided fixed orifice
may not be appropriately sized. Refer to the Engineering
Handbook for specific orifice information.
Table 3
Fixed Orifice Drill Sizes
Fixed Orifice Fixed Orifice
Unit Catalog # Drill Size
10ACE-024 100484-12 .062
10ACE-036 100484-22 .073
10ACE-048 100484-33 .086
10ACE-060 100484-44 .098
Install the fixed orifice as shown in figure 5, Do not twist the
cap tubes when loosening the seal nut from the orifice
housing,
II Metering Device Installation
_oO-RING j FIXED ORIFICE
| or
_'-_ f-_-_ EXPANSION VALVE &
// _ _ O-RING (See NOTE)
DISTRIBUTOR _i_(_ LIQUID LINESTUB
STRAINER
NOTE -If installing expansion valve with an indoor coil
that includes a fixed orifice, remove orifice before
installing valve,
Figure 5
Expansion Valve Systems
Expansion valves equipped with Chatleff fittings are avail-
able from Lennox, Refer to the Engineering Handbook for
expansion valves for use with specific match-ups.
505128M 03/06
Page 4
If you install a expansion valve with an indoor coil that
includes a fixed orifice, remove the orifice before the
expansion valve is installed.
AIMPORTANT
When checking the unit charge, use a manifold gauge set
that is equipped with "low loss" hoses. Do not use a man-
ifold gauge set with anything other than a "low loss" hose.
The service valves (liquid line - figure 6, vapor line - figures
7 and 8) and gauge ports are used for leak testing, eva-
cuating, charging and checking charge, Each valve is
equipped with a service port which has a factory-installed
Schrader valve. A service port cap protects the Schrader
valve from contamination and serves as the primary leak
seal.
To Access Schrader Port:
1. Remove service port cap with an adjustable wrench.
2. Connect gauge to the service port,
3, When testing is complete, replace service port cap.
Tighten finger tight, then torque per table 1 (Page 2).
To Open Front-Seated Service Valves:
1, Remove stem cap with an adjustable wrench,
2. Use a service wrench with a hex-head extension
(3/16" for liquid-line valve sizes; 5/16" for vapor-line
valve sizes) to back the stem out counterclockwise as
far as it will go,
3, Replace the stem cap. Tighten finger tight, then torque
per table 1 (Page 2).
To Close Front-Seated Service Valves:
1. Remove the stem cap with an adjustable wrench,
2. Use a service wrench with a hex-head extension
(3/16" for liquid-line valve sizes; 5/16" for vapor-line
valve sizes) to turn the stem clockwise to seat the
valve. Tighten it firmly,
3. Replace the stem cap, Tighten finger tight, then torque
per table 1 (Page 2),
Vapor Line Ball Valve
Ball-type service valve (10ACE-060 only, figure 8) func-
tions the same way as the other valves but cannot be re-
built; if one fails, replace with a new valve, The ball valve is
equipped with a service port with a factory-installed
Schrader valve. A service port cap protects the Schrader
valve from contamination and assures a leak-free seal.
Front-Seated Liquid Line Service Valve
STEM INSERT HEX
SCHRADER CAP
VALVE]OPENTO WRENCHHERE
L,NESETWHEN
VALVE IS CLOSED
(FRONT SEATED)] _
OUT-
DOOR
COl
OR
SERVICE
PORT CAP (VALVE FRONT-SEATED)
Valve in closed position Valve in open position
Figure 6
Front-Seated Vapor Line Service Valve
STEM CAP
SCHRADER VALVE
[OPEN TO LINE SET
INSERT WHEN VALVE IS
HEX CLOSED (FRONT
WRENCH SEATED)]
HERE
SERVICE
PORT CAP
TO
OUTDOOR r
COIL , SERVICE PORT
INDOOR
COIL
(VALVE
FRONT-SEATED)
Valve in closed position Valve in open position
Figure 7
Bali-Type Vapor Valve (Valve Closed)
sl M TO
OUTDOOR
COIL
USE ADJUSTABLE WRENCH STEM
TO OPEN: ROTATE STEM
COUNTER-CLOCKWISE 90 °.
TO CLOSE: ROTATE STEM
CLOCKWISE 90 ° .
CLOSED)
SERVICE PORT
TO (_SCHRADER VALVE
INDOOF
COIL SERVICE
PORT CAP
Figure 8
Page 5
10ACE SERIES
After the line set has been connected to the indoor and out-
door units, check the line set connections and indoor unit
for leaks,
,WARNING I
4. Connect a cylinder of nitrogen with a pressure regulat-
ing valve to the center port of the manifold gauge set,
5. Connect the manifold gauge set high pressure hose to
the vapor valve service port. (Normally, the high pres-
sure hose is connected to the liquid line port; however,
connecting it to the vapor port better protects the man-
ifold gauge set from high pressure damage,)
6. Adjust the nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge
set which will pressurize line set and indoor unit.
7. After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge nitrogen and
HCFC-22 mixture. Correct any leaks and recheck.
WARNING
AWARNING
I
I
Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper pip-
ing and compressor parts.
AIMPORTANT
WARNING I
Using an Electronic Leak Detector or Halide
1, Connect a cylinder of HCFC-22 to the center port of
the manifold gauge set.
2, With both manifold valves closed, open the valve on
the HCFC-22 cylinder (vapor only).
3, Open the high pressure side of the manifold to allow
the HCFC-22 into the line set and indoor unit. Weigh
in a trace amount of HCFC-22, [A trace amount is a
maximum of 2ounces (57 g) or 3 pounds (31 kPa)
pressure,] Close the valve on the HCFC-22 cylinder
and the valve on the high pressure side of the manifold
gauge set, Disconnect the HCFC-22 cylinder,
1. Connect manifold gauge set to the service valve ports
as follows:
low pressure gauge to vapor line service valve
high pressure gauge to liquid line service valve
2. Connect micron gauge,
3. Connect the vacuum pump (with vacuum gauge) to
the center port of the manifold gauge set,
4. Open both manifold valves and start the vacuum
pump.
5. Evacuate the line set and indoor unit to an absolute
pressure of 23,000 microns (29.01 inches of mercu-
ry). During the early stages of evacuation, it is desir-
able to close the manifold gauge valve at least once to
determine if there is a rapid rise in absolute pressure.
A rapid rise in pressure indicates a relatively large
leak, If this occurs, repeat the leak testing procedure.
NOTE -The term absolute pressure is defined as the
total actual pressure within a given volume or system,
above the absolute zero of pressure, Absolute pres-
sure in a vacuum is equal to atmospheric pressure mi-
nus vacuum pressure,
6. When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cyl-
inder with pressure regulator set to 150 psig (1034
kPa) and purge the hose. Open the manifold gauge
valves to break the vacuum in the line set and indoor
unit, Close the manifold gauge valves.
505128M 03/06
Page 6
,A CAUTION
AIMPORTANT
7. Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20-minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
9. When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vac-
uum pump and connect it to an upright cylinder of
HCFC-22 refrigerant. Open the manifold gauge valves
to break the vacuum from 1 to 2 psig positive pressure
in the line set and indoor unit. Close manifold gauge
valves and shut off the HCFC-22 cylinder and remove
the manifold gauge set.
1. Rotate the fan to check for frozen bearings or binding.
2. Inspect all factory- and field-installed wiring for loose
connections.
3. After evacuation is complete, open the liquid line and
vapor line service valves to release refrigerant charge
(contained in outdoor unit) into the system.
4. Replace the stem caps and secure finger tight, then
tighten an additional one-sixth (1/6) of a turn.
5. Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit's
nameplate. If not, do not start the equipment until you
have consulted the power company and the voltage
condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on pow-
er to the indoor blower and close the outdoor unit dis-
connect switch to start the unit.
7. Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
Page 7
10ACE SERIES
Units are factory charged with the amount of HCFC-22 re-
frigerant indicated on the unit nameplate. This charge is
based on a matching indoor coil and outdoor coil with a 15
ft. (4.6 m) line set. For varying lengths of line set, refer to
table 4 for refrigerant charge adjustment check.
Table 4
Refrigerant Charge per Line Set Lengths
Liquid Line Oz. per 5 ft. (g per 1.5 m) adjust
Set Diameter from 15 ft. (4.6 m) line set*
5/16 in. (8 mm) 2 ounce per 5 ft. (57 g per 1.5 m)
3/8 in. (9.5 mm) 3 ounce per 5 ft. (85 g per 1.5 m)
NOTE - *If line length is greater than !5 ft. (4.6 m), add this amount. If
line length is less than 15 ft. (4.6 m), subtract this amount.
The outdoor unit should be charged during warm weather.
However, applications arise in which charging must occur
in the colder months. The method of charging is deter-
mined by the unit's refrigerant metering device and the
outdoor ambient temperature.
Measure the liquid line temperature and the outdoor ambi-
ent temperature as outlined below:
1. Connect the manifold gauge set to the service valves:
low pressure gauge to vapor valve service port
high pressure gauge to liquid valve service port
2. Connect the center manifold hose to an upright cylin-
der of HCFC-22. Close manifold gauge set valves.
3. Set the room thermostat to call for heat. This will
create the necessary load for properly charging the
system in the cooling cycle.
4. Use a digital thermometer to record the outdoor ambi-
ent temperature.
5. When the heating demand has been satisfied, switch
the thermostat to cooling mode with a set point of 68 _F
(20_%). When pressures have stabilized, use a digital
thermometer to record the liquid line temperature.
6. The outdoor temperature will determine which charg-
ing method to use. Proceed with the appropriate
charging procedure.
Charge Using Weigh-in Method (Fixed Orifice/
TXV Systems) -Outdoor Temp. <65°F (18°C)
If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, use the weigh-in method to charge the
unit. Do this after any leaks have been repaired.
1. Recover the refrigerant from the unit.
2. Conduct a leak check, then evacuate as previously
outlined.
3. Weigh in the charge according to the total amount
shown on the unit nameplate,
If weighing facilities are not available or if you are charging
the unit during warm weather, follow one of the other pro-
cedures outlined below,
Charge Using Subcooling Method (Fixed
Orifice Systems) -Outdoor Temp. >_65°F (18°C)
If you charge a fixed orifice system when the outdoor ambi-
ent is 65 _F (18 _C) or above, use the subcooling method to
charge the unit.
1. With the manifold gauge hose still on the liquid service
port and the unit operating stably, use a digital
thermometer to record the liquid line temperature.
2. At the same time, record the liquid line pressure reading.
3. Use a temperature/pressure chart for R-22 to
determine the saturation temperature for the liquid line
pressure reading.
4. Subtract the liquid line temperature from the saturation
temperature (according to the chart) to determine
subcooling.
Saturation Temperature °F (°C)
-- = Liquid Line Temperature °F (°C)
= Subcooling Value °F (°C)
5. Compare the subcooling value with those in table 5. If
subcooling is greater than shown, recover some
refrigerant. If subcooling is less than shown, add some
refrigerant.
Table 5
Subcooling Values for Fixed Orifice Systems
Outdoor Liquid Subcooling _1"F (.6 C)]
Temp.
°F (°C) 10ACE-24 10ACE-36 10ACE-48 1OACE-60
65 (18) 10 (5.6) 17 (9.5) 15 (8.3) 14 (8)
70 (21) 9 (5) 17 (9.5) 14 (8) 15 (8.3)
75 (24) 8 (4.5) 16 (9) 13 (7) 15 (8.3)
80 (27) 7 (3.9) 15 (8.3) 13 (7) 14 (8)
85 (29) 6 (3.3) 14 (8) 12 (6.7) 14 (8)
90 (32) 5 (2.8) 14 (8) 12 (6.7) 13 (7)
95 (35) 4 (2.2) 12 (6.7) 12 (6.7) 13 (7)
100 (38) 4 (2.2) 11 (6) 11 (6) 12 (6.7)
105 (41) 3 (1.7) 10 (5.6) 10 (5.6) 12 (6.7)
110 (43) 3 (1.7) 9 (5) 9 (5) 11 (6)
115 (45) 2 (1.1) 8 (4.5) 8 (4.5) 10 (5.6)
505128M 03/06
Page 8
Charge Using Approach Method (TXV Systems)
- Outdoor Temperature >65°F (18°C)
The following procedure is intended as a general guide and
is for use on expansion valve (TXV) systems only. For best
results, indoor temperature should be 70°F (21°C) to 80°F
(26°C). Monitor system pressures while charging.
1. Record outdoor ambient temperature using a digital
thermometer.
2. Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.
3. Compare stabilized pressures with those provided in
table 7, "Normal Operating Pressures."
AIMPORTANT
NOTE -For best results, use the same digital ther-
mometer to check both outdoor ambient and fiquid
temperatures.
4, Check the liquid line temperature. The difference be-
tween the ambient and liquid temperatures should
match values given in table 6, Loss of charge results
in low capacity and efficiency.
5, If the values do not agree with the those in table 6, add
refrigerant to lower the approach temperature, or re-
cover refrigerant from the system to increase the ap-
proach temperature,
Table 6
Approach Values
10ACEMode,I -024I -030I -048I -000
Temp. °F(°C) [18 (10) [11 (6) [8(4.5) [13 (7)
Approach Value is the Liquid Line Temperature minus Outdoor Ambi-
ent Temperature °F (°C) + I°F (0.5°C)
Table 7
Normal Operating Pressures*
10ACE-024 10ACE-036 10ACE-048 10ACE-060
Temp°F LiqlsucLiqlsucLiqlsucLiqlsu°
Expansion Valve
65(18) 163 70 162 70 159 71 170 74
75 (24) 193 71 187 74 188 72 261 76
85 (29) 225 72 219 75 220 73 234 77
95 (35) 260 73 253 77 251 76 270 79
105 (41) 298 74 291 79 290 77 309 79
110 _3) 318 75 316 80 309 78 331 80
115 _5) 338 75 329 81 328 79 351 81
Fixed Orifice
65(18) 165 63 168 67 163 68 189 72
75 (24) 194 67 195 71 190 71 203 74
85(29) 224 70 224 75 220 74 233 77
95 (35) 257 73 255 78 251 77 265 79
105 (41) 293 76 289 82 288 79 301 82
110 _3) 313 78 305 83 307 80 319 83
115 _5) 332 79 324 84 325 82 339 84
* Values shown are typical pressures (in. psig +2psig); indoor unit
match up, indoor air quality equipment, and indoor load will cause
the pressures to vary.
** Temperature of the air entering the outside coil.
Page 9
10ACE SERIES
The outdoor unit and indoor blower cycle on demand from
the room thermostat. When the thermostat blower switch
is in the ON position, the indoor blower operates continu-
ously.
NOTE -Whfe residue may surface on guards and grilles
of outdoor units. This is caused by mild acids present in
minute quantities in the plasticizer applied to make the
coating flexible. The residue is comprised of non-toxic,
common fatty acids found in natural animal and vegetable
otis, and can be removed by wiping the parts with a cloth.
Once outside, and over time, the rain will wash off any re-
maining residue.
Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each cool-
ing season, the system should be checked as follows:
WARNÁNG I
1. Clean and inspect the outdoor coil. The coil may be
flushed with a water hose. Make sure power is off be-
fore cleaning,
The outdoor coil is protected by an inner mesh screen
and a wire cage (see figure 9).
Figure 9
6 pins
PUSH PIN
MESH SCREEN
If debris has collected between the mesh screen and
the coil and cannot be dislodged by spraying unpres-
surized water from the inside coil surface to the out-
side, the mesh may be removed by first removing the
top of the unit which will allow for removal of the wire
cage.
Then, using pliers to grip the head of the push pins, pull
straight out to extract the push pins along one side of
the coil, If necessary, remove the push pins along the
back of the unit; it is usually unnecessary to fully re-
move the inner mesh screen,
Drape the mesh screen back and wash the coil. When
all the debris has been removed from the coil, reinstall
the mesh screen by positioning it in its original position
and reinserting the push pin. No tool is required to
push the pin back into the same slot in the fins,
If the push pin is loose and tends not to stay in place,
brush the fins with a 22 fpi fin brush (except model
-024, 18 fpi), Line up the push pin a couple fins to the
right or left of the original hole and re-insert the pin,
2, Condenser fan motor is prelubricated and sealed, No
further lubrication is needed.
3, Visually inspect connecting lines and coils for evi-
dence of oil leaks,
4. Check wiring for loose connections.
5, Check for correct voltage at unit (unit operating),
6, Check amp-draw condenser fan motor,
Unit nameplate Actual
NOTE -If the owner reports insufficient cooling, the
un# should be gauged and the refrigerant charge
should be checked. Refer to the charging section in
this instruction.
Indoor Coil
1. Clean coil, if necessary.
2. Check connecting lines and coils for evidence of oil
leaks.
3. Check the condensate pan line and clean it if neces-
sary.
Indoor Unit
1, Clean or change filters,
2. Adjust blower speed for cooling, Measure the pressure
drop over the coil to determine the correct blower CFM
Refer to the unit information service manual for pressure
drop tables and procedure,
3. Belt Drive Blowers - Check belt for wear and proper
tension,
4, Check all wiring for loose connections
5. Check for correct voltage at unit (blower operating).
6. Check amp-draw on blower motor
Unit nameplate Actual
505128M 03/06
Page 10
RefertotheEngineeringHandbookforoptionalaccesso-
riesthatmayapplytothisunit,Thefollowingmayormay
notapply:
• LossofChargeKit
• HighPressureSwitchKit
• CompressorMonitor
CompressorCrankcaseHeater(standardon4 and5
tonunits)
• HailGuards
• MountingBases
• TimedOffControl
• Stand-offKit
• SoundCover
• LowAmbientKit
JobName
JobLocation
Installer
UnitModelNo,
NameplateVoltage
RatedLoadAmpacity
SerialNo.
Jobno. Date
City State
City State
ServiceTechnician
Compressor OutdoorFan
MaximumFuseorCircuitBreaker
ElectricalConnectionsTight? [] IndoorFilterclean?[]
IndoorBlowerRPM__ S,RDropOverIndoor(Dry)
DischargePressure VaporPressure
RefrigerantLines:- LeakChecked?[] ProperlyInsulated?[]
ServiceValves: --- FullyOpened? [] CapsTight? []
VoltageWithCompressorOperating
SupplyVoltage(UnitOff)
OutdoorCoilEnteringAirTemp.
RefrigerantChargeChecked?
OutdoorFanChecked?
Thermostat
Calibrated?[] ProperlySet?[]
[]
[]
Level? []
Page 11
10ACE SERIES
Page 1 of 12 - LENNOX  Air Conditioner/heat Pump(outside Unit) Manual L0805442
Page 2 of 12 - LENNOX  Air Conditioner/heat Pump(outside Unit) Manual L0805442
Page 3 of 12 - LENNOX  Air Conditioner/heat Pump(outside Unit) Manual L0805442
Page 4 of 12 - LENNOX  Air Conditioner/heat Pump(outside Unit) Manual L0805442
Page 5 of 12 - LENNOX  Air Conditioner/heat Pump(outside Unit) Manual L0805442
Page 6 of 12 - LENNOX  Air Conditioner/heat Pump(outside Unit) Manual L0805442
Page 7 of 12 - LENNOX  Air Conditioner/heat Pump(outside Unit) Manual L0805442
Page 8 of 12 - LENNOX  Air Conditioner/heat Pump(outside Unit) Manual L0805442
Page 9 of 12 - LENNOX  Air Conditioner/heat Pump(outside Unit) Manual L0805442
Page 10 of 12 - LENNOX  Air Conditioner/heat Pump(outside Unit) Manual L0805442
Page 11 of 12 - LENNOX  Air Conditioner/heat Pump(outside Unit) Manual L0805442
Page 12 of 12 - LENNOX  Air Conditioner/heat Pump(outside Unit) Manual L0805442

Navigation menu