LENNOX Air Conditioner/heat Pump(outside Unit) Manual L0805442
User Manual: LENNOX LENNOX Air conditioner/heat pump(outside unit) Manual LENNOX Air conditioner/heat pump(outside unit) Owner's Manual, LENNOX Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 12
Download | ![]() |
Open PDF In Browser | View PDF |
INSTALLATION INSTRUCTIONS ,?u2006 Lennox industries Inc, Dallas, Texas, USA 10ACE Series Units CONDENSER UNITS 505,128M 03/06 Supersedes 01/06 X_ WARNING X_ IMPORTANT _ Technical LL.L[ Publications Litho U.S.A. 10ACE Outdoor Units .......................... Shipping & Packing List ........................ General Information ........................... Unit Dimensions ............................... Setting the Unit ............................... Electrical ..................................... Refrigerant Piping ............................. Refrigerant Metering Devices ................... Manifold Gauge Set ........................... Service Valves ................................ Leak Testing .................................. Evacuation ................................... Start-Up ...................................... Refrigerant Charging ........................... System Operation ............................. Maintenance .................................. Optional Accessories .......................... Start-Up & Performance Check List .............. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE 1 1 2 2 2 3 4 4 5 5 6 6 7 8 10 10 11 11 AI_CAUTION _I_WARNING Lennox Merit ® 10ACE outdoor units are designed for use in either fixed orifice or expansion valve (TXV) systems, The TXV may require a field-installed hard start kit. Refer to the Lennox Engineering Handbook for expansion valve kits which must be ordered separately. 1 - Assembled outdoor unit 1 - Fixed orifice refrigerant metering device Check the unit for shipping damage. Consult last carrier immediately if damage is found. 03/06 IIIIIIIIIIIIIIIIIIIIIIHIllllllllllll Page 1 505,128M IIIIIIIIIIIIlllllll]lllllllllllllll .---11_4 -3/8 I._l-AIR f -_ _. !/ i © _\1 [I OPTIONAL UNIT LI -- STAND-OFFKIT(4) / I \\J__/II AIR ------ VAPOR LINE AIR T " _11/_ LIQUID LINE CONNECTION C I ILH C°MPRESSOR HII (Fieldlnstalled) " 14fl (Around perimeter of base) f 4-3/8 U]l x , \'- --' UI - II -- f2, I_._X_ --I_ Vl ,.._I _I .,-k_ I[U A_R COIL DRAIN OUTLETS f II! IF _llllll\\\\\\XX_"'_/..-_ 111-- Y _1--. li!11)1 ' _-%1 (111)1,/,.k, il Yt_J_\ - 4-3/8 I,_I" _'_ '/fT_'_%JJf/_.\ ---I,44-3/8 I(111) F c:z:::_ _11 . Illl ,I, (_ 6-3/8 _ _1,,_4-3/8__1 (162) I_ vI(111)I TOP VIEW BASE SECTION -- OUTDOOR COIL FAN C i DISCHARGE .._1 AIR _1 COMPRESSOR OPTIONAL UNIT STAND-OFF I • I\ VAPOR & LIQUID LINE CONNECTION KIT (4) (Field Installed) \ I 2-3/4 (70) 11 L.J. _ 'LLJ 2 (51) 3/4%, 10ACE Model A B C -024 25 (635) 24-1/4 (616) 24-1/4 (565) -036 -048 33 (635) 33 (838) 32-1/4 (616) 32-1/4 (819) 24-1/4 (565) 24-1/4 (616) -060 33 (940) 32-1/4 (921) 24-1/4 (718) SIDE VIEW Table 1 Torque These instructions are intended as a general guide and do not supersede national or local codes in any way. Consult authorities who have jurisdiction before installation, When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners. 03/06 Requirements Part Recommended Torque Service valve cap 8 ft.- lb. 11 NM Sheet metal screws 16 in.- lb. 2 NM Machine screws #10 28 in.- lb. 3 NM Compressor bolts 90 in.- lb. 10 NM Gauge port seal cap 8 ft.- lb. 11 NM Refer to unit dimensions for sizing mounting slab, platforms or supports. Refer to figure 1 for installation clearances. Page 2 505128M I ELECTRICAL INLETS g \ I Slab Mounting When installing unit at grade level, install on a level slab high enough above grade to allow adequate drainage of water. Top of slab should be located so run-off water from higher ground will not collect around unit, Installation 1, Install line voltage power supply to unit from a properly sized disconnect switch. 2. Install line voltage power supply to unit from a properly sized disconnect switch. Any excess high voltage field wiring should be trimmed or secured away from the low voltage field wiring (see figures 2 and 3), Separating // Clearances High/Low / Voltage Field Wiring WIRE TIES High Voltage Field Wiring Low Voltage Field Wiring ----- (as noted) Factory Wiring (as noted) Figure 2 *A service clearance of 30" (762 mm) must be maintained on one of the sides adjacent to the control box. Clearance to one of the other three sides must be 36" (914 mm). Clearance to one of the remaining two sides may be 12" (304 mm) and the final side may be 6" (152 Typical OUTDOOR Field Wiring START _ * ram), DUAL _FAN A clearance of 24" (610 mm) must be maintained between two units. 48" (1219 mm) clearance required on top of unit. Maximum soffit overhang is 36" (914 mm). Figure I CAPACITOR 1 Mounting __ K31 BLACK Install the unit at a minimum of 4 inches (102 mm) above the surface of the roof, Ensure the weight of the unit is properly distributed over roof joists and rafters, Redwood or steel supports are recommended, _WARNING *A& COMPRESSOR POTENT[AL RELAY * CONTACTOR F- TIMED OFF CONTROL (_ •-048 & -060 models In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC), CAPACITOR CE2 BLACK ORANGE RED .Roof Diagram NOTE) 208-230/60/1 G I I (SEE _ IL2 LE I GROUND WARNING! - ELECTRIC SHOCK HAZARD Can cause INJURY or DEATH, Unit must be grounded in accordance with national and local codes. NOTE - For use with copper conductors only. Refer to unit rating plate for minimum circuit ampacity and maximum over-current protection size. Figure Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size. 3 3. Ground unit at unit disconnect switch or to an earth ground. NOTE - To facilitate conduit, a hole is located in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting. Units are approved for use only with copper conductors. 24V, Class II circuit connections are made to the low voltage pigtafs. Refer to figure 3 for field wiring diagram. A complete unit wiring diagram is located inside the unit control box cover. 4. Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations. Page 3 10ACE SERIES NOTE - For proper voltages, select thermostat wire gauge per the following chart: Wire run length AWG # Insulation type less than 100' (30m) 18 color-coded, more than 100' (30m) 16 rating 35°C minimum Sweat Field Low Voltage Thermostat Wiring temperature Diagram Indoor Unit p..... Use 10ACE units in either TXV systems or fixed orifice systems, See the Lennox Engineering Handbook for approved TXV and fixed orifice match-ups and application information. Table 2 lists the unit liquid and vapor line sizes and corresponding line sets, Outdoor Unit @ heat Q ooo,,nq Q indoor blower Fixed Orifice NOTE - see unit wiring diagram for power supply connections. If indoor unit is not equipped with blower rela_zIt must be field-provided and installed (P-8-3251 or equivalent). Table 3 Fixed Orifice 4 Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections). Use Lennox L15 (sweat, nonflare) series line sets as shown in table 2 or use field-fabricated refrigerant lines, Refer to Refrigerant Piping Guide (Corp. 9351-L9) for proper size, type, and application of field-fabricated lines. Valve sizes are also listed in table 2. Table Refrigerant Model Liquid Line Liquid Line Vapor Line 3/8 in 3/4 in. 3/8 in 3/4 in. L15-41 (19mm) (10mm) (19mm) 15 ft,- 50 ft. (4.6 m - 15m) 3/8 in 7/8 in. 3/8 in 7/8 in. L15-65 (10 mm) (22 mm) (10 mm) (22 mm) 15 ft,- 50 ft. (4.6 m - 15m) 3/8 in 1-1/8 in. 3/8 in 1-1/8 in. Field (10 mm) (29 mm) (10 mm) (29 mm) Fabricated NOTE - Units are designed for line sets of up to 50 feet (15 m), For applications longer than 50 feet, consult the Lennox Refrigerant Piping Guide (Corp. 9351-L9), Select line set diameters from table 2 to ensure that oil returns to the compressor. .062 100484-22 .073 10ACE-048 100484-33 .086 10ACE-060 100484-44 .098 Metering Device Installation j FIXED ORIFICE | _ DISTRIBUTOR or f-_-_ _ EXPANSION VALVE & O-RING (See NOTE) _i_(_ LIQUID LINE STUB STRAINER NOTE - If installing expansion valve with an indoor coil that includes a fixed orifice, remove orifice before installing valve, Figure 5 Expansion Valve Systems Expansion valves equipped with Chatleff fittings are available from Lennox, Refer to the Engineering Handbook for expansion valves for use with specific match-ups. Page 4 03/06 100484-12 10ACE-036 L15 Line Sets (10mm) 505128M 10ACE-024 _'-_ // Line Set -036 -060 Fixed Orifice Drill Size _ o O-RING -024 -048 Unit II Line Kits Recommended Drill Sizes Fixed Orifice Catalog # Install the fixed orifice as shown in figure 5, Do not twist the cap tubes when loosening the seal nut from the orifice housing, 2 Valve Field Size Connections Vapor Line Systems 10ACE units are shipped with a fixed orifice refrigerant metering device. Replace the existing indoor unit fixed orifice with the orifice supplied with the outdoor unit. Place the supplied fixed orifice sticker on the indoor cabinet after installation. See table 3 for the fixed orifice size for each unit, In nonstandard applications, the provided fixed orifice may not be appropriately sized. Refer to the Engineering Handbook for specific orifice information. @ Figure Procedure 1, Cut ends of the refrigerant lines square (free from nicks or dents), Debur the ends. The pipe must remain round, do not pinch end of the line, 2. Wrap a wet cloth around the valve body and copper tube stub to protect it from heat damage during brazing, Wrap another wet cloth underneath the valve body to protect the base paint, 3, Quench the joints with a wet cloth to prevent possible heat damage to the valve core and opening port. 4. Install a field-provided filter dryer as close as possible to the expansion device, 5. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit, See figure 4. Typical Connection If you install a expansion valve with an indoor coil that includes a fixed orifice, remove the orifice before the expansion valve is installed. A IMPORTANT Front-Seated Liquid STEM CAP SCHRADER Line Service INSERT Valve HEX VALVE IS CLOSED (FRONT SEATED)] _ OUTVALVE ]OPEN TO DOOR WRENCH HERE COl L,NE SET WHEN OR SERVICE PORT CAP When checking the unit charge, use a manifold gauge set that is equipped with "low loss" hoses. Do not use a manifold gauge set with anything other than a "low loss" hose. (VALVE FRONT-SEATED) Valve in closed position Valve in open position Figure 6 The service valves (liquid line - figure 6, vapor line - figures 7 and 8) and gauge ports are used for leak testing, evacuating, charging and checking charge, Each valve is equipped with a service port which has a factory-installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal. To Access Schrader Port: 1. Remove service port cap with an adjustable wrench. 2. Connect gauge to the service port, 3, When testing is complete, replace service port cap. Tighten finger tight, then torque per table 1 (Page 2). To Open Front-Seated Service Valves: 1, Remove stem cap with an adjustable wrench, 2. Use a service wrench with a hex-head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to back the stem out counterclockwise as far as it will go, 3, Replace the stem cap. Tighten finger tight, then torque per table 1 (Page 2). To Close Front-Seated Service Valves: 1. Remove the stem cap with an adjustable wrench, 2. Use a service wrench with a hex-head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to turn the stem clockwise to seat the valve. Tighten it firmly, Front-Seated Vapor Line Service [OPEN TO LINE SET WHEN VALVEVALVE IS SCHRADER CLOSED (FRONT SEATED)] INSERT HEX WRENCH HERE SERVICE TO OUTDOOR r COIL , SERVICE PORT CAP PORT INDOOR COIL (VALVE FRONT-SEATED) Valve in closed position Valve in open position Figure Bali-Type 7 Vapor Valve (Valve Closed) sl M USE ADJUSTABLE WRENCH TO OPEN: ROTATE STEM COUNTER-CLOCKWISE TO CLOSE: CLOCKWISE TO OUTDOOR COIL STEM 90 °. ROTATE STEM 90 ° . 3. Replace the stem cap, Tighten finger tight, then torque per table 1 (Page 2), Vapor Valve STEM CAP CLOSED) Line Ball Valve Ball-type service valve (10ACE-060 only, figure 8) functions the same way as the other valves but cannot be rebuilt; if one fails, replace with a new valve, The ball valve is equipped with a service port with a factory-installed Schrader valve. A service port cap protects the Schrader valve from contamination and assures a leak-free seal. SERVICE TO INDOOF PORT (_SCHRADER COIL VALVE SERVICE PORT CAP Figure 8 Page 5 10ACE SERIES 4. Connect a cylinder of nitrogen with a pressure regulating valve to the center port of the manifold gauge set, 5. Connect the manifold gauge set high pressure hose to the vapor valve service port. (Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the manifold gauge set from high pressure damage,) 6. Adjust the nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set which will pressurize line set and indoor unit. 7. After a few minutes, open a refrigerant port to ensure the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge nitrogen and HCFC-22 mixture. Correct any leaks and recheck. After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks, I ,WARNING I WARNING Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper piping and compressor parts. A IMPORTANT I AWARNING I WARNING Using an Electronic Leak Detector or Halide 1, Connect a cylinder of HCFC-22 to the center port of the manifold gauge set. 2, With both manifold valves closed, open the valve on the HCFC-22 cylinder (vapor only). 3, Open the high pressure side of the manifold to allow the HCFC-22 into the line set and indoor unit. Weigh in a trace amount of HCFC-22, [A trace amount is a maximum of 2 ounces (57 g) or 3 pounds (31 kPa) pressure,] Close the valve on the HCFC-22 cylinder and the valve on the high pressure side of the manifold gauge set, Disconnect the HCFC-22 cylinder, Page 6 505128M 03/06 1. Connect manifold gauge set to the service valve ports as follows: • low pressure gauge to vapor line service valve • high pressure gauge to liquid line service valve 2. Connect micron gauge, 3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set, 4. Open both manifold valves and start the vacuum pump. 5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury). During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute pressure. A rapid rise in pressure indicates a relatively large leak, If this occurs, repeat the leak testing procedure. NOTE - The term absolute pressure is defined as the total actual pressure within a given volume or system, above the absolute zero of pressure, Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure, 6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit, Close the manifold gauge valves. ,A CAUTION A IMPORTANT 7. Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen from the line set and indoor unit. 8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves. 9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HCFC-22 refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off the HCFC-22 cylinder and remove the manifold gauge set. 1. Rotate the fan to check for frozen bearings or binding. 2. Inspect all factory- and field-installed wiring for loose connections. 3. After evacuation is complete, open the liquid line and vapor line service valves to release refrigerant charge (contained in outdoor unit) into the system. 4. Replace the stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn. 5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit's nameplate. If not, do not start the equipment until you have consulted the power company and the voltage condition has been corrected. 6. Set the thermostat for a cooling demand. Turn on power to the indoor blower and close the outdoor unit disconnect switch to start the unit. 7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate. Page 7 10ACE SERIES 2. Conduct a leak check, then evacuate as previously outlined. Units are factory charged with the amount of HCFC-22 refrigerant indicated on the unit nameplate. This charge is based on a matching indoor coil and outdoor coil with a 15 ft. (4.6 m) line set. For varying lengths of line set, refer to table 4 for refrigerant charge adjustment check. Table Refrigerant Charge 4 Oz. per 5 ft. (g per 1.5 m) adjust from 15 ft. (4.6 m) line set* 5/16 in. (8 mm) 2 ounce per 5 ft. (57 g per 1.5 m) 3/8 in. (9.5 mm) 3 ounce per 5 ft. (85 g per 1.5 m) If weighing facilities are not available or if you are charging the unit during warm weather, follow one of the other procedures outlined below, Charge Using Subcooling Method (Fixed Orifice Systems) - Outdoor Temp. >_65°F (18°C) per Line Set Lengths Liquid Line Set Diameter 3. Weigh in the charge according to the total amount shown on the unit nameplate, If you charge a fixed orifice system when the outdoor ambient is 65 _F (18 _C) or above, use the subcooling method to charge the unit. 1. With the manifold gauge hose still on the liquid service port and the unit operating stably, use a digital thermometer to record the liquid line temperature. 2. At the same time, record the liquid line pressure reading. NOTE - *If line length is greater than !5 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount. The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is determined by the unit's refrigerant metering device and the outdoor ambient temperature. Measure the liquid line temperature and the outdoor ambient temperature as outlined below: 1. Connect the manifold gauge set to the service valves: • low pressure gauge to vapor valve service port • high pressure gauge to liquid valve service port 2. Connect the center manifold hose to an upright cylinder of HCFC-22. Close manifold gauge set valves. 3. Set the room thermostat to call for heat. This will create the necessary load for properly charging the system in the cooling cycle. 4. Use a digital thermometer to record the outdoor ambient temperature. 5. When the heating demand has been satisfied, switch the thermostat to cooling mode with a set point of 68 _F (20_%). When pressures have stabilized, use a digital thermometer to record the liquid line temperature. 6. The outdoor temperature will determine which charging method to use. Proceed with the appropriate charging procedure. Charge Using Weigh-in TXV Systems) -Outdoor Method (Fixed Orifice/ Temp. <65°F (18°C) If the system is void of refrigerant, or if the outdoor ambient temperature is cool, use the weigh-in method to charge the unit. Do this after any leaks have been repaired. 1. Recover the refrigerant from the unit. Page 8 505128M 03/06 3. Use a temperature/pressure chart for R-22 to determine the saturation temperature for the liquid line pressure reading. 4. Subtract the liquid line temperature from the saturation temperature (according to the chart) to determine subcooling. Saturation Temperature °F (°C) -- = Liquid Line Temperature °F (°C) = Subcooling Value °F (°C) 5. Compare the subcooling value with those in table 5. If subcooling is greater than shown, recover some refrigerant. If subcooling is less than shown, add some refrigerant. Table Subcooling Values 5 for Fixed Liquid Subcooling Orifice Systems Outdoor Temp. °F (°C) _ 1"F (.6 C)] 10ACE-24 10ACE-36 10ACE-48 65 (18) 10 (5.6) 17 (9.5) 15 (8.3) 14 (8) 70 (21) 9 (5) 17 (9.5) 14 (8) 15 (8.3) 75 (24) 8 (4.5) 16 (9) 13 (7) 15 (8.3) 80 (27) 7 (3.9) 15 (8.3) 13 (7) 14 (8) 85 (29) 6 (3.3) 14 (8) 12 (6.7) 14 (8) 90 (32) 5 (2.8) 14 (8) 12 (6.7) 13 (7) 95 (35) 4 (2.2) 12 (6.7) 12 (6.7) 13 (7) 100 (38) 4 (2.2) 11 (6) 11 (6) 12 (6.7) 105 (41) 3 (1.7) 10 (5.6) 10 (5.6) 12 (6.7) 1OACE-60 110 (43) 3 (1.7) 9 (5) 9 (5) 11 (6) 115 (45) 2 (1.1) 8 (4.5) 8 (4.5) 10 (5.6) Table 6 Charge Using Approach Method (TXV Systems) - Outdoor Temperature >65°F (18°C) The following procedure is intended as a general guide and is for use on expansion valve (TXV) systems only. For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging. 1. Record outdoor ambient temperature thermometer. using a digital Approach Values 10ACEMode, I -024I -030I -048I -000 Temp. °F(°C) [ 18 (10) [ 11 (6) [ 8(4.5) [ 13 (7) Approach Value is the Liquid Line Temperature minus Outdoor Ambient Temperature °F (°C) + I°F (0.5°C) Table 2. Attach high pressure gauge set and operate unit for several minutes to allow system pressures to stabilize. 3. Compare stabilized pressures with those provided in table 7, "Normal Operating Pressures." Normal 10ACE-024 Temp°F Expansion A IMPORTANT Operating 10ACE-036 7 Pressures* 10ACE-048 10ACE-060 LiqlsucLiqlsucLiqlsucLiqlsu° Valve 65(18) 163 70 162 70 159 71 170 74 75 (24) 193 71 187 74 188 72 261 76 85 (29) 225 72 219 75 220 73 234 77 95 (35) 260 73 253 77 251 76 270 79 105 (41) 298 74 291 79 290 77 309 79 110 _3) 318 75 316 80 309 78 331 80 115 _5) 338 75 329 81 328 79 351 81 Fixed Orifice 65(18) 165 63 168 67 163 68 189 72 75 (24) 194 67 195 71 190 71 203 74 85(29) 224 70 224 75 220 74 233 77 95 (35) 257 73 255 78 251 77 265 79 4, Check the liquid line temperature. The difference between the ambient and liquid temperatures should match values given in table 6, Loss of charge results in low capacity and efficiency. 105 (41) 293 76 289 82 288 79 301 82 110 _3) 313 78 305 83 307 80 319 83 115 _5) 332 79 324 84 325 82 339 84 5, If the values do not agree with the those in table 6, add refrigerant to lower the approach temperature, or recover refrigerant from the system to increase the approach temperature, * NOTE - For best results, use the same digital thermometer to check both outdoor ambient and fiquid temperatures. Values shown are typical pressures (in. psig +2psig); indoor unit match up, indoor air quality equipment, and indoor load will cause the pressures to vary. ** Temperature of the air entering the outside coil. Page 9 10ACE SERIES If debris has collected between the mesh screen and the coil and cannot be dislodged by spraying unpressurized water from the inside coil surface to the outside, the mesh may be removed by first removing the top of the unit which will allow for removal of the wire cage. The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously. Then, using pliers to grip the head of the push pins, pull straight out to extract the push pins along one side of the coil, If necessary, remove the push pins along the back of the unit; it is usually unnecessary to fully remove the inner mesh screen, NOTE - Whfe residue may surface on guards and grilles of outdoor units. This is caused by mild acids present in minute quantities in the plasticizer applied to make the coating flexible. The residue is comprised of non-toxic, common fatty acids found in natural animal and vegetable otis, and can be removed by wiping the parts with a cloth. Once outside, and over time, the rain will wash off any remaining residue. Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows: Drape the mesh screen back and wash the coil. When all the debris has been removed from the coil, reinstall the mesh screen by positioning it in its original position and reinserting the push pin. No tool is required to push the pin back into the same slot in the fins, If the push pin is loose and tends not to stay in place, brush the fins with a 22 fpi fin brush (except model -024, 18 fpi), Line up the push pin a couple fins to the right or left of the original hole and re-insert the pin, I WARNÁNG 2, Condenser fan motor is prelubricated and sealed, No further lubrication is needed. 3, Visually inspect connecting dence of oil leaks, lines and coils for evi- 4. Check wiring for loose connections. 1. Clean and inspect the outdoor coil. The coil may be flushed with a water hose. Make sure power is off before cleaning, The outdoor coil is protected by an inner mesh screen and a wire cage (see figure 9). 5, Check for correct voltage at unit (unit operating), 6, Check amp-draw condenser fan motor, Unit nameplate Actual NOTE - If the owner reports insufficient cooling, the un# should be gauged and the refrigerant charge should be checked. Refer to the charging section in this instruction. • 6 pins Indoor Coil 1. Clean coil, if necessary. 2. Check connecting lines and coils for evidence of oil leaks. 3. Check the condensate pan line and clean it if necessary. Indoor Unit 1, Clean or change filters, 2. Adjust blower speed for cooling, Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tables and procedure, 3. Belt Drive Blowers - Check belt for wear and proper tension, PUSH 4, Check all wiring for loose connections PIN 5. Check for correct voltage at unit (blower operating). MESH SCREEN Figure 6. Check amp-draw on blower motor Unit nameplate Actual 9 Page 10 505128M 03/06 • RefertotheEngineering Handbook foroptionalaccessoriesthatmayapplytothisunit,Thefollowingmayor may notapply: • LossofChargeKit • HighPressure SwitchKit • Compressor Monitor • • • • • • Compressor Crankcase Heater(standardon4 and5 tonunits) HailGuards MountingBases TimedOffControl Stand-offKit SoundCover LowAmbientKit JobName Jobno. JobLocation City Installer City UnitModelNo, SerialNo. Nameplate Voltage RatedLoadAmpacity Compressor MaximumFuseor CircuitBreaker ElectricalConnections Tight? [] IndoorFilterclean?[] IndoorBlowerRPM__ S,RDropOverIndoor(Dry) Discharge Pressure VaporPressure RefrigerantLines:- LeakChecked?[] ProperlyInsulated?[] ServiceValves: --- FullyOpened? [] CapsTight? [] VoltageWithCompressor Operating Date State State ServiceTechnician OutdoorFan SupplyVoltage(UnitOff) OutdoorCoilEnteringAir Temp. Refrigerant ChargeChecked? OutdoorFanChecked? Thermostat Calibrated?[] ProperlySet?[] [] [] Level? [] Page 11 10ACE SERIES
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 12 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Mon Jun 30 04:22:43 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools