LENNOX Air Conditioner/heat Pump(outside Unit) Manual L0805500

User Manual: LENNOX LENNOX Air conditioner/heat pump(outside unit) Manual LENNOX Air conditioner/heat pump(outside unit) Owner's Manual, LENNOX Air conditioner/heat pump(outside unit) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 19

DownloadLENNOX  Air Conditioner/heat Pump(outside Unit) Manual L0805500
Open PDF In BrowserView PDF
LENNOX

INSTALLATION
INSTRUCTIONS

¢_2002 Lennox Industries Inc.
Dallas, Texas

HSXA12 Series Units
CONDENSING UNITS
504,540M
04/04
Supersedes 12/03

HSXA12 outdoor

units use R410A which is an ozone

friendly HFC refrigerant. This unit must be installed with a
matching indoor coil and line set as outlined in the Lennox
Engineering Handbook. HSXA12 outdoor units are designed for use in expansion valve (TXV) and fixed orifice
systems. Refer to the Lennox Engineering Handbook for
expansion valve kits which must be ordered separately, A
filter dryer approved for use with R410A has been shipped
with the unit. This component must be installed prior to operating the unit. Failure to install the provided filter dryer
will void the warranty.

1 - Assembled HSXA12 outdoor unit
1 - Liquid line filter drier (approved for use with R410A
systems)
1 - Fixed orifice refrigerant metering device
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.

FT_
Technical
.LLL[ Publications
Lithe U.S.A.

HSXA12 Outdoor Unit ...........................
Shipping And Packing List .......................
General Information .............................
Unit Dimensions ................................
Setting the Unit .................................
Electrical ......................................
Refrigerant Piping ..............................
Flushing Existing Line Set & Indoor Coil ...........
Refrigerant Metering Device ....................
Manifold Gauge Set ............................
Service Valves ................................
Leak Testing ..................................
Evacuation ...................................
Start-up ......................................
Charging .....................................
System Operation .............................
Maintenance ..................................
Optional Accessories ..........................
HSXA12 Check Points .........................

1
1
1
2
3
3
5
5
11
11
12
13
13
14
14
18
18
18
19

RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE

These instructions are intended as a general guide and do
not supersede national or local codes in any way. Consult
authorities having jurisdiction before installation.

WARNING

AWARNING

,IMPORTANT

04/04

IIIHllllllllliillllillllillllillllill

504,540M
Page 1

IIIHllllllllliillliillllllll

IN LET._

AIR

4-3/8
(111)

INLET

OPTIONAL
STAND-OFF

INLET

©

©

(Field

4-3/8
(111)

UNIT
KIT

Installed)

AIR

AIR

(Around

perimeter of base)

VAPOR LINE
CONNECTION

INLET'_

6-3/8
(162)

4-3/8
(111)

LIQUID LINE
CONNECTION

AIR

Top View

Top View
_-

C

Base
C

DISCHARGEr

_-_

Section

AIR

OUTDOOR
COIL FAN

COMPRESSOR_

A

VAPOR &
LIQUID LINE
CONNECTION

ELECTRICAL
INLETS

2-3/4 (70)

Side View

3/4
(19)

OPTIONAL
STAND-OFF
(Field

UNIT
KIT

Model No.
HSXA12-018
HSXA12-024
HSXA12-030
HSXA12-036
HSXA12-042
HSXA12-048

Side View

Installed)

A

B

C

in,

25

24-1/4

24-1/4

mm

635

616

616

in.

33

32-1/4

24-1/4

mm

838

819

616

29

28-1/4

28-1/4

737

718

718

in,

HSXA12-060
mm

Page 2

Roof Mounting
Install unit at a minimum of 4 inches above the surface of
the roof. Care must be taken to ensure weight of unit is
properly distributed over roof joists and rafters, Either redwood or steel supports are recommended,

&CAUTION
kCAUTION

In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current

Refer to unit dimensions for sizing mounting slab, platforms or supports, Refer to figure 1 for installation clearances,
Installation

Clearances

Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.

A WARNING

1 - Install line voltage power supply to unit from a properly
sized disconnect switch,
2 - Ground unit at unit disconnect switch or to an earth
(914 ram)

ground,
NOTE - To facilitate conduit, a hole is in the bottom of
the control box. Connect conduit to the control box us

*NO TE - A service clearance of 30" (762 mm) must be maintained on one of the sides adjacent to the control box. Clear-

ing a proper conduit fitting.

ance to one of the other three sides must be 36" (914 mm).
Clearance to one of the remaining two sides may be 12" (304
mm) and the final side may be 6" (152 mm).

NO TE - Units are approved for use only with copper
conductors.

NOTE - A clearance of 24" (610 mm) must be maintained
between two units.
NOTE - 48" (1219 mm) clearance required on top
of unit. Maximum soffit overhang is 36" (914 mm).

Figure

24V, Class II circuit connections are made in the low
voltage junction box, Refer to figure 4 for field wiring
diagram,

1

Slab Mounting
When installing a unit at grade level, the top of the slab
should be high enough above the grade so that water from
higher ground will not collect around the unit. See figure 2.
Slab should have a slope tolerance away from the building
of 2 degrees or 2 inches per 5 feet (51 mm per 1524 mm),
Refer to roof mounting section for barrier construction if
unit must face prevailing winter winds,
Slab Mounting

At Ground

structure

'i_

Level

discharge air

NOTE - A complete unit wiring diagram is located in
side the unit control box coven
3 - Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned
area and 5 feet (1.5 m) from the floor. It should not be
installed on an outside wall or where it can be effected
by sunlight, drafts or vibrations,
4 - Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit, See figure 3,

J,

12
Mounting slab must slope
away from building,

Figure

ground level

2

Page 3

Thermostat
Thermostat

Designations

Indoor Unit
NOTE - see unit wiring diagram for
power supply connections.

®

power

Outdoor Unit
[Wl;

t

-®

heat

E_

cooling

V_

-(_-

v

indoor blower

@
©
NOTE

- If the

@
[_

common

indoor

unit

is not

.....

equipped

with

blower

relay

It must

Figure

Typical

_0_

TDOOR
FAN

__

RED
YELLOW
BLACK

RELAY*

CI2
DUAL
CAPACITOR

TIMED

*A4
OFF

field-provided

and

installed

(P-8-3251

or equivalent).

A

CONTROL

KI
COMPRESSOR
CONTACTOR

NOTEFOR USE WITH COPPER
CONDUCTORS
ONLY.REFER
TO UNIT RATING
PLATE FOR MINIMUM
CIRCUIT
AMPACITY AND MAXIMUM OVERCURRENT
PROTECTION
SIZE

WARNINGELECTRIC
SHOCK HAZARD, CAN CAUSE
INJURY OR DEATH. UNIT MUST BE
GROUNDED IN ACCORDANCE WITH
NATIONAL
AND LOCAL CODES

50

COMPRESSOR

\ .....

Diagram

©
K3 I
POTENTIAL

C Outdoor Unit

/

3

Field Wiring

CAPACITOR
START *

be

PURPLE
LACK
ANGE

Y1 Outdoor Unit

l,'

208-230/60/I

A

"
D

1
GROUND

*May be optional

Figure

4

Page 4

Installing Refrigerant Line

If theHSXA12
unitisbeinginstalled
withanindoorcoiland
lineset,maketherefrigerant
connections
asoutlined
inthis
section.If anexistinglinesetand/orindoorcoilis goingto
beusedtocomplete
theHSXA12
system,refertothissection,aswellas theflushingsectionwhichfollows,
Fieldrefrigerantpipingconsistsof liquidandvaporlines
fromtheoutdoorunit(sweatconnections)
totheindoorcoil
(flareor sweatconnections).
UseLennoxL15(sweat,nonflare)serieslinesetsasshownintable1or usefield-fabricatedrefrigerant
lines.Referto Refrigerant
PipingGuide
(Corp,9351-L9)for propersize,type,andapplicationof
field-fabricated
lines.Valvesizesarealsolistedintable1.
Refrigerant Line Connections
HSXA12 Matched with New Indoor Coil and Line Set
If the HSXA12 is being used with an existing indoor coil
which was equipped with a liquid line which served as
a metering device (RFCI), the liquid line must be replaced prior to the installation of the HSXA12 unit.
If refrigerant lines are routed through a wall, seal and isolate
the opening so vibration is not transmitted to the building,
Table 1
Refrigerant
Line Sets
Valve Field Size
Connections

Recommended

Model

Line Set
L15
Line Sets

Liquid
Line

Vapor
Line

Liquid
Line

Vapor
Line

-018

3/8 in.
(10 mm)

5/8 in.
(16 mm)

3/8 in,
(10 mm)

5/8 in,
(19 mm)

L15-26
15 if, - 50 ft.
(4.6 m- 15 m)

024
-030
-036

3/8 in,
(10mm)

3/4 in,
(19mm)

3/8 in,
(10mm)

3/4 in,
(19mm)

L15-41
15 ft. - 50 ft.
(4.6m-15m)

-042
-048

3/8 in.
(10 mm)

7/8 in.
(22 mm)

3/8 in,
(10 mm)

7/8 in,
(22 mm)

3/8 in,

1-1/8 in,

3/8 in,

1-1/8 in.

Field

(10 mm)

(29 mm)

(10 mm)

(29 mm)

Fabricated

-060

During the installation of any heat pump or a/c system, it is
important to properly isolate the refrigerant lines to prevent
unnecessary vibration, Line set contact with the structure
(wall, ceiling or floor) causes some objectionable noise
when vibration is translated into sound, As a result, more
energy or vibration can be expected. Closer attention to
line set isolation must be observed,
Following are some points to consider when placing and
installing a high-efficiency outdoor unit:
1-Placement
- Be aware some localities are adopting
sound ordinances based on how noisy the unit is from
the adjacent property not at the original installation.
Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside a
window. Glass has a very high level of sound transmission.
2- Line Set Isolation - The following illustrations demonstrate procedures which ensure proper refrigerant line
set isolation. Figure 5 shows how to install line sets on
vertical runs. Figure 6 shows how to install line sets on
horizontal runs. Figure 7 shows how to make a transition
from horizontal to vertical. Finally, figure 8 shows how to
place the outdoor unit and line set.

L15-65
15 ft, - 50 ft.
(4.6 m - 15 m)

NOTE - Units are designed for line sets of up to fifty feet (15
m). For applications longer than fifty feet, consult the Lennox Refrigerant Piping Guide (Corp. 9351-L9). Select line
set diameters from table 1 to ensure that oil returns to the
compressor.

Page 5

Refrigerant Line Sets
How To Install Vertical Runs
(new construction shown)
NOTE - Similar installation practices should be used if
line set is to be installed on exterior of outside wall.
Outside Wall
\
r

IMPORTANT- Refrigerant
lines must not contact wall.

Vapor Line

Liquid Line

Wood Block
_,
Between Studs

Wire Tie

E

J

\

Strap
Sleeve

Liquid Line
Vapor Line
(wrapped

Inside Wall

Wire Tie

m

m

Wall

Wood Block

m

Wire Tie
Strap
r -,tit

L_
PVC Pipe

Caulk
Fiberglass
Insulation

Sleeve

IMPORTANT- Refrigerant
lines must not contact
structure.

Figure 5

Page 6

Refrigerant Line Sets:
Installing Horizontal Runs

To hang line set from joist or rafter,
use either metal strapping material
or anchored heavy nylon wire ties.

Wire Tie
(around vapor line only)

8 feet

Floor Joist or
Roof Rafter
j

/
/

Tape or Wire Tie

/

8 feet

Strapping Material (around vapor line only)

Metal Sleeve
\

Tape or Wire Tie

_)

h
r

/

Floor Joist or Roof Rafter

jf

Strap the vapor line to the joist or rafter at 8 ft.
intervals then strap the liquid line to the vapor line.

Figure 6

Page 7

)

Refrigerant Line Sets:
Transition From Vertical To Horizontal
Automotive
Muffler-Type
Hanger

Anchored Heavy
Nylon Wire Tie

)

I

Wall
Stud

Wall
Stud
i/

Strap Liquid Line
To Vapor Line

Strap Liquid Line
To Vapor Line
Liquid Line

Metal /
Sleeve

Va )or Line
Wrapped in
Armaflex

Metal
Sleeve

Liquid Line
Figure

Vapor Line
Wrapped in
Armaflex

7

Outside Unit Placement and Installation

Install unit away from windows.

Two 90 ° elbows
installed in line set
will reduce line set
vibration.

Figure

Page 8

8

AWARNING
,WARNING

Brazing Connection Procedure
1 - Cut ends of the refrigerant lines square (free from nicks
or dents). Debur the ends, The pipe must remain
round, do not pinch end of the line.

,IMPORTANT

2 - Before making line set connections, use dry nitrogen to
purge the refrigerant piping. This will help to prevent
oxidation and the introduction of moisture into the system.
3 - Use silver alloy brazing rods (5 or 6 percent minimum
silver alloy for copper-to-copper brazing or 45 percent
silver alloy for copper-to-brass or copper-to-steel brazing) which are rated for use with R410A refrigerant.
Wrap a wet cloth around the valve body and the copper
tube stub. Remove light maroon washers from service
valves and shield light maroon stickers in order to protect them during brazing. Braze the line set to the service valve.
4 - Wrap a wet cloth around the valve body and copper
tube stub to protect it from heat damage during brazing. Wrap another wet cloth underneath the valve body
to protect the base paint.

-&CAUTION

Quench the joints with a wet cloth to prevent possible
heat damage to the valve core and opening port.
NOTE - The tube end must stay bottomed in the fitting
during final assembly to ensure proper seating, sealing
and rigidity.
5 - Install the provided fixed orifice (or thermal expansion valve which is sold separately and approved
for use with R410A refrigerant) in the liquid line at the
indoor coil.

Required Equipment
You will need the following equipment in order to flush the
existing line set and indoor coil: two clean R22 recovery
bottles, an oilless recovery machine that has a pump down
feature, and two sets of gauges (one for use with R22 and
one for use with the R410A).

6 - Install the provided filter drier (approved for use with
R410A refrigerant) in the liquid line as close as possible to the expansion device. Do not leave the filter
drier uncapped for more than 10 to 15 minutes
prior to brazing, evacuation, and leak testing.
Polyol ester oils used in this system absorb moisture quickly. Failure to install the filter drier will
void the warranty.

Flushing
Procedure
1 - Remove existing R22 refrigerant using the appropriate procedure below.
If the existing outdoor unit is not equipped with
shut-off valves, or if the unit is not operational
AND you plan to use the existing R22 refrigerant
to flush the system - Disconnect all power to the existing outdoor unit. Connect to the existing unit, a

Page 9

clean recoverycylinderandthe recoverymachine
according
totheinstructions
provided
withtherecoverymachine.RemoveallR22refrigerant
fromtheexistingsystem,Refertogaugesaftershutdown
toconfirmthattheentiresystemiscompletely
voidofrefrigerant,Disconnect
theliquidandvaporlinesfromthe
existingoutdoorunit,
If the existing
outdoor unit is equipped
with
manual shut-off valves AND you plan to use NEW
R22 refrigerant to flush the system - Start the existing R22 system in the cooling mode and close the liquid line valve. Pump all of the existing R22 refrigerant
back into the outdoor unit. (It may be necessary to bypass the low pressure switches to ensure complete
refrigerant evacuation,) When the low side system
pressures reach 0 psig, close the vapor line valve.
Disconnect all power to the existing outdoor unit, Refer to gauges after shutdown to confirm that the
valves are not allowing refrigerant to flow back into
the low side of the system, Disconnect the liquid and
vapor lines from the existing outdoor unit,

2 - Remove the existing outdoor unit. Set the new R410A
unit and follow the brazing connection procedure
which begins on the previous page to make line set
connections. DO NOT install the provided fixed orifice yet.
Make low voltage and line voltage connections to the
new outdoor unit. DO NOT turn on power to the unit
or open the outdoor unit service valves at this
time.
3 - Remove the existing refrigerant flow control orifice or
thermal expansion valve before continuing with flushing procedures, The existing devices are not approved for use with R410A refrigerant and may prevent proper flushing, Use a field-provided fitting to reconnect the lines,

&IMPORTANT

Flushing Connections
Inverted R22 Cylinder
(Contains clean R22 to
be used for flushing)

Low
Pressure

High
Pressure

HSXA12
Service Valve

Indoor Coil

Existing Liquid Line

Liquid Line
Service Valve

Tank Return
Inlet
Discharge
RECOVERY

CYLINDER

RECOVERY

MACHINE

Figure 9

Page 10

Unit
GAUGE

MANIFOLD

Closed

NOTE- The inverted R22 cylinder must contain at least the
same amount of refrigerant as
was recovered from the existing
system.

4- Removethe pressuretap valve cores from the
HSXA12unit'sservicevalves,ConnectanR22cylinderwithcleanrefrigeranttothevaporservicevalve.
ConnecttheR22gaugesettotheliquidlinevalveand
connecta recoverymachinewithanemptyrecovery
tanktothegaugeset,
5 - Settherecovery
machineforliquidrecovery
andstart
therecoverymachine,Openthegaugesetvalvesto
allowtherecovery
machine
topulla vacuum
ontheexistingsystemlinesetandindoorcoil,
6 - InvertthecylinderofcleanR22andopenitsvalveto
allowliquidrefrigerant
toflowintothesystemthrough
thevaporlinevalve.Allowtherefrigerant
to passfrom
thecylinderandthroughthelinesetandtheindoorcoil
beforeitenterstherecoverymachine.
7 - Afterallofthe liquidrefrigeranthasbeenrecovered,
switchtherecovery
machine
tovaporrecovery
sothat
alloftheR22vaporis recovered.
Allowtherecovery
machinetopulla vacuumonthesystem.

may not be appropriately sized. Refer to the Engineering
Handbook for specific orifice information.
Table 2
Fixed Orifice Drill Sizes
Fixed Orifice Part #

Drill Size

HSXA12-018

Unit

29M88

.05

HSXA12-024

42J43

.063

HSXA12-030

42J43

.063

HSXA12-036

42J47

.071

HSXA12-042

42J51

.078

HSXA12-048

29M93

.081

HSXA12-060

42J57

.090

Install the fixed orifice as shown in figure 10. Do not twist
the cap tubes when loosening the seal nut from the orifice
housing. Use a wrench to back up the distributor,
Metering Device Installation

NOTE - A single system flush should remove all of the
mineral oil from the existing refrigerant lines and indoor coil. A second flushing may be done (using clean
refrigerant) if insufficient amounts of mineral oil were
removed during the first flush. Each time the system
is flushed, you must allow the recovery machine
to pull a vacuum on the system at the end of the
procedure.

distributor

I_

..._.j(fa

_valve

OR orifice

J

//

expansion
valve (opt.)

e
o-ring
strainer

liquid line
stub

gauge set valves, Pump the remaining refrigerant out
of the recovery machine and turn the machine off,

10 -Install the provided fixed orifice in the liquid line at the
indoor coil.

o-ring

O

8- Close the valve on the inverted R22 drum and the

9 - Use nitrogen to break the vacuum on the refrigerant
lines and indoor coil before removing the recovery machine, gauges and R22 refrigerant drum, Reinstall
pressure tap valve cores into HSXA12 service valves,

c torC;i.[inCst
a iie d )

Figure
Expansion

10

Valve Systems

Expansion valves equipped with Chatleff type fittings are
available from Lennox, Refer to the Engineering Handbook
for expansion valves for use with specific match-ups.
If you install an expansion valve with an indoor coil that
includes a fixed orifice, remove the orifice before the
expansion valve is installed.

• , IMPORTANT

HSXA12 units are applicable to either fixed orifice or an
expansion valve system. See the indoor coil installation
instructions and the Lennox Engineering Handbook for
approved TXV and fixed orifice match-ups and application
information, Table 1 lists the unit liquid and vapor line sizes
and corresponding line sets,
Fixed

Orifice

Systems

HSXA12 units are shipped with a fixed orifice refrigerant
metering device. Replace the existing indoor unit fixed orifice with the orifice supplied with the outdoor unit, Place the
supplied fixed orifice sticker on the indoor cabinet after
installation. See table 2 for the fixed orifice size for each
unit, In nonstandard applications, the provided fixed orifice

Manifold gauge sets used with systems charged with
R410A refrigerant must be capable of handling the higher
system operating pressures, The gauges should be rated
for use with pressures of 0 - 800 on the high side and a low
side of 30" vacuum to 250 psi with dampened speed to 500
psi. Gauge hoses must be rated for use at up to 800 psi of
pressure with a 4000 psi burst rating,

Page 11

Theliquidlineandvaporlineservicevalves(figures11and
12)andgaugeportsareusedforleaktesting,evacuating,
chargingandcheckingcharge,Seetable3 fortorquerequirements,
Eachvalveis equipped
witha serviceportwhichhasafactory-installed
Schradervalve.A serviceportcapprotects
theSchradervalvefromcontamination
andservesasthe
primaryleakseal.
Table3
Torque Requirements
Part

Recommended

Service Valve
(Valve Closed)

serviCeport

_,_m

cap

insert hex
wrench here

to outdoor coil
service
port cap

Schrader
to line

Torque

indoor coil

valve open

set when

valve

is

closed (front seated)
(valve front seated)

Service valve cap

8 ft,-lb.

11 NM

Sheet metal screws

16 in.- lb.

2 NM

Machine screws #10

28 in.- lb.

3 NM

90 in.-lb.

10 NM

8 ft.- lb.

11 NM

Compressor

bolts

Gauge port seal cap

To Access

Schrader

Service Valve
(Valve Open)

insert hex
wrench here
service
port

Port:

stem cap

©

\

to outdoor coil

1 - Remove service port cap with an adjustable wrench.
2 - Connect gauge to the service port.
3- When testing is completed, replace service port cap.
Tighten finger tight, then tighten an additional 1/6 turn.
To Open Service Valve:

service port

1 - Remove stem cap with an adjustable wrench.
2 - Use a service wrench with a hex-head extension to
back the stem out counterclockwise as far as it will go.

cap

to indoor coil
Schrader
valve

Figure

11

NOTE - Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.
3 - Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn,
To Close Service Valve:

Vapor

1 - Remove the stem cap with an adjustable wrench.
2 - Use a service wrench with a hex-head extension to
turn the stem clockwise to seat the valve, Tighten it
firmly.

er valves; the difference

NOTE - Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.
3 - Replace the stem cap, Tighten finger tight, then tighten
an additional 1/6 turn.

Line (Ball Type) Service Valve

Vapor line service valves function the same way as the othis in the construction,

These

valves are not rebuildable, If a valve has failed, you must
replace it. A ball valve is illustrated in figure 12,
The ball valve is equipped with a service port with a factoryinstalled Schrader valve, A service port cap protects the
Schrader valve from contamination
free seal.

Page 12

and assures a leak-

2 - With both manifold valves closed, connect the cylinder
of R410A refrigerant. Open the valve on the R410A cyl-

Ball Valve (Valve Open)
Use Adjustable Wrench
To open: rotate Stem Counter-clockwise
90 °.
To close: rotate Stem Clockwise 90 °.

inder (vapor only).
3 - Open the high pressure side of the manifold to allow

to outdoor coil

stem cap

_.,i-----"q__J/

R410A into the line set and indoor unit. Weigh in a trace
amount of R410A. [A trace amount is a maximum of 2

stem

ounces (57 g) refrigerant or 3 pounds (31 kPa) pressure]. Close the valve on the R410A cylinder and the
valve on the high pressure side of the manifold gauge

ball
(shown open)

set. Disconnect R410A cylinder.
to indoor coil

4 - Connect a cylinder of nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
5 - Connect the manifold gauge set high pressure hose to
the vapor valve service port. (Normally, the high pressure hose is connected to the liquid line port; however,
connecting it to the vapor port better protects the manifold gauge set from high pressure damage.)

service port
cap
service port
Schrader valve

Figure

6 - Adjust nitrogen pressure to 150 psig (1034 kPa). Open
the valve on the high side of the manifold gauge set in or-

12

der to pressurize the line set and the indoor unit.
After the line set has been connected to the indoor and
outdoor units, check the line set connections and indoor
unit for leaks.

7 - After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge nitrogen and R410A
mixture. Correct any leaks and recheck.

WARNING

XklMPORTANT
,WARNING
Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper piping and compressor parts.

WARNING

XkIMPORTANT

1 - Connect manifold gauge set to the service valve ports
as follows:
Using an Electronic

Leak Detector

1 - Connect a cylinder of R410A to the center port of the
manifold gauge set.

• low pressure gauge to vapor line service valve
• high pressure gauge to liquid line service valve
2 - Connect micron gauge.

Page 13

3 - Connectthevacuumpump(withvacuumgauge)tothe
centerportofthemanifoldgaugeset.
4- Openbothmanifoldvalvesand startthe vacuum
pump.
5 - Evacuate
the linesetandindoorunittoan absolute
pressureof23,000microns(29.01inchesof mercury).Duringtheearlystagesof evacuation,
it is desirabletoclosethemanifold
gaugevalveatleastonceto
determine
ifthereisa rapidriseinabsolutepressure.
A rapidriseinpressure
indicates
a relatively
largeleak.
If thisoccurs,repeattheleaktestingprocedure.
NOTE - The term absolute pressure means the total
actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure,
6 - When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa)
and purge the hose. Open the manifold gauge valves
to break the vacuum in the line set and indoor unit,
Close the manifold gauge valves,

IMPORTANT

1 - Rotate fan to check for frozen bearings or binding.
2 - Inspect all factory- and field-installed wiring for loose
connections.
3 - After evacuation is complete, open the liquid line and
vapor line service valves to release the refrigerant
charge (contained in outdoor unit) into the system,
4 - Replace the stem caps and secure finger tight, then
tighten an additional one-sixth (1/6) of a turn,
5 - Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit's
nameplate. If not, do not start the equipment until you
have consulted the power company and the voltage
condition has been corrected.
6 - Set the thermostat for a cooling demand. Turn on power to the indoor blower and close the outdoor unit disconnect switch to start the unit.
_

A, WARNING

Recheck voltage while the unit is running, Power must
be within range shown on the nameplate,

This system is charged with R410A refrigerant which operates at much higher pressures than R22, The provided liquid line filter drier is approved for use with R410A, Do not
replace it with components designed for use with R22, This
unit is NOT approved for use with coils which use capillary
tubes as a refrigerant metering device,
7 - Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.
8 - Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20-minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
9- When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of R410A
refrigerant. Open the manifold gauge valves to break
the vacuum from 1 to 2 psig positive pressure in the line
set and indoor unit. Close manifold gauge valves and
shut off the R410A cylinder and remove the manifold
gauge set.

Factory

Charge

Units are factory charged with the amount of R410A refrigerant indicated on the unit rating plate, This charge is
based on a matching indoor coil and outdoor coil with 15 ft.
(4.6 m) line set. For varying lengths of line set, refer to table
4 for refrigerant charge adjustment.
Table 4
Liquid Line Set
Diameter

Oz. per 5 ft. (grams per 1.5 m) adjust
from 15 ft. (4.6 m) line set*

3/8 in,
(10 ram)

3 ounces per 5 feet
(85g per 1.5 m)

*If line length
length

Page 14

is greater

is less than

than 15 ft. (4.6 m), add this amounL

15 ft. (4.6 m), subtract

this amounL

klMPORTANT

If line

The compressor is charged with sufficient polyol ester
oil for line set lengths up to 50 feet (15.2 m). If oil must
be added to the compressor in the field, Copeland has
approved Mobil EAL'" Arctic 22CC and ICI EMKARATE "_ RL32CF.
Units Delivered
Void of Charge
If the system is void of refrigerant, clean the system using the procedure described below.

4 - When the heating demand has been satisfied, switch
the thermostat to cooling mode with a set point of 68 ° F
(20°C). When pressures have stabilized, use a digital
thermometer to record the liquid line temperature,
5 - The outdoor temperature will determine which charging method to use, Proceed with the appropriate charging procedure,

1 - Use nitrogen to pressurize the system and check for
leaks. Repair leaks, if possible,
2 - Evacuate the system to remove as much of the moisture as possible,
3 - Use nitrogen to break the vacuum and install the provided filter drier in the system,
4 - Evacuate the system again. Then, weigh the appropriate amount of R410A refrigerant (listed on unit nameplate) into the system,
5 - Monitor the system to determine the amount of moisture remaining in the oil. Use test kit 10N46 to verify
that the moisture content is within the kit's dry color
range. It may be necessary to replace the filter drier
several times to achieve the required dryness level, If
system dryness is not verified, the compressor will
fail in the future.
Checking

Weighing

in the Charge

TXV Systems

- Outdoor

Fixed Orifice

or

Temp. < 65°F (18°C)

If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, the refrigerant charge should be
weighed into the unit, Do this after any leaks have been repaired.
1 - Recover the refrigerant from the unit,
2 - Conduct a leak check, then evacuate as previously
outlined,
3 - Weigh in the unit nameplate charge,
If weighing facilities are not available or if you are charging
the unit during warm weather, follow one of the other procedures outlined below.
Charging

Using the Subcooling
Fixed Orifice

Outdoor

Charge

Method

Systems

Temp. _>65°F (18°C))

The outdoor unit should be charged during warm weather,

If you charge a fixed orifice system when the outdoor ambi-

However, applications arise in which charging must occur
in the colder months, The method of charging is determined by the unit's refrigerant metering device and the

ent is 65<_F(18<_C)or above, use the subcooling method to
charge the unit.

outdoor

ambient

temperature.

Measure the liquid line temperature and the outdoor ambient temperature as outlined below:
1 - Connect the manifold gauge set to the service valves:
• low pressure gauge to vapor valve service port
• high pressure gauge to liquid valve service port
Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of R410A,

1 - With the manifold gauge hose still on the liquid service
port and the unit operating stably, use a digital thermometer to record the liquid line temperature.
2 - At the same time, record the liquid line pressure reading.
3 - Use a temperature/pressure chart for R410A to determine the saturation temperature for the liquid line pressure reading, See table 5,
4 - Subtract the liquid line temperature from the saturation
temperature (according to the chart) to determine subcooling. (Saturation temperature - Liquid line tem-

2 - Set the room thermostat to call for heat. This will create
the necessary load for properly charging the system in
the cooling cycle.
3 - Use a digital thermometer to record the outdoor ambient temperature,

perature = Subcooling)
5 - Compare the subcooling value with those in table 6, If
subcooling is greater than shown, recover some refrigerant. If subcooling is less than shown, add some refrigerant,

Page 15

Table 5
R410A Temperature/Pressure
Temperature
oF

Pressure
Psig

Temperature
oF

Pressure
Psig

Chart

Temperature
oF

Pressure
Psig

Temperature
oF

Pressure
Psig

32

1O018

63

178.5

94

290.8

125

445.9

33

102.9

64

181.6

95

295.1

126

451.8

34

105.0

65

184.3

96

299.4

127

457.6

35

107.1

66

187.7

97

303.8

128

463.5

36

109.2

67

190.9

98

308.2

129

469.5

37

111.4

68

194.1

99

312.7

130

475.6

38

113.6

69

197.3

IO0

317.2

131

481.6

39

115.8

7O

200.6

101

321.8

132

487.8

4O

118.0

71

203.9

102

326.4

133

494.0

41

120.3

72

207.2

103

331.0

134

500.2

42

122.6

73

210.6

104

335.7

135

506.5

43

125.0

74

214.0

105

340.5

136

512.9

44

127.3

75

217.4

106

345.3

137

519.3

45

129.7

76

220.9

107

350.1

138

525.8

46

132.2

77

224.4

108

355.0

139

532.4

47

134.6

78

228.0

109

360.0

140

539.0

48

137.1

79

231.6

110

365.0

141

545.6

49

139.6

8O

235.3

111

370.0

142

552.3

5O

142.2

81

239.0

112

375.1

143

559.1

51

144.8

82

242.7

113

380.2

144

565.9

52

147.4

83

246.5

114

385.4

145

572.8

53

150.1

84

250.3

115

390.7

146

579.8

54

152.8

85

254.1

116

396.0

147

586.8

55

155.5

86

258.0

117

401.3

148

593.8

56

158.2

87

262.0

118

406.7

149

601.0

57

161.0

88

266.0

119

412.2

150

608.1

58

163.9

89

270.0

120

417.7

151

615.4

59

166.7

9O

274.1

121

423.2

152

622.7

6O

169.6

91

278.2

122

428.8

153

630.1

61

172.6

92

282.3

123

434.5

154

637.5

62

195.5

93

286.5

124

440.2

155

645.0

Table 6
Subcooling
Outdoor
Temp. °F (°C)
65
70
75
80
85
90

(18)
(21)
(24)
(27)
(29)
(32)

Values for Fixed Orifice Systems
Liquid

-018
13 (7.2)
12 (6.7)
11 (6.1)
9 (5)

-024
13 (7.2)
11 (6.1)
10 (5.6)

8 (4.5)

7 (3.9)
6 (3.3)

6 (3.3)

95 (35)
100 (38)

5 (2.8)
5 (2.8)

105 (41)
110 (43)
115 (45t

4 (2.2)
3 (1.7)
2 (1.1t

9(5)

5 (2.8)
4
4
3
3

(2.2)
(2.2)
(1.7)
(1.7t

Subcoolin

-030
16 (8.9)

9 [+ l°F (.6°C)]

-042
11 (6.4)
10 (5.6)
9 (5)
8 (4.5)
7 (3.9)
6 (3.3)
6 (3.3)

-048
14 (7.8)
13 (7.2)
12 (6.7)
11 (6.1)
10 (5.6)
9 (5)

-060
13 (7.2)
12 (6.7)

(7.8)
(7.2)
(6.7)
(5.6)
(5)

-036
12 (6.7)
11 (6.1)
10 (5.6)
9 (5)
8 (4.5)
7 (3.9)
6 (3.3)

8 (4.5)

8 (4.5)

8 (4.5)

5 (2.8)

5 (2.8)

7 (3.9)
6 (3.3)
5 (2.8t

4 (2.2)
4 (2.2)
3 (1.7t

4 (2.2)
3 (1.7)
3 (1.7t

7
7
6
6

7
6
6
5

15 (8.3)
14
13
12
10
9

Page 16

(3.9)
(3.9)
(3.3)
(3.3t

11 (6.1)
10 (5.6)
10 (5.6)
9 (5)
(3.9)
(3.3)
(3.3)
(2.8t

Approach
Normal
TXV Systems

Method

Operating

- Outdoor

frigerant from the system to increase the approach
temperature.
Be aware of the R410A refrigerant cylinder. It will be
rose-colored. Refrigerant should be added through the
vapor valve in the liquid state. Some R410A cylinders
are equipped with a dip tube which allows you to
draw liquid refrigerant from the bottom of the cylinder without turning the cylinder upside-down. The
cylinder will be marked if it is equipped with a dip
tube.

and

Pressures
Temp. >_65°F (18°C)

The following procedure is intended as a general guide and
is for use on expansion valve systems only. For best results,
indoor temperature should be 70°F (21°C) to 80°F (26°C).
Monitor system pressures while charging.
1 - Record outdoor ambient temperature
thermometer.

using a digital

Table 7

2 - Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.

HSXA12

3 - Compare stabilized pressures with those provided in
table 8, "Normal Operating Pressures." Minor variations in these pressures may be expected due to differences in installations. Significant differences could
mean that the system is not properly charged or that a
problem exists with some component in the system.
Pressures higher than those listed indicate that the
system is overcharged. Pressures lower than those
listed indicate that the system is undercharged. Verify
adjusted charge using the approach method.

Approach

Values

-018
-024
-030

Approach Temperature
Liquid Line Outdoor Ambient °F (°C)
10 (5.6)
12 (6,7)
13 (7.2)

-036
-042
-048
-060

12 (6.7)
11 (6.1)
13 (7,2)
14 (7,8)

Model No.

Approach Method

A IMPORTANT

4 - Use the same digital thermometer you used to check
the outdoor ambient temperature to check the liquid
line temperature.
5 - The difference between the ambient and liquid temperatures should match values given in table 7. If the values don't agree with the those in table 7, add refrigerant to lower the approach temperature, or recover re-

Normal
Mode

fixed
orifice

TXV

Operating

Out. Coil
Entering Air
Temp.

-018

Pressures

Table 8
In psig (liquid +/- 10 and vapor
-030

-024

-036

+/- 5 PSIG)*

-042

-048

-060

OF(oc)

LIQ

SUC

LIQ

SUC

LIQ

SUC

LIQ

SUC

LIQ

SUC

LIQ

SUC

LIQ

SUC

65 (18.3)

238

123

261

131

261

128

268

130

254

121

270

124

280

121

75 (23.9)

275

131

300

135

300

133

308

134

296

128

311

130

332

126

85 (29.4)

317

136

343

139

343

138

351

138

340

133

356

134

379

130

95 (35.o)

362

141

391

143

387

141

398

142

389

138

404

139

427

135

105 (40.6)

410

144

441

147

434

145

447

146

440

142

456

143

479

140

65

234

133

256

134

256

137

264

135

256

124

269

131

262

121

75 (23.9)

270

135

298

137

296

139

305

138

296

127

312

133

304

127

85 (29.4)

312

137

344

140

339

141

349

139

341

133

357

135

349

132

95 (35.0)

361

138

394

142

384

144

396

140

389

136

406

137

397

136

(18.3)

409
141
448
143
432
146
446
143
440
140
460
140
449
140
105 (40.6)
*These are typical pressures only. Indoor indoor match up, indoor air quality, and indoor load will cause the pressures

to vary.

Page 17

Theoutdoorunitandindoorblowercycleondemandfrom
theroomthermostat.
Whenthethermostat
blowerswitchis
intheONposition,
theindoorbloweroperates
continuously.
Compressor Time Belay (TB1)
A compressor
timedelayis usedto preventcompressor
shortcyclingandto preventthecompressor
fromrunning
backwards.
Whenthereisdemandfora coolingcycle,the
controldelayscompressor
operation
forabout5 minutes
(+
2 minutes).Donotbypassthecontrol.
High Pressure

3 - Visually inspect connecting lines and coils for evidence
of oil leaks.
4 - Check wiring for loose connections.
5 - Check for correct voltage at unit (unit operating).
6 - Check amp-draw outdoor fan motor.
Unit nameplate
Actual
NQ TE - If owner complains of insufficient cooling, the
unit should be gauged and refrigerant
charge
checked. Refer to section on refrigerant charging in
this instruction.
Indoor

Coil

1 - Clean coil, if necessary.
2 - Check connecting lines and coils for evidence of oil
leaks.

Switch

HSXA12 units are also equipped with a low pressure switch
that is located in the vapor line of the compressor. The
switch (SPST, auto-reset, normally closed) removes power
from the compressor when vapor line pressure drops below factory setting at 40 + 5 psi.
Filter

2 - Outdoor fan motor is prelubricated and sealed. No further lubrication is needed.

Switch

HSXA12 units are equipped with a high pressure switch
that is located in the liquid line of the compressor. The
switch (SPST, manual reset, normally closed) removes
power from the compressor when discharge pressure rises
above factory setting at 640 + 10 psi.
Low Pressure

1 - Clean and inspect the outdoor coil. The coil may be
flushed with a water hose. Ensure the power is turned
off before you clean the coil.

Brier

A filter drier is shipped with each HSXA12 unit. The filter
drier must be field installed in the liquid line between the
liquid line service valve and the expansion valve. This filter drier must be installed to ensure a clean, moisturefree system. Failure to install the filter drier will void
the warranty. A replacement filter drier is available as
from Lennox.

AWARNING

Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each cooling
season, the system should be checked as follows:

3 - Check condensate line and clean, if necessary.
Indoor

Unit

1 - Clean or change filters.
2 - Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM
Refer to the unit information service manual for pressure
drop tables and procedure.
3 - Belt Drive Blowers - Check belt for wear and proper
tension.
4 - Check all wiring for loose connections
5 - Check for correct voltage at unit (blower operating).
6 - Check amp-draw on blower motor
Unit nameplate
Actual

Refer to the Engineering Handbook for optional accessories that may apply to this unit. The following may or may
not apply:
• Loss of Charge Kit
• High Pressure Switch Kit
• Compressor Monitor
• Compressor Crankcase Heater
• Hail Guards
• Mounting Bases
• Timed Off Control
• Stand-off Kit
• Sound Cover
• LowAmbient Kit

Page 18

Start-up
Job Name
Job Location
Installer
Unit Model No,

and Performance
Job No,

Check

List
Date

City
City
Serial No,

State
State
Service Technician

Nameplate Voltage
Rated Load Ampacity
Maximum Fuse or Circuit Breaker

Compressor

Electrical Connections Tight? []
Indoor Blower RPM

Indoor Filter Clean? []
S,R Drop Over Indoor (Dry)

Discharge Pressure
Refrigerant Lines:

Outdoor Fan
Supply Voltage (Unit Off) __
--

Vapor Pressure
Leak Checked? []

Service Valves Fully Opened? []
Voltage With Compressor Operating

Properly Insulated?

[]

Outdoor Coil Entering Air Temp,
Refrigerant Charge Checked?
Outdoor Fan Checked?

Service Valve Caps Tight? []
--

Calibrated? []

Page 19

[]
[]

Thermostat
Properly Set? []

Level? []



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 19
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Mon Jun 30 04:27:18 2008
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu